Powered by Deep Web Technologies
Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


1

Problem of Vain Energy Consumption in a VAV Air Conditioning System Shared By an Inner Zone and Exterior Zone  

E-Print Network (OSTI)

in winter and summer. Taking a practical project as example, this paper analyzes the energy consumption of a VAV air conditioning system that is shared by inner zone and exterior zone. The paper also points out the serious problem of useless energy...

Wenji, G.; Ling, C.; Dongdong, L.; Mei, S.; Li, Z.

2006-01-01T23:59:59.000Z

2

Air Conditioning  

Science Journals Connector (OSTI)

Air Conditioning ... CHEMISTS and engineers use air conditioning as a valuable tool in more than two hundred industries. ... Air conditioning is a tool with many facets. ...

MARGARET INGELS

1938-02-10T23:59:59.000Z

3

Application of the VRV Air-Conditioning System Heat Recovery Series in Interior Zone and Analysis of its Energy Saving  

E-Print Network (OSTI)

To reduce the energy consumption of air conditioning systems, we can use the VRV air conditioning system to supply cold loads in the winter for rooms in the construction inner zone where cold loads need to be supplied. The VRV air-conditioning...

Zhang, Q.; Li, D.; Zhang, J.

2006-01-01T23:59:59.000Z

4

Table HC9.6 Air Conditioning Characteristics by Climate Zone, 2005  

U.S. Energy Information Administration (EIA) Indexed Site

6 Air Conditioning Characteristics by Climate Zone, 2005 6 Air Conditioning Characteristics by Climate Zone, 2005 Million U.S. Housing Units Total......................................................................... 111.1 10.9 26.1 27.3 24.0 22.8 Do Not Have Cooling Equipment........................... 17.8 3.2 4.7 3.6 5.5 0.9 Have Cooling Equipment........................................ 93.3 7.7 21.4 23.7 18.5 21.9 Use Cooling Equipment......................................... 91.4 7.6 21.0 23.4 17.9 21.7 Have Equipment But Do Not Use it........................ 1.9 Q 0.4 0.4 0.6 0.3 Air-Conditioning Equipment 2, 3 Central System...................................................... 65.9 4.8 12.3 15.1 14.9 18.7 Without a Heat Pump......................................... 53.5 4.7 11.5 11.6 12.3 13.6 With a Heat Pump..............................................

5

DEST Software to Analyze System Zoning and Energy Consumption in Air Conditioning Systems  

E-Print Network (OSTI)

This paper reports on a study on how to appropriately divide system zoning by using DeST software to calculate the basis dynamic temperature and load of all rooms in an office building. Influent factors of weather conditions, building envelope...

Fan, Y.; Li, D.

2006-01-01T23:59:59.000Z

6

Primary zone air proportioner  

DOE Patents (OSTI)

An air proportioner is provided for a liquid hydrocarbon fueled gas turbine of the type which is convertible to oil gas fuel and to coal gas fuel. The turbine includes a shell for enclosing the turbine, an air duct for venting air in said shell to a gasifier, and a fuel injector for injecting gasified fuel into the turbine. The air proportioner comprises a second air duct for venting air from the air duct for mixing with fuel from the gasifier. The air can be directly injected into the gas combustion basket along with the fuel from the injector or premixed with fuel from the gasifier prior to injection by the fuel injector.

Cleary, Edward N. G. (San Diego, CA)

1982-10-12T23:59:59.000Z

7

Solar Heating and Air Conditioning  

Science Journals Connector (OSTI)

...given of the status of solar fired air conditioning...to an approach to cool storage in solar air conditioning systems...an assessment of cool storage for reducing peak electrical...rolling cylinder thermal energy storage device for compact...

1980-01-01T23:59:59.000Z

8

Requirements for Determining Refrigerant Charge Residential Air Conditioning Measures  

E-Print Network (OSTI)

Requirements for Determining Refrigerant Charge Residential Air Conditioning Measures Improved Refrigerant Charge Purpose Component packages require in some climate zones that split system air refrigerant charge. For the performance method, the proposed design is modeled with less efficiency

9

Air Conditioning | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Conditioning Conditioning Air Conditioning July 1, 2012 - 6:28pm Addthis Air conditioners cost U.S. homeowners more than $11 billion each year, and regular maintenance can keep your air conditioner running efficiently. | Photo courtesy of ©iStockphoto/JaniceRichard Air conditioners cost U.S. homeowners more than $11 billion each year, and regular maintenance can keep your air conditioner running efficiently. | Photo courtesy of ©iStockphoto/JaniceRichard How does it work? An air conditioner uses energy -- usually electricity -- to transfer heat from the interior of your home to the relatively warm outside environment. Two-thirds of all homes in the United States have air conditioners. Air conditioners use about 5% of all the electricity produced in the United States, at an annual cost of more than $11 billion to homeowners. As a

10

Fuel conditioning facility zone-to-zone transfer administrative controls.  

SciTech Connect

The administrative controls associated with transferring containers from one criticality hazard control zone to another in the Argonne National Laboratory (ANL) Fuel Conditioning Facility (FCF) are described. FCF, located at the ANL-West site near Idaho Falls, Idaho, is used to remotely process spent sodium bonded metallic fuel for disposition. The process involves nearly forty widely varying material forms and types, over fifty specific use container types, and over thirty distinct zones where work activities occur. During 1999, over five thousand transfers from one zone to another were conducted. Limits are placed on mass, material form and type, and container types for each zone. Ml material and containers are tracked using the Mass Tracking System (MTG). The MTG uses an Oracle database and numerous applications to manage the database. The database stores information specific to the process, including material composition and mass, container identification number and mass, transfer history, and the operators involved in each transfer. The process is controlled using written procedures which specify the zone, containers, and material involved in a task. Transferring a container from one zone to another is called a zone-to-zone transfer (ZZT). ZZTs consist of four distinct phases, select, request, identify, and completion.

Pope, C. L.

2000-06-21T23:59:59.000Z

11

Natural Air-Conditioning Systems  

Science Journals Connector (OSTI)

Recent research in summer air conditioning utilizing natural sources of coolness* are discussed. These systems are classified according to the sources of coolness, the modes of heat transfer and airflow, and t...

Mehdi N. Bahadori

1986-01-01T23:59:59.000Z

12

Measurement Methods to Determine Air Leakage Between Adjacent Zones  

NLE Websites -- All DOE Office Websites (Extended Search)

Measurement Methods to Determine Air Leakage Between Adjacent Zones Measurement Methods to Determine Air Leakage Between Adjacent Zones Title Measurement Methods to Determine Air Leakage Between Adjacent Zones Publication Type Report LBNL Report Number LBNL-5887E Year of Publication 2012 Authors Hult, Erin L., Darryl J. Dickerhoff, and Phillip N. Price Date Published 09/2012 Keywords infiltration, leakage, residential ventilation Abstract Air leakage between adjacent zones of a building can lead to indoor air quality and energy efficiency concerns, however there is no existing standard for measuring inter-zonal leakage.In this study, synthesized data and field measurements are analyzed in order to explore the uncertainty associated with different methods for collecting and analyzing fan pressurization measurements to calculate inter- zone leakage. The best of the measurement and analysis methods was a method that uses two blower doors simultaneously based on the methods of Herrlin and Modera (1988) to determine the inter-zone leakage to within 16% of the inter-zone leakage flow at 4Pa, over the range of expected conditions for a house and attached garage. Methods were also identified that use a single blower door to determine the inter-zone leakage to within 30% of its value. The test configuration selected can have a large impact on the uncertainty of the results and there are testing configurations and methods that should definitely be avoided. The most rigorous calculation method identified assumes a fixed value for the pressure exponent for the interface between the two zones (rather than determining the interface pressure exponent from the measured data) and then uses an optimization routine to fit a single set of air leakage coefficients and pressure exponents for each of three wall interfaces using both pressurization and depressurization data. Multiple pressure station tests have much less uncertainty than single pressure station approaches. Analyses of field data sets confirm a similar level of variation between test methods as was expected from the analysis of synthesized data sets and confirm the selection of specific test methods to reduce experimental uncertainty.

13

Central Air Conditioning | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Central Air Conditioning Central Air Conditioning Central Air Conditioning May 30, 2012 - 8:01pm Addthis Central air conditioners circulate cool air through a system of supply and return ducts. | Photo courtesy of ©iStockphoto/DonNichols. Central air conditioners circulate cool air through a system of supply and return ducts. | Photo courtesy of ©iStockphoto/DonNichols. What does this mean for me? Central air conditioning systems are thermostatically controlled and convenient to use. Central air conditioning systems must be installed properly to operate efficiently. Central air conditioning systems can share ductwork with your heating system. Central air conditioners circulate cool air through a system of supply and return ducts. Supply ducts and registers (i.e., openings in the walls,

14

High Energy Efficiency Air Conditioning  

SciTech Connect

This project determined the performance of a new high efficiency refrigerant, Ikon B, in a residential air conditioner designed to use R-22. The refrigerant R-22, used in residential and small commercial air conditioners, is being phased out of production in developed countries beginning this year because of concerns regarding its ozone depletion potential. Although a replacement refrigerant, R-410A, is available, it operates at much higher pressure than R-22 and requires new equipment. R-22 air conditioners will continue to be in use for many years to come. Air conditioning is a large part of expensive summer peak power use in many parts of the U.S. Previous testing and computer simulations of Ikon B indicated that it would have 20 - 25% higher coefficient of performance (COP, the amount of cooling obtained per energy used) than R-22 in an air-cooled air conditioner. In this project, a typical new R-22 residential air conditioner was obtained, installed in a large environmental chamber, instrumented, and run both with its original charge of R-22 and then with Ikon B. In the environmental chamber, controlled temperature and humidity could be maintained to obtain repeatable and comparable energy use results. Tests with Ikon B included runs with and without a power controller, and an extended run for several months with subsequent analyses to check compatibility of Ikon B with the air conditioner materials and lubricant. Baseline energy use of the air conditioner with its original R-22 charge was measured at 90 deg F and 100 deg F. After changeover to Ikon B and a larger expansion orifice, energy use was measured at 90 deg F and 100 deg F. Ikon B proved to have about 19% higher COP at 90 deg F and about 26% higher COP at 100 deg F versus R-22. Ikon B had about 20% lower cooling capacity at 90 deg F and about 17% lower cooling capacity at 100 deg F versus R-22 in this system. All results over multiple runs were within 1% relative standard deviation (RSD). All of these values agree well with previous results and computer simulations of Ikon B performance versus R-22. The lower cooling capacity of Ikon B is not a concern unless a particular air conditioner is near its maximum cooling capacity in application. Typically, oversized A/C systems are installed by contractors to cover contingencies. In the extended run with Ikon B, which lasted about 4.5 months at 100 deg F ambient temperature and 68% compressor on time, the air conditioner performed well with no significant loss of energy efficiency. Post-run analysis of the refrigerant, compressor lubricant oil, compressor, compressor outlet tubing, and the filter/dryer showed minor effects but nothing that was considered significant. The project was very successful. All objectives were achieved, and the performance of Ikon B indicates that it can easily be retrofitted into R-22 air conditioners to give 15 - 20% energy savings and a 1 - 3 year payback of retrofit costs depending on location and use. Ikon B has the potential to be a successful commercial product.

Edward McCullough; Patrick Dhooge; Jonathan Nimitz

2003-12-31T23:59:59.000Z

15

A New Approach to Industrial Air Conditioning  

E-Print Network (OSTI)

-dryer Systems Division, has marketed industrial drying machinery. These heat reactivated dryers can handle latent loads in industrial air conditioning systems. Through waste heat conservation, air conditioning costs can be reduced 25 to 50%, with applications...

Gravenstreter, T.

1982-01-01T23:59:59.000Z

16

Air-Conditioning Basics | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Air-Conditioning Basics Air-Conditioning Basics Air-Conditioning Basics August 16, 2013 - 1:59pm Addthis Air conditioning is one of the most common ways to cool homes and buildings. How Air Conditioners Work Air conditioners employ the same operating principles and basic components as refrigerators. Refrigerators use energy (usually electricity) to transfer heat from the cool interior of the refrigerator to the relatively warm surroundings; likewise, an air conditioner uses energy to transfer heat from the interior space to the relatively warm outside environment. An air conditioner uses a cold indoor coil called the evaporator. The condenser, a hot outdoor coil, releases the collected heat outside. The evaporator and condenser coils are serpentine tubing surrounded by aluminum fins. This tubing is usually made of copper.

17

Air Distribution and Microenvironment Evaluation of a Desktop Task Conditioning System  

E-Print Network (OSTI)

Task conditioning aims to provide each occupant with personalized clean air direct to the breathing zone. The microenvironment of a typical office workplace, consisting of two desktop task conditioning systems (a Horizontal Desk Grill (HDG...

Zheng, G.

2006-01-01T23:59:59.000Z

18

Lab Breakthrough: Desiccant Enhanced Evaporative Air Conditioning |  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Desiccant Enhanced Evaporative Air Conditioning Desiccant Enhanced Evaporative Air Conditioning Lab Breakthrough: Desiccant Enhanced Evaporative Air Conditioning May 29, 2012 - 5:22pm Addthis This breakthrough combines desiccant materials, which remove moisture from the air using heat, and advanced evaporative technologies to develop a cooling unit that uses 90 percent less electricity and up to 80 percent less total energy than traditional air conditioning. This solution, called the desiccant enhanced evaporative air conditioner (DEVAP), also controls humidity more effectively to improve the comfort of people in buildings. View the entire Lab Breakthrough playlist. What are the key facts? Recent materials advances and liquid desiccant advances to design the compact and cost-effective DEVAP system. DEVAP uses 90 percent less electricity and up to 80 percent less

19

Lab Breakthrough: Desiccant Enhanced Evaporative Air Conditioning |  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Lab Breakthrough: Desiccant Enhanced Evaporative Air Conditioning Lab Breakthrough: Desiccant Enhanced Evaporative Air Conditioning Lab Breakthrough: Desiccant Enhanced Evaporative Air Conditioning May 29, 2012 - 5:22pm Addthis This breakthrough combines desiccant materials, which remove moisture from the air using heat, and advanced evaporative technologies to develop a cooling unit that uses 90 percent less electricity and up to 80 percent less total energy than traditional air conditioning. This solution, called the desiccant enhanced evaporative air conditioner (DEVAP), also controls humidity more effectively to improve the comfort of people in buildings. View the entire Lab Breakthrough playlist. What are the key facts? Recent materials advances and liquid desiccant advances to design the compact and cost-effective DEVAP system.

20

Heating, Ventilation and Air Conditioning Efficiency  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Presented By: WALTER E. JOHNSTON, PE Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE Air Conditioning (HVAC) system is to provide and maintain a comfortable environment within a building for the occupants or for the process being conducted Many HVAC systems were not designed with energy efficiency as one of the design factors 3 Air Air is the major conductor of heat. Lack of heat = air conditioning OR 4 Btu - Amount of heat required to raise one pound of water 1 F = 0.252 KgCal 1 Pound of Water = About 1 Pint of Water ~ 1 Large Glass 1 Kitchen Match Basics of Air Conditioning = 1 Btu 5 = 6 Low Cost Cooling Unit 7 8 Typical Design Conditions 75 degrees F temperature 50% relative humidity 30 - 50 FPM air movement

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


21

Air Conditioning Heating and Refrigeration Institute Comment  

Energy.gov (U.S. Department of Energy (DOE))

These comments are submitted by the Air-Conditioning, Heating, and Refrigeration Institute (AHRI) in response to the U.S. Department of Energys (DOE) notice in the July 3, 2014 Federal Register...

22

Alternatives to Electric Air Conditioning Systems  

E-Print Network (OSTI)

The rapid escalation of electricity prices has created an opportunity to re-introduce gas-fired air conditioning systems to the commercial building market. In 1985 Gas Research Institute initiated a program to develop an advanced gas engine...

Lindsay, B. B.; Koplow, M. D.

1988-01-01T23:59:59.000Z

23

Changing patterns of air conditioning in Japan  

Science Journals Connector (OSTI)

Japanese air conditioning patterns have changed significantly over the past 30 years. The changes can be linked to increasing affluence and the consequent changes Japanese life patterns, but also to changes in...

Harold Wilhite; Hidetoshi Nakagami

1999-01-01T23:59:59.000Z

24

Impact of the Variable Refrigerant Volume Air Conditioning System on Building Energy Efficiency  

E-Print Network (OSTI)

The application of the variable refrigerant volume multi-zone air conditioning systems has met with mixed results since the publication of the Design Standard for Energy Efficiency of Public Buildings. This paper analyzes the characteristics...

Zhu, H.

2006-01-01T23:59:59.000Z

25

WIPP air-intake shaft disturbed-rock zone study  

SciTech Connect

The disturbed-rock zone surrounding the air-intake shaft at the Waste Isolation Pilot Plant (WIPP) site was investigated to determine the extent and the permeability of the disturbed-rock zone as a function of radial distance from the 6.1 m diameter shaft, at different elevations within the Salado. Gas- and brine-permeability tests were performed in the bedded halite of the Salado formation at two levels within the air-intake shaft. The gas- and brine-permeability test results demonstrated that the radial distance to an undisturbed formation permeability of 1 {times} 10{sup {minus}21} m{sup 2} was less than 3.0 m.

Dale, T. [INTERA Inc., Austin, TX (United States); Hurtado, L.D. [Sandia National Labs., Albuquerque, NM (United States). Repository Isolation Systems Dept.

1996-12-01T23:59:59.000Z

26

Exploring Maximum Humidity Control and Energy Conservation Opportunities with Single Duct Single Zone Air-Handling Units  

E-Print Network (OSTI)

Humidity control for single-duct single-zone (SDSZ) constant volume air handling units is known to be a challenge. The operation of these systems is governed by space temperature only. Under mild weather conditions, discharge air temperature can get...

Zhou, J.; Wei, G.; Turner, W. D.; Deng, S.; Claridge, D.

2006-01-01T23:59:59.000Z

27

Alternative Refrigerants for Building Air Conditioning  

E-Print Network (OSTI)

The majority of building air conditioning has traditionally been achieved with vapor compression technology using CFC-I I or HCFC-22 as refrigerant fluids. CFC-11 is being successfully replaced by HCFC-123 (retrofit or new equipment) or by HFC- 134a...

Bivens, D. B.

1996-01-01T23:59:59.000Z

28

Roswell International Air Center Airport (ROW) Pavement Condition and Analysis  

E-Print Network (OSTI)

Roswell International Air Center Airport (ROW) Pavement Condition and Analysis Submitted to: Jane M ................................................1. Conditions at Roswell International Air Center (ROW) 4 .................................Figure 1. Geographic Location of Roswell International Air Center (ROW) 4 ..............................Table 1

Cal, Mark P.

29

Seawater Air Conditioning for Downtown Engineering Project Manager  

E-Print Network (OSTI)

Seawater Air Conditioning for Downtown Honolulu Scott Higa Engineering Project Manager Honolulu Seawater Air Conditioning, LLC Abstract As a tropical island state, Hawaii has a year-round demand for air conditioning. Conventional air conditioning systems are energy intensive and represent close to 50 percent

Frandsen, Jannette B.

30

Section 38 - HVAC (Heating, Ventilation, Air Conditioning)  

Science Journals Connector (OSTI)

The term HVAC is an acronym for Heating, Ventilation (and) Air Conditioning, the industry term for any of various efforts to control conditions in a building or other enclosed area to improve comfort and efficiency. A closely related section is Refrigeration, which follows this one. Some contemporary HVAC techniques have ancient roots. Early forms of central heating and solar home heating were in use in Rome in the first century A.D. The earliest use of glass in windows (as opposed to a covering of wood, cloth, or hide, or simply an opening) is also attributed to the Romans at this same time. The first known use of solar-oriented building design in North America dates back to about the year 1050; i.e., the cliff dwellings built by the Anasazi (Ancient Pueblo) people of the Colorado Plateau area. Geothermal district heating was employed as early as the 1300s, in the Auvergne region of southern France. The foundation for modern central heating was established in the 1700s, first in England and then in France. The 1800s saw significant advances in the use of water heaters, especially the first automatic storage water heater (Edwin Ruud, 1889) and the first commercial solar water heater (Clarence Kemp, 1891). In comparison with heating, cooling technology was late in developing. The first successful method of producing ice occurred in 1851, and it was not until 1902 that Willis Haviland Carrier designed the first industrial air-conditioning system. His Carrier Air Conditioning Corporation would go on to develop air-conditioning systems for stores and theaters (1924) and for residential buildings (1928). Carrier remains the global leader in air conditioner production. The first air-conditioned automobile was produced by Packard in 1939. Recent entries in this section emphasize the use of alternative energy sources in heating and cooling, such as solar, photovoltaic, geothermal, and fuel cells. These advances include the ground-source heat pump, the Trombe wall, the heat pipe, and the PV/thermal hybrid system.

Cutler J. Cleveland; Christopher Morris

2014-01-01T23:59:59.000Z

31

Seminar 14 - Desiccant Enhanced Air Conditioning: Desiccant Enhanced Evaporative Air Conditioning (Presentation)  

SciTech Connect

This presentation explains how liquid desiccant based coupled with an indirect evaporative cooler can efficiently produce cool, dry air, and how a liquid desiccant membrane air conditioner can efficiently provide cooling and dehumidification without the carryover problems of previous generations of liquid desiccant systems. It provides an overview to a liquid desiccant DX air conditioner that can efficiently provide cooling and dehumidification to high latent loads without the need for reheat, explains how liquid desiccant cooling and dehumidification systems can outperform vapor compression based air conditioning systems in hot and humid climates, explains how liquid desiccant cooling and dehumidification systems work, and describes a refrigerant free liquid desiccant based cooling system.

Kozubal, E.

2013-02-01T23:59:59.000Z

32

Innovative Systems for Solar Air Conditioning of Buildings  

E-Print Network (OSTI)

Solar air conditioning is an attractive technology to achieve comfortable room conditions, especially in hot and sunny climates. In particular air conditioning systems based on sorption technologies offer several advantages as they can be designed...

Kessling, W.; Peltzer, M.

2004-01-01T23:59:59.000Z

33

E-Print Network 3.0 - air pollution zones Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

zones Search Powered by Explorit Topic List Advanced Search Sample search results for: air pollution zones Page: << < 1 2 3 4 5 > >> 1 Geology, Society and the Environmental health...

34

Alternative non-CFC mobile air conditioning  

SciTech Connect

Concern about the destruction of the global environment by chlorofluorocarbon (CFC) fluids has become an impetus in the search for alternative, non-CFC refrigerants and cooling methods for mobile air conditioning (MAC). While some alternative refrigerants have been identified, they are not considered a lasting solution because of their high global warming potential, which could result in their eventual phaseout. In view of this dilemma, environmentally acceptable alternative cooling methods have become important. This report, therefore, is aimed mainly at the study of alternative automotive cooling methodologies, although it briefly discusses the current status of alternative refrigerants. The alternative MACs can be divided into work-actuated and heat-actuated systems. Work-actuated systems include conventional MAC, reversed Brayton air cycle, rotary vane compressor air cycle, Stirling cycle, thermoelectric (TE) cooling, etc. Heat-actuated MACs include metal hydride cooling, adsorption cooling, ejector cooling, absorption cycle, etc. While we are better experienced with some work-actuated cycle systems, heat-actuated cycle systems have a high potential for energy savings with possible waste heat applications. In this study, each altemative cooling method is discussed for its advantages and its limits.

Mei, V.C.; Chen, F.C.; Kyle, D.M.

1992-09-01T23:59:59.000Z

35

Mitigation of thermoacoustic instability utilizing steady air injection near the flame anchoring zone  

SciTech Connect

The objective of this work is to investigate the effectiveness of steady air injection near the flame anchoring zone in suppressing thermoacoustic instabilities driven by flame-vortex interaction mechanism. We perform a systematic experimental study which involves using two different configurations of air injection in an atmospheric pressure backward-facing step combustor. The first configuration utilizes a row of micro-diameter holes allowing for air injection in the cross-stream direction just upstream of the step. The second configuration utilizes an array of micro-diameter holes located on the face of the step, allowing for air injection in the streamwise direction. The effects of each of these configurations are analyzed to determine which one is more effective in suppressing thermoacoustic instabilities at different operating conditions. The tests are conducted while varying the equivalence ratio and the inlet temperature. The secondary air temperature is always the same as the inlet temperature. We used pure propane or propane/hydrogen mixtures as fuels. Combustion dynamics are explored through simultaneous pressure and heat release-rate measurements, and high-speed video images. When the equivalence ratio of the reactant mixture is high, it causes the flame to flashback towards the inlet channel. When air is injected in the cross-stream direction, the flame anchors slightly upstream of the step, which suppresses the instability. When air is injected in the streamwise direction near the edge of step, thermoacoustic instability could be eliminated at an optimum secondary air flow rate, which depends on the operating conditions. When effective, the streamwise air injection prevents the shedding of an unsteady vortex, thus eliminating the flame-vortex interaction mechanism and resulting in a compact, stable flame to form near the step. (author)

Murat Altay, H.; Hudgins, Duane E.; Speth, Raymond L.; Annaswamy, Anuradha M.; Ghoniem, Ahmed F. [Massachusetts Institute of Technology, Department of Mechanical Engineering, Cambridge, MA 02139 (United States)

2010-04-15T23:59:59.000Z

36

Energy Conservation of Air Conditioning Systems in Large Public Buildings  

E-Print Network (OSTI)

with the heating characteristics of the exterior -protected construction, the set value of the temperature of the air-conditioning, the lectotype of the Central air-conditioning system, the regulation and the modification of the transmission and distribution system...

Liu, P.; Li, D.

2006-01-01T23:59:59.000Z

37

Influence of air conditioning management on heat island in Paris air street temperatures  

E-Print Network (OSTI)

Influence of air conditioning management on heat island in Paris air street temperatures Brice 2012 Available online 13 March 2012 Keywords: Air conditioning Heat island mitigation Urban heat island killer'', is exacerbated in urban areas owing to the heat island effect. Air conditioning (A/C) is a key

Ribes, Aurélien

38

STATE OF CALIFORNIA ICE STORAGE AIR CONDITIONING (ISAC) UNITS  

E-Print Network (OSTI)

cooling with the compressor). Yes No #12;STATE OF CALIFORNIA ICE STORAGE AIR CONDITIONING (ISAC) UNITS CECSTATE OF CALIFORNIA ICE STORAGE AIR CONDITIONING (ISAC) UNITS CEC-CF-6R-MECH-08 (Revised 08/09) CALIFORNIA ENERGY COMMISSION INSTALLATION CERTIFICATE CF-6R-MECH-08 Ice Storage Air Conditioning (ISAC) Units

39

Analysis of energy saving potential of air-side free cooling for data centers in worldwide climate zones  

Science Journals Connector (OSTI)

Abstract Based on the climate classification of ASHRAE 90.1 and the required operating environment conditions for data centers suggested by the ASHRAE Technical Committee TC 9.9, a dynamic building energy simulation program was used to examine the potential energy savings of the air-side free cooling technology with differential enthalpy control used in data centers in 17 climate zones. The results showed that significant free cooling potential was achieved in data centers located in mixed-humid, warm-marine, and mixed-marine climate zones. Because significant humidification is required to adjust outdoor air in climate zones with a lower dew point temperature, such as very-cold, subarctic, cool-dry, and cold-dry climate zones, the power consumed is even higher. Although the cooling degree day (CDD) and heating degree day (HDD) are key factors of climate classification and air conditioning energy consumption, they are not entirely correlated to the specific operating environment conditions of data centers. The results of this study showed that for every 2C decline in the indoor temperature of a data center, the energy saving of free cooling technology may decrease by 2.88.5%. The rate of decline varies in different climate zones.

Kuei-Peng Lee; Hsiang-Lun Chen

2013-01-01T23:59:59.000Z

40

CFD Simulation and Analysis of the Combined Evaporative Cooling and Radiant Ceiling Air-conditioning System  

E-Print Network (OSTI)

, and the ceiling cooling system deals with the other part of sensible loads in the air-conditioned zone, so that the condensation on radiant panels and the insufficiency of cooling capacity can be avoided. The cooling water at 18? used in the cooling coils...

Xiang, H.; Yinming, L.; Junmei, W.

2006-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


41

Using Modelica for Physical Modeling of Air-Conditioning Systems  

NLE Websites -- All DOE Office Websites (Extended Search)

Using Modelica for Physical Modeling of Air-Conditioning Systems Using Modelica for Physical Modeling of Air-Conditioning Systems Speaker(s): Jonas Eborn Date: August 23, 2007 - 12:00pm Location: 90-4133 Seminar Host/Point of Contact: Michael Wetter The Air Conditioning library is a commercial Modelica library for the steady-state and transient simulation of air conditioning systems using both compact micro-channel heat exchangers as well as fin-and-tube type heat exchangers. Currently it is mostly used by automotive OEMs and suppliers that need high-accuracy system level models to evaluate energy efficiency of systems developed under the pressure of reduced design cycle times. The library also has applications in other areas, including aircraft cooling systems and residential air-conditioning. The Air Conditioning library contains published correlations for heat and mass transfer and

42

New Method Gives Precise Control in Air Conditioning  

Science Journals Connector (OSTI)

The Niagara "Controlled Humidity Method" is a new system of air conditioning giving complete control of temperature and relative humidity, holding constant conditions or varying them at the will of the user. ... A condition of 15 grains o f moisture per pound of air at 85 dcg. ...

1950-01-09T23:59:59.000Z

43

New Method Gives Precise Control in Air Conditioning  

Science Journals Connector (OSTI)

The Niagara "Controlled Humidity Method" is a new system of air conditioning giving complete control of temperature and relative humidity, holding constant conditions or varying them at the will of the user. ... A condition of 15 grains of moisture per pound of air at 85 deg. ...

1950-02-13T23:59:59.000Z

44

Zoning and occupancy-moderation for residential space-conditioning under demand-driven electricity pricing  

E-Print Network (OSTI)

Occupancy-moderated zonal space-conditioning (OZS) refers to the partitioning of a residence into different zones and independently operating the space-conditioning equipment of each zone based on its occupancy. OZS remains ...

Leow, Woei Ling, 1977-

2012-01-01T23:59:59.000Z

45

The investigation of exhaust powered, automotive air cycle air conditioning  

E-Print Network (OSTI)

Pressure Ratio Net Power Test Apparatus Available Turbocompressors Turbine and Compressor Wheels Mounted to Shaft Turbocompressor Mounted. to Exhaust Line Total System Test Rig Full Throttle Performance Curves Subscript 'c' Corrected Results 13 13... an automotive air cycle unit which employed a rotary- vaned compressor. The prototype unit developed. cooling over various engine speeds because of the compressor being a positive displacement type which developed fairly high pressures on the order of 40 psia...

Holley, James Andrew

1978-01-01T23:59:59.000Z

46

Direct Digital Control in Air Conditioning Systems for Energy Efficiency  

E-Print Network (OSTI)

the function and the level of the building, but also save energy. At present, air-conditioning design in internal commercial buildings is becoming more complex and enormous. The proportion of air conditioning systems in the whole building is getting larger...

Liu, W.; Ye, A.; Li, D.

2006-01-01T23:59:59.000Z

47

NREL: Vehicle Ancillary Loads Reduction - Air Conditioning and Emissions  

NLE Websites -- All DOE Office Websites (Extended Search)

Conditioning and Emissions Conditioning and Emissions Air conditioning and indirect emissions go together in the sense that when a vehicle's air conditioning system is in use, fuel economy declines. When more petroleum fuel is burned, more pollution and greenhouse gases are emitted. An additional, "direct" source of greenhouse gas emissions is the refrigerant used in air conditioning. Called HFC-134a, this pressurized gas tends to seep through tiny openings and escapes into the atmosphere. It can also escape during routine service procedures such as system recharging. NREL's Vehicle Ancillary Loads Reduction team applied its vehicle systems modeling expertise in a study to predict fuel consumption and indirect emissions resulting from the use of vehicle air conditioning. The analysis

48

Heating, Ventilation, and Air Conditioning Renovations | Department of  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Heating, Ventilation, and Air Conditioning Renovations Heating, Ventilation, and Air Conditioning Renovations Heating, Ventilation, and Air Conditioning Renovations October 16, 2013 - 4:49pm Addthis Renewable Energy Options for HVAC Renovations Geothermal Heat Pumps (GHP) Solar Water Heating (SWH) Biomass Passive Solar Heating Biomass Heating Solar Ventilation Air Preheating Federal building renovations that encompass the heating, ventilation, and air conditioning (HVAC) systems in a facility provide a range of renewable energy opportunities. The primary technology option for HVAC renovations is geothermal heat pumps (GHP). Other options include leveraging a solar water heating (SWH) system to offset heating load or using passive solar heating or a biomass-capable furnace or boiler. Some facilities may also take

49

Air-Conditioning Systems Simulate World-Wide Climates  

Science Journals Connector (OSTI)

Air-Conditioning Systems Simulate World-Wide Climates ... WEATHER conditions equivalent to those in any part of the world can be simulated in a four-compartment test box set up at State College, Penna., by the U. S. Department of Agriculture's Regional Pasture Research Laboratory in its work to develop better pastures. ... Three heavily insulated doors permit access to each compartment; an inner door keeps conditioned air in the box from rushing out when the main door is opened. ...

1941-10-25T23:59:59.000Z

50

Multi-zone modeling and simulation of syngas combustion under laminar conditions  

Science Journals Connector (OSTI)

The use of laminar models has been generally accepted, as quench distances in engines and the distances obtained for laminar flame quench calculations could be well correlated. In this work a multi-zone model is presented in order to derive the quenching distance and heat flux in laminar syngasair flames based on recent developments in the science of combustion. Three typical mixtures of H2, CO, CH4, CO2 and N2 have been considered as representative of the syngas coming from wood gasification, and its laminar combustion is made in a static spherical vessel. The model is validated for the methaneair case and then applied to syngasair mixtures in order to estimate the heat flux to the walls and quenching distances. Two wall heat transfer models are implemented and compared. The classical Woschni model based on the hypotheses of forced convection and the Rivre model based on kinetic theory of gases. Conclusion could be drawn that the Rivre heat transfer model is capable to better reproduce the heat flux to the walls. Heat flux through the walls is higher for stoichiometric syngasair mixtures which follows the same behavior of the pressure inside the combustion vessel. Quenching distance of syngasair mixtures decreases with the heat flux increase, which is consistent with earlier studies. This model could be very useful in predicting the physical conditions of quenching especially for estimation of the quenching distance where the measurement is not possible such as in engines. However, the estimation given should be understood as an order of magnitude, because in turbulent conditions the flamewall interaction results in lower Peclet numbers than in the laminar case.

Eliseu Monteiro; Abel Rouboa; Marc Bellenoue; Bastien Boust; Julien Sotton

2014-01-01T23:59:59.000Z

51

Importance of Design Conditions for Sizing Air-Conditioning Plant  

E-Print Network (OSTI)

Design conditions based on the meteorological data collected at two weather stations located less than 10 km away from each other within Kuwait City are presented for dry-bulb temperature (DBT) and web-bulb temperature (WBT) prioritization...

Shaban, N.; Maheshwari, G. P.; Suri, R. K.

2000-01-01T23:59:59.000Z

52

Reducing Air-Conditioning System Energy Using a PMV Index  

E-Print Network (OSTI)

ICEBO2006, Shenzhen, China Maximize Comfort: Temperature, Humidity and IAQ Vol.I-4-1 Reducing Air-Conditioning System Energy Using a PMV Index Hui Li Qingfan Zhang Associate professor...

Li, H.; Zhang, Q.

2006-01-01T23:59:59.000Z

53

INFLUENCE OF DESIGN AND OPERATING CONDITIONS ON UNDERFLOOR AIR DISTRIBUTION (UFAD) SYSTEM PERFORMANCE  

E-Print Network (OSTI)

Underfloor Air Distribution (UFAD) Design Guide. Atlanta:to design and operate underfloor air distribution (UFAD)DESIGN AND OPERATING CONDITIONS ON UNDERFLOOR AIR DISTRIBUTION (

2012-01-01T23:59:59.000Z

54

Approaches to Selecting Design Temperatures for Air-Conditioning  

NLE Websites -- All DOE Office Websites (Extended Search)

Approaches to Selecting Design Temperatures for Air-Conditioning Approaches to Selecting Design Temperatures for Air-Conditioning Speaker(s): Eric Peterson Date: July 7, 2005 - 12:00pm Location: 90-3122 Seminar Host/Point of Contact: Philip Haves Edward A. Arens The presentation will describe and compare the methods of determining cooling design conditions used by ASHRAE and the Australian Institute of Refrigeration, Air-Conditioning and Heating. A case study based on weather data for Brisbane will be used to illustrate the issues that arise. One issue is the usefulness of the 3-hourly temperature observations archived in International Weather Office records compared to the hourly observations required by the ASHRAE method. Another issue is the use of daily maxima, which have been archived for over 100 years at many Australian locations. Daily data can easily be used to find trends

55

Study of thermoelectric technology for automobile air conditioning  

SciTech Connect

An analytical study was conducted to determine the feasibility of employing thermoelectric (TE) cooling technology in automobile air conditioners. The study addressed two key issues -- power requirements and availability of thermoelectric materials. In this paper, a mathematical model was developed to predict the performance of TE air conditioners and to analyze power consumption. Results show that the power required to deliver a cooling capacity of 4 kW (13,80 Btu/h) in a 38{degree}C (100{degree}F) environment will be 9.5 kW electric. Current TE modules suitable for air conditioning are made of bismuth telluride. The element tellurium is expected to be in short supply if TE cooling is widely implemented for auto air conditioning; some options available in this regard were studied and presented in this paper.

Mathiprakasam, B.; Heenan, P. (Midwest Research Inst., Kansas City, MO (United States)); Mei, V.C.; Chen, F.C. (Oak Ridge National Lab., TN (United States))

1991-01-01T23:59:59.000Z

56

Fault tolerant control of outdoor air and AHU supply air temperature in VAV air conditioning systems using PCA method  

Science Journals Connector (OSTI)

This paper presents a fault tolerant control method to control the outdoor air ventilation and AHU supply air temperature, which concerned indoor air quality and humidity, respectively to satisfy ASHRAE Standard in VAV systems. The principal component analysis method, joint angle method, and compensatory reconstruction are used to detect, isolate, and reconstruct the fault, respectively for fault tolerant control. They are tested and evaluated in a simulation environment under the condition of temperature and flow sensors with fix bias faults.

Xinqiao Jin; Zhimin Du

2006-01-01T23:59:59.000Z

57

INFLUENCE OF DESIGN AND OPERATING CONDITIONS ON UNDERFLOOR AIR DISTRIBUTION (UFAD) SYSTEM PERFORMANCE  

E-Print Network (OSTI)

zones. Variable speed fan coil units (VSFCU) provide air tounit (AHU) including an airside economizer, a chilled water cooling coil, and a relief fan.

2012-01-01T23:59:59.000Z

58

E-Print Network 3.0 - air-conditioning system driven Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

(3-0-3) Summary: and design of air-conditioning, heating, and refrigeration systems; including consideration of vapor... ME 4321 Refrigeration and Air Conditioning...

59

Modeling and Control of Aggregated Air Conditioning Loads Under Realistic Conditions  

E-Print Network (OSTI)

strategy is designed to track a desired demand curve and to ensure a stable and smooth response. I for a large fraction of electric demand. HVAC (Heating, Ventilation and air conditioning) systems and water heaters are examples of TCLs. They use local hysteresis control to maintain either air or water

Zhang, Wei

60

Analysis of Air Conditioning Effectiveness vs. Outdoor Conditions: Traditional Bins or Joint Frequency Bins?  

E-Print Network (OSTI)

There are a number of methods used to estimate the effectiveness of air conditioning equipment in handling loads. Full hourly computer simulations are probably the most accurate, but lack flexibility and are more cumbersome to use than more compact...

Cohen, B. M.

1998-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


61

Control Humidity With Single-Duct, Single-Zone, Constant Air Volume System  

E-Print Network (OSTI)

for the AHLJ after Adjusted Conditions I I Return Fan: off; Return Damper: closed; Outside Air Damper: closed (signal) I 7- 14-99 9:44 AM AHU Dimensions Total Air Flow (CW Average Velocity (FPM) Temperature ("F) Humidity (% RH) Dew Point (OF... (FPM) Humidity (% RH) 1 83.0 -... r------ L -/ Dew Point (OF) Static Pressure supply 24" x 24" 4450 1180 Outside Air N/ A 2490 N/ A Mix Air 20" x 36" 4530 1091 T~mnrmt~w~ (OF) I 67.6 1 73.0 I 72.1 I 85.7 I . - 62.9 10.75 Return Air...

Chen, H.; Deng, S.; Bruner, H. L.; Claridge, D. E.

2000-01-01T23:59:59.000Z

62

Date | 1Refrigeration and Air Conditioning EMA Education and Training Date | 2Refrigeration and Air Conditioning EMA Education and Training  

E-Print Network (OSTI)

Date | 1Refrigeration and Air Conditioning EMA Education and Training #12;Date | 2Refrigeration operating pressure (MOP) 5. De-humidifying (Te control) 6. Defrost funtions 7. Loss of charge detection (LOC control) 6. Defrost funtions 7. Loss of charge detection (LOC) 8. Bleed function 9. Sensor placement tips

Oak Ridge National Laboratory

63

Integrating VAV zone requirements with supply fan operation. [Variable Air Volume  

SciTech Connect

The use of communicating direct digital controls (DDC) with distributed intelligence offers new opportunities for energy conservation while maintaining occupant comfort in commercial buildings. Integrating control within a single DDC panel improves performance. Integrating control by communications between multiple controllers can further enhance system operation. One example is a DDC static pressure reset strategy for supply fan operation in variable air volume (VAV) supply air distribution systems. This strategy integrates the requirements of the VAV terminal units serving the building zones to minimize fan energy use. This article describes terminal unit operation, supply fan control, concurrent polling, operational data and power savings.

Warren, M.L. (ASI Controls, San Ramon, CA (United States)); Norford, L.K. (Massachusetts Inst. of Tech., Cambridge (United States))

1993-04-01T23:59:59.000Z

64

Energy audit case studies IIair conditioning (cooling) systems  

Science Journals Connector (OSTI)

This paper discusses a novel methodology for determination of the efficiencies of each segment in a centralized air conditioning (A/C) plant. The methodology is useful analytical tool in energy audit where it can be used for decision support for evolution of energy conservation measures and techno-economic evaluation of the various options. The procedure is applied to three A/C plants of capacity range from 50 to 500 TR. Losses in chilled air ducts and cycling losses in the refrigerant circuit are identified to be the major causes for decrease in the efficiency and capacity under rating of the systems. Effective controls and insulation of air ducts: have been shown to be the most cost effective solutions to improve the energy efficiency of the A/C plants. The generalized experimental data on overall performance of sixteen A/C plants is also provided.

M Siddhartha Bhatt

2000-01-01T23:59:59.000Z

65

Magnetic Refrigeration Technology for High Efficiency Air Conditioning  

SciTech Connect

Magnetic refrigeration was investigated as an efficient, environmentally friendly, flexible alternative to conventional residential vapor compression central air conditioning systems. Finite element analysis (FEA) models of advanced geometry active magnetic regenerator (AMR) beds were developed to minimize bed size and thus magnet mass by optimizing geometry for fluid flow and heat transfer and other losses. Conventional and magnetocaloric material (MCM) regenerator fabrication and assembly techniques were developed and advanced geometry passive regenerators were built and tested. A subscale engineering prototype (SEP) magnetic air conditioner was designed, constructed and tested. A model of the AMR cycle, combined with knowledge from passive regenerator experiments and FEA results, was used to design the regenerator beds. A 1.5 Tesla permanent magnet assembly was designed using FEA and the bed structure and plenum design was extensively optimized using FEA. The SEP is a flexible magnetic refrigeration platform, with individually instrumented beds and high flow rate and high frequency capability, although the current advanced regenerator geometry beds do not meet performance expectations, probably due to manufacturing and assembly tolerances. A model of the AMR cycle was used to optimize the design of a 3 ton capacity magnetic air conditioner, and the system design was iterated to minimize external parasitic losses such as heat exchanger pressure drop and fan power. The manufacturing cost for the entire air conditioning system was estimated, and while the estimated SEER efficiency is high, the magnetic air conditioning system is not cost competitive as currently configured. The 3 ton study results indicate that there are other applications where magnetic refrigeration is anticipated to have cost advantages over conventional systems, especially applications where magnetic refrigeration, through the use of its aqueous heat transfer fluid, could eliminate intermediate heat exchangers or oil distribution issues found in traditional vapor compression systems.

Boeder, A; Zimm, C

2006-09-30T23:59:59.000Z

66

Solar air-conditioning-active, hybrid and passive  

SciTech Connect

After a discussion of summer air conditioning requirements in the United States, active, hybrid, and passive cooling systems are defined. Active processes and systems include absorption, Rankine cycle, and a small variety of miscellaneous systems. The hybrid solar cooling and dehumidification technology of desiccation is covered as well as evaporative cooling. The passive solar cooling processes covered include convective, radiative and evaporative cooling. Federal and state involvement in solar cooling is then discussed. (LEW)

Yellott, J. I.

1981-04-01T23:59:59.000Z

67

Fetz Plumbing, Heating & Air Conditioning | Open Energy Information  

Open Energy Info (EERE)

Fetz Plumbing, Heating & Air Conditioning Fetz Plumbing, Heating & Air Conditioning Jump to: navigation, search Name Fetz Plumbing, Heating & Air Conditioning Address 115 Washington Street - P.O. Box 516 Place Urbana, Ohio Zip 43078 Sector Efficiency, Geothermal energy, Services, Solar Product Installation; Maintenance and repair Phone number 937-652-1136 Website http://fetzphc.com Coordinates 40.108862°, -83.757291° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":40.108862,"lon":-83.757291,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

68

E-Print Network 3.0 - air-conditioning units part Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

fans... : Use of mechanical equipment such as refrigeration, air conditioning, heating systems, ventilating fans... -handling units and mechanical, compressed air, and electric ......

69

Control of Computer Room Air Conditioning using IT Equipment Sensors  

E-Print Network (OSTI)

control routine to adjust setpoints for supply air temperaturecontrol routine to adjust setpoints for supply air temperaturesupply air temperature is provided. The fan-speed control

Bell, Geoffrey C.

2010-01-01T23:59:59.000Z

70

Control of Computer Room Air Conditioning using IT Equipment Sensors  

E-Print Network (OSTI)

8 Figure 5 Server rack Inlet Air Temperature (8 Figure 6 Server-rack Leaving Air Temperature (Rack .

Bell, Geoffrey C.

2010-01-01T23:59:59.000Z

71

Liquid over-feeding air conditioning system and method  

DOE Patents (OSTI)

A refrigeration air conditioning system utilizing a liquid over-feeding operation is described. A liquid refrigerant accumulator-heat exchanger is placed in the system to provide a heat exchange relationship between hot liquid refrigerant discharged from condenser and a relatively cool mixture of liquid and vaporous refrigerant discharged from the evaporator. This heat exchange relationship substantially sub-cools the hot liquid refrigerant which undergoes little or no evaporation across the expansion device and provides a liquid over-feeding operation through the evaporator for effectively using 100 percent of evaporator for cooling purposes and for providing the aforementioned mixture of liquid and vaporous refrigerant. 1 figure.

Mei, V.C.; Chen, F.C.

1993-09-21T23:59:59.000Z

72

Weatherking Heating & Air conditioning | Open Energy Information  

Open Energy Info (EERE)

Page Page Edit with form History Facebook icon Twitter icon » Weatherking Heating & Air conditioning Jump to: navigation, search Name Weatherking Heating & Air conditioning Address 51 Meadow Lane Place Northfield, Ohio Zip 44067 Sector Buildings, Efficiency, Geothermal energy, Renewable Energy, Services Product Business and legal services; Energy audits/weatherization; Energy provider: power production;Energy provider: wholesale;Engineering/architectural/design;Installation;Investment/finances;Maintenance and repair; Retail product sales and distribution Phone number 330-908-0281 Website http://www.weatherking1.com Coordinates 41.3340869°, -81.530299° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":41.3340869,"lon":-81.530299,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

73

E-Print Network 3.0 - air conditioning maintenance Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

Last Updated: 41702 Summary: , including refrigeration, air conditioning, heating systems, ventilating fans, roof ventilators, exhaust fans... : Use of mechanical equipment...

74

Investigating the Performance of Solar Air Conditioning Motivation/Background Findings  

E-Print Network (OSTI)

Investigating the Performance of Solar Air Conditioning Motivation/Background Findings Two Building-thermal collectors We investigated 3 types of solar cooling technologies: · Air conditioning consumes 10% of all conditioning can reduce energy consumption, only if paired with a suitable system · Conventional office air

75

An overview of solar assisted air-conditioning system application in small office buildings in Malaysia  

Science Journals Connector (OSTI)

In many regions of the world especially tropical weather in Malaysia, the demand for cooling of indoor air is growing due to increasing comfort expectations and increasing cooling loads. Air-conditioning, the most common cooling mechanism for providing ... Keywords: Malaysian climatic conditions, absorption chiller, evacuated tube solar collector, high energy consumption, peak load demand, solar assisted air conditioning system, solar energy

Lim Chin Haw; Kamaruzzaman Sopian; Yusof Sulaiman

2009-02-01T23:59:59.000Z

76

Analysis of a Dedicated Outdoor Air System and Low Temperature Supply Air Conditioning System  

E-Print Network (OSTI)

This paper presents the principles and the characteristics of a dedicated outdoor air system (DOAS) and low temperature supply air system. DOAS is offered based on the demands of indoor air quality and the low temperature supply air system...

Guang, L.; Li, R.

2006-01-01T23:59:59.000Z

77

Investigation of residential central air conditioning load shapes in NEMS  

SciTech Connect

This memo explains what Berkeley Lab has learned about how the residential central air-conditioning (CAC) end use is represented in the National Energy Modeling System (NEMS). NEMS is an energy model maintained by the Energy Information Administration (EIA) that is routinely used in analysis of energy efficiency standards for residential appliances. As part of analyzing utility and environmental impacts related to the federal rulemaking for residential CAC, lower-than-expected peak utility results prompted Berkeley Lab to investigate the input load shapes that characterize the peaky CAC end use and the submodule that treats load demand response. Investigations enabled a through understanding of the methodology by which hourly load profiles are input to the model and how the model is structured to respond to peak demand. Notably, it was discovered that NEMS was using an October-peaking load shape to represent residential space cooling, which suppressed peak effects to levels lower than expected. An apparent scaling down of the annual load within the load-demand submodule was found, another significant suppressor of the peak impacts. EIA promptly responded to Berkeley Lab's discoveries by updating numerous load shapes for the AEO2002 version of NEMS; EIA is still studying the scaling issue. As a result of this work, it was concluded that Berkeley Lab's customary end-use decrement approach was the most defensible way for Berkeley Lab to perform the recent CAC utility impact analysis. This approach was applied in conjunction with the updated AEO2002 load shapes to perform last year's published rulemaking analysis. Berkeley Lab experimented with several alternative approaches, including modifying the CAC efficiency level, but determined that these did not sufficiently improve the robustness of the method or results to warrant their implementation. Work in this area will continue in preparation for upcoming rulemakings for the other peak coincident end uses, commercial air conditioning and distribution transformers.

Hamachi LaCommare, Kristina; Marnay, Chris; Gumerman, Etan; Chan, Peter; Rosenquist, Greg; Osborn, Julie

2002-05-01T23:59:59.000Z

78

Solubility testing of actinides on breathing-zone and area air samples  

SciTech Connect

A solubility testing method for several common actinides has been developed with sufficient sensitivity to allow profiles to be determined from routine breathing zone and area air samples in the workplace. Air samples are covered with a clean filter to form a filter-sample-filter sandwich which is immersed in an extracellular lung serum simulant solution. The sample is moved to a fresh beaker of the lung fluid simulant each day for one week, and then weekly until the end of the 28 day test period. The soak solutions are wet ashed with nitric acid and hydrogen peroxide to destroy the organic components of the lung simulant solution prior to extraction of the nuclides of interest directly into an extractive scintillator for subsequent counting on a Photon-Electron Rejecting Alpha Liquid Scintillation (PERALS{reg_sign}) spectrometer. Solvent extraction methods utilizing the extractive scintillators have been developed for the isotopes of uranium, plutonium, and curium. The procedures normally produce an isotopic recovery greater than 95% and have been used to develop solubility profiles from air samples with 40 pCi or less of U{sub 3}O{sub 8}. Profiles developed for U{sub 3}O{sub 8} samples show good agreement with in vitro and in vivo tests performed by other investigators on samples from the same uranium mills.

Metzger, R.L.; Jessop, B.H.; McDowell, B.L. [Radiation Safety Engineering, Inc., Chandler, AZ (United States)

1996-02-01T23:59:59.000Z

79

Uranium redistribution under oxidizing conditions in Oklo natural reactor zone 2, Gabon  

SciTech Connect

This mineralogical study was completed to elucidate the relationships between uranium distribution and alteration products of the host rock of natural reactor zone clays just below the reactor core. Uraninite is preserved without any alteration in the reactor core. Uranium minerals are found to be present in the fractures in the reactor zone clays associated with iron-mineral veins, galena and Ti-bearing minerals. Uranium, for which the phases could not be identified, occurs in iron-mineral veins and the iron-mineral rim of pyrite grains in the reactor zone clays. Uranium is not associated with granular iron minerals occurring in the illite matrix of the reactor zone clays. The degree of crystallinity and uranium content of the three iron-bearing alteration products suggest that they formed under different conditions; the granular iron minerals, under alteration conditions where uranium was not mobilized while the iron-mineral veins and the iron-mineral rim of pyrite, under conditions in which uranium is mobilized after the formation of the granular iron minerals.

Isobe, H.; Ohnuki, T. [Japan Atomic Energy Research Inst., Tokai, Ibaraki (Japan); Murakami, T. [Ehime Univ., Matsuyama, Ehime (Japan); Gauthier-Lafaye, F. [CNRS, Strasbourg (France). Centre de Geochemie de la Surface

1995-12-31T23:59:59.000Z

80

Module Development and Simulation of the Variable Refrigerant Flow Air Conditioning System under Cooling Conditions in Energyplus  

E-Print Network (OSTI)

As a high-efficiency air conditioning scheme, the variable refrigerant flow (VRF) air-conditioning system is finding its way into medium-sized office buildings. Based on a generic dynamic building energy simulation environment, EnergyPlus, a new...

Zhou, Y.; Wu, J.; Wang, R.; Shiochi, S.

2006-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


81

Commissioning and Diagnosis of VAV Air-Conditioning Systems  

E-Print Network (OSTI)

This paper presents a fault detection and diagnosis (FDD) strategy based on system knowledge, qualitative states and object-oriented statistical process control (SPC) models for typical pressure-independent variable air volume (VAV) air...

Qin, J.; Wang, S.; Chan, C.; Xiao, F.

2006-01-01T23:59:59.000Z

82

Operation of Energy-Efficient Air-Conditioned Buildings: An Overview  

E-Print Network (OSTI)

To design an optimum HVAC airside system that provides comfort and air quality in the air-conditioned spaces with efficient energy consumption is a great challenge. This paper evaluates recent progresses of HVAC airside design for the air-conditioned...

Khalil, E. E.

2010-01-01T23:59:59.000Z

83

Air-Side Energy Use Calculations for Four HVAC Systems: Dual Duct Constant Volume (DDCAV), Dual Duct Variable Volume (DDVAV), Constant Volume with Reheat (CAVRH), Variable Volume with Reheat (VAVRH), Four Pipe Fan Coil Unit (FC), Four Pipe Induction Unit (FI), and Single Zone (SZ) Systems, Revised June 2002  

E-Print Network (OSTI)

(CAVRH), and variable volume with reheat (VAVRH), four pipe fan coil unit (FC), four pipe induction unit (FI), and a single zone air conditioning system (SZ). These calculations are presented in spreadsheets that include a running commentary so...

Haberl, J. S.; Bou-Saada, T. E.; Saman, N. F.

2001-01-01T23:59:59.000Z

84

Flywheel Cooling: A Cooling Solution for Non Air-Conditioned Buildings  

E-Print Network (OSTI)

"Flywheel Cooling" utillzes the natural cooling processes of evaporation, ventilation and air circulation. These systems are providing low-cost cooling for distribution centers, warehouses, and other non air-conditioned industrial assembly plants...

Abernethy, D.

85

Analysis of efficiency of control of operation conditions of air gas cooling devices at compressor stations  

Science Journals Connector (OSTI)

Based on calculations of energy consumption by air gas cooling devices, an analysis has been made of the efficiency of the methods of control of temperature conditions of the transported gas. Two types of air ...

A. V. Krupnikov; A. D. Vanyashov; I. A. Yanvarev

2010-05-01T23:59:59.000Z

86

HEATING, AIR-CONDITIONING AND REFRIGERATION DISTRIBUTORS INTERNATIONAL (HARDI)  

Energy.gov (U.S. Department of Energy (DOE))

OE Framework Document and Stakeholder Meeting regarding the Enforcement of the updated Energy Conservation Standards for Air Conditioners, Furnaces and Heat Pumps.

87

E-Print Network 3.0 - air conditioning hvac Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

systems play an important role in providing comfort in residential, commercial... of Heating, Refrigerating, and Air-Conditioning Engineers. Batterman S. and Burge H. 1995. "HVAC...

88

E-Print Network 3.0 - air-conditioning systems based Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

INVENTION, APPLICATION NO. 61297,958 OF 25 JAN 2010 Summary: for Efficient Heating, Cooling, Refrigeration, and Air Conditioning BY MILIVOJE M. KOSTIC, SYCAMORE, IL......

89

New Development of Simulation Methods on Refrigeration and Air Conditioning Equipments  

Science Journals Connector (OSTI)

Development status of classical simulation technology and application status of artificial intelligence on refrigeration and air conditioning equipments were introduced. The new concept of intelligence simulat...

Cao Wensheng

2011-01-01T23:59:59.000Z

90

E-Print Network 3.0 - air-conditioned domestic buildings Sample...  

NLE Websites -- All DOE Office Websites (Extended Search)

water chillers will contain more than 3 kg. If information... , air conditioning and heat pump technology. However, certain fire protection equipment that contains F......

91

Impact of Vehicle Air-Conditioning on Fuel Economy, Tailpipe Emissions, and Electric Vehicle Range: Preprint  

SciTech Connect

Vehicle air-conditioning can significantly impact fuel economy and tailpipe emissions of conventional and hybrid electric vehicles and reduce electric vehicle range. In addition, a new US emissions procedure, called the Supplemental Federal Test Procedure, has provided the motivation for reducing the size of vehicle air-conditioning systems in the US. The SFTP will measure tailpipe emissions with the air-conditioning system operating. Current air-conditioning systems can reduce the fuel economy of high fuel-economy vehicles by about 50% and reduce the fuel economy of today's mid-sized vehicles by more than 20% while increasing NOx by nearly 80% and CO by 70%.

Farrington, R.; Rugh, J.

2000-09-22T23:59:59.000Z

92

INFLUENCE OF DESIGN AND OPERATING CONDITIONS ON UNDERFLOOR AIR DISTRIBUTION (UFAD) SYSTEM PERFORMANCE  

E-Print Network (OSTI)

supply temperature setpoints, operation of blinds at peak conditions, impact of occupant control, andcontrols the AHU fan. In both UFAD and OH systems, supply air temperature (

2012-01-01T23:59:59.000Z

93

Capability of air filters to retain airborne bacteria and molds in heating, ventilating and air-conditioning (HVAC) systems  

Science Journals Connector (OSTI)

The capability of air filters (filterclass: F6, F7) to retain airborne outdoor microorganisms was examined in field experiments in two heating, ventilating and air conditioning (HVAC) systems. At the beginning of the 15-month investigation period, the first filter stages of both HVAC systems were equipped with new unused air filters. The number of airborne bacteria and molds before and behind the filters were determined simultaneously in 14 days-intervals using 6-stage Andersen cascade impactors. Under relatively dry ( 12 C) outdoor air conditions air filters led to a marked reduction of airborne microorganism concentrations (bacteria by approximately 70 % and molds by > 80 %). However, during long periods of high relative humidity (> 80 % R. H.) a proliferation of bacteria on air filters with subsequent release into the filtered air occured. These microorganisms were mainly smaller than 1.1 ?m therefore being part of the respirable fraction. The results showed furthermore that one possibility to avoid microbial proliferation is to limit the relative humidity in the area of the air filters to 80 % R. H. (mean of 3 days), e. g. by using preheaters in front of air filters in HVAC-systems.

Martin Mritz; Hans Peters; Bettina Nipko; Hennin Rden

2001-01-01T23:59:59.000Z

94

Test and Reconstruction of Air Conditioning System in a Hotel Lobby  

E-Print Network (OSTI)

Two air conditioning systems are equipped in a hotel lobby. It is found from the field test that the actual air rate is 40% and 16% of the nominal value, respectively, of the two systems, which is far lower than the design requirement. The air rate...

Wang, G.; Hu, Y.; Hu, S.; Chen, Q.

2006-01-01T23:59:59.000Z

95

HEATING, AIR-CONDITIONING AND REFRIGERATION DISTRIBUTORS INTERNATIONAL...  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

of the updated Energy Conservation Standards for Air Conditioners, Furnaces and Heat Pumps. DOE EX Parte Memo.pdf More Documents & Publications 3rd Semi-Annual Report to...

96

Development of Optimization Tool for Air Conditioning System Operation  

E-Print Network (OSTI)

Operations, Berlin, Germany, October 20-22, 2008 Outside air temperature and the absolute air humidity are predicted by the Auto-regressive Integrated Moving Average (ARIMA) model [1],[2]. The solar radiation on a horizontal surface... of the error margin Energy Consumption (set value A) Energy Consumption (set value B) ESL-IC-08-10-55 Proceedings of the Eighth International Conference for Enhanced Building Operations, Berlin, Germany, October 20-22, 2008 J VAV unit is also operated under...

Sumiyoshi, D.; Akashi, Y.

97

Improving the Performance of Air-Conditioning Systems in an ASEAN Climate  

E-Print Network (OSTI)

This paper describes an analysis of air conditioning performance under hot and humid tropical climate conditions appropriate to the Association of South East Asian Nations (ASEAN) countries. This region, with over 280 million people, has one...

Busch, J. F.; Warren, M. L.

1988-01-01T23:59:59.000Z

98

Cooling energy efficiency and classroom air environment of a school building operated by the heat recovery air conditioning unit  

Science Journals Connector (OSTI)

Abstract The recently-built school buildings have adopted novel heat recovery ventilator and air conditioning system. Heat recovery efficiency of the heat recovery facility and energy conservation ratio of the air conditioning unit were analytically modeled, taking the ventilation networks into account. Following that, school classroom displacement ventilation and its thermal stratification and indoor air quality indicated by the CO2 concentration have been numerically modeled concerning the effects of delivering ventilation flow rate and supplying air temperature. Numerical results indicate that the promotion of mechanical ventilation rate can simultaneously boost the dilution of indoor air pollutants and the non-uniformity of indoor thermal and pollutant distributions. Subsequent energy performance analysis demonstrates that classroom energy demands for ventilation and cooling could be reduced with the promotion of heat recovery efficiency of the ventilation facility, and the energy conservation ratio of the air conditioning unit decreases with the increasing temperatures of supplying air. Fitting correlations of heat recovery ventilation and cooling energy conservation have been presented.

Yang Wang; Fu-Yun Zhao; Jens Kuckelkorn; Di Liu; Li-Qun Liu; Xiao-Chuan Pan

2014-01-01T23:59:59.000Z

99

RHEOLOGICAL STUDY OF TWO-PHASE SECONDARY FLUIDS FOR REFRIGERATION AND AIR CONDITIONING.  

E-Print Network (OSTI)

, indirect refrigeration systems renews interest as they enable to notably reduce the use of environmental the refrigeration applications to the air-conditioning systems. However, this kind of process only remainsRHEOLOGICAL STUDY OF TWO-PHASE SECONDARY FLUIDS FOR REFRIGERATION AND AIR CONDITIONING. Mylène

Boyer, Edmond

100

The Use of Conditioned Air for Maintaining Quality of Stored Sorghum Grain.  

E-Print Network (OSTI)

.- ...... '. .................................... 21 .............................................. Design Method No: 3 21 Effects of Conditioned-air Storage on Grain Quality ........................................................... II! Insect Control...,~ of controlled storage environments for bulk yain are discussed. The initial vapor pressure of tile moisture in the grain and the partial pressure of !lie vapor in the conditioned air circulating through llle grain mass were found to be very important tl...

Person, Nat K. Jr.; Sorenson, J. W. Jr.; McCune, W. E.; Hobgood, Price

1967-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


101

Experimental Investigation on the Operation Performance of a Liquid Desiccant Air-conditioning System  

E-Print Network (OSTI)

A large share of energy consumption is taken by an air-conditioning system. It worsens the electricity load of the power network. Therefore, more and more scholars are paying attention to research on new types of air-conditioning systems...

Liu, J.; Wang, J.; Wu, Z.; Gu, W.; Zhang, G.

2006-01-01T23:59:59.000Z

102

Low-Flow Liquid Desiccant Air Conditioning: General Guidance and Site Considerations  

SciTech Connect

Dehumidification or latent cooling in buildings is an area of growing interest that has been identified as needing more research and improved technologies for higher performance. Heating, ventilating, and air-conditioning (HVAC) systems typically expend excessive energy by using overcool-and-reheat strategies to dehumidify buildings. These systems first overcool ventilation air to remove moisture and then reheat the air to meet comfort requirements. Another common strategy incorporates solid desiccant rotors that remove moisture from the air more efficiently; however, these systems increase fan energy consumption because of the high airside pressure drop of solid desiccant rotors and can add heat of absorption to the ventilation air. Alternatively, liquid desiccant air-conditioning (LDAC) technology provides an innovative dehumidification solution that: (1) eliminates the need for overcooling and reheating from traditional cooling systems; and (2) avoids the increased fan energy and air heating from solid desiccant rotor systems.

Kozubal, E.; Herrmann, L.; Deru, M.; Clark, J.

2014-09-01T23:59:59.000Z

103

Retrofitting Air Conditioning and Duct Systems in Hot, Dry Climates  

SciTech Connect

This technical report describes CARB's work with Clark County Community Resources Division in Las Vegas, Nevada, to optimize procedures for upgrading cooling systems on existing homes in the area to implement health, safety, and energy improvements. Detailed monitoring of five AC systems showed that three of the five systems met or exceeded air flow rate goals.

Shapiro, C.; Aldrich, R.; Arena, L.

2012-07-01T23:59:59.000Z

104

Humidity Control Systems for Civil Buildings in Hot Summer and Cold Winter Zone in China  

E-Print Network (OSTI)

In the hot summer and cold winter zone, moisture-laden outside air poses real problems for proper ventilation, air-conditioner sizing, and strategies to overcome the reduced dehumidification capacity of more energy-efficient air-conditioning (AC...

Yu, X.

2006-01-01T23:59:59.000Z

105

Research on Fuzzy Regulation Strategies in the Constant Air Volume Air Conditioning System  

E-Print Network (OSTI)

Yifeng Wu Honglin Wang Doctoral Candidate Associate Professor Master Master Master Master School of Municipal & Environmental Eng, Harbin Institute of Technology Harbin P.R. China, 150090 hitbai@163.com Abstract: The energy consumption... region and the same operating strategy was adopted[1]. Wang Li analyzed the temperature control principles to achieve economical operation in CAV system, and presented improved control strategy to integrate fresh air control with indoor air...

Bai, T.; Zhang, J.; Ning, N.; Tong, K.; Wu, Y.; Wang, H.

2006-01-01T23:59:59.000Z

106

Radon Mitigation in Schools Utilising Heating, Ventilating and Air Conditioning Systems  

Science Journals Connector (OSTI)

......and Air Conditioning Engineers (ASHRAE) standard Ventilation for Acceptable Indoor Air Quality...Two case studies are presented where HVAC technology was implemented for controlling...system in a two-storey building. The HVAC system's controls were restored and modified......

G. Fisher; B. Ligman; T. Brennan; R. Shaughnessy; B.H. Turk; B. Snead

1994-12-01T23:59:59.000Z

107

Optimization of the Fin Heat Pipe for Ventilating and Air Conditioning with a Genetic Algorithm  

E-Print Network (OSTI)

conservation, and it is urgent. At the same time, the energy consumption about air-conditioning of buildings continues to increase and the new wind energy accounts for 4%~12% of the buildings total energy consumption [1]. A heat recovery system for air...

Qian, J.; Sun, D.; Li, G.

2006-01-01T23:59:59.000Z

108

Effect of a Radiant Panel Cooling System on Indoor Air Quality of a Conditioned Space  

E-Print Network (OSTI)

This paper discusses the effect of a radiant cooling panel system on an indoor air quality (IAQ) of a conditioned space. In this study, ceiling radiant cooling panel, mechanical ventilation with fan coil unit (FCU) and 100% fresh air are used...

Mohamed, E.; Abdalla, K. N.

2010-01-01T23:59:59.000Z

109

Analysis of Energy Saving in a Clean Room Air-conditioning System  

E-Print Network (OSTI)

simulated and compared the summer energy consuming conditions of the two systems. Results prove the superiority of the 2nd return air system, and the validity of the simulation. Also, the air system energy performance in summer was illustrated with typical...

Liu, S.; Liu, J.; Pei, J.; Wang, M.

2006-01-01T23:59:59.000Z

110

"Table HC11.6 Air Conditioning Characteristics by Northeast Census Region, 2005"  

U.S. Energy Information Administration (EIA) Indexed Site

6 Air Conditioning Characteristics by Northeast Census Region, 2005" 6 Air Conditioning Characteristics by Northeast Census Region, 2005" " Million U.S. Housing Units" ,,"Northeast Census Region" ,"U.S. Housing Units (millions)" ,,,"Census Division" ,,"Total Northeast" "Air Conditioning Characteristics",,,"Middle Atlantic","New England" "Total",111.1,20.6,15.1,5.5 "Do Not Have Cooling Equipment",17.8,4,2.4,1.7 "Have Coolling Equipment",93.3,16.5,12.8,3.8 "Use Cooling Equipment",91.4,16.3,12.6,3.7 "Have Equipment But Do Not Use it",1.9,0.3,"Q","Q" "Air-Conditioning Equipment1, 2 " "Central System",65.9,6,5.2,0.8 "Without a Heat Pump",53.5,5.5,4.8,0.7

111

"Table HC13.6 Air Conditioning Characteristics by South Census Region, 2005"  

U.S. Energy Information Administration (EIA) Indexed Site

6 Air Conditioning Characteristics by South Census Region, 2005" 6 Air Conditioning Characteristics by South Census Region, 2005" " Million U.S. Housing Units" ,,"South Census Region" ,"U.S. Housing Units (millions)" ,,,"Census Division" ,,"Total South" "Air Conditioning Characteristics",,,"South Atlantic","East South Central","West South Central" "Total",111.1,40.7,21.7,6.9,12.1 "Do Not Have Cooling Equipment",17.8,1.4,0.8,0.2,0.3 "Have Cooling Equipment",93.3,39.3,20.9,6.7,11.8 "Use Cooling Equipment",91.4,38.9,20.7,6.6,11.7 "Have Equipment But Do Not Use it",1.9,0.5,"Q","Q","Q" "Air-Conditioning Equipment1, 2 "

112

Analysis of the Diagnostic Methods of the Performance Failure of Heating and Air Conditioning Systems  

E-Print Network (OSTI)

ICEBO2006, Shenzhen, China Co ntrol Systems for Energy Efficiency and Comfort, Vol. V-5-2 Analysis of the Diagnostic Methods of the Performance Failure of Heating and Air Conditioning Systems Lianyou LI Zhihong ZHANG Yong...

Li, L.; Zhang, Z.; Sun, Y.; Li, D.; Xie, H.

2006-01-01T23:59:59.000Z

113

Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Regulatory Burden RFI  

Energy.gov (U.S. Department of Energy (DOE))

These comments are submitted by the Air-Conditioning, Heating, and Refrigeration Institute (AHRI) in response to the U.S. Department of Energys (DOE) notice in the August 8, 2012 Federal Register...

114

Economic Analysis and Comparison of Waste Water Resource Heat Pump Heating and Air-Conditioning System  

E-Print Network (OSTI)

ICEBO2006, Shenzhen, China Renewable Energy Resources and a Greener Future, Vol.VIII-8-1 Economic Analysis and Comparison of Waste Water Resource Heat Pump Heating and Air-conditioning System Chunlei Zhang Suilin Wang Hongbing Chen...

Zhang, C.; Wang, S.; Chen, H.; Shi, Y.

2006-01-01T23:59:59.000Z

115

Multi-Domain Modeling and Simulation of Automotive Air Conditioning System Based On Modelica  

Science Journals Connector (OSTI)

The automotive air conditioning (AC) systems are complex systems where two-phase flow, pneumatic, mechanical and electrical components are coupled. Such systems coupled with various physical domains have great...

Jing Li; Yunqing Zhang

2013-01-01T23:59:59.000Z

116

Modelica Library for Building Heating, Ventilation and Air-Conditioning Systems  

E-Print Network (OSTI)

Austria, September 2006. Modelica As- sociation and Arsenalsystems. The ?exibility of Modelica has been T room in [ C]lss. AirConditioning - a Modelica li- o brary for dynamic

Wetter, Michael

2010-01-01T23:59:59.000Z

117

Demand response: a strategy to address residential air-conditioning peak load in Australia  

Science Journals Connector (OSTI)

Rapid growth in electricity network peak demand is increasing pressure for new investment which may be used for only a few hours a year. Residential air-conditioning is widely believed to be the prime cause of...

Robert Smith; Ke Meng; Zhaoyang Dong

2013-12-01T23:59:59.000Z

118

Numerical Analysis of the Channel Wheel Fresh Air Ventilator Under Frosting Conditions  

E-Print Network (OSTI)

channel wheel heat exchanger under different ambient conditions using the model developed. These include frost formation on the surface of the channel wheel heat exchanger, and impacts on the operational performance of the channel wheel fresh air...

Gao, B.; Dong, Z.; Cheng, Z.; Luo, E.

2006-01-01T23:59:59.000Z

119

Dependence of thermal destabilization of electric-arc plasma in an air flow on discharge conditions  

Science Journals Connector (OSTI)

The effect of the conditions of electric-arc burning in an air flow on the ... processes in the development of instability in an arc-discharge column is shown.

V. N. Borisyuk; S. V. Goncharik

1997-03-01T23:59:59.000Z

120

Research on Solar High-Temperature Absorption Air-Conditioning Systems  

Science Journals Connector (OSTI)

This paper studies the characteristics and performance of solar higher-temperature absorption air conditioning systems which employed linear concentrating collectors and double-effect absorption chillers. A solar...

Guoqing Yu; Jinhua Tang; Zhijun Zou

2009-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


121

E-Print Network 3.0 - automative air-conditioning systems Sample...  

NLE Websites -- All DOE Office Websites (Extended Search)

systems Page: << < 1 2 3 4 5 > >> 1 PLEASE HELP SAVE ENERGY Learn how to control the heating system for your room. Summary: & SW Heat & air conditioning control Cary E & NE &...

122

Feasibility of Municipal Water Mains as Heat Sink for Residential Air-Conditioning  

E-Print Network (OSTI)

It has been proposed that municipal water mains be used as the heat sink or the heat source for air-conditioning or heating, respectively. This paper addresses the extent of thermal contamination associated with the use of municipal water...

Vliet, G. C.

1994-01-01T23:59:59.000Z

123

Development and modelling of a solar assisted liquid desiccant dehumidification air-conditioning system  

Science Journals Connector (OSTI)

This paper presents the development and simulation of an advanced solar assisted liquid desiccant dehumidification air-conditioning system for ... regenerator, and an array of flat plate solar collectors. The sys...

Aqeel Kareem Mohaisen; Zhenjun Ma

2014-09-01T23:59:59.000Z

124

E-Print Network 3.0 - air conditioning heat Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

water. FIND... : Determine which condition feels colder. Contrast these results with a heat loss of 30 Wm2 under ormal room... in the case f air flow.o ANALYSIS: The hand will...

125

Energy Comparison Between Conventional and Chilled Water Thermal Storage Air Conditioning Systems  

E-Print Network (OSTI)

, encouraged by government subsidies and driven by the rapid and continual expansion in building construction, urban development, and the heavy reliance on Air Conditioning (AC) systems for the cooling of buildings. The Chilled Water Thermal Storage (CWTS...

Sebzali, M.; Hussain, H. J.; Ameer, B.

2010-01-01T23:59:59.000Z

126

Discussion of Air-Conditioning Energy-Savings in Hot-Summer and Cold-Winter Regions  

E-Print Network (OSTI)

Introducing several kinds of air-conditioning systems energy conservation measures, and according to the climate of the hot-summer and cold-winter region in China, this paper puts forward an overall conception for air-conditioning energy...

Zheng, W.; Gong, F.; Lou, X.; Cheng, J.

2006-01-01T23:59:59.000Z

127

The Coordinated Control of a Central Air Conditioning System Based on Variable Chilled Water Temperature and Variable Chilled Water Flow  

E-Print Network (OSTI)

At present, regulation of water flow by means of pump frequency conversion is one of the major methods for power-saving in central air conditioning systems. In this article, optimization regulation for central air conditioning system on the basis...

Liu, J.; Mai, Y.; Liu, X.

2006-01-01T23:59:59.000Z

128

Direct-Expansion Air-Conditioning System Performance in Low Humidity Applications: A Case Study  

E-Print Network (OSTI)

DIRECT-EXPANSION AIR-CONDITIONING SYSTEM PERFORMANCE IN LOW HUMIDITY APPLICATIONS: A CASE STUDY MUKESH K. KHATTAR, P.E. DENNIS KEEBAUGH, P.E. Senior Systems Engineer Senior Research Engineer Florida Solar Energy Center Shenandoah Solar Center... warehouse. The flat gravel roof is exposed to sun. The 16' ceiling is insulated with two inch spray foam. Entrance to the warehouse is through sealed and insulated doors located on the west partition wall. The air -conditioning sys tem on this leased...

Khattar, M. K.; Keebaugh, D.

1987-01-01T23:59:59.000Z

129

Energy-efficient heat recovery systems for air conditioning of indoor swimming pools  

SciTech Connect

Analysis of a conventional air-conditioning system for indoor swimming pools during the summer season is presented. The analysis showed that the cooling load is characterized by a large latent heat fraction. As a result, a reheating process must be used downstream of the cooling coil to achieve the proper design comfort condition in the pool area. This, in turn, increases the energy requirement per unit cooling load of the pool. Two heat recovery systems are proposed to reduce this energy. In the first system, ambient air is used for the reheating process in an air-to-air heat exchanger. In the second system, mixed air--recirculated and ambient air--is used for the reheating process. Heat recovery efficiency is defined as an index of the energy savings resulting from the use of the heat recovery system compared to that of a conventional air-conditioning system. At a wide range of ambient conditions it is found that the energy savings could be up to 70% of the energy required to operate a conventional air-conditioning system. A parametric study was carried out to size the air-to-air heat exchanger associated with these heat recovery systems, and the results showed that a heat exchanger having an effectiveness of 0.5 would give satisfactory results. The proposed heat recovery systems are also compared to the case of reheating using the heat rejection from the condenser of the refrigeration machine. The comparison showed that the proposed systems save more energy than reheating using the condenser heat. A typical case study is given to demonstrate the savings in energy consumption when these systems are used.

Elsayed, M.M.; El-Refaee, M.M. [Kuwait Univ., Safat (Kuwait). Mechanical Engineering Dept.; Borhan, Y.A. [Gulf Engineering Co., Safat (Kuwait)

1997-12-31T23:59:59.000Z

130

Energy Efficient Design, Air Conditioning Correspondence to Author:  

E-Print Network (OSTI)

ABSTRACT: HVAC maintain both comfort and safety of indoor air quality. The challenge of maintaining high product quality while simultaneously reducing production costs can often be met through investments in energy efficient technologies and energy efficiency practices. The greatest opportunities for energy efficiency exist at the design stage for HVAC systems in new industrial facilities. By sizing components of HVAC systems generally include dampers, supply and exhaust fans, filters, humidifiers, dehumidifiers, heating and cooling coils, ducts, and various sensors properly and designing energy efficiency into a new facility, an industry can minimize the energy consumption and operational costs of its plant HVAC systems from the outset. Optimizing system design and operations, such as minimizing laboratory ventilation, can also lead to significant reductions in energy use. Energy efficiency improvement is an important way to reduce these costs and to increase predictable earnings, especially in times of high energy price volatility. There are a variety of opportunities available at individual plants in the industry to reduce energy consumption in a cost-effective manner.

Parth Patel; Parth Patel

131

Advective Desorption of Uranium (VI) from Contaminated Hanford Vadose Zone Sediments under Saturated and Unsaturated Conditions  

SciTech Connect

Sedimentary, hydrologic, and geochemical variations in the Hanford subsurface environment, as well as compositional differences in contaminating waste streams, have created vast differences in the migration and mobility of uranium within the subsurface environment. A series of hydraulically-saturated and -unsaturated column experiments were performed to i.) assess the effect of water content on the advective desorption and migration of uranium from contaminated sediments, and ii.) evaluate the uranium concentration that can develop in porewater and/or groundwater as a result of desorption/dissolution reactions. Flow rate and moisture content were varied to evaluate the influence of contact time, pore water velocity, and macropore desaturation on aqueous uranium concentrations. Sediments were collected from the T-TX-TY tank farm complex and the 300 Area Process Ponds located on the Hanford Site, southeastern Washington State. The sediments vary in depth, mineralogy, and in contamination events. Experiments were conducted under mildly alkaline/calcareous conditions representative of conditions commonly encountered at repository sites across the arid western United States and, in particular, the Hanford site. Results illustrate the release of uranium from these sediments is kinetically controlled and low water contents encountered within the Hanford vadose zone result in the formation of mobile-immobile water regimes, which isolate a fraction of the reactive sites within the sediments, effectively reducing the concentration of uranium released into migrating porewaters.

Wellman, Dawn M.; Zachara, John M.; Liu, Chongxuan; Qafoku, Nikolla; Smith, Steven C.; Forrester, Steven W.

2008-11-03T23:59:59.000Z

132

Simulation- Assisted Audit of an Air Conditioned Office Building  

E-Print Network (OSTI)

Conference for Enhanced Building Operations, Berlin, Germany, October 20-22, 2008 performances of the installation. Finally, some significant retrofit opportunities are proposed. BUILDING DESCRIPTION Building design The considered building is an existing... Conference for Enhanced Building Operations, Berlin, Germany, October 20-22, 2008 In nominal heating conditions (outdoor : -10?C/RH 90%; indoor : 20?C/RH50%), with ?t = 30 K, this gives a sensible power demand of: g1843g4662g3046,g3041g3042g3040 =g343623...

Bertagnolio, S.; Lebrun, J.; Hannay, J.; Silva, C. A.

133

A comparison between the use of natural air and air containing ozone in conditioning farm products  

E-Print Network (OSTI)

H3 Ave, Air Volume& Otme 42EOO 52e98 45e 66 46e48 40, 65 56, 64 47, 31 48, 20 43. 65 51, 66 48. 99 48, 10 55. 98 52e98 42 00 50. 32 39EOO 41e31 41e 64 COe 65 39EOO 41, 25 41. 64 40. 63 , tatio Pressures In, H. C. ~ 4...

Wilkes, Lambert Henry

1953-01-01T23:59:59.000Z

134

Monitoring the Performance of a Residential Central Air Conditioner under Degraded Conditions on a Test Bench  

E-Print Network (OSTI)

valve increases. PREDICTION OF DEGRADED CONDITIONS There are several steady state simulation programs which are available to predict the design conditions of air conditioners and heat pumps [20, 21]. The ORNL and NIST models are popular and extensively... used in industry. Farzad modified ORNL model using NIST subroutines to simulate heat exchangers in a better fashion through tube-by-tube simulation [22]. Katipamula modified TRPUMP [TRansient PUMP, 23] to simulate transient conditions to elucidate about...

Palani, M.; O'Neal, D. L.; Haberl, J. S.

1992-01-01T23:59:59.000Z

135

Analysis of historical residential air-conditioning equipment sizing using monitored data  

SciTech Connect

Monitored data were analyzed to determine whether residential air conditioners in the Pacific Northwest historically have been sized properly to meet or slightly exceed actual cooling requirements. Oversizing air-conditioning equipment results in a loss of efficiency because of increased cycling and also lowers humidity control. On the other hand, the penalty of undersizing air-conditioning equipment may be some loss of comfort during extremely hot weather. The monitored data consist of hourly space-conditioning electrical energy use and internal air temperature data collected during the past 7 years from 75 residences in the Pacific Northwest. These residences are equipped with central air conditioners or heat pumps. The periods with the highest cooling energy use were analyzed for each site. A standard industry sizing methodology was used for each site to determine a sizing estimate. Both the sizing recommendation based on Manual J and peak monitored loads are compared to the capacity of the installed equipment for each site to study how the actual capacity differed from both the estimate of proper sizing and from actual demands. Characteristics of the maximum cooling loads are analyzed here to determine which conditions put the highest demand on the air conditioner. Specifically, internal air temperature data are used to determine when the highest cooling loads occur, at constant thermostat settings or when the thermostat was set down. This analysis of monitored data also provides insight into the extent that occupant comfort may be affected by undersizing air conditioners. The findings of this research indicate that cooling equipment historically has often but not always been oversized beyond industry-recommended levels. However, some occupants in homes with undersized, properly sized, and, in rare occasions, even oversized cooling equipment appear to suffer because the cooling equipment cannot always provide adequate cooling. Key findings are summarized.

Lucas, R.G.

1993-02-01T23:59:59.000Z

136

A dynamic model for air-based photovoltaic thermal systems working under real operating conditions  

Science Journals Connector (OSTI)

Abstract In this paper a dynamic model suitable for simulating real operating conditions of air-based photovoltaic thermal (PVT) systems is presented. The performance of the model is validated by using the operational data collected from the building integrated photovoltaic (PVT) systems installed in two unique buildings. The modelled air outlet temperature and electrical power match very well with the experimental data. In Solar Decathlon house PVT, the average (RMS) error in air outlet temperatures was 4.2%. The average (RMS) error in electrical power was also 4.2%. In the Sustainable Buildings Research Centre PVT, the average errors (RMS) of PV and air temperatures were 3.8% and 2.2%, respectively. The performance of the PVT system under changing working condition is also analysed in this paper. The analysis includes the effect of ambient air temperature, air inlet temperature, air flow rate and solar irradiation on thermal, electrical, first law and second law efficiencies. Both the thermal and the 1st law efficiencies almost linearly increased with the increase of the ambient temperature. However, the PVT electrical efficiency and the second law efficiency decreased with the increase of the ambient temperature. All efficiencies expect the second law efficiency decreased with increase of the PVT air inlet temperature. The second law efficiency first increased and then reduced. With increasing the air flow rate all the efficiencies increased. The electrical and second law efficiencies become less sensitive when the air flow rate exceeded 300l/s. Both the thermal and the 1st law efficiencies decreased while the electrical efficiency and the second law efficiency increased with the increase of the solar irradiation. The efficiencies found to be very sensitive for low level of solar irradiations. At about 400Wm?2 irradiation efficiencies became less sensitive.

M. Imroz Sohel; Zhenjun Ma; Paul Cooper; Jamie Adams; Robert Scott

2014-01-01T23:59:59.000Z

137

Demonstration and Testing of ClimaStat for Improved Rooftop Air-Conditioning Efficeincy  

NLE Websites -- All DOE Office Websites (Extended Search)

Demonstration and Testing of ClimaStat® for Improved Rooftop Air-Conditioning Efficiency Presented at IA Technology Deployment Working Group Meeting March 15, 2012 By Dan Howett, PE Oak Ridge National Laboratory Demonstration/Testing of ClimaStat ® for Improved Efficiency of RTU Air Conditioners * Technology from Advantek Consulting - Patented by Dr. Michael West in 2003. (US Patent #6427454) - Originally demonstrated under DOE's Inventions & Innovations program. * Current demonstration sponsored by DOD's ESTCP program * Uses off-the-shelf components to either... - Modify existing packaged air conditioners, or - Incorporate changes into new RTU equipment before installation * Initial tests show 15% improvement in HVAC efficiency.

138

Demonstration and Testing of ClimaStat for Improved Rooftop Air-Conditioning Efficeincy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Demonstration and Testing of ClimaStat® for Improved Rooftop Air-Conditioning Efficiency Presented at IA Technology Deployment Working Group Meeting March 15, 2012 By Dan Howett, PE Oak Ridge National Laboratory Demonstration/Testing of ClimaStat ® for Improved Efficiency of RTU Air Conditioners * Technology from Advantek Consulting - Patented by Dr. Michael West in 2003. (US Patent #6427454) - Originally demonstrated under DOE's Inventions & Innovations program. * Current demonstration sponsored by DOD's ESTCP program * Uses off-the-shelf components to either... - Modify existing packaged air conditioners, or - Incorporate changes into new RTU equipment before installation * Initial tests show 15% improvement in HVAC efficiency.

139

A diffusion approximation approach to stochastic modeling of air conditioning type loads  

E-Print Network (OSTI)

that the air conditioning unit is on and off. In the followino equations, TNIN and TNAX are the lower and upper limit temperatures of the thermostat deadband and To is the outside temperature. Gi 2Gw To Tw Cw Ci $ QeXt To - outside temperature Tw - wall... temperature Ti - inside temperature Gw ? thermal conductance of wall Gi - thermal conductance of air Cw - thermal capacitance of wall Ci ? thermal capacitance of air Qe - rated capacity of cooling unit Xt - zero-one process describing the switching...

Roy, Teresa Henryka

1981-01-01T23:59:59.000Z

140

Influence Of Upper Air Conditions On The Patagonia Icefields L. A. Rasmussen, H. Conway, C. F. Raymond  

E-Print Network (OSTI)

Influence Of Upper Air Conditions On The Patagonia Icefields L. A. Rasmussen, H. Conway, C. F, Second Fig ABSTRACT. Upper-air conditions archived in the NCEP-NCAR Reanalysis have been used cannot be determined, so the investigation is limited to examining relative changes in those upper air

Rasmussen, L.A.

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


141

Table HC15.7 Air-Conditioning Usage Indicators by Four Most Populated States, 2005  

U.S. Energy Information Administration (EIA) Indexed Site

7 Air-Conditioning Usage Indicators by Four Most Populated States, 2005 7 Air-Conditioning Usage Indicators by Four Most Populated States, 2005 Total.................................................................................. 111.1 7.1 7.0 8.0 12.1 Do Not Have Cooling Equipment.................................... 17.8 1.8 Q Q 4.9 Have Cooling Equipment................................................. 93.3 5.3 7.0 7.8 7.2 Use Cooling Equipment.................................................. 91.4 5.3 7.0 7.7 6.6 Have Equipment But Do Not Use it................................ 1.9 Q N Q 0.6 Type of Air-Conditioning Equipment 1, 2 Central System............................................................. 65.9 1.1 6.4 6.4 5.4 Without a Heat Pump................................................. 53.5 1.1 3.5 5.7 4.9 With a Heat Pump......................................................

142

Calibration of Predicted Hourly Zone-Level Supply Air Flows with Measurements  

E-Print Network (OSTI)

the chemical composition, then sends a signal to the control system to increase the ventilation rate, if necessary. This system cannot be modeled in eQuest. The null hypothesis H0 is true only if the t-value is less than tcritical; if t-value is greater..., daily and monthly calibration analysis: CV-RMSE[%] vs. t-test CV-RMSE [%] Zone Interval Time step t t,cr 2.1 NE Summer Hourly 18.8 Daily 9.5 Monthly 4.2 3 days Hourly 24.2 2.4 SW Summer Hourly 28.4 Daily 12.7 Monthly 4...

Mihai, A.; Zmeureanu, R.

2013-01-01T23:59:59.000Z

143

Innovative Evaporative and Thermally Activated Technologies Improve Air Conditioning, The Spectrum of Clean Energy Innovation (Fact Sheet)  

NLE Websites -- All DOE Office Websites (Extended Search)

Innovative Evaporative and Innovative Evaporative and Thermally Activated Technologies Improve Air Conditioning Researchers at the National Renewable Energy Laboratory (NREL) invented a breakthrough technology that improves air conditioning in a novel way-with heat. NREL combined desiccant materials, which remove moisture from the air using heat, and advanced evaporative technologies to develop a cooling unit that uses 90% less electricity and up to 80% less total energy than traditional air conditioning (AC). This solution, called the desiccant enhanced evaporative air conditioner (DEVap), also controls humidity more effectively to improve the comfort of people in buildings. Desiccants are an example of a thermally activated technology (TAT) that relies on heat instead

144

Aggregated Modeling and Control of Air Conditioning Loads for Demand Response  

E-Print Network (OSTI)

1 Aggregated Modeling and Control of Air Conditioning Loads for Demand Response Wei Zhang, Member, IEEE Abstract--Demand response is playing an increasingly impor- tant role in the efficient loads is especially important to evaluate the effec- tiveness of various demand response strategies

Zhang, Wei

145

Theoretical Study of a Novel Control Method of VAV Air-conditioning System Based on MATLAB  

E-Print Network (OSTI)

ICEBO2006, Shenzhen, China Control Systems for Energy Efficiency and Comfort, Vol. V-2-2 Theoretical Study of a Novel Control Method of VAV Air-conditioning System Based on MATLAB Zhigang Shi Songtao Hu Gang Wang Angui Li Xi?An University...

Shi, Z.; Hu, S.; Wang, G.; Li, A.

2006-01-01T23:59:59.000Z

146

Smart Operations of Air-Conditioning and Lighting Systems in Government Buildings for Peak Power Reduction  

E-Print Network (OSTI)

During the summer 2007 smart operation strategies for air-conditioning (A/C) and lighting systems were developed and tested in a number of governmental buildings in Kuwait as one of the solutions to reduce the national peak demand for electrical...

Al-Hadban, Y.; Maheshwari, G. P.; Al-Nakib, D.; Al-Mulla, A.; Alasseri, R.

147

A heuristic predictive logic controller applied to hybrid solar air conditioning plant  

Science Journals Connector (OSTI)

This paper shows the development of a heuristic predictive logic controller (HPLoC) applied to a solar air conditioning plant. The plant uses two energy sources, solar and gas, in order to warm up the water. The hot water feeds a single-effect absorption ...

Darine Zambrano; Winston Garca-Gabn; Eduardo F. Camacho

2007-04-01T23:59:59.000Z

148

Experimental Tests and Predictive Model of an Adsorptive Air Conditioning Unit  

Science Journals Connector (OSTI)

An adsorption air conditioning unit has been built operating with a heat and mass recovery cycle and a zeolite?water pair. A new consolidated adsorbent composite with good heat transfer properties has been developed and implemented in the adsorber. At an ...

Florence Poyelle; Jean-Jacques Guilleminot; Francis Meunier

1998-12-08T23:59:59.000Z

149

Comment submitted by the Air Conditioning, Heating and Refrigeration Institute (AHRI) regarding the Energy Star Verification Testing Program  

Energy.gov (U.S. Department of Energy (DOE))

This document is a comment submitted by the Air Conditioning, Heating and Refrigeration Institute (AHRI) regarding the Energy Star Verification Testing Program

150

Study of solar-assisted thermoelectric technology for automobile air conditioning  

SciTech Connect

An analytical study was conducted to determine the feasibility of employing solar energy assisted thermoelectric (TE) cooling technology in automobile air conditioners. The study addressed two key issues -- power requirements and availability of thermoelectric materials. In this paper a mathematical model was developed to predict the performance of TE air conditioners and to analyze power consumption. Results show that the power required to deliver a cooling capacity of 4 kW (13,680 Btu/h) in a 38 C (100 F) environment will be 9.5 kW electric. Current TE modules suitable for air conditioning are made of bismuth telluride. The element tellurium is expected to be in short supply if TE cooling is widely implemented for auto air conditioning; some options available in this regard were studied and presented in this paper. The photovoltaic (PV) cells, assumed to cover the roof area of a compact car can only generate about 225 W. However, this is more than enough to power a fan to provide air ventilation to the car interior which significantly reduces the peak cooling load when the car is parked in bright sunlight.

Mei, V.C.; Chen, F.C. [Oak Ridge National Lab., Oak Ridge, TN (United States); Mathiprakasam, B.; Heenan, P. [Midwest Research Inst., Kansas City, MO (United States)

1993-11-01T23:59:59.000Z

151

Effect of Intake Air Filter Condition on Light-Duty Gasoline Vehicles  

SciTech Connect

Proper maintenance can help vehicles perform as designed, positively affecting fuel economy, emissions, and the overall drivability. This effort investigates the effect of one maintenance factor, intake air filter replacement, with primary focus on vehicle fuel economy, but also examining emissions and performance. Older studies, dealing with carbureted gasoline vehicles, have indicated that replacing a clogged or dirty air filter can improve vehicle fuel economy and conversely that a dirty air filter can be significantly detrimental to fuel economy. The effect of clogged air filters on the fuel economy, acceleration and emissions of five gasoline fueled vehicles is examined. Four of these were modern vehicles, featuring closed-loop control and ranging in model year from 2003 to 2007. Three vehicles were powered by naturally aspirated, port fuel injection (PFI) engines of differing size and cylinder configuration: an inline 4, a V6 and a V8. A turbocharged inline 4-cylinder gasoline direct injection (GDI) engine powered vehicle was the fourth modern gasoline vehicle tested. A vintage 1972 vehicle equipped with a carburetor (open-loop control) was also examined. Results reveal insignificant fuel economy and emissions sensitivity of modern vehicles to air filter condition, but measureable effects on the 1972 vehicle. All vehicles experienced a measured acceleration performance penalty with clogged intake air filters.

Thomas, John F [ORNL] [ORNL; Huff, Shean P [ORNL] [ORNL; West, Brian H [ORNL] [ORNL; Norman, Kevin M [ORNL] [ORNL

2012-01-01T23:59:59.000Z

152

INSTALLATION CERTIFICATE CF-6R-MECH-08 Ice Storage Air Conditioning (ISAC) Units (Page 1 of 2)  

E-Print Network (OSTI)

cooling with the compressor). Yes No #12;INSTALLATION CERTIFICATE CF-6R-MECH-08 Ice Storage AirINSTALLATION CERTIFICATE CF-6R-MECH-08 Ice Storage Air Conditioning (ISAC) Units (Page 1 of 2) Site Address: Enforcement Agency: Permit Number: 2008 Residential Compliance Forms August 2009 Ice Storage Air

153

Characterizing excavation damaged zone and stability of pressurized lined rock caverns for underground compressed air energy storage  

E-Print Network (OSTI)

for Underground Compressed Air Energy Storage Hyung-Mok Kimperformance of compressed air energy storage (CAES) in linedcavern (LRC); Compressed air energy storage (CAES); TOUGH-

Kim, H.M.

2014-01-01T23:59:59.000Z

154

Low-Flow Liquid Desiccant Air-Conditioning: Demonstrated Performance and Cost Implications  

SciTech Connect

Cooling loads must be dramatically reduced when designing net-zero energy buildings or other highly efficient facilities. Advances in this area have focused primarily on reducing a building's sensible cooling loads by improving the envelope, integrating properly sized daylighting systems, adding exterior solar shading devices, and reducing internal heat gains. As sensible loads decrease, however, latent loads remain relatively constant, and thus become a greater fraction of the overall cooling requirement in highly efficient building designs, particularly in humid climates. This shift toward latent cooling is a challenge for heating, ventilation, and air-conditioning (HVAC) systems. Traditional systems typically dehumidify by first overcooling air below the dew-point temperature and then reheating it to an appropriate supply temperature, which requires an excessive amount of energy. Another dehumidification strategy incorporates solid desiccant rotors that remove water from air more efficiently; however, these systems are large and increase fan energy consumption due to the increased airside pressure drop of solid desiccant rotors. A third dehumidification strategy involves high flow liquid desiccant systems. These systems require a high maintenance separator to protect the air distribution system from corrosive desiccant droplet carryover and so are more commonly used in industrial applications and rarely in commercial buildings. Both solid desiccant systems and most high-flow liquid desiccant systems (if not internally cooled) add sensible energy which must later be removed to the air stream during dehumidification, through the release of sensible heat during the sorption process.

Kozubal, E.; Herrmann, L.; Deru, M.; Clark, J.; Lowenstein, A.

2014-09-01T23:59:59.000Z

155

Development of a high efficiency compressor/expander for an air cycle air conditioning system. Final report  

SciTech Connect

This document presents the methods and procedures used and the results obtained in the design, fabrication, and testing of a rotary vane type compressor operated on air cycle thermodynamics. The history and results of the testing of a similar expander are summarized and the full report of that work is referenced. The machine design used was based on one patented by Ecton Corporation. The goal of the reported effort was to demonstrate the attainable efficiencies of these machines. Appropriate test rigs were assembled and the machines were tested at various operating conditions. The compressor testing did not achieve the full design speed because of time constraints but important data was obtained at 87% speed (3000 rpm). The maximum measured total efficiencies were 78% for the expander and 71% for the compressor. Various design improvements which may yield improved performance were identified and reported.

Summers, R.L.; Smolinski, R.E.

1982-11-15T23:59:59.000Z

156

Energy Performance Comparison of Heating and Air Conditioning Systems for Multi-Family Residential Buildings  

SciTech Connect

The type of heating, ventilation and air conditioning (HVAC) system has a large impact on the heating and cooling energy consumption in multifamily residential buildings. This paper compares the energy performance of three HVAC systems: a direct expansion (DX) split system, a split air source heat pump (ASHP) system, and a closed-loop water source heat pump (WSHP) system with a boiler and an evaporative fluid cooler as the central heating and cooling source. All three systems use gas furnace for heating or heating backup. The comparison is made in a number of scenarios including different climate conditions, system operation schemes and applicable building codes. It is found that with the minimum code-compliant equipment efficiency, ASHP performs the best among all scenarios except in extremely code climates. WSHP tends to perform better than the split DX system in cold climates but worse in hot climates.

Wang, Weimin; Zhang, Jian; Jiang, Wei; Liu, Bing

2011-07-31T23:59:59.000Z

157

Numerical Analysis of Heat and Moisture Transfer in Underground Air-conditioning Systems  

E-Print Network (OSTI)

ICEBO2006, Shenzhen, China Maximize Comfort: Temperature, Humidity and IAQ Vol.I-6-3 Numerical Analysis of Heat and Moisture Transfer in Underground Air-conditioning Systems Qin Wang, Xiaoping Miao, Baoyi Cheng, Liangkai Fan EIEC, PLA...]. Youming Chen, Shengwei Wang, Ling Zhang. Application of System Identification of Hygrothermal Process in Buildings [M]. Construction and Industry Publishing Company in China, Beijing, 2004. [7]. J.R. Philip, D.A. de Vries. Moisture Movement in Porous...

Wang, Q.; Miao, X.; Cheng, B.; Fan, L.

2006-01-01T23:59:59.000Z

158

Identification of the Flow Resistance Coefficient and Validation of a Building Air Conditioning System  

E-Print Network (OSTI)

for HRC estimation is investigated in this paper. And some conclusions can be got as follows: 1) The MGO method is applicable for S value identification. The method is based on the principle for multi goal optimization. The process can be widely used...ICEBO2006, Shenzhen, China HVAC Technologies for Energy Efficiency, Vol. IV-11-2 Zhijian Hou Identification of the Flow Resistance Coefficient and Validation of a Building Air Conditioning System Zhiwei Lian...

Hou, Z.; Lian, Z.

2006-01-01T23:59:59.000Z

159

Airflow Simulation and Energy Analysis in Ventilated Room with a New Type of Air Conditioning  

E-Print Network (OSTI)

quality will be achieved. Our study aims to simulate airflow in the ventilated room with this new type of air conditioning. Radiation is taken into account by the energy conservation in the system. The following section presents algorithm, thermal..., the governing equations to be solved are the conservation equations for continuity, momentum, and energy as well as the equations for turbulent kinetic energy and its dissipation rate. The buoyancy effect is accounted for by Boussinesq approximation...

Liu, D.; Tang, G.; Zhao, F.

2006-01-01T23:59:59.000Z

160

Retrofitting Inefficient Rooftop Air-Conditioning Units Reduces U.S. Navy Energy Use (Fact Sheet)  

SciTech Connect

As part of the U.S. Navy's overall energy strategy, the National Renewable Energy Laboratory (NREL) partnered with the Naval Facilities Engineering Command (NAVFAC) to demonstrate market-ready energy efficiency measures, renewable energy generation, and energy systems integration. One such technology - retrofitting rooftop air-conditioning units with an advanced rooftop control system - was identified as a promising source for reducing energy use and costs, and can contribute to increasing energy security.

Not Available

2014-04-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


161

Table HC6.7 Air-Conditioning Usage Indicators by Number of Household Members, 2005  

U.S. Energy Information Administration (EIA) Indexed Site

7 Air-Conditioning Usage Indicators by Number of Household Members, 2005 7 Air-Conditioning Usage Indicators by Number of Household Members, 2005 Total........................................................................ 111.1 30.0 34.8 18.4 15.9 12.0 Do Not Have Cooling Equipment.......................... 17.8 5.4 5.3 2.7 2.5 2.0 Have Cooling Equipment...................................... 93.3 24.6 29.6 15.7 13.4 10.0 Use Cooling Equipment....................................... 91.4 24.0 29.1 15.5 13.2 9.7 Have Equipment But Do Not Use it...................... 1.9 0.6 0.5 Q 0.2 0.4 Type of Air-Conditioning Equipment 1, 2 Central System................................................... 65.9 15.3 22.6 10.7 9.9 7.3 Without a Heat Pump....................................... 53.5 12.5 17.9 8.7 8.2 6.3 With a Heat Pump............................................ 12.3

162

A novel air-conditioning system for proactive power demand response to smart grid  

Science Journals Connector (OSTI)

Abstract Power demand response is considered as one of the most promising solutions in relieving the power imbalance of an electrical grid that results a series of critical problems to the gird and end-users. In order to effectively make use of the demand response potentials of buildings, this paper presents a novel air-conditioning system with proactive demand control for daily load shifting and real time power balance in the developing smart grid. This system consists of a chilled water storage system (CWS) and a temperature and humidity independent control (THIC) air-conditioning system, which can significantly reduce the storage volume of the chilled water tank and effectively enable a building with more flexibility in changing its electricity usage patterns. The power demand of the proposed air-conditioning system can be flexibly controlled as desired by implementing two types of demand response strategies: demand side bidding (DSB) strategy and demand as frequency controlled reserve (DFR) strategy, in respond to the day-ahead and hour-ahead power change requirements of the grid, respectively. Considerable benefits (e.g., energy and cost savings) can be achieved for both the electricity utilities and building owners under incentive pricing or tariffs. A case study is conducted in a simulation platform to demonstrate the application of the proposed system in an office building.

Chengchu Yan; Xue Xue; Shengwei Wang; Borui Cui

2014-01-01T23:59:59.000Z

163

Effects of ambient humidity on the energy use of air conditioning equipment  

E-Print Network (OSTI)

economizer control with constant supply air temperature seteconomizer control with constant supply air temperature setcontrol under the constraint of constant supply air temperature

White, Justin George

2010-01-01T23:59:59.000Z

164

An Analysis of Price Determination and Markups in the Air-Conditioning and Heating Equipment Industry  

SciTech Connect

In this report we calculate the change in final consumer prices due to minimum efficiency standards, focusing on a standard economic model of the air-conditioning and heating equipment (ACHE) wholesale industry. The model examines the relationship between the marginal cost to distribute and sell equipment and the final consumer price in this industry. The model predicts that the impact of a standard on the final consumer price is conditioned by its impact on marginal distribution costs. For example, if a standard raises the marginal cost to distribute and sell equipment a small amount, the model predicts that the standard will raise the final consumer price a small amount as well. Statistical analysis suggest that standards do not increase the amount of labor needed to distribute equipment the same employees needed to sell lower efficiency equipment can sell high efficiency equipment. Labor is a large component of the total marginal cost to distribute and sell air-conditioning and heating equipment. We infer from this that standards have a relatively small impact on ACHE marginal distribution and sale costs. Thus, our model predicts that a standard will have a relatively small impact on final ACHE consumer prices. Our statistical analysis of U.S. Census Bureau wholesale revenue tends to confirm this model prediction. Generalizing, we find that the ratio of manufacturer price to final consumer price prior to a standard tends to exceed the ratio of the change in manufacturer price to the change in final consumer price resulting from a standard. The appendix expands our analysis through a typical distribution chain for commercial and residential air-conditioning and heating equipment.

Dale, Larry; Millstein, Dev; Coughlin, Katie; Van Buskirk, Robert; Rosenquist, Gregory; Lekov, Alex; Bhuyan, Sanjib

2004-01-30T23:59:59.000Z

165

E-Print Network 3.0 - air quality conditions Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

Air Summary: Learn More: www.arl.noaa.gov 17 A Breath of Fresh Air: Improving Air Quality Predictions... reduce air pollution by driving less and mowing their lawn when...

166

LiCl dehumidifier/LiBr absorption chiller hybrid air conditioning system with energy recovery  

SciTech Connect

This invention relates to a hybrid air conditioning system that combines a solar powered LiCl dehumidifier with a LiBr absorption chiller. The desiccant dehumidifier removes the latent load by absorbing moisture from the air, and the sensible load is removed by the absorption chiller. The desiccant dehumidifier is coupled to a regenerator and the desiccant in the regenerator is heated by solar heated hot water to drive the moisture therefrom before being fed back to the dehumidifier. The heat of vaporization expended in the desiccant regenerator is recovered and used to partially preheat the driving fluid of the absorption chiller, thus substantially improving the overall COP of the hybrid system.

Ko, S.M.

1980-06-03T23:59:59.000Z

167

LiCl dehumidifier LiBr absorption chiller hybrid air conditioning system with energy recovery  

SciTech Connect

This invention relates to a hybrid air conditioning system that combines a solar powered LiCl dehumidifier with a LiBr absorption chiller. The desiccant dehumidifier removes the latent load by absorbing moisture from the air, and the sensible load is removed by the absorption chiller. The desiccant dehumidifier is coupled to a regenerator and the desiccant in the regenerator is heated by solar heated hot water to drive the moisture therefrom before being fed back to the dehumidifier. The heat of vaporization expended in the desiccant regenerator is recovered and used to partially preheat the driving fluid of the absorption chiller, thus substantially improving the overall COP of the hybrid system. 4 figs.

Ko, S.M.

1980-06-03T23:59:59.000Z

168

Impact of Vehicle Air-Conditioning on Fuel Economy, Tailpipe Emissions, and Electric Vehicle Range: Preprint  

NLE Websites -- All DOE Office Websites (Extended Search)

Vehicle Air- Vehicle Air- Conditioning on Fuel Economy, Tailpipe Emissions, and Electric Vehicle Range Preprint September 2000 * NREL/CP-540-28960 R. Farrington and J. Rugh To Be Presented at the Earth Technologies Forum Washington, D.C. October 31, 2000 National Renewable Energy Laboratory 1617 Cole Boulevard Golden, Colorado 80401-3393 NREL is a U.S. Department of Energy Laboratory Operated by Midwest Research Institute * * * * Battelle * * * * Bechtel Contract No. DE-AC36-99-GO10337 NOTICE The submitted manuscript has been offered by an employee of the Midwest Research Institute (MRI), a contractor of the US Government under Contract No. DE-AC36-99GO10337. Accordingly, the US Government and MRI retain a nonexclusive royalty-free license to publish or reproduce the published

169

Commentary: Air-conditioning as a risk for increased use of healthservices  

SciTech Connect

In this issue of the journal, Preziosi et al. [2004] report the first study to assess differences in the utilization of health care related to the presence of air-conditioning in office workplaces. Although the study was simple and cross-sectional, the data variables from questionnaires, and the findings subject to a variety of questions, the findings are striking enough to deserve clarification. The study used a large random national sample of French women assembled for another purpose (to study antioxidant nutrients and prevention of cancer and cardiovascular disease). Participants reported health services and health events in monthly questionnaires over 1 year, and in one questionnaire in the middle of that period also reported whether air-conditioning was in use at their workplace. Fifteen percent of participants reported air-conditioning at work. Analyses adjusting for age and smoking status of participants found increases in most outcomes assessed: use of specific kinds of physicians, sickness absence, and hospital stays. While the increases in odds ratios (OR) and 95% confidence intervals (CI) were statistically significant for only otorhinolaryngology [OR (95% CI) = 2.33 (1.35-4.04)] and sickness absence [1.70 (1.13-2.58)], other increases were notable--dermatology [1.6 (0.98-2.65)]; hospital stay [1.51 (0.92-2.45)], and pneumonology [2.10 (0.65-6.82)]. The least elevated outcomes were for general practice medicine [0.99 (0.65-1.48)] and global medical visits [1.18 (0.67-2.07)]. [Preziosi et al., 2004 ,(Table 2)] Odds ratios for relatively common health outcomes often lie farther from the null than the risk ratios most useful for quantifying the increase in risk. Risk ratios, or prevalence ratios (PRs, the equivalent measure of effect for cross-sectional data), have seldom been used because of the convenience and availability of logistic regression models that estimate odds ratios. With baseline prevalences ranging up to 85.7% in the data from Preziosi et al. [2004], PRs allow a more appropriate estimate of the increase in each outcome associated with the risk factor of air-conditioning. The increase in prevalence was roughly estimated as [100* (crude PR * adjusted OR/crude OR)-100] %. Based on the data in Table 2 of Preziosi et al. [ 2004], estimates for the increased prevalence associated with air-conditioned offices include increases of 120% in otorhinolaryngology visits, and 40% in sickness absence. If these associated increases represented valid causal relationships, it would indicate enormous costs for employers and for society associated with air-conditioning systems, from increased health care and for reduced workplace productivity from sickness absence, in addition to a large burden of disease on workers.

Mendell, Mark J.

2004-06-01T23:59:59.000Z

170

Fuel-Free Compressed-Air Energy Storage: Fuel-Free, Ubiquitous Compressed-Air Energy Storage and Power Conditioning  

SciTech Connect

GRIDS Project: General Compression has developed a transformative, near-isothermal compressed air energy storage system (GCAES) that prevents air from heating up during compression and cooling down during expansion. When integrated with renewable generation, such as a wind farm, intermittent energy can be stored in compressed air in salt caverns or pressurized tanks. When electricity is needed, the process is reversed and the compressed air is expanded to produce electricity. Unlike conventional compressed air energy storage (CAES) projects, no gas is burned to convert the stored high-pressure air back into electricity. The result of this breakthrough is an ultra-efficient, fully shapeable, 100% renewable and carbon-free power product. The GCAES system can provide high quality electricity and ancillary services by effectively integrating renewables onto the grid at a cost that is competitive with gas, coal and nuclear generation.

None

2010-09-13T23:59:59.000Z

171

Solutions for Summer Electric Power Shortages: Demand Response andits Applications in Air Conditioning and Refrigerating Systems  

SciTech Connect

Demand response (DR) is an effective tool which resolves inconsistencies between electric power supply and demand. It further provides a reliable and credible resource that ensures stable and economical operation of the power grid. This paper introduces systematic definitions for DR and demand side management, along with operational differences between these two methods. A classification is provided for DR programs, and various DR strategies are provided for application in air conditioning and refrigerating systems. The reliability of DR is demonstrated through discussion of successful overseas examples. Finally, suggestions as to the implementation of demand response in China are provided.

Han, Junqiao; Piette, Mary Ann

2007-11-30T23:59:59.000Z

172

An experimental system for advanced heating, ventilating and air conditioning (HVAC) control  

Science Journals Connector (OSTI)

While having the potential to significantly improve heating, ventilating and air conditioning (HVAC) system performance, advanced (e.g., optimal, robust and various forms of adaptive) controllers have yet to be incorporated into commercial systems. Controllers consisting of distributed proportional-integral (PI) control loops continue to dominate commercial HVAC systems. Investigation into advanced HVAC controllers has largely been limited to proposals and simulations, with few controllers being tested on physical systems. While simulation can be insightful, the only true means for verifying the performance provided by HVAC controllers is by actually using them to control an HVAC system. The construction and modeling of an experimental system for testing advanced HVAC controllers, is the focus of this article. A simple HVAC system, intended for controlling the temperature and flow rate of the discharge air, was built using standard components. While only a portion of an overall HVAC system, it is representative of a typical hot water to air heating system. In this article, a single integrated environment is created that is used for data acquisition, controller design, simulation, and closed loop controller implementation and testing. This environment provides the power and flexibility needed for rapid prototyping of various controllers and control design methodologies.

Michael Anderson; Michael Buehner; Peter Young; Douglas Hittle; Charles Anderson; Jilin Tu; David Hodgson

2007-01-01T23:59:59.000Z

173

"Table HC15.6 Air Conditioning Characteristics by Four Most Populated States, 2005"  

U.S. Energy Information Administration (EIA) Indexed Site

6 Air Conditioning Characteristics by Four Most Populated States, 2005" 6 Air Conditioning Characteristics by Four Most Populated States, 2005" " Million U.S. Housing Units" ,"U.S. Housing Units (millions)","Four Most Populated States" "Air Conditioning Characteristics",,"New York","Florida","Texas","California" "Total",111.1,7.1,7,8,12.1 "Do Not Have Cooling Equipment",17.8,1.8,"Q","Q",4.9 "Have Cooling Equipment",93.3,5.3,7,7.8,7.2 "Use Cooling Equipment",91.4,5.3,7,7.7,6.6 "Have Equipment But Do Not Use it",1.9,"Q","N","Q",0.6 "Air-Conditioning Equipment1, 2 " "Central System",65.9,1.1,6.4,6.4,5.4

174

"Table HC11.7 Air-Conditioning Usage Indicators by Northeast Census Region, 2005"  

U.S. Energy Information Administration (EIA) Indexed Site

7 Air-Conditioning Usage Indicators by Northeast Census Region, 2005" 7 Air-Conditioning Usage Indicators by Northeast Census Region, 2005" " Million U.S. Housing Units" ,,"Northeast Census Region" ,"U.S. Housing Units (millions)" ,,,"Census Division" ,,"Total Northeast" "Air Conditioning Usage Indicators",,,"Middle Atlantic","New England" "Total",111.1,20.6,15.1,5.5 "Do Not Have Cooling Equipment",17.8,4,2.4,1.7 "Have Cooling Equipment",93.3,16.5,12.8,3.8 "Use Cooling Equipment",91.4,16.3,12.6,3.7 "Have Equipment But Do Not Use it",1.9,0.3,"Q","Q" "Type of Air-Conditioning Equipment1, 2" "Central System",65.9,6,5.2,0.8 "Without a Heat Pump",53.5,5.5,4.8,0.7

175

"Table HC15.7 Air-Conditioning Usage Indicators by Four Most Populated States, 2005"  

U.S. Energy Information Administration (EIA) Indexed Site

7 Air-Conditioning Usage Indicators by Four Most Populated States, 2005" 7 Air-Conditioning Usage Indicators by Four Most Populated States, 2005" " Million U.S. Housing Units" ,"Housing Units (millions)","Four Most Populated States" "Air Conditioning Usage Indicators",,"New York","Florida","Texas","California" "Total",111.1,7.1,7,8,12.1 "Do Not Have Cooling Equipment",17.8,1.8,"Q","Q",4.9 "Have Cooling Equipment",93.3,5.3,7,7.8,7.2 "Use Cooling Equipment",91.4,5.3,7,7.7,6.6 "Have Equipment But Do Not Use it",1.9,"Q","N","Q",0.6 "Type of Air-Conditioning Equipment1, 2" "Central System",65.9,1.1,6.4,6.4,5.4

176

"Table HC10.7 Air-Conditioning Usage Indicators by U.S. Census Region, 2005"  

U.S. Energy Information Administration (EIA) Indexed Site

7 Air-Conditioning Usage Indicators by U.S. Census Region, 2005" 7 Air-Conditioning Usage Indicators by U.S. Census Region, 2005" " Million U.S. Housing Units" ,"Housing Units (millions)","U.S. Census Region" "Air Conditioning Usage Indicators",,"Northeast","Midwest","South","West" "Total",111.1,20.6,25.6,40.7,24.2 "Do Not Have Cooling Equipment",17.8,4,2.1,1.4,10.3 "Have Cooling Equipment",93.3,16.5,23.5,39.3,13.9 "Use Cooling Equipment",91.4,16.3,23.4,38.9,12.9 "Have Equipment But Do Not Use it",1.9,0.3,"Q",0.5,1 "Type of Air-Conditioning Equipment1, 2" "Central System",65.9,6,17.3,32.1,10.5 "Without a Heat Pump",53.5,5.5,16.2,23.2,8.7

177

"Table HC13.7 Air-Conditioning Usage Indicators by South Census Region, 2005"  

U.S. Energy Information Administration (EIA) Indexed Site

7 Air-Conditioning Usage Indicators by South Census Region, 2005" 7 Air-Conditioning Usage Indicators by South Census Region, 2005" " Million U.S. Housing Units" ,,"South Census Region" ,"U.S. Housing Units (millions)" ,,,"Census Division" ,,"Total South" "Air Conditioning Usage Indicators",,,"South Atlantic","East South Central","West South Central" "Total",111.1,40.7,21.7,6.9,12.1 "Do Not Have Cooling Equipment",17.8,1.4,0.8,0.2,0.3 "Have Cooling Equipment",93.3,39.3,20.9,6.7,11.8 "Use Cooling Equipment",91.4,38.9,20.7,6.6,11.7 "Have Equipment But Do Not Use it",1.9,0.5,"Q","Q","Q" "Type of Air-Conditioning Equipment1, 2"

178

Energy Conservation and Comfort of Heat Pump Desiccant Air Conditioning System in Actual Living Space in Summer  

E-Print Network (OSTI)

Energy Conservation and Comfort of Heat Pump Desiccant Air Conditioning System in Actual Living and total heat exchanger in terms of both energy conservation and thermal comfort in summer. 1. COP

Miyashita, Yasushi

179

A genetic rule weighting and selection process for fuzzy control of heating, ventilating and air conditioning systems  

Science Journals Connector (OSTI)

In this paper, we propose the use of weighted linguistic fuzzy rules in combination with a rule selection process to develop accurate fuzzy logic controllers dedicated to the intelligent control of heating, ventilating and air conditioning systems concerning ... Keywords: BEMS, building energy management system, FLC, fuzzy logic controller, Fuzzy logic controllers, GA, genetic algorithm, Genetic algorithms, HVAC systems, HVAC, heating, ventilating, and air conditioning, KB, knowledge base, PMV, predicted mean vote index for thermal comfort, Rule selection, Weighted fuzzy rules

Rafael Alcal; Jorge Casillas; Oscar Cordn; Antonio Gonzlez; Francisco Herrera

2005-04-01T23:59:59.000Z

180

Energy and global warming impacts of next generation refrigeration and air conditioning technologies  

SciTech Connect

Significant developments have occurred in hydrofluorocarbon (HFC) and the application of ammonia and hydrocarbons as refrigerant working fluids since the original TEWI (Total Equivalent Warming Impact) report in 1991. System operating and performance data on alternative refrigerants and refrigeration technologies justify and updated evaluation of these new alternative refrigerants and competing technologies in well-characterized applications. Analytical and experimental results are used to show quantitative comparisons between HFCS, HFC blends, hydrocarbons, and ammonia, used as refrigerants. An objective evaluation is presented for commercial and near commercial non-CFC refrigerants/blowing agents and alternative refrigeration technologies. This information is needed for objective and quantitative decisions on policies addressing greenhouse gas emissions from refrigeration and air conditioning equipment. The evaluation assesses the energy use and global warming impacts of refrigeration and air conditioning technologies that could be commercialized during the phase out of HCFCS. Quantitative comparison TEWI for two application areas are presented. Opportunities for significant reductions in TEWI are seen with currently known refrigerants through improved maintenance and servicing practices and improved product designs.

Sand, J.R.; Fischer, S.K.; Baxter, V.D.

1996-10-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


181

Realisable 10-year reductions in European energy consumption for air conditioning  

Science Journals Connector (OSTI)

Abstract This paper summarises the results of a study to identify and quantify the potential impact of measures and policies to reduce the energy consumption of air conditioning in European countries over a 10-year period. The market penetration of air conditioning in Europe has increased steadily over several decades. On a business as usual basis, its energy consumption would increase by over 50% by 2020. Measures to restrict this increase are therefore important, but the savings potential straddles several overlapping areas which are subject to different constraints including those imposed by the replacement rates of systems and products, and the refurbishment rates of existing buildings. This work reported in this paper is based on the use of information from a variety of sources in a highly disaggregated model to assess the realisable savings over a 10-year period, taking into account relevant constraints. The paper summarises results at a European level, focussing on those cases that generate the greatest realisable savings. Savings are possible in three areas: improved equipment and system efficiency, reduced cooling loads, and more effective operation. The cases that offer the largest savings provide the basis for recommendations for policy measures, often using existing policy instruments. In addition, areas where further work is needed are identified. More detailed results and information about the study and additional recommendations can be found at http://www.bre.co.uk/searchresults.jsp?category=5&q=energy+management [1].

Roger Hitchin; Christine Pout; David Butler

2015-01-01T23:59:59.000Z

182

Advances in the development of energy efficient technologies: Sea Water Air Conditioning (SWAC)  

SciTech Connect

Sea water air conditioning (SWAC) is a cost effective and environmentally friendly alternative to and/or enhancement of air conditioning from mechanical chillers. SWAC pumps cold sea water from the appropriate ocean depths (50 to 3,000 feet depending on the climate and local characteristics) to the shore where it replaces (by direct cooling) or enhances (through use as condenser water) large mechanical chillers found in coastal facilities. SWAC direct cooling uses less than twenty per cent of the electricity of a mechanical chiller and uses no refrigerants whatsoever. Indirect cooling also offers substantial energy savings. Both systems dispense with the need for a cooling tower. Technical advances over the last twenty years in corrosion resistant alloys (titanium or aluminum), bio-fouling deterrence, and deep ocean pipeline deployment allow SWAC installations to use reliable, off-the-shelf technology. SWAC works in a variety of climates (existing installations are in Hawaii and Halifax, Nova Scotia), giving it significant domestic and international potential. Economy-of-scale advantages make it attractive to district cooling schemes.

Coony, J.E. [Boston Pacific Co., Inc., Washington, DC (United States)

1996-11-01T23:59:59.000Z

183

E-Print Network 3.0 - air filter condition Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

fans... , water treatment equipment, elevators (electric and hydraulic), sewer lift pumps, filter servicing in air... : Use of mechanical equipment such as refrigeration, air...

184

E-Print Network 3.0 - air conditioning energy Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

Geosciences 3 Energy Efficient Process Heating: Managing Air Flow Kevin Carpenter and Kelly Kissock Summary: Energy Efficient Process Heating: Managing Air Flow Kevin Carpenter...

185

E-Print Network 3.0 - air conditioning Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

Collection: Geosciences ; Environmental Sciences and Ecology 19 Connectable solar air collectors Solar Energy Centre Denmark Summary: Connectable solar air collectors Solar...

186

E-Print Network 3.0 - air conditioning applications Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

Storage, Conversion and Utilization ; Engineering 13 Connectable solar air collectors Solar Energy Centre Denmark Summary: Connectable solar air collectors Solar Energy Centre...

187

Ducts in Conditioned Space - Building America Top Innovation...  

Energy Savers (EERE)

moving ductwork into conditioned space in the hot-dry climate zone saved 8% to 15% on air-conditioning costs for homeowners. For this Top Innovation profile, Building America...

188

Effect of Intake Air Filter Condition on Vehicle Fuel Economy--ORNL/TM-2009/021  

NLE Websites -- All DOE Office Websites (Extended Search)

021 021 Effect of Intake Air Filter Condition on Vehicle Fuel Economy February 2009 Prepared by Kevin Norman Shean Huff Brian West DOCUMENT AVAILABILITY Reports produced after January 1, 1996, are generally available free via the U.S. Department of Energy (DOE) Information Bridge. Web site http://www.osti.gov/bridge Reports produced before January 1, 1996, may be purchased by members of the public from the following source. National Technical Information Service 5285 Port Royal Road Springfield, VA 22161 Telephone 703-605-6000 (1-800-553-6847) TDD 703-487-4639 Fax 703-605-6900 E-mail info@ntis.gov Web site http://www.ntis.gov/support/ordernowabout.htm Reports are available to DOE employees, DOE contractors, Energy Technology Data Exchange

189

New Automotive Air Conditioning System Simulation Tool Developed in MATLAB/Simulink  

SciTech Connect

Further improvements in vehicle fuel efficiency require accurate evaluation of the vehicle's transient total power requirement. When operated, the air conditioning (A/C) system is the largest auxiliary load on a vehicle; therefore, accurate evaluation of the load it places on the vehicle's engine and/or energy storage system is especially important. Vehicle simulation software, such as 'Autonomie,' has been used by OEMs to evaluate vehicles' energy performance. A transient A/C simulation tool incorporated into vehicle simulation models would also provide a tool for developing more efficient A/C systems through a thorough consideration of the transient A/C system performance. The dynamic system simulation software Matlab/Simulink was used to develop new and more efficient vehicle energy system controls. The various modeling methods used for the new simulation tool are described in detail. Comparison with measured data is provided to demonstrate the validity of the model.

Kiss, T.; Chaney, L.; Meyer, J.

2013-07-01T23:59:59.000Z

190

Evaluation Framework and Analyses for Thermal Energy Storage Integrated with Packaged Air Conditioning  

SciTech Connect

Few third-party guidance documents or tools are available for evaluating thermal energy storage (TES) integrated with packaged air conditioning (AC), as this type of TES is relatively new compared to TES integrated with chillers or hot water systems. To address this gap, researchers at the National Renewable Energy Laboratory conducted a project to improve the ability of potential technology adopters to evaluate TES technologies. Major project outcomes included: development of an evaluation framework to describe key metrics, methodologies, and issues to consider when assessing the performance of TES systems integrated with packaged AC; application of multiple concepts from the evaluation framework to analyze performance data from four demonstration sites; and production of a new simulation capability that enables modeling of TES integrated with packaged AC in EnergyPlus. This report includes the evaluation framework and analysis results from the project.

Kung, F.; Deru, M.; Bonnema, E.

2013-10-01T23:59:59.000Z

191

Heating, Ventilating, and Air-Conditioning: Recent Advances in Diagnostics and Controls to Improve Air-Handling System Performance  

SciTech Connect

The performance of air-handling systems in buildings needs to be improved. Many of the deficiencies result from myths and lore and a lack of understanding about the non-linear physical principles embedded in the associated technologies. By incorporating these principles, a few important efforts related to diagnostics and controls have already begun to solve some of the problems. This paper illustrates three novel solutions: one rapidly assesses duct leakage, the second configures ad hoc duct-static-pressure reset strategies, and the third identifies useful intermittent ventilation strategies. By highlighting these efforts, this paper seeks to stimulate new research and technology developments that could further improve air-handling systems.

Wray, Craig; Wray, Craig P.; Sherman, Max H.; Walker, I.S.; Dickerhoff, D.J.; Federspiel, C.C.

2008-02-01T23:59:59.000Z

192

NREL's Energy-Saving Technology for Air Conditioning Cuts Peak Power Loads Without Using Harmful Refrigerants (Fact Sheet)  

SciTech Connect

This fact sheet describes how the DEVAP air conditioner was invented, explains how the technology works, and why it won an R&D 100 Award. Desiccant-enhanced evaporative (DEVAP) air-conditioning will provide superior comfort for commercial buildings in any climate at a small fraction of the electricity costs of conventional air-conditioning equipment, releasing far less carbon dioxide and cutting costly peak electrical demand by an estimated 80%. Air conditioning currently consumes about 15% of the electricity generated in the United States and is a major contributor to peak electrical demand on hot summer days, which can lead to escalating power costs, brownouts, and rolling blackouts. DEVAP employs an innovative combination of air-cooling technologies to reduce energy use by up to 81%. DEVAP also shifts most of the energy needs to thermal energy sources, reducing annual electricity use by up to 90%. In doing so, DEVAP is estimated to cut peak electrical demand by nearly 80% in all climates. Widespread use of this cooling cycle would dramatically cut peak electrical loads throughout the country, saving billions of dollars in investments and operating costs for our nation's electrical utilities. Water is already used as a refrigerant in evaporative coolers, a common and widely used energy-saving technology for arid regions. The technology cools incoming hot, dry air by evaporating water into it. The energy absorbed by the water as it evaporates, known as the latent heat of vaporization, cools the air while humidifying it. However, evaporative coolers only function when the air is dry, and they deliver humid air that can lower the comfort level for building occupants. And even many dry climates like Phoenix, Arizona, have a humid season when evaporative cooling won't work well. DEVAP extends the applicability of evaporative cooling by first using a liquid desiccant-a water-absorbing material-to dry the air. The dry air is then passed to an indirect evaporative cooling stage, in which the incoming air is in thermal contact with a moistened surface that evaporates the water into a separate air stream. As the evaporation cools the moistened surface, it draws heat from the incoming air without adding humidity to it. A number of cooling cycles have been developed that employ indirect evaporative cooling, but DEVAP achieves a superior efficiency relative to its technological siblings.

Not Available

2012-07-01T23:59:59.000Z

193

Regression analysis of residential air-conditioning energy consumption at Dhahran, Saudi Arabia  

SciTech Connect

The energy consumption of a house air conditioner located at Dhahran, Saudi Arabia, is modeled as a function of weather parameters and total (global) solar radiation on a horizontal surface. The selection of effective parameters that significantly influence energy consumption is carried out using general stepping regression methods. The problem of collinearity between the regressors is also investigated. The final model involves parameters of total solar radiation on a horizontal surface, wind speed, and temperature difference between the indoor and outdoor condition. However, the model coefficients are functions of relative humidity and/or temperature difference between the indoor and outdoor condition. Model adequacy is examined by the residual analysis technique. Model validation is carried out by the data-splitting technique. The sensitivity of the model indicates that relative humidity and temperature difference strongly influence the cooling energy consumption. It was found that an increase in relative humidity from 20% to 100% can cause a 100% increase in cooling energy consumption during the high cooling season.

Abdel-Nabi, D.Y.; Zubair, S.M.; Abdelrahman, M.A.; Bahel, V. (Energy Systems Group, Div. of Energy Resources, Research Inst., King Fahd Univ. of Petroleum and Minerals, Dhahran (SA))

1990-01-01T23:59:59.000Z

194

"Table HC3.7 Air-Conditioning Usage Indicators by Owner-Occupied Housing Unit, 2005"  

U.S. Energy Information Administration (EIA) Indexed Site

7 Air-Conditioning Usage Indicators by Owner-Occupied Housing Unit, 2005" 7 Air-Conditioning Usage Indicators by Owner-Occupied Housing Unit, 2005" " Million U.S. Housing Units" ,," Owner-Occupied Housing Units (millions)","Type of Owner-Occupied Housing Unit" ,"U.S. Housing Units (millions)" ,,,"Single-Family Units",,"Apartments in Buildings With--" "Air Conditioning Usage Indicators",,,"Detached","Attached","2 to 4 Units","5 or More Units","Mobile Homes" "Total",111.1,78.1,64.1,4.2,1.8,2.3,5.7 "Do Not Have Cooling Equipment",17.8,11.3,9.3,0.6,"Q",0.4,0.9 "Have Cooling Equipment",93.3,66.8,54.7,3.6,1.7,1.9,4.8 "Use Cooling Equipment",91.4,65.8,54,3.6,1.7,1.9,4.7

195

"Table HC3.6 Air Conditioning Characteristics by Owner-Occupied Housing Units, 2005"  

U.S. Energy Information Administration (EIA) Indexed Site

6 Air Conditioning Characteristics by Owner-Occupied Housing Units, 2005" 6 Air Conditioning Characteristics by Owner-Occupied Housing Units, 2005" " Million U.S. Housing Units" ,," Owner-Occupied Housing Units (millions)","Type of Owner-Occupied Housing Unit" ,"U.S. Housing Units (millions" ,,,"Single-Family Units",,"Apartments in Buildings With--" "Air Conditioning Characteristics",,,"Detached","Attached","2 to 4 Units","5 or More Units","Mobile Homes" "Total",111.1,78.1,64.1,4.2,1.8,2.3,5.7 "Do Not Have Cooling Equipment",17.8,11.3,9.3,0.6,"Q",0.4,0.9 "Have Cooling Equipment",93.3,66.8,54.7,3.6,1.7,1.9,4.8 "Use Cooling Equipment",91.4,65.8,54,3.6,1.7,1.9,4.7

196

SOLAS Mid Term Strategy Initiative "Air-sea gas fluxes at Eastern boundary upwelling and Oxygen Minimum Zone (OMZ) systems"  

E-Print Network (OSTI)

of SOLAS and to the Workshop Véronique Garçon 09:50 Surface (energy and water) fluxes at the air1 SOLAS Mid Term Strategy Initiative "Air-sea gas fluxes at Eastern boundary upwelling and Oxygen

197

Global warming impacts of ozone-safe refrigerants and refrigeration, heating, and air-conditioning technologies  

SciTech Connect

International agreements mandate the phase-out of many chlorine containing compounds that are used as the working fluid in refrigeration, air-conditioning, and heating equipment. Many of the chemical compounds that have been proposed, and are being used in place of the class of refrigerants eliminated by the Montreal Protocol are now being questioned because of their possible contributions to global warming. Natural refrigerants are put forth as inherently superior to manufactured refrigerants because they have very low or zero global warming potentials (GWPs). Questions are being raised about whether or not these manufactured refrigerants, primarily hydrofluorocarbons (HFCs), should be regulated and perhaps phased out in much the same manner as CFCs and HCFCs. Several of the major applications of refrigerants are examined in this paper and the results of an analysis of their contributions to greenhouse warming are presented. Supermarket refrigeration is shown to be an application where alternative technologies have the potential to reduce emissions of greenhouse gases (GHG) significantly with no clear advantage to either natural or HFC refrigerants. Mixed results are presented for automobile air conditioners with opportunities to reduce GHG emissions dependent on climate and comfort criteria. GHG emissions for hermetic and factory built systems (i.e. household refrigerators/freezers, unitary equipment, chillers) are shown to be dominated by energy use with much greater potential for reduction through efficiency improvements than by selection of refrigerant. The results for refrigerators also illustrate that hydrocarbon and carbon dioxide blown foam insulation have lower overall effects on GHG emissions than HFC blown foams at the cost of increased energy use.

Fischer, S.; Sand, J.; Baxter, V.

1997-12-01T23:59:59.000Z

198

Meteorological Conditions Dependence of Radon Concentration in the Air above the Atlantic Ocean  

Science Journals Connector (OSTI)

... very likely to happen in June, and, finally, we have connected the concentration of radon and of its descendants to the origin of the air masses, for the air ... If the air comes from the north-west of France or from Great Britain, its radon concentration is always between 10 and 27 pc./m3; the mean speed wind blowing ...

J. FONTAN; D. BLANC; A. BOUVILLE; J. LACAZE

1963-02-09T23:59:59.000Z

199

Indoor air environment and night cooling energy efficiency of a southern German passive public school building operated by the heat recovery air conditioning unit  

Science Journals Connector (OSTI)

Abstract The recently built school building has adopted a novel heat recovery air conditioning system. Heat recovery efficiency of the heat recovery facility and energy conservation ratio of the air conditioning unit were analytically modeled, taking the ventilation networks into account. Following that, school classroom displacement ventilation and its thermal stratification have been numerically investigated concerning the effects of the heat flow flux of passive cooling within the ceiling concrete in the classroom due to night ventilation in summer which could result in cooling energy storage. Numerical results indicate that the promotion of passive cooling can simultaneously decrease the volume averaged indoor temperatures and the non-uniformity of indoor thermal distributions. Subsequent energy performance analysis demonstrates that classroom energy demands for ventilation and cooling could be reduced with the promotion of heat recovery efficiency of the ventilation facility, and the energy conservation ratio of the air-cooling unit decreases with the increasing temperatures of exhaust air and the heat flux value for passive cooling within the classroom ceiling concrete. Fitting correlations of heat recovery ventilation and cooling energy conservation have been presented.

Yang Wang; Fu-Yun Zhao; Jens Kuckelkorn; Xiao-Hong Li; Han-Qing Wang

2014-01-01T23:59:59.000Z

200

Removal of submicron particles using a carbon fiber ionizer-assisted medium air filter in a heating, ventilation, and air-conditioning (HVAC) system  

Science Journals Connector (OSTI)

Laboratory tests of particle removal were performed with a pair of carbon fiber ionizers installed upstream of a glass fiber air filter. For air flow face velocities of 0.4, 0.6, and 0.8m/s, the overall particle removal efficiencies of the filter for all submicron particles were 17%, 16%, and 14%, respectively, when the ionizers were not turned on. These values increased to 27%, 23%, and 19%, respectively, when the ionizers were used to generate ions of 6.0נ109ions/cm3 in concentration. The carbon fiber ionizers were then installed in front of a glass fiber air filter located in a heating, ventilation, and air-conditioning (HVAC) system. Field tests were performed in a test office room with a total indoor particle concentration of 2.2נ104particles/cm3. When the flow rate was 75 cubic meters per hour (CMH), the steady-state values of the total indoor particle concentrations using the glass fiber air filter with and without ionizers decreased to 0.87נ104particles/cm3 and 1.15נ104particles/cm3, respectively, resulting in a 25% decrease of the ionizer effect. When the operation flow rate was increased to 115 and 150CMH, the effect of the ionizer decreased to 19% and 17%, respectively. These experimental data match the results calculated using a mass-balance model whose parameters were determined from laboratory tests.

Jae Hong Park; Ki Young Yoon; Jungho Hwang

2011-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


201

Experimental evaluation of automotive air-conditioning using HFC-134a and HC-134a  

Science Journals Connector (OSTI)

An experimental study to evaluate the energy consumption of an automotive air conditioning is presented. In this study these refrigerants will be tested using the experimental rig which simulated the actual cars as a cabin complete with a cooling system component of the actual car that is as the blower evaporator condenser radiators electric motor which acts as a vehicle engine and then the electric motor will operate the compressor using a belt and pulley system as well as to the alternator will recharge the battery. The compressor working with the fluids HFC-134a and HC-134a and has been tested varying the speed in the range 1000 1500 2000 and 2500 rpm. The measurements taken during the one hour experimental periods at 2-minutes interval times for temperature setpoint of 20C with internal heat loads 0 500 700 and 1000 W. The final results of this study show an overall better energy consumption of the HFC-134a compared with the HC-134a.

Azhar Abdul Aziz

2012-01-01T23:59:59.000Z

202

Relationship between the merit factor of thermoelectric materials and the air conditioning unit of urban electric cars  

SciTech Connect

The main benefit of electric cars is to reduce air pollution in cities that is thus desirable to equip them with non polluting air conditioning units and this rules out frigorific compressors operating with CFC. The planned replacement of CFC by HFC is at best an interim solution. The best solution is certainly to use thermoelectric air conditioning units, which are inherently pollution-free. However, these have a fairly low COPF when compared to traditional compressor units. We study the relationship between the cooling of the interior of urban electric cars and the merit factor of the thermoelectric material in their Peltier unit. This should help provide concrete target properties of future T E materials. {copyright} {ital 1995} {ital American} {ital Institute} {ital of} {ital Physics}.

Buffet, J. [Counsulting Engineer, 2 av. DODE de la BRUNERIE 75016 Paris (France)

1994-08-10T23:59:59.000Z

203

E-Print Network 3.0 - air conditioning committee Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

Committee Meeting Minutes January 16, 2008 Darden 126 Attendees... Transit Service, Maintenance Shop, Operations, Administration, Air and HSCMedical Center. Major Source: Whittle,...

204

E-Print Network 3.0 - air conditioning devices Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

Interaction Institute, Carnegie... cities of the developing world, urban air pollution has worsened, which has been detrimental... to the health of their populations. At...

205

Assessment of adsorber bed designs in waste-heat driven adsorption cooling systems for vehicle air conditioning and refrigeration  

E-Print Network (OSTI)

Assessment of adsorber bed designs in waste-heat driven adsorption cooling systems for vehicle air conditioning Finned tube adsorber bed Specific cooling power Adsorber bed to adsorbent mass ratio a b s t r a c t Adsorber bed design strongly affects the performance of waste-heat driven adsorption cooling systems (ACS

Bahrami, Majid

206

ENSC 461 PROJECT: Next generation air conditioning systems for vehicles Assigned date: Feb. 21, 2011 Due date: April 11, 2011  

E-Print Network (OSTI)

to significant power consumption of vapour-compression systems, finding a new "green" refrigerant is another vehicles (HEVs), as it is the second most energy consuming system after the electric motor. Further, HVAC air conditioning systems used in the automotive industry are based on vapour-compression refrigeration

Bahrami, Majid

207

Une mthode simple de prvision des tempratures de l'air et de la surface du sol en conditions de geles  

E-Print Network (OSTI)

Une méthode simple de prévision des températures de l'air et de la surface du sol en conditions de l'air et du sol, on a tracé des abaques qui expriment le refroidissement en conditions de ciel clair frost conditions. A one-dimensional model of nocturnal change in soil and air temperature has been used

Paris-Sud XI, Université de

208

Influence of Mobile Air-Conditioning on Vehicle Emissions and Fuel Consumption:? A Model Approach for Modern Gasoline Cars Used in Europe  

Science Journals Connector (OSTI)

However, apart from studies involving MOBILE6 in the United States (1) and other U. S. studies (2?5), air-conditioning activity in relation to meteorological conditions has not been thoroughly investigated. ... For manual air conditioners, a good setting was sought before the test and the knobs for cooling and ventilation were readjusted if the temperature drifted more than 1 C. ... The temperatures of the conditioned air range from 5 to 11 C. ...

Martin F. Weilenmann; Ana-Marija Vasic; Peter Stettler; Philippe Novak

2005-11-04T23:59:59.000Z

209

Proposal for the award of a contract for the design, supply, installation and commissioning of an HVAC (Heating, Ventilation and Air Conditioning) system for Building 3862  

E-Print Network (OSTI)

Proposal for the award of a contract for the design, supply, installation and commissioning of an HVAC (Heating, Ventilation and Air Conditioning) system for Building 3862

2014-01-01T23:59:59.000Z

210

2014-06-23 Issuance: Energy Conservation Standards for Walk-in Coolers and Freezers; Air-Conditioning, Heating, & Refrigeration Institute Petition for Reconsideration  

Energy.gov (U.S. Department of Energy (DOE))

This document is the agency response to the Energy Conservation Standards for Walk-in Coolers and Freezers; Air-Conditioning, Heating, & Refrigeration Institute Petition for Reconsideration.

211

Proposal for the award of a contract for the design, supply, installation and commissioning of Heating, Ventilation and Air-Conditioning (HVAC) systems for the PS accelerator infrastructure  

E-Print Network (OSTI)

Proposal for the award of a contract for the design, supply, installation and commissioning of Heating, Ventilation and Air-Conditioning (HVAC) systems for the PS accelerator infrastructure

2012-01-01T23:59:59.000Z

212

Proposal for the award of a contract for dismantling, removal and packaging of the existing Heating, Ventilation and Air-Conditioning (HVAC) systems in the PS tunnel  

E-Print Network (OSTI)

Proposal for the award of a contract for dismantling, removal and packaging of the existing Heating, Ventilation and Air-Conditioning (HVAC) systems in the PS tunnel

2012-01-01T23:59:59.000Z

213

Case Study: The Effective Use of an Extensive Logical rule Based Data Analytics Approach in Establishing Root Cause of Performance Issues in Widespread Deployments of Unitary Space Air Conditioning Units  

E-Print Network (OSTI)

Today a significant percentage of office spaces are air conditioned using widely deployed unitary systems, either Fan Coil Units (FCU) or Variable Air Volume (VAV) boxes, to achieve high degrees of air conditioned zonal control. However establishing...

Brady, N.

2013-01-01T23:59:59.000Z

214

Ductless Mini-Split Air Conditioners | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Ductless Mini-Split Air Conditioners Ductless Mini-Split Air Conditioners Ductless Mini-Split Air Conditioners August 9, 2012 - 4:05pm Addthis A ductless mini-split air conditioner is one solution to cooling part of a house. | Photo courtesy of ©iStockphoto/LUke1138. A ductless mini-split air conditioner is one solution to cooling part of a house. | Photo courtesy of ©iStockphoto/LUke1138. What does this mean for me? A ductless mini-split air conditioner is easier to install than a central air conditioning system. A ductless mini-split air conditioner provides zoned air conditioning without ducting. A ductless mini-split air conditioner is relatively easy to install and does not provide an entry point for intruders as some room air conditioners do. Ductless, mini split-system air-conditioners (mini splits) have numerous

215

Ductless Mini-Split Air Conditioners | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Ductless Mini-Split Air Conditioners Ductless Mini-Split Air Conditioners Ductless Mini-Split Air Conditioners August 9, 2012 - 4:05pm Addthis A ductless mini-split air conditioner is one solution to cooling part of a house. | Photo courtesy of ©iStockphoto/LUke1138. A ductless mini-split air conditioner is one solution to cooling part of a house. | Photo courtesy of ©iStockphoto/LUke1138. What does this mean for me? A ductless mini-split air conditioner is easier to install than a central air conditioning system. A ductless mini-split air conditioner provides zoned air conditioning without ducting. A ductless mini-split air conditioner is relatively easy to install and does not provide an entry point for intruders as some room air conditioners do. Ductless, mini split-system air-conditioners (mini splits) have numerous

216

Energy-Saving Design for Pressure Difference Control in Variable Flow Air Conditioning Systems  

E-Print Network (OSTI)

Zhang Senior Engineer Postgraduate Wuhan Architectural Design Institute, Wuhan, China, 430014 Chenyh918@263.net Abstract: This paper analyzes energy-saving design for pressure-difference control in a variable flow air...

Chen, Y.; Zhang, Z.

2006-01-01T23:59:59.000Z

217

Economic Analysis of a Waste Water Resource Heat Pump Air-Conditioning System in North China  

E-Print Network (OSTI)

This paper describes the situation of waste water resource in north China and the characteristics and styles of a waste water resource heat pump system, and analyzes the economic feasibility of a waste water resource heat pump air...

Chen, H.; Li, D.; Dai, X.

2006-01-01T23:59:59.000Z

218

E-Print Network 3.0 - air-borne dust conditions Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

L., Guo, J., Dan, M., Zhang, W., Wang, Z., and Hao, Z.: The air-borne particulate pollution... Discussions Regional characteristics of spring Asian dust and its impact on...

219

Study of Air Ingress Across the Duct During the Accident Conditions  

SciTech Connect

The goal of this project is to study the fundamental physical phenoena associated with air ingress in very high temperature reactors (VHTRs). Air ingress may occur due to a nupture of primary piping and a subsequent breach in the primary pressure boundary in helium-cooled and graphite-moderated VHTRs. Significant air ingress is a concern because it introduces potential to expose the fuel, graphite support rods, and core to a risk of severe graphite oxidation. Two of the most probable air ingress scenarios involve rupture of a control rod or fuel access standpipe, and rupture in the main coolant pipe on the lower part of the reactor pressure vessel. Therefor, establishing a fundamental understanding of air ingress phenomena is critical in order to rationally evaluate safety of existing VHTRs and develop new designs that mimimize these risks. But despite this importance, progress toward development these predictive capabilities has been slowed by the complex nature of the underlaying phenomena. The combination of interdiffusion among multiple species, molecular diffusion, natural convection, and complex geometries, as well as the multiple chemical reactions involved, impose significant roadblocks to both modeling and experiment design. The project team will employ a coordinated experimental and computational effort that will help gain a deeper understanding of multiphased air ingress phenomena. THis project will enhance advanced modeling and simulation methods, enabling calculation of nuclear power plant transients and accident scenarios with a high degree of confidence. The following are the project tasks: Perform particle image velocimetry measurement of multiphase air ingresses Perform computational fluid dynamics analysis of air ingress phenomena

Hassan, Yassin

2013-05-06T23:59:59.000Z

220

Adaptive HVAC zone modeling for sustainable buildings  

Science Journals Connector (OSTI)

Control of energy flows within a building is critical to achieving optimal performance of heating, ventilation and air-conditioning (HVAC) systems. To design optimal HVAC control strategies, a dynamic model of the HVAC system particularly the building zones that it services is essential. As analysis of building energy consumption is facilitated by the accurate prediction of indoor environmental conditions, techniques that dynamically model HVAC zones are crucial, and as such, is an active area of research. This paper focuses on real-time HVAC zone model fitting and prediction techniques based on physical principles, as well as the use of genetic algorithms for optimization. The proposed approach is validated by comparing real-time HVAC zone model fitting and prediction against the corresponding experimental measurements. In addition, comparison with prediction results using an algorithm based on feedback-delayed Kalman filters has demonstrated the superiority of the proposed approach in terms of prediction accuracy.

Glenn Platt; Jiaming Li; Ronxin Li; Geoff Poulton; Geoff James; Josh Wall

2010-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


221

Combustion and \\{NOx\\} emissions of biomass-derived syngas under various gasification conditions utilizing oxygen-enriched-air and steam  

Science Journals Connector (OSTI)

The purpose of this study is to investigate the \\{NOx\\} emissions from combustion of syngas derived from gasification of three different biomass feedstock (i.e., pine, mapleoak mixture, and seed corn) at different oxygen-enriched-air and steam conditions. Three different oxygen-enriched-air and steam conditions were tested for each feedstock, thus resulting in nine different sets of syngas. The biomass-derived syngas was burned in an industrial burner that was integrated into the gasification system. The gasifier and burner are rated at 800kW and 879kW thermal, respectively. For each set of biomass-derived syngas, \\{NOx\\} emissions were measured at different burner operating conditions including various heat rates and equivalence ratios using emission analyzers with chemiluminescence technology. All the combustion test conditions are in the lean mixture ranges in order to avoid the peak temperature limitation of both the burner and combustion chamber. Results show that \\{NOx\\} emissions using syngas obtained from woody feedstock decrease almost linearly as the combustion mixture becomes leaner and the heat rate decreases. When compared to natural gas, syngas from both woody feedstock generates higher \\{NOx\\} emissions even when the heat rates are comparable, indicating that fuel \\{NOx\\} formation is highly important in biomass-derived syngas combustion. In contrast to syngas from woody feedstock, syngas from seed corn results in peak \\{NOx\\} emissions before \\{NOx\\} decreases with leaner conditions. The trend is observed for all fuel flow rates and all oxygen-enriched-air and steam conditions of seed corn-derived syngas. Among the three feedstock, seed corn has the highest nitrogen content which yields the highest ammonia concentration in syngas, which, in turn, results in the highest \\{NOx\\} emissions for all test conditions. Overall, the \\{NOx\\} emissions from seed corn-derived syngas combustion are approximately in the range of 450900ppm higher compared to those from wood-derived syngas combustion.

Cuong Van Huynh; Song-Charng Kong

2013-01-01T23:59:59.000Z

222

Enhanced Operation Strategies for Air-Conditioning and Lighting Systems Toward Peak Power Reduction for an Office Building in Kuwait  

E-Print Network (OSTI)

Enhanced?Operation?Strategies?for?Air? Conditioning?and?Lighting? Systems?Toward?Peak?Power?Reduction? for?an?Office?Building?in?Kuwait F. Alghimlas A. Al-Mulla G.P. Maheshwari D. Al-Nakib Building and Energy Technologies Department... Environment and Urban Development Division ICEBO 2012 Manchester, United Kingdom October 23-26, 2012 Electricity?Use?by?Sector?in?Kuwait Percentages?of?Primary?Energy?Utilization Percentages?of?Electricity?Utilization Yearly?Increase?in...

Alghimlas, F.; Al-Mulla, A.; Maheshwari, G.P.; Al-Nakib, D.

2012-01-01T23:59:59.000Z

223

Performance and evaluation of gas-engine-driven rooftop air conditioning equipment at the Willow Grove Naval Air Station. Final report (revised October 21, 1996)  

SciTech Connect

The performance was evaluated of a new US cooling technology that has been installed for the first time at a federal facility. The technology is a 15-ton natural gas-engine-driven rooftop air conditioning unit made by Thermo King. Two units were installed to serve the Navy Exchange at Willow Grove. The savings potential at Willow Grove is described and that in the federal sector estimated. Conditions for implementation are discussed. In summary, the new technology is generally cost-effective at sites where marginal electricity cost (per MBtu at the meter) is more than 4 times the marginal gas cost (per MBtu at the meter) and annual full-load-equivalent cooling hours exceed 2,000.

Armstrong, P.R.; Katipamula, S.

1996-10-01T23:59:59.000Z

224

Influence of Fault and Optimization of PID Parameters in Building Air-Conditioning System  

E-Print Network (OSTI)

200 400 600 800 0 200 400 600 800 8 10 12 14 16 18 Supply air flow volume A ir flo w v ol um e[ m 3 / h] A ir flo w v ol um e[ m 3 / h] (b)Supply air flow volume Time[hour] 0 10 20 0.6 0.8 1 1.2 1....4 18161412108 Time[hour] Secondary inlet water temp. Secondary outlet water temp. Secondary pump water flow volume w at er fl ow v ol um e[ m 3 / h] Te m p. [d eg .C ] (d)Secondary inlet & outlet water temp. / water flow volume 10...

Kuniyoshi, K.; Akashi, Y.; Sumiyoshi, D.; Song, Y.

2005-01-01T23:59:59.000Z

225

Initial phase zone for phase locking to the resonance, using main condition of phase stability in DC-biased single-sided multipactor  

SciTech Connect

In the present work, the concept of accurate phase stability is employed to study a DC-biased single-sided multipactor. A main condition of phase stability was introduced in our previous studies of two-sided multipactors [M. Mostajeran, J. Instrum. 8, P04024 (2013); M. Mostajeran and M. Lamehi Rachti, Nucl. Instrum. Methods Phys. Res. A 615, 15 (2010)]. Using the same condition and assuming zero initial velocity for the secondary electrons, a regime of multipactors outside the resonance zones is found. The theoretical results are then verified by numerical simulation.

Mostajeran, M., E-mail: mostajeran@yazd.ac.ir [Faculty of Physics, Yazd University, P.O. Box 89195-741, Yazd (Iran, Islamic Republic of)

2014-05-15T23:59:59.000Z

226

Combustion of single biomass particles in air and in oxy-fuel conditions  

Science Journals Connector (OSTI)

Abstract The combustion behaviors of four different pulverized biomasses were evaluated in the laboratory. Single particles of sugarcane bagasse, pine sawdust, torrefied pine sawdust and olive residue were burned in a drop-tube furnace, set at 1400K, in both air and O2/CO2 atmospheres containing 21, 30, 35, and 50% oxygen mole fractions. High-speed and high-resolution images of single particles were recorded cinematographically and temperaturetime histories were obtained pyrometrically. Combustion of these particles took place in two phases. Initially, volatiles evolved and burned in spherical envelope flames of low-luminosity; then, upon extinction of these flames, char residues ignited and burned in brief periods of time. This behavior was shared by all four biomasses of this study, and only small differences among them were evident based on their origin, type and pre-treatment. Volatile flames of biomass particles were much less sooty than those of previously burned coal particles of analogous size and char combustion durations were briefer. Replacing the background N2 gas with CO2, i.e., changing from air to an oxy-fuel atmosphere, at 21% O2 impaired the intensity of combustion; reduced the combustion temperatures and lengthened the burnout times of the biomass particles. Increasing the oxygen mole fraction in CO2 to 2835% restored the combustion intensity of the single biomass particles to that in air.

Juan Riaza; Reza Khatami; Yiannis A. Levendis; Luca lvarez; Mara V. Gil; Covadonga Pevida; Fernando Rubiera; Jos J. Pis

2014-01-01T23:59:59.000Z

227

E-Print Network 3.0 - air-conditioning systemsfor occupant Sample...  

NLE Websites -- All DOE Office Websites (Extended Search)

University Collection: Biology and Medicine 3 Introduction Prior research has shown that energy savings are Summary: conditions for human occupancy. American Society of Heating,...

228

Memorandum To: GENERAL COUNSEL, DEPARTMENT OF ENERGY (DOE) From: JONATHAN MELCHI, HEATING, AIR-CONDITIONING AND REFRIGERATION  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

To: GENERAL COUNSEL, DEPARTMENT OF ENERGY (DOE) To: GENERAL COUNSEL, DEPARTMENT OF ENERGY (DOE) From: JONATHAN MELCHI, HEATING, AIR-CONDITIONING AND REFRIGERATION DISTRIBUTORS INTERNATIONAL (HARDI) Date: 1/12/2012 Subject: EX PARTE COMMUNICATION MEMO DOE ATTENDEES: Ashley Armstrong, John Cymbalsky, David Case, Laura Barhydt HARDI ATTENDEES: Talbot Gee, Jonathan Melchi AREAS OF DISCUSSION: DOE Framework Document and Stakeholder Meeting regarding the Enforcement of the updated Energy Conservation Standards for Air Conditioners, Furnaces and Heat Pumps. The meeting took place on Thursday January 5 th , 2012 from 2pm to 3-pm. The following topics were discussed. 1.) Sell-Through. HARDI asked for clarification on the DOE's notation on the Framework Document

229

23.11.2014bo Akademi Univ -Thermal and Flow Engineering Piispankatu 8, 20500 Turku 1/36 7. Air conditioning, cooling towers  

E-Print Network (OSTI)

23.11.2014?bo Akademi Univ - Thermal and Flow Engineering Piispankatu 8, 20500 Turku 1/36 7. Air conditioning, cooling towers Ron Zevenhoven ?bo Akademi University Thermal and Flow Engineering Laboratory Engineering Piispankatu 8, 20500 Turku 2/36 7.1 Humid air #12;23.11.2014 ?bo Akademi Univ - Thermal and Flow

Zevenhoven, Ron

230

Energy and economic performance analysis of an open cycle solar desiccant dehumidification air-conditioning system for application in Hong Kong  

Science Journals Connector (OSTI)

In this article, a transient simulation model and the EnergyPlus were used to study the energy performance and economical feasibility for integrating a solar liquid desiccant dehumidification system with a conventional vapor compression air-conditioning system for the weather condition of Hong Kong. The vapor compression system capacity in the solar assisted air-conditioning system can be reduced to 19kW from original 28kW of a conventional air-conditioning system as a case study due to the solar desiccant cooling. The economical performance of the solar desiccant dehumidification system is compared with that of the conventional air-conditioning system. The results show that the energy saving potentials due to incorporation of the solar desiccant dehumidification system in a traditional air-conditioning system is significant for the hot wet weather in Hong Kong due to higher COP resulted from higher supply chilled water temperature from chiller plants. The annual operation energy savings for the hybrid system is 6760kWh and the payback period of the hybrid system is around 7years. The study shows that the solar assisted air-conditioning is a viable technology for utilizations in subtropical areas.

Yutong Li; Lin Lu; Hongxing Yang

2010-01-01T23:59:59.000Z

231

Heating, Ventilation, and Air Conditioning Design Strategy for a Hot-Humid Production Builder  

SciTech Connect

BSC worked directly with the David Weekley Homes - Houston division to redesign three floor plans in order to locate the HVAC system in conditioned space. The purpose of this project is to develop a cost effective design for moving the HVAC system into conditioned space. In addition, BSC conducted energy analysis to calculate the most economical strategy for increasing the energy performance of future production houses. This is in preparation for the upcoming code changes in 2015. The builder wishes to develop an upgrade package that will allow for a seamless transition to the new code mandate. The following research questions were addressed by this research project: 1. What is the most cost effective, best performing and most easily replicable method of locating ducts inside conditioned space for a hot-humid production home builder that constructs one and two story single family detached residences? 2. What is a cost effective and practical method of achieving 50% source energy savings vs. the 2006 International Energy Conservation Code for a hot-humid production builder? 3. How accurate are the pre-construction whole house cost estimates compared to confirmed post construction actual cost? BSC and the builder developed a duct design strategy that employs a system of dropped ceilings and attic coffers for moving the ductwork from the vented attic to conditioned space. The furnace has been moved to either a mechanical closet in the conditioned living space or a coffered space in the attic.

Kerrigan, P.

2014-03-01T23:59:59.000Z

232

US Department of Energys Regulatory Negotiations Convening on Commercial Certification for Heating, Ventilating, Air-Conditioning, and Refrigeration Equipment  

Energy.gov (U.S. Department of Energy (DOE))

This document provides Public Information for Convening Interviews for US Department of Energys Regulatory Negotiations Convening on Commercial Certification for Heating, Ventilating, Air-Conditioning, and Refrigeration Equipment

233

The Technical and Economical Analysis of a Centralized Air-Conditioning System with Cold Storage Refrigeration in High-Rise Residential Buildings  

E-Print Network (OSTI)

In recent years, the application of a centralized air-conditioning system (CACS) with cold storage refrigeration in high-rise residential buildings has gradually increased. Due to the large difference between civil residential buildings...

Xiang, C.; Xie, G.

2006-01-01T23:59:59.000Z

234

Using Hydrated Salt Phase Change Materials for Residential Air Conditioning Peak Demand Reduction and Energy Conservation in Coastal and Transitional Climates in the State of California  

E-Print Network (OSTI)

The recent rapid economic and population growth in the State of California have led to a significant increase in air conditioning use, especially in areas of the State with coastal and transitional climates. This fact makes ...

Lee, Kyoung Ok

2013-05-31T23:59:59.000Z

235

Impact of Charge Degradation on the Life Cycle Climate Performance of a Residential Air-Conditioning System  

SciTech Connect

Vapor compression systems continuously leak a small fraction of their refrigerant charge to the environment, whether during operation or servicing. As a result of the slow leak rate occurring during operation, the refrigerant charge decreases until the system is serviced and recharged. This charge degradation, after a certain limit, begins to have a detrimental effect on system capacity, energy consumption, and coefficient of performance (COP). This paper presents a literature review and a summary of previous experimental work on the effect of undercharging or charge degradation of different vapor compression systems, especially those without a receiver. These systems include residential air conditioning and heat pump systems utilizing different components and refrigerants, and water chiller systems. Most of these studies show similar trends for the effect of charge degradation on system performance. However, it is found that although much experimental work exists on the effect of charge degradation on system performance, no correlation or comparison between charge degradation and system performance yet exists. Thus, based on the literature review, three different correlations that characterize the effect of charge on system capacity and energy consumption are developed for different systems as follows: one for air-conditioning systems, one for vapor compression water-to-water chiller systems, and one for heat pumps. These correlations can be implemented in vapor compression cycle simulation tools to obtain a better prediction of the system performance throughout its lifetime. In this paper, these correlations are implemented in an open source tool for life cycle climate performance (LCCP) based design of vapor compression systems. The LCCP of a residential air-source heat pump is evaluated using the tool and the effect of charge degradation on the results is studied. The heat pump is simulated using a validated component-based vapor compression system model and the LCCP results obtained using the three charge degradation correlations are compared.

Beshr, Mohamed [University of Maryland, College Park; Aute, Vikrant [University of Maryland, College Park; Abdelaziz, Omar [ORNL; Fricke, Brian A [ORNL; Radermacher, Reinhard [University of Maryland, College Park

2014-01-01T23:59:59.000Z

236

Japanese and American competition in the development of scroll compressors and its impact on the American air conditioning industry  

SciTech Connect

This report examines the technological development of scroll compressors and its impact on the air conditioning equipment industry. Scroll compressors, although considered to be the compressors of the future for energy-efficient residential heat pumps and possibly for many other applications, are difficult to manufacture on a volume-production base. The manufacturing process requires computer-aided, numerically controlled tools for high-precision fabrication of major parts. Japan implemented a global strategy for dominating the technological world market in the 1970s, and scroll compressor technology benefited from the advent of new-generation machine tools. As a result, if American manufacturers of scroll compressors purchase or are essentially forced to purchase numerically controlled tools from Japan in the future, they will then become dependent on their own competitors because the same Japanese conglomerates that make numerically controlled tools also make scroll compressors. This study illustrates the importance of the basic machine tool industry to the health of the US economy. Without a strong machine tool industry, it is difficult for American manufacturers to put innovations, whether patented or not, into production. As we experience transformation in the air conditioning and refrigeration market, it will be critical to establish a consistent national policy to provide healthy competition among producers, to promote innovation within the industry, to enhance assimilation of new technology, and to eliminate practices that are incompatible with these goals. 72 refs., 8 figs., 1 tab.

Ushimaru, Kenji (Energy International, Inc., Bellevue, WA (USA))

1990-02-01T23:59:59.000Z

237

Development of cold seawater air conditioning systems for application as a demand side management tool for Hawaii and other subtropical climates  

SciTech Connect

Because of the proximity to deep cold seawater for many coastal regions in Hawaii and the high demand for air conditioning in large buildings, seawater air conditioning (SWAC) is a major potential sustainable energy resource for Hawaii and other subtropical regions of the world. The basic concept of seawater air conditioning is the use deep cold seawater to cool the chilled water in one or more air conditioned buildings as opposed to using energy intensive refrigeration systems. The economic viability of the seawater air conditioning is determined by comparing the construction and operating costs of the seawater supply system to the construction and operating costs of conventional air conditioning systems. The State of Hawaii commissioned an analysis to identify the technical and economic opportunities and limitations in the use of SWAC in Hawaii. The result of this work is a feasibility analysis of SWAC systems in the state and the potential associated energy savings. The study looked at the prospects of installing such a system at a major new resort development on Oahu called West Beach.

Kaya, M.H. [State of Hawaii, Honolulu, HI (United States). Dept. of Business, Economic Development, and Tourism

1996-10-01T23:59:59.000Z

238

Modeling ground thermal conditions and the limit of permafrost within the nearshore zone of the Mackenzie Delta, Canada  

E-Print Network (OSTI)

the duration of time ice is bottomfast and the thermal insulation of the overlying snowpack [Stevens et al examines the interrelated effects of snow and ice on ground thermal conditions beneath regions of shallow ice that ranged from 10 cm to 100 cm thick, with intrasite variability as much as 4.7°C. Measured

Moorman, Brian

239

Estimated 2017 Refrigerant Emissions of 2,3,3,3-tetrafluoropropene (HFC-1234yf) in the United States Resulting from Automobile Air Conditioning  

Science Journals Connector (OSTI)

The use of MAC systems also consumes significant quantities of fuel as compared to similar driving conditions without operating the air conditioning. ... However, turning off the air conditioner and rolling-down the windows also decreases fuel economy due to increased air drag but this scenario is not considered in these studies (1, 2). ... In 2006, the European Commission issued Directive 2006/40/EC (commonly known as the F-Gas Directive) (3), which requires new types of air-conditioned cars sold in the EU to have a refrigerant with a GWP of 150 or less starting in 2011, and all new vehicles to have a refrigerant with a GWP of 150 or less by 2017. ...

Stella Papasavva; Deborah J. Luecken; Robert L. Waterland; Kristen N. Taddonio; Stephen O. Andersen

2009-11-12T23:59:59.000Z

240

Experimental and kinetic study of autoignition in methane/ethane/air and methane/propane/air mixtures under engine-relevant conditions  

SciTech Connect

The ignition delay of homogeneous methane/air mixtures enriched with small fractions of ethane/propane was measured using the reflected-shock technique at temperatures from 900 to 1400 K and pressures from 16 to 40 bar. The results show complex effects of ethane/propane on the ignition of methane, but a common trend observed with both hydrocarbons is an increased promotion effect for temperatures below 1100 K. A detailed kinetic mechanism was used to investigate the interaction between ethane/propane and the ignition chemistry of methane under the above conditions. It was found that at relatively low temperatures, the reactions between ethane/propane and methylperoxy (CH{sub 3}O{sub 2}) lead to an enhanced rate of formation of OH radicals in the initiation phase of the ignition. By systematically applying the quasi-steady-state assumptions to the intermediate species involved in the main reaction path identified, we have achieved an analytical description of the ignition process in the transitional temperature regime. The analytical solutions agree reasonably well with the detailed kinetic model and the experimental results for both ignition delay and concentrations of major intermediate species.

Huang, J.; Bushe, W.K. [Department of Mechanical Engineering, University of British Columbia, 6950 Applied Science Lane, Vancouver, British Columbia (Canada V6T 1Z4)

2006-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


241

Safety Assessment for a Surface Repository in the Chernobyl Exclusion Zone - Methodology for Assessing Disposal under Intervention Conditions - 13476  

SciTech Connect

The Radioactive Waste Disposal Facility (RWDF) Buryakovka was constructed in 1986 as part of the intervention measures after the accident at Chernobyl NPP (ChNPP). Today, RWDF Buryakovka is still being operated but its maximum capacity is nearly reached. Plans for enlargement of the facility exist since more than 10 years but have not been implemented yet. In the framework of an European Commission Project DBE Technology GmbH prepared a safety analysis report of the facility in its current state (SAR) and a preliminary safety analysis report (PSAR) based on the planned enlargement. Due to its history RWDF Buryakovka does not fully comply with today's best international practices and the latest Ukrainian regulations in this area. The most critical aspects are its inventory of long-lived radionuclides, and the non-existent multi-barrier waste confinement system. A significant part of the project was dedicated, therefore, to the development of a methodology for the safety assessment taking into consideration the facility's special situation and to reach an agreement with all stakeholders involved in the later review and approval procedure of the safety analysis reports. Main aspect of the agreed methodology was to analyze the safety, not strictly based on regulatory requirements but on the assessment of the actual situation of the facility including its location within the Exclusion Zone. For both safety analysis reports, SAR and PSAR, the assessment of the long-term safety led to results that were either within regulatory limits or within the limits allowing for a specific situational evaluation by the regulator. (authors)

Haverkamp, B.; Krone, J. [DBE TECHNOLOGY GmbH, Eschenstr. 55, D-31224 Peine (Germany)] [DBE TECHNOLOGY GmbH, Eschenstr. 55, D-31224 Peine (Germany); Shybetskyi, I. [Radioenvironmental Centre at Presidium of National Academy of Sciences of Ukraine, Ul. O. Gonchara 55 b, 01054 Kiev (Ukraine)] [Radioenvironmental Centre at Presidium of National Academy of Sciences of Ukraine, Ul. O. Gonchara 55 b, 01054 Kiev (Ukraine)

2013-07-01T23:59:59.000Z

242

Drag coefficient for the air-sea exchange: foam impact in hurricane conditions  

E-Print Network (OSTI)

A physical model is proposed for the estimation of the foam impact on the variation of the effective drag coefficient, C_d, with reference to the wind speed U10 in stormy and hurricane conditions. In the present model C_d is approximated by partitioning the sea surface into foam-covered and foam-free areas. Based on the available optical and radiometric measurements of the fractional foam coverage and the characteristic roughness of the sea-surface in the saturation limit of the foam coverage, the model yields the resulting dependence of C_d vs U10. This dependence is in fair agreement with that evaluated from field measurements of the vertical variation of the mean wind speed.

Golbraikh, Ephim

2014-01-01T23:59:59.000Z

243

Solutions for Summer Electric Power Shortages: Demand Response and its Applications in Air Conditioning and Refrigerating Systems  

E-Print Network (OSTI)

for DR and demand side management, along with operationalresponse), DSM (demand side management), DR strategy, air

Han, Junqiao; Piette, Mary Ann

2008-01-01T23:59:59.000Z

244

Comment submitted by the Air Conditioning, Heating and Refrigeration Institute (AHRI) regarding the Energy Star Verification Testing Program  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

AHRI Comments - DOE Verification Testing in Support of Energy Star AHRI Comments - DOE Verification Testing in Support of Energy Star May 9, 2011 P a g e | 1 May 9, 2010 Ms. Ashley Armstrong U.S. Department of Energy 1000 Independence Avenue, SW Washington, DC 20585 RE: DOE Verification Testing in Support of Energy Star Dear Ms. Armstrong: I am writing on behalf of the Air Conditioning, Heating and Refrigeration Institute (AHRI) to address the proposed DOE requirements for verification testing in support of the Energy Star program. AHRI is the trade association representing manufacturers of heating, cooling, and commercial refrigeration equipment. More than 300 members strong, AHRI is an internationally recognized advocate for the industry, and develops standards for and certifies the performance of many of the

245

Uncertainty of sound power levels determined following Air Conditioning Heating and Refrigeration Institute Standard 220  

Science Journals Connector (OSTI)

As part of the AHRI ASA-ANSI and ISO standards development processes the uncertainty of sound power measurements needs to be quantified for inclusion in sound power standards. A study of four reverberation rooms with volumes of 140 280 560 and 1790 cubic meters was undertaken. Sound power levels for five noise sources (two vertical shafted sound sources two horizontal shafted sound sources and a leaf blower) were determined using ARI Standard 220. Variables investigated include: source location source orientation room conditions source operating characteristics and microphone traverse length. The frequency range of interest was 25 Hz to 10 kHz. Measurements were repeated and the order of tests was randomized. Of particular interest was the difference between the 140 cubic foot room and the other rooms to confirm the room qualification process required by ARI Standard 220 because the 140 cubic foot room does not meet the ARI Standard 220 qualification process but does meet the requirements in ISO 3741. This work will be helpful in understanding the sources of variation and allow for a starting point for determining if improvements are needed and if so what factors should be considered.

2010-01-01T23:59:59.000Z

246

Copper contamination effects on hydrogen-air combustion under SCRAMJET (supersonic combustion ramjet) testing conditions  

SciTech Connect

Two forms of copper catalytic reactions (homogeneous and heterogeneous) in hydrogen flames were found in a literature survey. Hydrogen atoms in flames recombine into hydrogen molecules through catalytic reactions, and these reactions which affect the timing of the combustion process. Simulations of hydrogen flames with copper contamination were conducted by using a modified general chemical kinetics program (GCKP). Results show that reaction times of hydrogen flames are shortened by copper catalytic reactions, but ignition times are relatively insensitive to the reactions. The reduction of reaction time depends on the copper concentration, copper phase, particle size (if copper is in the condensed phase), and initial temperature and pressure. The higher the copper concentration of the smaller the particle, the larger the reduction in reaction time. For a supersonic hydrogen flame (Mach number = 4.4) contaminated with 200 ppm of gaseous copper species, the calculated reaction times are reduced by about 9%. Similar reductions in reaction time are also computed for heterogeneous copper contamination. Under scramjet testing conditions, the change of combustion timing appears to be tolerable (less than 5%) if the Mach number is lower than 3 or the copper contamination is less than 100 ppm. The higher rate the Mach number, the longer the reaction time and the larger the copper catalytic effects. 7 tabs., 8 figs., 34 refs.

Chang, S.L.; Lottes, S.A.; Berry, G.F.

1990-01-01T23:59:59.000Z

247

NRELs Energy-Saving Technology for Air Conditioning Cuts Peak Power Loads Without Using Harmful Refrigerants (Fact Sheet), NREL (National Renewable Energy Laboratory)  

NLE Websites -- All DOE Office Websites (Extended Search)

DEVAP Slashes Peak Power Loads DEVAP Slashes Peak Power Loads Desiccant-enhanced evaporative (DEVAP) air-condi- tioning will provide superior comfort for commercial buildings in any climate at a small fraction of the elec- tricity costs of conventional air-conditioning equip- ment, releasing far less carbon dioxide and cutting costly peak electrical demand by an estimated 80%. Air conditioning currently consumes about 15% of the electricity generated in the United States and is a major contributor to peak electrical demand on hot summer days, which can lead to escalating power costs, brownouts, and rolling blackouts. DEVAP employs an innovative combination of air-cooling technologies to reduce energy use by up to 81%. DEVAP also shifts most of the energy needs to thermal energy sources, reducing annual electricity use by up

248

Thermal and air quality acceptability in buildings that reduce energy by reducing minimun airflow from overhead diffusers  

E-Print Network (OSTI)

assessments of indoor air-quality in five European122 D. Perceived air quality vs. binned zone air126 E. Perceived air quality vs. binned discharge air

2012-01-01T23:59:59.000Z

249

Analysis and experimental study on formation conditions of large-scale barrier-free diffuse atmospheric pressure air plasmas in repetitive pulse mode  

SciTech Connect

Atmospheric air diffuse plasmas have enormous application potential in various fields of science and technology. Without dielectric barrier, generating large-scale air diffuse plasmas is always a challenging issue. This paper discusses and analyses the formation mechanism of cold homogenous plasma. It is proposed that generating stable diffuse atmospheric plasmas in open air should meet the three conditions: high transient power with low average power, excitation in low average E-field with locally high E-field region, and multiple overlapping electron avalanches. Accordingly, an experimental configuration of generating large-scale barrier-free diffuse air plasmas is designed. Based on runaway electron theory, a low duty-ratio, high voltage repetitive nanosecond pulse generator is chosen as a discharge excitation source. Using the wire-electrodes with small curvature radius, the gaps with highly non-uniform E-field are structured. Experimental results show that the volume-scaleable, barrier-free, homogeneous air non-thermal plasmas have been obtained between the gap spacing with the copper-wire electrodes. The area of air cold plasmas has been up to hundreds of square centimeters. The proposed formation conditions of large-scale barrier-free diffuse air plasmas are proved to be reasonable and feasible.

Li, Lee, E-mail: leeli@mail.hust.edu.cn; Liu, Lun; Liu, Yun-Long; Bin, Yu; Ge, Ya-Feng; Lin, Fo-Chang [State Key Laboratory of Advanced Electromagnetic Engineering and Technology, School of Electric and Electronic Engineering, HuaZhong University of Science and Technology (HUST), Wuhan 430074 (China)

2014-01-14T23:59:59.000Z

250

Energy Performance Evaluation and Development of Control Strategies for the Air-conditioning System of a Building at Construction Stage  

E-Print Network (OSTI)

. These control strategies mainly involve optimal chiller sequencing control, cooling tower sequencing control, optimal water pressure differential set-point control, AHU supply air static pressure reset control and DCV-based fresh air control, etc. To assess...

Wang, S.; Xu, X.; Ma, Z.

2006-01-01T23:59:59.000Z

251

Deemed Savings Estimates for Legacy Air Conditioning and WaterHeating Direct Load Control Programs in PJM Region  

SciTech Connect

During 2005 and 2006, the PJM Interconnection (PJM) Load Analysis Subcommittee (LAS) examined ways to reduce the costs and improve the effectiveness of its existing measurement and verification (M&V) protocols for Direct Load Control (DLC) programs. The current M&V protocol requires that a PURPA-compliant Load Research study be conducted every five years for each Load-Serving Entity (LSE). The current M&V protocol is expensive to implement and administer particularly for mature load control programs, some of which are marginally cost-effective. There was growing evidence that some LSEs were mothballing or dropping their DLC programs in lieu of incurring the expense associated with the M&V. This project had several objectives: (1) examine the potential for developing deemed savings estimates acceptable to PJM for legacy air conditioning and water heating DLC programs, and (2) explore the development of a collaborative, regional, consensus-based approach for conducting monitoring and verification of load reductions for emerging load management technologies for customers that do not have interval metering capability.

Goldman, Charles

2007-03-01T23:59:59.000Z

252

Distribution of small dispersive coal dust particles and absorbed radioactive chemical elements in conditions of forced acoustic resonance in iodine air filter at nuclear power plant  

E-Print Network (OSTI)

The physical features of distribution of the small dispersive coal dust particles and the adsorbed radioactive chemical elements and their isotopes in the absorber with the granular filtering medium with the cylindrical coal granules were researched in the case of the intensive air dust aerosol stream flow through the iodine air filter (IAF). It was shown that, at the certain aerodynamic conditions in the IAF, the generation of the acoustic oscillations is possible. It was found that the acoustic oscillations generation results in an appearance of the standing acoustic waves of the air pressure (density) in the IAF. In the case of the intensive blow of the air dust aerosol, it was demonstrated that the standing acoustic waves have some strong influences on both: 1) the dynamics of small dispersive coal dust particles movement and their accumulation in the IAF; 2) the oversaturation of the cylindrical coal granules by the adsorbed radioactive chemical elements and their isotopes in the regions, where the antin...

Ledenyov, Oleg P

2013-01-01T23:59:59.000Z

253

Air Conditioning Cold/Heat Source Analysis of the Inclusion of the Monetary Values of Environmental Damage Based on the LCA Theory  

E-Print Network (OSTI)

of Life Cycle Assessment (LCA) and Willingness - to - pay (WTP). The analysis makes it possible to compare the technical and eco-nomic differences of the air conditioning system based on business economics to a system with greater empha-sis on socio...

Li, Z.; Duanmu, L.; Shu, H.; Zhu, Y.

2006-01-01T23:59:59.000Z

254

2014-02-07 Issuance: Certification of Commercial Heating, Ventilation, and Air-conditioning, Water Heating, and Refrigeration Equipment; Notice of Proposed Rulemaking  

Energy.gov (U.S. Department of Energy (DOE))

This document is a pre-publication Federal Register notice of proposed rulemaking regarding certification of commercial heating, ventilation, and air-conditioning, water-heating, and refrigeration equipment, as issued by the Deputy Assistant Secretary for Energy Efficiency on February 7, 2014.

255

2014-11-25 Issuance: Energy Conservation Standards for Small, Large, and Very Large Air-cooled Commercial Package Air Conditioning and Heating Equipment; Extension of Public Comment Period  

Energy.gov (U.S. Department of Energy (DOE))

This document is a pre-publication Federal Register extension of the public comment period regarding energy conservation standards for small, large and very large air-cool commercial package air conditioning and heating equipment, as issued by the Deputy Assistant Secretary for Energy Efficiency on November 25, 2014. Though it is not intended or expected, should any discrepancy occur between the document posted here and the document published in the Federal Register, the Federal Register publication controls. This document is being made available through the Internet solely as a means to facilitate the public's access to this document.

256

2014-09-18 Issuance: Energy Conservation Standard for Small, Large, and Very Large Air-Cooled Commercial Package Air Conditioning and Heating Equipment; Notice of Proposed Rulemaking and Public Meeting  

Energy.gov (U.S. Department of Energy (DOE))

This document is a pre-publication Federal Register Notice of Proposed Rulemaking and Public Meeting regarding Energy Conservation Standards for Small, large, and Very Large Air-Cooled Commercial Package Air Conditioning and Heating Equipment, as issued by the Assistant Secretary for Energy Efficiency and Renewable Energy on September 18, 2014. Though it is not intended or expected, should any discrepancy occur between the document posted here and the document published in the Federal Register, the Federal Register publication controls. This document is being made available through the Internet solely as a means to facilitate the public's access to this document.

257

METHOD FOR SIMULTANEOUS 90SR AND 137CS IN-VIVO MEASUREMENTS OF SMALL ANIMALS AND OTHER ENVIRONMENTAL MEDIA DEVELOPED FOR THE CONDITIONS OF THE CHERNOBYL EXCLUSION ZONE  

SciTech Connect

To perform in vivo simultaneous measurements of the {sup 90}Sr and {sup 137}Cs content in the bodies of animals living in the Chernobyl Exclusion Zone (ChEZ), an appropriate method and equipment were developed and installed in a mobile gamma beta spectrometry laboratory. This technique was designed for animals of relatively small sizes (up to 50 g). The {sup 90}Sr content is measured by a beta spectrometer with a 0.1 mm thick scintillation plastic detector. The spectrum processing takes into account the fact that the measured object is 'thick-layered' and contains a comparable quantity of {sup 137}Cs, which is a characteristic condition of the ChEZ. The {sup 137}Cs content is measured by a NaI scintillation detector that is part of the combined gamma beta spectrometry system. For environmental research performed in the ChEZ, the advantages of this method and equipment (rapid measurements, capability to measure live animals directly in their habitat, and the capability of simultaneous {sup 90}Sr and {sup 137}Cs measurements) far outweigh the existing limitations (considerations must be made for background radiation and the animal size, skeletal shape and body mass). The accuracy of these in vivo measurements is shown to be consistent with standard spectrometric and radiochemical methods. Apart from the in vivo measurements, the proposed methodology, after a very simple upgrade that is also described in the article, works even more accurately with samples of other media, such as soil and plants.

Farfan, E.; Jannik, T.

2011-10-01T23:59:59.000Z

258

ISSUANCE 2014-12-23: Energy Conservation Program for Certain Industrial Equipment: Energy Conservation Standards and Test Procedures for Commercial Heating, Air-Conditioning, and Water-Heating Equipment, Notice of Proposed Rulemaking  

Energy.gov (U.S. Department of Energy (DOE))

Energy Conservation Program for Certain Industrial Equipment: Energy Conservation Standards and Test Procedures for Commercial Heating, Air-Conditioning, and Water-Heating Equipment, Notice of Proposed Rulemaking

259

Energy consumption and optimization of internally cooled/heated liquid desiccant air-conditioning system: A case study in Hong Kong  

Science Journals Connector (OSTI)

Abstract LDAC (liquid desiccant air-conditioning system) is promising for reducing the energy consumption, and improving the indoor air quality. In this paper, the operation performance of LDAC with internally cooled/heated dehumidifier/regenerator was simulated and optimized. The cooling tower and solar collectors were employed as the cooling/heating source. Four nested iteration loops were developed and solved for system modeling. A typical commercial building in Hong Kong was selected as a case study, which air-conditioning load was obtained by Energy-plus. Results show that with the increase of solar collector area, the electricity consumption of AC (air-conditioning systems) system reduced by 1135% in original system, but only a part of dehumidification demand was handled with liquid desiccant ventilation, which led to a low chiller COP (coefficient of performance). By adding a cooling coil for the solution entering dehumidifier, the electricity saving effectively increased to 2247%, while the heat demand for regeneration also increased by 17%. So, a heat exchanger between water leaving regenerator and solution leaving dehumidifier was introduced. With the lower thermal requirement (reduced by 20%) and higher solar fraction (increased from 30 to 40%), the saving further increased to 2949%, and the required collector area obviously reduced by 5060% for the similar energy saving purpose.

Ronghui Qi; Lin Lu

2014-01-01T23:59:59.000Z

260

Energy Consumption Simulation and Analysis of Heat Pump Air Conditioning System in Wuhan by the BIN Method  

E-Print Network (OSTI)

to simulate the annual energy consumption of groundwater heat pump systems (GWHPS) for an office building in Wuhan. Its annual energy consumption was obtained and compared with the partner of the air source heat pump systems (ASHPS). The results show...

Wen, Y.; Zhao, F.

2006-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


261

DOE/EA-1673: Environmental Assessment for Energy Conservation Program for Certain Industrial Equipment: Energy Conservation Standards and Test Procedures for Commercial Heating, Air-Conditioning, and Water-Heating Equipment (July 2009)  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

3 3 Environmental Assessment for 10 CFR 431 Energy Conservation Program for Certain Industrial Equipment: Energy Conservation Standards and Test Procedures for Commercial Heating, Air- Conditioning, and Water-Heating Equipment July 2009 8-i CHAPTER 8. ENVIRONMENTAL ASSESSMENT TABLE OF CONTENTS 8.1 INTRODUCTION ............................................................................................................... 8-1 8.2 AIR QUALITY ANALYSIS ............................................................................................... 8-1 8.3 AIR POLLUTANT DESCRIPTIONS ................................................................................ 8-1 8.4 AIR QUALITY REGULATIONS ...................................................................................... 8-3

262

RoomZoner: Occupancy-based Room-Level Zoning of a Centralized HVAC System  

E-Print Network (OSTI)

RoomZoner: Occupancy-based Room-Level Zoning of a Centralized HVAC System Tamim Sookoor & Kamin. In this paper we present a CPS that enables a centralized Heating, Ventila- tion, and Air Conditioning (HVAC application due to residential HVAC systems ac- counting for over 15% of all U.S. energy usage, making it one

Whitehouse, Kamin

263

Investigation and Analysis of Energy Consumption and Cost of Electric Air Conditioning Systems in Civil Buildings in Changsha  

E-Print Network (OSTI)

based on the electric refrigeration. Among the heat sources, the prospect of gas boilers is better. In addition, the air source heat pump depends heavily on whether some crucial issues such as frost can be solved during its application. The water-source...

Xie, D.; Chen, J.; Zhang, G.; Zhang, Q.

2006-01-01T23:59:59.000Z

264

Air Leakage and Air Transfer Between Garage and Living Space  

SciTech Connect

This research project focused on evaluation of air transfer between the garage and living space in a single-family detached home constructed by a production homebuilder in compliance with the 2009 International Residential Code and the 2009 International Energy Conservation Code. The project gathered important information about the performance of whole-building ventilation systems and garage ventilation systems as they relate to minimizing flow of contaminated air from garage to living space. A series of 25 multi-point fan pressurization tests and additional zone pressure diagnostic testing characterized the garage and house air leakage, the garage-to-house air leakage, and garage and house pressure relationships to each other and to outdoors using automated fan pressurization and pressure monitoring techniques. While the relative characteristics of this house may not represent the entire population of new construction configurations and air tightness levels (house and garage) throughout the country, the technical approach was conservative and should reasonably extend the usefulness of the results to a large spectrum of house configurations from this set of parametric tests in this one house. Based on the results of this testing, the two-step garage-to-house air leakage test protocol described above is recommended where whole-house exhaust ventilation is employed. For houses employing whole-house supply ventilation (positive pressure) or balanced ventilation (same pressure effect as the Baseline condition), adherence to the EPA Indoor airPLUS house-to-garage air sealing requirements should be sufficient to expect little to no garage-to-house air transfer.

Rudd, A.

2014-09-01T23:59:59.000Z

265

A Site-Scale Model For Fluid And Heat Flow In The Unsaturated Zone Of Yucca  

Open Energy Info (EERE)

Site-Scale Model For Fluid And Heat Flow In The Unsaturated Zone Of Yucca Site-Scale Model For Fluid And Heat Flow In The Unsaturated Zone Of Yucca Mountain, Nevada Jump to: navigation, search GEOTHERMAL ENERGYGeothermal Home Journal Article: A Site-Scale Model For Fluid And Heat Flow In The Unsaturated Zone Of Yucca Mountain, Nevada Details Activities (0) Areas (0) Regions (0) Abstract: A three-dimensional unsaturated-zone numerical model has been developed to simulate flow and distribution of moisture, gas and heat at Yucca Mountain, Nevada, a potential repository site for high-level radioactive waste. The model takes into account the simultaneous flow dynamics of liquid water, vapor, air and heat in the highly heterogeneous, fractured porous rock in the unsaturated zone (UZ). This model is intended for use in the prediction of the current and future conditions in the UZ so

266

Innovative Method for Performance Inspections often save 20-30% through Optimization of Air-Conditioning and Refrigeration  

E-Print Network (OSTI)

of performance?. (Nordtest.) Esbo, Finland. 16. NT VVS 116, 1997. ?Refrigeration and heat pump equipment: Check-ups and performance data inferred from measurements under field conditions in the refrigerant system?. (Nordtest.) Esbo, Finland. ESL-IC-10...

Berglof, K.

2010-01-01T23:59:59.000Z

267

US Department of Energys Regulatory Negotiations Convening on Commercial Certification for Heating, Ventilating, Air-Conditioning, and Refrigeration Equipment  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

US Department of Energy's Regulatory Negotiations Convening on US Department of Energy's Regulatory Negotiations Convening on Commercial Certification for Heating, Ventilating, Air-Conditioning, and Refrigeration Equipment Public Information for Convening Interviews I. What are the substantive issues DOE seeks to address? Strategies for grouping various basic models for purposes of certification; Identification of non-efficiency attributes, which do not impact the measured consumption of the equipment as tested by DOE's test procedure; The information that is certified to the Department; The timing of when the certification should be made relative to distribution in commerce; and Alterations to a basic model that would impact the certification.

268

2014-09-23 Issuance: Energy Conservation Standard for Walk-in Coolers and Freezers; Air-Conditioning, Heating, & Refrigeration Institute Petition for Reconsideration Notice of Public Meeting  

Energy.gov (U.S. Department of Energy (DOE))

This document is a pre-publication Federal Register notice of public meeting regarding energy conservation standards for walk-in coolers and freezers; Air-Conditioning, Heating, & Refrigeration Institute petition for reconsideration, as issued by the Deputy Assistant Secretary for Energy Efficiency on September 23, 2014. Though it is not intended or expected, should any discrepancy occur between the document posted here and the document published in the Federal Register, the Federal Register publication controls. This document is being made available through the Internet solely as a means to facilitate the public's access to this document.

269

Using energy audits to investigate the impacts of common air-conditioning design and installation issues on peak power demand and energy consumption in Austin, Texas  

Science Journals Connector (OSTI)

This study presents an analysis of a unique dataset of 4971 energy audits performed on homes in Austin, Texas in 20092010. We quantify the prevalence of typical air-conditioner design and installation issues such as low efficiency, oversizing, duct leakage, and low measured capacity, and estimate the impacts that resolving these issues would have on peak power demand and cooling energy consumption. We estimate that air-conditioner use in single-family residences currently accounts for 1718% of peak demand in Austin, and we found that improving equipment efficiency alone could save up to 205MW, or 8%, of peak demand. We estimate that 31% of systems in this study were oversized, leading to up to 41MW of excess peak demand. Replacing oversized systems with correctly sized higher efficiency units has the potential for further savings of up to 81MW. We estimate that the mean system could achieve 18% and 20% in cooling energy savings by sealing duct leaks and servicing their air-conditioning units to achieve 100% of nominal capacity, respectively. Although this analysis is limited to the City of Austin, understanding the methods described herein could allow electric utilities in similar climates to make better-informed decisions when considering efficiency improvement programs.

Joshua D. Rhodes; Brent Stephens; Michael E. Webber

2011-01-01T23:59:59.000Z

270

Proposal for the award of a contract for the design, supply, installation and commissioning of a Heating Ventilation and Air Conditioning (HVAC) system for the HIE-ISOLDE infrastructure  

E-Print Network (OSTI)

Proposal for the award of a contract for the design, supply, installation and commissioning of a Heating Ventilation and Air Conditioning (HVAC) system for the HIE-ISOLDE infrastructure

2012-01-01T23:59:59.000Z

271

Proposal for the award of a contract for the design, supply, installation and commissioning of a Heating, Ventilation and Air-Conditioning (HVAC) system for the computer room of the CERN Control Centre  

E-Print Network (OSTI)

Proposal for the award of a contract for the design, supply, installation and commissioning of a Heating, Ventilation and Air-Conditioning (HVAC) system for the computer room of the CERN Control Centre

2012-01-01T23:59:59.000Z

272

Impacts of Mixing on Acceptable Indoor Air Quality in Homes  

NLE Websites -- All DOE Office Websites (Extended Search)

Impacts of Mixing on Acceptable Indoor Air Quality in Homes Impacts of Mixing on Acceptable Indoor Air Quality in Homes Title Impacts of Mixing on Acceptable Indoor Air Quality in Homes Publication Type Journal Article LBNL Report Number LBNL-3048E Year of Publication 2010 Authors Sherman, Max H., and Iain S. Walker Journal HVAC & Research Journal Keywords air distribution, indoor air quality, mechanical ventilation, mixing, other, resave, residential ventilation, ventilation effectiveness Abstract Ventilation reduces occupant exposure to indoor contaminants by diluting or removing them. In a multi-zone environment such as a house, every zone will have different dilution rates and contaminant source strengths. The total ventilation rate is the most important factor in determining occupant exposure to given contaminant sources, but the zone-specific distribution of exhaust and supply air and the mixing of ventilation air can play significant roles. Different types of ventilation systems will provide different amounts of mixing depending on several factors such as air leakage, air distribution system, and contaminant source and occupant locations. Most U.S. and Canadian homes have central heating, ventilation, and air conditioning systems, which tend to mix the air; thus, the indoor air in different zones tends to be well mixed for significant fractions of the year. This article reports recent results of investigations to determine the impact of air mixing on exposures of residential occupants to prototypical contaminants of concern. We summarize existing literature and extend past analyses to determine the parameters than affect air mixing as well as the impacts of mixing on occupant exposure, and to draw conclusions that are relevant for standards development and for practitioners designing and installing home ventilation systems. The primary conclusion is that mixing will not substantially affect the mean indoor air quality across a broad population of occupants, homes, and ventilation systems, but it can reduce the number of occupants who are exposed to extreme pollutant levels. If the policy objective is to minimize the number of people exposed above a given pollutant threshold, some amount of mixing will be of net benefit even though it does not benefit average exposure. If the policy is to minimize exposure on average, then mixing air in homes is detrimental and should not be encouraged. We also conclude that most homes in the US have adequate mixing already, but that new, high-performance homes may require additional mixing. Also our results suggest that some differentiation should be made in policies and standards for systems that provide continuous exhaust, thereby reducing relative dose for occupants overall

273

Distribution of small dispersive coal dust particles and absorbed radioactive chemical elements in conditions of forced acoustic resonance in iodine air filter at nuclear power plant  

E-Print Network (OSTI)

The physical features of distribution of the small dispersive coal dust particles and the adsorbed radioactive chemical elements and their isotopes in the absorber with the granular filtering medium with the cylindrical coal granules were researched in the case of the intensive air dust aerosol stream flow through the iodine air filter (IAF). It was shown that, at the certain aerodynamic conditions in the IAF, the generation of the acoustic oscillations is possible. It was found that the acoustic oscillations generation results in an appearance of the standing acoustic waves of the air pressure (density) in the IAF. In the case of the intensive blow of the air dust aerosol, it was demonstrated that the standing acoustic waves have some strong influences on both: 1) the dynamics of small dispersive coal dust particles movement and their accumulation in the IAF; 2) the oversaturation of the cylindrical coal granules by the adsorbed radioactive chemical elements and their isotopes in the regions, where the antinodes of the acoustic waves are positioned. Finally, we completed the comparative analysis of the theoretical calculations with the experimental results, obtained for the cases of: 1) the experimental aerodynamic modeling of physical processes of the absorbed radioactive chemical elements and their isotopes distribution in the IAF; and 2) the gamma-activation spectroscopy analysis of the absorbed radioactive chemical elements and their isotopes distribution in the IAF. We made the innovative propositions on the necessary technical modifications with the purpose to improve the IAF technical characteristics and increase its operational time at the nuclear power plant (NPP), going from the completed precise characterization of the IAF parameters at the long term operation.

Oleg P. Ledenyov; Ivan M. Neklyudov

2013-06-14T23:59:59.000Z

274

Development of empirical temperature and humidity-based degraded-condition indicators for low-tonnage air conditioners  

E-Print Network (OSTI)

was equipped with the ability to use either a short-tube orifice (STO) or a thermal expansion valve (TXV). The degraded conditions studied include low evaporator airflow, high and low-charge, and a blocked condenser coil. The work presented in this thesis...

Watt, James Bonner

2012-06-07T23:59:59.000Z

275

Peak Demand Reduction from Pre-Cooling with Zone Temperature Reset in an Office Building  

E-Print Network (OSTI)

control system does not support global reset of zone temperatures, strategies involving reset of supply air temperature

Xu, Peng

2010-01-01T23:59:59.000Z

276

Characteristics of Photosynthesis in Wheat Cultivars with Different Sensitivities to Ozone Under O3-Free Air Concentration Enrichment Conditions  

Science Journals Connector (OSTI)

With the help of the Chinese Ozone-Free Air Concentration Enrichment (O3FACE) platform, the responses of photosynthsis characteristics to elevated O3 concentration were investigated using winter wheat (Tritcium aestivum L.) cultivars Yannong 19 and Yangmai 16, which differ in sensitivities to O3. Under O3 treatment for 75 d, the net photosynthetic rate (Pn), stomtal conductance (Gs), and transpiration rate (Tr) decreased significantly in both cultivars, whereas the intercellular CO2 concentration (Ci) changed slightly. The O3-sensitive cultivar Yannong 19 had larger reductions in Pn (61.1%), Gs (68.0%), and Tr (57.4%) than Yangmai 16 (27.9%, 37.5%, and 27.9%, respectively). This indicated that the reduction of Pn mostly resulted from the nonstomatal factors in cooperation with stomal factors. In the chlorophyll fluorescence parameters, the maximal photochemical efficiency of PSII in the dark (Fv/Fm), the potential activity of PSII (Fv/Fo), the photochemical quenching (qP), and the rate of photochemical reaction (Prate) decreased in the O3 treatment, but the nonphotochemical quenching (NPQ) and the rate of thermal dissipation (Drate) showed a upward tendency. The change tendency of total soluble protein content and the amount of Rubisco was similar to that of chlorophyll fluorescence parameters and Pn. The results implied that the major nonstomal factors responsible for the Pn decrease under elevated O3 concentration were the Ribulose-1,5-bisphosphate (RuBP) carboxylation limitation and the damage of PSII. The change extents of all the parameters were larger in Yannong 19 than in Yangmai 16. The high Tr value and slow reduction of Rubisco amount in Yangmai 16 are probably crucial reasons for its high photosynthetic rate.

Ji-Ling CAO; Liang WANG; Qing ZENG; Jing LIANG; Hao-Ye TANG; Zu-Bin XIE; Gang LIU; Jian-Guo ZHU; Kazhuhiko KOBAYASHI

2009-01-01T23:59:59.000Z

277

Are Ventilation Filters Degrading Indoor Air Quality in California Classrooms?  

E-Print Network (OSTI)

airconditioning IAQ:Indoorairquality LBNL:LawrenceDegrading Indoor Air Quality in California Classrooms? HDEGRADING INDOOR AIR QUALITY IN CALIFORNIA CLASSROOMS?

Fisk, Michael G. Apte and William J.

2009-01-01T23:59:59.000Z

278

Zero Zone Comment | Department of Energy  

Energy Savers (EERE)

Order 13563 certification, compliance and enforcement regulations for Commercial Refrigeration Equipment (CRE) Air Conditioning Heating and Refrigeration Institute Comment...

279

Experimental investigation of supersonic low pressure air plasma flows obtained with different arc-jet operating conditions  

SciTech Connect

A stationary arc-jet plasma flow at low pressure is used to simulate some properties of the gas flow surrounding a vehicle during its entry into celestial body's atmospheres. This paper presents an experimental study concerning plasmas simulating a re-entry into our planet. Optical measurements have been carried out for several operating plasma conditions in the free stream, and in the shock layer formed in front of a flat cylindrical plate, placed in the plasma jet. The analysis of the spectral radiation enabled the identification of the emitting species, the determination of the rotational and vibrational temperatures in the free-stream and in the shock layer and the determination of the distance of the shock to the flat plate face. Some plasma fluid parameters like, stagnation pressure, specific enthalpy and heat flux have been determined experimentally along the plasma-jet axis.

Lago, Viviana; Ndiaye, Abdoul-Aziz [Laboratoire ICARE CNRS, 1C Av. de la Recherche Scientifique 45071 Orleans Cedex 2 (France)

2012-11-27T23:59:59.000Z

280

The impacts of duct design on life cycle costs of central residential heating and air-conditioning systems  

Science Journals Connector (OSTI)

Abstract Many central residential HVAC systems in the U.S. operate at high external static pressures due to a combination of system restrictions. Undersized and constricted ductwork are thought to be key culprits that lead to excess external static pressures in many systems, although the magnitude of energy impacts associated with restrictive ductwork and the costs or benefits associated with addressing the problem are not well known. Therefore, this work uses annual energy simulations of two typical new single-family homes in two separate climates in the United States (Austin, TX and Chicago, IL) to predict the impacts of various external static pressure ductwork designs from independent HVAC contractors (using both flexible and rigid sheet metal ductwork materials) on annual space conditioning energy use. Results from the simulations are combined with estimates of the initial installation costs of each duct design made by each contractor to evaluate the total life cycle costs or savings of using lower pressure duct designs in the two homes over a 15-year life cycle. Lower pressure ductwork systems generally yielded life cycle cost savings, particularly in homes with PSC blowers and particularly when making comparisons with constant ductwork materials (i.e., comparing flex only or rigid only).

Brent Stephens

2014-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


281

Student Zone  

NLE Websites -- All DOE Office Websites (Extended Search)

Student Zone Student Zone Homework Helpers All About Atoms - Learn about the parts of the atom! Virginia State Standards of Learning Practice Tests - Practice taking the SOL tests! Subjects currently include algebra, math, science and technology. Table of Elements - Basic physical and historical information about the elements! [Printable Version] Questions and Answers - Have a question? Need an answer? Check here first! Glossary of Science Terms - Definitions of some of the terms used on this site. Jefferson Lab Virtual Tour - How do scientists explore inside atoms? Video Resources Frostbite Theater - Short science experiments using liquid nitrogen, static electricity and more! Physics Out Loud - Jefferson Lab scientists and other experts explain some of the common words and terms used in nuclear physics research.

282

With harmful ozone concentrations tied to meteorological conditions, EPA investigates the U.S. air quality implications of a changing climate.  

E-Print Network (OSTI)

%, vehicle miles traveled increased 103% and energy consumption increased 30% (U.S. EPA 2008). Air pollution- port emphasized that the U.S. air quality management system must be "flexible and vigilant" to ensure

Cohen, Ronald C.

283

Supply Fan Control for Constant Air Volume Air Handling Units  

E-Print Network (OSTI)

Since terminal boxes do not have a modulation damper in constant volume (CV) air handling unit (AHU) systems, zone reheat coils have to be modulated to maintain the space temperature with constant supply airflow. This conventional control sequence...

Cho, Y.; Wang, G.; Liu, M.

2007-01-01T23:59:59.000Z

284

AIR QUALITY: Control Enters New Phase  

Science Journals Connector (OSTI)

AIR QUALITY: Control Enters New Phase ... Federal enforcement of air pollution is about to enter a new, more technically sophisticated, phase. ... Now air pollution control moves into the criteria and standards period, when numbers eventually will be the basis for enforcement and the country becomes zoned into 32 air quality regions. ...

1968-08-05T23:59:59.000Z

285

Optimization of Air Conditioning Cycling  

E-Print Network (OSTI)

Benchmark Long Cycle .............................................................................................. 95 5.46 System Pressures and Temperatures Valve Part Cycle Vs Benchmark Long Cycle...

Seshadri, Swarooph

2012-10-19T23:59:59.000Z

286

Effects of gaseous NH{sub 3} and SO{sub 2} on the concentration profiles of PCDD/F in flyash under post-combustion zone conditions  

SciTech Connect

Highlights: Black-Right-Pointing-Pointer Influence of NH{sub 3} and SO{sub 2} on 2378-PCDD/F in flyash and flue gases was investigated. Black-Right-Pointing-Pointer NH{sub 3} decreased the concentration of PCDD and PCDF by 34-75% in the flyash. Black-Right-Pointing-Pointer NH{sub 3} decreased the concentration of PCDD and PCDF by 21-40% from the flue gases. Black-Right-Pointing-Pointer SO{sub 2} led to 99% PCDD and 93% PCDF reductions in the flyash. Black-Right-Pointing-Pointer SO{sub 2} led to 89% PCDD and 76% PCDF reductions in the flue gases. - Abstract: The influence of gaseous ammonia and sulphur dioxide on the formation of 2378-substituted PCDD/F on a reference flyash from a municipal waste incinerator has been investigated using a laboratory scale fixed-bed reactor. The reference flyash samples (BCR-490) was reacted under a simulated flue gas stream at temperatures of 225 and 375 Degree-Sign C for 96 h. The experiments were carried out in two series: first with simulated flue gas alone, and then with injection of NH{sub 3} or SO{sub 2} gas into the flue gas just before the reactor inlet. It was found that the injection of gaseous ammonia into the flue gas could decrease the concentration of both PCDD and PCDF by 34-75% from the solid phase and by 21-40% from the gas phase. Converting the results to I-TEQ values, it could reduce the total I-TEQ values of PCDD and PCDF in the sum of the flyash and exhaust flue gas by 42-75% and 24-57% respectively. The application of SO{sub 2} led to 99% and 93% reductions in the PCDD and PCDF average congener concentrations, respectively in the solid phase. In the gas phase, the total reductions were 89% and 76% for PCDD and PCDF, respectively. Moreover, addition of SO{sub 2} reduced the total I-TEQ value of PCDD and PCDF in the flyash and exhaust flue gas together by 60-86% and 72-82% respectively. Sulphur dioxide was more effective than ammonia in suppressing PCDD/F formation in flyash under the conditions investigated.

Hajizadeh, Yaghoub; Onwudili, Jude A. [Energy Research Institute, University of Leeds, Leeds LS2 9JT (United Kingdom); Williams, Paul T., E-mail: p.t.williams@leeds.ac.uk [Energy Research Institute, University of Leeds, Leeds LS2 9JT (United Kingdom)

2012-07-15T23:59:59.000Z

287

Studies in the Respiratory and Carbohydrate Metabolism of Plant Tissues. III. Experimental Studies of the Formation of Carbon Dioxide and of the Changes in Lactic Acid and other Products in Potato Tubers in Air Following Anaerobic Conditions  

Science Journals Connector (OSTI)

...in Air Following Anaerobic Conditions J. Barker A. F. El Saifi This paper is the third in a series dealing with the anaerobic metabolism of potato tubers. In the two earlier papers (Barker Saifi 1952a, b) we considered the changes which occurred during...

1953-01-01T23:59:59.000Z

288

Studies in the Respiratory and Carbohydrate Metabolism of Plant Tissues. IV. The Relation between the Rate of Carbon Dioxide Production in Potato Tubers in Air Following Anaerobic Conditions, and the Accompanying Changes in Lactic Acid Content and Sugar Concentration  

Science Journals Connector (OSTI)

...Following Anaerobic Conditions, and the Accompanying Changes in Lactic Acid Content and Sugar Concentration J. Barker A. F. El Saifi In part III of this series data were presented for the changes in air following periods of anaerobiosis in the rate of production...

1953-01-01T23:59:59.000Z

289

Numerical Analysis of a Cold Air Distribution System  

E-Print Network (OSTI)

Cold air distribution systems may reduce the operating energy consumption of air-conditioned air supply system and improve the outside air volume percentages and indoor air quality. However, indoor temperature patterns and velocity field are easily...

Zhu, L.; Li, R.; Yuan, D.

2006-01-01T23:59:59.000Z

290

Code-compliant 2X4 Walls for Zones Marine 4-8 - Code Notes | Building  

NLE Websites -- All DOE Office Websites (Extended Search)

Code-compliant 2X4 Walls for Zones Marine 4-8 - Code Notes Code-compliant 2X4 Walls for Zones Marine 4-8 - Code Notes The 2009 International Residential Code and International Energy Conservation Code do not permit trade-offs for installing high-efficiency heating, ventilation, and air conditioning equipment-installing a 90%+ furnace as a trade-off for 2" x 4" stud walls with R-13 insulation. The more permanent building insulation and sealing features now take precedence. However, there still remain optional strategies allowing 2" x 4" exterior stud walls. cn_code-compliant_2x4_walls_for_zones_marine_4-8.pdf Document Details Prepared by: Pacific Northwest National Laboratory for the U.S. Department of Energy Building Energy Codes Program Focus: Compliance Building Type: Residential Code Referenced:

291

High-Efficiency Window Air Conditioners - Building America Top...  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Window Air Conditioners - Building America Top Innovation This photo shows a window air conditioning unit in place in a window frame. Window air conditioners are inexpensive,...

292

EMISSIONS TO AIR OPERATIONAL PROCEDURE  

E-Print Network (OSTI)

EMISSIONS TO AIR OPERATIONAL PROCEDURE Swansea University Estates Services Singleton Park Swansea to Air Department: Estates and Facilities Site: All Author: Ambreen Jahangir Approved by: Mark Durdin PURPOSE: To minimise emissions and discharges to air from boilers, fume cupboards, air conditioning

Harman, Neal.A.

293

An investigation of the heat and mass transfer by free convection from humid air to a horizontal metal plate under frosting conditions  

E-Print Network (OSTI)

AN INVESTIOATION OF THE NEAT AND MASS TRANSFER BY FREE CONVECTION FROM HUMID AIR TO A HDRIZOHTAL METAL PLATE UNDER FROSTINO COND1TIONS A Thesis By BOBBY BELL~ JR. Submitted to the Graduate College of Texas A%M University in partial... ~ ~ ~. . . 60 - 61 17 Total Heat Transferred, to Plate vs. Time ~ 18 19 20 Thermal Conductivity Coefficient of Frost vso Time. . . . . . . . . . ~ ~ . . ~ ~ Heat Transfer Convective Coefficient vs. Time ~ 0 4 ~ 0 ~ ~ 4 ~ ~ ~ Resistivity of' Air...

Bell, Bobby

2012-06-07T23:59:59.000Z

294

Incentive zoning and environmental quality in Boston's Fenway neighborhood  

E-Print Network (OSTI)

A density bonus, also called incentive zoning, is a conditional liberalization of zoning regulations, allowing a real estate development to exceed as-of-right density limits in exchange for the in-kind provision or purchase ...

DeFlorio, Joshua (Joshua C.)

2007-01-01T23:59:59.000Z

295

China Energy Efficiency Round Robin Testing Results for Room Air Conditioners  

E-Print Network (OSTI)

check in the air conditioning products category is indicatednumber of domestic air conditioning product manufacturers100 million worth of air conditioner products to 14 major

Zhou, Nan

2010-01-01T23:59:59.000Z

296

Coupling Air Flow Models to Load/Energy Models and Implications for  

NLE Websites -- All DOE Office Websites (Extended Search)

Coupling Air Flow Models to Load/Energy Models and Implications for Coupling Air Flow Models to Load/Energy Models and Implications for Envelope Component Testing and Modeling Speaker(s): Brent Griffith Date: July 30, 2002 - 12:00pm Location: Bldg. 90 Seminar Host/Point of Contact: Dariush Arasteh Air models allow accounting for air temperature variations within a thermal zone or along the surface of an envelope component. A recently completed ASHRAE research project (RP-1222) produced a source code toolkit focused on coupling airflow models to load routines typical of whole building energy simulation. The two modeling domains are computed separately (and iteratively) with relevant temperature boundary conditions passed back and forth. One of the air models in the toolkit is a new contribution to crude/fast airflow modeling that is based on solving the Euler equation

297

Heat balance for two commercial broiler barns with solar preheated ventilation air  

Science Journals Connector (OSTI)

In temperate climatic zones, solar air heaters can reduce heating loads, and increase winter ventilation rates thereby improving inside air quality and livestock performance without additional fuel input. A heat balance was carried out to measure bird heat production under field conditions on two commercial broiler barns to evaluate the impact of solar heated ventilation air on bird performance, and identify strategies to reduce winter heating load. Located 40km east of Montreal, Canada, the experimental broiler barns were identically built with three floors housing 6500 birds per floor in an all-in all-out fashion. Equipped with solar air pre-heaters over their fresh air inlets, the barns were instrumented to monitor inlet, inside and outside air conditions, ventilation rate and heating system operating time. The effects on bird performance were observed from November 2007 to March 2009 by alternating their operation between the barns. The measured sensible and total heat productions of 4.5W and 8.4W, respectively, for 1kg birds corresponded to laboratory measured values. Bird performance was not affected by the solar air pre-heaters which increased the ventilation rate above normal during only 20% of the daytime period. Room air temperature stratification resulted in 2040kW of heat losses during the winter, representing 25% of the total natural gas heat load. Because inside air moved directly to the fans, large and rapid increases in ventilation inlet air temperature, produced by the solar air pre-heaters, resulted in further heat losses equivalent to 15% of the solar energy recovered. Sustainable energy management in livestock barns requiring heating should incorporate an air mixing system to eliminate air temperature stratification and improve fan flows.

Sbastien Cordeau; Suzelle Barrington

2010-01-01T23:59:59.000Z

298

E-Print Network 3.0 - air-to-air heat pumps Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

conditions... data on the seasonal performance of air-to-air residential heat pump systems. The purpose of this paper... of operation 10, 197778, the Control House ......

299

Other Fresnel Zone Antennas  

Science Journals Connector (OSTI)

In the preceding chapters, theoretical investigations and experiments on a number of Fresnel zone antennas are presented. This chapter is intended to introduce a wider range of Fresnel zone antennas. Section 7...

Y. Jay Guo; Stephen K. Barton

2002-01-01T23:59:59.000Z

300

Enterprise Zone Program (Illinois)  

Energy.gov (U.S. Department of Energy (DOE))

The Enterprise Zone Program provides eligible businesses that relocate or expand to a designated zone with tax incentives such as: 1) an investment tax credit; 2) a job tax credit for each job...

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


301

Alternative Energy Zone (Ohio)  

Energy.gov (U.S. Department of Energy (DOE))

Ohio's Alternative Energy Zones are made possible through Ohio's Senate Bill 232, which reduced taxes on alternative energy projects. The Alternative Energy Zones are designated on a county-by...

302

Zoning and Permitting Resources  

Energy.gov (U.S. Department of Energy (DOE))

Zoning and permitting is commonly controlled by local governments and may be applicable to both residential and commercial properties.

303

A robust CO2-based demand-controlled ventilation control strategy for multi-zone HVAC systems  

Science Journals Connector (OSTI)

There have been increasingly growing concerns over the quality of the air inside buildings and the associated energy use. The CO2-based demand-controlled ventilation DCV is one of the strategies that could offer a great opportunity to reduce energy consumption in HVAC systems. However, implementing CO2-based DCV under ASHRAE Standard 62.1 20042010 is not simple as it was under previous versions due to the changes in breathing-zone ventilating rate calculations. Thus, this paper provides insight into the performance of a multi-zone VAV system under different operating and ventilation conditions, discusses the difficulties in the CO2-based DCV, and proposes a robust DCV strategy based on the supply air CO2 concentration. The proposed strategy offers great benefits in terms of better indoor air control and improved energy efficiency. To evaluate the proposed strategy, energy simulations were performed on various USA locations and for a typical two-story office building conditioned by a VAV system. The results show that a significant energy saving could be achieved by implementing the proposed strategy as compared to the design-occupancy ASHRAE Standard 62.1 2010 multi-zone procedure and the amount of saving that could be up to 23% depends mainly on locations and the actual occupancy profile.

Nabil Nassif

2012-01-01T23:59:59.000Z

304

Air Flow Distribution in the Sales Area of a Supermarket  

E-Print Network (OSTI)

temperature, air velocity and humidity in different zones. The results of a study of a sales area of a supermarket in Harbin are presented in this paper, including air temperature, air velocity and humidity. According to the assessment index of air flow...

Fang, X.; Song, C.; Zhao, J.; Wang, Z.

2006-01-01T23:59:59.000Z

305

Common Air Conditioner Problems | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Common Air Conditioner Problems Common Air Conditioner Problems Common Air Conditioner Problems May 30, 2012 - 6:41pm Addthis A refrigerant leak is one common air conditioning problem. | Photo courtesy of ©iStockphoto/BanksPhotos. A refrigerant leak is one common air conditioning problem. | Photo courtesy of ©iStockphoto/BanksPhotos. What does this mean for me? You can eliminate the most common air conditioner problems before hiring an air conditioning technician. You can do some air conditioner maintenance and repair tasks yourself. One of the most common air conditioning problems is improper operation. If your air conditioner is on, be sure to close your home's windows and outside doors. For room air conditioners, isolate the room or a group of connected rooms as much as possible from the rest of your home.

306

Common Air Conditioner Problems | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Common Air Conditioner Problems Common Air Conditioner Problems Common Air Conditioner Problems May 30, 2012 - 6:41pm Addthis A refrigerant leak is one common air conditioning problem. | Photo courtesy of ©iStockphoto/BanksPhotos. A refrigerant leak is one common air conditioning problem. | Photo courtesy of ©iStockphoto/BanksPhotos. What does this mean for me? You can eliminate the most common air conditioner problems before hiring an air conditioning technician. You can do some air conditioner maintenance and repair tasks yourself. One of the most common air conditioning problems is improper operation. If your air conditioner is on, be sure to close your home's windows and outside doors. For room air conditioners, isolate the room or a group of connected rooms as much as possible from the rest of your home.

307

Compressed Air  

NLE Websites -- All DOE Office Websites (Extended Search)

BPA Utility Reimbursement Programs for Compressed Air Projects Customer Proposal Template Measurement & Verification Plan for Compressed Air CA 2006-15 A template for utilities to...

308

Swimming pools as heat sinks for air conditioners: California feasibility analysis  

Science Journals Connector (OSTI)

Earlier studies used field testing of swimming pool temperatures to validate a mathematical model for predicting the temperature of an unheated pool. Combining those results with manufacturers data on the performance of vapor-compression air conditioners as a function of heat rejection temperature, the analyses in the paper suggest that rejecting air conditioning heat to a swimming pool can save approximately 2530% of single-family residential cooling electricity use and reduce cooling electricity demand during peak conditions by 3035%, as compared to using the same compressor to reject the heat to ambient air. The savings is expected to vary depending on the severity of the climate, as well as the pool temperature experienced during the summer. The original model was refined so as to accommodate air-conditioner heat rejection to predict pool temperatures based on weather data, pool size, shading of the pool, and air-conditioner heat rejection to the pool. The results of an experimental validation of the augmented pool thermal model are presented here. In addition, the model of a pool-coupled air conditioning system was used to develop a design tool for determining the pool size needed to absorb realistic heat rejection from air conditioners in various California climate zones.

Curtis Harrington; Mark Modera

2013-01-01T23:59:59.000Z

309

The use of phase change materials in domestic heat pump and air-conditioning systems for short term storage: A review  

Science Journals Connector (OSTI)

Abstract Heat pumps for space heating and cooling are a mature and highly efficient technology that can take advantage of renewable energies. They can also provide energy savings by load shifting when they operate together with thermal energy storage (TES). This paper presents a literature review of TES systems using phase change materials (PCM) potentially applicable to domestic heat pumps used in residential and administrative buildings. The paper describes the systems proposed by the different authors and presents the main conclusions of the studies. The TES systems presented are not only used as energy storage to shift the load demand but also for other applications such as heat recovery or defrosting in air-conditioners. The PCM have the suitable melting temperature to work together with standard heat pumps in each application. Moreover, some systems where the heat pump is coupled to latent heat thermal energy storage (LHTES) units and other energy sources or where the TES system is incorporated in a radiant floor or air distribution system have also been included.

Pere Moreno; Cristian Sol; Albert Castell; Luisa F. Cabeza

2014-01-01T23:59:59.000Z

310

Exergy efficiency of a counterflow air/air heat exchanger with vapour condensation  

Science Journals Connector (OSTI)

The exergy efficiency of a counterflow hot moist air/...?1 for the temperature and humidity ratio of hot moist air respectively are considered. Constant ambient air conditions of 20C and 0.01 kgkg?1 were assume...

J. Jilek; J. H. Young

1993-01-01T23:59:59.000Z

311

Dirty Air Conditioners: Energy Implications of Coil Fouling Jeffrey Siegel, Lawrence Berkeley National Laboratory/ UC Berkeley  

E-Print Network (OSTI)

Berkeley National Laboratory ABSTRACT Residential air conditioning is responsible for a substantial amount greater for marginal systems or extreme conditions. These energy issues, as well as possible indoor air conditioning commissioning and maintenance practices. Introduction Residential air conditioning is responsible

312

Studies in the Respiratory and Carbohydrate Metabolism of Plant Tissues. V. Experimental Studies of the Formation of Carbon Dioxide and of the Changes in Lactic Acid, Sucrose and in Certain Fractions of Keto-Acids in Potato Tubers in Air Following Anaerobic Conditions  

Science Journals Connector (OSTI)

...in Certain Fractions of Keto-Acids in Potato Tubers in Air Following Anaerobic Conditions J. Barker L. W. Mapson Barker Saifi (1953 b), suggested that the initial rapid increase and the subsequent slower decrease in the output of potatoes in air after...

1953-01-01T23:59:59.000Z

313

Building America Case Study: Air Leakage and Air Transfer Between Garage and Living Space, Waldorf, Maryland (Fact Sheet)  

SciTech Connect

This research project focused on evaluation of air transfer between the garage and living space in a single-family detached home constructed by a production homebuilder in compliance with the 2009 International Residential Code and the 2009 International Energy Conservation Code. The project gathered important information about the performance of whole-building ventilation systems and garage ventilation systems as they relate to minimizing flow of contaminated air from garage to living space. A series of 25 multi-point fan pressurization tests and additional zone pressure diagnostic testing characterized the garage and house air leakage, the garage-to-house air leakage, and garage and house pressure relationships to each other and to outdoors using automated fan pressurization and pressure monitoring techniques. While the relative characteristics of this house may not represent the entire population of new construction configurations and air tightness levels (house and garage) throughout the country, the technical approach was conservative and should reasonably extend the usefulness of the results to a large spectrum of house configurations from this set of parametric tests in this one house. Based on the results of this testing, the two-step garage-to-house air leakage test protocol described above is recommended where whole-house exhaust ventilation is employed. For houses employing whole-house supply ventilation (positive pressure) or balanced ventilation (same pressure effect as the Baseline condition), adherence to the EPA Indoor airPLUS house-to-garage air sealing requirements should be sufficient to expect little to no garage-to-house air transfer.

Not Available

2014-11-01T23:59:59.000Z

314

Room Air Conditioners | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Room Air Conditioners Room Air Conditioners Room Air Conditioners July 1, 2012 - 5:35pm Addthis A window air conditioner is one solution to cooling part of a house. | Photo courtesy of ©iStockphoto/kschulze. A window air conditioner is one solution to cooling part of a house. | Photo courtesy of ©iStockphoto/kschulze. What does this mean for me? Room air conditioners are less expensive and disruptive to install than central air conditioning systems. Room air conditioners can be a cost-effective alternative to central air conditioning systems. How does it work? Room air conditioners work by cooling one part of your home. Room or window air conditioners cool rooms rather than the entire home or business. If they provide cooling only where they're needed, room air conditioners are less expensive to operate than central units, even though

315

Mobile machine hazardous working zone warning system  

DOE Patents (OSTI)

A warning system is provided for a mobile working machine to alert an individual of a potentially dangerous condition in the event the individual strays into a hazardous working zone of the machine. The warning system includes a transmitter mounted on the machine and operable to generate a uniform magnetic field projecting beyond an outer periphery of the machine in defining a hazardous working zone around the machine during operation. A receiver, carried by the individual and activated by the magnetic field, provides an alarm signal to alert the individual when he enters the hazardous working zone of the machine. 3 figs.

Schiffbauer, W.H.; Ganoe, C.W.

1999-08-17T23:59:59.000Z

316

Mobile machine hazardous working zone warning system  

DOE Patents (OSTI)

A warning system is provided for a mobile working machine to alert an individual of a potentially dangerous condition in the event the individual strays into a hazardous working zone of the machine. The warning system includes a transmitter mounted on the machine and operable to generate a uniform magnetic field projecting beyond an outer periphery of the machine in defining a hazardous working zone around the machine during operation thereof. A receiver, carried by the individual and activated by the magnetic field, provides an alarm signal to alert the individual when he enters the hazardous working zone of the machine.

Schiffbauer, William H. (Connellsville, PA); Ganoe, Carl W. (Pittsburgh, PA)

1999-01-01T23:59:59.000Z

317

Air Quality  

NLE Websites -- All DOE Office Websites (Extended Search)

What We Monitor & Why » What We Monitor & Why » Air Quality Air Quality To preserve our existing wilderness-area air quality, LANL implements a conscientious program of air monitoring. April 12, 2012 Real-time data monitoring for particulate matter An air monitoring field team member tests one of LANL's tapered element oscillating microbalance samplers, which collects real-time particulate matter data. Contact Environmental Communication & Public Involvement P.O. Box 1663 MS M996 Los Alamos, NM 87545 (505) 667-0216 Email LANL monitors air quality 24 hours a day, 365 days a year. Why we monitor air LANL monitors many different pathways in order to assess their impact on workers, the public, animals, and plants. We monitor the air around the Laboratory to ensure our operations are not affecting the air of nearby

318

Applying a Domestic Water-cooled Air-conditioner in Subtropical Cities  

E-Print Network (OSTI)

Water-cooled air-conditioning systems (WACS) are in general more energy efficient than air-cooled air-conditioning systems (AACS), especially in subtropical climates where the outdoor air is hot and humid. Related studies focused on evaluating...

Lee, W.; Chen, H.

2006-01-01T23:59:59.000Z

319

Renaissance Zones (North Dakota)  

Energy.gov (U.S. Department of Energy (DOE))

Renaissance Zones allow qualifying businesses and individuals to claim one or more tax incentives for purchasing, leasing, or making improvements to real property located in a North Dakota...

320

Ventilation Air Preconditioning Systems  

E-Print Network (OSTI)

Ventilation Air Preconditioning Systems Mukesh Khattar Michael J. Brandemuehl Manager, Space Conditioning and Refrigeration Associate Professor Customer Systems Group Joint Center for Energy Management Electric Power Research Institute Campus... costs, the small, modular nature of the system allows great flexibility for fitting into retrofit geometries and saves space in new construction. Moreover, a single chiller can serve multiple air-handling units-in stark contrast to packaged...

Khattar, M.; Brandemuehl, M. J.

1996-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


321

The design, construction, and instrumentation of a chamber to study heat, mass, and momentum transfer from humid air to metal under conditions of frosting and free convection  

E-Print Network (OSTI)

It wns decided to use two heating coils, one as a steady input heater and the other as a control heater, From the preceding calculations a control hester twenty feet in length wns installed in the aiF flow along with a steady input heater coil forty... and thermocouple leads until the disks were parallel to and in contact with the teat surfaces. under these conditions the sero point of the scale wss marked. Then while a steel rule was held perpsadicular to the test surface and close to one of the copper disks...

Hutchison, James P

1961-01-01T23:59:59.000Z

322

Climate Zones Robinson Projection  

E-Print Network (OSTI)

Climate Zones Africa ´Robinson Projection Copyright 2007. The Trustees of Columbia University University. Population, Landscape, and Climate Estimates (PLACE). Further information available at: http://sedac.ciesin.columbia.edu/place/ Publish Date: 03/13/07 0 500 km Climate zones were taken from the Köppen Climate Classification map

Columbia University

323

About Nuccio Heating & Air Headquartered in Tampa, Florida, Nuccio Heating & Air serves  

E-Print Network (OSTI)

­ the majority being highly mobile ­ sell and service heating and air conditioning systems for the company customer service Industry Focus Heating and air conditioning services Size 52 employees Case Study Nuccio Fixing Problems Fast In Florida's competitive air conditioning industry, the differentiator is "speed

Fisher, Kathleen

324

Building America Webinar: High Performance Space Conditioning...  

Energy Savers (EERE)

Strategies for Affordable Housing Building America Webinar: High Performance Space Conditioning Systems, Part II - Air Distribution Retrofit Strategies for Affordable...

325

Unsaturated Zone and Saturated Zone Transport Properties (U0100)  

SciTech Connect

This Analysis/Model Report (AMR) summarizes transport properties for the lower unsaturated zone hydrogeologic units and the saturated zone at Yucca Mountain and provides a summary of data from the Busted Butte Unsaturated Zone Transport Test (UZTT). The purpose of this report is to summarize the sorption and transport knowledge relevant to flow and transport in the units below Yucca Mountain and to provide backup documentation for the sorption parameters decided upon for each rock type. Because of the complexity of processes such as sorption, and because of the lack of direct data for many conditions that may be relevant for Yucca Mountain, data from systems outside of Yucca Mountain are also included. The data reported in this AMR will be used in Total System Performance Assessment (TSPA) calculations and as general scientific support for various Process Model Reports (PMRs) requiring knowledge of the transport properties of different materials. This report provides, but is not limited to, sorption coefficients and other relevant thermodynamic and transport properties for the radioisotopes of concern, especially neptunium (Np), plutonium (Pu), Uranium (U), technetium (Tc), iodine (I), and selenium (Se). The unsaturated-zone (UZ) transport properties in the vitric Calico Hills (CHv) are discussed, as are colloidal transport data based on the Busted Butte UZTT, the saturated tuff, and alluvium. These values were determined through expert elicitation, direct measurements, and data analysis. The transport parameters include information on interactions of the fractures and matrix. In addition, core matrix permeability data from the Busted Butte UZTT are summarized by both percent alteration and dispersion.

J. Conca

2000-12-20T23:59:59.000Z

326

Deep Vadose Zone Field Activities  

NLE Websites -- All DOE Office Websites (Extended Search)

HANFORD ADVISORY BOARD, RAP March 6, 2013 Presented by: John Morse DEEP VADOSE ZONE ACTIVITIES Page 2 Deep Vadose Zone Areas Page 3 Deep Vadose Zone Field Activities FY 2014...

327

Development Opportunity Zone Credit  

Energy.gov (U.S. Department of Energy (DOE))

The Development Opportunity Zone Credits incent new and expanding businesses in the Cities of Beloit, Janesville and Kenosha by providing non-refundable tax credits to assist with the creation and...

328

Deep Vadose Zone  

Energy.gov (U.S. Department of Energy (DOE))

The Mission of the Deep Vadose Zone Applied Field Research Initiative is to protect water resources across the DOE complex over the long-term by developing effective solutions to solve DOEs most...

329

Queen Anne's County- Solar Zoning  

Energy.gov (U.S. Department of Energy (DOE))

Queen Anne's County zoning code allows for ground mounted solar arrays in areas zoned as "open space," "agricultural," and "countryside" districts.

330

EVENT CLOUDS : lighter than air architectural structures  

E-Print Network (OSTI)

EVENT CLOUD is a versatile covering system that allows events to happen independently to weather conditions. It consists of a lighter than air pneumatic structure, filled either with helium or hot air, that covers spaces ...

Peydro Duclos, Ignacio

2014-01-01T23:59:59.000Z

331

Thermal decay in underfloor air distribution (UFAD) systems: Fundamentals and influence on system performance  

E-Print Network (OSTI)

zones. Variable-speed fan coil units ( FCU) supply air tounit (AHU) including an economizer, chilled water cooling coil, hot water heating coil and supply fan.

Lee, Kwang Ho; Schiavon, Stefano; Bauman, Fred; Webster, Tom

2012-01-01T23:59:59.000Z

332

Heating, Ventilation, and Air Conditioning Projects | Department...  

Office of Energy Efficiency and Renewable Energy (EERE) Indexed Site

- Grenada, MS -- International Copper Association - New York, NY -- Wieland - Ulm, Germany -- Heat Transfer Technologies - Abington, PA Multi-Function Fuel-Fired Heat Pump...

333

Air Pollution  

Science Journals Connector (OSTI)

Both natural processes and human activities contribute to air pollution, with the combustion of fossil fuels being the largest anthropogenic source of air pollutants. Adverse health effects (above all respiratory and cardiovascular complications), damage to crops, natural vegetation and materials, reduced visibility and changed radiation balance of the atmosphere are the major consequences of high concentrations of air pollutants. Technical fixes can sharply reduce emissions from large stationary sources and lower the rates of automotive emissions, but the rising number of vehicles and longer time spent on the road will call for more radical solutions to traffic-generated photochemical smog now present in all major urban areas.

V. Smil

2001-01-01T23:59:59.000Z

334

Microconvection effects at double?diffusive gradient zone boundaries  

Science Journals Connector (OSTI)

Microconvection in double?diffusive gradient zones is predicted to occur near the zone boundaries because of effects of boundary undulation and temperature modulation caused by impinging thermals in adjacent convecting zones. The equations that govern convective motion in a double?diffusive horizontal slab are solved for boundary conditions that incorporate these effects. Solution of these equations predicts a weakened salinity gradient near the gradient zone boundary between the rising thermals. When the salinity gradient is too weak instability occurs taking the form of descending plumes which are seen in experiments.

John R. Hull; Yojana Katti

1988-01-01T23:59:59.000Z

335

REVIEW OF AIR FLOW MEASUREMENT TECHNIQUES  

Office of Scientific and Technical Information (OSTI)

9747 9747 Review of Airflow Measurement Techniques Jennifer McWilliams Energy Performance of Buildings Group Environmental Energy Technologies Division Lawrence Berkeley National Laboratory Berkeley, CA 94720 December 1, 2002 Abstract Airflow measurement techniques are necessary to determine the most basic of indoor air quality questions: "Is there enough fresh air to provide a healthy environment for the occupants of the building?" This paper outlines airflow measurement techniques, but it does not make recommendations for techniques that should be used. The airflows that will be discussed are those within a room or zone, those between rooms or zones, such as through doorways (open or closed) or passive vents, those between the building and

336

Analysis of air leakage measurements of US houses  

Science Journals Connector (OSTI)

Abstract Building envelope airtightness is important for residential energy use, occupant health and comfort. We analyzed the air leakage measurements of 134,000 single-family detached homes in US, using normalized leakage (NL) as the metric. Weatherization assistance programs (WAPs) and residential energy efficiency programs contributed most of the data. We performed regression analyses to examine the relationship between NL and various house characteristics. Explanatory variables that are correlated with NL include year built, climate zone, floor area, house height, and whether homes participated in \\{WAPs\\} or if they are energy efficiency rated homes. Foundation type and whether ducts are located outside or inside the conditioned space are also found to be useful parameters for predicting NL. We developed a regression model that explains approximately 68% of the observed variability across US homes. Of these variables considered, year built and climate zone are the two that have the largest influence on NL. The regression model can be used to predict air leakage values for individual homes, and distributions for groups of homes, based on their characteristics. Using RECS 2009 data, the regression model predicts 90% of US houses have NL between 0.22 and 1.95, with a median of 0.67.

Wanyu R. Chan; Jeffrey Joh; Max H. Sherman

2013-01-01T23:59:59.000Z

337

Bos > AIR  

E-Print Network (OSTI)

The advent of air travel has produced a building typology completely new to the 20th century. The outdated planning of regions for airports render most existing airports as isolated, autonomous instances in the urban ...

Lee, Kevin Young

2014-01-01T23:59:59.000Z

338

Unsaturated Zone I. Overview  

E-Print Network (OSTI)

Chapter 2 Unsaturated Zone I. Overview If the Yucca Mountain site is deemed suitable for re of the extent of welding, the tuffs within the UZ at Yucca Mountain are grouped informally into hydrogeologic Yucca Mountain is illustrated in Figure 2-1 on page 14. A. Why UZ Was Chosen Initial studies of Yucca

339

Subduction Zone | Open Energy Information  

Open Energy Info (EERE)

Subduction Zone Subduction Zone Jump to: navigation, search GEOTHERMAL ENERGYGeothermal Home Print PDF Subduction Zone Dictionary.png Subduction Zone: A tectonic process in which one tectonic plate is forced beneath another and sinks into the mantle as the plates converge Other definitions:Wikipedia Reegle Tectonic Settings List of tectonic settings known to host modern geothermal systems: Extensional Tectonics Subduction Zone Rift Zone Hot Spot Non-Tectonic Strike-Slip A classic cartoon illustrating a typical simplified subduction zone. http://www.columbia.edu/~vjd1/subd_zone_basic.htm Subduction zones occur where one tectonic plate is pulled under another. Most often the subducting plate is oceanic crust and contains many hydrous minerals. As the oceanic plate subducts it dewaters into the mantle,

340

Iron opacity predictions under solar interior conditions  

Science Journals Connector (OSTI)

......predictions under solar interior conditions...using Opacity Project atomic data for...conditions within the solar convective zone...greatest binding energy per nucleon...measurements for photon energies greater than 1...region of the solar convective zone...for the Opacity Project (OP) and opal......

D. S. Whittaker; G. J. Tallents

2009-12-21T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


341

Economical Analysis of the Cold Air Distribution System: A Case Study  

E-Print Network (OSTI)

In this paper, we briefly introduce the super cold air distribution technique. By comparing the schemes of two air conditioning systems, including a modified air conditioning system, this paper analyzes the technique parameters and the economics...

Zhou, Z.; Xu, W.; Li, J.; Zhao, J.; Niu, L.

2006-01-01T23:59:59.000Z

342

Accommodation Zone | Open Energy Information  

Open Energy Info (EERE)

source source History View New Pages Recent Changes All Special Pages Semantic Search/Querying Get Involved Help Apps Datasets Community Login | Sign Up Search Page Edit History Facebook icon Twitter icon » Accommodation Zone Jump to: navigation, search GEOTHERMAL ENERGYGeothermal Home Print PDF Accommodation Zone Dictionary.png Accommodation Zone: Accommodation zones occur at fault intersections consisting of belts of interlocking, oppositely dipping normal faults. Multiple subsurface fault intersections in these zones are a favorable host for geothermal activity. Other definitions:Wikipedia Reegle Controlling Structures List of controlling structures typically associated with geothermal systems: Major Normal Fault Termination of a Major Normal Fault Stepover or Relay Ramp in Normal Fault Zones

343

Solid oxide fuel cell systems with hot zones having improved reactant distribution  

DOE Patents (OSTI)

A Solid Oxide Fuel Cell (SOFC) system having a hot zone with a center cathode air feed tube for improved reactant distribution, a CPOX reactor attached at the anode feed end of the hot zone with a tail gas combustor at the opposing end for more uniform heat distribution, and a counter-flow heat exchanger for efficient heat retention.

Poshusta, Joseph C.; Booten, Charles W.; Martin, Jerry L.

2012-11-06T23:59:59.000Z

344

Proposal for the award of a contract for the design, supply, installation and commissioning of a ventilation and air conditioning system for the ECN3 experimental area and the TCC8 and GHN300 service tunnels and for the dismantling of the existing system  

E-Print Network (OSTI)

Proposal for the award of a contract for the design, supply, installation and commissioning of a ventilation and air conditioning system for the ECN3 experimental area and the TCC8 and GHN300 service tunnels and for the dismantling of the existing system

2014-01-01T23:59:59.000Z

345

Air Resources: Prevention and Control of Air Contamination and Air  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Air Resources: Prevention and Control of Air Contamination and Air Air Resources: Prevention and Control of Air Contamination and Air Pollution, Air Quality Classifications and Standards, and Air Quality Area Classifications (New York) Air Resources: Prevention and Control of Air Contamination and Air Pollution, Air Quality Classifications and Standards, and Air Quality Area Classifications (New York) < Back Eligibility Agricultural Fuel Distributor Industrial Institutional Investor-Owned Utility Local Government Multi-Family Residential Municipal/Public Utility Nonprofit Rural Electric Cooperative Schools State/Provincial Govt Transportation Tribal Government Utility Program Info State New York Program Type Environmental Regulations Provider NY Department of Environmental Conservation These regulations establish emissions limits and permitting and operational

346

Building Technologies Office: Climate Zones  

NLE Websites -- All DOE Office Websites (Extended Search)

Climate Zones to Climate Zones to someone by E-mail Share Building Technologies Office: Climate Zones on Facebook Tweet about Building Technologies Office: Climate Zones on Twitter Bookmark Building Technologies Office: Climate Zones on Google Bookmark Building Technologies Office: Climate Zones on Delicious Rank Building Technologies Office: Climate Zones on Digg Find More places to share Building Technologies Office: Climate Zones on AddThis.com... About Take Action to Save Energy Partner With DOE Activities Solar Decathlon Building America Research Innovations Research Tools Building Science Education Climate-Specific Guidance Solution Center Partnerships Meetings Publications Home Energy Score Home Performance with ENERGY STAR Better Buildings Neighborhood Program Challenge Home Guidelines for Home Energy Professionals

347

Rift Zone | Open Energy Information  

Open Energy Info (EERE)

Rift Zone Rift Zone Jump to: navigation, search GEOTHERMAL ENERGYGeothermal Home Print PDF Rift Zone Dictionary.png Rift Zone: A divergent plate boundary within a continent Other definitions:Wikipedia Reegle Tectonic Settings List of tectonic settings known to host modern geothermal systems: Extensional Tectonics Subduction Zone Rift Zone Hot Spot Non-Tectonic Strike-Slip The Rio Grande Rift exemplifies rift zone tectonics - increased volcanic activity and the formation of graben structures (reference: science-art.com) Rift valleys occur at divergent plate boundaries, resulting in large graben structures and increased volcanism. The East African Rift is an example of a continental rift zone with increased volcanism, while the Atlantic's spreading Mid-Ocean Ridge is host to an enormous amount of geothermal

348

The Enterprise Zone (Rhode Island)  

Energy.gov (U.S. Department of Energy (DOE))

The Enterprise Zone offers tax incentives to business expanding their workforce by 5% at facilities in designated enterprise zones. The tax credit is equal to 50% of the annual wages paid to a new...

349

Enterprise Zone | Open Energy Information  

Open Energy Info (EERE)

Zone Jump to: navigation, search This article is a stub. You can help OpenEI by expanding it. Retrieved from "http:en.openei.orgwindex.php?titleEnterpriseZone&oldid542697"...

350

The Galactic Habitable Zone  

SciTech Connect

We propose the concept of a "Galactic Habitable Zone" (GHZ). Similar to the circumstellar habitable zone (CHZ), the GHZ is that region in a spiral galaxy where life can exist. The width of the GHZ is controlled by two factors. The inner (closest to the center of the galaxy) limit is set by threats to complex life: nearby transient sources of ionizing radiation and comet impacts. Such threats tend to increase close to the galactic center. The outer limit is imposed by galactic chemical evolution, specifically the abundance of heavier elements. Observation of stars in the Milky Way galaxy suggests that the outer reaches of a spiral galaxy may be too poor in heavy elements to allow terrestrial complex life to exist.

Guillermo Gonzalez

2009-08-21T23:59:59.000Z

351

Estimates of Uncertainty in multi-zoned air leakage measurements  

E-Print Network (OSTI)

electrically- heated multi- family buildings. Proc. ACEEEEnergy Analysis for Multi-family Buildings: A Case Study.an example of multi-family buildings. Further introductory

Hult, Erin L.

2014-01-01T23:59:59.000Z

352

Experimental characterization of an industrial pulverized coal-fired furnace under deep staging conditions  

SciTech Connect

Measurements have been performed in a 300 MWe, front-wall-fired, pulverized-coal, utility boiler. This boiler was retrofitted with boosted over fire air injectors that allowed the operation of the furnace under deeper staging conditions. New data are reported for local mean gas species concentration of O{sub 2}, CO, CO{sub 2}, NOx, gas temperatures and char burnout measured at several ports in the boiler including those in the main combustion and staged air regions. Comparisons of the present data with our previous measurements in this boiler, prior to the retrofitting with the new over fire system, show lower O{sub 2} and higher CO concentrations for the new situation as a consequence of the lower stoichiometry in the main combustion zone associated with the present boiler operating condition. Consistently, the measured mean NOx concentrations in the main combustion zone are now lower than those obtained previously, yielding emissions below 500 mg/Nm{sup 3}at 6% O{sub 2}. Finally, the measured values of particle burnout at the furnace exit are acceptable being those measured in the main combustion zone comparable with those obtained with the conventional over fire system.

Costa, M.; Azevedo, J.L.T. [Universidade Tecnica de Lisboa, Lisbon (Portugal)

2007-07-01T23:59:59.000Z

353

Study on one-dimensional steady combustion of highly densified biomass briquette (bio-coke) in air flow  

Science Journals Connector (OSTI)

Abstract Combustion experiments on cylindrical bio-coke (BIC), a highly densified biomass briquette, have been conducted to observe whether quasi-one-dimensional steady combustion can be attained in room temperature air flow. In the experiments, the air flow velocity was the main test condition and the fuel consumption rate when the bottom surface of the BIC sample burned was evaluated as the regression rate of the combustion zone at the bottom surface. In addition, one-dimensional calculations based on an energy equation at the combustion zone were conducted to understand the mechanism that results in steady combustion and predict the effect of water and volatile matter content in BIC on the extinction limit. The results showed that steady combustion of the BIC sample could be attained in 4.67m/s or more, and, in contrast, extinction was observed in 3.82m/s or less. The critical regression rate explained by the combustion zone temperature was shown, and the reason combustion becomes unsteady could be explained by the energy balance at the combustion zone. Though the main reason for extinction was radiation heat loss, the heat loss by water and volatile matter was not negligible. Therefore, the effect of water and volatile matter content on steady combustion must be considered.

Takero Nakahara; Hui Yan; Hiroyuki Ito; Osamu Fujita

2014-01-01T23:59:59.000Z

354

Alberta Health Services, Calgary Zone  

E-Print Network (OSTI)

Organizational Chart ­ AHS, Calgary Zone, Community, Rural and Mental Health Page 12 Organizational Chart ­ AHS, Calgary Zone, Addiction and Mental Health Page 13 Organizational Chart ­ AHS, Calgary Zone, Clinical specialty care clinics. 3) Increasing efficiency in our specialty clinics. 4) Standardizing care

Habib, Ayman

355

Two-zone countercurrent smelter system and process  

DOE Patents (OSTI)

A process for continuously smelting iron ore by use of coal to yield molten iron or semi-steel is disclosed. The process comprises the steps of establishing a melt covered by slag; inducing the slag and the molten iron to flow countercurrently to one another, toward opposite ends of the smelter; maintaining iron oxide-reducing conditions in that zone of the smelter towards which the slag flows; maintaining carbon-oxidizing conditions in that zone of the smelter towards which the molten iron flows; continuously or semicontinuously tapping the slag from the reducing zone end of the smelter; continuously or semicontinuously tapping the molten iron from the oxidizing zone end of the smelter; and adding to both zones iron ore, coal, oxygen, and flux at addition rates sufficient to keep the molten iron in the reducing zone substantially saturated with carbon, maintain in the slag being tapped an FeO content of about 5 weight percent or less, and maintain in the molten iron being tapped a carbon content of about 0.5 to 5 weight percent. A slag dam preferably is included in the smelter, to impede the backflow of the slag from the reducing zone to the oxidizing zone. A metal bath dam with one or more flow-through portals also is preferably used, submerged below the slag dam, to impede the backflow of the hot metal.

Cox, James H. (Toronto, CA); Fruehan, Richard J. (Murrysville, PA); Elliott, deceased, John F. (late of Winchester, MA)

1995-01-01T23:59:59.000Z

356

Two-zone countercurrent smelter system and process  

DOE Patents (OSTI)

A process for continuously smelting iron ore by use of coal to yield molten iron or semi-steel is disclosed. The process comprises the steps of establishing a melt covered by slag; inducing the slag and the molten iron to flow countercurrently to one another, toward opposite ends of the smelter; maintaining iron oxide-reducing conditions in that zone of the smelter towards which the slag flows; maintaining carbon-oxidizing conditions in that zone of the smelter towards which the molten iron flows; continuously or semicontinuously tapping the slag from the reducing zone end of the smelter; continuously or semicontinuously tapping the molten iron from the oxidizing zone end of the smelter; and adding to both zones iron ore, coal, oxygen, and flux at addition rates sufficient to keep the molten iron in the reducing zone substantially saturated with carbon, maintain in the slag being tapped an FeO content of about 5 weight percent or less, and maintain in the molten iron being tapped a carbon content of about 0.5 to 5 weight percent. A slag dam preferably is included in the smelter, to impede the backflow of the slag from the reducing zone to the oxidizing zone. A metal bath dam with one or more flow-through portals also is preferably used, submerged below the slag dam, to impede the backflow of the hot metal. 8 figures.

Cox, J.H.; Fruehan, R.J.; Elliott, J.F.

1995-01-03T23:59:59.000Z

357

Maintaining Your Air Conditioner | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Maintaining Your Air Conditioner Maintaining Your Air Conditioner Maintaining Your Air Conditioner June 18, 2013 - 6:20pm Addthis Replacing or cleaning air conditioner filters is a critical maintenance task. | Photo courtesy of ©iStockphoto/firemanYU. Replacing or cleaning air conditioner filters is a critical maintenance task. | Photo courtesy of ©iStockphoto/firemanYU. What does this mean for me? Regular maintenance keeps your air conditioner running as efficiently as possible. Maintaining your air conditioner will save you money by extending the unit's life. An air conditioner's filters, coils, and fins require regular maintenance for the unit to function effectively and efficiently throughout its years of service. Neglecting necessary maintenance ensures a steady decline in air conditioning performance while energy use steadily increases.

358

Maintaining Your Air Conditioner | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Maintaining Your Air Conditioner Maintaining Your Air Conditioner Maintaining Your Air Conditioner June 18, 2013 - 6:20pm Addthis Replacing or cleaning air conditioner filters is a critical maintenance task. | Photo courtesy of ©iStockphoto/firemanYU. Replacing or cleaning air conditioner filters is a critical maintenance task. | Photo courtesy of ©iStockphoto/firemanYU. What does this mean for me? Regular maintenance keeps your air conditioner running as efficiently as possible. Maintaining your air conditioner will save you money by extending the unit's life. An air conditioner's filters, coils, and fins require regular maintenance for the unit to function effectively and efficiently throughout its years of service. Neglecting necessary maintenance ensures a steady decline in air conditioning performance while energy use steadily increases.

359

Strategy Guideline: Compact Air Distribution Systems  

SciTech Connect

This Strategy Guideline discusses the benefits and challenges of using a compact air distribution system to handle the reduced loads and reduced air volume needed to condition the space within an energy efficient home. Traditional systems sized by 'rule of thumb' (i.e., 1 ton of cooling per 400 ft2 of floor space) that 'wash' the exterior walls with conditioned air from floor registers cannot provide appropriate air mixing and moisture removal in low-load homes. A compact air distribution system locates the HVAC equipment centrally with shorter ducts run to interior walls, and ceiling supply outlets throw the air toward the exterior walls along the ceiling plane; alternatively, high sidewall supply outlets throw the air toward the exterior walls. Potential drawbacks include resistance from installing contractors or code officials who are unfamiliar with compact air distribution systems, as well as a lack of availability of low-cost high sidewall or ceiling supply outlets to meet the low air volumes with good throw characteristics. The decision criteria for a compact air distribution system must be determined early in the whole-house design process, considering both supply and return air design. However, careful installation of a compact air distribution system can result in lower material costs from smaller equipment, shorter duct runs, and fewer outlets; increased installation efficiencies, including ease of fitting the system into conditioned space; lower loads on a better balanced HVAC system, and overall improved energy efficiency of the home.

Burdick, A.

2013-06-01T23:59:59.000Z

360

CHAMPS-Multizone?A Combined Heat, Air, Moisture and Pollutant Simulation Environment for Whole-building Performance Analysis  

E-Print Network (OSTI)

supply air temperature HVAC filter (only in filter case) OAof HVAC air handler as supply and return zones Filters canfilter efficiency for extensive property E Two different types of HVAC

Feng, Wei

2014-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


361

Heat transfer characteristics of laminar methane/air flame impinging normal to a cylindrical surface  

SciTech Connect

An experimental study has been conducted to determine the heat transfer characteristics of methane/air laminar flames impinging normal to a cylindrical surface. Effects of variations in the values of Reynolds number (Re = 600-1300), equivalence ratio ({phi} = 0.8-1.3), dimensionless separation distance (H/d = 1-5), and burner diameter to cylinder diameter ratio (d/D = 0.0538-0.1076) have been investigated. Three important configurations, viz., flame inner reaction zone far away, just touching and intercepted by the impingement surface, were examined in detail. High stagnation point heat fluxes were obtained when tip of the flame inner reaction zone just touched the target surface. Stagnation point heat fluxes were either zero or negative when the inner reaction zone was intercepted by the impingement surface. An off-stagnation peak in heat flux was obtained at moderate separation distances above the flame tip. Both stagnation point and peak heat fluxes increased with Re when the inner reaction zone length was less than the separation distance. Heat fluxes in the wall-jet region were high at high Re. Maximum heat fluxes were obtained for initially fuel-rich mixture conditions due to entrainment of the surrounding air. Smaller burner diameters produced high heat flux at the stagnation region for fixed Reynolds number and opposite trends were seen in the wall-jet region. A secondary rise in stagnation point heat flux was obtained at larger separation distances. This secondary rise in heat flux was quite significant for larger burner diameters and at low flow rates. Correlations were developed for stagnation point heat flux. Results were also compared with flat plate under identical operating conditions. (author)

Chander, Subhash; Ray, Anjan [Department of Mechanical Engineering, Indian Institute of Technology, Delhi, New Delhi 110 016 (India)

2007-11-15T23:59:59.000Z

362

Cracking of Composite Modified Alloy 825 Primary Air Port Tubes  

SciTech Connect

Twenty primary air ports fabricated from modified Alloy 825-based composite tubes underwent a metallurgical examination to document the mode and extent of cracking on the external fireside surface of a kraft recovery boiler. Collectively, the crack features found are most consistent with thermal fatigue, but corrosion fatigue cannot be ruled out. Regardless of the true cracking mechanism, temperature cycling is implicated as a critical factor for crack propagation. on the basis of the relative crack lengths observed, membrane welds and tube weld repairs, and their adjacent heat-affected zones, appear to be more susceptible to cracking than the cladding itself. This work suggests that mills should avoid boiler operating conditions that promote large temperature fluctuations, which can cause Alloy 825-based composite tubes to crack.

Kish, Joseph R. [Paprican; Keiser, James R [ORNL; Singbeil, Douglas [Paprican; Willoughby, Adam W [ORNL; Longmire, Hu Foster [ORNL

2007-04-01T23:59:59.000Z

363

Optimal supply air temperature with respect to energy use in a variable air volume system  

Science Journals Connector (OSTI)

In a variable air volume (VAV) system with 100% outdoor air, the cooling need in the building is satisfied with a certain air flow at a certain supply air temperature. To minimize the system energy use, an optimal supply air temperature can be set dependent on the load, specific fan power (SFP), chiller coefficient of performance, outdoor temperature and the outdoor relative humidity. The theory for an optimal supply air temperature is presented and the heating, ventilation and air-conditioning (HVAC) energy use is calculated depending on supply air temperature control strategy, average U-value of the building envelope and two outdoor climates. The analyses show that controlling the supply air temperature optimally results in a significantly lower HVAC energy use than with a constant supply air temperature. The optimal average U-value of the building envelope is in practise mostly zero.

Fredrik Engdahl; Dennis Johansson

2004-01-01T23:59:59.000Z

364

Liquid zone seal  

DOE Patents (OSTI)

A seal assembly that provides a means for establishing multiple pressure zones within a system. The seal assembly combines a plate extending from the inner wall of a housing or inner enclosure that intersects with and is immersed in the fluid contained in a well formed in a tray contained within the enclosure. The fluid is a low vapor pressure oil, chemically inert and oxidation resistant. The use of a fluid as the sealing component provides a seal that is self-healing and mechanically robust not subject to normal mechanical wear, breakage, and formation of cracks or pinholes and decouples external mechanical vibrations from internal structural members.

Klebanoff, Leonard E. (Dublin, CA)

2001-01-01T23:59:59.000Z

365

The air plasma spraying  

Science Journals Connector (OSTI)

The air plasma spraying is characterized by using of a compressed air as a plasma forming gas. Here is shown the application of benefits of the present technology compared with other spraying process. The creation of the present process was possible due to a reliable plasma torch and certain condition of heating and deposition of powder materials on a work. Plasma torch develops a power up to 50 kW and can work during 14 hours without replacement of a cathode and during 25 hours as for an anode what is acceptable for industrial application. When spraying of coatings a minimum waste of alloying elements is attained with slight increase of oxygen in coating which is comparable with argon plasma spraying in the open. In certain cases the air plasma spraying allows to obtain more perfect coatings and at high performance. The present method finds large application at restoration and strengthening of machine parts, at forming of components etc. The air plasma spraying provides high quality coatings at low cost of components.

Valery S. Klubnikin

1993-01-01T23:59:59.000Z

366

Air Corrosivity in U.S. Outdoor-Air-Cooled Data Centers is Similar to That  

NLE Websites -- All DOE Office Websites (Extended Search)

Air Corrosivity in U.S. Outdoor-Air-Cooled Data Centers is Similar to That Air Corrosivity in U.S. Outdoor-Air-Cooled Data Centers is Similar to That in Conventional Data Centers Title Air Corrosivity in U.S. Outdoor-Air-Cooled Data Centers is Similar to That in Conventional Data Centers Publication Type Report LBNL Report Number LBNL-4951E Year of Publication 2011 Authors Coles, Henry C., Tae Won Han, Phillip N. Price, Ashok J. Gadgil, and William F. Tschudi Date Published 03/2011 Abstract There is a concern that environmental-contamination caused corrosion may negatively affect Information Technology (IT) equipment reliability. Nineteen data centers in the United States and two in India were evaluated using Corrosion Classification Coupons (CCC) to assess environmental air quality as it may relate IT equipment reliability. The data centers were of two basic types: "closed" and outside-air cooled. A closed data center provides cool air to the IT equipment using air conditioning in which only a small percentage of the recirculation air is "make-up" air continuously supplied from outside to meet human health requirements. An outside-air cooled data center uses outside air directly as the primary source for IT equipment cooling. Corrosion measuring coupons containing copper and silver metal strips were placed in both "closed" and outside-air cooled data centers. The coupons were placed at each data center (closed and outside-air cooled types) with the location categorized into three groups:

367

Truman STaTe univerSiTyWELCOME HOME! Air Conditioner  

E-Print Network (OSTI)

air conditioner requests.If you need air conditioning and are assigned to Centennial,Grim,or Fair,Missouri Hall,Ryle Hall and West Campus Suites have air conditioning included).The documentation must that requires the need for air conditioning. Please fill out the form on the reverse side of this sheet, attach

Gering, Jon C.

368

Energy performance of underfloor air distribution systems part IV: underfloor plenum testing and modeling  

E-Print Network (OSTI)

loss of control of the supply air temperature from thecontrol of the thermal conditions above and below the plenum. Hence, a relatively low plenum supply air temperature

Bauman, Fred; Jin, Hui

2007-01-01T23:59:59.000Z

369

Fatigue and Creep Crack Propagation behaviour of Alloy 617 in the Annealed and Aged Conditions  

SciTech Connect

The crack propagation behaviour of Alloy 617 was studied under various conditions. Elevated temperature fatigue and creep-fatigue crack growth experiments were conducted at 650 and 800 degrees C under constant stress intensity (triangle K) conditions and triangular or trapezoidal waveforms at various frequencies on as-received, aged, and carburized material. Environmental conditions included both laboratory air and characteristic VHTR impure helium. As-received Alloy 617 displayed an increase in the crack growth rate (da/dN) as the frequency was decreased in air which indicated a time-dependent contribution component in fatigue crack propagation. Material aged at 650C did not display any influence on the fatigue crack growth rates nor the increasing trend of crack growth rate with decreasing frequency even though significant microstructural evolution, including y (Ni3Al) after short times, occurred during aging. In contrast, carburized Alloy 617 showed an increase in crack growth rates at all frequencies tested compared to the material in the standard annealed condition. Crack growth studies under quasi-constant K (i.e. creep) conditions were also completed at 650 degrees C and a stress intensity of K = 40 MPa9 (square root)m. The results indicate that crack growth is primarily intergranular and increased creep crack growth rates exist in the impure helium environment when compared to the results in laboratory air. Furthermore, the propagation rates (da/dt) continually increased for the duration of the creep crack growth either due to material aging or evolution of a crack tip creep zone. Finally, fatigue crack propagation tests at 800 degrees C on annealed Alloy 617 indicated that crack propagation rates were higher in air than impure helium at the largest frequencies and lowest stress intensities. The rates in helium, however, eventually surpass the rates in air as the frequency is reduced and the stress intensity is decreased which was not observed at 650 degrees C.

Julian K. Benz; Richard N. Wright

2013-10-01T23:59:59.000Z

370

Impact of Infiltration and Ventilation on Measured Space Conditioning...  

Energy Savers (EERE)

to provide needed ventilation under drier summer and winter conditions and reduce the air introduced during periods of peak space conditioning. For more information, see the...

371

Western Renewable Energy Zones (Presentation)  

SciTech Connect

This presentation summarizes recent developments and trends pertaining to competitive renewable energy zones, transmission planning and the integration of renewable generation resources.

Hein, J.

2011-06-01T23:59:59.000Z

372

Enhanced air/fuel mixing for automotive Stirling engine turbulator-type combustors  

SciTech Connect

This patent describes a combustor for use in a Stirling engine and the like. It comprises: a combustor chamber; a fuel inlet couple to the chamber to inject fuel therein; a turbulator means disposed in the chambers downstream of the fuel inlet means for injecting combustion air into the chamber, the turbulator means being so positioned to cause a mixing of the combustion air and fuel injected in the chamber; diverter means for dividing the combustion air and creating a primary mixing zone downstream fa the primary mixing zone; and wherein the primary mixing zone comprises a fuel rich zone where combustion initiates and the secondary mixing zone has sufficient combustion air to complete combustion of the fuel.

Riecke, G.T.; Stotts, R.E.

1992-02-25T23:59:59.000Z

373

Beyond Earth: Designing Root Zone Environments for Reduced Gravity Conditions  

Science Journals Connector (OSTI)

...unsuitable for plant growth in greenhouses. Volumetric water content-based...estimates under artificial lighting (860 mumol m2 d1) can reach...to manage water in the Svet Greenhouse on board the Russian Space...force-drained systems (e.g., greenhouse production) is preferred...

Scott B. Jones; Dani Or; Robert Heinse; Markus Tuller

374

Indoor Air Quality Forms 169 This section of the document is a collec-  

E-Print Network (OSTI)

Indoor Air Quality Forms 169 This section of the document is a collec- tion of the forms the investigator collect his or her thoughts. Indoor Air Quality Forms #12;: to be used in con- junction with the Zone/Room Record when calculating quantities of outdoor air

375

DOE Requires Air-Con International to Cease Sales of Inefficient Air  

NLE Websites -- All DOE Office Websites (Extended Search)

Requires Air-Con International to Cease Sales of Inefficient Requires Air-Con International to Cease Sales of Inefficient Air Conditioners and Proposes Penalties DOE Requires Air-Con International to Cease Sales of Inefficient Air Conditioners and Proposes Penalties September 21, 2010 - 6:43pm Addthis The Department has issued a Notice of Noncompliance Determination and Proposed Civil Penalty to Air-Con, International, requiring Air-Con to cease the sale of certain air-conditioning systems in the United States and proposing a civil penalty of $231,090 for sales of these products in violation of the applicable energy efficiency standards. This action reflects the Department's continued commitment to act aggressively to remove unlawful products from the market. In March, 2010, the Department issued a subpoena requiring Air-Con to

376

Site-Scale Saturated Zone Flow Model  

SciTech Connect

The purpose of this model report is to document the components of the site-scale saturated-zone flow model at Yucca Mountain, Nevada, in accordance with administrative procedure (AP)-SIII.lOQ, ''Models''. This report provides validation and confidence in the flow model that was developed for site recommendation (SR) and will be used to provide flow fields in support of the Total Systems Performance Assessment (TSPA) for the License Application. The output from this report provides the flow model used in the ''Site-Scale Saturated Zone Transport'', MDL-NBS-HS-000010 Rev 01 (BSC 2003 [162419]). The Site-Scale Saturated Zone Transport model then provides output to the SZ Transport Abstraction Model (BSC 2003 [164870]). In particular, the output from the SZ site-scale flow model is used to simulate the groundwater flow pathways and radionuclide transport to the accessible environment for use in the TSPA calculations. Since the development and calibration of the saturated-zone flow model, more data have been gathered for use in model validation and confidence building, including new water-level data from Nye County wells, single- and multiple-well hydraulic testing data, and new hydrochemistry data. In addition, a new hydrogeologic framework model (HFM), which incorporates Nye County wells lithology, also provides geologic data for corroboration and confidence in the flow model. The intended use of this work is to provide a flow model that generates flow fields to simulate radionuclide transport in saturated porous rock and alluvium under natural or forced gradient flow conditions. The flow model simulations are completed using the three-dimensional (3-D), finite-element, flow, heat, and transport computer code, FEHM Version (V) 2.20 (software tracking number (STN): 10086-2.20-00; LANL 2003 [161725]). Concurrently, process-level transport model and methodology for calculating radionuclide transport in the saturated zone at Yucca Mountain using FEHM V 2.20 are being carried out in the model report, ''Site-Scale Saturated Zone Transport'', MDL-NBS-HS-000010 Rev 01 (BSC 2003 [162419]). The velocity fields are calculated by the flow model, described herein, independent of the transport processes, and are then used as inputs to the transport model. Justification for this abstraction is presented in the model report, ''Saturated Zone Flow and Transport Model Abstraction'', MDL-NBS-HS-000021 (BSC 2003 [164870]).

G. Zyvoloski

2003-12-17T23:59:59.000Z

377

Building America Case Study: Evaluating Through-Wall Air Transfer...  

Energy Savers (EERE)

the performance of market-available through-wall air transfer fans with respect to Air Conditioning Contractors of America (ACCA) Manual RS and ASHRAE Standard 55-2010...

378

Optimizing Electric Humidifier Operation with an Air Side Economizer  

E-Print Network (OSTI)

Air side economizer cycle is a control scheme that is often used in WAC systems to reduce cooling energy consumption by introducing variable quantities of ambient air into a conditioned space to satisfy the space cooling load (free cooling...

Shami, U. F.

1996-01-01T23:59:59.000Z

379

E-Print Network 3.0 - air service management Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

2010 Summary: Management Policy: 2.1 ASHRAE: American Society of Heating, Refrigeration & Air-Conditioning Engineers 2... of the supplied air with the air already in the room. 3.0...

380

Chapter 28 - Air Quality Status and Trends  

Science Journals Connector (OSTI)

Abstract This chapter describes the condition of air quality, based on air pollutant concentrations, i.e. criteria pollutants, in airsheds around the world, as well as certain air toxics in urban areas and hot spots. The variability of pollutant concentrations in space and time are discussed, as well as differences in air pollution between more industrialized and economically developed regions vs developing nations. The status and trends of atmospheric concentrations of tropospheric ozone, oxides of nitrogen, oxides of sulfur, carbon monoxide, lead, and particulate matter are discussed. Examples of air toxics include benzene, polycyclic aromatic hydrocarbons, dioxins, aldehydes, and metals, e.g. mercury. Regional and global trends include acid deposition, depletion of the stratospheric ozone layer, and climate change. Indoor air quality is discussed. The chapter concludes with a description of an air quality index.

Daniel Vallero

2014-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


381

Air handling unit supply air temperature optimal control during economizer cycles  

Science Journals Connector (OSTI)

Most air handling units (AHUs) in commercial buildings have an air economizer cycle for free cooling under certain outside air conditions. During the economizer cycle, the outside air and return air dampers are modulated to seek supply air temperature at its setpoint. The supply air temperature is typically set at 55F (13C) to control humidity in the space. However, dehumidification is not necessary when the outside air is dry. Meanwhile, the space may have less cooling load due to envelope heat loss and/or occupant schedule changes. These facts provide an opportunity to use higher supply air temperature to reduce or eliminate mechanical cooling and terminal box reheat. On the contrary, a higher supply air temperature requires increased air flow as well as fan power. Therefore, an optimization question is formed, through which an optimal supply air temperature is identified to minimize total energy consumption. In this paper a steady-state energy consumption model is established for AHU systems under the economizer, and then an analytical optimization method is used to seek an optimal supply air temperature setpoint to minimize the energy cost. This paper presents AHU system energy modeling, supply air temperature optimization, simulated energy savings, and control sequence development.

Gang Wang; Li Song

2012-01-01T23:59:59.000Z

382

Air Leakage of Furnaces and Air Handlers  

NLE Websites -- All DOE Office Websites (Extended Search)

Air Leakage of Furnaces and Air Handlers Air Leakage of Furnaces and Air Handlers Title Air Leakage of Furnaces and Air Handlers Publication Type Journal Article LBNL Report Number LBNL-5553E Year of Publication 2010 Authors Walker, Iain S., Mile Lubliner, Darryl J. Dickerhoff, and William W. Delp Journal 2010 ACEEE Summer Study on Energy Efficiency in Buildings The Climate for efficiency is now Date Published 08/2010 Abstract In recent years, great strides have been made in reducing air leakage in residential and to a lesser extent small commercial forced air duct systems. Several authorities have introduced low leakage limits for thermal distribution systems; for example, the State of California Energy Code for Buildings gives credit for systems that leak less than 6% of the total air flow at 25 Pa.

383

Air Sealing for New Home Construction | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

for New Home Construction for New Home Construction Air Sealing for New Home Construction May 2, 2012 - 6:09pm Addthis Air Sealing for New Home Construction What does this mean for me? Air sealing your house properly during construction will save you energy and money. Ideally, air-sealing techniques are tailored to your site and climate zone. How does it work? Workers will seal all the paths that air can leak in and out of your new home during construction. This process requires care and attention to detail, and it's best to hire professionals with experience building energy-efficient homes. Minimizing air movement in and out of a house is key to building an energy-efficient home. Controlling air leakage is also critical to moisture control. It's always best to use techniques and materials identified as best

384

Metal-Air Batteries  

SciTech Connect

Metal-air batteries have much higher specific energies than most currently available primary and rechargeable batteries. Recent advances in electrode materials and electrolytes, as well as new designs on metal-air batteries, have attracted intensive effort in recent years, especially in the development of lithium-air batteries. The general principle in metal-air batteries will be reviewed in this chapter. The materials, preparation methods, and performances of metal-air batteries will be discussed. Two main metal-air batteries, Zn-air and Li-air batteries will be discussed in detail. Other type of metal-air batteries will also be described.

Zhang, Jiguang; Bruce, Peter G.; Zhang, Gregory

2011-08-01T23:59:59.000Z

385

Ambient Operation of Li/Air Batteries  

SciTech Connect

In this work, Li/air batteries based on nonaqueous electrolytes were investigated in ambient conditions (with an oxygen partial pressure of 0.21 atm and relative humidity of ~20%). A heat-sealable polymer membrane was used as both an oxygen-diffusion membrane and as a moisture barrier for Li/air batteries. The membrane also can minimize the evaporation of the electrolyte from the batteries. Li/air batteries with this membrane can operate in ambient conditions for more than one month with a specific energy of 362 Wh kg-1, based on the total weight of the battery including its packaging. Among various carbon sources used in this work, Li/air batteries using Ketjenblack (KB) carbon-based air electrodes exhibited the highest specific energy. However, KB-based air electrodes expanded significantly and absorbed much more electrolyte than electrodes made from other carbon sources. The weight distribution of a typical Li/air battery using the KB-based air electrode was dominated by the electrolyte (~70%). Lithium-metal anodes and KB-carbon anodes account for only 5.12% and 5.78% of the battery weight, respectively. We also found that only ~ 20% of the mesopore volume of the air electrode was occupied by reaction products after discharge. To further improve the specific energy of the Li/air batteries, the microstructure of the carbon electrode needs to be further improved to absorb much less electrolyte while still holding significant amounts of reaction products

Zhang, Jiguang; Wang, Deyu; Xu, Wu; Xiao, Jie; Williford, Ralph E.

2010-07-01T23:59:59.000Z

386

DOE Takes Action to Stop the Sales of Air-Con Air Conditioner Models Shown  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Takes Action to Stop the Sales of Air-Con Air Conditioner Takes Action to Stop the Sales of Air-Con Air Conditioner Models Shown to Violate Federal Energy Efficiency Appliance Standards DOE Takes Action to Stop the Sales of Air-Con Air Conditioner Models Shown to Violate Federal Energy Efficiency Appliance Standards September 23, 2010 - 12:00am Addthis Washington, DC - The Department of Energy announced today that it has taken action against Air-Con, International, requiring the company to stop selling certain air conditioning systems in the U.S. that have been shown to violate minimum energy efficiency appliance standards. DOE is proposing a civil penalty of more than $230,000 for importing and distributing these inefficient cooling products. This action and the proposed penalties are part of the Department's continued commitment to act aggressively to remove

387

Climate Zones | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Residential Buildings » Building America » Climate Zones Residential Buildings » Building America » Climate Zones Climate Zones Building America determines building practices based on climate zones to achieve the most energy savings in a home. This page offers some general guidelines on the definitions of the various climate regions based on heating degree-days, average temperatures, and precipitation. You can also view the Guide to Determining Climate Regions by County. Hot-Humid A hot-humid climate is generally defined as a region that receives more than 20 in. (50 cm) of annual precipitation and where one or both of the following occur: A 67°F (19.5°C) or higher wet bulb temperature for 3,000 or more hours during the warmest 6 consecutive months of the year; or A 73°F (23°C) or higher wet bulb temperature for 1,500 or more

388

The problem of vertical zoning  

Science Journals Connector (OSTI)

...deposits, genesis sheet silicates silicates talc United States Vermont Vertical zoning GeoRef, Copyright 2012, American Geosciences...levelgivingasmuchas29ouncesofgold per ton." Similar descriptionsof the Yankee Girl and other minesin the districtconvincinglydemonstrateverticalchangesin...

Charles Frederick Park

389

Unsaturated Zone Hydrology Jasper Vrugt  

E-Print Network (OSTI)

CEE 271 Unsaturated Zone Hydrology Instructor Jasper Vrugt Engineering Tower #834E / #536 (LAB) Tel.: 505-231-2698 jasper @uci.edu Office Hours: By Appointment Lecture, 1 hour; discussion, 20 minutes: ICS

Vrugt, Jasper A.

390

Wetlands and Riparian Zones | Open Energy Information  

Open Energy Info (EERE)

and Riparian Zones Jump to: navigation, search Retrieved from "http:en.openei.orgwindex.php?titleWetlandsandRiparianZones&oldid612217" Category: NEPA Resources...

391

Air Pollution Control  

Science Journals Connector (OSTI)

Petroleum and chemical processes are responsible for many emissions both into the air. Most relevant emissions into the air are nitrous oxides (NOx), sulfur oxides ... compounds (VOC).The major cause of all air pollution

Alireza Bahadori

2014-01-01T23:59:59.000Z

392

Hickam Air Force Base  

Energy.gov (U.S. Department of Energy (DOE))

Hickam Air Force Base spans 2,850 acres in Honolulu, Hawaii. The military base is home to the 15th Airlift Wing, the Hawaii Air National Guard, and the Pacific Air Forces headquarters.

393

OLYMPIC AIR QUALITY QUESTIONABLE  

Science Journals Connector (OSTI)

OLYMPIC AIR QUALITY QUESTIONABLE ... Athletes GOING FOR GOLD worry about Beijings air ... Atmospheric chemists say the air quality during the Beijing Games literally rests on which direction the winds blow. ...

RACHEL PETKEWICH

2008-07-28T23:59:59.000Z

394

Air Quality and Pollution  

Science Journals Connector (OSTI)

Air quality refers to the physical, chemical, and biological characteristics of air, both in outside space and in enclosed ... other non?industrial working places, and residencies. Air pollution is the abnormal ...

Zoran Marmut

2008-01-01T23:59:59.000Z

395

Aire Rite Finds Center for Family Business Just Right Huntington Beach Company Founded in 1972 Joins CSUF Center for Family Business  

E-Print Network (OSTI)

Beach-based Aire Rite Air Conditioning and Refrigeration to its Center membership. The premier network of multi-generational family business leaders. Aire Rite Air Conditioning and Refrigeration, Inc and optimization programs for air conditioning, building automation, food machinery, and refrigeration equipment

de Lijser, Peter

396

Scrubbing of contaminants from contaminated air streams with aerogel materials with optional photocatalytic destruction  

SciTech Connect

Disclosed is a method for separating a vaporous or gaseous contaminant from an air stream contaminated therewith. This method includes the steps of: (a) passing said contaminated air into a contact zone in which is disposed an aerogel material capable of selecting adsorbing said contaminant from air and therein contacting said contaminated air with an aerogel material; and (b) withdrawing from said zone, air depleted of said contaminant. For present purposes, "contaminant" means a material not naturally occurring in ambient air and/or a material naturally occurring in air but present at a concentration above that found in ambient air. Thus, the present invention scrubs (or treats) air for the purpose of returning it to its ambient composition. Also disclosed herein is a process for the photocatalytic destruction of contaminants from an air stream wherein the contaminated air stream is passed into a control cell or contact zone in which is disposed a photocatalytic aerogel and exposing said aerogel to ultraviolet (UV) radiation for photocatalytically destroying the adsorbed contaminant, and withdrawing from said cell an exhaust air stream depleted in said contaminant.

Attia, Yosry A. (221 Oakland Park Ave., Columbus, OH 43214)

2000-01-01T23:59:59.000Z

397

Outside Air Ventilation Controller - Building America Top Innovation...  

Energy Savers (EERE)

demand up to 50% in California's central valley climates and can eliminate the need for air conditioning altogether in the coastal climate. Variations of these systems are being...

398

Covered Product Category: Residential Air-Source Heat Pumps ...  

Office of Energy Efficiency and Renewable Energy (EERE) Indexed Site

excluded. Specify or select products that are ENERGY STAR-qualified. To find qualified products, go to the Consortium for Energy Efficiency (CEE) and Air Conditioning and...

399

Development of an isothermal 2D zonal air volume model with impulse  

NLE Websites -- All DOE Office Websites (Extended Search)

Development of an isothermal 2D zonal air volume model with impulse Development of an isothermal 2D zonal air volume model with impulse conservation Title Development of an isothermal 2D zonal air volume model with impulse conservation Publication Type Conference Paper Year of Publication 2010 Authors Victor, Norrefeldt, Thierry Stephane Nouidui, and Gunnar Gruen Conference Name Clima 2010, 10th Rehva World Congress "Sustainable Energy Use in Buildings" Conference Location Antalya, Turkey Abstract This paper presents a new approach to model air flows with a zonal model. The aim of zonal models is to perform quick simulations of the air distribution in rooms. Therefore an air volume is subdivided into several discrete zones, typically 10 to 100. The zones are connected with flow elements computing the amount of air exchanged between them. In terms of complexity and needed computational time zonal models are a compromise between CFDcalculations and the approximation of perfect mixing. In our approach the air flow velocity is used as property of the zones. Thus the distinction between normal zones and jet or plume influenced zones becomes obsolete. The model is implemented in the object oriented and equation based language Modelica. A drawback of the new formulation is that the calculated flow pattern depends on the discretization. Nevertheless, the results show that the new zonal model performs well and is a useful extension to existing models.

400

Modeling Building Thermal Response to HVAC Zoning Virginia Smith  

E-Print Network (OSTI)

Modeling Building Thermal Response to HVAC Zoning Virginia Smith Department of Computer Science HVAC systems account for 38% of building energy usage. Studies have indicated at least 5-15% waste due to unoccu- pied spaces being conditioned. Our goal is to minimize this waste by retrofitting HVAC systems

Whitehouse, Kamin

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


401

Category:ASHRAE Climate Zones | Open Energy Information  

Open Energy Info (EERE)

ASHRAE Climate Zones ASHRAE Climate Zones Jump to: navigation, search Climate Zones defined in the ASHRAE 169-2006 standards. Pages in category "ASHRAE Climate Zones" The following 30 pages are in this category, out of 30 total. C Climate Zone 1A Climate Zone 1B Climate Zone 2A Climate Zone 2B Climate Zone 3A Climate Zone 3B Climate Zone 3C Climate Zone 4A Climate Zone 4B Climate Zone 4C C cont. Climate Zone 5A Climate Zone 5B Climate Zone 5C Climate Zone 6A Climate Zone 6B Climate Zone 7A Climate Zone 7B Climate Zone 8A Climate Zone 8B Climate Zone Number 1 C cont. Climate Zone Number 2 Climate Zone Number 3 Climate Zone Number 4 Climate Zone Number 5 Climate Zone Number 6 Climate Zone Number 7 Climate Zone Number 8 Climate Zone Subtype A Climate Zone Subtype B Climate Zone Subtype C Retrieved from

402

Initial Conditions  

Science Journals Connector (OSTI)

Before we can run a transient analysis, we must find the appropriate set of initial conditions for the variables. The most important requirement of initial conditions is that they do not contradict any of the ...

Michael Tiller Ph.D.

2001-01-01T23:59:59.000Z

403

E-Print Network 3.0 - air treatment system Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

Last Updated: 41702 Summary: , including refrigeration, air conditioning, heating systems, ventilating fans, roof ventilators, exhaust fans... , water treatment equipment,...

404

E-Print Network 3.0 - air handling systems Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

Last Updated: 41702 Summary: , including refrigeration, air conditioning, heating systems, ventilating fans, roof ventilators, exhaust fans... , water treatment equipment,...

405

A dual pore carbon aerogel based air cathode for a highly rechargeable lithium-air battery  

Science Journals Connector (OSTI)

Abstract Cathode structure plays a vital role in lithium-air battery for that it can provide space for discharged products accommodation and free path for oxygen, e? and Li+ transport. However, pore blockage, cathode passivation and degradation all result in low discharge rates and poor cycling capability. To get rid of these predicaments, a novel highly conductive dual pore carbon aerogel based air cathode is fabricated to construct a lithium-air battery, which exhibits 18 to 525 cycles in the LiTFSI/sulfolane electrolyte at a current density varying from 1.00mAcm?2 to 0.05mAcm?2, accompanied by a high energy efficiency of 78.32%. We postulate that the essence lies in that the as-prepared air cathode inventively create a suitable tri-phase boundary reaction zone, facilitating oxygen and Li+ diffusion in two independant pore channels, thus realizing a relative higher discharge rate capability, lower pore blockage and cathode passivation. Further, pore structure, carbon loading, rate capability, discharge depth and the air's effect are exploited and coordinated, targeting for a high power and reversible lithium-air battery. Such nano-porous carbon aerogel air cathode of novel dual pore structure and material design is expected to be an attractive alternative for lithium-air batteries and other lithium based batteries.

Fang Wang; Yang-Hai Xu; Zhong-Kuan Luo; Yan Pang; Qi-Xing Wu; Chun-Sheng Liang; Jing Chen; Dong Liu; Xiang-hua Zhang

2014-01-01T23:59:59.000Z

406

Innovation and Success in Planning and Zoning  

Energy.gov (U.S. Department of Energy (DOE))

This document summarizes several successful initiatives to implement solar-friendly planes and zoning codes.

407

Hot Air Stratification of Ceiling Air Supply in a Large Space Building  

E-Print Network (OSTI)

ICEBO2006, Shenzhen, China Maximize Comfort: Temperature, Humidity and IAQ Vol.I-5-3 Hot Air Stratification of Ceiling Air Supply in a Large Space Building Hanqing Wang Zhiyong Wang Changrong Liu Ph.D. Professor Doctoral... of flow and temperature fields in atrium with ceiling height of 130 m [J]. ASHRAE Trans, 1995, 101(2): 1144-1157. [9] Wang han-qing, et al. Numerical simulation research on delaminating phenomena of ordinary air-conditional room [J]. Journal...

Wang, H.; Wang, Z.; Liu, C.

2006-01-01T23:59:59.000Z

408

Air Pollution Spring 2010  

E-Print Network (OSTI)

and control. 6. Examine regional and global air pollution issues. Prerequisite: CHEM 113 and (MATH 261 or MATHATS 555 Air Pollution Spring 2010 T Th 11:00 ­ 12:15, NESB 101 Instructor: Prof. Sonia Kreidenweis an understanding of types and sources of air pollution. 2. Examine concentrations of air pollutants

409

Under consideration for publication in J. Fluid Mech. 1 The fluid dynamics of an underfloor air  

E-Print Network (OSTI)

conditioning was invented by Willis Haviland Carrier. Carrier had his first patent `Apparatus for Treating Air the term `air conditioning' in a 1906 patent claim. Cooling for human comfort, rather than industrial need, began in 1924, in the J.L. Hudson Department Store in Detroit, Michigan. Air conditioning of apartments

Linden, Paul F.

410

Advanced Strategy Guideline: Air Distribution Basics and Duct Design  

SciTech Connect

This report discusses considerations for designing an air distribution system for an energy efficient house that requires less air volume to condition the space. Considering the HVAC system early in the design process will allow adequate space for equipment and ductwork and can result in cost savings. Principles discussed that will maximize occupant comfort include delivery of the proper amount of conditioned air for appropriate temperature mixing and uniformity without drafts, minimization of system noise, the impacts of pressure loss, efficient return air duct design, and supply air outlet placement, as well as duct layout, materials, and sizing.

Burdick, A.

2011-12-01T23:59:59.000Z

411

Reactive Air Aluminization  

SciTech Connect

Ferritic stainless steels and other alloys are of great interest to SOFC developers for applications such as interconnects, cell frames, and balance of plant components. While these alloys offer significant advantages (e.g., low material and manufacturing cost, high thermal conductivity, and high temperature oxidation resistance), there are challenges which can hinder their utilization in SOFC systems; these challenges include Cr volatility and reactivity with glass seals. To overcome these challenges, protective coatings and surface treatments for the alloys are under development. In particular, aluminization of alloy surfaces offers the potential for mitigating both evaporation of Cr from the alloy surface and reaction of alloy constituents with glass seals. Commercial aluminization processes are available to SOFC developers, but they tend to be costly due to their use of exotic raw materials and/or processing conditions. As an alternative, PNNL has developed Reactive Air Aluminization (RAA), which offers a low-cost, simpler alternative to conventional aluminization methods.

Choi, Jung-Pyung; Chou, Y. S.; Stevenson, Jeffry W.

2011-10-28T23:59:59.000Z

412

Confined Zone Dispersion Project: A DOE assessment  

SciTech Connect

The goal of the US Department of Energy (DOE) Clean Coal Technology (CCT) program is to furnish the energy marketplace with a number of advanced, more efficient, and environmentally responsible coal utilization technologies through demonstration projects. These projects seek to establish the commercial feasibility of the most promising advanced coal technologies that have developed beyond the proof-of-concept (POC) stage. This document serves as a DOE post-project assessment of the Confined Zone Dispersion Project in CCT Round 3. In 1990, Bechtel Corporation entered into a cooperative agreement to conduct the demonstration project. The Seward Power Station of Pennsylvania Electric Company (now GPU Genco) was the host site. DOE funded 43 percent of the total project cost of $12,173,000. The project was started in June 1990 and was scheduled to be completed in June 1993. As a result of various operating problems, the schedule was extended into 1994 without additional cost to DOE. Bechtel provided the additional financing and GPU Genco provided electricity, steam, and water to operate the unit. The independent evaluation contained herein is based primarily on information from Bechtel's final technical report (1994) as well as other references cited. Confined Zone Dispersion (CZD) is a flue gas desulfurization (FGD) process that removes sulfur dioxide (SO{sub 2}). A finely atomized slurry of reactive lime, calcium hydroxide or Ca(OH){sub 2} is injected into the flue-gas duct work, between the air preheater and the second-stage ESP. The lime reacts with the SO{sub 2}, forming dry solid reaction products. The downstream ESP captures the 2 reaction products along with the fly ash entrained in the flue gas. The CZD process was demonstrated on Unit 5, a 147-MWe utility unit with two flue gas ducts. One of the ducts was extended to provide the requisite residence time and retrofitted with the CZD lime injection equipment.

NONE

1999-11-30T23:59:59.000Z

413

The Effect of Reduced Evaporator Air Flow on the Performance of a Residential Central Air Conditioner  

E-Print Network (OSTI)

This paper discusses the measured degradation in performance of a residential air conditioning system operating under reduced evaporator air flow. Experiments were conducted using a R-22 three-ton split-type cooling system with a short-tube orifice...

Palani, M.; O'Neal, D.; Haberl, J.

414

Effect of Outside Air Ventilation Rate on Volatile Organic Compound  

NLE Websites -- All DOE Office Websites (Extended Search)

Outside Air Ventilation Rate on Volatile Organic Compound Outside Air Ventilation Rate on Volatile Organic Compound Concentrations in a Call Center Title Effect of Outside Air Ventilation Rate on Volatile Organic Compound Concentrations in a Call Center Publication Type Journal Article Year of Publication 2003 Authors Hodgson, Alfred T., David Faulkner, Douglas P. Sullivan, Dennis L. DiBartolomeo, Marion L. Russell, and William J. Fisk Journal Atmospheric Environment Volume 37 Start Page Chapter Pagination 5517-5528 Abstract A study of the relationship between outside air ventilation rate and concentrations of volatile organic compounds (VOCs) generated indoors was conducted in a call center office building. The building, with two floors and a floor area of 4,600 m2, was located in the San Francisco Bay Area, CA. Ventilation rates were manipulated with the building's four air handling units (AHUs). VOC concentrations in the AHU returns were measured on seven days during a 13-week period. VOC emission factors were determined for individual zones on days when they were operating at near steady-state conditions. The emission factor data were subjected to principal component (PC) analysis to identify groups of co-varying compounds. Potential sources of the PC vectors were ascribed based on information from the literature supporting the associations. Two vectors with high loadings of compounds including formaldehyde, 2,2,4-trimethyl-1,3- pentanediol monoisobutyrate, decamethylcyclopentasiloxane (d5 siloxane), and isoprene likely identified occupant-related sources. One vector likely represented emissions from building materials. Another vector represented emissions of solvents from cleaning products. The relationships between indoor minus outdoor VOC concentrations and ventilation rate were qualitatively examined for eight VOCs. Of these, acetaldehyde and hexanal, which were likely associated with material sources, and d5 siloxane exhibited general trends of higher concentrations at lower ventilation rates. For other compounds, the operation of the building and variations in pollutant generation and removal rates apparently combined to obscure the inverse relationship between VOC concentrations and ventilation. This result emphasizes the importance of utilizing source control measures, in addition to adequate ventilation, to limit concentrations of VOCs of concern in office buildings

415

Modeling biogechemical reactive transport in a fracture zone  

SciTech Connect

A coupled model of groundwater flow, reactive solute transport and microbial processes for a fracture zone of the Aspo site at Sweden is presented. This is the model of the so-called Redox Zone Experiment aimed at evaluating the effects of tunnel construction on the geochemical conditions prevailing in a fracture granite. It is found that a model accounting for microbially-mediated geochemical processes is able to reproduce the unexpected measured increasing trends of dissolved sulfate and bicarbonate. The model is also useful for testing hypotheses regarding the role of microbial processes and evaluating the sensitivity of model results to changes in biochemical parameters.

Molinero, Jorge; Samper, Javier; Yang, Chan Bing, and Zhang, Guoxiang; Guoxiang, Zhang

2005-01-14T23:59:59.000Z

416

The Ironies of Zoning: A Vision for the Future  

Wind Powering America (EERE)

Ironies of Zoning: Ironies of Zoning: A Vision For The Future Jim Green NREL ASES Small Wind Division Webinar January 17, 2008 2 Utility Poles Jefferson County, Colorado 3 Transmission Lines Cell Phone Towers Jefferson County, Colorado 4 How Do Wind Turbines Compare? Charlotte, Vermont 5 How Do Wind Turbines Compare? 6 Windmill... or not? Adams County, Colorado Credit: Jim Green, NREL 7 Dutch Windmills Eyesore or Cultural Icon? Eyesore or Cultural Icon? 8 American Windmills Eyesore or Cultural Icon? Eyesore or Cultural Icon? Cedaredge, Colorado Limon, Colorado 9 Vision for the Future Industry Residential Business Farm Schools * Envision a future in which wind power is embraced in the local landscape because it expresses community support for clean air, reduced carbon emissions, and strong local economies through use of a sustainable,

417

Ventilation System Effectiveness and Tested Indoor Air Quality Impacts  

SciTech Connect

Ventilation system effectiveness testing was conducted at two unoccupied, single-family, detached lab homes at the University of Texas - Tyler. Five ventilation system tests were conducted with various whole-building ventilation systems. Multizone fan pressurization testing characterized building and zone enclosure leakage. PFT testing showed multizone air change rates and interzonal airflow. Cumulative particle counts for six particle sizes, and formaldehyde and other Top 20 VOC concentrations were measured in multiple zones. The testing showed that single-point exhaust ventilation was inferior as a whole-house ventilation strategy. It was inferior because the source of outside air was not direct from outside, the ventilation air was not distributed, and no provision existed for air filtration. Indoor air recirculation by a central air distribution system can help improve the exhaust ventilation system by way of air mixing and filtration. In contrast, the supply and balanced ventilation systems showed that there is a significant benefit to drawing outside air from a known outside location, and filtering and distributing that air. Compared to the Exhaust systems, the CFIS and ERV systems showed better ventilation air distribution and lower concentrations of particulates, formaldehyde and other VOCs. System improvement percentages were estimated based on four System Factor Categories: Balance, Distribution, Outside Air Source, and Recirculation Filtration. Recommended System Factors could be applied to reduce ventilation fan airflow rates relative to ASHRAE Standard 62.2 to save energy and reduce moisture control risk in humid climates. HVAC energy savings were predicted to be 8-10%, or $50-$75/year.

Rudd, A.; Bergey, D.

2014-02-01T23:59:59.000Z

418

Enterprise Zone Program (Alabama) | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Alabama) Alabama) Enterprise Zone Program (Alabama) < Back Eligibility Commercial Construction Industrial Savings Category Alternative Fuel Vehicles Hydrogen & Fuel Cells Buying & Making Electricity Water Home Weatherization Solar Wind Program Info State Alabama Program Type Enterprise Zone Provider Alabama Department of Economic and Community Affairs The Enterprise Zone Program provides certain tax incentives to corporations, partnerships and proprietorships that locate or expand within designated Enterprise Zones. In addition to state-level tax incentives, businesses may also receive local tax and non-tax incentives for locating or expanding within a designated Enterprise Zone. Section 5 of the Alabama Enterprise Zone Program offers the following tax incentives: Credit based

419

Renewable Energy Renaissance Zones | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Renewable Energy Renaissance Zones Renewable Energy Renaissance Zones Renewable Energy Renaissance Zones < Back Eligibility Commercial Industrial Local Government Savings Category Bioenergy Solar Buying & Making Electricity Alternative Fuel Vehicles Heating & Cooling Swimming Pool Heaters Water Heating Commercial Heating & Cooling Heating Wind Maximum Rebate None Program Info Start Date 07/12/2006 State Michigan Program Type Industry Recruitment/Support Rebate Amount 100% abatement of Michigan Business Tax, state education tax, personal and real property taxes, and local income taxes Provider Michigan Economic Development Corporation In 2006, Michigan enacted legislation allowing for the creation of Renewable Energy Renaissance Zones (RERZ). Renaissance zones -- renewable energy renaissance zones are just one type -- offer significant tax

420

Enterprise Zone Program (Louisiana) | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Enterprise Zone Program (Louisiana) Enterprise Zone Program (Louisiana) Enterprise Zone Program (Louisiana) < Back Eligibility Commercial Construction Developer Fuel Distributor Industrial Installer/Contractor Institutional Investor-Owned Utility Nonprofit Retail Supplier Systems Integrator Utility Savings Category Alternative Fuel Vehicles Hydrogen & Fuel Cells Buying & Making Electricity Water Home Weatherization Solar Wind Program Info State Louisiana Program Type Corporate Tax Incentive Enterprise Zone Provider Louisiana Economic Development The Enterprise Zone Program is a jobs incentive program providing Louisiana income and franchise tax credits to businesses hiring at least 35% of net, new jobs from targeted groups. Enterprise Zones (EZs) are areas with high unemployment, low income, or a high percentage of residents receiving some

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


421

Connection of the Panama fracture zone with the Galapagos rift zone, eastern tropical Pacific  

Science Journals Connector (OSTI)

Magnetic data recently collected in the eastern tropical Pacific confirm that the Galapagos rift zone is connected to the Panama fracture zone by a short north-south...

Paul J. Grim

1970-08-01T23:59:59.000Z

422

Healthy Air Act (Maryland)  

Energy.gov (U.S. Department of Energy (DOE))

The Maryland Healthy Air Act was developed with the purpose of bringing Maryland into attainment with the National Ambient Air Quality Standards (NAAQS) for ozone and fine particulate matter by the...

423

Air and Water Pollution  

Science Journals Connector (OSTI)

Air Pollution.... Many pollutants enter our bodies through the air we breathe at 13,000l/day ... to quantitatively understand the basic environmental physics of pollution. This chapter covers the foll...

David Hafemeister

2014-01-01T23:59:59.000Z

424

Aesculap, Inc. Air Products  

E-Print Network (OSTI)

Aesculap, Inc. Air Products Air Products Foundation Alaric Compliance Services, LLC Alvin H. Butz & Herger, Inc. Sodexo Campus Services Sodexo Inc. and Affiliates Stupp Bros., Inc. Sugarbush Products, Inc

Napier, Terrence

425

Minimize Compressed Air Leaks  

Energy.gov (U.S. Department of Energy (DOE))

This tip sheet outlines a strategy for compressed air leak detection and provides a formula for cost savings calculations.

426

The Border Cities Enterprise Zone Program (Minnesota)  

Energy.gov (U.S. Department of Energy (DOE))

The Border Cities Enterprise Zone Program provides business tax credits to businesses that invest, develop, expand, and create jobs in identified Border-Cities Enterprise Zones. Companies may be...

427

Farmland Security Zone | Open Energy Information  

Open Energy Info (EERE)

Zone Jump to: navigation, search OpenEI Reference LibraryAdd to library Legal Document- OtherOther: Farmland Security ZoneLegal Abstract California Department of Conservation,...

428

Enterprise Zone Sales Tax Exemption (Kansas)  

Energy.gov (U.S. Department of Energy (DOE))

The Enterprise Zone Sales Tax Exemption offers businesses located in such economic development zones a 100 percent sales tax exemption on the purchase of labor and materials to construct or remodel...

429

Local Option- Rural Renewable Energy Development Zones  

Energy.gov (U.S. Department of Energy (DOE))

Cities, counties, or several contiguous counties in Oregon can set up Rural Renewable Energy Development Zones. The zone can only cover territory outside of the urban growth boundary of any large...

430

Air Products effective way  

E-Print Network (OSTI)

PE O A e s a b O T A O ENNST Overview Air Products effective way standard me Departm Shipping has recently y of shipping eans. Air Pro ontainer that es of this pro onduct mark eep accelera eep the cost tilize widely a earch and m m visited Air er needs wer model was cr m approache ms

Demirel, Melik C.

431

Steam generator air-cooling and ways to increase its effectiveness  

SciTech Connect

To shorten the downtime for repair of steam turbines, various methods for rapid cooling of the turbine can be used. One method is to cool the turbine with free air whose movement is controlled by a standard ejector through the flow passage in sequence of the high-, medium-, and low-pressure zones of the turbine. The effectiveness of air cooling the turbine through use of a counterflow system for controlling air flow through the turbine is discussed.

Kulichikhin, V.V.; Tazhiev, E.I.; Leshchinskii, A.M.; Zubov, P.A.

1982-10-01T23:59:59.000Z

432

Conditioning-specific reflex modification occurs when an unconditionedresponse(UR)ismodifiedinthe absence  

E-Print Network (OSTI)

not generalize from air puff to electro- dermal stimulation even though conditioning occurs to comparable levels can be obtained only at high air puff intensi- ties even though conditioning is supported by lower airConditioning-specific reflex modification occurs when an unconditionedresponse

433

Eastern Energy Zones Mapping Tool  

Energy.gov (U.S. Department of Energy (DOE))

The Eastern Interconnection States Planning Council (EISPC) has released the Energy Zones (EZ) Mapping Tool, a free, web-based interactive tool that will help states and other stakeholders in the Eastern Interconnection identify geographic areas suitable for the development of clean energy resources (natural gas, sequestration or utilitization locations for C02 from coal, nuclear, and renewable) which can potentially provide significant amounts of new electric power generation.

434

Determining the Right Air Quality for Your Compressed Air System  

Energy.gov (U.S. Department of Energy (DOE))

This tip sheet outlines the main factors for determining the right air quality for compressed air systems.

435

Experimental investigation of wood combustion in a fixed bed with hot air  

SciTech Connect

Highlights: Upward combustion is a new combustion concept with ignition by hot primary air. Upward combustion has three stages: short drying, rapid devolatilization and char combustion. Variation of fuel moisture and inert content have little influence on the combustion. Experimental comparison between conventional and upward combustion is presented. - Abstract: Waste combustion on a grate with energy recovery is an important pillar of municipal solid waste (MSW) management in the Netherlands. In MSW incinerators fresh waste stacked on a grate enters the combustion chamber, heats up by radiation from the flame above the layer and ignition occurs. Typically, the reaction zone starts at the top of the waste layer and propagates downwards, producing heat for drying and devolatilization of the fresh waste below it until the ignition front reaches the grate. The control of this process is mainly based on empiricism. MSW is a highly inhomogeneous fuel with continuous fluctuating moisture content, heating value and chemical composition. The resulting process fluctuations may cause process control difficulties, fouling and corrosion issues, extra maintenance, and unplanned stops. In the new concept the fuel layer is ignited by means of preheated air (T > 220 C) from below without any external ignition source. As a result a combustion front will be formed close to the grate and will propagate upwards. That is why this approach is denoted by upward combustion. Experimental research has been carried out in a batch reactor with height of 4.55 m, an inner diameter of 200 mm and a fuel layer height up to 1 m. Due to a high quality two-layer insulation adiabatic conditions can be assumed. The primary air can be preheated up to 350 C, and the secondary air is distributed via nozzles above the waste layer. During the experiments, temperatures along the height of the reactor, gas composition and total weight decrease are continuously monitored. The influence of the primary air speed, fuel moisture and inert content on the combustion characteristics (ignition rate, combustion rate, ignition front speed and temperature of the reaction zone) is evaluated. The upward combustion concept decouples the drying, devolatilization and burnout phase. In this way the moisture and inert content of the waste have almost no influence on the combustion process. In this paper an experimental comparison between conventional and reversed combustion is presented.

Markovic, Miladin, E-mail: m.markovic@utwente.nl; Bramer, Eddy A.; Brem, Gerrit

2014-01-15T23:59:59.000Z

436

Property:ASHRAE 169 Climate Zone Subtype | Open Energy Information  

Open Energy Info (EERE)

ASHRAE 169 Climate Zone Subtype ASHRAE 169 Climate Zone Subtype Jump to: navigation, search This is a property of type Page. Pages using the property "ASHRAE 169 Climate Zone Subtype" Showing 25 pages using this property. (previous 25) (next 25) A Abbeville County, South Carolina ASHRAE 169-2006 Climate Zone + Climate Zone Subtype A + Acadia Parish, Louisiana ASHRAE 169-2006 Climate Zone + Climate Zone Subtype A + Accomack County, Virginia ASHRAE 169-2006 Climate Zone + Climate Zone Subtype A + Ada County, Idaho ASHRAE 169-2006 Climate Zone + Climate Zone Subtype B + Adair County, Iowa ASHRAE 169-2006 Climate Zone + Climate Zone Subtype A + Adair County, Kentucky ASHRAE 169-2006 Climate Zone + Climate Zone Subtype A + Adair County, Missouri ASHRAE 169-2006 Climate Zone + Climate Zone Subtype A +

437

Property:ASHRAE 169 Climate Zone Number | Open Energy Information  

Open Energy Info (EERE)

Number Number Jump to: navigation, search This is a property of type Page. Pages using the property "ASHRAE 169 Climate Zone Number" Showing 25 pages using this property. (previous 25) (next 25) A Abbeville County, South Carolina ASHRAE 169-2006 Climate Zone + Climate Zone Number 3 + Acadia Parish, Louisiana ASHRAE 169-2006 Climate Zone + Climate Zone Number 2 + Accomack County, Virginia ASHRAE 169-2006 Climate Zone + Climate Zone Number 4 + Ada County, Idaho ASHRAE 169-2006 Climate Zone + Climate Zone Number 5 + Adair County, Iowa ASHRAE 169-2006 Climate Zone + Climate Zone Number 5 + Adair County, Kentucky ASHRAE 169-2006 Climate Zone + Climate Zone Number 4 + Adair County, Missouri ASHRAE 169-2006 Climate Zone + Climate Zone Number 5 + Adair County, Oklahoma ASHRAE 169-2006 Climate Zone + Climate Zone Number 3 +

438

Thin Air Breathing  

NLE Websites -- All DOE Office Websites (Extended Search)

Thin Air Breathing Thin Air Breathing Name: Amy Location: N/A Country: N/A Date: N/A Question: Why is it hard to breathe in thin air? What health dangers do mountain climbers face at high altitudes? Replies: Among the obvious dangers of losing ones footing, the oxygen available in the air is considerable less at higher altitudes. If I recall correctly, 21% of the atmosphere at standard temperature and pressure at sea level is composed of oxygen. This is less at higher altitudes. One can lose consciousness and even die in an oxygen deficient environment with changes from oxygen content to lower than 19.5%. This can unfortunate effect can occur within minutes. Dr. Myron The air is not really thin at high altitudes. The problem is that air pressure is lower. As altitude increases, air pressure decreases. In order for your lungs to fill with air, the air pressure in your lungs has to be less than the pressure of the air outside your lungs. Air moves from areas of higher pressure to lower pressure. As your diaphragm (the muscle that separates your chest cavity from your abdominal cavity) moves downward, the size of your chest cavity increases. This decreases the pressure in your chest and air flows in. When the diaphragm is up, it puts pressure on the chest cavity and the pressure in the lungs is greater than outside the lungs. Air flows out. This is an example of Boyle's Law. The movement of the diaphragm is controlled by the brainstem. Anyway-the reason that it is harder for some people to breathe at higher altitudes is that the air pressure differences aren't as great between the inside of the lungs and outside.

439

Enterprise Zone Program (Georgia) | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Georgia) Georgia) Enterprise Zone Program (Georgia) < Back Eligibility Agricultural Commercial Construction Developer Fuel Distributor General Public/Consumer Industrial Installer/Contractor Investor-Owned Utility Municipal/Public Utility Retail Supplier Rural Electric Cooperative Systems Integrator Transportation Tribal Government Utility Savings Category Alternative Fuel Vehicles Hydrogen & Fuel Cells Buying & Making Electricity Water Home Weatherization Solar Wind Program Info State Georgia Program Type Enterprise Zone Personal Tax Incentives Property Tax Incentive Provider Georgia Department of Community Affairs The Enterprise Zone Program provides various tax incentives to businesses within designated underdeveloped zones in rural or urban areas. The State Enterprise Zone program intends to improve geographic areas within cities

440

Enterprise Zones (Iowa) | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Zones (Iowa) Zones (Iowa) Enterprise Zones (Iowa) < Back Eligibility Agricultural Commercial Construction Fuel Distributor Industrial Installer/Contractor Institutional Investor-Owned Utility Municipal/Public Utility Nonprofit Rural Electric Cooperative Utility Savings Category Alternative Fuel Vehicles Hydrogen & Fuel Cells Buying & Making Electricity Water Home Weatherization Solar Wind Program Info State Iowa Program Type Enterprise Zone Industry Recruitment/Support Training/Technical Assistance Provider Iowa Economic Development Authority The Enterprise Zones Program is an incentive for business expansion designed to stimulate development by targeting economically distressed areas in Iowa. Through state and local tax incentives, businesses and developers are encouraged to make new investments, and create or retain

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


441

Overview: Zoning for Small Wind Turbines  

Wind Powering America (EERE)

Overview: Overview: Zoning for Small Wind Turbines Jim Green NREL ASES Small Wind Division Webinar January 17, 2008 2 Zoning Basics * Zoning is one form of land use law * Based on legal principle of "police power:" the power to regulate in order to promote the health, morals, safety, and general welfare of the community * Zoning authority originates from state laws called "zoning enabling legislation" - Standard Zoning Enabling Act, Dept. of Commerce, 1920s * Enabling legislation delegates land use authority to local jurisdictions, "Home Rule" - counties, parishes, boroughs, townships, municipalities, cities, villages, etc. 3 Zoning is Daunting * 3,034 counties (National Association of Counties) * 16,504 townships * 19,429 municipalities (National League of Cities)

442

Enhanced Enterprise Zones (Missouri) | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Enhanced Enterprise Zones (Missouri) Enhanced Enterprise Zones (Missouri) Enhanced Enterprise Zones (Missouri) < Back Eligibility Commercial Industrial Savings Category Alternative Fuel Vehicles Hydrogen & Fuel Cells Buying & Making Electricity Water Home Weatherization Solar Wind Program Info State Missouri Program Type Enterprise Zone Corporate Tax Incentive Provider Missouri Department of Economic Development Enhanced Enterprise Zones aim at attracting new businesses or promoting an expansion of existing business in Missouri Enhanced Enterprise Zone. Tax credits will be an amount authorized by DED, based on the state economic benefit, supported by the number of new jobs, wages and new capital investment that the project will create. To qualify, individual business eligibility will be determined by the zone, based on creation of

443

Residential Forced Air System Cabinet Leakage and Blower Performance  

NLE Websites -- All DOE Office Websites (Extended Search)

Residential Forced Air System Cabinet Leakage and Blower Performance Residential Forced Air System Cabinet Leakage and Blower Performance Title Residential Forced Air System Cabinet Leakage and Blower Performance Publication Type Report LBNL Report Number LBNL-3383E Year of Publication 2010 Authors Walker, Iain S., Darryl J. Dickerhoff, and William W. Delp Publisher Lawrence Berkeley National Laboratory City Berkeley Keywords air flow measurement, air leakage, blower power measurement, blowers, energy performance of buildings group, forced air systems, furnaces, indoor environment department, other, public interest energy research (pier) program, residential hvac Abstract This project evaluated the air leakage and electric power consumption of Residential HVAC components, with a particular focus on air leakage of furnace cabinets. Laboratory testing of HVAC components indicated that air leakage can be significant and highly variable from unit to unit - indicating the need for a standard test method and specifying maximum allowable air leakage in California State energy codes. To further this effort, this project provided technical assistance for the development of a national standard for Residential HVAC equipment air leakage. This standard is being developed by ASHRAE and is called "ASHRAE Standard 193P - Method of test for Determining the Air Leakage Rate of HVAC Equipment". The final part of this project evaluated techniques for measurement of furnace blower power consumption. A draft test procedure for power consumption was developed in collaboration with the Canadian General Standards Board: CSA 823 "Performance Standard for air handlers in residential space conditioning systems".

444

U.S. Climate Zones Map for Commercial Buildings  

Annual Energy Outlook 2012 (EIA)

U.S. Climate Zone U. S. Climate Zones for 2003 CBECS: climate zones map Note:Map updated with corrections, February 2012 Further Explanation on How Climate Zones are Defined...

445

U.S. Climate Zones Map for Commercial Buildings  

Annual Energy Outlook 2012 (EIA)

Past Climate Zones U. S. Climate Zones for 1979-1999 CBECS: climate zone map Return to Climate Zones for 2003 CBECS Return to CBECS Home Page Note:Map updated with corrections,...

446

Property:Buildings/ModelClimateZone | Open Energy Information  

Open Energy Info (EERE)

ModelClimateZone ModelClimateZone Jump to: navigation, search This is a property of type Page. It links to pages that use the form Buildings Model. The allowed values for this property are: Climate Zone 1A Climate Zone 1B Climate Zone 2A Climate Zone 2B Climate Zone 3A Climate Zone 3B Climate Zone 3C Climate Zone 4A Climate Zone 4B Climate Zone 4C Climate Zone 5A Climate Zone 5B Climate Zone 5C Climate Zone 6A Climate Zone 6B Climate Zone 7A Climate Zone 7B Climate Zone 8A Climate Zone 8B Pages using the property "Buildings/ModelClimateZone" Showing 12 pages using this property. G General Merchandise 2009 TSD Chicago High Plug Load 50% Energy Savings + Climate Zone 5A + General Merchandise 2009 TSD Chicago High Plug Load Baseline + Climate Zone 5A + General Merchandise 2009 TSD Chicago Low Plug Load 50% Energy Savings + Climate Zone 5A +

447

Continuity conditions for a fault consisting of obliquely aligned cracks  

E-Print Network (OSTI)

by the ambient stress, and other regions that are open and ¯uid- or air-®lled (e.g. Nagy 1992). The fault may as a ¯uid conduit or a seal depending on the fault zone complexity or microstructural details (Jones & Knipe 1996). Therefore, prediction of the fault seal potential is important. One way to characterize

Cambridge, University of

448

Better Unitary Equipment Air-Handlers for Efficiency and Humidity Control  

E-Print Network (OSTI)

procedure gives too little credit for advanced air handlers that reduce air conditioning load and facilitate adaptive humidity control through automatic fan speed adjustment. DC permanent magnet variable speed motors have much lower market share than less...

Sachs, H. M.

2002-01-01T23:59:59.000Z

449

Air-Con International: Order (2010-SE-0301) | Department of Energy  

Office of Environmental Management (EM)

finding Air-Con had imported and distributed in commerce in the U.S. various models of air-conditioning units. The Order adopted a Compromise Agreement, which reflected...

450

CFD Simulation and Measurement Validation of Air Distribution at the Hunan International Exhibition Center  

E-Print Network (OSTI)

The Hunan International Exhibition Center (HIEC) is a large space building. A stratified air-conditioning system on the second floor of the building has been adopted. Due to some problems with the air supply jet diffuser, CFD simulations were...

Deng, T.; Zhang, Q.; Zhang, G.; Yuan, H.

2006-01-01T23:59:59.000Z

451

Laboratory Test Report for ThermaStor Ultra-Aire XT150H Dehumidifier  

SciTech Connect

This report documents the performance of the ThermaStor Ultra-Aire XT150H Dehumidifier. Its performance was measured across a wide range of inlet air conditions and fit to a numerical model.

Christensen, D.; Winkler, J.

2009-12-01T23:59:59.000Z

452

Verification of a cohesive zone model for ductile fracture  

SciTech Connect

In the present paper, ductile crack growth in an aluminum alloy is numerically simulated using a cohesive zone model under both plane stress and plane strain conditions for two different fracture types, shear and normal modes. The cohesive law for ductile fracture consists of two parts--a specific materials` separation traction and energy. Both are assumed to be constant during ductile fracture (stable crack growth). In order to verify the assumed cohesive law to be suitable for ductile fracture processes, experimental records are used as control curves for the numerical simulations. For a constant separation traction, determined experimentally from tension test data, the corresponding cohesive energy was determined by finite element calculations. It is confirmed that the cohesive zone model can be used to characterize a single ductile fracture mode and is roughly independent of stable crack extension. Both the cohesive traction and the cohesive fracture energy should be material specific parameters. The extension of the cohesive zone is restricted to a very small region near the crack tip and is in the order of the physical fracture process. Based on the present observations, the cohesive zone model is a promising criterion to characterize ductile fracture.

Yuan, H.; Lin, G.; Cornec, A. [GKSS Research Centre Geesthacht (Germany). Inst. of Materials Research

1996-04-01T23:59:59.000Z

453

SEQUESTRATION AND TREATMENT OF VADOSE ZONE SOLVENTS USING EDIBLE OILS  

SciTech Connect

Edible oils have emerged as an effective treatment amendment for a variety of contaminants. When applied to chlorinated volatile organic compounds (cVOCs) in the saturated zone, edible oils have been shown to enhance anaerobic bioremediation and sequester the contaminants. However, edible oils have not been applied to the vadose zone for contaminant treatment. Soybean oil was injected into the vadose zone in M-Area at the Department of Energy's (DOE) Savannah River Site (SRS) as a research study to evaluate the effectiveness of edible oils for solvent sequestration and the ability to change a vadose system from aerobic to anaerobic to initiate reductive dechlorination. The proposed use of this technique would be an enhanced attenuation/transition step after active remediation. The goals of the research were to evaluate oil emplacement methods and monitoring techniques to measure oil placement, partitioning and degradation. Gas sampling was the cornerstone for this evaluation. Analyses for cVOCs and biotransformation products were performed. Overall, the cVOC concentration/flux reduction was 75-85% in this vadose zone setting. Destruction of the cVOCs by biotic or abiotic process has not yet been verified at this site. No reductive dechlorination products have been measured. The deployment has resulted in a substantial generation of light hydrocarbon gases and geochemical conditions that would support cometabolism.

Riha, B; Brian02 Looney, B; Richard Hall (NOEMAIL), R

2008-03-28T23:59:59.000Z

454

Environmental Quality: Air (Louisiana)  

Energy.gov (U.S. Department of Energy (DOE))

The Department of Environmental Quality regulates air quality in Louisiana. The Department has an established a fee system for funding the monitoring, investigation and other activities required...

455

Air-Quality Regulations  

Science Journals Connector (OSTI)

n...Federal, state and/or local regulations constructed for the purpose of protecting air quality, e.g., low volatile organic compounds...

Jan W. Gooch

2011-01-01T23:59:59.000Z

456

Air-quality regulations  

Science Journals Connector (OSTI)

n....Federal, state and/or local regulations constructed for the purpose of protecting air quality, e.g., low volatile organic compounds...

2007-01-01T23:59:59.000Z

457

Economizer control assembly for regulating the volume flow of outdoor ambient air  

SciTech Connect

An economizer assembly is disclosed wherein a sliding door is utilized for covering an outdoor ambient air opening allowing outdoor ambient air flow into a space to be conditioned. A motor shaft arrangement connected via a rotating drive rod is utilized to slidably displace the door to any position necessary to effectively regulate air flow. The utilization of this economizer control arrangement with a rooftop type air conditioning unit is further disclosed.

Michaels, D.D. Jr.

1984-10-23T23:59:59.000Z

458

Near-field/altered-zone models report  

SciTech Connect

The U.S. Department of Energy is studying Yucca Mountain as the possible site for the first underground repository for permanent disposal of spent fuel from commercial nuclear reactors as well as for other types high-level nuclear waste. Emplacement of high-level radioactive waste, especially commercial spent nuclear fuel (CSNF), in Yucca Mountain will release a large amount of heat into the rock above and below the repository. The heating rate will decrease with time, creating a thermal pulse. Over a period of several thousand years, the rock temperature will rise initially, then drop when the production of decay heat falls below the rate at which heat escapes from the hot zone. Besides raising the rock temperature, much of this heat will vaporize water, which will then condense in cooler regions. The condensate is likely to form a gravity-driven heat pipe above the repository, creating the possibility that water may drain back onto the waste packages (WPs) or that it may ''shed'' through the pillars between emplacement drifts. The long-term importance of these effects has been investigated through the development, testing, and application of thermohydrologic (TH) models. Other effects, such coupled chemical and mechanical processes, may also influence the movement of water above, within, and below the emplacement drifts. A recent report on thermally driven coupled processes (Hardin and Chesnut, 1997) provides a qualitative assessment of the probable significance of these processes for the Yucca Mountain Site Characterization Project (YMSCP) and is the phenomenological framework for the present report. This report describes the conceptual and numerical models that have been developed to predict the thermal, mechanical, hydrologic, and chemical responses to the cumulative heat production of the potential host rock at Yucca Mountain. As proposed, the repository horizon will be situated within the Topopah Spring tuff, in the adjacent middle nonlithophysal and lower lithophysal units. These units are made up of moderately to densely welded, devitrified, fractured tuff. The rock's chemical composition is comparable to that of typical granite, but has textural features and mineralogical characteristics of large-scale, silicic volcanism. Because the repository horizon will be approximately 300 m below the ground surface and 200 m above the water table, the repository will be partially saturated. The welded tuff matrix in the host units is highly impermeable, but water and gas flow readily through fractures. The degree of fracturing in these units is highly variable, and the hydrologic significance of fracturing is an important aspect of site investigation. This report describes the characterization and modeling of a region around the potential repository--the altered zone--a region in which the temperature will be increased significantly by waste-generated heat. Numerical simulation has shown that, depending on the boundary conditions, rock properties, and repository design features incorporated in the models, the altered zone (AZ) may extend from the water table to the ground surface. This report also describes models of the near field, the region comprising the repository emplacement drifts and the surrounding rock, which are critical to the performance of engineered components. Investigations of near-field and altered-zone (NF/AZ) processes support the design of underground repository facilities and engineered barriers and also provide constraint data for probabilistic calculations of waste-isolation performance (i.e., performance assessment). The approach to investigation, which is an iterative process involving hypothesis testing and experimentation, has relied on conceptualizing engineered barriers and on performance analysis. This report is a collection, emphasizing conceptual and numerical models, of the recent results contributed from studies of NF/AZ processes and of quantitative measures of NF/AZ performance. The selection and presentation of contributions are intended to show the iterative development of understand

Hardin, E. L., LLNL

1998-03-01T23:59:59.000Z

459

Effect of Return Air Leakage on Air Conditioner Performance in Hot/Humid Climates  

E-Print Network (OSTI)

provided rebates to residential customers for purchasing high efficiency air conditioners and heat pumps. The rebates have helped increase the demand for higher efficiency air conditioning units. However, even the most efficient system will not perform... of supply ducts (Table 1). The predominance of return duct leakage over supply duct leakage confirmed the investigators' theory that installers were more careful to seal seams on supply ducts (Robison and Lambert, 1989). Table 1 - Measured Leakage...

O'Neal, D. L.; Rodriguez, A.; Davis, M.; Kondepudi, S.

1996-01-01T23:59:59.000Z

460

Displacement Transfer Zone | Open Energy Information  

Open Energy Info (EERE)

Displacement Transfer Zone Displacement Transfer Zone Jump to: navigation, search GEOTHERMAL ENERGYGeothermal Home Print PDF Displacement Transfer Zone Dictionary.png Displacement Transfer Zone: Displacement transfer zones facilitate the transfer of strain between normal and strike-slip faults. Intersections between strike-slip faults in the Walker Lane and N- to NNE-striking normal faults commonly host geothermal systems, focused along the normal faults proximal to their dilational intersections with nearby strike-slip faults. Other definitions:Wikipedia Reegle Controlling Structures List of controlling structures typically associated with geothermal systems: Major Normal Fault Termination of a Major Normal Fault Stepover or Relay Ramp in Normal Fault Zones Apex or Salient of Normal Fault

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


461

Climate Zone 5A | Open Energy Information  

Open Energy Info (EERE)

Zone 5A Zone 5A Jump to: navigation, search A type of climate defined in the ASHRAE 169-2006 standard consisting of Climate Zone Number 5 and Climate Zone Subtype A. Climate Zone 5A is defined as Cool- Humid with IP Units 5400 < HDD65ºF ≤ 7200 and SI Units 3000 < HDD18ºC ≤ 4000 . The following places are categorized as class 5A climate zones: Adair County, Iowa Adair County, Missouri Adams County, Illinois Adams County, Indiana Adams County, Iowa Adams County, Nebraska Adams County, Pennsylvania Albany County, New York Allegan County, Michigan Alleghany County, North Carolina Allegheny County, Pennsylvania Allen County, Indiana Allen County, Ohio Andrew County, Missouri Antelope County, Nebraska Appanoose County, Iowa Armstrong County, Pennsylvania Arthur County, Nebraska

462

Climate Zone 5B | Open Energy Information  

Open Energy Info (EERE)

Climate Zone 5B Climate Zone 5B Jump to: navigation, search A type of climate defined in the ASHRAE 169-2006 standard consisting of Climate Zone Number 5 and Climate Zone Subtype B. Climate Zone 5B is defined as Dry with IP Units 5400 < HDD65ºF ≤ 7200 and SI Units 3000 < HDD18ºC ≤ 4000 . The following places are categorized as class 5B climate zones: Ada County, Idaho Adams County, Colorado Adams County, Washington Apache County, Arizona Arapahoe County, Colorado Asotin County, Washington Baker County, Oregon Beaver County, Utah Benewah County, Idaho Bent County, Colorado Benton County, Washington Boulder County, Colorado Broomfield County, Colorado Canyon County, Idaho Carson City County, Nevada Cassia County, Idaho Catron County, New Mexico Chelan County, Washington Cheyenne County, Colorado

463

Climate Zone Number 1 | Open Energy Information  

Open Energy Info (EERE)

Climate Zone Number 1 Climate Zone Number 1 Jump to: navigation, search A type of climate defined in the ASHRAE 169-2006 standard. Climate Zone Number 1 is defined as Very Hot - Humid(1A) with IP Units 9000 < CDD50ºF and SI Units 5000 < CDD10ºC Dry(1B) with IP Units 9000 < CDD50ºF and SI Units 5000 < CDD10ºC . The following places are categorized as class 1 climate zones: Broward County, Florida Hawaii County, Hawaii Honolulu County, Hawaii Kalawao County, Hawaii Kauai County, Hawaii Maui County, Hawaii Miami-Dade County, Florida Monroe County, Florida Retrieved from "http://en.openei.org/w/index.php?title=Climate_Zone_Number_1&oldid=21604" Category: ASHRAE Climate Zones What links here Related changes Special pages Printable version Permanent link Browse properties

464

Climate Zone 2A | Open Energy Information  

Open Energy Info (EERE)

Climate Zone 2A Climate Zone 2A Jump to: navigation, search A type of climate defined in the ASHRAE 169-2006 standard consisting of Climate Zone Number 2 and Climate Zone Subtype A. Climate Zone 2A is defined as Hot - Humid with IP Units 6300 < CDD50ºF ≤ 9000 and SI Units 3500 < CDD10ºC ≤ 5000 . The following places are categorized as class 2A climate zones: Acadia Parish, Louisiana Alachua County, Florida Allen Parish, Louisiana Anderson County, Texas Angelina County, Texas Appling County, Georgia Aransas County, Texas Ascension Parish, Louisiana Assumption Parish, Louisiana Atascosa County, Texas Atkinson County, Georgia Austin County, Texas Avoyelles Parish, Louisiana Bacon County, Georgia Baker County, Florida Baker County, Georgia Baldwin County, Alabama Bastrop County, Texas

465

Enterprise Zone Program (Texas) | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Enterprise Zone Program (Texas) Enterprise Zone Program (Texas) Enterprise Zone Program (Texas) < Back Eligibility Commercial Savings Category Alternative Fuel Vehicles Hydrogen & Fuel Cells Buying & Making Electricity Water Home Weatherization Solar Wind Program Info State Texas Program Type Corporate Tax Incentive Enterprise Zone Provider Texas Wide Open for Business The Enterprise Zone Program eligible projects to apply for state sales and use tax refunds on purchases of all taxable items purchased for use at qualified business sites related to the project or activity. The level and amount of refund is related to the capital investment and jobs created at the qualified business site. In addition, local communities must offer incentives to participants under the enterprise zone program, such as tax

466

Climate Zone 3B | Open Energy Information  

Open Energy Info (EERE)

Climate Zone 3B Climate Zone 3B Jump to: navigation, search A type of climate defined in the ASHRAE 169-2006 standard consisting of Climate Zone Number 3 and Climate Zone Subtype B. Climate Zone 3B is defined as Dry with IP Units 4500 < CDD50ºF ≤ 6300 and SI Units 2500 < CDD10ºC < 3500 . The following places are categorized as class 3B climate zones: Andrews County, Texas Baylor County, Texas Borden County, Texas Brewster County, Texas Butte County, California Callahan County, Texas Chaves County, New Mexico Childress County, Texas Clark County, Nevada Cochise County, Arizona Coke County, Texas Coleman County, Texas Collingsworth County, Texas Colusa County, California Concho County, Texas Contra Costa County, California Cottle County, Texas Crane County, Texas Crockett County, Texas

467

Coastal Zone Management Act | Open Energy Information  

Open Energy Info (EERE)

Zone Management Act Zone Management Act Jump to: navigation, search Statute Name Coastal Zone Management Act Year 1972 Url [[File:|160px|link=]] Description The Coastal Zone Management Act of 1972 (CZMA; Pub.L. 92-583, 86 Stat. 1280, enacted October 27, 1972, 16 U.S.C. §§ 1451-1464, Chapter 33) is an Act of Congress passed in 1972 to encourage coastal states to develop and implement coastal zone management plans (CZMPs). This act was established as a United States National policy to preserve, protect, develop, and where possible, restore or enhance, the resources of the Nation's coastal zone for this and succeeding generations. References Wikipedia[1] National Oceanic and Atmospheric Administration[2] The U.S. Congress recognized the importance of meeting the challenge of

468

International MODIS and AIRS processing package: AIRS products and applications  

E-Print Network (OSTI)

International MODIS and AIRS processing package: AIRS products and applications Elisabeth Weisz presented and discussed in this paper demonstrate that the IMAPP AIRS retrieval product is rigorously parameters from the operational AIRS L2 product and data from other instruments. Keywords: AIRS, IMAPP

Li, Jun

469

Clean air act and National Ambient Air Quality Standards (NAAQS)  

E-Print Network (OSTI)

Clean air act and National Ambient Air Quality Standards (NAAQS) Ozone: Sources/Environmental Effects Particulates (PM): Sources/Environmental Effects #12;National Ambient Air Quality Standards (NAAQS) The Clean Air Act requires EPA to set National Ambient Air Quality Standards for pollutants considered

Weber, Rodney

470

HVAC Radial Air Bearing Heat Exchangers Research Project | Department of  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Radial Air Bearing Heat Exchangers Radial Air Bearing Heat Exchangers Research Project HVAC Radial Air Bearing Heat Exchangers Research Project The U.S. Department of Energy is currently conducting research into heating, ventilation, and air conditioning (HVAC) radial air bearing heat exchangers. Rotary air bearing heat exchanger technology simultaneously solves four long standing problems of conventional "fan-plus-finned-heat-sink" heat exchangers. Project Description This project seeks to design, fabricate, and test successive generations of prototype radial air bearing heat exchanger devices based on lessons learned and further insights into device optimization, computational fluid dynamic studies for parametric optimization and determination of scaling laws, and laboratory measurement of flow field and heat transfer

471

Compressed Air System Optimization  

E-Print Network (OSTI)

Several years ago I went to a gas station and noticed that my car's tires were low on air. I saw the gas station had an air compressor, but it cost a quarter to use the compressor. I paid my quarter and used the compressor. I realized...

Aegerter, R.

472

Recirculating electric air filter  

DOE Patents (OSTI)

An electric air filter cartridge has a cylindrical inner high voltage electrode, a layer of filter material, and an outer ground electrode formed of a plurality of segments moveably connected together. The outer electrode can be easily opened to remove or insert filter material. Air flows through the two electrodes and the filter material and is exhausted from the center of the inner electrode.

Bergman, W.

1985-01-09T23:59:59.000Z

473

Portable oven air circulator  

DOE Patents (OSTI)

A portable air circulating apparatus for use in cooking ovens which is used to create air currents in the oven which transfer heat to cooking foodstuffs to promote more rapid and more uniform cooking or baking, the apparatus including a motor, fan blade and housing of metallic materials selected from a class of heat resistant materials.

Jorgensen, Jorgen A. (Bloomington, MN); Nygren, Donald W. (Minneapolis, MN)

1983-01-01T23:59:59.000Z

474

Enterprise Zone Incentives (Florida) | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Incentives (Florida) Incentives (Florida) Enterprise Zone Incentives (Florida) < Back Eligibility Agricultural Commercial Fuel Distributor Industrial Retail Supplier Systems Integrator Savings Category Alternative Fuel Vehicles Hydrogen & Fuel Cells Buying & Making Electricity Water Home Weatherization Solar Wind Program Info State Florida Program Type Enterprise Zone Provider Florida Department of Economic Opportunity Enterprise Zone Incentives encourage business growth within certain geographic areas targeted for economic revitalization. Businesses which create jobs within a designated zone are eligible for several tax incentives, including sales and use tax credit, tax refunds for machinery or equipment, sales tax refund for building materials, and a sales tax exemption for electrical energy

475

Streamside Management Zones (Montana) | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Streamside Management Zones (Montana) Streamside Management Zones (Montana) Streamside Management Zones (Montana) < Back Eligibility Utility Fed. Government Commercial Agricultural Investor-Owned Utility State/Provincial Govt Industrial Construction Municipal/Public Utility Local Government Residential Installer/Contractor Rural Electric Cooperative Tribal Government Low-Income Residential Schools Retail Supplier Institutional Multi-Family Residential Systems Integrator Fuel Distributor Nonprofit General Public/Consumer Transportation Savings Category Buying & Making Electricity Water Home Weatherization Solar Wind Program Info State Montana Program Type Environmental Regulations Provider Montana Department of Natural Resources and Conservation This chapter sets streamside management zones as encompassing a strip at

476

Meeting the Air Leakage  

NLE Websites -- All DOE Office Websites (Extended Search)

Meeting the Air Leakage Meeting the Air Leakage Requirements of the 2012 IECC The U.S. Department of Energy (DOE) recognizes the enormous potential that exists for improving the energy efficiency, safety and comfort of homes. The newest edition of the International Energy Conservation Code ® (IECC) (2012) sets the bar higher for energy efficiency, and new air sealing requirements are one of the key new provisions. This guide is a resource for understanding the new air leakage requirements in the 2012 IECC and suggestions on how these new measures can be met. It also provides information from Building America's Air Sealing Guide, Best Practices and case studies on homes that are currently meeting the provisions. The 2012 IECC and a few International Residential Code (IRC) requirements are referenced throughout the guide.

477

Gas Powered Air Conditioning Absorption vs. Engine-Drive  

E-Print Network (OSTI)

the cooling effect of water evaporation to cool a facilities water cooling system while the gas engine drive chiller uses a standard "freon" compressor driven by a gas engine' to provide its cooling. In the absorption chiller, a heat generator boils... for the water in the evaporator section. A pump then moves the dilute solution back to the generator to continue the process. GED chillers are no different than their electric counterparts except an engine drives the compressor instead of an electric motor...

Phillips, J. N.

1996-01-01T23:59:59.000Z

478

Cool Storage for Solar and Conventional Air Conditioning  

Science Journals Connector (OSTI)

The term thermal energy storage can apply to any storage function for which the principal inputs and outputs are thermal energy, whether as hotness or as coolness. Generally, hotness storage technologies h...

C. J. Swet

1989-01-01T23:59:59.000Z

479

Keeping Cool Without Air Conditioning | Department of Energy  

Office of Environmental Management (EM)

in summer. If you have a big deciduous tree in front of a sunny window, it blocks the sun in the summer, but lets it in in the winter when you actually need the heat" He just...

480

Desiccant Enhanced Evaporative Air-Conditioning (DEVap): Evaluation...  

NLE Websites -- All DOE Office Websites (Extended Search)

can be sourced from fuels such as natural gas, waste heat, solar, or biofuels. Thermal energy consumption correlates directly to the humidity level in the operating environment....

Note: This page contains sample records for the topic "zone air conditioning" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


481

Smart School Symposium Heating Ventilation and Air Conditioning Session  

E-Print Network (OSTI)

used in Schools Efficiency Metrics for HVAC Equipment Historical Perspective on Efficiency · Weather data is not the same, and has a big impact on building loads as well as the performance of HVAC;School Load Data Metrics · Using the ASHRAE 90.1 benchmark buildings models I have developed

California at Davis, University of

482

Swozzle based burner tube premixer including inlet air conditioner for low emissions combustion  

DOE Patents (OSTI)

A burner for use in a combustion system of a heavy-duty industrial gas turbine includes a fuel/air premixer having an air inlet, a fuel inlet, and an annular mixing passage. The fuel/air premixer mixes fuel and air into a uniform mixture for injection into a combustor reaction zone. The burner also includes an inlet flow conditioner disposed at the air inlet of the fuel/air premixer for controlling a radial and circumferential distribution of incoming air. The pattern of perforations in the inlet flow conditioner is designed such that a uniform air flow distribution is produced at the swirler inlet annulus in both the radial and circumference directions. The premixer includes a swozzle assembly having a series of preferably air foil shaped turning vanes that impart swirl to the airflow entering via the inlet flow conditioner. Each air foil contains internal fuel flow passages that introduce natural gas fuel into the air stream via fuel metering holes that pass through the walls of the air foil shaped turning vanes. By injecting fuel in this manner, an aerodynamically clean flow field is maintained throughout the premixer. By injecting fuel via two separate passages, the fuel/air mixture strength distribution can be controlled in the radial direction to obtain optimum radial concentration profiles for control of emissions, lean blow outs, and combustion driven dynamic pressure activity as machine and combustor load are varied.

Tuthill, Richard Sterling (Bolton, CT); Bechtel, II, William Theodore (Scotia, NY); Benoit, Jeffrey Arthur (Scotia, NY); Black, Stephen Hugh (Duanesburg, NY); Bland, Robert James (Clifton Park, NY); DeLeonardo, Guy Wayne (Scotia, NY); Meyer, Stefan Martin (Troy, NY); Taura, Joseph Charles (Clifton Park, NY); Battaglioli, John Luigi (Glenville, NY)

2002-01-01T23:59:59.000Z

483

Analysis of Air Leakage Measurements of US Houses  

NLE Websites -- All DOE Office Websites (Extended Search)

Air Leakage Measurements of US Houses Air Leakage Measurements of US Houses Title Analysis of Air Leakage Measurements of US Houses Publication Type Journal Article Year of Publication 2013 Authors Chan, Wanyu R., Jeffrey Joh, and Max H. Sherman Journal Energy and Buildings Start Page 616 Pagination 616-625 Date Published 08/2013 Abstract Building envelope airtightness is important for residential energy use, occupant health and comfort. Weanalyzed the air leakage measurements of 134,000 single-family detached homes in US, using normalizedleakage (NL) as the metric. Weatherization assistance programs (WAPs) and residential energy efficiencyprograms contributed most of the data. We performed regression analyses to examine the relationshipbetween NL and various house characteristics. Explanatory variables that are correlated with NL includeyear built, climate zone, floor area, house height, and whether homes participated in WAPs or if theyare energy efficiency rated homes. Foundation type and whether ducts are located outside or inside theconditioned space are also found to be useful parameters for predicting NL. We developed a regressionmodel that explains approximately 68% of the observed variability across US homes. Of these variablesconsidered, year built and climate zone are the two that have the largest influence on NL. The regressionmodel can be used to predict air leakage values for individual homes, and distributions for groups ofhomes, based on their characteristics. Using RECS 2009 data, the regression model predicts 90% of UShouses have NL between 0.22 and 1.95, with a median of 0.67.

484

Air Handling Unit Supply Air Temperature Optimization During Economizer Cycles  

E-Print Network (OSTI)

Air Handling Unit Supply Air Temperature Optimization during Economizer Cycles Gang Wang, Zhan Wang, Ke Xu and Mingsheng Liu University of Nebraska Lincoln Omaha, Nebraska, USA ABSTRACT Most air handling units (AHUs) in commercial...

Xu, K.; Liu, M.; Wang, G.; Wang, Z.

2007-01-01T23:59:59.000Z

485

An observational study of the South Pacific Convergence Zone using satellite and model re-analysis data  

E-Print Network (OSTI)

Satellite derived wind, rain rate and sea surface temperature data combined with NCEP analysis data are used to examine the structure of the South Pacific Convergence Zone (SPCZ) during La Nina conditions. Annual means indicate that the axes...

Cocks, Stephen Brenton

2004-09-30T23:59:59.000Z

486

Heat transfer pathways in underfloor air distribution (UFAD) systems  

E-Print Network (OSTI)

Conference of the Society of Heat- ing, Air-Conditioning,permission. QC-06-053 Heat Transfer Pathways in Underfloorthis paper: Results of heat gain shown in this theoretical

Bauman, F.; Jin, H.; Webster, T.

2006-01-01T23:59:59.000Z

487

Automatic Continuous Commissioning of Measurement Instruments in Air Handling Units  

E-Print Network (OSTI)

This paper presents a robust strategy based on a condition-based adaptive statistical method for automatic commissioning of measurement instruments typically employed in air-handling units (AHU). The multivariate statistic method, principal...

Xiao, F.; Wang, S.

2006-01-01T23:59:59.000Z

488

Using EMCS Data to Document and Improve Air Handler Performance  

E-Print Network (OSTI)

Traditionally, energy monitoring and control systems (EMCS) have been used, as the name implies, to monitor and control heating, ventilating and air conditioning systems, however, this paper will identify other benefits of an EMCS. Recording EMCS...

Brightbill, E. L.; Rutt, J. P.

1998-01-01T23:59:59.000Z

489

Hybrid Zones and Sexual Selection 503 HYBRID ZONES AND SEXUAL SELECTION: INSIGHTS FROM  

E-Print Network (OSTI)

Hybrid Zones and Sexual Selection 503 HYBRID ZONES AND SEXUAL SELECTION: INSIGHTS FROM THE AWASH BABOON HYBRID ZONE (Papio hamadryas anubis x P. h. hamadryas) Thore J. Bergman and Jacinta C. Beehner, have focused on the impact of sexual selection on populations of naturally occurring hybrid animals

490

Air ejector augmented compressed air energy storage system  

DOE Patents (OSTI)

Energy is stored in slack demand periods by charging a plurality of underground reservoirs with air to the same peak storage pressure, during peak demand periods throttling the air from one storage reservoir into a gas turbine system at a constant inlet pressure until the air pressure in the reservoir falls to said constant inlet pressure, thereupon permitting air in a second reservoir to flow into said gas turbine system while drawing air from the first reservoir through a variable geometry air ejector and adjusting said variable geometry air ejector, said air flow being essentially at the constant inlet pressure of the gas turbine system.

Ahrens, Frederick W. (Naperville, IL); Kartsounes, George T. (Naperville, IL)

1980-01-01T23:59:59.000Z

491

Abatement of Air Pollution: Prohibition of Air Pollution (Connecticut)  

Energy.gov (U.S. Department of Energy (DOE))

All air pollution not otherwise covered by these regulations is prohibited. Stationary sources which cause air pollution must be operated in accordance with all applicable emissions standards and...

492

Trapping capacity of fault zones, downdip Yegua Formation, Texas Gulf Coast basin  

E-Print Network (OSTI)

PROCEDURES. 25 Methods of Measurement Conversion to Mercury/Air System. . Sample Preparation. SHEARED ZONE EVALUATIONS. . 27 31 32 34 Introduction. Cities Service Dincans I Well (CD I). General Crude Kirby Lumber 2 Well (GCK2). . . . Texture...). . . . . . . . . . . . . . . . 23 10 Mercury injection cell apparatus for measurement of capillary pressure (Keelan, 1982) 28 11 Centrifugal apparatus for capillary pressure tests (Keelan, 1982). . . 30 12 Plot of porosity with depth for the total cored interval of interest...

Hintz, Jena Christine

2012-06-07T23:59:59.000Z

493

The CitiSense Air Quality Monitoring Mobile Sensor Node Piero Zappi, Elizabeth Bales, Jing Hong Park, William Griswold and Tajana Simuni Rosing  

E-Print Network (OSTI)

conditions than the national ambient air quality standard [1]. Current air pollutant measurement networks. For example, The San Diego Air Pollution Control District (SDAPCD) maintains only five air pollutant samplingThe CitiSense Air Quality Monitoring Mobile Sensor Node Piero Zappi, Elizabeth Bales, Jing Hong

Simunic, Tajana

494

Air Pollution and Health Effects  

Science Journals Connector (OSTI)

The quality of the air we breathe is still a major concern to human health. Notwithstanding the air pollution mitigation efforts that have been pursued since ... be attributed to the effects of urban outdoor air

Ana Isabel Miranda; Joana Valente

2014-01-01T23:59:59.000Z

495

Air Quality (Nova Scotia, Canada)  

Energy.gov (U.S. Department of Energy (DOE))

Nova Scotia Environment is responsible for monitoring the air quality in the province, as well as administering fines and permits relating to air quality. The Air Quality Regulations state...

496

Global air quality and climate  

E-Print Network (OSTI)

CRITICAL REVIEW Global air quality and climatewz Arlene M.determine regional air quality and can alter climate.to-continental scale air quality. Reducing the O 3 precursor

2012-01-01T23:59:59.000Z

497

Proceedings of Coastal Zone 07 Portland, Oregon  

E-Print Network (OSTI)

analysis, Seaside Oregon, GIS, flood hazard maps, shoreline change, digital elevation model INTRODUCTION, 2006). The flood maps and GIS data are briefly described here. 100- AND 500-YEAR FLOOD MAPSProceedings of Coastal Zone 07 Portland, Oregon July 22 to 26, 2007 Coastal Zone 07: Wong 1 GIS

498

Deep Vadose Zone Applied Field Research Initiative  

E-Print Network (OSTI)

.S. Department of Energy (DOE) Office of Environmental Management and the Richland Operations Office to develop and fate of deep vadose zone contamination in order to protect our nation's water resources. To that end) Devising means to implement and monitor flux reduction strategies to reduce vadose zone contamination below

499

Treating tar sands formations with karsted zones  

DOE Patents (OSTI)

Methods for treating a tar sands formation are described herein. The tar sands formation may have one or more karsted zones. Methods may include providing heat from one or more heaters to one or more karsted zones of the tar sands formation to mobilize fluids in the formation. At least some of the mobilized fluids may be produced from the formation.

Vinegar, Harold J. (Bellaire, TX); Karanikas, John Michael (Houston, TX)

2010-03-09T23:59:59.000Z

500

Prediction of Room Air Diffusion for Reduced Diffuser Flow Rates  

E-Print Network (OSTI)

modeling at the air supply device (ASHRAE Research Project RP -1009, ?Simplified Diffuser Boundary Conditions for Numerical Room Airflow Models, 2001) 2.2.4 Box model Nielsen (1989, 1992) proposed the box method with an imaginary box near.... Nielsen (1989, 13 1992). Results obtained from the box method are in good agreement with the measured data. Figure 5 Methods for momentum modeling in front of an air supply device (ASHRAE RP -1009, ?Simplified Diffuser Boundary Conditions...

Gangisetti, Kavita

2011-02-22T23:59:59.000Z