Title: Degradation of Nylon 6,6 Fire-Suppression Casing from Plutonium Glove Boxes Under Alpha and Neutron Irradiation

Journal Article · · Nuclear Technology
DOI:https://doi.org/10.13182/NT14-47· OSTI ID:1235660
 [1];  [2];  [1];  [2];  [2]
  1. Univ. of Texas, Austin, TX (United States)
  2. Los Alamos National Lab. (LANL), Los Alamos, NM (United States)

Nylon 6,6 tensile specimens, conforming to the casing for self-contained fire extinguisher systems, have been irradiated using both an accelerator He++ ion beam and a 5-Ci PuBe neutron source to model the radiation damage these systems would likely incur over a lifetime of operation within glove boxes. Following irradiation, these samples were mechanically tested using standard practices as described in ASTM D638. The results of the He++ study indicate that the tensile strength of the nylon specimens undergoes some slight (<10%) degradation while other properties of the samples, such as elongation and tangent modulus, appear to fluctuate with increasing dose levels. The He++-irradiated specimens also have a noticeable level of discoloration corresponding to increasing levels of dose. The neutron-irradiated samples show a higher degree of mechanical degradation than the He++-irradiated samples.

Research Organization:
Los Alamos National Lab. (LANL), Los Alamos, NM (United States)
Sponsoring Organization:
USDOE
Grant/Contract Number:
AC52-06NA25396
OSTI ID:
1235660
Report Number(s):
LA-UR-12-26151
Journal Information:
Nuclear Technology, Vol. 191, Issue 1; ISSN 0029-5450
Publisher:
American Nuclear Society (ANS)Copyright Statement
Country of Publication:
United States
Language:
English

Similar Records

Testing of SRS and RFETS Nylon Bag Material
Technical Report · Tue Nov 03 00:00:00 EST 1998 · OSTI ID:1235660

STRENGTH OF IRRADIATED DRAWN AND UNDRAWN NYLON
Journal Article · Fri Jul 01 00:00:00 EDT 1960 · Brit. J. Appl. Phys. · OSTI ID:1235660

Optical absorption as a sensitive monitor of tensile strength loss in thermally aged nylon 6,6
Conference · Tue Jan 01 00:00:00 EST 1985 · OSTI ID:1235660