The Impact of Refrigerant Charge, Air Flow and Expansion Devices on the Measured Performance of an Air-Source Heat Pump Part I
Journal Article
·
· ASHRAE Transactions
OSTI ID:1039948
- ORNL
This paper describes extensive tests performed on a 3-ton R-22 split heat pump in heating mode. The tests contain 150 steady-state performance tests, 18 cyclic tests and 18 defrost tests. During the testing work, the refrigerant charge level was varied from 70 % to 130% relative to the nominal value; the outdoor temperature was altered by three levels at 17 F (-8.3 C), 35 F (1.7 C) and 47 F (8.3 C); indoor air flow rates ranged from 60% to 150% of the rated air flow rate; and the expansion device was switched from a fixed-orifice to a thermal expansion value. Detailed performance data from the extensive steady state cyclic and defrost testing performed were presented and compared.
- Research Organization:
- Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)
- Sponsoring Organization:
- USDOE Office of Energy Efficiency and Renewable Energy (EERE)
- DOE Contract Number:
- DE-AC05-00OR22725
- OSTI ID:
- 1039948
- Journal Information:
- ASHRAE Transactions, Vol. 117; ISSN 0001-2505
- Country of Publication:
- United States
- Language:
- English
Similar Records
Modeling Improvements for Air Source Heat Pumps using Different Expansion Devices at Varied Charge Levels Part II
Shortening the defrost cycle time with active enhancement within the suction-line accumulator of an air-source heat pump
Laboratory determination of frosting and defrosting losses for a high-efficiency air-source heat pump
Journal Article
·
Sat Jan 01 00:00:00 EST 2011
· ASHRAE Transactions
·
OSTI ID:1039948
Shortening the defrost cycle time with active enhancement within the suction-line accumulator of an air-source heat pump
Book
·
Tue Dec 31 00:00:00 EST 1996
·
OSTI ID:1039948
Laboratory determination of frosting and defrosting losses for a high-efficiency air-source heat pump
Conference
·
Thu Jan 01 00:00:00 EST 1981
·
OSTI ID:1039948