Hazards of conveyor belt fires
This report describes a US Bureau of Mines study on the hazards of large-scale conveyor belt fires in underground coal mines, as a function of both air velocity and distance from belt surface to gallery roof. The fire hazards considered were smoke obscuration, toxic effects of carbon monoxide (CO), and elevated air temperatures downstream of the fire. All of these hazards scale with the ratio of fire intensity to ventilation airflow. These hazards were all found to be greater at the lower belt-to-roof distance, owing to the greater fire intensities that resulted. The hazards of smoke obscuration and elevated CO levels were greater at lower air velocities. Smoke obscuration was found to be the earliest hazard, reaching critical levels before the stages of flame spread. Fire growth rates during rapid flame spread were much greater than rates measured during the early stages of flame spread. Fire growth rates during rapid flame spread were much greater than rates measured during the early stages of belt burning. Data were analyzed to determine the early-warning capability of fire sensors. Smoke sensors provided the earliest warning, followed closely by CO sensors. Thermal sensors did not exhibit any early warning capability.
- OSTI ID:
- 175939
- Resource Relation:
- Other Information: PBD: 1995
- Country of Publication:
- United States
- Language:
- English
Similar Records
Impact of air velocity on the development and detection of small coal fires
Impact of air velocity on the development and detection of small coal fires. Report of investigations/1993