Thermal performance of advanced heat exchangers for ammonia refrigeration systems
Journal Article
·
· Heat Transfer Engineering
- Argonne National Lab., IL (United States)
Current practice in the ammonia industry is to use plain tubes. This article demonstrates that the coefficient of performance (COP) can be increased by about 11% using tubes with ammonia-side enhancement and by about 26% using tubes with ammonia-side and water-side enhancement. Further improvements with respect to energy and cost are possible with the compact heat exchanger types -- plate-frame and plate-fin -- because they can be optimized for the system conditions for each application. These findings are based on experimentally determined overall heat transfer coefficients that were obtained for candidate heat exchangers for the Ocean Thermal Energy Conversion (OTEC) program.
- Research Organization:
- Argonne National Lab. (ANL), Argonne, IL (United States)
- DOE Contract Number:
- W-31109-ENG-38
- OSTI ID:
- 143737
- Journal Information:
- Heat Transfer Engineering, Vol. 14, Issue 4; Other Information: PBD: Oct-Dec 1993
- Country of Publication:
- United States
- Language:
- English
Similar Records
OTEC performance tests of the Alfa-Laval plate heat exchanger as an ammonia evaporator
Biofouling monitors for noncylindrical OTEC heat exchanger tubes
Compound air-side heat transfer enhancement in a cross-flow refrigerant-to-air heat exchanger
Technical Report
·
Sun Apr 01 00:00:00 EST 1984
·
OSTI ID:143737
Biofouling monitors for noncylindrical OTEC heat exchanger tubes
Journal Article
·
Sun Aug 01 00:00:00 EDT 1982
· J. Sol. Energy Eng.; (United States)
·
OSTI ID:143737
Compound air-side heat transfer enhancement in a cross-flow refrigerant-to-air heat exchanger
Conference
·
Sun Dec 31 00:00:00 EST 1995
·
OSTI ID:143737