Powered by Deep Web Technologies
Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


1

Final Project Report: Self-Correcting Controls for VAV System Faults Filter/Fan/Coil and VAV Box Sections  

SciTech Connect

This report addresses original research by the Pacific Northwest National Laboratory for the California Institute for Energy and Environment on self-correcting controls for variable-air-volume (VAV) heating, ventilating and air-conditioning systems and focuses specifically on air handling and VAV box components of the air side of the system. A complete set of faults for these components was compiled and a fault mode analysis performed to understand the detectable symptoms of the faults and the chain of causation. A set of 26 algorithms was developed to facilitate the automatic correction of these faults in typical commercial VAV systems. These algorithms include training tests that are used during commissioning to develop models of normal system operation, passive diagnostics used to detect the symptoms of faults, proactive diagnostics used to diagnose the cause of a fault, and finally fault correction algorithms. Ten of the twenty six algorithms were implemented in a prototype software package that interfaces with a test bed facility at PNNL's Richland, WA, laboratory. Measurement bias faults were instigated in the supply-air temperature sensor and the supply-air flow meter to test the algorithms developed. The algorithms as implemented in the laboratory software correctly detected, diagnosed and corrected these faults. Finally, an economic and impact assessment was performed for the State of California for deployment of self-correcting controls. Assuming 15% HVAC energy savings and a modeled deployment profile, 3.1-5.8 TBu of energy savings are possible by year 15.

Brambley, Michael R.; Fernandez, Nicholas; Wang, Weimin; Cort, Katherine A.; Cho, Heejin; Ngo, Hung; Goddard, James K.

2011-05-01T23:59:59.000Z

2

Field testing of component-level model-based fault detection methods for mixing boxes and VAV fan systems  

SciTech Connect

An automated fault detection and diagnosis tool for HVAC systems is being developed, based on an integrated, life-cycle, approach to commissioning and performance monitoring. The tool uses component-level HVAC equipment models implemented in the SPARK equation-based simulation environment. The models are configured using design information and component manufacturers' data and then fine-tuned to match the actual performance of the equipment by using data measured during functional tests of the sort using in commissioning. This paper presents the results of field tests of mixing box and VAV fan system models in an experimental facility and a commercial office building. The models were found to be capable of representing the performance of correctly operating mixing box and VAV fan systems and detecting several types of incorrect operation.

Xu, Peng; Haves, Philip

2002-05-16T23:59:59.000Z

3

Impacts of Static Pressure Reset on VAV System Air Leakage, Fan Power and Thermal Energy - Part I: Theoretical Model and Simulation  

E-Print Network (OSTI)

As for a variable air volume (VAV) system, the air duct static pressure is a typical control variable maintained by modulating supply fan speed. The static pressure equals to the summation of the duct pressure loss downstream of the sensor to the terminal box and box inlet static pressure. Typically, the air duct static pressure is set as a constant set point based on the system design information and sensor location. However, under partial load conditions, the terminal box dampers have to be closed more since either required airflow is less than the design airflow which directly leads to much less pressure loss. Thus the static pressure set point should be reset lower in order to reduce fan power, avoid noise at terminal box dampers and box damper malfunction due to excessive pressure. Different static pressure reset schedules are reviewed and compared, considering the influence of outside air temperature on the building load, availability of the VAV box damper positions, the airflow ratio based static pressure reset has also applicable advantages over the existing constant static pressure set point and two typical reset methods. This paper present the theoretical models to express the impacts of static pressure reset on fan airflow, fan head, air leakage, fan power and thermal energy for both pressure independent and pressure dependent boxes. The impacts are also demonstrated using the parametric analysis and numerical results to show the benefits of the static pressure reset including reducing fan power, cooling energy and heating energy.

Liu, M.; Feng, J.; Wang, Z.; Wu, L.; Zheng, K.; Pang, W.

2007-01-01T23:59:59.000Z

4

Impacts of Static Pressure Reset on VAV System Air Leakage, Fan Power and Thermal Energy - Part 2: Case Demonstration for a Typical Climate System  

E-Print Network (OSTI)

In Part 1 of this paper, the theoretical models, integrating the fan airflow, fan head, air leakage factors, are developed to analyze the impacts of the static pressure reset on both pressure dependent and pressure independent terminal boxes. In this part, a simulated air handling unit (AHU) system in Omaha NE is used to demonstrate the energy savings performance in one typical climate year. This AHU system has a static pressure reset system and two constant static pressure systems, one having pressure dependent terminal boxes and one having pressure independent terminal boxes. These simulated systems were compared mainly on the basis of fan power energy consumption and thermal energy consumption in totally a year. The example presents a good agreement with the theoretical model and simulation results. It was also shown that static pressure reset provides a promising and challenging way for the energy performance in VAV system.

Liu, M.; Zheng, K.; Wu, L.; Wang, Z.; Johnson, C.

2007-01-01T23:59:59.000Z

5

Duct Leakage Impacts on VAV System Performance in Large Commercial  

NLE Websites -- All DOE Office Websites (Extended Search)

Duct Leakage Impacts on VAV System Performance in Large Commercial Duct Leakage Impacts on VAV System Performance in Large Commercial Buildings Title Duct Leakage Impacts on VAV System Performance in Large Commercial Buildings Publication Type Report LBNL Report Number LBNL-53605 Year of Publication 2003 Authors Wray, Craig P., and Nance Matson Abstract The purpose of this study is to evaluate the variability of duct leakage impacts on air distribution system performance for typical large commercial buildings in California. Specifically, a hybrid DOE-2/TRNSYS sequential simulation approach was used to model the energy use of a low-pressure terminal-reheat variable-air-volume (VAV) HVAC system with six duct leakage configurations (tight to leaky) in nine prototypical large office buildings (representing three construction eras in three California climates where these types of buildings are common). Combined fan power for the variable-speed-controlled supply and return fans at design conditions was assumed to be 0.8 W/cfm. The VAV system that we simulated had perfectly insulated ducts, and maintained constant static pressure in the ducts upstream of the VAV boxes and a constant supply air temperature at the air-handler. Further evaluations of duct leakage impacts should be carried out in the future after methodologies are developed to deal with duct surface heat transfer effects, to deal with airflows entering VAV boxes from ceiling return plenums (e.g., to model parallel fan-powered VAV boxes), and to deal with static pressure reset and supply air temperature reset strategies.

6

Field testing of component-level model-based fault detection methods for mixing boxes and VAV fan systems  

E-Print Network (OSTI)

precluded testing the fan based on design data. Since thisStatic Pressure (inWg) fan CFM SF-SP SF-SP-Design-Sim time (supply fan pressure rise) SF- DP SF-DP-Design-simulated D.

Xu, Peng; Haves, Philip

2002-01-01T23:59:59.000Z

7

Field testing of component-level model-based fault detection methods for mixing boxes and VAV fan systems  

E-Print Network (OSTI)

measurement of airflow rate. Supply fan speed (0-1) SA S.A.Supply Fan test S.B.Fan pressure rise calibration SF-DP-Simulated Pressure

Xu, Peng; Haves, Philip

2002-01-01T23:59:59.000Z

8

Performance of ECM controlled VAV fan powered terminal units  

E-Print Network (OSTI)

Empirical performance models of fan airflow, primary airflow and power consumption were developed for series and parallel variable air volume fan powered terminal units. An experimental setup and test procedure were created to test the terminal units at typical design pressures and airflows. Each terminal unit observed in this study used an 8 in (20.3 cm) primary air inlet. Two fan motor control methods were considered. The primary control of interest was the electronically commutated motor (ECM) controller. Data collected were compared with previous research regarding silicon rectified control (SCR) units. Generalized models were developed for both series and parallel terminal units. Coefficients for performance models were then compared with comparable SCR controlled units. Non-linear statistical modeling was performed using SPSS software (2008). In addition to airflow and power consumption modeling, power quality was also quantified. Relationships between real power (watts) and apparent power (VA) were presented as well as harmonic frequencies and total harmonic distortion. Power quality was recorded for each ECM controlled terminal unit tested. Additional tests were also made to SCR controlled terminal units used in previous research (Furr 2006). The airflow and power consumption performance models had an R2 equal to 0.990 or greater for every terminal unit tested. An air leakage model was employed to account for leakage in the parallel designed VAV terminal units when the internal fan was turned off. For the leakage model, both ECM and SCR controlled units achieved an R2 greater than or equal to 0.918.

Cramlet, Andrew Charles

2008-08-01T23:59:59.000Z

9

Development of a Laboratory Verified Single-Duct VAV System Model with Fan Powered Terminal Units Optimized Using Computational Fluid Dynamics  

E-Print Network (OSTI)

Single Duct Variable Air Volume (SDVAV) systems use series and parallel Fan Powered Terminal Units to control the air flow in conditioned spaces. This research developed a laboratory verified model of SDVAV systems that used series and parallel fan terminal units where the fan speeds were controlled by either Silicon Controlled Rectifiers (SCR) or Electronically Commutated Motors (ECM) motors. As part of the research, the model was used to compare the performance of the systems and to predict the harmonics generated by ECM systems. All research objectives were achieved. The CFD model, which was verified with laboratory measurements, showed the potential to identify opportunities for improvement in the design of the FPTU and accurately predicted the static pressure drop as air passed through the unit over the full operating range of the FPTU. Computational fluid dynamics (CFD) models of typical a FPTU were developed and used to investigate opportunities for optimizing the design of FPTUs. The CFD model identified key parameters required to conduct numerical simulations of FPTU and some of the internal components used to manufacture the units. One key internal component was a porous baffle used to enhance mixing when primary air and induced air entered the mixing chamber. The CFD analysis showed that a pressure-drop based on face velocity model could be used to accurately predict the performance of the FPTU. The SDVAV simulation results showed that parallel FPTUs used less energy overall than series systems that used SCR motors as long as primary air leakage was not considered. Simulation results also showed that series ECM FPTUs used about the same amount of energy, within 3 percent, of parallel FPTU even when leakage was not considered. A leakage rate of 10 percent was enough to reduce the performance of the parallel FPTU to the level of the series SCR system and the series ECM FPTUs outperformed the parallel FPTUs at all weather locations used in the study.

Davis, Michael A.

2010-08-01T23:59:59.000Z

10

Duct leakage impacts on VAV system performance in California large commercial buildings  

SciTech Connect

The purpose of this study is to evaluate the variability of duct leakage impacts on air distribution system performance for typical large commercial buildings in California. Specifically, a hybrid DOE-2/TRNSYS sequential simulation approach was used to model the energy use of a low-pressure terminal-reheat variable-air-volume (VAV) HVAC system with six duct leakage configurations (tight to leaky) in nine prototypical large office buildings (representing three construction eras in three California climates where these types of buildings are common). Combined fan power for the variable-speed-controlled supply and return fans at design conditions was assumed to be 0.8 W/cfm. Based on our analyses of the 54 simulation cases, the increase in annual fan energy is estimated to be 40 to 50% for a system with a total leakage of 19% at design conditions compared to a tight system with 5% leakage. Annual cooling plant energy also increases by about 7 to 10%, but reheat energy decreases (about 3 to 10%). In combination, the increase in total annual HVAC site energy is 2 to 14%. The total HVAC site energy use includes supply and return fan electricity consumption, chiller and cooling tower electricity consumption, boiler electricity consumption, and boiler natural gas consumption. Using year 2000 average commercial sector energy prices for California ($0.0986/kWh and $7.71/Million Btu), the energy increases result in 9 to 18% ($7,400 to $9,500) increases in HVAC system annual operating costs. Normalized by duct surface area, the increases in annual operating costs are 0.14 to 0.18 $/ft{sup 2}. Using a suggested one-time duct sealing cost of $0.20 per square foot of duct surface area, these results indicate that sealing leaky ducts in VAV systems has a simple payback period of about 1.3 years. Even with total leakage rates as low as 10%, duct sealing is still cost effective. This suggests that duct sealing should be considered at least for VAV systems with 10% or more total duct leakage. The VAV system that we simulated had perfectly insulated ducts, and maintained constant static pressure in the ducts upstream of the VAV boxes and a constant supply air temperature at the airhandler. Further evaluations of duct leakage impacts should be carried out in the future after methodologies are developed to deal with duct surface heat transfer effects, to deal with airflows entering VAV boxes from ceiling return plenums (e.g., to model parallel fan-powered VAV boxes), and to deal with static pressure reset and supply air temperature reset strategies.

Wray, Craig P.; Matson, Nance E.

2003-10-01T23:59:59.000Z

11

Variable Speed Drive Volumetric Tracking (VSDVT) for Airflow Control in Variable Air Volume (VAV) Systems  

E-Print Network (OSTI)

An airflow control method has been developed for variable air volume (VAV) systems. This airflow control method is named VSD volumetric tracking (VSDVT) since both the supply and return airflows are determined using signals of the variable speed drives (VSD) instead of the flow stations. Its performance is studied and compared with the fan tracking (FT) method using model simulations. The VSDVT maintains a constant building pressure and the required outside airflow under all load conditions, reduces the annual return air fan energy by up to 50%, and the annual supply air fan energy by up to 30%. This paper presents the VSDVT method, the system models, and the simulation results.

Liu, M.

2002-01-01T23:59:59.000Z

12

Commissioning and Diagnosis of VAV Air-Conditioning Systems  

E-Print Network (OSTI)

This paper presents a fault detection and diagnosis (FDD) strategy based on system knowledge, qualitative states and object-oriented statistical process control (SPC) models for typical pressure-independent variable air volume (VAV) air-conditioning systems. Eight FDD schemes are built to detect the eleven pre-defined VAV faults using the qualitative and quantitative FDD approaches within the strategy at two steps. The ten hard faults, which would affect the system operation, are analyzed at Step 1. The soft fault, which would not affect the basic system operation but would impact the supervisory controls, is analyzed at Step 2. The strategy is tested and validated on typical VAV systems involving multiple faults, both in simulation and in-situ tests. A software package is developed as a BMS-assisted automatic commissioning tool based on the FDD strategy. Off-line tests were conducted in both the simulated building and the real building.

Qin, J.; Wang, S.; Chan, C.; Xiao, F.

2006-01-01T23:59:59.000Z

13

The Optimization of Control Parameters for VAV HVAC System Commissioning  

E-Print Network (OSTI)

One of the technical subjects in commissioning for HVAC system is to enhance control performance and time efficiency, while the tuning of the optimal parameters to control HVAC system takes much time and labor in particular. Therefore, we propose a kind of commissioning technique as follows. We identified the dynamic characteristics of components of an actual VAV HVAC system such as rooms, VAV dampers, two way valves and chilled water coils, and verified the behaviors of the models and choose the optimal control parameters on a personal computer. Then adopting them for the actual system, we verified the control performance. Through the procedure, we showed the possibility of off-site and off-line control parameter tuning to reduce the cost and time at on-site and in on-line using the measured data in a real HVAC system.

Song, S.; Maehara, K.; Sagara, N.

2006-01-01T23:59:59.000Z

14

Modeling of ECM Controlled Series Fan-powered VAV Terminal Units  

E-Print Network (OSTI)

Semi-empirical models for series fan-powered variable air volume terminal units (FPTUs) were developed based on models of the primary, plenum, fan airflow and the fan power consumption. The experimental setups and test procedures were developed respectively for primary, plenum and fan airflow to test each component of the FPTUs at typical design pressures and airflows. Two sizes of the terminal units from three manufacturers were used in this study. All of the FPTUs were equipped with electronically commutated motors (ECM). Data provided by the models were compared against the data from previous experiments to prove the models’ validity. Regression modeling was performed by using SigmaStat. The model of primary airflow had an R2 above 0.948 for all the terminal units evaluated while the plenum airflow model had an R2 above 0.99. For all the terminal units, the R2 of the fan airflow model was ranged from 0.973 to 0.998. Except for one fan, the fan power consumption model was able to characterize the power performance and had an R2 above 0.986. By combining the airflow and power models, the model for series FPTU was developed. Verification was made to prove the FPTU model’s validity by comparing the measured and predicted data of airflow and power consumption. Correction factors were used in the primary airflow model to compensate for the difference caused by large measurement errors and the system effects. The predicted values were consistent with measurements and no offset was needed in the primary airflow model. Generally, the newly established model was able to describe the airflow performance as well as power consumption of series FPTUs without adding complexity.

Yin, Peng

2010-08-01T23:59:59.000Z

15

Analysis of the Energy Consumption of VAV System in Different Supply Air Control Strategies  

Science Conference Proceedings (OSTI)

Variable air volume (VAV) system has been widely applied due to its characteristics of eminent energy saving and thermal comfort. Because of its above characteristics, sophisticated automatic control systems are required to support its operation. While ... Keywords: VAV A/C system, supply air control strategy, energy consumption analysis

Junjie Guo, Xiangxin Cheng

2012-07-01T23:59:59.000Z

16

EVALUATION OF TRANSITIONS FOR TESTING AGRICULTURAL VENTILATION FANS WITH THE FAN ASSESSMENT NUMERATION SYSTEM (FANS).  

E-Print Network (OSTI)

??The Fan Assessment Numeration System (FANS) is an improved air velocity traverse method for measuring in situ fan performance. The FANS has been widely used,… (more)

Lopes, Igor Moreira

2012-01-01T23:59:59.000Z

17

Determining Critical Pressure and Duct Leakage in VAV Air-Handling...  

NLE Websites -- All DOE Office Websites (Extended Search)

for moving air in buildings use a significant amount of energy. It is well known that fan energy use in variable-air-volume (VAV) systems can be reduced by resetting the supply...

18

Determining Critical Pressure and Duct Leakage in VAV Air-Handling Units  

NLE Websites -- All DOE Office Websites (Extended Search)

Determining Critical Pressure and Duct Leakage in VAV Air-Handling Units Determining Critical Pressure and Duct Leakage in VAV Air-Handling Units Speaker(s): Clifford Federspiel Date: December 3, 2003 - 12:00pm Location: Bldg. 90 Seminar Host/Point of Contact: Nance Matson Fans for moving air in buildings use a significant amount of energy. It is well known that fan energy use in variable-air-volume (VAV) systems can be reduced by resetting the supply duct pressure. The standard way to reset duct pressure is by controlling the most-open terminal damper to a nearly open position. Most systems can't measure terminal damper positions, so pressures are either not reset at all or use ad hoc resetting strategies that are configured sub-optimally. In this seminar I will describe a new method of determining the critical supply duct pressure for VAV systems.

19

INFLUENCE OF FAN OPERATION ON FAN ASSESSMENT NUMERATION SYSTEM (FANS) TEST RESULTS.  

E-Print Network (OSTI)

??The use of velocity traverses to measure in-situ air flow rate of ventilation fans can be subject to significant errors. The Fan Assessment Numeration System… (more)

Morello, Gabriela Munhoz

2011-01-01T23:59:59.000Z

20

Theoretical Study of a Novel Control Method of VAV Air-conditioning System Based on MATLAB  

E-Print Network (OSTI)

The main purpose of this study is to put forward a novel nonlinear feedback control strategy on controlling indoor air temperature by variable air volume. A dynamic model of a typical room for a VAV air-conditioning system is established. The performance of the novel control strategy is investigated. Simulation of the controlling air temperature, on which the novel strategy is adopted, was carried out based on MATLAB in the VAV system. In order to show that the novel control strategy outperforms conventional PID control, a comparison is made between the performance of conventional PID and the novel nonlinear feedback control strategy. The results show that nonlinear feedback control strategy outperforms a conventional PID control system in terms of celerity, stability and other aspects.

Shi, Z.; Hu, S.; Wang, G.; Li, A.

2006-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


21

Energy Savings for Occupancy-Based Control (OBC) of Variable-Air-Volume (VAV) Systems  

SciTech Connect

This study evaluates the savings potential of occupancy based control (OBC) for large office buildings with VAV terminal boxes installed.

Zhang, Jian; Lutes, Robert G.; Liu, Guopeng; Brambley, Michael R.

2013-01-24T23:59:59.000Z

22

Automatic Commissioning of Multiple VAV Terminals  

E-Print Network (OSTI)

A site survey on a modern operating commercial building screened 261 ineffective VAV (Variable Air Volume) boxes (20.9% of the total boxes in the building) and summarized ten typical faults for VAV air-conditioning system(s) resulting in energy waste, performance degradation or totally out of control. A strategy is developed to automatically check the health condition of VAV terminals and diagnose the faults. Hybrid approach is employed to establish a commissioning and re-commissioning tool of VAV air-conditioning system. Performance indices with expert rules based on system physical characteristics are adopted to detect and diagnose the nine of the ten faults. PCA (Principal Component Analysis) method is developed to detect and diagnose the VAV box flow sensor bias (Fault 10) and to reconstruct the faulty sensors. A multiple VAV fault FDD strategy for a VAV entire system is developed, which is validated in simulation and filed tests.

Qin, J.; Wang, S.

2004-01-01T23:59:59.000Z

23

Parametric System Curves: Correlations Between Fan Pressure Rise and Flow for Large Commercial Buildings  

SciTech Connect

A substantial fraction of HVAC energy use in large commercial buildings is due to fan operation. Fan energy use depends in part on the relationship between system pressure drop and flow through the fan, which is commonly called a "system curve." As a step toward enabling better selections of air-handling system components and analyses of common energy efficiency measures such as duct static pressure reset and duct leakage sealing, this paper shows that a simple four-parameter physical model can be used to define system curves. Our model depends on the square of the fan flow, as is commonly considered. It also includes terms that account for linear-like flow resistances such as filters and coils, and for supply duct leakage when damper positions are fixed or are changed independently of static pressure or fan flow. Only two parameters are needed for systems with variable-position supply dampers (e.g., VAV box dampers modulating to control flow). For these systems, reducing or eliminating supply duct leakage does not change the system curve. The parametric system curve may be most useful when applied to field data. Non-linear techniques could be used to fit the curve to fan pressure rise and flow measurements over a range of operating conditions. During design, when measurements are unavailable, one could use duct design calculation tools instead to determine the coefficients.

Sherman, Max; Wray, Craig

2010-05-19T23:59:59.000Z

24

Analysis of the Potential Energy Savings for 14 Office Buildings with VAV Systems  

E-Print Network (OSTI)

At the beginning of an existing building commissioning (EBCx)/energy retrofit project, some form of screening is usually applied to determine whether there is sufficient potential for savings to justify a formal EBCx assessment/energy audit. In this study, an improved methodology for potential energy savings estimation from EBCx/retrofit measures, based on Baltazar's methodology (2006), is proposed to perform this type of screening. The improvements are included on optimization parameters, space load calculation, simulation of buildings with multiple types of HVAC systems, AHU shutdown simulation, among others. The improved methodology was used to estimate annual potential energy cost savings for 14 office buildings in Austin, TX with either single duct VAV (SDVAV) systems or dual duct VAV (DDVAV) systems. The estimates are based on very limited information about the buildings and the built-in HVAC systems as well as one year of utility bills. From this analysis, the methodology has predicted an average total potential savings of 36% for SDVAV systems with electric terminal reheat, 22% for SDVAV systems with hot water reheat, and 25% for DDVAV systems. To validate these results, the estimated potential savings are compared with savings proposed in respective EBCx assessment reports. Based on the comparison of the report estimates and the potential savings with the improved methodology, it was found that 'generalized' factors of assessment predicted energy cost savings to estimated potential energy cost savings could be found. The factors identified in these cases were 0.68, 0.66, and 0.61 for each type of system - SDVAV w/electric reheat, SDVAV w/hot water reheat, and DDVAV, respectively.

Claridge, D. E.; Liu, J.; Baltazar, J. C.

2010-01-01T23:59:59.000Z

25

Smart Fan Modules And System  

DOE Patents (OSTI)

A fan module including: two or more individual fans, each fan having an air movement means and a motor engaged with the air movement means for accelerating air entering each of the two or more individual fans; a temperature sensor for sensing a temperature associated with the two or more fans and for outputting a first signal corresponding to the temperature; rotational speed sensor for outputting a second signal corresponding to a rotational speed of each of the two or more fans; and a processor for receiving the first and second signals and controlling the two or more individual fans based on the first and second signals. A fan module including: two or more individual fans, each fan having an air movement means and a motor engaged with the air movement means for accelerating air entering each of the two or more individual fans; a temperature sensor for sensing a temperature associated with the two or more fans and for outputting a first signal corresponding to the temperature; rotational speed sensor for outputting a second signal corresponding to a rotational speed of each of the two or more fans; and a processor for receiving the first and second signals and controlling the two or more individual fans based on the first and second signals.

Cipolla, Thomas M. (Katonah, NY); Kaufman, Richard I. (Somers, NY); Mok, Lawrence S. (Brewster, NY)

2003-07-15T23:59:59.000Z

26

Improving Control of a Dual-Duct Single-Fan Variable Air Volume Systems  

E-Print Network (OSTI)

This paper discusses improved control strategies for dual-duct single-fan variable air volume (VAV) systems. Common control strategy for supply air volume modulation is evaluated, and an improved air volume control strategy that maintains separate cold and hot air duct static pressure set points is presented. The paper also explores the interactions between the cold and hot deck temperatures and duct static pressures, and discusses the impact of non-ideal deck temperature settings on duct static pressures and overall system energy consumption. To compensate the negative impact of non-ideal cold and hot deck temperature set points, the authors propose using real-time duct static pressure readings as feedback signals to fine-tune the deck temperature set points. These new control schemes can reduce simultaneous cooling and heating while reducing fan power consumption.

Wei, G.; Martinez, J.; Minihan, T.; Brundidge, T.; Claridge, D. E.; Turner, W. D.

2003-01-01T23:59:59.000Z

27

Duct leakage impacts on VAV system performance in California large commercial buildings  

E-Print Network (OSTI)

divided by the supply fan design airflow. The downstreamThe supply (and return) fan design airflow was determined byThe intermediate-floor supply fan design airflows for each

Wray, Craig P.; Matson, Nance E.

2003-01-01T23:59:59.000Z

28

A Functional Test Procedure for the improved commissioning of a VAV system  

E-Print Network (OSTI)

In the context of the IEA40 research project, a specification of a “Functional Test Procedure” was progressively developed using the CA-MET building in Namur as real size test bench for the application and validation of the procedure. The target system is a typical VAV system devoted to the ventilation, cooling and air conditioning functions. The procedure consists in a series of operations to be applied to the system, considered as a set of connected components and taking into account the following constraints: 1) time availability 2) intrinsic limitations of the system 3) reference performances. The proposed procedure is divided in two sets of actions: 1) a number of preliminary actions allowing to take the best benefit of the subsequent phases: a) identification of available measurement points b) identification of actuators characteristics c) identification of control strategies d) aeraulic network calculations e) selection of measurement techniques and experimental design 2) the verification tasks themselves: The philosophy of the verification process is to bring the system into a number of states which allowed each specific check to be carried out. The organisation of the procedure tries to optimize the time spent for commissioning by logically sequencing the operations according to the following order: 1) test in manual (ie not controlled by the BEMS) operation 2) test in manual (ie not controlled by the BEMS) stop 3) test in normal operation 4) test at maximum flowrate 5) test at minimum flowrate 6) test in automatic stop The paper will provide the specific operations to be carried out at each step and will illustrate the whole process with the prototyping work performed on the CA-MET building in Namur.

Andre, P.; Lacote, P.; Aparecida Silva, C.; Hannay, J.; Lebrun, J.

2004-01-01T23:59:59.000Z

29

Problem of Vain Energy Consumption in a VAV Air Conditioning System Shared By an Inner Zone and Exterior Zone  

E-Print Network (OSTI)

In northern China, there are a large number of space buildings divided in inner zone and exterior zone based on usage requirements. The exterior zone needs to be heated in winter and cooled in summer, while the inner zone needs to be cooled both in winter and summer. Taking a practical project as example, this paper analyzes the energy consumption of a VAV air conditioning system that is shared by inner zone and exterior zone. The paper also points out the serious problem of useless energy consumption for this kind of system.

Wenji, G.; Ling, C.; Dongdong, L.; Mei, S.; Li, Z.

2006-01-01T23:59:59.000Z

30

Characterization of air recirculation in multiple fan ventilation systems.  

E-Print Network (OSTI)

??Booster fans, large underground fans, can increase the volumetric efficiency of ventilation systems by helping to balance the pressure and quantity distribution throughout a mine,… (more)

Wempen, Jessica Michelle

2012-01-01T23:59:59.000Z

31

Supply Fan Control for Constant Air Volume Air Handling Units  

E-Print Network (OSTI)

Since terminal boxes do not have a modulation damper in constant volume (CV) air handling unit (AHU) systems, zone reheat coils have to be modulated to maintain the space temperature with constant supply airflow. This conventional control sequence causes a significant amount of reheat and constant fan power under partial load conditions. Variable Frequency Drives (VFDs) can be installed on these constant air volume systems. The fan speed can be modulated based on the maximum zone load. This paper present the procedure to control the supply fan speed and analyzes the thermal performance and major fan energy and thermal energy savings without expensive VAV retrofit through the actual system operation.

Cho, Y.; Wang, G.; Liu, M.

2007-01-01T23:59:59.000Z

32

Advanced Manufacturing Office: Training: Fan Systems  

NLE Websites -- All DOE Office Websites (Extended Search)

the tool and presents the basics-and the benefits-of using it to target opportunities for energy savings in your plant. Fan System Assessment - self-paced workshop Availability:...

33

Fan System Assessment - End User Training | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fan System Assessment - End User Training Fan System Assessment - End User Training Fan System Assessment - End User Training December 18, 2013 7:30AM to 4:30PM EST Boise, Idaho Optimizing industrial fan systems can take on many forms, but any fan optimization project must meet the needs of the process. This self-paced workshop highlights the benefits of fan system optimization and examines fan system performance characteristics and practical issues concerning measurement data. The session introduces the FSAT software. This powerful analysis software helps you quantify the potential benefits of configuring fan systems for optimal performance, calculate the amount of energy use by your fan system, and estimate fan system efficiency. Learn how the software works, what data is required for FSAT, and how to interpret assessment

34

Control system for heat exchangers fans in a refrigeration system  

Science Conference Proceedings (OSTI)

The paper presents a method for controlling evaporator and condenser fans in a refrigeration system. The refrigeration system includes a refrigerant circuit defined by a compressor, a condenser, a throttling device, and an evaporator. The system includes ... Keywords: controlling, fan, refrigeration system, variable frequency drive unit

Cristian Iosifescu; Valeriu Damian; C?lin Ciufudean

2010-05-01T23:59:59.000Z

35

Duct leakage impacts on VAV system performance in California large commercial buildings  

E-Print Network (OSTI)

kW) Total Fan Power (kW) Climate Zone CZ3 (Oakland) CZ9 (Coil Sizes (kBtu/(h·floor)) Climate Zone CZ3 (Oakland) CZ9 (all three vintages and climate zones ranged from 0.9999 to

Wray, Craig P.; Matson, Nance E.

2003-01-01T23:59:59.000Z

36

Water-side Economizer for Non-Fan Cooling Systems  

NLE Websites -- All DOE Office Websites (Extended Search)

changes to the commercial provisions of the 2012 IECC: Water-side Economizer for Non-Fan Cooling Systems R Hart Pacific Northwest National Laboratory January 2013 Proposal...

37

Fan Foundation Systems--Analysis and Design Guidelines  

Science Conference Proceedings (OSTI)

Dynamic analysis is the most effective tool for determining the root causes of excessive fan vibration. This study demonstrated the importance of using such analysis in conjunction with a "total systems" approach that considers how the properties of all major fan system components, including foundation, piles, and soil conditions, contribute to vibration.

1986-08-19T23:59:59.000Z

38

Fan System Effects: How Fan Ductwork Design Impacts Overall System Efficiency and What the Approach Should be for Optimization  

E-Print Network (OSTI)

"In order to establish the aerodynamic performance characteristics of a custom fan or even a line of fans, the accepted practice of the industry is to carry out testing on a scale model in a laboratory to develop its fan performance curve. Then by applying affinity laws in conjunction with very specific rules that address scaling issues, the performance characteristics of geometrically similar fans can be predicted. These affinity laws (frequently referred to as fan laws) also allow the performance of fans operating at different speeds or handling gases at different density values to be accurately predicted. However, it is often found that even fans with well defined and pedigreed performance curves are unable to meet their performance expectations once they are installed on the systems for which they have been sold. This is primarily due to the adverse aerodynamic impact of the inlet or outlet connections on the performance capacity of the fan and thus on the overall system efficiency. The general term for design conditions at inlets or outlets of fans that cause deficient aerodynamic performance is ‘system effects’. The characteristics of fan system effects are that they reduce fan capacity and are both velocity and geometry dependent. On the inlet side of a fan, this generally characterizes itself by a flow pattern that is highly non?uniform. On the discharge side, the high and low velocity flow streams leaving the fan may simply be prevented from redeveloping a uniform flow profile and normal static pressure conversion before encountering a disturbance. The term can also apply to system elements such as silencers, elbows and transitions. For these components, the actual pressure drop across them may be significantly higher than their calculated or rated values if the velocity profile of the entering flow is skewed or non?uniform. For either case (fan connection or system component), the result is that additional power will be required to address the flow rate required by the system. In many instances, system designers are simply unfamiliar with the importance of understanding system effects as it pertains to new fan selections and the attendant power requirements. At a minimum, a reasonable approach for new fan projects should be to establish the theoretical system effect of connection designs by using a recognized document such as Air Movement and Control Association Publication 201. The objective should be to first minimize their impact through appropriate connection design modifications in conjunction with potential fan inlet and outlet re?orientation. Once the system effects are minimized, the residual value should be applied to the fan performance specification in order to ensure that the fan is selected for the required aerodynamic capacity. For system components, an approach that has proved to be of significant value is to predict the flow pattern using computation fluid dynamics (CFD) modelling tools and in this process, the design can be tweaked until the designer finds the overall pressure drops of a system are minimized to the greatest practical extent. Similarly, CFD can be used to predict the flow profile at a fan inlet to ensure that it is as uniform as practically possible. This paper reviews the concept of system effects from the perspective of fan power requirements and provides a methodology for approaching system design from the perspective of optimizing fan energy use while achieving the required system capacity."

Martin, V.

2009-05-01T23:59:59.000Z

39

Design and Specification Guidelines for Large Draft Fans and Systems  

Science Conference Proceedings (OSTI)

Design shortcomings in draft fans and related air-gas systems can cause fan failure and costly outages of large fossil fuel power plants. These guidelines will help engineers and manufacturers achieve a better understanding of the design features needed to minimize such failures.

1983-12-01T23:59:59.000Z

40

COOLING FAN AND SYSTEM PERFORMANCE AND EFFICIENCY IMPROVEMENTS  

Science Conference Proceedings (OSTI)

Upcoming emissions regulations (Tiers 3, 4a and 4b) are imposing significantly higher heat loads on the cooling system than lesser regulated machines. This work was a suite of tasks aimed at reducing the parasitic losses of the cooling system, or improving the design process through six distinct tasks: 1. Develop an axial fan that will provide more airflow, with less input power and less noise. The initial plan was to use Genetic Algorithms to do an automated fan design, incorporating forward sweep for low noise. First and second generation concepts could not meet either performance or sound goals. An experienced turbomachinery designer, using a specialized CFD analysis program has taken over the design and has been able to demonstrate a 5% flow improvement (vs 10% goal) and 10% efficiency improvement (vs 10% goal) using blade twist only. 2. Fan shroud developments, using an 'aeroshroud' concept developed at Michigan State University. Performance testing at Michigan State University showed the design is capable of meeting the goal of a 10% increase in flow, but over a very narrow operating range of fan performance. The goal of 10% increase in fan efficiency was not met. Fan noise was reduced from 0 to 2dB, vs. a goal of 5dB at constant airflow. The narrow range of fan operating conditions affected by the aeroshroud makes this concept unattractive for further development at this time 3. Improved axial fan system modeling is needed to accommodate the numbers of cooling systems to be redesigned to meet lower emissions requirements. A CFD fan system modeling guide has been completed and transferred to design engineers. Current, uncontrolled modeling practices produce flow estimates in some cases within 5% of measured values, and in some cases within 25% of measured values. The techniques in the modeling guide reduced variability to the goal of + 5% for the case under study. 4. Demonstrate the performance and design versatility of a high performance fan. A 'swept blade mixed flow' fan was rapid prototyped from cast aluminum for a performance demonstration on a small construction machine. The fan was mounted directly in place of the conventional fan (relatively close to the engine). The goal was to provide equal airflow at constant fan speed, with 75% of the input power and 5 dB quieter than the conventional fan. The result was a significant loss in flow with the prototype due to its sensitivity to downstream blockage. This sensitivity to downstream blockage affects flow, efficiency, and noise all negatively, and further development was terminated. 5. Develop a high efficiency variable speed fan drive to replace existing slipping clutch style fan drives. The goal for this task was to provide a continuously variable speed fan drive with an efficiency of 95%+ at max speed, and losses no greater than at max speed as the fan speed would vary throughout its entire speed range. The process developed to quantify the fuel savings potential of a variable speed fan drive has produced a simple tool to predict the fuel savings of a variable speed drive, and has sparked significant interest in the use of variable speed fan drive for Tier 3 emissions compliant machines. The proposed dual ratio slipping clutch variable speed fan drive can provide a more efficient system than a conventional single ratio slipping clutch fan drive, but could not meet the established performance goals of this task, so this task was halted in a gate review prior to the start of detailed design. 6. Develop a cooling system air filtration device to allow the use of automotive style high performance heat exchangers currently in off road machines. The goal of this task was to provide a radiator air filtration system that could allow high fin density, louvered radiators to operate in a find dust application with the same resistance to fouling as a current production off-road radiator design. Initial sensitivity testing demonstrated that fan speed has a significant impact on the fouling of radiator cores due to fine dusts, so machines equipped with continuously variabl

Ronald Dupree

2005-07-31T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


41

Field testing of component-level model-based fault detection methods for mixing boxes and VAV fan systems  

E-Print Network (OSTI)

based methods of fault detection and diagnosis (FDD).Component-level FDD, which is the subject of the work

Xu, Peng; Haves, Philip

2002-01-01T23:59:59.000Z

42

Field testing of component-level model-based fault detection methods for mixing boxes and VAV fan systems  

E-Print Network (OSTI)

and diagnosis for cooling towers. ASHRAE Trans. , vol.107,of faults in the cooling tower circuit of a central chilled

Xu, Peng; Haves, Philip

2002-01-01T23:59:59.000Z

43

Improve the Energy Efficiency of Fan Systems, Software Tools for Industry, Industrial Technologies Program (ITP) (Fact Sheet)  

Science Conference Proceedings (OSTI)

This fact sheet describes how the Industrial Technologies Program Fan System Assessment Tool (FSAT) can help quantify energy consumption and savings opportunities in industrial fan systems.

Not Available

2008-12-01T23:59:59.000Z

44

Energy Efficient Single Stack Exhaust Fan Systems (E3S3F)  

E-Print Network (OSTI)

This paper first investigates the fan energy performance of a constant air volume exhaust system. Two single stack energy efficient exhaust fan systems (E3S3F) are presented. The E3S3F-I has the static pressure sensor located at the inlet of the exhaust fan. It has been found to consume up to 15% less fan power than conventional constant air volume exhaust systems. The E3S3F-II uses a variable speed device to maintain the static pressure at the entrance of the stack. It consumes up to 60% less fan power than conventional constant volume exhaust systems.

Wang, G.; Liu, M.

2001-01-01T23:59:59.000Z

45

The Lillehammer Submarine Fan Complex.  

E-Print Network (OSTI)

??Abstract The Lillehammer Submarine Fan Complex is a mixed mud/sand rich turbidite fan system. The fan complex was deposited in the Neoproterozoic Hedmark rift basin… (more)

Skaten, Maren Kristin Møllerup

2006-01-01T23:59:59.000Z

46

Toward green systems for cleanrooms: Energy efficient fan-filter units  

E-Print Network (OSTI)

filter unit (FFU), energy efficiency, green system, electricToward Green Systems for Cleanrooms: Energy Efficient Fan-energy efficient models; Market transformation toward “green”

Jeng, Ming-Shan; Xu, Tengfang; Lan, Chao-Ho

2004-01-01T23:59:59.000Z

47

Toward green systems for cleanrooms: Energy efficient fan-filter units  

E-Print Network (OSTI)

Toward Green Systems for Cleanrooms: Energy Efficient Fan-FFU), energy efficiency, green system, electric power use,are challenges and benefits in green designs that integrate

Jeng, Ming-Shan; Xu, Tengfang; Lan, Chao-Ho

2004-01-01T23:59:59.000Z

48

Parametric System Curves: Correlations Between Fan Pressure Rise and Flow for Large Commercial Buildings  

E-Print Network (OSTI)

distribution, duct design, system curve, fans, leakage iiifan pressure rise and flow measurements over a range of operating conditions. During design,

Sherman, Max

2010-01-01T23:59:59.000Z

49

DUCTED FAN INLET/EXIT AND ROTOR TIP FLOWIMPROVEMENTS FOR VERTICAL LIFT SYSTEMS.  

E-Print Network (OSTI)

??Ducted fan based vertical lift systems are excellent candidates to be in the group of the next generation vertical lift vehicles, with many potential applications… (more)

Akturk, Ali

2010-01-01T23:59:59.000Z

50

Predicting of fan speed for energy saving in HVAC system based on adaptive network based fuzzy inference system  

Science Conference Proceedings (OSTI)

In this paper, a HVAC (heating, ventilating and air-conditioning) system has two different zones was designed and fan motor speed to minimize energy consumption of the HVAC system was controlled by a conventional (proportional-integral-derivative) PID ... Keywords: ANFIS, Air flow control, Energy saving, Fan motor speed predicting, HVAC system, PID control, Temperature control

Servet Soyguder; Hasan Alli

2009-05-01T23:59:59.000Z

51

Engine having hydraulic and fan drive systems using a single high pressure pump  

DOE Patents (OSTI)

An engine comprises a hydraulic system attached to an engine housing that includes a high pressure pump and a hydraulic fluid flowing through at least one passageway. A fan drive system is also attached to the engine housing and includes a hydraulic motor and a fan which can move air over the engine. The hydraulic motor includes an inlet fluidly connected to the at least one passageway.

Bartley, Bradley E. (Manito, IL); Blass, James R. (Bloomington, IL); Gibson, Dennis H. (Chillicothe, IL)

2000-01-01T23:59:59.000Z

52

Parametric System Curves: Correlations Between Fan Pressure Rise and Flow for Large Commercial Buildings  

E-Print Network (OSTI)

Filter Pressure Loss Model for Fan Energy Calculation in Air2010. “Selecting Efficient Fans”. ASHRAE Journal, Vol. 52,Equipment: Chapter 20 – Fans”. Atlanta, GA: American Society

Sherman, Max

2010-01-01T23:59:59.000Z

53

Evaluation of ASD Systems for Electric Arc Furnace and Argon Oxygen Decarburization Refiner Baghouse Fans  

Science Conference Proceedings (OSTI)

An adjustable speed drive (ASD) offers opportunities to operate dust collection fans in a more energy efficient manner. This report focuses on the system requirements and provides a method for successfully applying ASDs to dust extraction baghouse systems in a steel melting and refining application in order to realize full energy savings and operational improvements.

1998-01-23T23:59:59.000Z

54

Software Verification and Validation Test Report for the HEPA filter Differential Pressure Fan Interlock System  

Science Conference Proceedings (OSTI)

The HEPA Filter Differential Pressure Fan Interlock System PLC ladder logic software was tested using a Software Verification and Validation (V&V) Test Plan as required by the ''Computer Software Quality Assurance Requirements''. The purpose of his document is to report on the results of the software qualification.

ERMI, A.M.

2000-09-05T23:59:59.000Z

55

The Louis Stokes Laboratories, Building 50, National Institutes...  

NLE Websites -- All DOE Office Websites (Extended Search)

VAV supply and exhaust fans, although in the pump system, the VAV terminal units are replaced by water control valves and cooling and heating coils. Differential pressure sensors...

56

Toward green systems for cleanrooms: Energy efficient fan-filter units  

E-Print Network (OSTI)

M. and F. Tsau. 2002. Fan-Filter Unit (FFU) Test Procedures.Laboratory Methods of Testing Fans for Rating, Air MovementTest Procedure For Fan-Filter Units (not published). [6] Xu,

Jeng, Ming-Shan; Xu, Tengfang; Lan, Chao-Ho

2004-01-01T23:59:59.000Z

57

HEPA Filter Differential Pressure Fan Interlock System Functional Requirements and Technical Design Criteria  

SciTech Connect

Double-shell tanks (DSTs) and Double Contained Receiver Tanks (DCRTs) are actively ventilated, along with certain single-shell tanks (SSTs) and other RPP facilities. The exhaust air stream on a typical primary ventilation system is drawn through two stages of high-efficiency particulate air (HEPA) filtration to ensure confinement of airborne radioactive materials. Active ventilation exhaust stacks require a stack CAM interlock to detect releases from postulated accidents, and to shut down the exhaust fan when high radiation levels are detected in the stack airstream. The stack CAM interlock is credited as a mitigating control to stop continued unfiltered radiological and toxicological discharges from the stack, which may result from an accident involving failure of a HEPA filter. This document defines the initial technical design baseline for a HEPA filter AP fan interlock system.

TUCK, J.A.

2000-05-11T23:59:59.000Z

58

Guidelines for Induced Flue Gas Recirculation: Volume 1: Reducing Air/Gas System Resistance and Enhancing Fan Capacity  

Science Conference Proceedings (OSTI)

This document guides users through a logical sequence, or "road map," of activities and decisions for optimizing solutions for fans, ducts, and related equipment in fossil plant combustion air and gas systems.

1999-12-13T23:59:59.000Z

59

Rui Fan  

NLE Websites -- All DOE Office Websites (Extended Search)

Rui Fan Rui Fan 1 Cyclotron Road MS 90-4000 Berkeley CA 94720 Office Location: 90-2087 (510) 486-6305 RFan@lbl.gov Vision & Mission Organization Awards Fellowship Staff Services...

60

Feasibility Study: Ductless Hydronic Distribution Systems with Fan Coil Delivery  

SciTech Connect

The primary objectives of this study are to estimate potential energy savings relative to conventional ducted air distribution, and to identify equipment requirements, costs, and barriers with a focus on ductless hydronic delivery systems that utilize water-to-air terminal units in each zone. Results indicate that annual heating and cooling energy use can be reduced by up to 27% assuming replacement of the conventional 13 SEER heat pump and coil with a similarly rated air-to-water heat pump.

Springer, D.; Dakin, B.; Backman, C.

2012-07-01T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


61

VAV Reheat Versus Active Chilled Beams and DOAS  

E-Print Network (OSTI)

and fan power. Table 1. Design Fan Power CFM CFM/ft2 Ext.has about 40% higher fan power at design conditions than the10 shows, the VAVR Design uses less fan power than the ACB+

Stein, Jeff; Taylor, Steven

2013-01-01T23:59:59.000Z

62

Coarse-clastic turbidite sedimentation : the neoproterozoic Imsdalen submarine fan complex, Hedmark Basin, South Norway.  

E-Print Network (OSTI)

??The Imsdalen Submarine Fan Complex is a gravel and coarse sand dominated turbidite fan system. The fan complex was deposited in the Neoproterozoic Hedmark rift… (more)

Stalsberg, Martin

2004-01-01T23:59:59.000Z

63

Fan Dai  

NLE Websites -- All DOE Office Websites (Extended Search)

Fan Dai Fan Dai China Energy Group Lawrence Berkeley National Laboratory 1 Cyclotron Road MS 90R2002 Berkeley CA 94720 Office Location: 90-2117S (510) 486-4000 FDai@lbl.gov Fan Dai is a Ph.D. Candidate in Environmental Policy at the College of Environmental Science and Forestry, State University of New York, and a LL.M. Candidate at Berkeley School of Law, University of California. Fan's research during her stay in LBNL's China Energy Group focuses on Energy Efficiency Governance, U.S.-China Clean Energy Partnership, the Carbon Cap-and-Trade Program in California and what China can learn from California's program. Prior to LBNL, she interned at the China National Center for Climate Change Strategy and International Cooperation (NCSC), China Youth Action Climate Network (CYCAN), and China State Forestry

64

FANS - Control  

Science Conference Proceedings (OSTI)

... If set to H+ and a magnet controller is connected, you are ... Typically motors 3, 4, 5, and 6 are fixed for FANS operation A fixed motor will not be ...

65

ZHAOSHENG FAN  

NLE Websites -- All DOE Office Websites (Extended Search)

ZHAOSHENG FAN Biosciences Division, Argonne National Laboratory, Argonne, IL 60439 Phone: (630) 252-1566; email: zfan@anl.gov EDUCATION Ph.D., Soil Physics, 2007, North Dakota...

66

Optimized Fan Control In Variable Air Volume HVAC Systems Using Static Pressure Resets: Strategy Selection and Savings Analysis  

E-Print Network (OSTI)

The potential of static pressure reset (SPR) control to save fan energy in variable air volume HVAC systems has been well documented. Current research has focused on the creation of reset strategies depending on specific system features. As the commissioning process has begun to require the prediction of savings, knowledge of the extent to which various SPR control strategies impact fan energy has become increasingly important. This research aims to document existing SPR control strategies and utilize building data and simulation to estimate fan energy use. A comprehensive review of the literature pertaining to SPR control was performed and the results were organized into a top-down flow chart tool. Based on the type of feedback available from a particular system, or lack thereof, this tool will facilitate the selection of a SPR control strategy. A field experiment was conducted on a single duct variable air volume system with fixed discharge air temperature and static pressure setpoints. Finally, an air-side model of the experimental system was created using detailed building design information and calibrated using field measurements. This model was used to estimate the fan energy required to supply the trended airflow data using fixed static pressure (FSP) and SPR control based on zone demand, system demand, and outside air temperature. While utilizing trend data from November 1, 2008 to February 12, 2009, the FSP control of the experimental system was used as the baseline for ranking the energy savings potential of nine different forms of duct static pressure control. The highest savings (73-74%) were achieved using zonal demand based SPR control. System demand based SPR control yielded savings ranging from 59 to 76%, which increased when the duct sensor was positioned near the fan discharge and under similar zone load conditions. The outside air temperature based SPR control yielded savings of 65% since the experimental system supplied primarily perimeter zones. Finally, increasing the FSP setpoint from 2 to 3 inWG increased fan energy by 45%, while decreasing the setpoint from 2 to 1 inWG decreased fan energy by 41%.

Kimla, John

2009-12-01T23:59:59.000Z

67

Museum Fan Downloads  

NLE Websites -- All DOE Office Websites (Extended Search)

Museum Fan Downloads Participate with us Participate Share your Stories Museum Fan Downloads invisible utility element Museum Fan Downloads Help the Bradbury Science Museum by...

68

Laboratory evaluation of fan/filter units' aerodynamic and energy performance  

E-Print Network (OSTI)

such as motor types, fan wheels, design, and orientations ofventilation system design, testing of fans and ventilation

Xu, Tengfang; Jeng, Ming-Shan

2004-01-01T23:59:59.000Z

69

Save Energy with Axial Fans  

E-Print Network (OSTI)

There are several ways to save energy in wet cooling towers and air cooled heat exchangers using axial fans. This paper will discuss ways to improve fan system efficiency in wet and dry towers both during the design phase and after installation by specifying energy efficient equipment. Variable pitch fan versus fixed pitch fan operation is discussed in terms of energy savings and means of control. The areas of interest to wet cooling tower users would be the influence on fan diameter and operating point on horsepower, how and when are velocity recovery stacks effective, the effect of varying fan speed to improve efficiency, and tip clearance effects. The areas of interest to dry tower (air cooled heat exchanger) users would be the effect of inlet losses, approach velocity losses, and losses due to air recirculation.

Monroe, R. C.

1981-01-01T23:59:59.000Z

70

An Initial Study on Applying Active Noise Control to an Insulated Box Fan Used in Ventilation System Applications.  

E-Print Network (OSTI)

??In many different applications and buildings fans are used to remove unwanted and used air. These fans often generate broadband and tonal noise. Commonly, passive… (more)

Larsson, Martin; Johansson, Sven; Muddala, S.M.; Gafar, A.E.; Håkansson, Lars; Tarkka, Juhani

2009-01-01T23:59:59.000Z

71

Performance Optimization of a Fan System- Overcoming Impacts of Modified Design Criteria Due to Regulatory Requirements and Changed Operating Conditions  

E-Print Network (OSTI)

The Louisiana Pacific mill in Tomahawk Wisconsin manufactures oriented-strand board. Several large induced-draft fans and combustion-air blowers were operating inefficiently at this mill. This case study highlights a systems approach that was applied to address fan inefficiency. Energy savings from optimizing the system are estimated to be 338 kW, nearly half of the original measured input power of 678 kW. The project is currently being implemented and will have a payback period of less than 8 months. The opportunities here are typical of opportunities thought to exist in most industrial plants. In this case, process needs changed due to environmental regulations and change of location, but the system did not, leading to low overall system efficiency.

Wroblewski, R. G.; Preis, F.; Smith, R.

1997-04-01T23:59:59.000Z

72

PCS Nitrogen: Combustion Fan System Optimization Improves Performance and Saves Energy at a Chemical Plant  

Science Conference Proceedings (OSTI)

This U.S. Department of Energy Industrial Technologies Program case study describes how, in 2003, PCS Nitrogen, Inc., improved the efficiency of the combustion fan on a boiler at the company's chemical fertilizer plant in Augusta, Georgia. The project saved $420,000 and 76,400 million British thermal units (MBtu) per year. In addition, maintenance needs declined, because there is now less stress on the fan motor and bearings and less boiler feed water usage. This project was so successful that the company has implemented more efficiency improvements that should result in energy cost savings of nearly $1 million per year.

Not Available

2005-01-01T23:59:59.000Z

73

Power Reduction Scheme of Fans in a Blade System by Considering the Imbalance of CPU Temperatures  

Science Conference Proceedings (OSTI)

In order to develop a data center power efficiency index, we built a test bed of a data center and measured power components and environmental variables in some detail, including the power consumption and temperature of each node, rack and air conditioning ... Keywords: Data center, Power consumption, Power efficiency, CPU temperature, Fan speed

Yuetsu Kodama; Satoshi Itoh; Toshiyuki Shimizu; Satoshi Sekiguchi; Hiroshi Nakamura; Naohiko Mori

2010-12-01T23:59:59.000Z

74

Imbalance of CPU temperatures in a blade system and its impact for power consumption of fans  

Science Conference Proceedings (OSTI)

We are now developing a new metric of data center power efficiency to fairly evaluate the contribution of each improvement for power efficiency. In order to develop it, we built a testbed of a data center and measured power consumption of each components ... Keywords: CPU temperature, Data center, Fan speed, Power consumption, Power efficiency

Yuetsu Kodama; Satoshi Itoh; Toshiyuki Shimizu; Satoshi Sekiguchi; Hiroshi Nakamura; Naohiko Mori

2013-03-01T23:59:59.000Z

75

THE WORLD'S Biggest Fan Collection  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

WORLD'S Biggest Fan Collection WORLD'S Biggest Fan Collection If you only know the Big Ass Fan Company as the preeminent designer and manufacturer of high volume, low speed fans for factories and cows, it's time you get to know us better. While we continue to lead the way in industrial and agricultural air movement, we've also refined these designs to bring the same innovation and benefits of our famous fans to circulate an ocean of air in sound-sensitive commercial spaces and homes. And when our customers said they wanted something for smaller spaces, we listened - and we think you'll like the results. We've got you covered - ceiling to floor, wall to door! Features ï‚ž New patented airfoil system uses 10 Powerfoil airfoils, winglets and patent-pending AirFence(tm) technology to increase

76

Fan Mei | BNL  

NLE Websites -- All DOE Office Websites (Extended Search)

Fan Mei Postdoctoral Research Associate Fan is currently working as a postdoctoral research associate with Jian Wang, investigating aerosol microphysical properties in three recent...

77

Fault Detection and Diagnosis in Building HVAC Systems  

E-Print Network (OSTI)

in AHU of VAV system”, Energy Conversion & Management, 30.energy efficient building management system”, Energy Conversionenergy efficient building management system”, Energy Conversion

Najafi, Massieh

2010-01-01T23:59:59.000Z

78

Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems  

E-Print Network (OSTI)

comparison of VAV and VRF air conditioning systems in anThe variable refrigerant flow (VRF) and ground source heatthe energy efficiency of VRF systems compared with GSHP

Hong, Tainzhen

2010-01-01T23:59:59.000Z

79

Modelling the architecture of distal sand-rich lobe deposits : an example from Fan 2, Skoorsteenberg Formation, Tanqua Karoo, South Africa.  

E-Print Network (OSTI)

??Fan 2, one of five submarine fan systems of the Tanqua fan complex in the south-western Karoo Basin, South Africa, is subdivided into Lower, Middle… (more)

Steyn, Rochelle

2009-01-01T23:59:59.000Z

80

Active Noise Control of a Radial Fan.  

E-Print Network (OSTI)

??This thesis work aims at investigating the use of an active noise control (ANC) system on a radial fan. This was done by studying the… (more)

Murthy, Muddala

2009-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


81

System dynamics based models for selecting HVAC systems for office buildings: a life cycle assessment from carbon emissions perspective.  

E-Print Network (OSTI)

??This study aims to explore the life cycle environmental impacts of typical heating ventilation and air condition (HVAC) systems including variable air volume (VAV) system,… (more)

Chen, S

2011-01-01T23:59:59.000Z

82

Ceiling Fan | Open Energy Information  

Open Energy Info (EERE)

Ceiling Fan Jump to: navigation, search TODO: Add description List of Ceiling Fan Incentives Retrieved from "http:en.openei.orgwindex.php?titleCeilingFan&oldid267151"...

83

Development of In-Situ Fan Curve Measurement with One Airflow Measurement  

E-Print Network (OSTI)

Fan airflow is the key parameter for air volume tracking control in variable air volume systems. One of the airflow measurement methods is to determine airflow using the fan speed, fan head, and fan curve. Both fan speed and fan head can be measured accurately. Therefore, the accuracy of the fan airflow depends on the accuracy of the fan curve. An experimental method has been developed to determine the in-situ fan curve with only one airflow measurement. This paper presents the theoretical background, experimental procedures, and verification results.

Liu, G.; Joo, I. S.; Song, L.; Liu, M.

2003-01-01T23:59:59.000Z

84

Development of a High Efficiency Ceiling Fan  

E-Print Network (OSTI)

The potential of ceiling fans to improve comfort during the cooling season is well documented (Rohles et al.. 1983; Fairey et al.. 1986). There are at least two cases: In the first where air conditioning is unavailable, adding ceiling fans may significantly improve building comfort and health although actually increasing energy use. However, the more common circumstance is where ceiling fans are used with the objective of providing a higher cooling system thermostat set point with acceptable comfort. Fans can also potentially avoid the use of air conditioning during "swing" seasons. Although studies commonly suggest a 2-6OF increase in the thermostat set point, data from 386 surveyed Central Florida households suggests that although fans are used an average of 13.4 hours per day, no statistically valid difference can be observed in thermostat settings between households using fans and those without them (James et al., 1996). Part of this may be due to the lack of sufficiently wide air distribution coverage within rooms (Rohles et al, 1983; Sonne and Parker, 1998). Studies touting potential cooling savings of up to 40% have usually been sponsored by fan manufacturers (eg. A.D. Little, 1981). These often make unrealistic assumptions such as presuming that occupants are within four feet of a fan with only one fan in use and a 6°F elevation of the thermostat setting. An environmental chamber study by Consumer Reports showed that the long-reported de-stratification benefits when heating are largely unsubstantiated (Consumer Reports. 1993). Thus. benefits from ceiling fans are only to reduce cooling needs and this is completely contingent on sufficient changes in interior comfort to warrant raising of the cooling thermostat. Two other factors must be taken into account in assessing the benefits of fans: their actual energy use and the added internal heat gains produced by the fans during operation. The measured electrical demand of ceiling fans varies between 5 and 115 Watts depending on model and speed selection. A power demand of 40 W at medium speed is probably typical (Chandra, 1985). Thus, a fan used for six months of the year would use 175 kwh. With 4.3 ceiling fans in an average Florida home, this amounts to about 800 kwh of fan energy consumption --about 5% of total electricity use. Also, all of the energy use of fans is eventually converted to heat within the home which must eventually be removed by ventilation air or the cooling system.

Parker, D. S.; Callahan, M. P.; Sonne, J. K.; Su, G. H.; Hibbs, B. D.

2000-01-01T23:59:59.000Z

85

Aerodynamic Experiments on a Ducted Fan in Hover and Edgewise Flight.  

E-Print Network (OSTI)

??Ducted fans and ducted rotors have been integrated into a wide range of aerospace vehicles, including manned and unmanned systems. Ducted fans offer many potential… (more)

Myers, Leighton

2009-01-01T23:59:59.000Z

86

Nien-fan Zhang  

Science Conference Proceedings (OSTI)

Nien-fan Zhang. Technical Areas of Research and Consulting: Statistical process control Time series analysis and forecasting. Awards: ...

2012-07-16T23:59:59.000Z

87

Fan Energy Savings Decisions  

E-Print Network (OSTI)

Axial fans are used for thousands of industrial applications consuming millions of kilowatts daily. The decision that saves dollars is to either automatically change fan speed or change blade pitch to save up to 50 percent of consumed power over a fixed pitch, constant speed fan. A discussion of the merits of each type is presented with actual test results.

Monroe, R. C.

1985-05-01T23:59:59.000Z

88

How low can you go? Low pressure drop laboratory design  

E-Print Network (OSTI)

0.7” w.g. full design flow through fan and stack only, VAV0.7” w.g. full design flow through fan and stack only, VAVTraditional Design Parameter Comment Fan System Efficiency

Weale, John; Rumsey, Peter; Sartor, Dale; Lock, Lee Eng

2001-01-01T23:59:59.000Z

89

INTEGRATED ENERGY SYSTEMS: PRODUCTIVITY & BUILDING SCIENCE  

E-Print Network (OSTI)

of Large Commercial HVAC Systems Led by Erik Kolderup, Eley Associates, Inc. Advanced VAV System Design will modify their rating system for tubular daylighting devices; and 2) U-factor results will affect how NFRC) E3 10/03 Advanced VAV System Design Guideline (Eley) E4 5/03 Integrated Design of Small Commercial

90

Operation and Maintenance Guidelines for Draft Fans  

Science Conference Proceedings (OSTI)

The reliability, efficiency, and safety of draft fans in fossil fuel power plants depend on effective operating and maintenance practices. These guidelines systematically present state-of-the-art techniques that utility personnel can use in operation, maintenance, troubleshooting, inspection, and weld repair of major fan components and auxiliary systems.

1999-05-13T23:59:59.000Z

91

Building Energy Software Tools Directory: EZDOE  

NLE Websites -- All DOE Office Websites (Extended Search)

and much more. The Systems data involves all information concerning air handling and heat delivery systems. VAV, constant volume, PTAC, dual duct, twofour pipe fan coils, and...

92

Efficiency of a liquid desiccant dehumidification system regenerated by using solar collectors/regenerators with photovoltaic fans  

Science Conference Proceedings (OSTI)

A hybrid solar dehumidification air-conditioning system was used to study the absorption of water vapor from moist air by contacting the air with aqueous solutions that contained from 90 to 94% triethylene glycol (TEG). For the packings of 2-inch polypropylene Jaeger Tri-Packs, which have a surface-to-volume ratio of 157 m{sup 2}/m{sup 3} (48 ft{sup 2}/ft{sup 3}), the efficiency of dehumidification can reach 93.3%. The environmental air was introduced into the dehumidifier cocurrently flowing with the liquid desiccant, and the liquid desiccant was sprayed on the top of the packing material. The air-to-liquid mass flow ratio was controlled in a range of 0.46 to 1.36. As the moisture was absorbed from air by the TEG solution, the solution was diluted. The regeneration of the solution was carried out in 20-piece (38.8 m{sup 2}) basin-type solar collectors/regenerators whose regeneration coefficients of performance are above 0.2. Air generated by photovoltaic fans was blown into the solar collectors/regenerators and carried away the water vapor from the evaporation of the aqueous desiccant solution. On the basis of the experimental results, the system performance is acceptable for most applications.

Tsair-Wang Chung; Wei-Yih Wu; Wen-Jih Yan; Ching-Lin Huang [Industrial Technology Research Institute, Taiwan (China)

1995-04-01T23:59:59.000Z

93

Module Development and Simulation of the Variable Refrigerant Flow Air Conditioning System under Cooling Conditions in Energyplus  

E-Print Network (OSTI)

As a high-efficiency air conditioning scheme, the variable refrigerant flow (VRF) air-conditioning system is finding its way into medium-sized office buildings. Based on a generic dynamic building energy simulation environment, EnergyPlus, a new module is developed and the energy usage of the VRF system is investigated. This paper compares the energy consumption of the VRF system with that of two conventional air-conditioning systems, namely, the variable air volume (VAV) system and the fan-coil plus fresh air (FPFA) system. A generic office building is used to accommodate the different types of heating, ventilating, and air conditioning (HVAC) systems. Our objective is to examine the energy consumption of the VRF system applied to office buildings and make suggestions for evaluating and making decisions on HVAC systems in the early stages of building design. Simulation results show that the energy-saving potential of the VRF system is expected to achieve 22.2 percent and 11.7 percent, compared to the VAV system and the FPFA system, respectively. An energy-usage breakdown of electricity end-users in various systems is also presented.

Zhou, Y.; Wu, J.; Wang, R.; Shiochi, S.

2006-01-01T23:59:59.000Z

94

Record of Communication Concerning Ceiling Fan and Ceiling Fan...  

NLE Websites -- All DOE Office Websites (Extended Search)

Record of Communication Concerning Ceiling Fan and Ceiling Fan Light Kit Framework Document-Docket No. EERE-2012-BT-STD-0045 Record of Communication Concerning Ceiling Fan and...

95

Demonstration of Intelligent Control and Fan Improvements in Computer Room  

NLE Websites -- All DOE Office Websites (Extended Search)

Demonstration of Intelligent Control and Fan Improvements in Computer Room Demonstration of Intelligent Control and Fan Improvements in Computer Room Air Handlers Title Demonstration of Intelligent Control and Fan Improvements in Computer Room Air Handlers Publication Type Report Refereed Designation Unknown LBNL Report Number LBNL-6007E Year of Publication 2012 Authors Coles, Henry C., Steve E. Greenberg, and Corrine Vita Document Number LBNL-6007E Date Published 12/2012 Publisher Lawrence Berkeley National Laboratory City Berkeley, CA Keywords air distribution, building technology and urban systems department, computer room air handler, crah control, data center, data center crah, ec fan, ecm, ecm fan, fan speed control, high tech and industrial systems group, plug fan, variable frequency drive, vfd, wireless control Abstract

96

Fan Repair Guideline  

Science Conference Proceedings (OSTI)

The successful repair of a fan component is affected by a number of different factors. These include correctly assessing the root cause of failure, determining the best repair option, implementation of proper repair procedures, and compliance with applicable codes and standards. However, in many situations the proper solution is not clearly evident. The purpose of this document is to provide guidance in the area of induced draft / forced draft fan repair. Specifically, this document deals with the repair...

2002-08-15T23:59:59.000Z

97

Effect of building airtightness and fan size on the performance of mechanical ventilation systems in new U.S. houses: a critique of ASHRAE standard 62.2-2003  

E-Print Network (OSTI)

Determining Air Leakage Rate by Fan Pressurization. Americanof Building Envelopes by the Fan Pressurization Method.Dominated by Strong Exhaust Fan. ASHRAE Transactions. Vol

Roberson, J.

2004-01-01T23:59:59.000Z

98

Evaluation of the cooling fan efficiency index.  

E-Print Network (OSTI)

Evaluation of the Cooling Fan Efficiency indexfor a desk fan anda computer fan Stefano Schiavon 1,2,* , M. Sc. PhD

Schiavon, Stefano; Melikov, Arsen

2009-01-01T23:59:59.000Z

99

Fans for Cooling | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fans for Cooling Fans for Cooling Fans for Cooling May 30, 2012 - 7:46pm Addthis Ceiling fans circulate air in a room to help keep occupants cool. | Photo courtesy of ©iStockphoto/jimkruger Ceiling fans circulate air in a room to help keep occupants cool. | Photo courtesy of ©iStockphoto/jimkruger What does this mean for me? You may be able to keep your home cool with energy-efficient and well-placed fans. Fans are less expensive to operate than air conditioners. Circulating fans include ceiling fans, table fans, floor fans, and fans mounted to poles or walls. These fans create a wind chill effect that will make you more comfortable in your home, even if it's also cooled by natural ventilation or air conditioning. Ceiling Fans Ceiling fans are considered the most effective of these types of fans,

100

Introduction of a Cooling Fan Efficiency Index  

E-Print Network (OSTI)

with four cooling fans of different designs available on thedesign, installation, and use, the performance of cooling fans

Schiavon, Stefano; Melikov, Arsen

2009-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


101

Best Practice for Energy Efficient Cleanrooms: Fan-FilterUnits  

Science Conference Proceedings (OSTI)

The HVAC systems in cleanrooms may use 50 percent or more of the total cleanroom energy use. Fan energy use accounts for a significant portion (e.g., over 50%) of the HVAC energy use in cleanrooms such as ISO Classes 3, 4, or 5. Three types of air-handling systems for recirculating airflows are commonly used in cleanrooms: (1) fan-tower systems with pressurized plenum, (2) ducted HEPA systems with distributed-fans, and (3) systems with fan-filter units. Because energy efficiency of the recirculation systems could vary significantly from system type to system type, optimizing aerodynamic performance in air recirculation systems appears to be a useful approach to improve energy efficiency in cleanrooms. Providing optimal airflows through careful planning, design and operation, including air change rate, airflow uniformity, and airflow speed, is important for controlling particle contamination in cleanrooms. In practice, the use of fan-filter units (FFUs) in the air-handling system is becoming more and more popular because of this type of system may offer a number of advantages. Often modular and portable than traditional recirculation airflow systems, FFUs are easier to install, and can be easily controlled and monitored to maintain filtration performance. Energy efficiency of air handling systems using fan-filter units can, however, be lower than their counterparts and may vary significantly from system to system because of the difference in energy performance, airflow paths, and the operating conditions of FFUs.

Xu, Tengfang

2005-06-15T23:59:59.000Z

102

Introduction of a Cooling Fan Efficiency Index  

E-Print Network (OSTI)

°C °F Cooling Effect (?t eq ) °C °F Fan Power, W (P f ) Cooling-Fan Efficiency (CFE) °C/W °F/Wand B. Jones. 1983. Ceiling fans as extenders of the summer

Schiavon, Stefano; Melikov, Arsen

2009-01-01T23:59:59.000Z

103

The Internet World of Fan Fiction.  

E-Print Network (OSTI)

??Fan fiction, the most popular creative outlet for fans, allows the amateur writer an opportunity to be published and receive immediate feedback from peers. As… (more)

Herzing, Melissa Jean

2008-01-01T23:59:59.000Z

104

HVAC Fans and Dampers Maintenance Guide  

Science Conference Proceedings (OSTI)

Heating, ventilation, and air conditioning (HVAC) systems serve an important function in nuclear power plants because these systems are responsible for maintaining many environmental conditions throughout the facility. Failure of these components can induce undesirable radiological conditions and stressful working conditions, and can compromise the life of qualified equipment. Some HVAC fan and damper failures are preventable by monitoring operating parameters and performing recommended maintenance activ...

1999-08-26T23:59:59.000Z

105

Designing Axial Flow Fan for Flow and Noise  

E-Print Network (OSTI)

A comprehensive finite element methodology is developed to predict the compressible flow performance of a non-symmetric 7-blade axial flow fan, and to quantify the source strength and sound pressure levels at any location in the system. The acoustic and flow performances of the fan are predicted simultaneously using a computational aero-acoustic technique combining transient flow analysis and noise propagation. The calculated sound power levels compare favorably with the measured sound power data per AMCA 300-96 code.

Subrata Roy; Phillip Cho; Fred Périé; International Off-highway

1999-01-01T23:59:59.000Z

106

Performance Assessment of Photovoltaic Attic Ventilator Fans  

E-Print Network (OSTI)

Controlling summer attic heat gain is important to reducing air conditioning energy use in homes in hot-humid climates. Both heat transfer through ceilings and t attic duct systems can make up a large part of peak cooling demand, Attic ventilation has long been identified as a method to abate such heat gains. We present test results from using the photovoltaic (PV) attic ventilator fans in a test home to assess impact on attic and cooling energy performance.

Parker, D. S.; Sherwin, J. R.

2000-01-01T23:59:59.000Z

107

Activation of Vav by the Gammaherpesvirus M2 Protein Contributes to the Establishment of Viral Latency in B Lymphocytes  

E-Print Network (OSTI)

Gammaherpesviruses subvert eukaryotic signaling pathways to favor latent infections in their cellular reservoirs. To this end, they express proteins that regulate or replace functionally specific signaling proteins of eukaryotic cells. Here we describe a new type of such viral-host interaction that is established through M2, a protein encoded by murine gammaherpesvirus 68. M2 associates with Vav proteins, a family of phosphorylation-dependent Rho/Rac exchange factors that play critical roles in lymphocyte signaling. M2 expression leads to Vav1 hyperphosphorylation and to the subsequent stimulation of its exchange activity towards Rac1, a process mediated by the formation of a trimolecular complex with Src kinases. This heteromolecular complex is coordinated by proline-rich and Src family-dependent phosphorylated regions of M2. Infection of Vavdeficient mice with gammaherpesvirus 68 results in increased long-term levels of latency in germinal center B lymphocytes, corroborating the importance of the M2/Vav cross talk in the process of viral latency. These results reveal a novel strategy used by the murine gammaherpesvirus family to subvert the lymphocyte signaling machinery to its own benefit. The persistence of herpesvirus in the infected organism is dictated by the establishment of latency in particular cell types within the host. In the case of gammaherpesviruses, such as

Lénia Rodrigues; Marta Pires De Mir; María J. Caloca; Xosé R. Bustelo; J. Pedro Simas

2005-01-01T23:59:59.000Z

108

Comparison of emerging diagnostic tools for large commercial HVAC systems  

E-Print Network (OSTI)

contracting, design decision information, fan benchmarking,Fan Systems (UCB Tools), University of California at Berkeley, Center for Environmental Design

Friedman, Hannah; Piette, Mary Ann

2001-01-01T23:59:59.000Z

109

title Potential Global Benefits of Improved Ceiling Fan Energy...  

NLE Websites -- All DOE Office Websites (Extended Search)

Fan Energy Efficiency year month keywords bottom up Ceiling fan Celing Fans efficiency energy efficiency Financial incentives Market Transformation residential Standards and...

110

Nonlinear fan instability of electromagnetic waves  

Science Conference Proceedings (OSTI)

This paper studies the linear and nonlinear stages of the fan instability, considering electromagnetic waves of the whistler frequency range interacting resonantly with energetic electron fluxes in magnetized plasmas. The main attention is paid to determine the wave-particle interaction processes that can lead to the excitation of intense electromagnetic waves by nonequilibrium particle distributions involving suprathermal tails, and to explain under what conditions and through what mechanisms they can occur, develop, and saturate. This paper presents and discusses two main processes: (i) the linear fan instability and (ii) the nonlinear process of dynamical resonance merging, which can significantly amplify the energy carried by linearly destabilized waves after they saturate due to particle trapping. This study consists of (i) determining analytically and numerically, for parameters typical of space and laboratory plasmas, the linear growth rates of whistlers excited by suprathermal particle fluxes through the fan instability, as well as the corresponding thresholds and the physical conditions at which the instability can appear, (ii) building a theoretical self-consistent 3D model and a related numerical code for describing the nonlinear evolution of the wave-particle system, and (iii) performing numerical simulations to reveal and characterize the nonlinear amplification process at work, its conditions of development, and its consequences, notably in terms of electromagnetic wave radiation. The simulations show that when the waves have reached sufficient energy levels owing to the linear fan instability, they saturate by trapping particles and due to the complex dynamics of these particles in the electromagnetic fields, the resonant velocities' domains of the waves overlap and merge, meanwhile a strong increase of the wave energy occurs.

Krafft, C. [Laboratoire de Physique des Plasmas, Ecole Polytechnique, 91128 Palaiseau Cedex (France) and University Paris Sud, 91405 Orsay Cedex (France); Volokitin, A. [Space Research Institute (IKI), 117997, 84/32 Profsoyuznaya Str., Moscow (Russian Federation)

2010-10-15T23:59:59.000Z

111

Induced draft fan innovation for heat recovery steam generators  

SciTech Connect

A first of its kind, induced draft (ID) heat recovery steam generators (HRSG) have been in service at a cogeneration facility since 1991. A preliminary engineering study considered a forced draft (FD) fan to supply combustion air to the HRSG duct burners (when the combustion turbine (CT) is out of service) as a traditional design; however, the study indicated that the FD fan may require the HRSG duct burner to be shut off following a CT trip and re-ignited after the FD fan was in service. Although the induced draft HRSG design cost more than the FD fan design, the induced draft design has improved the cogeneration facility's steam generation reliability by enabling the HRSG to remain in service following a CT trip. This paper briefly summarizes the preliminary engineering study that supported the decision to select the ID fan design. The paper also discusses the control system that operates the fresh-air louvers, duct burners, HRSG, and ID fan during a CT trip. Startup and operating experiences are presented that demonstrate the effectiveness of the design. Lessons learned are also summarized for input into future induced draft HRSG designs.

Beasley, O.W.; Hutchins, E.C. (Oklahoma Gas and Electric Co., Oklahoma City, OK (United States)); Predick, P.R.; Vavrek, J.M. (Sargent and Lundy, Chicago, IL (United States))

1994-04-01T23:59:59.000Z

112

Effect of building airtightness and fan size on the performance of mechanical ventilation systems in new U.S. houses: a critique of ASHRAE standard 62.2-2003  

E-Print Network (OSTI)

as sizing a fan to deliver the design ventilation rate (fans and natural infiltration, in order to properly designfans should be as small as necessary to deliver the effective design

Roberson, J.

2004-01-01T23:59:59.000Z

113

CBE EnergyPlus Modeling Methods for UFAD Systems  

E-Print Network (OSTI)

For these studies the fan design volume (and fan size) willall use the same AHU Fan design static pressure (FSP). ThisMethods for UFAD Systems Fan design efficiencies EnergyPlus

Webster, Tom; Bauman, Fred; Lee, Kwang Ho; Schiavon, Stefano; Daly, Alan; Hoyt, Tyler

2012-01-01T23:59:59.000Z

114

Ceiling Fan and Ceiling Fan Light Kit use in the U.S. Results of a Survey on Amazon Mechanical Turk  

E-Print Network (OSTI)

Ceiling Fan and Ceiling Fan Light Kit use in the U.S. —Ceiling Fan and Ceiling Fan Light Kit use in the U.S. —fans and ceiling fan light kits in the United States (

Kantner, Colleen L.S.

2013-01-01T23:59:59.000Z

115

Sound maintenance practices protect fan investments  

Science Conference Proceedings (OSTI)

Since underground coal miners depend on axial fans, lack of maintenance could prove costly. A number of pre-emptive actions that can help keep fans running at optimal performance can also be taken. 2 photos.

Bauer, M.

2009-11-15T23:59:59.000Z

116

Building Energy Software Tools Directory: ENERPASS  

NLE Websites -- All DOE Office Websites (Extended Search)

for each zone. A wide range of HVAC systems can be modelled including make-up air units, heat recovery ventilators, rooftop units, VAV, four-pipe fan coil, and dual duct. The...

117

Publications  

NLE Websites -- All DOE Office Websites (Extended Search)

Zheng, and Xiufeng Pang. "Impacts of Static Pressure Reset on VAV System Air Leakage, Fan Power, and Thermal Energy." ASHRAE Transactions 116, no. 1 (2010): 428-436. 2009 Cho,...

118

MECHANICAL DRAFT FANS FOR THE MODERN INCINERATOR  

E-Print Network (OSTI)

design and modiftcation. Spe cial blading and fan construction for use under corrosive conditions this will be kept fairly constant by air or water cooling during noral op eration. Since the fan will be designed. Volume control on a single inlet fan can be accomplished with a variable inlet #12;vane, designed

Columbia University

119

CHANGES IN SANDSTONE DISTRIBUTIONS BETWEEN THE UPPER, MIDDLE, AND LOWER FAN IN THE ARKANSAS JACKFORK GROUP  

E-Print Network (OSTI)

This study is a statistical analysis of the sandstone distribution within the Arkansas Jackfork Group which is a passive margin fan complex. Passive margin fan systems are typically associated with long fluvial transport, fed by deltas, wide shelf, efficient basin transport, that result in a bypassing system. Passive margin fans are generally fine-grained, mud rich, and well sorted. These fans can be separated into three units (upper, middle, and lower fan) based on their location within the fan and how the sediments are deposited. Five outcrops from the Arkansas Jackfork Group have been chosen for this study and each were divided into different facies dependent on sandstone percentages in certain bed sets. The amount of sandstone for each facies was calculated and a statistical approximation for each outcrop was determined. Sandstone distribution curves were made for each outcrop to show a graphic representation of how the sandstone is dispersed. After analyzing different upper, middle, and lower fan outcrops, it is clear there is an obvious change in the sandstone percentage and distribution. The upper fan deposit has an overall sandstone percentage of approximately 77.5% and is deposited in beds that are mainly amalgamated; 10-30m thick. Sandstone is deposited moderately even and is quite concentrated throughout the exposure. The middle fan outcrops contain approximately 72.6% sandstone and show similar patterns, except that the amalgamated sandstone beds are not as thick, 5-15m and contain more shale in between layers. As expected the lower fan outcrop is completely different in both sandstone percentage and distribution. The lower fan has approximately 65.4% sandstone. The distribution of sandstone is more concentrated in each of the individual units, or systems, but the overall complex has two systems separated by a massive marine shale bed, 33.5 m, that contains virtually no sand.

Mack, Clayton P.

2009-05-01T23:59:59.000Z

120

Experimental Evaluation of Installed Cooking Exhaust Fan Performance  

NLE Websites -- All DOE Office Websites (Extended Search)

Experimental Evaluation of Installed Cooking Exhaust Fan Performance Experimental Evaluation of Installed Cooking Exhaust Fan Performance Title Experimental Evaluation of Installed Cooking Exhaust Fan Performance Publication Type Report LBNL Report Number LBNL-4183E Year of Publication 2010 Authors Singer, Brett C., William W. Delp, and Michael G. Apte Publisher Lawrence Berkeley National Laboratory City Berkeley Keywords airflow & pollutant transport group, cooktop, energy analysis and environmental impacts department, gas burners, indoor air quality, indoor environment department, kitchen, nitrogen dioxide, oven, pollutant emissions, range hood, residential, source control, task ventilation, technology, sustainability and impact assessment group Abstract The installed performance of cooking exhaust fans was evaluated through residential field experiments conducted on a sample of 15 devices varying in design and other characteristics. The sample included two rear downdraft systems, two under-cabinet microwave over range (MOR) units, three different installations of an under-cabinet model with grease screens across the bottom and no capture hood, two devices with grease screens covering the bottom of a large capture hood (one under-cabinet, one wall-mount chimney), four under-cabinet open hoods, and two open hoods with chimney mounts over islands. Performance assessment included measurement of airflow and sound levels across fan settings and experiments to quantify the contemporaneous capture efficiency for the exhaust generated by natural gas cooking burners. Capture efficiency is defined as the fraction of generated pollutants that are removed through the exhaust and thus not available for inhalation of household occupants. Capture efficiency (CE) was assessed for various configurations of burner use (e.g. single front, single back, combination of one front and one back, oven) and fan speed setting. Measured airflow rates were substantially lower than the levels noted in product literature for many of the units. This shortfall was observed for several units costing in excess of $1000. Capture efficiency varied widely (from <5% to roughly 100%) across devices and across conditions for some devices. As expected, higher capture efficiencies were achieved with higher fan settings and the associated higher air flow rates. In most cases, capture efficiencies were substantially higher for rear burners than for front burners. The best and most consistent performance was observed for open hoods that covered all cooktop burners and operated at higher airflow rates. The lowest capture efficiencies were measured when a front burner was used with a rear backdraft system or with lowest fan setting for above the range systems that do not cover the front burners.

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


121

Performance Analysis of Dual-Fan, Dual-Duct Constant Volume Air-Handling Units  

E-Print Network (OSTI)

Dual-fan, dual-duct air-handling units introduce outside air directly into the cooling duct and use two variable speed devices to independently maintain the static pressure of the hot and the cold air ducts. Analytical models have been developed to compare fan power and thermal energy consumption of dualfan, dual-duct constant volume air-handling units with single-fan, dual-duct constant volume airhandling units. This study shows that the dual-fan, dual-duct system uses less fan power and less thermal energy during winter, and uses more thermal energy during summer. Thermal energy performance can be significantly improved if the thermal energy penalty can be decreased or eliminated.

Joo, I. S.; Liu, M.

2001-01-01T23:59:59.000Z

122

Knowing fans, knowing music : an exploration of fan interaction on Twitter  

E-Print Network (OSTI)

know many local Ritter fans yet” 26 She responded about aI see you're a Buffy fanare you also a Browncoat? : )”The term Browncoats refers to fans of the short-lived sci-fi

McCollum, Nick

2011-01-01T23:59:59.000Z

123

Submitting Organization Hongyou Fan Sandia National Laboratories  

NLE Websites -- All DOE Office Websites (Extended Search)

&24; 2007 R&D 100 Award Entry Form &24; Submitting Organization Hongyou Fan Sandia National Laboratories Advanced Materials Laboratory 1001 University Boulevard SE Albuquerque, NM...

124

A passive margin-type submarine fan complex, Permian Ecca Group, South Africa  

Science Conference Proceedings (OSTI)

A submarine fan complex, comprising five arenaceous fan systems separated by basinal shale units, occurs in the southwestern part of the intracratonic Karoo basin in South Africa. Although basin development is related to a subduction zone bordering the palaeo-Pacific ocean to the south of Gondwanaland and the evolution of the Cape Fold Belt, the entire Lower Permian Ecca Group basin-fill succession reflects depositional characteristics of a passive-margin setting. The submarine fan complex, 250 m thick, originated from sediments supplied by Mississippi-type deltas dominating the Ecca coastline. The fine grain-size and low sand/shale ratio of the submarine fan and deltaic deposits reflect the maturity of the ancient river systems. Outcrops of the fan complex are well exposed and cover an area of 650 km{sup 2}. The strata are not affected by folding, and deep erosion allows three-dimensional viewing of mid-fan to outer-fan deposits. Features of interest include stacked lobe deposits displayed along 2.5 km of a 60 m high cliff section, and a transverse cliff section through channel-fill deposits 500 m wide. Paleocurrent directions reveal that each sequence had its own main source area located to the northwest and south of its present geographic location. The cyclic nature of the fan complex is attributed to relative sea-level changes; deposition took place on the basin floor in water depths that do not exceed 500 m. Shoaling of the basin to wave base depths is reflected in the pro-delta and delta front deposits overlying the uppermost fan sequence. Major factors in controlling direction of fan progradation were delta switching and basin floor topography.

Wickens, H.D. (SOEKOR-Pty. Ltd., Parow (South Africa)); Bouma, A.H. (Louisiana State Univ., Baton Rouge (United States))

1991-03-01T23:59:59.000Z

125

Experimental Evaluation of Installed Cooking Exhaust Fan Performance  

SciTech Connect

The installed performance of cooking exhaust fans was evaluated through residential field experiments conducted on a sample of 15 devices varying in design and other characteristics. The sample included two rear downdraft systems, two under-cabinet microwave over range (MOR) units, three different installations of an under-cabinet model with grease screens across the bottom and no capture hood, two devices with grease screens covering the bottom of a large capture hood (one under-cabinet, one wall-mount chimney), four under-cabinet open hoods, and two open hoods with chimney mounts over islands. Performance assessment included measurement of airflow and sound levels across fan settings and experiments to quantify the contemporaneous capture efficiency for the exhaust generated by natural gas cooking burners.Capture efficiency is defined as the fraction of generated pollutants that are removed through the exhaust and thus not available for inhalation of household occupants. Capture efficiency (CE) was assessed for various configurations of burner use (e.g., single front, single back, combination of one front and one back, oven) and fan speed setting. Measured airflow rates were substantially lower than the levels noted in product literature for many of the units. This shortfall was observed for several units costing in excess of $1000. Capture efficiency varied widely (from<5percent to roughly 100percent) across devices and across conditions for some devices. As expected, higher capture efficiencies were achieved with higher fan settings and the associated higher air flow rates. In most cases, capture efficiencies were substantially higher for rear burners than for front burners. The best and most consistent performance was observed for open hoods that covered all cooktop burners and operated at higher airflow rates. The lowest capture efficiencies were measured when a front burner was used with a rear backdraft system or with lowest fan setting for above the range systems that do not cover the front burners.

Singer, Brett C.; Delp, William W.; Apte, Michael G.

2010-11-01T23:59:59.000Z

126

Advanced Energy-Efficient Filtration: Fan Filter Unit  

E-Print Network (OSTI)

Efficient Fan- Filter Units, Proceedings of SEMI TechnicalFor Evaluating Fan-Filter Unit Performance – Applications inPerformance of Fan-Filter Units, Version 1.2 (2004, public

Xu, Tengfang

2005-01-01T23:59:59.000Z

127

Advanced Energy-Efficient Filtration: Fan Filter Unit  

E-Print Network (OSTI)

Cleanrooms: Energy Efficient Fan- Filter Units, ProceedingsStandard Method For Evaluating Fan-Filter Unit Performance –Energy Performance of Fan-Filter Units, Version 1.2 (2004,

Xu, Tengfang

2005-01-01T23:59:59.000Z

128

Best Practice for Energy Efficient Cleanrooms: Fan-Filter Units  

E-Print Network (OSTI)

control F iltra ti on ? Fan Efficiency ? Right Sizing ?Energy Performance of Fan-Filte r Units, Version 1.3 (2005),RP36.1 (Draft). Testing Fan-Filter Units. Draft Recommended

Xu, Tengfang

2005-01-01T23:59:59.000Z

129

The Effect of Inlet Flow Profile Distortion on Fan Performance  

Science Conference Proceedings (OSTI)

Performance tests on fans for utility and industrial applications are based on codes that expect a relatively uniform velocity profile at the fan inlet. Unfortunately, when fans scaled up from the ideal model fans are installed in actual utility and industrial applications, non-uniform or distorted flow patterns often occur at the inlet of the fan. This project sought to determine and, if possible, quantify the effect on fan performance of distorted inlet flow profiles. A second goal was to determine whe...

2010-02-22T23:59:59.000Z

130

Redesign of ceiling fan - adapted to the Scandinavian market.  

E-Print Network (OSTI)

?? The master degree thesis project, at Halmstad University, was made in cooperation with Hunter Fan, one of the leading fan companies on the American… (more)

Eliasson, Anna

2007-01-01T23:59:59.000Z

131

Potential Global Benefits of Improved Ceiling Fan Energy Efficiency  

NLE Websites -- All DOE Office Websites (Extended Search)

Global Benefits of Improved Ceiling Fan Energy Efficiency Title Potential Global Benefits of Improved Ceiling Fan Energy Efficiency Publication Type Report LBNL Report Number...

132

Duct leakage impacts on VAV system performance in California large commercial buildings  

E-Print Network (OSTI)

GLOSSARY 34 REFERENCES. 34 APPENDIX I: BUILDING SCHEDULES.. 37 APPENDIX II: REGRESSION EQUATIONS AND COEFFICIENTS . 40 APPENDIX III: ENERGY

Wray, Craig P.; Matson, Nance E.

2003-01-01T23:59:59.000Z

133

Duct leakage impacts on VAV system performance in California large commercial buildings  

E-Print Network (OSTI)

air leakage rate, then proposed buildings will be rewarded for sealingduct sealing even more cost-effective. Table 5. TRNSYS Air-

Wray, Craig P.; Matson, Nance E.

2003-01-01T23:59:59.000Z

134

Duct leakage impacts on VAV system performance in California large commercial buildings  

E-Print Network (OSTI)

electricity consumption, and boiler natural gas consumption. Using yearelectricity consumption, and boiler natural gas consumption. Using yearelectricity consumption, and boiler natural gas consumption. Using year

Wray, Craig P.; Matson, Nance E.

2003-01-01T23:59:59.000Z

135

Duct leakage impacts on VAV system performance in California large commercial buildings  

E-Print Network (OSTI)

chiller and cooling tower electricity consumption, boilerchiller and cooling tower electricity consumption, boilerheat outdoors using a cooling tower. A natural-gas-fired

Wray, Craig P.; Matson, Nance E.

2003-01-01T23:59:59.000Z

136

Fan-fold shielded electrical leads  

DOE Patents (OSTI)

Disclosed are fan-folded electrical leads made from copper cladded Kapton, for example, with the copper cladding on one side serving as a ground plane and the copper cladding on the other side being etched to form the leads. The Kapton is fan folded with the leads located at the bottom of the fan-folds. Electrical connections are made by partially opening the folds of the fan and soldering, for example, the connections directly to the ground plane and/or the lead. The fan folded arrangement produces a number of advantages, such as electrically shielding the leads from the environment, is totally non-magnetic, and has a very low thermal conductivity, while being easy to fabricate. 3 figs.

Rohatgi, R.R.; Cowan, T.E.

1996-06-11T23:59:59.000Z

137

Fan-fold shielded electrical leads  

DOE Patents (OSTI)

Fan-folded electrical leads made from copper cladded Kapton, for example, with the copper cladding on one side serving as a ground plane and the copper cladding on the other side being etched to form the leads. The Kapton is fan folded with the leads located at the bottom of the fan-folds. Electrical connections are made by partially opening the folds of the fan and soldering, for example, the connections directly to the ground plane and/or the lead. The fan folded arrangement produces a number of advantages, such as electrically shielding the leads from the environment, is totally non-magnetic, and has a very low thermal conductivity, while being easy to fabricate.

Rohatgi, Rajeev R. (Mountain View, CA); Cowan, Thomas E. (Livermore, CA)

1996-01-01T23:59:59.000Z

138

Hot Thermal Storage/Selective Energy System Reduces Electric Demand for Space Cooling As Well As Heating in Commercial Application  

E-Print Network (OSTI)

Based on an experimental residential retrofit incorporating thermal storage, and extensive subsequent modeling, a commercial design was developed and implemented to use hot thermal storage to significantly reduce electric demand and utility energy costs during the cooling season as well as the heating season. To achieve air conditioning savings, the system separates dehumidification from sensible cooling; dehumidifies by desiccant absorption, using heat from storage to dry the desiccant; and then cools at an elevated temperature improving overall system efficiency. Efficient heat for desiccant regeneration is provided by a selective-energy system coupled with thermal storage. The selective-energy system incorporates diesel cogeneration, solar energy and off-peak electric resistance heating. Estimated energy and first cost savings, as compared with an all-electric VAV HVAC system, are: 30 to 50% in ductwork size and cost; 30% in fan energy; 25% in air handling equipment; 20 to 40% in utility energy for refrigeration; 10 to 20% in refrigeration equipment; and space savings due to smaller ductwork and equipment.

Meckler, G.

1985-01-01T23:59:59.000Z

139

Ceiling Fan and Ceiling Fan Light Kit use in the U.S. Results of a Survey on Amazon Mechanical Turk  

E-Print Network (OSTI)

Intellect, LLC (2011). Ceiling fan consumer survey data fromconsumption from ceiling fans. 5 References Amazon.com. (January/February 2001). Ceiling fans: Fulfilling the energy

Kantner, Colleen L.S.

2013-01-01T23:59:59.000Z

140

Performance evaluation of cleanroom environmental systems  

E-Print Network (OSTI)

utilize three common designs: a) Fan-tower with pressurized-design at early stage of the project, and by adopting fans andheat from fan operation. Like optimizing system design and

Xu, Tengfang

2003-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


141

Quiet Computing with BSD: Fan control with sysctl hw.sensors.  

E-Print Network (OSTI)

We will discuss the topic of fan control and introduce sysctl-based interfacing with the fancontrolling capabilities of microprocessor system hardware monitors on OpenBSD. The discussed prototype implementation reduces the noise and power-consumption characteristics in fans of personal computers, especially of those PCs that are designed from off-the-shelf components. We further argue that our prototype is easier, robuster and more intuitive to use compared to solutions available elsewhere. 1.

Constantine A. Murenin; Raouf Boutaba

2010-01-01T23:59:59.000Z

142

Root-Cause Failure Analysis: Fossil-Fired Power Plant Draft Fans  

Science Conference Proceedings (OSTI)

This report describes the collection and analysis of fan-related outage data for 61 large fossil fuel steam power plants. The outage causes are ranked in terms of their impact on production, and a systematic search for generic root causes is described. Recommendations are made for short-term corrective measures and for longer-term research efforts to significantly improve fan system reliability.

1983-07-01T23:59:59.000Z

143

Cooling with a Whole House Fan | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Cooling with a Whole House Fan Cooling with a Whole House Fan Cooling with a Whole House Fan May 30, 2012 - 6:54pm Addthis Whole house fan installed as part of a home retrofit project in California. | Photo courtesy of Lieko Earle, NREL. Whole house fan installed as part of a home retrofit project in California. | Photo courtesy of Lieko Earle, NREL. What does this mean for me? A whole-house fan may be sufficient to cool your house, at least for part of the year. In many climates, a whole-house fan can save you money and maintain comfort during the cooling season. How does it work? A whole-house fan works by pulling air in through windows and exhausting it through the attic and roof. Whole house cooling using a whole house fan can substitute for an air conditioner most of the year in most climates. Whole house fans combined

144

Laugh out loud in real life : women's humor and fan identity; Women's humor and fan identity.  

E-Print Network (OSTI)

??The emerging field of fan studies has, until recently, been defined only by the research that has taken place within it. Almost universally, this research… (more)

Klink, Madeline LeNore

2010-01-01T23:59:59.000Z

145

Fanning the Flames of Romance: An Exploration of Fan Fiction and the Romance Novel.  

E-Print Network (OSTI)

??Fan fiction and romance novels constitute two bodies of romantic literature being produced for and by women within dramatically different environments. The purpose of this… (more)

Morrissey, Katherine

146

Evaluation of the cooling fan efficiency index.  

E-Print Network (OSTI)

between the cooling effect (measured with a thermal manikin)output is the body cooling effect [5]. Thermal manikins withThermal manikins can be used to measure the fan cooling

Schiavon, Stefano; Melikov, Arsen

2009-01-01T23:59:59.000Z

147

Experimental Evaluation of Installed Cooking Exhaust Fan Performance  

Science Conference Proceedings (OSTI)

The installed performance of cooking exhaust fans was evaluated through residential field experiments conducted on a sample of 15 devices varying in design and other characteristics. The sample included two rear downdraft systems, two under-cabinet microwave over range (MOR) units, three different installations of an under-cabinet model with grease screens across the bottom and no capture hood, two devices with grease screens covering the bottom of a large capture hood (one under-cabinet, one wall-mount chimney), four under-cabinet open hoods, and two open hoods with chimney mounts over islands. Performance assessment included measurement of airflow and sound levels across fan settings and experiments to quantify the contemporaneous capture efficiency for the exhaust generated by natural gas cooking burners.Capture efficiency is defined as the fraction of generated pollutants that are removed through the exhaust and thus not available for inhalation of household occupants. Capture efficiency (CE) was assessed for various configurations of burner use (e.g., single front, single back, combination of one front and one back, oven) and fan speed setting. Measured airflow rates were substantially lower than the levels noted in product literature for many of the units. This shortfall was observed for several units costing in excess of $1000. Capture efficiency varied widely (fromfan settings and the associated higher air flow rates. In most cases, capture efficiencies were substantially higher for rear burners than for front burners. The best and most consistent performance was observed for open hoods that covered all cooktop burners and operated at higher airflow rates. The lowest capture efficiencies were measured when a front burner was used with a rear backdraft system or with lowest fan setting for above the range systems that do not cover the front burners.

Singer, Brett C.; Delp, William W.; Apte, Michael G.

2010-11-01T23:59:59.000Z

148

An Innovative Method for Dynamic Characterization of Fan Filter Unit Operation.  

E-Print Network (OSTI)

Filtration: Fan filter units. Final Report, LawrencePerformance of Fan Filter Units, Version 1.3. ” BerkeleyEfficient Fan filter units,” Proceedings of Semiconductor

Xu, Tengfang

2006-01-01T23:59:59.000Z

149

Uranium-series comminution ages of continental sediments: Case study of a Pleistocene alluvial fan  

E-Print Network (OSTI)

of a stream-dominated alluvial fan, San Joaquin valley,on Quaternary fluvial fans, San Joaquin Basin, California,M. , (Eds), Alluvial Fans: Geomorphology, Sedimentology,

Lee, Victoria E.

2010-01-01T23:59:59.000Z

150

An Innovative Method for Dynamic Characterization of Fan Filter Unit Operation.  

E-Print Network (OSTI)

Laboratory Methods of Testing Fans for Rating. ASHRAE. 1987.Efficient Filtration: Fan filter units. Final Report,Energy Performance of Fan Filter Units, Version 1.3. ”

Xu, Tengfang

2006-01-01T23:59:59.000Z

151

Characteristics of some submarine fan channels, Permian Ecca Group, South Africa  

Science Conference Proceedings (OSTI)

The vary well exposed submarine fan complex in the southwestern part of the Karoo basin permits close examination of channel-fills and in places their associated overbank deposits. The complex comprises five arenaceous fan systems some of which attain 60 m in thickness. The fans are vertically stacked and separated by basinal shale deposits; each system with its own direction of growth. The association of channelized sandstone bodies and thin-bedded sandstone and shale packages in an updip position from predominantly stacked lobe deposits suggest preservation of middle fan settings. A 500 m wide, 20 m thick channel-fill consisting massive amalgamated sandstone beds occupying the channel thalweg occurs in a setting dominated by thin-bedded, ripple-laminated sandstone and shale. Gradual thinning of the channel-fill beds toward the channel edges, lack of internal lateral accretion, and a high width to depth ratio suggests a low sinuous to straight channel. The channel-fill is capped by an abandonment facies characterized by ripple-laminated sandstone and shale. Stacked, laterally offset channel-fill deposits with highly erosional contacts and typical well-bedded overbank deposits form channel-overbank complexes and characterize the mid-fan region of the uppermost fan system. Palaeocurrent directions and gradual diminishing of bed-thickness away from the generally massively bedded, amalgamated channel-fill sandstones confirm a simultaneous channel/overbank origin for these deposits. Levee morphology has not been recognized. Both examples of channel-fills cited reveal part of the complexity of the channelized portions of submarine fans and hence the implications thereof in exploring for hydrocarbon reservoirs.

Bouma, A.H. (Louisiana State Univ., Baton Rouge (United States)); Dev Wickens, H. (Soekor, Parow (South Africa))

1991-03-01T23:59:59.000Z

152

Fan-less long range alpha detector  

DOE Patents (OSTI)

A fan-less long range alpha detector which operates by using an electrical field between a signal plane and the surface or substance to be monitored for air ions created by collisions with alpha radiation. Without a fan, the detector can operate without the possibility of spreading dust and potential contamination into the atmosphere. A guard plane between the signal plane and the electrically conductive enclosure and maintained at the same voltage as the signal plane, reduces leakage currents. The detector can easily monitor soil, or other solid or liquid surfaces.

MacArthur, Duncan W. (Los Alamos, NM); Bounds, John A. (Los Alamos, NM)

1994-01-01T23:59:59.000Z

153

Fan-less long range alpha detector  

DOE Patents (OSTI)

A fan-less long range alpha detector is disclosed which operates by using an electrical field between a signal plane and the surface or substance to be monitored for air ions created by collisions with alpha radiation. Without a fan, the detector can operate without the possibility of spreading dust and potential contamination into the atmosphere. A guard plane between the signal plane and the electrically conductive enclosure and maintained at the same voltage as the signal plane, reduces leakage currents. The detector can easily monitor soil, or other solid or liquid surfaces. 2 figures.

MacArthur, D.W.; Bounds, J.A.

1994-05-10T23:59:59.000Z

154

Fan blade development. Final report Sep 81-Sep 82  

SciTech Connect

The objective of this program was to develop an improved fan blade that could be utilized in place of the current steel fan blade on the Pedal Ventilator Kit (PVK). The goals of the program were to reduce both the unit cost and weight of the fan while maintaining its effectiveness and reliability. A value analysis study was conducted on the fan blade to determine material/design revisions that offered potential manufacturing economies. Based on the conclusions of the study, two designs were chosen for fabrication. The two fan designs were constructed and tested. As a result of the performance testing, one fan blade emerged as the optimum design. Fifteen fan blades of the optimum design were constructed for FEMA inspection and distribution. Preliminary specifications were generated for the fan blade assembly. in addition, production cost estimates based on a procurement of 100,000 units were formulated for FEMA budgetary purposes.

Buday, J.M.

1982-09-01T23:59:59.000Z

155

Fan Blade Fracture in a Welded Assembly - Programmaster.org  

Science Conference Proceedings (OSTI)

About this Abstract. Meeting, Materials Science & Technology 2013. Symposium, Failure Analysis and Prevention. Presentation Title, Fan Blade Fracture in a ...

156

Heavy Vehicle Systems Optimization 2003 Annual Progress Report  

NLE Websites -- All DOE Office Websites (Extended Search)

... 55 A. Cooling Fan and System Performance and Efficiency Improvements Caterpillar Incorporated; R.L....

157

TR-034 Geomorphology March 2006 Coastal fan destabilization  

E-Print Network (OSTI)

the watershed boundary). 3.0 STUDY DESIGN AND METHODS To evaluate fans from a broad range of coastal conditionsTR-034 Geomorphology March 2006 Coastal fan destabilization and forest management by T.H. Millard Columbia V9L 1V2 Citation: Millard, T.H., D.J. Wilford and M.E. Oden. 2006. Coastal fan destabilization

158

Recent Sediments of the Monterey Deep-Sea Fan  

E-Print Network (OSTI)

T Or THE MONTEREV DEEP SEA FAN PLAlE Conpl1.d and ren1our.dO F THE MONTEREY DEEP- SEA FAN by P a t Wilde Berkeley,of segmented alluvial fans in w e s t e r n F r e s n o

Wilde, Pat

1965-01-01T23:59:59.000Z

159

High Efficiency Fans and High Efficiency Electrical Motors  

E-Print Network (OSTI)

Replacing nominal efficient electrical motors with premium efficiency can save on electrical power costs in cotton gins. Connected horsepower load on industrial air fans is approximately 60% of the total horsepower in a typical cotton gin. By replacing old inefficient centrifugal fans with new higher efficiency fans, additional power savings can be achieved.

Breedlove, C. W.

1989-09-01T23:59:59.000Z

160

Data Linking with Ontology Alignment Zhengjie Fan  

E-Print Network (OSTI)

Data Linking with Ontology Alignment Zhengjie Fan INRIA & LIG 655, avenue de l'Europe, Montbonnot data on the web, so that users can share information semantically. Then, linking isolated data sets to to be compared, so that it enhances the accuracy of the linking process. I propose a data linking method

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


161

Lattice congruences, fans and Hopf algebras  

Science Conference Proceedings (OSTI)

We give a unified explanation of the geometric and algebraic properties of two well-known maps, one from permutations to triangulations, and another from permutations to subsets. Furthermore we give a broad generalization of the maps. Specifically for ... Keywords: Malvenuto-Reutenauer Hopf algebra, coexter group, fan poset, hyperplane arrangement, pattern avoidance, permutohedron, poset of regions, weak order

Nathan Reading

2005-05-01T23:59:59.000Z

162

List of Whole House Fans Incentives | Open Energy Information  

Open Energy Info (EERE)

Whole House Fans Incentives Whole House Fans Incentives Jump to: navigation, search The following contains the list of 26 Whole House Fans Incentives. CSV (rows 1 - 26) Incentive Incentive Type Place Applicable Sector Eligible Technologies Active Alliant Energy Interstate Power and Light (Gas and Electric) - Farm Equipment Energy Efficiency Incentives (Iowa) Utility Rebate Program Iowa Agricultural Agricultural Equipment Ceiling Fan Clothes Washers Custom/Others pending approval Dishwasher Doors Heat recovery Lighting Motor VFDs Motors Refrigerators Water Heaters Windows Whole House Fans Room Air Conditioners Ground Source Heat Pumps Yes Alliant Energy Interstate Power and Light - Farm Equipment Energy Efficiency Incentives (Minnesota) Utility Rebate Program Minnesota Agricultural Agricultural Equipment

163

List of Ceiling Fan Incentives | Open Energy Information  

Open Energy Info (EERE)

Fan Incentives Fan Incentives Jump to: navigation, search The following contains the list of 99 Ceiling Fan Incentives. CSV (rows 1 - 99) Incentive Incentive Type Place Applicable Sector Eligible Technologies Active AEP Ohio (Electric) - Residential Energy Efficiency Rebate Program (Ohio) Utility Rebate Program Ohio Residential Building Insulation Ceiling Fan Central Air conditioners Custom/Others pending approval Duct/Air sealing Heat pumps Lighting Motors Programmable Thermostats Windows Yes AEP Ohio (Gas) - Residential Energy Efficiency Rebate Program (Ohio) Utility Rebate Program Ohio Residential Building Insulation Ceiling Fan Central Air conditioners Custom/Others pending approval Dehumidifiers Duct/Air sealing Heat pumps Lighting Motors Programmable Thermostats

164

Modeling of Electronically Commutated Motor Controlled Fan-powered Terminal Units  

E-Print Network (OSTI)

Empirical models of airflow and power consumption were developed for series and parallel variable air volume fan powered terminal units (FPTUs). An experimental setup and test procedure were developed to test the terminal units over typical operating ranges. The terminal units in this study used either an 8 in. (20.32 cm) or a 12 in. (30.48 cm) primary air inlet. All terminal units utilized electronically commutated motor (ECM) controllers. Data collected were compared against previous data collected for silicon controlled rectifier (SCR) units. Generalized models were developed for both series and parallel units, and compared against models developed for SCR units. In addition to the performance modeling, power factor and power quality data were also collected for each terminal unit. The power quality analysis included recording and analyzing harmonic distortion for current, voltage, and power up to the 25th harmonic. The total harmonic distortion (THD) was also recorded and presented. For the series terminal units, models were developed for fan airflow, fan power, and primary airflow. The models for fan airflow all had R2 values above 0.987. The models for fan power all had R2 values above 0.968. The models for primary airflow all had R2 values above 0.895. For the parallel terminal units, models were developed for leakage, fan airflow, fan power, and primary airflow. All of the leakage models had R2 values above 0.826. All of the fan airflow models had R2 values above 0.955. All of the fan power models had R2 values above 0.922. All of the primary airflow models had R2 values above 0.872. The real power THD was below 1.5 percent for both series and parallel FPTUs. The current THD ranged from 84 percent to 172 percent for series FPTUs and from 83 percent to 183 percent for parallel FPTUs. The voltage THD was below 1.4 percent for both series and parallel FPTUs. The performance models developed will help improve the accuracy of building energy simulation programs for heating, ventilation, and air conditioning (HVAC) systems utilizing ECM controlled FPTUs. Increasing the accuracy of these simulations will allow HVAC system designers to better optimize their designs for specific building types in a wide variety of climates.

Edmondson, Jacob Lee

2009-12-01T23:59:59.000Z

165

Analysing International Sports Fan Motivations and Constraints: The Case of Japanese International Sports Fan Tourists and Rugby World Cup Fan Tourists.  

E-Print Network (OSTI)

??The scale of professional sports leagues and mega sports events has expanded recently. Many sports fans travel to foreign countries to watch international events featuring… (more)

Nishio, Tatsuru

2013-01-01T23:59:59.000Z

166

Mass and fans in attached sunspaces  

DOE Green Energy (OSTI)

The effect of thermal storage mass on the performance of an attached sunspace is investigated for a particular design in Boston. Mass in the sunspace and in the adjoining building are compared. Performance is evaluated in terms of temperature conditions in the sunspace and delivery of useful solar heat to the adjoining building. The dependence of the results on the manner of heat delivery is studied. Both natural convection and fan-forced air flow are included.

Jones, R.W.; McFarland, R.D.; Lazarus, G.S.

1982-01-01T23:59:59.000Z

167

Use of fan rig data for the understanding and prediction of fan broadband noise and noise changes due to a variable area nozzle.  

E-Print Network (OSTI)

??This thesis presents the results of the research component of this EngD, entitled Use of fan rig data for the understanding and prediction of fan… (more)

Deane, Eugene Pio

2009-01-01T23:59:59.000Z

168

Engineering Task Plan for Hepa Filter Differential Pressure (DP) Fan Interlock Upgrades  

SciTech Connect

This document provides a plan for installation of Differential Pressure (DP) fan interlocks on the primary ventilation systems in selected Tank Farm facilities. This plan contains the engineering tasks required for installation and is summarized by the Acceptance for Beneficial Use list. Individuals responsible for each task are identified and scheduled accordingly.

SIMONS, S.R.

2000-05-19T23:59:59.000Z

169

An Aerodynamic Design Technique For Optimizing Fan Blade Spacing  

E-Print Network (OSTI)

INTRODUCTION Aerodynamic shape optimization involves designing the most efficient shapes of bodies that move through fluids. An optimization algorithm perturbs the shape of an airfoil until it finds the shape which best exhibits a given design objective. For an inverse design technique, this objective is a prescribed aerodynamic distribution, usually the surface pressure distribution. Liebeck pressure distributions [1], for example, have been demonstrated to generate airfoils with high lift to drag ratios. When designing fans, consideration must be given not only to the shape of the fan blades, but also to the distance separating the fan blades. This spacing is defined by the pitch/chord ratio t/l, where the pitch, t, is the distance between fan blades, and the chord, l, is the length of each fan blade. In this work, an inverse algorithm is developed, then used to design fan blade shapes and to find the optimal blade spacing.

T. Rogalsky; R.W. Derksen; Rt N; Rt N; S. Kocabiyik

1999-01-01T23:59:59.000Z

170

Buildings Energy Data Book: 5.5 Thermal Distribution Systems  

Buildings Energy Data Book (EERE)

5 5 Typical Commercial Building Thermal Energy Distribution Design Load Intensities (Watts per SF) Distribution System Fans Other Central System Supply Fans Cooling Tower Fan Central System Return Fans Air-Cooled Chiller Condenser Fan 0.6 Terminal Box Fans 0.5 Exhaust Fans (2) Fan-Coil Unit Fans (1) Condenser Fans 0.6 Packaged or Split System Indoor Blower 0.6 Pumps Chilled Water Pump Condenser Water Pump Heating Water Pump Note(s): Source(s): 0.1 - 0.2 0.1 - 0.2 1) Unducted units are lower than those with some ductwork. 2) Strong dependence on building type. BTS/A.D. Little, Energy Consumption Characteristics of Commercial Building HVAC Systems, Volume II:Thermal Distribution, Auxiliary Equipment, and Ventilation, Oct. 1999, Table 3-1, p. 3-6. 0.3 - 1.0 0.1 - 0.3 0.1 - 0.4

171

Effect of baselevel change on floodplain and fan sediment storage and ephemeral tributary channel morphology, Navarro River, California  

E-Print Network (OSTI)

CHANGE ON FLOODPLAIN AND FAN SEDIMENT STORAGE AND EPHEMERALaffects floodplain and fan sediment storage and smalllowered baselevel on floodplain and fan sediment storage and

Florsheim, Joan L; Mount, Jeffrey F.; Rutten, Luke T.

2000-01-01T23:59:59.000Z

172

Field Study of Exhaust Fans for Mitigating Indoor Air Quality Problems: Final Report to Bonneville Power Administration  

E-Print Network (OSTI)

Using Mechanical Ventilation Exhaust Fans Air-to-Air Heatexpected from exhaust fan A-I Infiltration contribution toIndoor Air Quality -- Exhaust Fan Mitigation" Final Report

Grimsrud, David T.

2009-01-01T23:59:59.000Z

173

Stratigraphic evolution and characteristics of lobes : a high-resolution study of Fan 3, Tanqua Karoo, South Africa.  

E-Print Network (OSTI)

??Fan 3 is one of four basin-floor fans that form part of the Tanqua Karoo Fan Complex in South Africa. It can be subdivided into… (more)

Neethling, J. M.

2009-01-01T23:59:59.000Z

174

Active control of fan noise and vortex shedding.  

E-Print Network (OSTI)

??[Truncated abstract] The subject of fan noise generating mechanisms and its control has been studied intensively over the past few decades as a result of… (more)

Wong, Yee-Jun

2004-01-01T23:59:59.000Z

175

Optimization of Active Noise Control for Small Axial Cooling Fans.  

E-Print Network (OSTI)

??Previous work has shown that active noise control is a feasible solution to attenuate tonal noise radiated by small axial cooling fans, such as those… (more)

Monson, Brian B 1979-

2006-01-01T23:59:59.000Z

176

Characteristics of Residential Housing Units by Ceiling Fans, 2001  

U.S. Energy Information Administration (EIA)

A reporting of the number of housing units using ceiling fans in U.S. households as reported in the 2001 Residential Energy Consumption Survey

177

Table 1. Household Characteristics by Ceiling Fans, 2001  

U.S. Energy Information Administration (EIA)

A reporting of the number of housing units using ceiling fans in U.S. households as reported in the 2001 Residential Energy Consumption Survey

178

Cooling Tower Fan Motor Power Optimization Study  

Science Conference Proceedings (OSTI)

Cooling towers are in use at more than 200 major electric generating plants in the United States, representing approximately 800 units and a total of more than 210,000 MW. The auxiliary power consumed by cooling tower fan motors can significantly reduce the net power output of steam-cycle power plants. Cooling tower specifications are established by the economic and operational requirements of maximum unit load and the most demanding environmental conditions expected in the tower’s locale. Since power pl...

2011-11-16T23:59:59.000Z

179

Standard Methods of Characterizing Performance of Fan Filter Units, Version 3.0  

E-Print Network (OSTI)

power input to operate the FFU at certain airflow conditions, including fan motor, controller, and transformerpower supply to the fan motor, speed control and display device, transformer,power demand shall include fan motor, speed control and display device, transformer,

Xu, Tengfang

2007-01-01T23:59:59.000Z

180

An Innovative Method for Dynamic Characterization of Fan Filter Unit Operation.  

E-Print Network (OSTI)

power for fan motor, controller, and accessories such as transformerpower demand shall include fan motor, speed control and display device, transformer,power demand shall include the fan, frequency drive motor, speed control device, transformer

Xu, Tengfang

2006-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


181

An Innovative Method for Dynamic Characterization of Fan Filter Unit Operation.  

E-Print Network (OSTI)

that is affected by fan-wheel design, air-path and size,by- 4-ft) fan filter units with various design, operation,differential – the design and control schemes of fan filter

Xu, Tengfang

2006-01-01T23:59:59.000Z

182

Development of a Fan-Filter Unit Test Standard, Laboratory Validations, and its Applications across Industries  

E-Print Network (OSTI)

Energy Performance of Fan-Filter Units, Version 1.3 (2005).Energy Performance of Fan-Filter Units, Version 2.0 (2006).Evaluation of Fan-filter Units’ Aerodynamic and Energy

Xu, Tengfang

2008-01-01T23:59:59.000Z

183

Development of a Fan-Filter Unit Test Standard, Laboratory Validations, and its Applications across Industries  

E-Print Network (OSTI)

Energy Performance of Fan-Filter Units, Version 1.3 (2005).Energy Performance of Fan-Filter Units, Version 2.0 (2006).Laboratory Evaluation of Fan-filter Units’ Aerodynamic and

Xu, Tengfang

2008-01-01T23:59:59.000Z

184

Laboratory evaluation of fan/filter units' aerodynamic and energy performance  

E-Print Network (OSTI)

Jeng, M.S. , F. Tsau. 2002. Fan-Filter Unit (FFU) TestLaboratory Methods of Testing Fans for Rating, Air MovementTest Procedure For Fan-Filter Units (not published). Xu,

Xu, Tengfang; Jeng, Ming-Shan

2004-01-01T23:59:59.000Z

185

Standard Methods of Characterizing Performance of Fan Filter Units, Version 3.0  

E-Print Network (OSTI)

Efficient Filtration: Fan-filter Units. Final Report,Xu. 2007. “The Development of Fan Filter Unit with Flow Rate2007. “Performance of Large Fan Filter Units for Cleanroom

Xu, Tengfang

2007-01-01T23:59:59.000Z

186

“Starring” Madhuri as Durga: The Madhuri Dixit Temple and Performative Fan-Bhakti of Pappu Sardar  

E-Print Network (OSTI)

Devotion and Defiance in Fan Activity. ” In Ravi Vasudevan,Temple and Performative Fan-Bhakti of Pappu Sardar / 415Temple and Performative Fan-Bhakti of Pappu Sardar Shalini

Kakar, Shalini

2009-01-01T23:59:59.000Z

187

Fan-speed-aware scheduling of data intensive jobs  

Science Conference Proceedings (OSTI)

As server processor power densities increase, the cost of air cooling also grows resulting from higher fan speeds. Our measurements show that vibrations induced by fans in high-end servers and its rack neighbors cause a dramatic drop in hard disk bandwidth, ... Keywords: cooling, disk i/o, energy, thermal, vibration

Christine S. Chan; Yanqin Jin; Yen-Kuan Wu; Kenny Gross; Kalyan Vaidyanathan; Tajana `imuni Rosing

2012-07-01T23:59:59.000Z

188

Choosing the right boiler air fans at Weston 4  

SciTech Connect

When it came to choosing the three 'big' boiler air fans - forced draft, induced draft and primary air, the decision revolved around efficiency. The decision making process for fan selection for the Western 4 supercritical coal-fired plant is described in this article. 3 photos.

Spring, N.

2009-04-15T23:59:59.000Z

189

Condition Monitoring of Fans With Rolling Element Bearings  

Science Conference Proceedings (OSTI)

Data on high-frequency vibration caused by the impacts of bearing pits and spalls can help utilities schedule equipment maintenance. One data collection technique, developed through long-term monitoring of combustion air axial fans at the Pennsylvania Electric Company Homer City station, helps plant personnel anticipate failures of draft fan antifriction bearings by several months.

1988-03-22T23:59:59.000Z

190

Feedback Applications in Active Noise Control for Small Axial Cooling Fans.  

E-Print Network (OSTI)

??Feedback active noise control (ANC) has been applied as a means of attenuating broadband noise from a small axial cooling fan. Such fans are used… (more)

Green, Matthew J 1978-

2006-01-01T23:59:59.000Z

191

The effect of fan and heat sink design on heat removal from microprocessor chips.  

E-Print Network (OSTI)

??Air flow and heat removal characteristics for fan/heat sink designs used to cool Pentium class processors were analyzed. Five designs were tested for fan speed,… (more)

Baltrip, Kedra G

2012-01-01T23:59:59.000Z

192

Exact solutions to combinatorial optimizations and the traveling baseball fan problem.  

E-Print Network (OSTI)

?? The traveling baseball fan problem is an extension of the classic traveling salesman problem, in which a sports fan wishes to travel to the… (more)

Terrell, Neal D.

2013-01-01T23:59:59.000Z

193

Il fenomeno dei fan nel mercato della musica. Analisi netnografica dei seguaci italiani di Bruce Springsteen.  

E-Print Network (OSTI)

??Lo studio ha ad oggetto la comunità dei fan italiani di Bruce Springsteen. Dopo aver analizzato la letteratura e descritto il fenomeno dei fan e… (more)

Gallo, Sara

2007-01-01T23:59:59.000Z

194

Costs and benefits of energy efficiency improvements in ceiling fans  

SciTech Connect

Ceiling fans contribute significantly to residential electricity consumption, especially in developing countries with warm climates. The paper provides analysis of costs and benefits of several options to improve the efficiency of ceiling fans to assess the global potential for electricity savings and green house gas (GHG) emission reductions. Ceiling fan efficiency can be cost-effectively improved by at least 50% using commercially available technology. If these efficiency improvements are implemented in all ceiling fans sold by 2020, 70 terawatt hours per year could be saved and 25 million metric tons of carbon dioxide equivalent (CO2-e) emissions per year could be avoided, globally. We assess how policies and programs such as standards, labels, and financial incentives can be used to accelerate the adoption of efficient ceiling fans in order to realize potential savings.

Shah, Nihar; Sathaye, Nakul; Phadke, Amol; Letschert, Virginie [Lawrence Berkeley National Lab., CA (United States). Environmental Energy Technology Division] [Lawrence Berkeley National Lab., CA (United States). Environmental Energy Technology Division

2013-10-15T23:59:59.000Z

195

Method for fabricating fan-fold shielded electrical leads  

DOE Patents (OSTI)

Fan-folded electrical leads made from copper cladded Kapton, for example, with the copper cladding on one side serving as a ground plane and the copper cladding on the other side being etched to form the leads. The Kapton is fan folded with the leads located at the bottom of the fan-folds. Electrical connections are made by partially opening the folds of the fan and soldering, for example, the connections directly to the ground plane and/or the lead. The fan folded arrangement produces a number of advantages, such as electrically shielding the leads from the environment, is totally non-magnetic, and has a very low thermal conductivity, while being easy to fabricate.

Rohatgi, Rajeev R. (Mountain View, CA); Cowan, Thomas E. (Livermore, CA)

1994-01-01T23:59:59.000Z

196

Method for fabricating fan-fold shielded electrical leads  

DOE Patents (OSTI)

Fan-folded electrical leads made from copper cladded Kapton, for example, with the copper cladding on one side serving as a ground plane and the copper cladding on the other side being etched to form the leads. The Kapton is fan folded with the leads located at the bottom of the fan-folds. Electrical connections are made by partially opening the folds of the fan and soldering, for example, the connections directly to the ground plane and/or the lead. The fan folded arrangement produces a number of advantages, such as electrically shielding the leads from the environment, is totally non-magnetic, and has a very low thermal conductivity, while being easy to fabricate. 3 figures.

Rohatgi, R.R.; Cowan, T.E.

1994-12-27T23:59:59.000Z

197

Review: The Dragon & The Elephant: Agricultural and Rural Reforms in China and India edited by Ashok Gulati and Shenggen Fan  

E-Print Network (OSTI)

Ashok Gulati and Shenggen Fan (Eds. ) Reviewed by VarinderIndia Gulati, Ashok and Fan, Shenggen (Eds. ). The Dragon &

Jain, Varinder

2008-01-01T23:59:59.000Z

198

Key Findings from the NBI PIER Project: Optimization of Airside Design  

NLE Websites -- All DOE Office Websites (Extended Search)

Key Findings from the NBI PIER Project: Optimization of Airside Design Key Findings from the NBI PIER Project: Optimization of Airside Design Speaker(s): Mark Hydeman Date: April 29, 2004 - 12:00pm Location: Bldg. 90 Seminar Host/Point of Contact: Philip Haves Mark Hydeman, PE, Principal from Taylor Engineering will present key results from the NBI PIER research on built-up VAV systems for which he was the Principal Investigator. These include the potential for supply pressure reset for energy savings and to prevent operation in surge; a new way of modeling fan performance; and an optimized approach for selecting and controlling VAV boxes. The project produced a design guide on air-side VAV systems that is available from the CEC website at http://www.energy.ca.gov/reports/2003-11-17_500-03-082_A-11.PDF a new model for the evaluation of fan system design and controls and a series of

199

The Fan Observatory Bench Optical Spectrograph (FOBOS)  

E-Print Network (OSTI)

The Fan Observatory Bench Optical Spectrograph (FOBOS) is intended for single-object optical spectroscopy at moderate resolution (R~1500-3000) using a fiber-fed, bench-mounted design to maintain stability. Whenever possible, the instrument uses off-the-shelf components to maintain a modest cost. FOBOS supports Galactic astronomy projects that require consistently well-measured (~5 km/sec) radial velocities for large numbers of broadly distributed and relatively bright (Vdesign was optimized for use in the range 470-670 nm. Test data indicate that the instrument is stable and capable of measuring radial velocities with precision better than 3 km/sec at a resolution of R~1500 with minimal calibration overhead.

Jeffrey D. Crane; Steven R. Majewski; Richard J. Patterson; Michael F. Skrutskie; Elena Y. Adams; Peter M. Frinchaboy

2005-02-23T23:59:59.000Z

200

Submitting Organization Hongyou Fan Sandia National Laboratories  

NLE Websites -- All DOE Office Websites (Extended Search)

 2007 R&D 100 Award Entry Form  Submitting Organization Hongyou Fan Sandia National Laboratories Advanced Materials Laboratory 1001 University Boulevard SE Albuquerque, NM 87106, USA 505-272-7128 (phone) 505-272-7336 (fax) hfan@sandia.gov AFFIRMATION: I affirm that all information submitted as a part of, or supplemental to, this entry is a fair and accurate represen- tation of this product. Submitter's signature_______________________________ Earl Stromberg Lockheed Martin Aeronautics Mail Zone 2893 PO Box 748 Fort Worth, TX 76101, USA 817-763-7376 (phone) 817-762-6911 (fax) Earl.W.Stromberg@lmco.com Self-Assembling Process for Fabricating Tailored Thin Films This simple, economical nanotechnology coating process enables the development of nanoparticle thin films

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


201

Performance of thermal distribution systems in large commercial buildings  

NLE Websites -- All DOE Office Websites (Extended Search)

Performance of thermal distribution systems in large commercial buildings Performance of thermal distribution systems in large commercial buildings Title Performance of thermal distribution systems in large commercial buildings Publication Type Journal Article LBNL Report Number LBNL-44331 Year of Publication 2002 Authors Xu, Tengfang T., François Rémi Carrié, Darryl J. Dickerhoff, William J. Fisk, Jennifer A. McWilliams, Duo Wang, and Mark P. Modera Journal Energy and Buildings Volume 34 Start Page Chapter Pagination 215-226 Abstract This paper presents major findings of a field study on the performance of five thermal distribution systems in four large commercial buildings. The five systems studied are typical single-duct or dual-duct constant air volume (CAV) systems and variable air volume (VAV) systems, each of which serves an office building or a retail building with floor area over 2,000 m2. The air leakage from ducts are reported in terms of effective leakage area (ELA) at 25 Pa reference pressure, the ASHRAE-defined duct leakage class, and air leakage ratios. The specific ELAs ranged from 0.7 to 12.9 cm2 per m2 of duct surface area, and from 0.1 to 7.7 cm2 per square meter of floor area served. The leakage classes ranged from 34 to 757 for the five systems and systems sections tested. The air leakage ratios are estimated to be up to one-third of the fan- supplied airflow in the constant-air-volume systems. The specific ELAs and leakage classes indicate that air leakage in large commercial duct systems varies significantly from system to system, and from system section to system section even within the same thermal distribution system. The duct systems measured are much leakier than the ductwork specified as "unsealed ducts" by ASHRAE. Energy losses from supply ducts by conduction (including convection and radiation) are found to be significant, on the scale similar to the losses induced by air leakage in the duct systems. The energy losses induced by leakage and conduction suggest that there are significant energy-savings potentials from duct-sealing and insulation practice in large commercial buildings

202

Particle trajectories and acceleration during 3D fan reconnection  

E-Print Network (OSTI)

Context. The primary energy release in solar flares is almost certainly due to magnetic reconnection, making this a strong candidate as a mechanism for particle acceleration. While particle acceleration in 2D geometries has been widely studied, investigations in 3D are a recent development. Two main classes of reconnection regimes at a 3D magnetic null point have been identified: fan and spine reconnection Aims. Here we investigate particle trajectories and acceleration during reconnection at a 3D null point, using a test particle numerical code, and compare the efficiency of the fan and spine regimes in generating an energetic particle population. Methods. We calculated the time evolution of the energy spectra. We discuss the geometry of particle escape from the two configurations and characterise the trapped and escaped populations. Results. We find that fan reconnection is less efficent than spine reconnection in providing seed particles to the region of strong electric field where acceleration is possible. The establishment of a steady-state spectrum requires approximately double the time in fan reconnection. The steady-state energy spectrum at intermediate energies (protons 1 keV to 0.1 MeV) is comparable in the fan and spine regimes. While in spine reconnection particle escape takes place in two symmetric jets along the spine, in fan reconnection no jets are produced and particles escape in the fan plane, in a ribbon-like structure.

S. Dalla; P. K. Browning

2008-11-07T23:59:59.000Z

203

Acceptance test procedure MICON software exhaust fan control modifications  

Science Conference Proceedings (OSTI)

This acceptance test verifies the MICON program changes for the new automatic transfer switch ATS-2 alarms, the Closed Loop Cooling isolator status, the CB-3 position alarm, and the alarms for the new emergency fan damper backup air compressor.

SILVAN, G.R.

1999-05-21T23:59:59.000Z

204

Searching optimal shapes for blades of a fan  

E-Print Network (OSTI)

A nonlinear differential equation about optimal shapes for blades of a fan. A boundary value differential problem from engineering, geometrical or physical bonds. A relation between linear profiles and constant speed along the side under flow.

Gianluca Argentini

2008-03-26T23:59:59.000Z

205

Sinewave parameter estimation using the fast fan-chirp transform  

E-Print Network (OSTI)

Sinewave analysis/synthesis has long been an important tool for audio analysis, modification and synthesis. The recently introduced fan-chirp Transform (FChT) [2,3] has been shown to improve the fidelity of sinewave parameter ...

Dunn, Robert B.

206

Developing a Standard Test Method for Characterizing Fan-filter...  

NLE Websites -- All DOE Office Websites (Extended Search)

Developing a Standard Test Method for Characterizing Fan-filter Units Used in Industries Speaker(s): Tim Xu Date: July 21, 2008 - 12:00pm Location: 90-3122 Seminar HostPoint of...

207

Variable Speed Fan Retrofits for Computer Room Air Conditioners  

NLE Websites -- All DOE Office Websites (Extended Search)

Variable-Speed Fan Retrofits for Computer-Room Air Conditioners Prepared for the U.S. Department of Energy Federal Energy Management Program Technology Case Study Bulletin By...

208

Use of VFDs on Asphalt Plant Induced Draft Fans  

E-Print Network (OSTI)

Studies of 10 asphalt plants in the Intermountain Region have identified average ID fan energy savings of 68% by controlling airflow using Variable Frequency Drives (VFDs) on the fan motors in place of damper control (inlet or outlet). Average paybacks were 3-5 years before utility incentives. In the 10 plants evaluated, the ID fans accounted for as much as 30% of the total plant electrical consumption. In the majority of these plants the outlet dampers were typically 50%-60% closed. Fan motors ranged from 200 Hp to 500 Hp. With approximately 3,600 existing asphalt plants in operation across the United States, a large opportunity for retrofits exists. Working with manufacturers and owners, a new standard can be established for installing VFDs on all plants.

Anderson, G. R.; Case, P. L.; Lowery, J.

2005-01-01T23:59:59.000Z

209

Crossover distributions at the edge of the rarefaction fan  

E-Print Network (OSTI)

We consider the weakly asymmetric limit of simple exclusion process with drift to the left, starting from step Bernoulli initial data with $\\rho_-fan. We study the fluctuations of the process observed along slopes in the fan, which are given by the Hopf--Cole solution of the Kardar-Parisi-Zhang (KPZ) equation, with appropriate initial data. For slopes strictly inside the fan, the initial data is a Dirac delta function and the one point distribution functions have been computed in [Comm. Pure Appl. Math. 64 (2011) 466-537] and [Nuclear Phys. B 834 (2010) 523-542]. At the edge of the rarefaction fan, the initial data is one-sided Brownian. We obtain a new family of crossover distributions giving the exact one-point distributions of this process, which converge, as $T\

Ivan Corwin; Jeremy Quastel

2010-06-07T23:59:59.000Z

210

A Tip Driven Fan Based on SERAPHIM Technology  

SciTech Connect

SERAPHIM technology appears capable of efficiently driving a tip driven fan. If the motor is powered using an inverter and resonant circuit, the size and weight could be considerably below that of a comparable rotary electric motor.

MARDER, BARRY M.

2002-01-01T23:59:59.000Z

211

Property:Building/SPElectrtyUsePercCirculationFans | Open Energy  

Open Energy Info (EERE)

SPElectrtyUsePercCirculationFans SPElectrtyUsePercCirculationFans Jump to: navigation, search This is a property of type String. Circulation fans Pages using the property "Building/SPElectrtyUsePercCirculationFans" Showing 25 pages using this property. (previous 25) (next 25) S Sweden Building 05K0001 + 18.6715328229 + Sweden Building 05K0002 + 0.0 + Sweden Building 05K0003 + 3.84924044288 + Sweden Building 05K0004 + 13.5679722118 + Sweden Building 05K0005 + 10.115947775 + Sweden Building 05K0006 + 10.4348038368 + Sweden Building 05K0007 + 3.09034005771 + Sweden Building 05K0008 + 1.5024342653 + Sweden Building 05K0009 + 13.4365662073 + Sweden Building 05K0010 + 0.0 + Sweden Building 05K0011 + 2.75323793817 + Sweden Building 05K0012 + 15.8993705073 + Sweden Building 05K0013 + 1.11354848212 +

212

Property:Building/SPElectrtyUsePercFans | Open Energy Information  

Open Energy Info (EERE)

SPElectrtyUsePercFans SPElectrtyUsePercFans Jump to: navigation, search This is a property of type String. Fans Pages using the property "Building/SPElectrtyUsePercFans" Showing 25 pages using this property. (previous 25) (next 25) S Sweden Building 05K0001 + 7.29539104961 + Sweden Building 05K0002 + 16.7673965927 + Sweden Building 05K0003 + 27.9131959869 + Sweden Building 05K0004 + 12.2479817873 + Sweden Building 05K0005 + 29.1925346224 + Sweden Building 05K0006 + 15.8653423601 + Sweden Building 05K0007 + 12.809449974 + Sweden Building 05K0008 + 22.2979541594 + Sweden Building 05K0009 + 22.7088540206 + Sweden Building 05K0010 + 13.3738132017 + Sweden Building 05K0011 + 25.1040933765 + Sweden Building 05K0012 + 22.6542018423 + Sweden Building 05K0013 + 24.3166483485 +

213

Record of Communication Concerning Ceiling Fan and Ceiling Fan Light Kit Framework Document—Docket No. EERE-2012-BT-STD-0045  

Energy.gov (U.S. Department of Energy (DOE))

This memo provides an overview of communications made to DOE staff on the subject of possible changes to standards and test procedures for ceiling fans and ceiling fan light kits.

214

Ceiling Fan and Ceiling Fan Light Kit use in the U.S. Results of a Survey on Amazon Mechanical Turk  

E-Print Network (OSTI)

air conditioning .31   3.7   Impact of ceiling fans on air conditioningowners increased the air conditioning thermostat temperature

Kantner, Colleen L.S.

2013-01-01T23:59:59.000Z

215

Alternate Air Delivery Systems for Hot and Humid Climates  

E-Print Network (OSTI)

Carter & Burgess first began using triple deck multi-zone units, in place of traditional VAV systems, on the Texas State Capitol restoration. Since the completion of that project design in early 1991, our firm has now used triple deck multi-zone units in the Harris County Criminal Courts Building in Houston, one of the most hot and humid climates in the United States, as well as in several other facilities. This paper will discuss the adoption of ASHRAE 62, its effects on VAV systems, and how triple deck multi-zone units offer an alternative system to cooling in hot and humid climates. We recommend all design firms add triple deck multizone units to their repertoire of design solutions.

Wallace, M.

1996-01-01T23:59:59.000Z

216

Architectural characteristics of fine-grained submarine fans: A model applicable to the Gulf of Mexico  

Science Conference Proceedings (OSTI)

Submarine fan deposits in the Gulf of Mexico, modern and ancient, fall in the category of fine-grained, low overall sand/shale ratio basin-floor fans. Models published over the years that have been applied to both exploration and production are based on sand-rich fans, most of which were deposited in active margin settings. These models should not be used for the Gulf of Mexico or any other deep water system with similar basinal settings. Observations from the excellent outcrops of the Permian Tanqua Karoo in southwestern South Africa, together with information from the modern Mississippi Fan, and the Jackfork turbidites in Arkansas, enable the construction of a model that addresses the architecture of both the macro and meso-scale depositional features of fine-grained turbidite systems. At the entrance to the basin floor the conduit, carved out across the slope, may start to widen. Most of the density flows moving through do not necessarily occupy the conduit`s entire width. The result is a complex of laterally and vertically stacked channel fills and associated levee-overbank deposits with a good degree of connectivity. The channel fills are mostly massive, whereas the levee deposits are low-contrast, low-resistivity thin-bedded sandstones and shales with high permeability. Such sandstones can be potentially very productive. The channels gradually become smaller and as their influence on directing the heads of turbidity currents decreases, oblong sheet sands are deposited, each having a very large width to thickness ratio and a high sand/shale ratio. The vertical stacking patterns within these sheet sands commonly display lateral offset of individual beds or groups of beds, and therefore form a distinct reservoir type with varying internal fluid-flow characteristics.

Bouma, A.H.; Coleman, J.H. [Louisiana State Univ., Baton Rouge, LA (United States); DeV Wickens, H. [and others

1995-10-01T23:59:59.000Z

217

Heavy Vehicle Systems Optimization Program - 2005 Annual Progress...  

NLE Websites -- All DOE Office Websites (Extended Search)

... 69 A. Cooling Fan and System Performance and Efficiency Improvements Caterpillar, Inc., R.L. Dupree, et...

218

Measured Natural Cooling Enhancement of a While House Fan  

E-Print Network (OSTI)

An experimental study was carried out in the summer of 1991 to investigate the natural cooling potential of use of a whole house fan in Central Florida's hot and humid climate. The residential building, in Cocoa Beach, FL, is typical of much of the existing housing stock in Florida: a concrete block structure with R-11 ceiling insulation. The building was ventilated with all windows open during the three month summer test period (June- August). Air temperatures and relative humidity inside the home interior along with exterior meteorological conditions (insolation, wind speed, air temperature, relative humidity) were scanned every five seconds with integrated averages recorded on a multi-channel data logger every 15- minutes. The house was naturally ventilated during the first half of summer. After a significant period of pre-retrofit summer data had been collected characterizing the building's thermal response, a 24" whole house fan was installed. The house was then force ventilated during evening hours for the remainder of the summer to establish potential of whole-house fans to improve interior comfort conditions. The electrical consumption of the fan was measured at both available fan speeds. Measurements revealed that the building interior was 3 - 6°F cooler during the evening hours after the whole house fan was operated. However, data also showed that nighttime humidity levels rose: relative humidity increased from 74% to 83% during the nighttime period where fan-powered ventilation was used. Using the data results, an analysis was performed using Orlando, Florida TMY data to see how limits to whole house ventilation based on humidity and temperature conditions would affect the potential of such a cooling strategy.

Parker, D. S.

1994-01-01T23:59:59.000Z

219

Photo of the Week: Fan-tastic | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fan-tastic Fan-tastic Photo of the Week: Fan-tastic August 17, 2012 - 10:30am Addthis In Jonesboro, Arkansas, a Nordex USA employee stands between utility-scale components that will eventually make up a completed wind turbine. Under the Recovery Act, Nordex USA received a tax credit to assist in the creation of the Jonesboro manufacturing facility, which opened in October 2010. | Photo courtesy of Nordex USA. In Jonesboro, Arkansas, a Nordex USA employee stands between utility-scale components that will eventually make up a completed wind turbine. Under the Recovery Act, Nordex USA received a tax credit to assist in the creation of the Jonesboro manufacturing facility, which opened in October 2010. | Photo courtesy of Nordex USA. Sarah Gerrity Sarah Gerrity Multimedia Editor, Office of Public Affairs

220

Cooling Tower Energy Conservation Through Hydraulic Fan Drives  

E-Print Network (OSTI)

Many companies offer gearboxes, shafts, and couplings for cooling tower fan drives, with little or no innovation. These companies have traditionally been purchased with an emphasis on cost and not "Return on Investment!" In the past, when energy conservation or "Return on Investment" was emphasized, the only alternative was to add an expensive frequency inverter for variable speed control. This meant expensive rewiring, placing additional controls in an already crowded control room, or constructing a special building for them. However, with H.E.M.'s patented Hydraulic Fan Drive, one receives variable speed control and more efficiency for approximately the price of a mechanical drive. The new, more efficient Hydraulic Drive allows for a variable speed control and the ability to sense water temperature to control fan speed.

Dickerson, J.

1991-06-01T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


221

Field Study of Exhaust Fans for Mitigating Indoor Air Quality Problems: Final Report to Bonneville Power Administration  

E-Print Network (OSTI)

operation at low fan speeds (LBL design) and operation --continuously design in the heat exchangers exhaust fans onDesign The basic objective of this project, to study the effects of exhaust fan

Grimsrud, David T.

2009-01-01T23:59:59.000Z

222

Blue fan palm distribution and seed removal patterns in three desert oases of northern Baja California, Mexico  

E-Print Network (OSTI)

DOI 10.1007/s11258-009-9682-4 Blue fan palm distribution anddistribution patterns of the blue fan palm, Brahea armata,i) the levels of blue fan palm seed removal by vertebrates

Wehncke, Elisabet V.; López-Medellín, Xavier; Ezcurra, Exequiel

2010-01-01T23:59:59.000Z

223

Key Findings from the NBI PIER Project: Optimization of Airside...  

NLE Websites -- All DOE Office Websites (Extended Search)

reset for energy savings and to prevent operation in surge; a new way of modeling fan performance; and an optimized approach for selecting and controlling VAV boxes. The...

224

Income Tax Deduction for Solar-Powered Roof Vents or Fans (Indiana...  

Open Energy Info (EERE)

1232012 References DSIRE1 Summary Indiana allows taxpayers to take a deduction on solar-powered roof fans (or vent, also sometimes called an attic fan) installed in a home...

225

Income Tax Deduction for Solar-Powered Roof Vents or Fans  

Energy.gov (U.S. Department of Energy (DOE))

Indiana allows taxpayers to take a deduction on solar-powered roof fans (or vent, also sometimes called an attic fan) installed in a home that the taxpayer owns or leases. The deduction is for 50%...

226

Laugh out loud in real life : women's humor and fan identity  

E-Print Network (OSTI)

The emerging field of fan studies has, until recently, been defined only by the research that has taken place within it. Almost universally, this research focuses on self-identified fans. However, scholars are beginning ...

Klink, Madeline LeNore

2010-01-01T23:59:59.000Z

227

Experimental investigation of a six inch diameter, four inch span cross-flow fan .  

E-Print Network (OSTI)

??Investigations into the use of a cross-flow fan as a potential source of propulsion and lift have arisen due to the cross-flow fan's geometry, light… (more)

Ulvin, Jessica M.

2008-01-01T23:59:59.000Z

228

A satisfiability algorithm for constant depth boolean circuits with unbounded fan-in gates  

E-Print Network (OSTI)

Boolean Circuits with Unbounded Fan-In Gates A dissertationAC 0 by allowing unbounded fan-in M OD m 1 , . . . , M OD mSince each gate in ? has fan-in at most k and ? has depth D

Matthews, William Grant

2011-01-01T23:59:59.000Z

229

Fan Aerodynamic Performance Guarantees: Do Your Policies, Procedures and Penalties Provide Adequate Certainty?  

E-Print Network (OSTI)

With few exceptions, fan vendors do not provide a written guarantee regarding aerodynamic performance. Some fan vendors even go so far as to state in their terms and conditions of sale that fan performance is not guaranteed unless it is specifically reque

Kaufman, S. G.; Martin, V.; Falk, M. A.

2004-01-01T23:59:59.000Z

230

Acceptance test report MICON software exhaust fan control modifications  

Science Conference Proceedings (OSTI)

This report documents the results the acceptance test HNF-4108 which verifies the MICON program changes for the new automatic transfer switch ATS-2 alarms, the Closed Loop Cooling isolator status, the CB-3 position alarm, the alarms for the new emergency fan damper backup air compressor, and the generator sequencer logic.

SILVAN, G.R.

1999-05-20T23:59:59.000Z

231

The Forming of AISI 409 sheets for fan blade manufacturing  

SciTech Connect

The necessity of adapting the standardized fan models to conditions of higher temperature has emerged due to the growth of concern referring to the consequences of the gas expelling after the Mont Blanc tunnel accident in Italy and France, where even though, with 100 fans in operation, 41 people died. The objective of this work is to present an alternative to the market standard fans considering a new technology in constructing blades. This new technology introduces the use of the stainless steel AISI 409 due to its good to temperatures of gas exhaust from tunnels in fire situation. The innovation is centered in the process of a deep drawing of metallic sheets in order to keep the ideal aerodynamic superficies for the fan ideal performance. Through the impression of circles on the sheet plane it is shown, experimentally, that, during the pressing process, the more deformed regions on the sheet plane of the blade can not reach the deformation limits of the utilized sheet material.

Foroni, F. D.; Menezes, M. A.; Moreira Filho, L. A. [ITA - Aeronautic Technological Institute, IEM, Praca Mal. Eduardo Gomes, 50 - Vila das Acacias - S. J. Campos, Brasil - CEP 1228-900 (Brazil)

2007-04-07T23:59:59.000Z

232

Sand-rich submarine fans, Mio-Pliocene of Santa Monica Basin, offshore California: Untapped exploration targets  

Science Conference Proceedings (OSTI)

Santa Monica Basin lies directly west of Los Angeles Basin, one of the world's most prolific oil provinces. Published literature suggests that Santa Monica Basin was starved of coarse clastics during the late Miocene through Pliocene. However, seismic sequence stratigraphy indicates that deposition of sand-rich fans alternated with mixed-load systems throughout the Delmontian and Repettian stages. Seismic sequences and facies are calibrated to seismic and well data from Beta Oil Field, in San Pedro Basin to the south. Eustasy evidently played a dominant role in controlling sedimentation. Variations in tan lithology, thickness, and basinward extent correspond to worldwide changes in sea level. Regional erosion surfaces apparently signify drops in sea level. Overlying thick seismic packages display hummocky to chaotic seismic facies separated by high- to low-amplitude continuous reflections. These configurations are interpreted as inner- to mid-fan channels separated by overbank deposits in sand-rich lowstand fans. High-amplitude basinwide reflections bound the tops of the sand-rich intervals, and likely represent condensed sections formed during sea-level rises. Thin seismic intervals above the condensed sections display downlap, and are interpreted as interbedded sandstones and shales of prograding highstand fans. Sediment input to Santa Monica Basin, based on seismic-facies and isochron patterns, was predominantly from the (present-day) north, with subordinate input from the east. High-amplitude eustatic variations dominated deposition and sequence development even in this tectonically active basin Previously unidentified sand-rich fans are present, and have not been drilled.

May, J.A.; McMillen, K.J.

1996-01-01T23:59:59.000Z

233

Correlation efficiency as a tool to establish depositional subenvironments in submarine fans  

Science Conference Proceedings (OSTI)

Depositional units in submarine fan systems commonly are too large to be entirely or sufficiently exposed in an outcrop to properly identify. Channel fills can be massive, bedded, or any combination thereof. The layering can be horizontal or inclined. Typical bedded series can be thick or thin bedded, or a combination with or without a certain cyclicity. Occurrence of sedimentary structures is not yet a decisive interpretation characteristic. At the present, the Lower Permian Skoorsteenberg Formation of the Southwest Karoo in South Africa may be the best example of long, nontilted, outcrops where entire subenvironments can be observed. Using that knowledge, outcrop information from several areas, and ideas from the literature, we attempted correlations in two spillways in the Jackfork Group in Arkansas. A layer-by-layer correlation failed, even after small layer package could be established using an occasional thick shale break, a major slump, or a very thick massive sandstone layer for dividing both sides of the spillway. A [open quotes]semi-logarithmic[close quotes] display of measured thickness provides patterns of variations in layer thickness that normally are sufficiently typical to use as a correlation tool between both sides. This is not a foolproof system and one should consider additional parameters, such as location within the entire fan system. However, the degree of correlatibility helps identify or suggest depositional environments.

Bouma, A.H.; Cook, T.W. (Louisiana State Univ., Baton Rouge, LA (United States)); Devries, M.B. (Exxon Exploration Company, Houston, TX (United States))

1993-09-01T23:59:59.000Z

234

GOTHIC Analysis of Containment Fan Cooler Unit (CFCU) Cooling Water Response Following a LOCA with Loss of Offsite Power  

Science Conference Proceedings (OSTI)

This report presents a simplified method to predict the thermal hydraulic status of a containment fan cooling system under a loss of coolant accident (LOCA) with loss of off-site power (LOOP). GOTHIC 5.0c, a general purpose thermal hydraulics computer program for analysis of nuclear power plants and confinements buildings, has been used for the calculation, and the results have been compared with those from RETRAN.

1997-12-23T23:59:59.000Z

235

Introduction of a Cooling Fan Efficiency Index  

E-Print Network (OSTI)

Thermal Biology 31:53–9. ASHRAE. 2004. ANSI/ASHRAE Standardand field measurements. ASHRAE Transactions 99(2):733–49.system in office building. ASHRAE Transactions 104(1):1153–

Schiavon, Stefano; Melikov, Arsen

2009-01-01T23:59:59.000Z

236

Variable Speed Fan Retrofits for Computer Room Air Conditioners  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Variable-Speed Fan Variable-Speed Fan Retrofits for Computer-Room Air Conditioners Prepared for the U.S. Department of Energy Federal Energy Management Program Technology Case Study Bulletin By Lawrence Berkeley National Laboratory Steve Greenberg September 2013 2 Contacts Steve Greenberg Lawrence Berkeley National Laboratory One Cyclotron Road, 90R3111 Berkeley, California 94720 (510) 486-6971 segreenberg@lbl.gov For more information on FEMP, please contact: Will Lintner, P.E., CEM Federal Energy Management Program U.S. Department of Energy 1000 Independence Ave. S.W. Washington, D. C. 20585-0121 (202) 586-3120 william.lintner@ee.doe.gov 3 Acknowledgements EPRI: Dennis Symanski, Brian Fortenbery Synapsense: Garret Smith, Patricia Nealon Vigilent: Corinne Vita

237

Generator Fan/Blower Design, Inspection, and Maintenance  

Science Conference Proceedings (OSTI)

Turbo-generator rotor cooling fans and blowers are highly stressed components of a generator rotor. As such, their failures can result in expensive damages and extended outages. This best practices document provides guidelines that help plant managers understand potential failure mechanisms and their root causes, anticipate issues before failures occur, and prepare inspection and contingency plans.The guidelines are applicable to both nuclear and fossil turbo-generator rotors. Both axial ...

2012-12-13T23:59:59.000Z

238

Turning on the Fan and Turning off the A/C | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Turning on the Fan and Turning off the A/C Turning on the Fan and Turning off the A/C Turning on the Fan and Turning off the A/C September 20, 2010 - 3:00pm Addthis As part of some recent money- and energy-savings improvements I've been making to my home, a couple of weeks ago I installed a ceiling fan in my main living room. Chris Stewart Senior Communicator at DOE's National Renewable Energy Laboratory As part of some recent money- and energy-savings improvements I've been making to my home, a couple of weeks ago I installed a ceiling fan in my main living room. Part of my research led me to understand how ceiling fans are considered the most effective fans compared among table fans, floor fans, and fans mounted to poles or walls because they effectively circulate the air in a room to create a draft throughout the room.

239

Turning on the Fan and Turning off the A/C | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Turning on the Fan and Turning off the A/C Turning on the Fan and Turning off the A/C Turning on the Fan and Turning off the A/C September 20, 2010 - 3:00pm Addthis As part of some recent money- and energy-savings improvements I've been making to my home, a couple of weeks ago I installed a ceiling fan in my main living room. Chris Stewart Senior Communicator at DOE's National Renewable Energy Laboratory As part of some recent money- and energy-savings improvements I've been making to my home, a couple of weeks ago I installed a ceiling fan in my main living room. Part of my research led me to understand how ceiling fans are considered the most effective fans compared among table fans, floor fans, and fans mounted to poles or walls because they effectively circulate the air in a room to create a draft throughout the room.

240

Improved recovery from Gulf of Mexico reservoirs. Volume I (of 4): Task 1, conduct research on mud-rich submarine fans. Final report, February 14, 1995--October 13, 1996  

Science Conference Proceedings (OSTI)

The objective for this portion of the research involved conducting field studies and laboratory investigations to develop and refine models for mud-rich submarine fan architectures used by seismic analysis and reservoir engineers. These research aspects have been presented in two papers as follows: (1) Bouma, A.H., {open_quotes}Review of Fine-Grained Submarine Fans and Turbidite Systems{close_quotes}; (2) Kirkova, J.T. and Lorenzo, J.M., {open_quotes}Synthetic Seismic Modeling of Measured Submarine Fans Sections, Case Study of the Tanqua Complex, Karoo, South Africa{close_quotes} The {open_quotes}Review of Fine-Grained Submarine Fans and Turbidite Systems{close_quotes} by Arnold Bouma discusses research targeted toward stimulating an increase in oil and gas recovery by developing new and improved geological understanding. The {open_quotes}Synthetic Seismic Modeling of Measured Submarine Fan Sections, Case Study of the Tanqua Complex, Karoo, South Africa{close_quotes} by J.T. Kirkova and J.M. Lorenso discusses the limitations of verticle resolution and how this affects the interpretation and characterization of submarine fan complexes.

Kimbrell, W.C.; Bassiouni, Z.A.; Bourgoyne, A.T.

1997-01-13T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


241

Savings in electric cooling energy by the use of a whole-house fan. Final report  

Science Conference Proceedings (OSTI)

Hour-by-hour cooling performances of a typical ranch house, with and without the use of a whole-house fan, were compared for the climate conditions throughout the contiguous United States. The comparative analyses were made by the use of NBSWHF, a modified version of NBSLD, to simulate the complex thermal coupling of whole-house-fan ventilated attic space. The calculations were performed for two operational modes: a cyclic fan mode and a stepwise continuous mode.

Kusuda, T.; Bean, J.W.

1981-05-01T23:59:59.000Z

242

How Has a Ceiling Fan Affected the Way You Heat and Cool Your Home? |  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Has a Ceiling Fan Affected the Way You Heat and Cool Your Home? Has a Ceiling Fan Affected the Way You Heat and Cool Your Home? How Has a Ceiling Fan Affected the Way You Heat and Cool Your Home? September 23, 2010 - 7:30am Addthis On Monday, Chris told you about his new ceiling fan and how it's changed the way he cools his home. In warm weather, ceiling fans cool people (not rooms) by producing a wind-chill effect-which is why you should turn off fans when you leave the room. A ceiling fan allows you to raise the thermostat setting about 4°F with no reduction in comfort. Ceiling fans don't just cool in the summer; you can also reverse the direction in the winter to provide an updraft and force warm air down into the room. How has a ceiling fan affected the way you heat and cool your home? Each Thursday, you have the chance to share your thoughts on a question

243

How Has a Ceiling Fan Affected the Way You Heat and Cool Your Home? |  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Has a Ceiling Fan Affected the Way You Heat and Cool Your Home? Has a Ceiling Fan Affected the Way You Heat and Cool Your Home? How Has a Ceiling Fan Affected the Way You Heat and Cool Your Home? September 23, 2010 - 7:30am Addthis On Monday, Chris told you about his new ceiling fan and how it's changed the way he cools his home. In warm weather, ceiling fans cool people (not rooms) by producing a wind-chill effect-which is why you should turn off fans when you leave the room. A ceiling fan allows you to raise the thermostat setting about 4°F with no reduction in comfort. Ceiling fans don't just cool in the summer; you can also reverse the direction in the winter to provide an updraft and force warm air down into the room. How has a ceiling fan affected the way you heat and cool your home? Each Thursday, you have the chance to share your thoughts on a question

244

NIST Test Fans the Flames for High-Rise Fire Safety  

Science Conference Proceedings (OSTI)

... Once the fires were under way, a variety of ventilation tests were conducted. For example, in one test, a large fan was placed at the front door to ...

2012-12-17T23:59:59.000Z

245

Fallout fans: Negotiations over text integrity in the age of the active audience.  

E-Print Network (OSTI)

??This study investigated how fans and producers of media texts negotiate text integrity, which is defined as an ideal about the validity, wholeness, and truth… (more)

Milner, Ryan M.

2008-01-01T23:59:59.000Z

246

DISCRETE-FREQUENCY AND BROADBAND NOISE RADIATION FROM DIESEL ENGINE COOLING FANS.  

E-Print Network (OSTI)

??This effort focuses on measuring and predicting the discrete-frequency and broadband noise radiated by diesel engine cooling fans. Unsteady forces developed by the interaction of… (more)

Kim, Geon-Seok

2007-01-01T23:59:59.000Z

247

A Real Reflection of How I Write: Young Adult Female Authors Seizing Agency Through Fan Fiction.  

E-Print Network (OSTI)

??This research project examines ""fan fiction"" (stories based upon existing texts such as movies, books, and video games) written by a young adult female and… (more)

Coleman, Susanna

2008-01-01T23:59:59.000Z

248

Failure of a Fan Hub Blade Made of an A713 Al-Zn Alloy  

Science Conference Proceedings (OSTI)

About this Abstract. Meeting, Materials Science & Technology 2012. Symposium, Failure Analysis and Prevention. Presentation Title, Failure of a Fan Hub Blade ...

249

Topography based fan control for heavy trucks; Topografibaserad kylfläktstyrning för tunga fordon.  

E-Print Network (OSTI)

?? This thesis is a study of how cooling fan control can be improved by using road topography information. Two such controllers are presented, one… (more)

Lerede, Niclas

2009-01-01T23:59:59.000Z

250

Error Sensor Placement for Active Control of an Axial Cooling Fan.  

E-Print Network (OSTI)

??Recent experimental achievements in active noise control (ANC) for cooling fans have used near-field error sensors whose locations are determined according to a theoretical condition… (more)

Shafer, Benjamin M 1979-

2007-01-01T23:59:59.000Z

251

FLIGHT CONTROL DESIGN OF TANDEM DUCTED FAN AIRCRAFT USING REDUNDANT CONTROL EFFECTORS.  

E-Print Network (OSTI)

??Controllability and stability of ducted fan air vehicles is a challenging problem due to their complex nonlinear aerodynamics and dynamic behavior. At the same time,… (more)

Ozdemir, Gurbuz

2010-01-01T23:59:59.000Z

252

Investigation of performance improvements including application of inlet guide vanes to a cross-flow fan .  

E-Print Network (OSTI)

??The inherent characteristics of a cross-flow fan allowing for easy thrust vectoring as well as potential airfoil boundary layer control make it an attractive propulsive… (more)

Cordero, Samuel F.

2009-01-01T23:59:59.000Z

253

Perimeter fan performance in forced draught air-cooled steam condensers.  

E-Print Network (OSTI)

??ENGLISH ABSTRACT: Axial flow fan arrays form part of air-cooled steam condensers in direct drycooled power plants. This dissertation investigates the performance of axial flow… (more)

Van der Spuy, Sybrand Johannes

2011-01-01T23:59:59.000Z

254

Measuring Advances in HVAC Distribution System Design  

E-Print Network (OSTI)

of this "thermal mixing", the heating and cooling loadsyear) Cooling Plant Heating Plant Fans Total Thermal Tobllthermal distribution system includes the components that carry the heating and cooling

Franconi, E.

2011-01-01T23:59:59.000Z

255

Vehicle Cooling Systems - Energy Innovation Portal  

Hydrogen and Fuel Cell; Hydropower, Wave and ... The cabin cooling system includes at least one fan to draw the hot air into the cooling duct at a ...

256

Arbitrary surface flank milling of fan, compressor, and impeller blades  

SciTech Connect

It is generally conceived that a blade surface is flank millable if it can be closely approximated by a ruled surface; otherwise the slow machining process of point milling has to be employed. However, the authors have now demonstrated that the ruled surface criterion for flank milling is neither necessary nor sufficient. Furthermore, many complex arbitrary surfaces typical of the blades in fans, axial compressors, and centrifugal impellers in aviation gas turbines are actually closely flank millable and can be rendered exactly flank millable with one or more passes per surface often without sacrificing, indeed usually with gain, in performance.

Wu, C.Y. [Pratt and Whitney Canada Incorporated, Longueuil, Quebec, (Canada). Design Engineering

1995-07-01T23:59:59.000Z

257

Inlet swirl distortion effects on the generation and propagation of fan rotor shock noise  

E-Print Network (OSTI)

A body-force-based fan model for the prediction of multiple-pure-tone noise generation is developed in this thesis. The model eliminates the need for a full-wheel, three-dimensional unsteady RANS simulation of the fan blade ...

Defoe, Jeff (Jeffrey James)

2011-01-01T23:59:59.000Z

258

Impact-resistant boron/aluminum composites for large fan blades  

SciTech Connect

Blade-like specimens were subjected to static ballistic impact testing to determine their relative FOD impact resistance levels. It was determined that a plus or minus 15 deg layup exhibited good impact resistance. The design of a large solid boron/aluminum fan blade was conducted based on the FOD test results. The CF6 fan blade was used as a baseline for these design studies. The solid boron/aluminum fan blade design was used to fabricate two blades. This effort enabled the assessment of the scale up of existing blade manufacturing details for the fabrication of a large B/Al fan blade. Existing CF6 fan blade tooling was modified for use in fabricating these blades.

Oller, T.L.; Salemme, C.T.; Bowden, J.H.; Doble, G.S.; Melnyk, P.

1977-12-01T23:59:59.000Z

259

Microsoft Word - Control_and_Fan_Improvements_in_CRAHs.doc  

NLE Websites -- All DOE Office Websites (Extended Search)

07E 07E Demonstration of Intelligent Control and Fan Improvements in Computer Room Air Handlers Henry Coles and Steve Greenberg, Lawrence Berkeley National Laboratory Corinne Vita, Vigilent Environmental Energy Technologies Division November 2012 DISCLAIMER This document was prepared as an account of work sponsored by the United States Government. While this document is believed to contain correct information, neither the United States Government nor any agency thereof, nor The Regents of the University of California, nor any of their employees, makes any warranty, express or implied, or assumes any legal responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe

260

Fan-shaped and toric textures of mesomorphic oxadiazoles  

E-Print Network (OSTI)

When a family of non symmetrical heterocycled compounds is investigated, a variety of mesophases can be observed with rather different features. Here we report the behaviour of seven different members among a family of such materials, that consists of mesomorphic oxadiazole compounds. In two of these compounds, the optical microscope investigation shows very interesting behaviours. In their smectic phases, fan-shaped and toric textures, sometimes with periodic instability, are observed. Moreover, the nematic phase displays a texture transition. Texture transitions have been previously observed only inside the nematic phase of some compounds belonging to the families of the oxybenzoic and cyclohexane acids. In these two oxadiazole compounds we can observe what we define as a "toric nematic phase", heating the samples from the smectic phase. The toric nematic texture disappears as the sample is further heated, changing into a smooth texture.

A. Sparavigna; A. Mello; B. Montrucchio

2007-04-11T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


261

Remediation strategies of shaft and common mode voltages in adjustable speed drive systems.  

E-Print Network (OSTI)

??AC motors are largely used in a wide range of modern systems, from household appliances to automated industry applications such as: ventilations systems, fans, pumps,… (more)

Adabi Firouzjaee, Jafar

2010-01-01T23:59:59.000Z

262

Upper Campanian and lower Maestrichtian depositional systems and gas production, southern Sacramento basin, California  

SciTech Connect

Upper Campanian and lower Maestrichtian strata of the southern Sacramento basin include four west- and southwest-prograding submarine-fan/slope/delta systems. The Winters, Lathrop, Tracy, and Blewett formations consist of submarine-fan and related slope/basin-plain deposits that were fed by various deltaic complexes of the Starkey Formation. Four major basinwide transgressive shale units (Sacramento Shale, Sawtooth Shale, Ragged Valley Shale, and H and T Shale) help intrasystem correlations. The Winters, Tracy, and Blewett fans are small, radial, coalescing sand-rich systems that contain the following principal facies: (1) sandstone-filled inner fan channel deposits, (2) mudstone-dominated inner fan interchannel deposits, (3) middle-fan amalgamated suprafan-type sandstone-rich channel deposits, and (4) mudstone-dominated outer fan deposits. The Lathrop fans are larger, elongate, mixed-sediment systems that contain basin-plain, outer fan lobe, middle fan-channel, levee, interchannel, and inner fan channel facies. The Sierran-derived fluvio-deltaic Starkey Formation can be divided into six sand-rich deltaic cycles that can be subdivided on the basis of log signaturres and spatial distribution into prodelta, delta-front, lower delta-plain, and upper delta-plain/fluvial facies. More than 50 gas fields produce from these systems. Stratigraphic traps include updip pinchouts of submarine canyon/gullies and inner fan channels into slope shale, especially in the many overlapping and coalescing sand-rich systems. Lateral pinchouts of outer fan lobes and middle-fan suprafan-type bodies are also productive. Structural traps generally characterize production from deltaic deposits because of the more continuous nature of these bodies.

Moore, D.W.; Nilsen, T.H. (Applied Earth Technology, Inc., Redwood City, CA (USA))

1990-05-01T23:59:59.000Z

263

Property:Building/SPBreakdownOfElctrcityUseKwhM2Fans | Open Energy  

Open Energy Info (EERE)

Fans Fans Jump to: navigation, search This is a property of type String. Fans Pages using the property "Building/SPBreakdownOfElctrcityUseKwhM2Fans" Showing 25 pages using this property. (previous 25) (next 25) S Sweden Building 05K0001 + 5.21311928139 + Sweden Building 05K0002 + 18.5995610535 + Sweden Building 05K0003 + 20.3514016294 + Sweden Building 05K0004 + 8.08671679198 + Sweden Building 05K0005 + 16.0166245259 + Sweden Building 05K0006 + 10.358795651 + Sweden Building 05K0007 + 8.3953561818 + Sweden Building 05K0008 + 9.28527472527 + Sweden Building 05K0009 + 12.8398873749 + Sweden Building 05K0010 + 20.0966982674 + Sweden Building 05K0011 + 6.90408963585 + Sweden Building 05K0012 + 8.60719192175 + Sweden Building 05K0013 + 16.7539365907 +

264

Property:Building/SPBreakdownOfElctrcityUseKwhM2CirculationFans | Open  

Open Energy Info (EERE)

CirculationFans CirculationFans Jump to: navigation, search This is a property of type String. Circulation fans Pages using the property "Building/SPBreakdownOfElctrcityUseKwhM2CirculationFans" Showing 25 pages using this property. (previous 25) (next 25) S Sweden Building 05K0001 + 13.3422495258 + Sweden Building 05K0002 + 0.0 + Sweden Building 05K0003 + 2.80646609789 + Sweden Building 05K0004 + 8.95823904901 + Sweden Building 05K0005 + 5.55016340076 + Sweden Building 05K0006 + 6.81308969891 + Sweden Building 05K0007 + 2.02541916787 + Sweden Building 05K0008 + 0.625641025641 + Sweden Building 05K0009 + 7.59721281624 + Sweden Building 05K0010 + 0.0 + Sweden Building 05K0011 + 0.757191316527 + Sweden Building 05K0012 + 6.04077487892 + Sweden Building 05K0013 + 0.767224182906 +

265

Application of Adjustable Speed Drives to Induced Draft Fans at NSP-SHERCO Power Plant  

Science Conference Proceedings (OSTI)

Induced draft (ID) fans on power boilers control the flow of flue gasses from the boiler to the atmosphere-and their smooth operation is essential to the efficient operation of any generating station. Adjustable speed drive (ASD) control of an electric motor ID fan can provide significant energy savings while increasing the accuracy and precision of boiler draft and fuel gas flow regulation. This study quantified the energy savings and identified other benefits of applying ASDs to four existing electric-...

1999-10-19T23:59:59.000Z

266

Generation of fan-states of radiation field in a cavity  

E-Print Network (OSTI)

A scheme of generating recently introduced fan-states | \\alpha, 2k>_F (\\alpha is complex, k=1,2,3,...) is proposed basing on a \\Lambda-type atom-cavity field interaction. We show that with suitable atomic preparations and measurements a passage of a sequence of N atoms through a cavity may transform an initial field coherent state | \\alpha> to a fan-state | \\alpha, 2k>_F with k=2^{N-2}.

Nguyen Ba An; Truong Minh Duc

2001-11-30T23:59:59.000Z

267

Applicability of fan spray nozzles to stripping insoluble gases from viscous liquids  

SciTech Connect

Fan spray nozzle stripping appears to be a practical technique for separating dilute volatile solutes from nonvolatile solvents. In particular this technique can be used to strip molecular tritium and tritium fluoride at extremely small concentration (in the parts per million range) from molten salts used as blanket materials in a fusion reactor. Under adjusted operating conditions of the fan spray as it leaves the nozzle, a high percentage of the theoretically maximum achievable stripping would take place from the expanding sheet of the fan spray as it leaves the nozzle and before it breaks up. Although the only available experimental data are for aqueous solutions, a new theoretical analysis of the fan spray sheet demonstrates the applicability of this technique to nonaqueous liquids. The equation derived from this analysis relates the theoretically achievable mass transfer efficiency to the properties of the liquid flowing through the fan spray nozzle and to the operating conditions of the nozzle. Any fluid with viscosity higher than or equal to that of water would be expected to follow this equation as long as a fan-shaped sheet is formed under the operating conditions of the nozzle.

Tseng, H.H.; Johnson, E.F.

1983-08-01T23:59:59.000Z

268

The noise power spectrum in CT with direct fan beam reconstruction  

Science Conference Proceedings (OSTI)

The noise power spectrum (NPS) is a useful metric for understanding the noise content in images. To examine some unique properties of the NPS of fan beam CT, the authors derived an analytical expression for the NPS of fan beam CT and validated it with computer simulations. The nonstationary noise behavior of fan beam CT was examined by analyzing local regions and the entire field-of-view (FOV). This was performed for cases with uniform as well as nonuniform noise across the detector cells and across views. The simulated NPS from the entire FOV and local regions showed good agreement with the analytically derived NPS. The analysis shows that whereas the NPS of a large FOV in parallel beam CT (using a ramp filter) is proportional to frequency, the NPS with direct fan beam FBP reconstruction shows a high frequency roll off. Even in small regions, the fan beam NPS can show a sharp transition (discontinuity) at high frequencies. These effects are due to the variable magnification and therefore are more pronounced as the fan angle increases. For cases with nonuniform noise, the NPS can show the directional dependence and additional effects.

Baek, Jongduk; Pelc, Norbert J. [Department of Radiology, Stanford University, Stanford, California 94305 (United States); Department of Radiology, Stanford University, Stanford, California 94305 (United States); Department of Electrical Engineering, Stanford University, Stanford, California 94305 (United States) and Department of Bioengineering, Stanford University, Stanford, California 94305 (United States)

2010-05-15T23:59:59.000Z

269

Channel complex architecture of fine-grained submarine fans at the base-of-slope  

Science Conference Proceedings (OSTI)

The fan-valley or upper fan channel connects the submarine canyon on the outer shelf-upper slope to the basin proper. It is an erosionally-formed channel that is a conduit for sediment transported to the basin. The valley may widen where it enters the base-of-slope area. Most of the density flows are much smaller than the initial flow and therefore will not occupy the entire width of the upper fan channel. Smaller individual channels will be constructed resulting in a massive fill comprised of amalgamated sandstones. Sand-rich levees and overbank deposits flank each channel. Channel switching may take place toward locations with a slightly steeper gradient. These switches most likely result from irregular flow successions and different flow sizes. Erosion between successive channels is common, removing part of the channel fill and levee-overbank deposits. This results in a disorderly distribution of low-permeability barriers creating local obstruction to connectivity. A study of the sedimentological architecture of the updip mid-fan channel complex was conducted on cliff sections of the Permian Tanqua Karoo subbasin in South Africa, and in Big Rock Quarry in North Little Rock, Arkansas. Seismic records of the base-of-slope of the Mississippi Fan show a widening pattern, and of the Bryant Canyon Fan Complex south of the Sigsbee Escarpment the channel complexity. Integration of seismic data in outcrop observations improves our understanding of the complexity of many good reservoir sands, typically overlain by slope shales.

Bouma, A.H. [Louisiana State Univ., Baton Rouge, LA (United States); Gwang, H. [Kunsan National Univ. (Korea, Democratic People`s Republic of); Van Antwerepen, O. [Univ. of Port Elizabeth (South Africa)] [and others

1995-10-01T23:59:59.000Z

270

Limit processes for TASEP with shocks and rarefaction fans  

E-Print Network (OSTI)

We consider the totally asymmetric simple exclusion process (TASEP) with two-sided Bernoulli initial condition, i.e., with left density rho_- and right density rho_+. We consider the associated height function, whose discrete gradient is given by the particle occurrences. Macroscopically one has a deterministic limit shape with a shock or a rarefaction fan depending on the values of rho_{+/-}. We characterize the large time scaling limit of the fluctuations as a function of the densities rho_{+/-} and of the different macroscopic regions. Moreover, using a slow decorrelation phenomena, the results are extended from fixed time to the whole space-time, except along the some directions (the characteristic solutions of the related Burgers equation) where the problem is still open. On the way to proving the results for TASEP, we obtain the limit processes for the fluctuations in a class of corner growth processes with external sources, of equivalently for the last passage time in a directed percolation model with two-sided boundary conditions. Additionally, we provide analogous results for eigenvalues of perturbed complex Wishart (sample covariance) matrices.

Ivan Corwin; Patrik L. Ferrari; Sandrine Péché

2010-02-18T23:59:59.000Z

271

Advanced Integrated Systems Technology Development  

E-Print Network (OSTI)

fan designs .of each of the four major fan designs Fans for local airof various fan, motor, inlet and outlet designs, and by

2013-01-01T23:59:59.000Z

272

Field Study of Exhaust Fans for Mitigating Indoor Air Quality Problems: Final Report to Bonneville Power Administration  

E-Print Network (OSTI)

Fans Air-to-Air Heat Exchangers. . . . . . . . . . . . . . .expected from heat exchangers Ventilation expected fromventilation supplied by heat exchanger and exhaust flow. .

Grimsrud, David T.

2009-01-01T23:59:59.000Z

273

LETTER REPORT INDEPENDENT VERIFICATION OF THE HIGH FLUX BEAM REACTOR DECOMMISSIONING PROJECT FAN HOUSE, BUILDING 704 BNL  

Science Conference Proceedings (OSTI)

5098-LR-01-0 -LETTER REPORT INDEPENDENT VERIFICATION OF THE HIGH FLUX BEAM REACTOR DECOMMISSIONING PROJECT FAN HOUSE, BUILDING 704 BROOKHAVEN NATIONAL LABORATORY

P.C. Weaver

2010-10-22T23:59:59.000Z

274

Caratterizzazione del rumore generato dal fan di motori aeronautici e Metodo inverso per la ricostruzione della sorgente.  

E-Print Network (OSTI)

??Il seguente lavoro tratta una procedura per la ricostruzione della sorgente acustica del fan di un motore turbofan per uso aeronautico mediante metodo inverso. Tale… (more)

BIANCHI, FRANCESCO

2009-01-01T23:59:59.000Z

275

Stay Cool for Less Money with a Ceiling Fan | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Stay Cool for Less Money with a Ceiling Fan Stay Cool for Less Money with a Ceiling Fan Stay Cool for Less Money with a Ceiling Fan May 12, 2009 - 5:00am Addthis Allison Casey Senior Communicator, NREL After a few late snowstorms here in Colorado, I am more than ready to turn off the heat and enjoy some warm spring weather. We haven't had any heat waves here yet, but many of you have already been trying to stay cool; our friends in Washington, D.C. were sweltering (by comparison) in 90+°F weather just a couple short weeks ago! Whether you're still anticipating snow or have broken out the sandals and tank tops, you may be starting to think about keeping your summer cooling costs down. One easy way to keep cool while saving money is using a ceiling fan. Did you know that a ceiling fan could allow you to raise the thermostat

276

Development of HVAC System Performance Criteria Using Factorial Design and DOE-2 Simulation  

E-Print Network (OSTI)

A new approach is described for the development of Heating, Ventilating, and Air-conditioning (HVAC) System Performance Criteria for the Texas Building Energy Design Standard. This approach integrates a design of experimental methodology and DOE-2 simulation to identify the effects of control parameters on HVAC system energy performance. Three new criteria - transport, plant, and system performance factors-are used as measures of system performance. The procedure has been applied to the development of criteria for a variable-air-volume (VAV) and a constant-air-volume (CAV) system in three Texas climates. The results show that the air distribution system pressure loss, cooling coil exit temperature set-pint, operation of an economizer, and use of dead band controls have significant effects on air transport energy use and total system performance. The selection of control strategies and set-points have a clear impact on energy use. There is also a great energy-saving potential of converting from a CAV to a VAV system.

Hou, D.; Jones, J. W.; Hunn, B. D.; Banks, J. A.

1996-01-01T23:59:59.000Z

277

Model Predictive Control of HVAC Systems: Implementation and Testing at the University of California, Merced  

E-Print Network (OSTI)

fan speed (rpm)      N fan ,0 :    design fan speed (P fan :    fan power (kW)    m cw ,0 :    design water mass 

Haves, Phillip

2010-01-01T23:59:59.000Z

278

A PDI for your HVAC System  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

8/3/2012 Technical Approach Develop a PDI for HVAC PDI focus is on Inspecting Installation - a $10 Chinese sweatshop t-shirt gets a QA/QC sticker, why not a $10k HVAC system? Develop & require diagnostics that confirm good installations: - Air flow, duct leakage, refrigerant charge, delivered temperatures, system pressures, filter requirements, fan power, noise - On board diagnostics (OBD) for flow, pressures, fan power, charge Make it a warranty requirement, code requirement, permit requirement, etc. Recommended Guidance Develop the PDI checklist and label (include target and system test results) - External Tests: duct leaks - Internal Tests: OBD for system pressures, air flow, charge, fan power - Labels: Certify tight equipment

279

Automated Aspect Recommendation through Clustering-Based Fan-in Analysis  

Science Conference Proceedings (OSTI)

Identifying code implementing a crosscutting concern (CCC) automatically can benefit the maintainability and evolvability of the application. Although many approaches have been proposed to identify potential aspects, a lot of manual work is typically ... Keywords: ranking metric, automated aspect recommendation, clustering-based fan-in analysis, crosscutting concern, refactorable aspects, aspect mining, method clusters, lexical based clustering

Danfeng Zhang; Yao Guo; Xiangqun Chen

2008-09-01T23:59:59.000Z

280

Experimental Modal Analysis on a Rotating Fan Using Tracking-CSLDV  

Science Conference Proceedings (OSTI)

Continuous Scan Laser Doppler Vibrometry (CSLDV) modifies the traditional mode of operation of a vibrometer by sweeping the laser measurement point continuously over the structure while measuring, enabling one to measure spatially detailed mode shapes quickly and minimizing the inconsistencies that can arise if the structure or test conditions change with time. When a periodic scan path is employed, one can decompose the measurement into the response that would have been measured at each point traversed by the laser and obtain the structure's mode shapes and natural frequencies using conventional modal analysis software. In this paper, continuous-scan vibrometry is performed on a rotating fan, using computer controlled mirrors to track the rotating fan blades while simultaneously sweeping the measurement point over the blades. This has the potential to circumvent the difficulty of attaching contact sensors such as strain gauges, which might modify the structure and invalidate the results. In this work, impact excitation was used to excite a 3-blade fan rotating at various speeds, and the blades were scanned with a cloverleaf pattern that captured the bending of all three blades simultaneously. Some specialized signal processing is helpful in minimizing the effect of rotation frequency harmonics in the measurements, and specific scan strategies are needed to avoid those frequencies, both of these issues are discussed in the paper. While noise in the laser vibrometer does pose some difficulty, the results show that several modes could be extracted and that the tracking-CSLDV results agree with measurements obtained from the parked fan.

Gasparoni, Andrea; Castellini, Paolo; Tomasini, Enrico P. [Dipartimento di Meccanica, Universita Politecnica delle Marche, Via Brecce Bianche, 60131 Ancona (Italy); Allen, Matthew S.; Yang Shifei; Sracic, Michael W. [Department of Engineering Physics, University of Wisconsin-Madison, 535 Engineering Research Building, 1500 Engineering Drive, Madison, WI 53706 (United States)

2010-05-28T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


281

Fan to parallel beam conversion in CAT by rubber sheet transformation  

SciTech Connect

A technique for converting fan-beam projections to parallel-beam projections for use in computed tomography is presented. The problem is approached by use of a rubber sheet transformation. Since the data is discretized, an interpolation step is necessary. For densely sampled data this approach appears satisfactory and a significant reduction in photon noise is observable in computer simulations.

Wecksung, G.W.; Kruger, R.P.; Morris, R.A.

1979-01-01T23:59:59.000Z

282

Variable Speed Fan Retrofits for Computer Room Air Conditioners  

Energy.gov (U.S. Department of Energy (DOE))

Case study describes various concepts for more cost-effective cooling solutions in data centers, while keeping in mind that the reliability of computing systems and their respective cooling systems is always a key criterion.

283

Microsoft Word - defense_in_depth_fanning.doc  

NLE Websites -- All DOE Office Websites (Extended Search)

Energy Engineering and Systems Analysis What is Defense in Depth? Defense in Depth is a safety philosophy that guides the design, construction, inspection, operation, and...

284

Room Temperature Control During Season Switchover with Single Duct Variable Air Volume System Without Reheat  

E-Print Network (OSTI)

The Langford “A” building houses the College of Architecture on TAMU campus. There are ten singleduct variable air volume (VAV) air-handling units (AHUs) without reheat serving the building. The local pneumatic thermostats modulate the dampers of VAV boxes to maintain room temperature at their setpoints. The thermostat action is switched from direct acting (DA) to reverse acting (RA) when the season changes from fall to winter and vice versa from winter to spring, based on the out side air temperature, when season changes. This results in various parts of the building ether too cold or too hot during the season change. This paper presents that the thermostat action will be switched according to cooling loads or discharge air temperature, instead of outside air temperature. For the interior zone, thermostat action does not need to be switched at all. The comfort is improved and savings is achieved by the new control scheme. Because some air-handling units (AHUs) serve both interior and exterior zones, this system never worked as intended. The system must be modified to have zone reheat and the AHUs discharge air temperature is set below dew point for humidity control.

Liu, C.; Deng, S.; Claridge, D. E.; Turner, W. D.; Bruner, H.

2003-01-01T23:59:59.000Z

285

Design of compartmental silencer for HVAC system  

Science Conference Proceedings (OSTI)

Air conditioning and ventilation system is the major noise sources in the commercial building. Noise will be propagated from fan and through the associated ductwork into working area. In order to reduce the noise transmitted

Y. H. Chan; Y. S. Choy; R. C. K. Leung

2012-01-01T23:59:59.000Z

286

Memorandum Memorializing Ex Parte Communication, DOE impending determination of coverage for commercial and industrial fans, blowers, and fume hoods.  

Energy.gov (U.S. Department of Energy (DOE))

The meeting was requested by AMCA International to introduce the association’s leadership, standards, and experience in developing fan standards to DOE; to learn more about the DOE process for...

287

Science on Saturday attracts science fans of all ages | Princeton Plasma  

NLE Websites -- All DOE Office Websites (Extended Search)

Science on Saturday attracts science fans of all ages Science on Saturday attracts science fans of all ages By Jeanne Jackson DeVoe January 28, 2013 Tweet Widget Facebook Like Google Plus One Joshua E. G. Peek, a Hubble Fellow at Columbia University's Department of Astronomy and son of PPPL physicist and former director Robert Goldston, discusses "Outer Space!" (Photo by Elle Starkman/PPPL Office of Communications) Joshua E. G. Peek, a Hubble Fellow at Columbia University's Department of Astronomy and son of PPPL physicist and former director Robert Goldston, discusses "Outer Space!" Gallery: High school senior Varuni Bewtra comes to the lectures to learn about possible careers in science. (Photo by Photo by Jeanne Jackson DeVoe/PPPL Office of Communications) High school senior Varuni Bewtra comes to the lectures to learn about

288

Simulation of the Post-Retrofit Thermal Energy Use for the Perry-Castaneda Library Building with the Use of Simplified System Models  

E-Print Network (OSTI)

Several state owned buildings with dual-duct constant volume (DDCV) systems are being retrofitted with energy efficient variable air volume (VAV) systems as part of Texas LoanSTAR Program. One method of determining the energy savings resulting from energy conserving retrofits relies on the use of a model for the daily whole building consumption, Epre, in the pre-retrofit configuration. Epre is typically a function of primary influencing parameters such as ambient temperature, humidity, building internal gains and others (Figure 1). Following the retrofit, the energy saved, E,av is determined using measured daily consumption, Emea3 as shown in Figure 1. This method is being used in the Texas LoanSTAR monitoring and analysis program for buildings that have adequate pre-retrofit monitored data. Unfortunately, in the Perry-Castaneda Library (PCL) building, the retrofits were completed before the monitoring instrumentation was installed. Therefore, no pre-retrofit monitored data are available for this building. Hence another method to estimate savings is needed. Such a method was developed and tested (Katipamula and Claridge 1991). This method was based on the use of the ASHRAE TC 4.7 simplified energy analysis procedure (SEAP). It involved developing one model each for the VAV (post-retrofit system) and the DDCV (pre-retrofit system) systems.

Katipamula, S.; Claridge, D. E.

1991-01-01T23:59:59.000Z

289

Simulation of the Post-Retrofit Thermal Energy Use for the University Teaching Center (UTC) Building with the Use of Simplified System Models  

E-Print Network (OSTI)

Several state owned buildings with dual-duct constant volume (DDCV) systems have been retrofitted with energy efficient variable air volume systems (VAV) as part of the Texas LoanSTAR Program. One method of determining the energy savings resulting from energy conserving retrofits relies on the use of a model for the daily whole building consumption, Epre, in the pre-retrofit configuration. Epre is typically a function of primary influencing parameters such as ambient temperature, humidity, building internal gains and others (Figure 1). Following the retrofit, the energy saved, Esav is determined using measured daily consumption, Emea3 as shown in Figure 1. This method is being used in the Texas LoanSTAR monitoring and analysis program for buildings that have adequate pre-retrofit monitored data (Kelly et al., 1992). Unfortunately, in the University Teaching Center (UTC) the retrofits were completed before the monitoring instrumentation was installed. Therefore, no pre-retrofit monitored data are available. Hence another method to estimate savings was needed. Such a method was developed and tested on a large engineering center (Katipamula and Claridge 1991). This method was based on the use of the ASHRAE TC 4.7 simplified energy analysis procedure (SEAP). It involved developing one model each for the VAV (post-retrofit system) and the DDCV (pre-retrofit system) systems.

Katipamula, S.; Claridge, D. E.

1991-01-01T23:59:59.000Z

290

Standard practice for examination of fiberglass reinforced plastic fan blades using acoustic emission  

E-Print Network (OSTI)

1.1 This practice provides guidelines for acoustic emission (AE) examinations of fiberglass reinforced plastic (FRP) fan blades of the type used in industrial cooling towers and heat exchangers. 1.2 This practice uses simulated service loading to determine structural integrity. 1.3 This practice will detect sources of acoustic emission in areas of sensor coverage that are stressed during the course of the examination. 1.4 This practice applies to examinations of new and in-service fan blades. 1.5 This practice is limited to fan blades of FRP construction, with length (hub centerline to tip) of less than 3 m [10 ft], and with fiberglass content greater than 15 % by weight. 1.6 AE measurements are used to detect emission sources. Other nondestructive examination (NDE) methods may be used to evaluate the significance of AE sources. Procedures for other NDE methods are beyond the scope of this practice. 1.7 Units—The values stated in either SI units or inch-pound units are to be regarded separately as sta...

American Society for Testing and Materials. Philadelphia

2010-01-01T23:59:59.000Z

291

Design, testing and two-dimensional flow modeling of a multiple-disk fan  

Science Conference Proceedings (OSTI)

A multiple-disk Tesla type fan has been designed, tested and analyzed two-dimensionally using the conservation of angular momentum principle. Experimental results showed that such multiple-disk fans exhibited exceptionally low performance characteristics, which could be attributed to the low viscosity, tangential nature of the flow, and large mechanical energy losses at both suction and discharge sections that are comparable to the total input power. By means of theoretical analysis, local and overall shearing stresses on the disk surfaces have been determined based on tangential and radial velocity distributions of the air flow of different volume flow rates at prescribed disk spaces and rotational speeds. Then the total power transmitted by rotating disks to air flow, and the power acquired by the air flow in the gap due to transfer of angular momentum have been obtained by numerically integrating shearing stresses over the disk surfaces. Using the measured shaft and hydraulic powers, these quantities were utilized to evaluate mechanical energy losses associated with the suction and discharge sections of the fan. (author)

Engin, Tahsin; Oezdemir, Mustafa; Cesmeci, Sevki [Department of Mechanical Engineering, The University of Sakarya, Esentepe Campus, 54187 Sakarya (Turkey)

2009-11-15T23:59:59.000Z

292

Random fan-out state induced by site-random interlayer couplings  

Science Conference Proceedings (OSTI)

We study the low-temperature properties of a classical Heisenberg model with site-random interlayer couplings on the cubic lattice. This model is introduced as a simplified effective model of Sr(Fe{sub 1-x}Mn{sub x})O{sub 2}, which was recently synthesized. In this material, when x=0.3, ({pi}{pi}{pi}) and ({pi}{pi}0) mixed ordering is observed by neutron diffraction measurements. Using Monte Carlo simulations, we find an exotic bulk spin structure that explains the experimentally obtained results. We name this spin structure the ''random fan-out state.'' The mean-field calculations provide an intuitive understanding of this phase being induced by the site-random interlayer couplings. Since Rietveld analysis assuming the random fan-out state agrees well with the neutron diffraction pattern of Sr(Fe{sub 0.7}Mn{sub 0.3})O{sub 2}, we conclude that the random fan-out state is reasonable for the spin-ordering pattern of Sr(Fe{sub 0.7}Mn{sub 0.3})O{sub 2} at the low-temperature phase.

Tamura, Ryo; Kawashima, Naoki; Yamamoto, Takafumi; Tassel, Cedric; Kageyama, Hiroshi [Institute for Solid State Physics, University of Tokyo, 5-1-5 Kashiwa-no-ha, Kashiwa, Chiba 277-8581 (Japan); Department of Energy and Hydrocarbon Chemistry, Graduate School of Engineering, Kyoto University, Nishikyouku, Kyoto 615-8510 (Japan)

2011-12-01T23:59:59.000Z

293

Economic Recovery of Oil Trapped at Fan Margins Using Hig Angle Wells Multiple Hydraulic Fractures  

Science Conference Proceedings (OSTI)

The Yowlumne field is a giant field in the southern San Joaquin basin, Kern County, California. It is a deep (13,000 ft) waterflood operation that produces from the Miocene- aged Stevens Sand. The reservoir is interpreted as a layered, fan-shaped, prograding turbidite complex containing several lobe-shaped sand bodies that represent distinct flow units. A high ultimate recovery factor is expected, yet significant quantities of undrained oil remain at the fan margins. The fan margins are not economic to develop using vertical wells because of thinning pay, deteriorating rock quality, and depth. This project attempts to demonstrate the effectiveness of exploiting the northeast distal fan margin through the use of a high- angle well completed with multiple hydraulic- fracture treatments. A high-angle well offers greater pay exposure than can be achieved with a vertical well. Hydraulic-fracture treatments will establish vertical communication between thin interbedded layers and the wellbore. The equivalent production rate and reserves of three vertical wells are anticipated at a cost of approximately two vertical wells. The near-horizontal well penetrated the Yowlumne sand; a Stevens sand equivalent, in the distal fan margin in the northeast area of the field. The well was drilled in a predominately westerly direction towards the interior of the field, in the direction of improving rock quality. Drilling and completion operations proved to be very challenging, leading to a number of adjustments to original plans. Hole conditions resulted in obtaining less core material than desired and setting intermediate casing 1200 ft too high. The 7 in. production liner stuck 1000 ft off bottom, requiring a 5 in. liner to be run the rest of the way. The cement job on the 5 in. liner resulted in a very poor bond, which precluded one of three hydraulic fracture treatments originally planned for the well. Openhole logs confirmed most expectations going into the project about basic rock properties: the formation was shaly with low porosities, and water saturations were in line with expectations, including the presence of some intervals swept out by the waterflood. High water saturations at the bottom of the well eliminated one of the originally planned hydraulic fracture treatments. Although porosities proved to be low, they were more uniform across the formation than expected. Permeabilities of the various intervals continue to be evaluated, but appear to be better than expected from the porosity log model derived in Budget Period One. The well was perforated in all pay sections behind the 5 in. liner. Production rates and phases agree nicely with log calculations, fractional flow calculations, and an analytical technique used to predict the rate performance of the well.

Laue, M.L.

1997-11-21T23:59:59.000Z

294

High-amplitude reflection packets (HARPs) of the Mississippi Fan, Gulf of Mexico  

E-Print Network (OSTI)

Examination of seismic data from the deep-water Gulf of Mexico reveals the presence of High-Amplitude Reflection Packets (HARPs). An analog study conducted by the Ocean Drilling Program Leg 155 identified and described Amazon Fan HARPs as a stacked, relatively unconfined series of graded turbidites overlain by a channel-levee. HARP seismic facies thin laterally and onlap antecedent bathymetry (preexisting submarine topography). HARP areal extent is controlled by antecedent bathymetry and turbidity flow sediment volumes. Mississippi Fan HARP deposition can be described by three depositional models: the "avulsion" model, the "fill and spill" model, and the "transition" model. The "avulsion" depositional model, developed by Flood et al. (1991), describes avulsion of submarine channel-levees by turbidity flows. Subsequent turbidity flows exit the channel-levee at the avulsion point and are deposited as unchannelized HARPs. The "fill and spill" model, developed by Satterfield and Behrens (1990), describes turbidite deposition in the Gulf of Mexico salt province. Initial stages of the "fill and spill" model accurately describe the seismic geometries of HARPs confined by adjacent salt structures. The "transition" model was developed in this study to describe the Gulf of Mexico HARP seismic geometries seen in the transition zone from the salt province to the abyssal plain. The HARPs described by the "transition" model contain an upslope segment confined by salt structures and a downslope segment confined by antecedent bathymetry. Utilizing seismic data from the Gulf of Mexico and core and well-log data from the Amazon Fan, this study has determined that HARPs and related channel-levees have hydrocarbon play potential. HARP sheet sands, internal HARP channel fill, overlying channel-levee fill, and overbank levee sands are potential reservoir units. Detrital carbonate and hemipelagic shale source rocks are in place in the deep-water Gulf of Mexico. In addition, structurally derived migration pathways combine with percolation as potential migration processes. This study integrates identification and description of HARP seismic facies relationships, current and newly developed depositional models, interpretation of stratigraphic controls, HARP internal reservoir architecture, and determination of HARP hydrocarbon potential in order to predict HARP deposition in the Mississippi Fan and other mud-rich fans worldwide.

Francis, Jason Michael

2000-01-01T23:59:59.000Z

295

Active Noise Control of a Two-Fan Exhaust-Mounted Array Using Near-Field Control Sources and Error Sensors.  

E-Print Network (OSTI)

??Multiple fans are sometimes used in an array configuration to cool various types of electronic equipment. In addition to adding another noise source, using two… (more)

Rust, Ryan Leonard 1982-

2010-01-01T23:59:59.000Z

296

Reason and reaction: The dual route of decision making process on social media usage: The case of hospitality brand fan pages.  

E-Print Network (OSTI)

??A new phenomenon on Facebook, resulting from social media revolution, is the emergence of numerous Facebook fan pages. This form of online brand community is… (more)

Manthiou, Aikaterini

2012-01-01T23:59:59.000Z

297

Study of the effects of ambient conditions upon the performance of fan powdered, infrared, natural gas burners. Quarterly technical progress report, January 1, 1996--March 31, 1996  

DOE Green Energy (OSTI)

The objective of this investigation is to characterize the operation of fan powered infrared burner (PER) at various gas compositions and ambient conditions and develop design guidelines for appliances containing PER burners for satisfactory performance. During this past quarter, a porous radiant burner testing facility consisting of a commercial deep-fat fryer, an FTIR based spectral radiance measurement system, a set of flue gas analysis components, and a fuel gas mixing station was constructed. The measurement capabilities of the system were tested using methane and the test results were found to be consistent with the literature. Various gas mixtures were tested. Results indicated that the stability limits of the burner and emissions vary with fuel gas composition and air/fuel ratio. However, the maximum radiant efficiency of the burner remained constant. Results obtained from this study can be useful to develop optimum design guidelines for PER burner manufacturers.

Bai, T.; Yeboah, Y.D.; Sampath, R.

1996-04-01T23:59:59.000Z

298

Strategy for the Operation of Cooling Towers with variable Speed Fans  

E-Print Network (OSTI)

Within the SPS Cooling Water Project at CERN aimed at the reduction of water consumption, this primary open cooling loop will be closed and all the primary cooling circuit components will be upgraded to the new required duty and brought to the necessary safety and operability standards. In particular the tower fans will be fitted with variable frequency drives to replace the existing two speed motors. This paper presents a study to optimize the operation of SPS cooling towers taking into account outdoor conditions (wet and dry bulb temperatures) and the entirety of the primary circuit in which they will operate.

Iñigo-Golfín, J

2001-01-01T23:59:59.000Z

299

Busemann functions and the speed of a second class particle in the rarefaction fan  

E-Print Network (OSTI)

In this paper we will show how the results found in Cator and Pimentel 2009, about the Busemann functions in last-passage percolation, can be used to calculate the asymptotic distribution of the speed of a single second class particle starting from an arbitrary deterministic configuration which has a rarefaction fan, in either the totally asymetric exclusion process, or the Hammersley interacting particle process. The method will be to use the well known last-passage percolation description of the exclusion process and of the Hammersley process, and then the well known connection between second class particles and competition interfaces.

Eric Cator; Leandro P. R. Pimentel

2010-08-10T23:59:59.000Z

300

FANS - Principle  

Science Conference Proceedings (OSTI)

... detecting all scattered neutrons with energy Ef energies, with moderate ... which changes to optimize intensity during the ...

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


301

FANS - Overview  

Science Conference Proceedings (OSTI)

... Pyrolytic Graphite [PG(002)], Without small shield: 2.5 meV ? E ? 25.0 meV With small shield: 3.7 meV ? E ? 45.0 meV. ...

302

Influence of provenance on detrital and diagenetic mineralogy of small tertiary fans in southwestern Montana  

SciTech Connect

In the North Boulder River basin in southwestern Montana, alluvial fans of the Renova (Oligocene-Miocene) and the Sixmile Creek (Miocene) Formations were deposited on the flanks of north-south-trending uplifts that also supplied the detritus. The Elkhorn Mountain volcanics (78 m.y.) overlying the Boulder batholith make up the western highlands, a small patch of Precambrian Belt Group rocks occur in the southwest and Paleozoic siliciclastic and carbonate rocks forming the eastern margin. The fan sediments thus allow adequate control for studying the influence of source rocks on detrital and diagenetic mineralogy. Modal analysis of 6228 grains in 31 thin sections shows a decrease of VRF away from the igneous sources (37% to 1% in a north-south transect; 37% to 7% in a west-east transect) along with an increase in quartz (8% to 24% and 3% to 13%) and plagioclase (2% to 16% and 2% to 10%); orthoclase abundance is low except in the southwest. Volcanic ash and glass shards are found in the younger sediments in the northern part of the basin. Their data show a positive correlation between the abundance of orthoclase and kaolinite (north-south transect); between SRF and carbonate cement (west-east transect) and between glass shards and smectite (both north-south and west-east transects). They infer that the diagenetic mineralogy of these sands was controlled essentially by the detrital particles, which were strongly controlled by source rocks in this area.

Olson, J.; Basu, A.

1987-05-01T23:59:59.000Z

303

Recent Developments of the Modelica"Buildings" Library for Building Energy and Control Systems  

Science Conference Proceedings (OSTI)

At the Modelica 2009 conference, we introduced the Buildings library, a freely available Modelica library for building energy and control systems. This paper reports the updates of the library and presents example applications for a range of heating, ventilation and air conditioning (HVAC) systems. Over the past two years, the library has been further developed. The number of HVAC components models has been doubled and various components have been revised to increase numerical robustness.The paper starts with an overview of the library architecture and a description of the main packages. To demonstrate the features of the Buildings library, applications that include multizone airflow simulation as well as supervisory and local loop control of a variable air volume (VAV) system are briefly described. The paper closes with a discussion of the current development.

Wetter, Michael; Zuo, Wangda; Nouidui, Thierry Stephane

2011-04-01T23:59:59.000Z

304

VELOCITY MEASUREMENTS FOR A SOLAR ACTIVE REGION FAN LOOP FROM HINODE/EIS OBSERVATIONS  

Science Conference Proceedings (OSTI)

The velocity pattern of a fan loop structure within a solar active region over the temperature range 0.15-1.5 MK is derived using data from the EUV Imaging Spectrometer (EIS) on board the Hinode satellite. The loop is aligned toward the observer's line of sight and shows downflows (redshifts) of around 15 km s{sup -1} up to a temperature of 0.8 MK, but for temperatures of 1.0 MK and above the measured velocity shifts are consistent with no net flow. This velocity result applies over a projected spatial distance of 9 Mm and demonstrates that the cooler, redshifted plasma is physically disconnected from the hotter, stationary plasma. A scenario in which the fan loops consist of at least two groups of 'strands'-one cooler and downflowing, the other hotter and stationary-is suggested. The cooler strands may represent a later evolutionary stage of the hotter strands. A density diagnostic of Mg VII was used to show that the electron density at around 0.8 MK falls from 3.2 Multiplication-Sign 10{sup 9} cm{sup -3} at the loop base, to 5.0 Multiplication-Sign 10{sup 8} cm{sup -3} at a projected height of 15 Mm. A filling factor of 0.2 is found at temperatures close to the formation temperature of Mg VII (0.8 MK), confirming that the cooler, downflowing plasma occupies only a fraction of the apparent loop volume. The fan loop is rooted within a so-called outflow region that displays low intensity and blueshifts of up to 25 km s{sup -1} in Fe XII {lambda}195.12 (formed at 1.5 MK), in contrast to the loop's redshifts of 15 km s{sup -1} at 0.8 MK. A new technique for obtaining an absolute wavelength calibration for the EIS instrument is presented and an instrumental effect, possibly related to a distorted point-spread function, that affects velocity measurements is identified.

Young, P. R. [College of Science, George Mason University, 4400 University Drive, Fairfax, VA 22030 (United States); O'Dwyer, B.; Mason, H. E. [Department of Applied Mathematics and Theoretical Physics, University of Cambridge, Wilberforce Road, Cambridge, CB3 0WA (United Kingdom)

2012-01-01T23:59:59.000Z

305

A high-resolution 2-DH numerical scheme for process-based modeling of 3-D turbidite fan stratigraphy  

Science Conference Proceedings (OSTI)

A generic three-dimensional process-based model is presented, aimed at simulation of the construction of turbidite fan stratigraphy by low-density turbidity current events. It combines theoretical formulations on density flow and sediment transport of ... Keywords: MacCormack scheme, Operator splitting, Shock-capturing technique, Stratigraphic modeling, Turbidite reservoirs, Turbidity currents

Remco M. Groenenberg; Kees Sloff; Gert Jan Weltje

2009-08-01T23:59:59.000Z

306

Study of the Effects of Ambient Conditions Upon the Performance of Fan Powered, Infrared Natural Gas Burners  

SciTech Connect

The objective of this investigation was to characterize the operation of a fan-powered, infrared burner (IR burner) at various gas compositions and ambient conditions, develop numerical model to simulate the burner performances, and provide design guidelines for appliances containing PIR burners for satisfactory performance.

Clark Atlanta University

2002-12-02T23:59:59.000Z

307

Towards a syntactic signature for domain models: proposed descriptive metrics for visualizing the entity fan-out frequency distribution  

Science Conference Proceedings (OSTI)

The main objective of this paper is to find a minimal set of measures that allow the immediate, intuitive characterisation and visualization of the syntactic structure of models covering a particular application domain. The measures are validated ... Keywords: case measures, enterprise models, entity fan-out distribution, metrics, model analysis, model complexity, modelling

Jean-Paul van Belle

2002-09-01T23:59:59.000Z

308

Tracer airflow measurement system (TRAMS)  

DOE Patents (OSTI)

A method and apparatus for measuring fluid flow in a duct is disclosed. The invention uses a novel high velocity tracer injector system, an optional insertable folding mixing fan for homogenizing the tracer within the duct bulk fluid flow, and a perforated hose sampling system. A preferred embodiment uses CO.sub.2 as a tracer gas for measuring air flow in commercial and/or residential ducts. In extant commercial buildings, ducts not readily accessible by hanging ceilings may be drilled with readily plugged small diameter holes to allow for injection, optional mixing where desired using a novel insertable foldable mixing fan, and sampling hose.

Wang, Duo (Albany, CA)

2007-04-24T23:59:59.000Z

309

Toward green systems for cleanrooms: Energy efficient fan-filter units  

E-Print Network (OSTI)

information to users and designers to make informed decisions such as selecting more energy efficient models; Market

Jeng, Ming-Shan; Xu, Tengfang; Lan, Chao-Ho

2004-01-01T23:59:59.000Z

310

Parametric System Curves: Correlations Between Fan Pressure Rise and Flow for Large Commercial Buildings  

E-Print Network (OSTI)

to meet a varying space conditioning load. Thus, withoutexample, at a given space conditioning load, reducing supply

Sherman, Max

2010-01-01T23:59:59.000Z

311

Laboratory evaluation of fan/filter units' aerodynamic and energy performance  

SciTech Connect

The paper discusses the benefits of having a consistent testing method to characterize aerodynamic and energy performance of FFUs. It presents evaluation methods of laboratory-measured performance of ten relatively new, 1220 mm x 610 mm (or 4 ft x 2 ft) fan-filter units (FFUs), and includes results of a set of relevant metrics such as energy performance indices (EPI) based upon the sample FFUs tested. This paper concludes that there are variations in FFUs' performance, and that using a consistent testing and evaluation method can generate compatible and comparable FFU performance information. The paper also suggests that benefits and opportunities exist for our method of testing FFU energy performance to be integrated in future recommended practices.

Xu, Tengfang; Jeng, Ming-Shan

2004-07-27T23:59:59.000Z

312

The global distribution of large subaerial distributary fluvial systems  

E-Print Network (OSTI)

Large subaerial distributary fluvial systems are cone-shaped, alluvial deposits that are ubiquitous features on Earth. These non-marine, non-lacustrine deposits have superficial similarities to small alluvial fans but are at a scale that is orders of magnitude larger. A variety of terms have been used to identify these features, including alluvial cone, inland delta, wet alluvial fan, humid alluvial fan, alluvial fan, subaerial fan, terminal fan, and megafan. The first systematic examination of these features was presented by Wilkinson et al. (1997). This thesis attempts to provide a more detailed characterization and classification of these features. Fourteen systems in South America, Africa, and Asia were examined using Shuttle photography and AVHRR imagery. This study included: (1) maps of each system and their global distribution, (2) morphometric analyses, (3) classifications by climate, geology, and hydrology, and (4) a comparison to other fluvial systems. These systems have areas 8,881 to 239,583 km², radii 130 to 806 km, and slopes 0.00006 to 0.00079. Active and former river channel patterns on these features suggest that they formed by the action of a single river avulsing across the feature. The area of these features is unrelated to the area of the upstream drainage basin, but is related to the size of the downstream basin. This sample of systems occurs in a variety of climates and in two different geologic settings - foreland basins and half graben. The rivers on all systems are orientated transverse to the trend of the adjacent mountain range or fault. A variety of channel patterns are found on these systems. Considering the definitions of alluvial fans, rivers, and deltas, these systems are best classified as a specific variety of alluvial fan. A new alluvial fan classification scheme more inclusive than that proposed by Stanistreet and McCarthy (1993) is needed. The adoption of a common term to describe these systems - such as megafan - would help to eliminate some of the definitional ambiguities between them and other alluvial fans. Knowledge of these features will enhance our ability to interpret analogous features in the rock record, including important petroleum and water aquifers (e.g., the Ogallala Formation).

Gwynn, David Wilkinson

2002-01-01T23:59:59.000Z

313

Energy Efficient Laboratory Fume Hood  

Allows use of small HVAC systems ; Avoids expensive control systems required by VAV fume hoods ; ABSTRACT: Fume hoods, used to protect the ...

314

Building Energy Software Tools Directory: ENERPASS  

NLE Websites -- All DOE Office Websites (Extended Search)

ENERPASS ENERPASS Detailed building energy simulation program for residential and smaller commercial buildings. ENERPASS calculates the annual energy use for space heating, cooling, lighting, water heating and fan energy. The calculations are performed on an hourly basis using hourly measured weather data. ENERPASS can model up to seven building zones and provides hourly temperature and humidity predictions for each zone. A wide range of HVAC systems can be modelled including make-up air units, heat recovery ventilators, rooftop units, VAV, four-pipe fan coil, and dual duct. The program uses full screen data entry in an easy-to-use format. A typical building model can be generated in one to two hours. In IEA validation studies ENERPASS results compare favorably with other hourly based computer

315

Building Energy Software Tools Directory: DONKEY  

NLE Websites -- All DOE Office Websites (Extended Search)

DONKEY DONKEY Logo for DONKEY Determines the size of a duct network using the static regain, constant pressure gradient, or balanced pressure drop method. Duct sizes can also be fixed and the program handles rectangular, round or oval ducts. DONKEY can calculate duct leakage and heat loss/gain and automatically locate balancing dampers throughout the duct system. The sound power levels throughout the entire network are calculated at each of the seven octave band frequencies from 63 to 4000 Hz taking into account self generated noise by the fan, ducts, fittings, VAV boxes, registers, grilles and the attenuation of ducts, fittings, plenums and any duct silencers specified. Account is taken of noise transmitted both from the fan down to the terminals and from the terminals back up the network.

316

J.L. Liscum-Powell, S.D. Pautz, C.R. Drumm, W.C. Fan, W.J. Bohnhoff...  

National Nuclear Security Administration (NNSA)

of the Ceptre Code to Cable SGEMP Problems J.L. Liscum-Powell, * S.D. Pautz, * C.R. Drumm, * W.C. Fan, * W.J. Bohnhoff, * L.J. Lorence * * Sandia National Laboratories,...

317

VARIATION IN EROSION/DEPOSITION RATES OVER THE LAST FIFTTY YEARS ON ALLUVIAL FAN SURFACES OF L. PLEISTOCENE-MID HOLOCENE AGE, ESTIMATIONS USING 137CS SOIL PROFILE DATA, AMARGOSA VALLEY, NEVADA  

DOE Green Energy (OSTI)

Variations in erosion and deposition for the last fifty years (based on estimates from 137Cs profiles) on surfaces (Late Pleistocene to Late Holocene in age) making up the Fortymile Wash alluvial fan south of Yucca Mountain, is a function of surface age and of desert pavement development or absence. For purposes of comparing erosion and deposition, the surfaces can be examined as three groups: (1) Late Pleistocene surfaces possess areas of desert pavement development with thin Av or sandy A horizons, formed by the trapping capabilities of the pavements. These zones of deposition are complemented by coppice dune formation on similar parts of the surface. Areas on the surface where no pavement development has occurred are erosional in nature with 0.0 +/- 0.0 cm to 1.5 +/- 0.5 cm of erosion occurring primarily by winds blowing across the surface. Overall these surfaces may show either a small net depositional gain or small erosional loss. (2) Early Holocene surfaces have no well-developed desert pavements, but may have residual gravel deposits in small areas on the surfaces. These surfaces show the most consistent erosional surface areas on which it ranges from 1.0 +/-.01 cm to 2.0+/- .01 cm. Fewer depositional forms are found on this age of surface so there is probably a net loss of 1.5 cm across these surfaces. (3) The Late Holocene surfaces show the greatest variability in erosion and deposition. Overbank deposition during floods cover many edges of these surfaces and coppice dune formation also creates depositional features. Erosion rates are highly variable and range from 0.0 +/- 0.0 to a maximum of 2.0+/-.01. Erosion occurs because of the lack of protection of the surface. However, the common areas of deposition probably result in the surface having a small net depositional gain across these surfaces. Thus, the interchannel surfaces of the Fortymile Wash fan show a variety of erosional styles as well as areas of deposition. The fan, therefore, is a dynamic system that primarily responds to the incising of the channels into the upper fan surface, and the development of protecting desert pavements with time.

C. Harrington; R. Kelly; K.T. Ebert

2005-08-26T23:59:59.000Z

318

Ventilation Systems for Cooling | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Ventilation Systems for Cooling Ventilation Systems for Cooling Ventilation Systems for Cooling May 30, 2012 - 6:19pm Addthis Proper ventilation helps you save energy and money. | Photo courtesy of JD Hancock. Proper ventilation helps you save energy and money. | Photo courtesy of JD Hancock. Ventilation is the least expensive and most energy-efficient way to cool buildings. Ventilation works best when combined with methods to avoid heat buildup in your home. In some cases, natural ventilation will suffice for cooling, although it usually needs to be supplemented with spot ventilation, ceiling fans, and window fans. For large homes, homeowners might want to investigate whole house fans. Interior ventilation is ineffective in hot, humid climates where

319

Ventilation Systems for Cooling | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Ventilation Systems for Cooling Ventilation Systems for Cooling Ventilation Systems for Cooling May 30, 2012 - 6:19pm Addthis Proper ventilation helps you save energy and money. | Photo courtesy of JD Hancock. Proper ventilation helps you save energy and money. | Photo courtesy of JD Hancock. Ventilation is the least expensive and most energy-efficient way to cool buildings. Ventilation works best when combined with methods to avoid heat buildup in your home. In some cases, natural ventilation will suffice for cooling, although it usually needs to be supplemented with spot ventilation, ceiling fans, and window fans. For large homes, homeowners might want to investigate whole house fans. Interior ventilation is ineffective in hot, humid climates where

320

Final Report Independent Verification Survey of the High Flux Beam Reactor, Building 802 Fan House Brookhaven National Laboratory Upton, New York  

Science Conference Proceedings (OSTI)

On May 9, 2011, ORISE conducted verification survey activities including scans, sampling, and the collection of smears of the remaining soils and off-gas pipe associated with the 802 Fan House within the HFBR (High Flux Beam Reactor) Complex at BNL. ORISE is of the opinion, based on independent scan and sample results obtained during verification activities at the HFBR 802 Fan House, that the FSS (final status survey) unit meets the applicable site cleanup objectives established for as left radiological conditions.

Evan Harpeneau

2011-06-24T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


321

An Iterative Solver with a Convergence-Acceleration Technique for Pressure Field in an Uneven-Spacing Grid System  

Science Conference Proceedings (OSTI)

A straightforward iterative method is developed for solving the pressure field in three-dimensional, anelastic, nonhydrostatic, mesoscale models with uneven-spacing grid systems for which direct FFT (fan Fourier transform) schemes cannot be ...

Chih-Yue Jim Kao; Lawrence H. Auer

1990-07-01T23:59:59.000Z

322

Ultrabroadband optical parametric chirped-pulse amplifier using a fan-out periodically poled crystal with spectral spatial dispersion  

Science Conference Proceedings (OSTI)

Based on the full two-dimensional characteristics of the quasi-phase-matched fan-out periodically poled crystal, a scalable and engineerable scheme for ultrabroadband optical parametric chirped-pulse amplification is proposed, which can significantly broaden the gain bandwidth by the spatial separation of different frequency components of the signal pulse and manipulation of the distribution of the pump beam along the fan-out direction of the crystal. The theoretical analysis shows that the signal pulse can be amplified with minimal spectrum narrowing, and the initial spectrum can be broadened considerably if needed. Based on this scheme, using a fan-out periodically poled 5% mol MgO-doped congruent lithium niobate with a configuration of 5x0.5x5 mm{sup 3} and two pump beams, the 3.3-{mu}m middle-infrared ultrabroadband optical parametric chirped-pulse amplifier is designed. The numerical computation results confirm that the -3 dB gain bandwidth of this amplifier exceeds 320 nm and can be further broadened.

Chen Liezun; Wang Youwen [Key Laboratory for Micro/Nano Optoelectronic Devices of Ministry of Education, School of Information Science and Engineering, Hunan University, Changsha 410082 (China); Department of Physics and Electronic Information Science, Hengyang Normal University, Hengyang 421008 (China); Wen Shuangchun; Fan Dianyuan [Key Laboratory for Micro/Nano Optoelectronic Devices of Ministry of Education, School of Information Science and Engineering, Hunan University, Changsha 410082 (China); You Kaiming [Department of Physics and Electronic Information Science, Hengyang Normal University, Hengyang 421008 (China); Qian Liejia [Department of Optical Science and Engineering, Fudan University, Shanghai 200433 (China)

2010-10-15T23:59:59.000Z

323

Economic Recovery of Oil Trapped at Fan Margins Using High Angle Wells Multiple Hydraulic Fractures  

SciTech Connect

This project attempts to demonstrate the effectiveness of exploiting thin-layered, low-energy deposits at the distal margin of a prograding turbidite complex through the use of hydraulically fractured horizontal or high-angle wells. The combination of a horizontal or high-angle well and hydraulic fracturing will allow greater pay exposure than can be achieved with conventional vertical wells while maintaining vertical communication between thin interbedded layers and the wellbore. A high-angle well will be drilled in the fan-margin portion of a slope-basin clastic reservoir and will be completed with multiple hydraulic-fracture treatments. Geologic modeling, reservoir characterization, and fine-grid reservoir simulation will be used to select the well location and orientation. Design parameters for the hydraulic-fracture treatments will be determined, in part, by fracturing an existing test well. Fracture azimuth will be predicted by passive seismic monitoring of a fracture-stimulation treatment in the test well using logging tools in an offset well.

Mike L. Laue

1997-10-30T23:59:59.000Z

324

ECONOMIC RECOVERY OF OIL TRAPPED AT FAN MARGINS USING HIGH ANGLE WELLS AND MULTIPLE HYDRAULIC FRACTURES  

Science Conference Proceedings (OSTI)

This project attempts to demonstrate the effectiveness of exploiting thin-layered, low-energy deposits at the distal margin of a prograding turbidite complex through the use of hydraulically fractured horizontal or high-angle wells. The combination of a horizontal or high-angle well and hydraulic fracturing will allow greater pay exposure than can be achieved with conventional vertical wells while maintaining vertical communication between thin interbedded layers and the wellbore. A high-angle well will be drilled in the fan-margin portion of a slope-basin clastic reservoir and will be completed with multiple hydraulic-fracture treatments. Geologic modeling, reservoir characterization, and fine-grid reservoir simulation will be used to select the well location and orientation. Design parameters for the hydraulic-fracture treatments will be determined, in part, by fracturing an existing test well. Fracture azimuth will be predicted by passive seismic monitoring of a fracture-stimulation treatment in the test well using logging tools in an offset well.

Mike L. Laue

1998-11-06T23:59:59.000Z

325

Simulation of energy performance of underfloor air distribution (UFAD) systems  

E-Print Network (OSTI)

3. Impact of supply fan design static pressure for UFADdifferences in supply fan design static pressure. Pressuresterminal units. Supply fan design power increases by 32.8

2009-01-01T23:59:59.000Z

326

The Energy Saving Potential of Membrane-Based Enthalpy Recovery...  

NLE Websites -- All DOE Office Websites (Extended Search)

The Energy Saving Potential of Membrane-Based Enthalpy Recovery in Vav Systems for Commercial Office Buildings Title The Energy Saving Potential of Membrane-Based Enthalpy Recovery...

327

The Energy Saving Potential of Membrane-Based Enthalpy Recovery...  

NLE Websites -- All DOE Office Websites (Extended Search)

The Energy Saving Potential of Membrane-Based Enthalpy Recovery in VAV System for Commercial Office Buildings Title The Energy Saving Potential of Membrane-Based Enthalpy Recovery...

328

Publications  

NLE Websites -- All DOE Office Websites (Extended Search)

Haves Clear All Filters 2012 Wang, Liping, Philip Haves, and John Breshears. "The Energy Saving Potential of Membrane-Based Enthalpy Recovery in VAV System for Commercial...

329

Thermal decay in underfloor air distribution (UFAD) systems: Fundamentals and influence on system performance  

E-Print Network (OSTI)

supply temperature AHU fan design static pressure AHU fanshown in Table 1, AHU fan design static pressure for series

Lee, Kwang Ho; Schiavon, Stefano; Bauman, Fred; Webster, Tom

2012-01-01T23:59:59.000Z

330

Adaptive planning using megavoltage fan-beam CT for radiation therapy with testicular shielding  

Science Conference Proceedings (OSTI)

This study highlights the use of adaptive planning to accommodate testicular shielding in helical tomotherapy for malignancies of the proximal thigh. Two cases of young men with large soft tissue sarcomas of the proximal thigh are presented. After multidisciplinary evaluation, preoperative radiation therapy was recommended. Both patients were referred for sperm banking and lead shields were used to minimize testicular dose during radiation therapy. To minimize imaging artifacts, kilovoltage CT (kVCT) treatment planning was conducted without shielding. Generous hypothetical contours were generated on each 'planning scan' to estimate the location of the lead shield and generate a directionally blocked helical tomotherapy plan. To ensure the accuracy of each plan, megavoltage fan-beam CT (MVCT) scans were obtained at the first treatment and adaptive planning was performed to account for lead shield placement. Two important regions of interest in these cases were femurs and femoral heads. During adaptive planning for the first patient, it was observed that the virtual lead shield contour on kVCT planning images was significantly larger than the actual lead shield used for treatment. However, for the second patient, it was noted that the size of the virtual lead shield contoured on the kVCT image was significantly smaller than the actual shield size. Thus, new adaptive plans based on MVCT images were generated and used for treatment. The planning target volume was underdosed up to 2% and had higher maximum doses without adaptive planning. In conclusion, the treatment of the upper thigh, particularly in young men, presents several clinical challenges, including preservation of gonadal function. In such circumstances, adaptive planning using MVCT can ensure accurate dose delivery even in the presence of high-density testicular shields.

Yadav, Poonam [Department of Human Oncology, University of Wisconsin, Madison, Madison, WI (United States); Department of Medical Physics, University of Wisconsin, Madison, Madison, WI (United States); School of Advance Sciences, Vellore Institue of Technology University, Vellore, Tamil Nadu (India); Kozak, Kevin [Department of Human Oncology, University of Wisconsin, Madison, Madison, WI (United States); Tolakanahalli, Ranjini [Department of Human Oncology, University of Wisconsin, Madison, Madison, WI (United States); Department of Medical Physics, University of Wisconsin, Madison, Madison, WI (United States); Ramasubramanian, V. [School of Advance Sciences, Vellore Institue of Technology University, Vellore, Tamil Nadu (India); Paliwal, Bhudatt R. [Department of Human Oncology, University of Wisconsin, Madison, Madison, WI (United States); Department of Medical Physics, University of Wisconsin, Madison, Madison, WI (United States); University of Wisconsin, Riverview Cancer Centre, Wisconsin Rapids, WI (United States); Welsh, James S. [Department of Human Oncology, University of Wisconsin, Madison, Madison, WI (United States); Department of Medical Physics, University of Wisconsin, Madison, Madison, WI (United States); Rong, Yi, E-mail: rong@humonc.wisc.edu [Department of Human Oncology, University of Wisconsin, Madison, Madison, WI (United States); University of Wisconsin, Riverview Cancer Centre, Wisconsin Rapids, WI (United States)

2012-07-01T23:59:59.000Z

331

ECONOMIC RECOVERY OF OIL TRAPPED AT FAN MARGINS USING HIGH ANGLE WELLS AND MULTIPLE HYDRAULIC FRACTURES  

Science Conference Proceedings (OSTI)

This project attempts to demonstrate the effectiveness of exploiting thin-layered, low-energy deposits at the distal margin of a prograding turbidite complex through the use of hydraulically fractured horizontal or high-angle wells. The combination of a horizontal or high-angle well and hydraulic fracturing will allow greater pay exposure than can be achieved with conventional vertical wells while maintaining vertical communication between thin interbedded layers and the wellbore. A high-angle well will be drilled in the fan-margin portion of a slope-basin clastic reservoir and will be completed with multiple hydraulic-fracture treatments. Geologic modeling, reservoir characterization, and fine-grid reservoir simulation will be used to select the well location and orientation. Design parameters for the hydraulic-fracture treatments will be determined, in part, by fracturing an existing test well. Fracture azimuth will be predicted by passive seismic monitoring of a fracture-stimulation treatment in the test well using logging tools in an offset well. The long radius, near horizontal well was drilled during the first quarter of 1996. Well conditions resulted in the 7 in. production liner sticking approximately 900 ft off bottom. Therefore, a 5 in. production liner was necessary to case this portion of the target formation. Swept-out sand intervals and a poor cement bond behind the 5 in. liner precluded two of the three originally planned hydraulic fracture treatments. As a result, all pay intervals behind the 5 in. liner were perforated and stimulated with a non-acid reactive fluid. Following a short production period, the remaining pay intervals in the well (behind the 7 in. liner) were perforated. The well was returned to production to observe production trends and pressure behavior and assess the need to stimulate the new perforations.

Mike L. Laue

2001-09-28T23:59:59.000Z

332

Comparing Two Types of Magnetically- Coupled Adjustable Speed Drives with Variable Frequency Drives in Pump and Fan Applications  

E-Print Network (OSTI)

This paper presents the results from laboratory tests on MagnaDrive Corporations fixed-magnet magnetically-coupled adjustable speed drive (MC-ASD) and Coyote Electronics electromagnetic MC-ASD as compared to a typical variable frequency drive (VFD) for typical fan and pump loads. It also discusses advantages and disadvantages of using mechanical MC-ASD versus VFDs and it provides field experience with VFDs in refrigerated warehouses as well as the fixed magnet MC-ASD in wastewater and other field applications. Laboratory tests for a 50 hp fan retrofit showed electronic VFD savings at 62%, the MagnaDrive Coupling at 39% and PAYBACK Drive at 46%. At $0.06/kWh and list prices, the simple payback for the VFD is 2.4 years, the MagnaDrive is 4.6 years and the PAYBACK is 1.9 years. MagnaDrive has models from 25 to 500 hp while PAYBACK has models from 3 to 200 hp. Contractors to the Northwest Energy Efficiency Alliance have helped to install VFDs for about 300 evaporator fans in over two dozen refrigerated warehouses and to install fixed-magnet MC-ASDs in about 50 applications with about half of these controlling wastewater pumps. The Alliance has no particular field experience with the electcromagnetic coupling. The primary advantages of magnetically coupled adjustable speed drives (MC-ASD) over VFDs come from reduced maintenance, resistance to dirty environments, separation of load vibration from the motor, and less stringent requirements for precise shaft alignment. Field experience indicates reductions in noise and repairs from vibration loads, tolerance of poor electrical power quality, and ease of installation are often more important than energy savings. The MC-ASDs are being used where VFDs have not survived or are considered too complicated.

Anderson, K. J.; Chvala, W. D.

2003-05-01T23:59:59.000Z

333

CALIFORNIA ENERGY Market Connections Report  

E-Print Network (OSTI)

of Large Commercial HVAC Systems Led by Erik Kolderup, Eley Associates, Inc. Advanced VAV System Design will modify their rating system for tubular daylighting devices; and 2) U-factor results will affect how NFRC) E3 10/03 Advanced VAV System Design Guideline (Eley) E4 5/03 Integrated Design of Small Commercial

334

Comparative guide to emerging diagnostic tools for large commercial HVAC systems  

E-Print Network (OSTI)

speed-corrected fan metrics for measured and design data tospeed- corrected fan metrics for measured and design data tocfm), and fan efficiency ratio (measured efficiency/design

Friedman, Hannah; Piette, Mary Ann

2001-01-01T23:59:59.000Z

335

Avoiding low frequency noise in packaged HVAC equipment  

Science Conference Proceedings (OSTI)

The purpose of this article is to help those involved in the design and commissioning of packaged HVAC systems to understand the root causes of low frequency noise problems and how to avoid many of them at the design stage. In the 1980's, two things happened to dramatically change the types of noise problems encountered in typical new construction. The first was the introduction of new energy regulations that favored variable air volume (VAV) distribution systems over constant volume air distribution systems. A by-product of VAV design is that mid- and high frequency sound pressure levels produced by current air terminal devices and diffusers in many applications are significantly lower than in the past. The second factor was a trend away from the use of built-up central station fan equipment in favor of packaged, floor-by-floor air handlers or rooftop units. As a result, today's HVAC system noise problems are not confined to just the roar and hiss of the past, but now include intense low frequency rumble and time modulation. Indeed, most current noise problems in modern buildings occur in the frequency range well below 250 Hz. A large fraction of these are a result of the dominant sound pressure levels in the 12 to 40 Hz region. These factors, combined with a substantial increase in the level of low frequency sound from the rest of the system, can produce a non-neutral, time modulated, rumbly sounding background noise that many people find objectionable.

Ebbing, C.E. (Carrier Corp., Syracuse, NY (United States). Commercial Unitary Division); Blazier, W.E.Jr. (Warren Blazier Associates, San Francisco, CA (United States))

1993-06-01T23:59:59.000Z

336

Building Energy Software Tools Directory: HAP  

NLE Websites -- All DOE Office Websites (Extended Search)

HAP HAP HAP logo. A versatile system design tool and an energy simulation tool in one package, Carrier�s Hourly Analysis Program (HAP) provides the ease of use of a Windows-based graphical user interface and the computing power of modern 32-bit software. HAP�s design module uses a system-based approach to HVAC load estimating. This approach tailors sizing procedures and results to the specific type of system being considered. Central AHUs, packaged rooftop units, split systems, fan coils, water source heat pumps and PTACs can easily be sized, as can CAV, VAV and multiple-zone systems. Calculation rigor and integrity are provided by the ASHRAE Transfer Function Method for calculating building heat flow. HAP�s energy analysis module performs an hour-by-hour simulation of

337

Reserve growth through geological characterization of heterogeneous reservoirs - an example from mud-rich submarine fan reservoirs of Permian Spraberry Trend, west Texas  

SciTech Connect

Tight, naturally fractured Permian submarine fan reservoirs in the Midland basin contained more than 10.5 billion bbl of oil at discovery. Ultimate recovery is estimated to average 7% of the original oil in place. At abandonment 4 billion bbl of nonresidual mobile oil will remain in untapped or poorly drained reservoir compartments. This unproduced mobile oil is the target for Spraberry reserve growth through strategic infill drilling. Mid-fan facies of three separate submarine fans are productive in the Shackelford and Preston waterflood units (SPWU) in the central Spraberry Trend. Braided to meandering paleodip-oriented channels are flanked by levees which grade into upward-coarsening, unconfined distal fan sediment. Facies boundaries compartmentalize the reservoir, providing for interwell, stratigraphic entrapment of oil. Field-wide heterogeneity is pronounced. Stacking of channels in the upper Spraberry in the eastern half of the SPWU results in a dip-oriented belt of better reservoir quality. Wells completed in this axis have produced two to six times the amount of oil produced from wells located off of the depo-axis. Although fractures are important in early production, the contribution of matrix porosity is critical throughout the life of the reservoir. Current economics dictate that reserve growth might best be attained by siting new strategic infill wells in depositional axes and by selective recompletions of existing wells in areas of poorer reservoir quality for bypassed oil in undrained reservoir compartments.

Tyler, N.; Gholston, J.C.

1987-05-01T23:59:59.000Z

338

Structure function of the nucleus in the perturbative QCD with $N_c\\to\\infty$ (BFKL pomeron fan diagrams)  

E-Print Network (OSTI)

Equation for the sum of BFKL pomeron fan diagrams is rederived by direct summation and solved numerically for rapidities $y\\leq 50$. At high rapidities y>20 the resulting cross-sections for the scattering of a longitudinally polarized $q\\bar q$ pair on the nucleus cease to depend on its transverse dimension and tend to a constant limit 0.1768 $R_A^2$, which corresponds to scattering of a colour dipole on a black disk. Thus the unitarity is restored and the singularity in the j plane is reduced to a simple pole at j=1.The nuclear structure function at small x behaves as $Q^2\\ln(1/x)$. The found gluon density has a soliton-like form in the $\\log k$ space: its form is close to Gaussian, independent of rapidity, the centermoving towards higher $\\log k$ with a nearly constant velocity as rapidity increases.

M. A. Braun

2000-01-26T23:59:59.000Z

339

Review of Literature on Terminal Box Control, Occupancy Sensing Technology and Multi-zone Demand Control Ventilation (DCV)  

Science Conference Proceedings (OSTI)

This report presents an overall review of the standard requirement, the terminal box control, occupancy sensing technology and DCV. There is system-specific guidance for single-zone systems, but DCV application guidance for multi-zone variable air volume (VAV) systems is not available. No real-world implementation case studies have been found using the CO2-based DCV. The review results also show that the constant minimum air flow set point causes excessive fan power consumption and potential simultaneous heating and cooling. Occupancy-based control (OBC) is needed for the terminal box in order to achieve deep energy savings. Key to OBC is a technology for sensing the actual occupancy of the zone served in real time. Several technologies show promise, but none currently fully meets the need with adequate accuracy and sufficiently low cost.

Liu, Guopeng; Dasu, Aravind R.; Zhang, Jian

2012-03-01T23:59:59.000Z

340

INTERACTION OF A SOLAR SPACE HEATING SYSTEM WITH THE THERMAL BEHAVIOR OF A BUILDING  

E-Print Network (OSTI)

Pant Rfict Fan coil heat exchanger effectiveness. c min Fanis modeled as a fan-coil heat exchanger. The fan coil outputsystem with a fan-coil heat exchanger sized for a solar

Vilmer, Christian

2013-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


341

Autonomous grain combine control system  

DOE Patents (OSTI)

A system for controlling a grain combine having a rotor/cylinder, a sieve, a fan, a concave, a feeder, a header, an engine, and a control system. The feeder of the grain combine is engaged and the header is lowered. A separator loss target, engine load target, and a sieve loss target are selected. Grain is harvested with the lowered header passing the grain through the engaged feeder. Separator loss, sieve loss, engine load and ground speed of the grain combine are continuously monitored during the harvesting. If the monitored separator loss exceeds the selected separator loss target, the speed of the rotor/cylinder, the concave setting, the engine load target, or a combination thereof is adjusted. If the monitored sieve loss exceeds the selected sieve loss target, the speed of the fan, the size of the sieve openings, or the engine load target is adjusted.

Hoskinson, Reed L.; Kenney, Kevin L.; Lucas, James R.; Prickel, Marvin A.

2013-06-25T23:59:59.000Z

342

Building Energy Software Tools Directory: DUCTSIZE  

NLE Websites -- All DOE Office Websites (Extended Search)

DUCTSIZE DUCTSIZE DUCTSIZE logo. Quickly calculates optimal duct sizes using either the static regain, equal friction, or constant velocity method. Data entry can be accomplished manually or taken graphically from either Drawing Board or AutoCAD.� Duct sizes can be calculated on a round, rectangular, and flat oval basis. Noise levels and required attenuation are printed for each runout duct. A library of fan data for noise calculations is built into the program.� DUCTSIZE allows an unlimited number of duct sections, and is suitable for both constant volume and VAV systems as diversity is accounted for.�� DUCTSIZE also has an option for specifying duct height and width constraints to control sizes. This feature is also useful for analyzing problems in existing systems where the duct sizes are already specified.�

343

Petrology, geochronology and provenance of the Laingsburg and Tanqua Karoo submarine fan systems, Ecca Group, South Africa.  

E-Print Network (OSTI)

??The integration of whole-rock chemistry, heavy mineral chemistry, detrital zircon morphology and age dating has enabled high-resolution characterization of the Permian Laingsburg and Tanqua submarine… (more)

Nguema Mve, Oliver Patrice

2005-01-01T23:59:59.000Z

344

Furnace Technology Systems Workshop Preliminary Schedule ...  

Science Conference Proceedings (OSTI)

Mar 3, 2013 ... and emissions. 9:40 – 10:25. Robinson Fans Inc. Deanna Weaver. Blowers/ Exhausters. This presentation will cover the basics of fan design.

345

TF30 third-stage composite fan blade service program. Final technical report 1 Jul 1970--31 Dec 1977. [BORSIC/aluminum  

SciTech Connect

The successful application of advanced composites as the structural material for aircraft jet engine rotating parts will significantly reduce engine weight and improve engine performance characteristics. To solve the component design, manufacturing, and quality assurance problems associated with such an application, a program was conducted to design and develop BORSIC/Aluminum third-stage fan blades, which would operate satisfactorily in the TF30-P-7 or P-9 engine models. Program objectives successfully were to improve the existing design of a composite material fan blade, manufacture the blade, and demonstrate its quality by bench and engine environment testing. The scope of the program required to meet these objectives included establishing design and fabrication procedures, developing special tooling, evaluating current nondestructive inspection techniques and adapting these techniques to composite materials, establishing quality assurance criteria, and developing comprehensive bench and engine environment test programs to adequately demonstrate fan-blade quality. During the program, several sets of BORSIC/Aluminum blades weighing 40 percent less than comparable TF30 bill of material titanium blades were successfully produced and tested. On the basis of extensive test program, and with the establishment of quality control criteria and repair procedures, the blades were deemed acceptable for evaluation in a flight program. During the total program, 246 engine-configuration blades were manufactured and non-destructively inspected; with an overall acceptance rate of 92.3%.

Randall, D.G.

1978-05-15T23:59:59.000Z

346

Modeling and Measurement Constraints in Fault Diagnostics for HVAC Systems Massieh Najafi1  

E-Print Network (OSTI)

Modeling and Measurement Constraints in Fault Diagnostics for HVAC Systems Massieh Najafi1 , David for determining HVAC diagnostics, methods to detect faults in HVAC systems are still generally undeveloped. Most in a substantial increase in energy use. For example, failure of an HVAC fan may prevent cool air from one

347

SOLERAS program. Engineering field test of a solar cooling system. Final report  

Science Conference Proceedings (OSTI)

A solar-powered air conditioning system was designed, constructed, and installed at a Phoenix, Arizona site whose climatic conditions approximate those of Saudi Arabia. The nominal 18 ton capacity Rankine cycle chiller system with hot and cold storage and conventional fan/coil delivery units was operated for two cooling seasons and met its design objectives.

Not Available

1983-05-01T23:59:59.000Z

348

Human portable preconcentrator system  

DOE Patents (OSTI)

A preconcentrator system and apparatus suited to human portable use wherein sample potentially containing a target chemical substance is drawn into a chamber and through a pervious screen. The screen is adapted to capture target chemicals and then, upon heating, to release those chemicals into the chamber. Chemicals captured and then released in this fashion are then carried to a portable chemical detection device such as a portable ion mobility spectrometer. In the preferred embodiment, the means for drawing sample into the chamber comprises a reversible fan which, when operated in reverse direction, creates a backpressure that facilitates evolution of captured target chemicals into the chamber when the screen is heated.

Linker, Kevin L. (Albuquerque, NM); Bouchier, Francis A. (Albuquerque, NM); Hannum, David W. (Albuquerque, NM); Rhykerd, Jr., Charles L. (Albuquerque, NM)

2003-01-01T23:59:59.000Z

349

Energy Efficiency Building Code for Commercial Buildings in Sri Lanka  

E-Print Network (OSTI)

Fan System Designfor specified areas. 3.3 Fan System Design Criteria 3.3.1for the combined fan system at design conditions. 3.3.4

2000-01-01T23:59:59.000Z

350

Commercial thermal distribution systems, Final report for CIEE/CEC  

E-Print Network (OSTI)

Implications Specify actual fan design kW/CFM if desired. Ifconstant flow rate fan design power part-load-ratiorelevant than the original fan design data. Similarly, if

Xu, T.

2011-01-01T23:59:59.000Z

351

Improving Steam System Performance: A Sourcebook for Industry, Second Edition (Book) (Revised)  

Science Conference Proceedings (OSTI)

Improving Steam System Performance: A Sourcebook for Industry was developed for the U.S. Department of Energy's (DOE) Advanced Manufacturing Office (AMO), formerly the Industrial Technologies Program. AMO undertook this project as a series of sourcebook publications. Other topics in this series include: compressed air systems, pumping systems, fan systems, process heating and motor and drive systems. For more information about program resources, see AMO in the Where to Find Help section of this publication.

Not Available

2012-10-01T23:59:59.000Z

352

Eddy current transducing system  

SciTech Connect

In a program funded by the Office of Energy Related Inventions of the Department of Energy, Vatell Corporation developed a prototype Turbine Blade Condition Monitor. This microcomputer-based system was tested to determine its performance in measuring individual blade clearance and time of arrival on a Pratt Whitney (Canada) JT15D jet engine. A Vatell eddy-current sensor mounted in the housing of the engine at mid-chord of the N1 first stage provided the signals. The N1 first stage is a 31 in. diameter fan with 28 titanium blades, operating over a speed range of approximately 7000 to 14,000 rpm. Tests showed that the monitoring system transduced blade clearances with a precision of .0001 in., simultaneously indicating times of arrival within 0.1 microseconds, equivalent to a pitch of .0015 in. Patterns of blade clearances and timing variations were observed for various engine operating conditions, and the clearance and time of arrival signatures'' of the fan stage were recorded. Manufacturing variations in blade pitch were readily detected, as were indications of blade and hub vibration. The report contains a detailed description of the development program, examples of waveforms and recorded data, circuit diagrams, software, setup and operating procedures for the monitoring system. 66 refs.

1991-09-13T23:59:59.000Z

353

INTERACTION OF A SOLAR SPACE HEATING SYSTEM WITH THE THERMAL BEHAVIOR OF A BUILDING  

E-Print Network (OSTI)

and Duffie [17], the fan give 185 % of the design heat loadfan coil heating system sized at 130 % of design load tofan coil output power of 32 kW (110 kBtu/hr), or about three times the design

Vilmer, Christian

2013-01-01T23:59:59.000Z

354

Performance of thermal distribution systems in large commercial buildings  

E-Print Network (OSTI)

sizing and design, e.g. , excessive fan-power requirement,fan-power and energy savings could be realized by better design

Xu, T.

2011-01-01T23:59:59.000Z

355

FANS - Sample Change  

Science Conference Proceedings (OSTI)

... result of neutrons with incident energies higher than ... between the sample position and the detector bank. ... 60 to 300 seconds per energy point and ...

356

FANS - Changing Monochromators  

Science Conference Proceedings (OSTI)

... designed to maintain high neutron intensity for all incident energies: Copper [Cu ... Thus if one observes strong peaks at high energy transfer, these ...

357

Nien-fan Zhang  

Science Conference Proceedings (OSTI)

... for Autocorrelated Data Advances in Statistics ... Section of Bayesian Statistical Science of American ... Journal of Statistical Computation and Simulation ...

2010-10-04T23:59:59.000Z

358

FANS - Sample Change  

Science Conference Proceedings (OSTI)

... This is achieved by placing a cadmium shield between the sample position and the detector bank. In order to place the ...

359

Fuel processor for fuel cell power system  

DOE Patents (OSTI)

A catalytic organic fuel processing apparatus, which can be used in a fuel cell power system, contains within a housing a catalyst chamber, a variable speed fan, and a combustion chamber. Vaporized organic fuel is circulated by the fan past the combustion chamber with which it is in indirect heat exchange relationship. The heated vaporized organic fuel enters a catalyst bed where it is converted into a desired product such as hydrogen needed to power the fuel cell. During periods of high demand, air is injected upstream of the combustion chamber and organic fuel injection means to burn with some of the organic fuel on the outside of the combustion chamber, and thus be in direct heat exchange relation with the organic fuel going into the catalyst bed.

Vanderborgh, Nicholas E. (Los Alamos, NM); Springer, Thomas E. (Los Alamos, NM); Huff, James R. (Los Alamos, NM)

1987-01-01T23:59:59.000Z

360

Advancement of Electrochromic Windows  

E-Print Network (OSTI)

Research Energy Systems Integration Advancement ofintegration issues related to using EC windows within a whole building energy efficient systemenergy- savings benefit with EC-daylighting-HVAC integration (assuming a conventional VAV system

2006-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


361

Variable temperature seat climate control system  

DOE Patents (OSTI)

A temperature climate control system comprises a variable temperature seat, at least one heat pump, at least one heat pump temperature sensor, and a controller. Each heat pump comprises a number of Peltier thermoelectric modules for temperature conditioning the air in a main heat exchanger and a main exchanger fan for passing the conditioned air from the main exchanger to the variable temperature seat. The Peltier modules and each main fan may be manually adjusted via a control switch or a control signal. Additionally, the temperature climate control system may comprise a number of additional temperature sensors to monitor the temperature of the ambient air surrounding the occupant as well as the temperature of the conditioned air directed to the occupant. The controller is configured to automatically regulate the operation of the Peltier modules and/or each main fan according to a temperature climate control logic designed both to maximize occupant comfort during normal operation, and minimize possible equipment damage, occupant discomfort, or occupant injury in the event of a heat pump malfunction.

Karunasiri, Tissa R. (Van Nuys, CA); Gallup, David F. (Pasadena, CA); Noles, David R. (Glendale, CA); Gregory, Christian T. (Alhambra, CA)

1997-05-06T23:59:59.000Z

362

A Comparative Study for the Air Distribution System of a Cleanroom with  

NLE Websites -- All DOE Office Websites (Extended Search)

A Comparative Study for the Air Distribution System of a Cleanroom with A Comparative Study for the Air Distribution System of a Cleanroom with High Cooling Load and Airborne Molecular Sources Speaker(s): Shih-Cheng Hu Date: June 20, 2008 - 12:00pm Location: 90-3122 Seminar Host/Point of Contact: Tim Xu With rapid change of production line in Taiwan IT Industries; increased productivity/flexibility in the same cleanroom space is required urgently. We have systematically compared two cleanroom ventilation systems i.e. conventional and ceiling return system. The wall return system has fixed location of Fan filter unit (FFU), return air shaft/wall and dry coiling coil. The ceiling return system with a specially designed Fan Filter Dry Coil Unit (FFDCU) installed just above a production tool with high heat/particle sources. For a wall return system, reduced flexibility and

363

How the Number and Placement of Sensors Controlling Room Air Distribution Systems Affect Energy Use and Comfort  

E-Print Network (OSTI)

This study assesses the impact of sensor number and placement on the energy needed to condition a typical office using several likely variants of an underfloor air distribution system (UFAD). The study uses an empirical-based room stratification model developed from full-scale tests of UFAD systems. Annual energy consumption is calculated for an interior zone using outside air temperature bin data. The comfort criteria are taken from ASHRAE standard 55-92. The simulations indicate that there are benefits derived from using more than one temperature sensor to control conditions in the occupied zone of a room. Among these are: 1. By adjusting both supply air temperature and volume to maintain the maximum allowable thermal gradient in the occupied (lower) part of the room, an optimal supply air condition can reduce energy use (relative to the best arrangement of a single sensor) while maintaining comfort; 2. Discomfort caused by stratification can be detected by having one of the sensors located at foot level; 3. For the simulated UFAD interior zone of a typical office building in Sacramento, an overall energy saving of 8%/24% (VAV/CAV respectively) can be achieved when two sensors as opposed to one are used to control room conditions.

Wang, D.; Arens, E.; Webster, T.; Shi, M.

2002-01-01T23:59:59.000Z

364

Single-Duct Constant Air Volume System Supply Air Temperature Reset: Using Return Air Temperature or Outside Air Temperature?  

E-Print Network (OSTI)

The supply air temperature set point for a singleduct constant air volume air handling unit (AHU) system is often reset based on either return air temperature or outside air temperature in order to reduce simultaneous cooling and heating energy consumption. Both reset strategies make engineering sense as long as the reset schedules are reasonable. Quite often the decision to use one over the other is made with the assumption that they will all achieve some sorts of energy savings. However, the impact of these two strategies on AHU energy consumption could be very different. A comparison of these two commonly used supply air temperature reset strategies for a single-duct constant air volume system is presented in this paper. It is shown that from either the building energy consumption or building comfort point of view, the reset strategy based on outside air temperature is inherently better than that based on return air temperature. Significant amount of heating energy savings can be achieved by switching from return air temperature based reset to outside air temperature based reset. The reset strategy can also benefit variable air volume (VAV) AHUs. An improved supply air temperature set point reset control strategy is proposed by combining and staging the outside air and return air temperature based resets.

Wei, G.; Turner, W. D.; Claridge, D.; Liu, M.

2002-01-01T23:59:59.000Z

365

Interaction of a solar space heating system with the thermal behavior of a building  

DOE Green Energy (OSTI)

The thermal behavior of a building in response to heat input from an active solar space heating system is analyzed to determine the effect of the variable storage tank temperature on the cycling rate, on-time, and off-time of a heating cycle and on the comfort characteristics of room air temperature swing and of offset of the average air temperature from the setpoint (droop). A simple model of a residential building, a fan coil heat-delivery system, and a bimetal thermostat are used to describe the system. A computer simulation of the system behavior has been developed and verified by comparisons with predictions from previous studies. The system model and simulation are then applied to determine the building response to a typical hydronic solar heating system for different solar storage temperatures, outdoor temperatures, and fan coil sizes. The simulations were run only for those cases where there was sufficient energy from storage to meet the building load requirements.

Vilmer, C.; Warren, M.L.; Auslander, D.

1980-12-01T23:59:59.000Z

366

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions  

E-Print Network (OSTI)

Air static pressure must be maintained at a certain level leaving the air-handing unit (AHU) to force a suitable amount of air through the terminal boxes. However, an excessive static pressure level is often used due to ( 1 ) lack of a control device in a constant volume system (CV); (2) malfunctioning control device in a variable volume (VAV) system; and (3) fear of failure to maintain room temperature. High static pressure often develops excessive damper leakage in older mixing boxes. This results in an inappropriate mixing of hot and cold air and an excessive amount of air entering the space. Consequently, the actual fan power, heating and cooling energy consumption all become significantly higher than the design values. Even worse, the system may not be able to maintain room conditions due to unwanted simultaneous heating and cooling, and may be noisy due to the excessive static pressure. This paper proposes to control the hot duct pressure and the Variable Frequency Drives ( VFD's) to control the fan static i.e. the cold duct pressure. Both a theoretical analysis and a case study results are presented in this paper.

Liu, M.; Zhu, Y.; Claridge, D. E.; White, E.

1996-01-01T23:59:59.000Z

367

High-tech buildings - Market transformation project  

E-Print Network (OSTI)

systems’ design use different concepts for the fans and thesystem design utilizes multiple small fans to push airin older fan-filter units, and inefficient design and layout

Applications Team

2001-01-01T23:59:59.000Z

368

2.1E Supplement  

E-Print Network (OSTI)

load EFRAC Fraction of design fan energy at current airflowby the central system supply fan at design flow. It will beand exhaust fan electrical consumption at design conditions.

Winkelmann, F.C.

2010-01-01T23:59:59.000Z

369

Application of Target Value Design to Energy Efficiency Investments  

E-Print Network (OSTI)

the original basis of design, fan wall system, withoutreflect the single fan vane axial design for the aira unique AHU design using a ‘vane axial fan. ’ Following a

Lee, Hyun Woo

2012-01-01T23:59:59.000Z

370

Summary and early findings from a second generation information monitoring and diagnostic system  

E-Print Network (OSTI)

Chillers Two-cells Cooling Towers 17 AHUs, 20 Hp Supply Fan,condition for the cooling tower fans. Figure D. Condenserdown the chiller and cooling tower fans ran intermittently.

Piette, Mary Ann; Kinney, Satkartar; Bourassa, Norman; Kinney, Kristopher L.; Shockman, Christine

2003-01-01T23:59:59.000Z

371

Computer program for conducting acoustical analyses of HVAC systems.  

Science Conference Proceedings (OSTI)

An interactive Windows?based computer program has been developed that can be used to conduct complete acoustical analyses of HVAC systems. The program can be used to track sound from a HVACsound source such as a fan to a room. Both sound from a single path between a sound source and room or from multiple paths between a sound source and room can be investigated. The program has a full set of editing features that include change

Douglas D. Reynolds; Scott C. Mitchell

1996-01-01T23:59:59.000Z

372

A Study of the Advanced Systems at the CMU Intelligent Workplace with an Evaluation of Potential Applications to Texas A&M International University  

E-Print Network (OSTI)

A detailed study has been conducted of the performance of several innovative aspects of the Intelligent Workplace (IW) at Carnegie Mellon University, a low energy consumption building that uses radiant heating, cooling and a desiccant ventilation unit. The following aspects have been studied in detail: the heat transfer process of radiant mullions and overhead radiant panels, the impact of the radiator position on heating load and thermal comfort, the influence of infiltration on indoor humidity in a radiantly cooled office with a solid desiccant ventilation unit, and an energy consumption comparison of the sensible heating and cooling systems with a single duct VAV system. Transferability of the advanced building technologies that are being studied at the IW was investigated by examining them to see if they could be applied in an advanced technology test bed at Texas A&M International University (TAMIU) in Laredo, Texas. Additionally, a sustainability assessment for the current TAMIU campus was performed with an analysis of the potential for TAMIU to obtain LEED certification from the US Green Building Council. This report summarizes the conclusions and observations of these studies.

Claridge, D. E.; Gong, X.; Verdict, M.; Clingenpeel, K.

2008-04-01T23:59:59.000Z

373

Systems  

E-Print Network (OSTI)

Abstract Developing usable and robust mixed reality systems requires unique human–computer interaction techniques and customized hardware systems. The design of the hardware is directed by the requirements of the rich 3D interactions that can be performed using immersive mobile MR systems. Geometry modeling and capture, navigational annotations, visualizations, and training simulations are all enhanced using augmented computer graphics. We present the design guidelines that have led us through 10 years of evolving mobile outdoor MR hardware systems.

Benjamin Avery; Ross T. Smith; Wayne Piekarski; Bruce H. Thomas

2009-01-01T23:59:59.000Z

374

Best Practices for Energy Efficient Cleanrooms Efficient HVAC Systems: Variable-Speed-Drive Chillers  

E-Print Network (OSTI)

Right sizing ? Cooling tower and condenser optimization ?chillers, water pumps, and cooling tower or condenser fans.MUAH + RCU Fans Pumps Cooling Towers Figure 1. Benchmarked

Xu, Tengfang

2005-01-01T23:59:59.000Z

375

Supporting Concurrent Task Deployment Wireless Sensor Networks* S. Guo, C. Fan, and T.D.C. Little  

E-Print Network (OSTI)

-specialist and for it to subsequently discover and associate with its corresponding HVAC control loop. We claim that this involves are required or when the mission of the system changes. We consider a technique that is intended to support multiple concurrent missions by the system by exploiting available resources of the sensor network

Little, Thomas

376

Establishment of an Environmental Control Technology Laboratory with a Circulating Fluidized-Bed Combustion System  

DOE Green Energy (OSTI)

This report is to present the progress made on the project entitled ''Establishment of an Environmental Control Technology Laboratory (ECTL) with a Circulating Fluidized-Bed Combustion (CFBC) System'' during the period January 1, 2007 through March 31, 2007. The effort in this quarter has concentrated on installing the CFBC Facility and for conducting cold fluidization operations tests in the CFBC facility. The assembly of the ash recirculation pipe duct from the cyclones back to the bed area of the combustor, including the upper and lower loop seals was completed. The electric bed pre-heater was installed to heat the fluidizing air as it enters the wind box. The induced draft fan along with its machine base and power supply was received and installed. The flue gas duct from secondary cyclone outlet to induced draft fan inlet was received and installed, as well as the induced fan flue gas discharge duct. Pressure testing from the forced draft fan to the outlet of the induced fan was completed. In related research a pilot-scale halogen addition test was conducted in the empty slipstream reactor (without (Selective Catalytic Reduction) SCR catalyst loading) and the SCR slipstream reactor with two commercial SCR catalysts. The greatest benefits of conducting slipstream tests can be flexible control and isolation of specific factors. This facility is currently used in full-scale utility and will be combined into 0.6MW CFBC in the future. This work attempts to first investigate performance of the SCR catalyst in the flue gas atmosphere when burning Powder River Basin (PRB), including the impact of PRB coal flue gas composition on the reduction of nitrogen oxides (NOx) and the oxidation of elemental mercury (Hg(0)) under SCR conditions. Secondly, the impacts of hydrogen halogens (Hydrogen fluoride (HF), Hydrogen chloride (HCl), Hydrogen Bromide (HBr) and Hydrogen Iodine (HI)) on Hg(0) oxidation and their mechanisms can be explored.

Wei-Ping Pan; Yan Cao; John Smith

2007-03-31T23:59:59.000Z

377

Residential Dehumidification Systems Research for Hot-Humid Climates: September 1, 2001 -- December 30, 2003  

SciTech Connect

Twenty homes were tested and monitored in the hot-humid climate of Houston, Texas, U.S.A., to evaluate the humidity control performance and operating cost of six different integrated dehumidification and ventilation systems that could be applied by production homebuilders. Temperature and relative humidity were monitored at four living-space locations and in the conditioned attic where the space-conditioning equipment and air-distribution ducts were located. Equipment operational time was monitored for heating, cooling, dehumidification, and ventilation. Results showed that energy efficiency measures, combined with controlled mechanical ventilation, change the sensible and latent cooling load fractions such that dehumidification separate from the cooling system is required to maintain indoor relative humidity below 60% throughout the year. The system providing the best overall value, including humidity control, first cost, and operating cost, involved a standard dehumidifier located in a hall closet with a louvered door and central-fan-integrated supply ventilation with fan cycling.

Rudd, A. F.; Lstiburek, J. W.; Eng, P.; Ueno, K.

2005-02-01T23:59:59.000Z

378

Hydronic Radiant Cooling Systems  

NLE Websites -- All DOE Office Websites (Extended Search)

4 4 Hydronic Radiant Cooling Systems Cooling nonresidential buildings in the U.S. contributes significantly to electrical power consumption and peak power demand. Part of the electrical energy used to cool buildings is drawn by fans transporting cool air through the ducts. The typical thermal cooling peak load component for California office buildings can be divided as follows: 31% for lighting, 13% for people, 14% for air transport, and 6% for equipment (in the graph below, these account for 62.5% of the electrical peak load, labeled "chiller"). Approximately 37% of the electrical peak power is required for air transport, and the remainder is necessary to operate the compressor. DOE-2 simulations for different California climates using the California

379

Hydronic rooftop cooling systems  

DOE Patents (OSTI)

A roof top cooling unit has an evaporative cooling section that includes at least one evaporative module that pre-cools ventilation air and water; a condenser; a water reservoir and pump that captures and re-circulates water within the evaporative modules; a fan that exhausts air from the building and the evaporative modules and systems that refill and drain the water reservoir. The cooling unit also has a refrigerant section that includes a compressor, an expansion device, evaporator and condenser heat exchangers, and connecting refrigerant piping. Supply air components include a blower, an air filter, a cooling and/or heating coil to condition air for supply to the building, and optional dampers that, in designs that supply less than 100% outdoor air to the building, control the mixture of return and ventilation air.

Bourne, Richard C. (Davis, CA); Lee, Brian Eric (Monterey, CA); Berman, Mark J. (Davis, CA)

2008-01-29T23:59:59.000Z

380

Economic recovery of oil trapped at fan margins using high angle wells and multiple hydraulic fractures. Quarterly report, July 1--September 30, 1997  

SciTech Connect

This project attempts to demonstrate the effectiveness of exploiting thin-layered, low-energy deposits at the distal margin of a prograding turbidite complex through the use of hydraulically fractured horizontal or high-angle wells. The combination of a horizontal or high-angle well and hydraulic fracturing will allow greater pay exposure than can be achieved with conventional vertical wells while maintaining vertical communication between thin interbedded layers and the wellbore. A high-angle well will be drilled in the fan-margin portion of a slope-basin clastic reservoir and will be completed with multiple hydraulic-fracture treatments. Geologic modeling, reservoir characterization, and fine-grid reservoir simulation will be used to select the well location and orientation. Design parameters for the hydraulic-fracture treatments will be determined, in part, by fracturing an existing test well. Fracture azimuth will be predicted by passive seismic monitoring of a fracture-stimulation treatment in the test well using logging tools in an offset well. The long radius, near horizontal well has been drilled. After pumping a remedial cement squeeze, all pay behind the 5 in. liner was perforated and stimulated. Once wellwork is complete for the existing perforations, a hydraulic fracture treatment will be pumped through a short interval of clustered perforations in the 7 in. liner. Following this frac, all pay behind the 7 in. liner will be perforated and completion operations will be final.

Laue, M.L.

1997-10-30T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


381

Microcomputer-based monitoring and control system with uranium mining application. Information circular  

SciTech Connect

The Bureau of Mines investigated a microprocessor-based real-time control and monitoring system for uranium mining applications. The system is capable of controlling and monitoring up to 768 stations within 3 km of the central processor on a common four-wire cable. It can be used in conjunction with detectors to continuously monitor and display radiation working levels at points throughout the mine. Surface alarms are sounded for critical situations such as rapid radiation buildup, loss of power to monitors or fans, and changes in air door position. Permanent records of all changes are automatically printed out with their time of occurrence. Printouts can also be obtained for shift reports or trend logs. The system can be used to remotely control fan startup and shutdown, and also can alert miners of underground conditions by blowing horns or turning on lights. Battery backup keeps the system operative for up to 4 h in case of a mine power outage. A special software feature permits automatic, time-delayed, sequential restart of fans.

Sheeran, C.T.; Franklin, J.C.

1984-01-01T23:59:59.000Z

382

SUBSURFACE VISUAL ALARM SYSTEM ANALYSIS  

SciTech Connect

The ''Subsurface Fire Hazard Analysis'' (CRWMS M&O 1998, page 61), and the document, ''Title III Evaluation Report for the Surface and Subsurface Communication System'', (CRWMS M&O 1999a, pages 21 and 23), both indicate the installed communication system is adequate to support Exploratory Studies Facility (ESF) activities with the exception of the mine phone system for emergency notification purposes. They recommend the installation of a visual alarm system to supplement the page/party phone system The purpose of this analysis is to identify data communication highway design approaches, and provide justification for the selected or recommended alternatives for the data communication of the subsurface visual alarm system. This analysis is being prepared to document a basis for the design selection of the data communication method. This analysis will briefly describe existing data or voice communication or monitoring systems within the ESF, and look at how these may be revised or adapted to support the needed data highway of the subsurface visual alarm. system. The existing PLC communication system installed in subsurface is providing data communication for alcove No.5 ventilation fans, south portal ventilation fans, bulkhead doors and generator monitoring system. It is given that the data communication of the subsurface visual alarm system will be a digital based system. It is also given that it is most feasible to take advantage of existing systems and equipment and not consider an entirely new data communication system design and installation. The scope and primary objectives of this analysis are to: (1) Briefly review and describe existing available data communication highways or systems within the ESF. (2) Examine technical characteristics of an existing system to disqualify a design alternative is paramount in minimizing the number of and depth of a system review. (3) Apply general engineering design practices or criteria such as relative cost, and degree of difficulty and complexity in determining requirements in adapting existing data communication highways to support the subsurface visual alarm system. These requirements would include such things as added or new communication cables, added Programmable Logic Controller (PLC), Inputs and Outputs (I/O), and communication hardware components, and human machine interfaces and their software operating system. (4) Select the best data communication highway system based on this review of adapting or integrating with existing data communication systems.

D.W. Markman

2001-08-06T23:59:59.000Z

383

Fuel processor for fuel cell power system. [Conversion of methanol into hydrogen  

DOE Patents (OSTI)

A catalytic organic fuel processing apparatus, which can be used in a fuel cell power system, contains within a housing a catalyst chamber, a variable speed fan, and a combustion chamber. Vaporized organic fuel is circulated by the fan past the combustion chamber with which it is in indirect heat exchange relationship. The heated vaporized organic fuel enters a catalyst bed where it is converted into a desired product such as hydrogen needed to power the fuel cell. During periods of high demand, air is injected upstream of the combustion chamber and organic fuel injection means to burn with some of the organic fuel on the outside of the combustion chamber, and thus be in direct heat exchange relation with the organic fuel going into the catalyst bed.

Vanderborgh, N.E.; Springer, T.E.; Huff, J.R.

1986-01-28T23:59:59.000Z

384

Descriptions and diagrams of the primary and annulus ventilation systems of the double-shell tank farms as of January 1988  

Science Conference Proceedings (OSTI)

This document is a compilation of information describing the ventilation systems of the Double-Shell Tank farms (214-AN, -AP, -AW, -AW, -AY, -AZ, and -SY). A general description of the primary tank and annulus ventilation systems is given along with specific information on the high efficiency particulate air (HEPA) filters, condensers, preheaters, exhaust fans, and piping. This information is considered to be current as of January 1988. 38 refs, 20 figs, 30 tabs.

Blackman, A.E.; Waters, E.D.

1994-12-28T23:59:59.000Z

385

Fermilab Tevatron high level rf accelerating systems  

SciTech Connect

Eight tuned rf cavities have been installed and operated in the F0 straight section of the Tevatron. Their mechanical placement along the beam line enables them to be operated for colliding beams as two independent groups of four cavities, group 1-4 accelerating antiprotons and group 5-8 accelerating protons. The only difference is that the spacing between cavities 4 and 5 was increased to stay clear of the F0 colliding point. The cavities can easily be rephased by switching cables in a low-level distribution system (fan-out) so that the full accelerating capability of all eight cavities can be used during fixed target operations. Likewise, the cables from capacitive probes on each cavity gap can be switched to proper lengths and summed in a fan-back system to give an rf signal representing the amplitude and phase as ''seen by the beam,'' separately for protons and antiprotons. Such signals have been used to phase lock the Tevatron to the Main Ring for synchronous transfer.

Kerns, Q.; Kerns, C.; Miller, H.; Tawser, S.; Reid, J.; Webber, R.; Wildman, D.

1985-06-01T23:59:59.000Z

386

Thermal distribution systems in commercial buildings  

NLE Websites -- All DOE Office Websites (Extended Search)

Thermal distribution systems in commercial buildings Thermal distribution systems in commercial buildings Title Thermal distribution systems in commercial buildings Publication Type Journal Article LBNL Report Number LBNL-51860 Year of Publication 2003 Authors Diamond, Richard C., Craig P. Wray, Darryl J. Dickerhoff, Nance Matson, and Duo Wang Start Page Chapter Abstract Previous research suggests that HVAC thermal distribution systems in commercial buildings suffer from thermal losses, such as those caused by duct air leakage and poor duct location. Due to a lack of metrics and data showing the potentially large energy savings from reducing these losses, the California building industry has mostly overlooked energy efficiency improvements in this area. The purpose of this project is to obtain the technical knowledge needed to properly measure and understand the energy efficiency of these systems. This project has three specific objectives: to develop metrics and diagnostics for determining system efficiencies, to develop design and retrofit information that the building industry can use to improve these systems, and to determine the energy impacts associated with duct leakage airflows in an existing large commercial building. The primary outcome of this project is the confirmation that duct leakage airflows can significantly impact energy use in large commercial buildings: our measurements indicate that adding 15% duct leakage at operating conditions leads to an increase in fan power of about 25 to 35%. This finding is consistent with impacts of increased duct leakage airflows on fan power that have been predicted by previous simulations. Other project outcomes include the definition of a new metric for distribution system efficiency, the demonstration of a reliable test for determining duct leakage airflows, and the development of new techniques for duct sealing. We expect that the project outcomes will lead to new requirements for commercial thermal distribution system efficiency in future revisions of California's Title 24.

387

Sensible and Latent Cooling Load Control Using Centrally-Ducted, Variable-Capacity Space Conditioning Systems in Low Sensible Load Environments  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Sensible and Latent Cooling Load Control Using Centrally-Ducted, Variable-Capacity Space Conditioning Systems in Low Sensible Load Environments James Cummings BA-PIRC; Florida Solar Energy Center Presented at BA Summer Meeting, July 26, 2012 The gist of my message * Fixed capacity AC systems generally provide good RH control in typical residences. * In low-load homes, they may be less effective in achieving good RH control. * On the other hand, variable capacity AC systems have several characteristics which can provide improved RH control in homes. - Both Nordyne and Carrier have variable capacity units, varying from about 40% to 100% of nominal full capacity. - What is variable capacity? -- condenser fan, compressor speed, and AHU fan speed. The gist, continued

388

Fan-beam Reconstruction Methods  

E-Print Network (OSTI)

In a previous paper a technique was developed for finding reconstruction algorithms for arbitrary ray-sampling schemes. The resulting algorithms use a general linear operator, the kernel of which depends on the details ...

Horn, Berthold K.P.

1977-11-01T23:59:59.000Z

389

Subsurface Ventilation System Description Document  

Science Conference Proceedings (OSTI)

The Subsurface Ventilation System supports the construction and operation of the subsurface repository by providing air for personnel and equipment and temperature control for the underground areas. Although the system is located underground, some equipment and features may be housed or located above ground. The system ventilates the underground by providing ambient air from the surface throughout the subsurface development and emplacement areas. The system provides fresh air for a safe work environment and supports potential retrieval operations by ventilating and cooling emplacement drifts. The system maintains compliance within the limits established for approved air quality standards. The system maintains separate ventilation between the development and waste emplacement areas. The system shall remove a portion of the heat generated by the waste packages during preclosure to support thermal goals. The system provides temperature control by reducing drift temperature to support potential retrieval operations. The ventilation system has the capability to ventilate selected drifts during emplacement and retrieval operations. The Subsurface Facility System is the main interface with the Subsurface Ventilation System. The location of the ducting, seals, filters, fans, emplacement doors, regulators, and electronic controls are within the envelope created by the Ground Control System in the Subsurface Facility System. The Subsurface Ventilation System also interfaces with the Subsurface Electrical System for power, the Monitored Geologic Repository Operations Monitoring and Control System to ensure proper and safe operation, the Safeguards and Security System for access to the emplacement drifts, the Subsurface Fire Protection System for fire safety, the Emplacement Drift System for repository performance, and the Backfill Emplacement and Subsurface Excavation Systems to support ventilation needs.

Eric Loros

2001-07-25T23:59:59.000Z

390

Subsurface Ventilation System Description Document  

Science Conference Proceedings (OSTI)

The Subsurface Ventilation System supports the construction and operation of the subsurface repository by providing air for personnel and equipment and temperature control for the underground areas. Although the system is located underground, some equipment and features may be housed or located above ground. The system ventilates the underground by providing ambient air from the surface throughout the subsurface development and emplacement areas. The system provides fresh air for a safe work environment and supports potential retrieval operations by ventilating and cooling emplacement drifts. The system maintains compliance within the limits established for approved air quality standards. The system maintains separate ventilation between the development and waste emplacement areas. The system shall remove a portion of the heat generated by the waste packages during preclosure to support thermal goals. The system provides temperature control by reducing drift temperature to support potential retrieval operations. The ventilation system has the capability to ventilate selected drifts during emplacement and retrieval operations. The Subsurface Facility System is the main interface with the Subsurface Ventilation System. The location of the ducting, seals, filters, fans, emplacement doors, regulators, and electronic controls are within the envelope created by the Ground Control System in the Subsurface Facility System. The Subsurface Ventilation System also interfaces with the Subsurface Electrical System for power, the Monitored Geologic Repository Operations Monitoring and Control System to ensure proper and safe operation, the Safeguards and Security System for access to the emplacement drifts, the Subsurface Fire Protection System for fire safety, the Emplacement Drift System for repository performance, and the Backfill Emplacement and Subsurface Excavation Systems to support ventilation needs.

NONE

2000-10-12T23:59:59.000Z

391

Furnace Systems Technology Workshop  

Science Conference Proceedings (OSTI)

TMS Networking and Online Tools, X ... TMS Social Network and Site Tools .... furnace technology, fundamentals of fans and blowers, reduction of melt loss, refractory ... Sutton - Harbison-Walker Refractories; Jon Gillespie - Gillespie & Powers ...

392

Cooling System Basics | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Cooling System Basics Cooling System Basics Cooling System Basics August 16, 2013 - 1:08pm Addthis Cooling technologies used in homes and buildings include ventilation, evaporative cooling, air conditioning, absorption cooling, and radiant cooling. Learn more about how these technologies work. Ventilation Ventilation allows air to move into and out of homes and buildings either by natural or mechanical means. Evaporative Cooling In dry climates, evaporative cooling or "swamp cooling" provides an experience like air conditioning, but with much lower energy use. An evaporative cooler uses the outside air's heat to evaporate water inside the cooler. The heat is drawn out of the air and the cooled air is blown into the space by the cooler's fan. Air Conditioning Air conditioners, which employ the same operating principles and basic

393

Simulation and Optimization of HVAC Systems  

E-Print Network (OSTI)

We developed a mathematical model of a simple Heating, Ventilation and Air Conditioning (HVAC) system and implemented the model using the VisSim simulation language. We used Fourier methods to approximate (and simplify) temperature and humidity data for the model. We created an objective function to be minimized which recorded the cost of running this HVAC system. We studied different methods for minimizing the cost function, including direct search methods using VisSim and completed preliminary studies of a Dynamic Programming programming approach to simplify the optimization problem. ii Contents 0 Executive Summary 1 1 Introduction 2 2 Evaluation of Simulation Packages 3 3 Simple Room Model for an HVAC System 5 3.1 Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 3.2 Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 3.3 Splitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 3.4 Mixer . . . ....

Ane Coughlin; George D. Ellington; Ellen Phifer; Brian Rieksts

1998-01-01T23:59:59.000Z

394

Cooling System Basics | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Cooling System Basics Cooling System Basics Cooling System Basics August 16, 2013 - 1:08pm Addthis Cooling technologies used in homes and buildings include ventilation, evaporative cooling, air conditioning, absorption cooling, and radiant cooling. Learn more about how these technologies work. Ventilation Ventilation allows air to move into and out of homes and buildings either by natural or mechanical means. Evaporative Cooling In dry climates, evaporative cooling or "swamp cooling" provides an experience like air conditioning, but with much lower energy use. An evaporative cooler uses the outside air's heat to evaporate water inside the cooler. The heat is drawn out of the air and the cooled air is blown into the space by the cooler's fan. Air Conditioning Air conditioners, which employ the same operating principles and basic

395

Valance heating/cooling system attains largest application in 1,000-room hotel  

SciTech Connect

Room temperatures in the 1,000 guest rooms of Chicago's Hyatt Regency Hotel are controlled by a valance heating and cooling system that functions by means of radiation and convection. The valances are mounted below the ceiling and consists of finned tubes and a drain tube contained within a wall-mounted enclosure. The finned tubes and drain are connected to a riser system, that is connected to a hot and cold water supply. The economics of the system is discussed and with no fans, motors, or blowers to run, energy is conserved. (MCW)

1976-08-01T23:59:59.000Z

396

Heat pump system  

DOE Patents (OSTI)

An air heating and cooling system for a building includes an expansion type refrigeration circuit and a vapor power circuit. The refrigeration circuit includes two heat exchangers, one of which is communicated with a source of indoor air from the building and the other of which is communicated with a source of air from outside the building. The vapor power circuit includes two heat exchangers, one of which is disposed in series air flow relationship with the indoor refrigeration circuit heat exchanger and the other of which is disposed in series air flow relationship with the outdoor refrigeration circuit heat exchanger. Fans powered by electricity generated by a vapor power circuit alternator circulate indoor air through the two indoor heat exchangers and circulate outside air through the two outdoor heat exchangers. The system is assembled as a single roof top unit, with a vapor power generator and turbine and compressor thermally insulated from the heat exchangers, and with the indoor heat exchangers thermally insulated from the outdoor heat exchangers.

Swenson, Paul F. (Shaker Heights, OH); Moore, Paul B. (Fedhaven, FL)

1983-01-01T23:59:59.000Z

397

Heat pump system  

DOE Patents (OSTI)

An air heating and cooling system for a building includes an expansion type refrigeration circuit and a vapor power circuit. The refrigeration circuit includes two heat exchangers, one of which is communicated with a source of indoor air from the building and the other of which is communicated with a source of air from outside the building. The vapor power circuit includes two heat exchangers, one of which is disposed in series air flow relationship with the indoor refrigeration circuit heat exchanger and the other of which is disposed in series air flow relationship with the outdoor refrigeration circuit heat exchanger. Fans powered by electricity generated by a vapor power circuit alternator circulate indoor air through the two indoor heat exchangers and circulate outside air through the two outdoor heat exchangers. The system is assembled as a single roof top unit, with a vapor power generator and turbine and compressor thermally insulated from the heat exchangers, and with the indoor heat exchangers thermally insulated from the outdoor heat exchangers.

Swenson, Paul F. (Cleveland, OH); Moore, Paul B. (Fedhaven, FL)

1977-01-01T23:59:59.000Z

398

Panasonic Ecology Systems formerly Matsushita Ecology Systems Co | Open  

Open Energy Info (EERE)

Panasonic Ecology Systems formerly Matsushita Ecology Systems Co Panasonic Ecology Systems formerly Matsushita Ecology Systems Co Jump to: navigation, search Name Panasonic Ecology Systems (formerly Matsushita Ecology Systems Co) Place Kasugai, Aichi, Japan Zip 468-8522 Sector Solar, Wind energy Product Japanese manufacturer of energy efficient residential and commercial electronic goods such as air conditioners, fans, and 'hybrid tower' which uses wind and solar power as street lights. Coordinates 35.277859°, 137.011215° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":35.277859,"lon":137.011215,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

399

Heavy Vehicle Essential Power Systems Workshop  

DOE Green Energy (OSTI)

Essential power is a crosscutting technology area that addresses the efficient and practical management of electrical and thermal requirements on trucks. Essential Power Systems: any function on the truck, that is not currently involved in moving the truck, and requires electrical or mechanical energy; Truck Lights; Hotel Loads (HVAC, computers, appliances, lighting, entertainment systems); Pumps, starter, compressor, fans, trailer refrigeration; Engine and fuel heating; and Operation of power lifts and pumps for bulk fluid transfer. Transition from ''belt and gear driven'' to auxiliary power generation of electricity - ''Truck Electrification'' 42 volts, DC and/ or AC; All electrically driven auxiliaries; Power on demand - manage electrical loads; Benefits include: increased fuel efficiency, reduced emission both when truck is idling and moving down the road.

Susan Rogers

2001-12-12T23:59:59.000Z

400

Heavy Vehicle Essential Power Systems Workshop  

SciTech Connect

Essential power is a crosscutting technology area that addresses the efficient and practical management of electrical and thermal requirements on trucks. Essential Power Systems: any function on the truck, that is not currently involved in moving the truck, and requires electrical or mechanical energy; Truck Lights; Hotel Loads (HVAC, computers, appliances, lighting, entertainment systems); Pumps, starter, compressor, fans, trailer refrigeration; Engine and fuel heating; and Operation of power lifts and pumps for bulk fluid transfer. Transition from ''belt and gear driven'' to auxiliary power generation of electricity - ''Truck Electrification'' 42 volts, DC and/ or AC; All electrically driven auxiliaries; Power on demand - manage electrical loads; Benefits include: increased fuel efficiency, reduced emission both when truck is idling and moving down the road.

Susan Rogers

2001-12-12T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


401

Energy Conservation in Process Chilled Water Systems  

E-Print Network (OSTI)

The energy consumption of the chiller and cooling tower in a process cooling application was analyzed using the TRNSYS computer code. The basic system included a constant speed centrifugal chiller and an induced-draft, counterflow cooling tower. Typical performance data was used to generate empirical models of the chiller and cooling tower. The cooling load profile was based on averaged electrical demand data for three plastic processing plants. The simulation was conducted using hourly Typical Meteorological Year weather data to determine the cooling tower operating conditions. Three alternative systems were modeled to predict the savings associated with the following energy conservation options: 1) variable speed drive chiller, 2) two-speed cooling tower fan, and 3) natural cycle cooling. The annual energy savings are presented as a function of cooling tower outlet temperature and average cooling load ratio.

Ambs, L. L.; DiBella, R. A.

1993-03-01T23:59:59.000Z

402

Effect of a Radiant Panel Cooling System on Indoor Air Quality of a Conditioned Space  

E-Print Network (OSTI)

This paper discusses the effect of a radiant cooling panel system on an indoor air quality (IAQ) of a conditioned space. In this study, ceiling radiant cooling panel, mechanical ventilation with fan coil unit (FCU) and 100% fresh air are used. Temperature sensors are located at different locations inside the conditioned space in order to sense dry bulb temperatures, relative humidity to compare it with standard ASHRAE comfort values. The present investigation indicates that the radiant cooling system not only improves the indoor air quality but also reduces the building energy consumption in the conditioned space.

Mohamed, E.; Abdalla, K. N.

2010-01-01T23:59:59.000Z

403

Labs21 Laboratory Modeling Guidelines using ASHRAE 90.1-1999  

E-Print Network (OSTI)

with fixed design airflow the operating fan horsepower islaboratory fan systems and promote more efficient designs.fan systems. Adjustments for components that are only in the proposed design,

2008-01-01T23:59:59.000Z

404

2.1E Sample Run Book  

E-Print Network (OSTI)

MAIN SUPPLY FAN (CFM ) SYSTEM DESIGN PARAMETERS ALTITUDEF) I.02 FAN KW 31- STORY OFFICE BLDG, CHICAGO DESIGN - LOAD2A SYST_ DESIGN PARAMETERS SYSTEm4 NAME SYSI SUPPLY FAN (CFM)

Winkelmann, F.C.

2010-01-01T23:59:59.000Z

405

TNKVNT: A model of the Tank 48 purge/ventilation exhaust system. Revision 1  

DOE Green Energy (OSTI)

The waste tank purge ventilation system for Tank 48 is designed to prevent dangerous concentrations of hydrogen or benzene from accumulating in the gas space of the tank. Fans pull the gas/water vapor mixture from the tank gas space and pass it sequentially through a demister, a condenser, a reheater, and HEPA filters before discharging to the environment. Proper operation of the HEPA filters requires that the gas mixture passing through them has a low relative humidity. The ventilation system has been modified by increasing the capacity of the fans and changing the condenser from a two-pass heat exchanger to a single-pass heat exchanger. It is important to understand the impact of these modifications on the operation of the system. A hydraulic model of the ventilation exhaust system has been developed. This model predicts the properties of the air throughout the system and the flowrate through the system, as functions of the tank gas space and environmental conditions. This document serves as a Software Design Report, a Software Coding report, and a User`s Manual. All of the information required for understanding and using this code is herein contained: the governing equations are fully developed, the numerical algorithms are described in detail, and an extensively commented code listing is included. This updated version of the code models the entire purge ventilation system, and is therefore more general in its potential applications.

Shadday, M.A. Jr.

1996-04-01T23:59:59.000Z

406

Performance Evaluation for Modular, Scalable Overhead Cooling Systems In Data Centers  

E-Print Network (OSTI)

Power Transformer Power Strip Current Figure 1. EquipmentCurrent Transformer Power Transformer Cold Aisle Fan unit (Power Meter Fan Total Relative Humidity Diff. Pressure Flow Rate Current Transformer

Xu, TengFang T.

2009-01-01T23:59:59.000Z

407

Early evaluation of a second generation information monitoring and diagnostic system  

E-Print Network (OSTI)

20 HP pumps Two-cells Cooling Towers Air Handlers Boiler 17overheat condition for the cooling tower fans. Figure 5.2.down the chiller and cooling tower fans ran intermittently.

2002-01-01T23:59:59.000Z

408

HVAC system analysis: energy audit review  

SciTech Connect

Although most energy audits do not investigate HVAC systems in as much detail as would most design consultants, audit data can be most informative. For certain types of buildings, air-conditioning energy usage can be estimated by its absence from energy bills during winter months, and heating energy usage can be estimated by its absence from energy bills during the summer months. Cooling and heating energy usage can be even more accurately broken down when a fossil fuel is used for heating while electrical energy is used for cooling. It is easy to establish fairly accurate energy consumption estimates for lighting, fan motors, and pumps; this can be done by verifying their loads and multiplying them by known operating hours. The numerous notes contained in some energy audits may also provide ideas for retrofitting energy-consuming areas.

Harmon, K.S.

1983-01-01T23:59:59.000Z

409

Commercial thermal distribution systems, Final report for CIEE/CEC  

Science Conference Proceedings (OSTI)

According to the California Energy Commission (CEC 1998a), California commercial buildings account for 35% of statewide electricity consumption, and 16% of statewide gas consumption. Space conditioning accounts for roughly 16,000 GWh of electricity and 800 million therms of natural gas annually, and the vast majority of this space conditioning energy passes through thermal distribution systems in these buildings. In addition, 8600 GWh per year is consumed by fans and pumps in commercial buildings, most of which is used to move the thermal energy through these systems. Research work at Lawrence Berkeley National Laboratory (LBNL) has been ongoing over the past five years to investigate the energy efficiency of these thermal distribution systems, and to explore possibilities for improving that energy efficiency. Based upon that work, annual savings estimates of 1 kWh/ft{sup 2} for light commercial buildings, and 1-2 kWh/ft{sup 2} in large commercial buildings have been developed for the particular aspects of thermal distribution system performance being addressed by this project. Those savings estimates, combined with a distribution of the building stock based upon an extensive stock characterization study (Modera et al. 1999a), and technical penetration estimates, translate into statewide saving potentials of 2000 GWh/year and 75 million thermal/year, as well as an electricity peak reduction potential of 0.7 GW. The overall goal of this research program is to provide new technology and application knowledge that will allow the design, construction, and energy services industries to reduce the energy waste associated with thermal distribution systems in California commercial buildings. The specific goals of the LBNL efforts over the past year were: (1) to advance the state of knowledge about system performance and energy losses in commercial-building thermal distribution systems; (2) to evaluate the potential of reducing thermal losses through duct sealing, duct insulation, and improved equipment sizing; and (3) to develop and evaluate innovative techniques applicable to large buildings for sealing ducts and encapsulating internal duct insulation. In the UCB fan project, the goals were: (1) to develop a protocol for testing, analyzing and diagnosing problems in large commercial building built-up air handling systems, and (2) to develop low-cost measurement techniques to improve short term monitoring practices. To meet our stated goals and objectives, this project: (1) continued to investigate and characterize the performance of thermal distribution systems in commercial buildings; (2) performed energy analyses and evaluation for duct-performance improvements for both small and large commercial buildings; (3) developed aerosol injection technologies for both duct sealing and liner encapsulation in commercial buildings; and (4) designed energy-related diagnostic protocols based on short term measurement and used a benchmarking database to compare subject systems with other measured systems for certain performance metrics. This year's efforts consisted of the following distinct tasks: performing characterization measurements for five light commercial building systems and five large-commercial-building systems; analyzing the potential for including duct performance in California's Energy Efficiency Standards for Residential and Non-Residential Buildings (Title 24), including performing energy and equipment sizing analyses of air distribution systems using DOE 2.1E for non-residential buildings; conducting laboratory experiments, field experiments, and modeling of new aerosol injection technologies concepts for sealing and coating, including field testing aerosol-based sealing in two large commercial buildings; improving low-cost fan monitoring techniques measurements, and disseminating fan tools by working with energy practitioners directly where possible and publishing the results of this research and the tools developed on a web-site. The final report consists of five sections listed below. Each section includes its related

Xu, Tengfang; Bechu, Olivier; Carrie, Remi; Dickerhoff, Darryl; Fisk, William; Franconi, Ellen; Kristiansen, Oyvind; Levinson, Ronnen; McWilliams, Jennifer; Wang, Duo; Modera, Mark; Webster, Tom; Ring, Erik; Zhang, Qiang; Huizenga, Charlie; Bauman, Fred; Arens, Ed

1999-12-01T23:59:59.000Z

410

Commercial thermal distribution systems, Final report for CIEE/CEC  

SciTech Connect

According to the California Energy Commission (CEC 1998a), California commercial buildings account for 35% of statewide electricity consumption, and 16% of statewide gas consumption. Space conditioning accounts for roughly 16,000 GWh of electricity and 800 million therms of natural gas annually, and the vast majority of this space conditioning energy passes through thermal distribution systems in these buildings. In addition, 8600 GWh per year is consumed by fans and pumps in commercial buildings, most of which is used to move the thermal energy through these systems. Research work at Lawrence Berkeley National Laboratory (LBNL) has been ongoing over the past five years to investigate the energy efficiency of these thermal distribution systems, and to explore possibilities for improving that energy efficiency. Based upon that work, annual savings estimates of 1 kWh/ft{sup 2} for light commercial buildings, and 1-2 kWh/ft{sup 2} in large commercial buildings have been developed for the particular aspects of thermal distribution system performance being addressed by this project. Those savings estimates, combined with a distribution of the building stock based upon an extensive stock characterization study (Modera et al. 1999a), and technical penetration estimates, translate into statewide saving potentials of 2000 GWh/year and 75 million thermal/year, as well as an electricity peak reduction potential of 0.7 GW. The overall goal of this research program is to provide new technology and application knowledge that will allow the design, construction, and energy services industries to reduce the energy waste associated with thermal distribution systems in California commercial buildings. The specific goals of the LBNL efforts over the past year were: (1) to advance the state of knowledge about system performance and energy losses in commercial-building thermal distribution systems; (2) to evaluate the potential of reducing thermal losses through duct sealing, duct insulation, and improved equipment sizing; and (3) to develop and evaluate innovative techniques applicable to large buildings for sealing ducts and encapsulating internal duct insulation. In the UCB fan project, the goals were: (1) to develop a protocol for testing, analyzing and diagnosing problems in large commercial building built-up air handling systems, and (2) to develop low-cost measurement techniques to improve short term monitoring practices. To meet our stated goals and objectives, this project: (1) continued to investigate and characterize the performance of thermal distribution systems in commercial buildings; (2) performed energy analyses and evaluation for duct-performance improvements for both small and large commercial buildings; (3) developed aerosol injection technologies for both duct sealing and liner encapsulation in commercial buildings; and (4) designed energy-related diagnostic protocols based on short term measurement and used a benchmarking database to compare subject systems with other measured systems for certain performance metrics. This year's efforts consisted of the following distinct tasks: performing characterization measurements for five light commercial building systems and five large-commercial-building systems; analyzing the potential for including duct performance in California's Energy Efficiency Standards for Residential and Non-Residential Buildings (Title 24), including performing energy and equipment sizing analyses of air distribution systems using DOE 2.1E for non-residential buildings; conducting laboratory experiments, field experiments, and modeling of new aerosol injection technologies concepts for sealing and coating, including field testing aerosol-based sealing in two large commercial buildings; improving low-cost fan monitoring techniques measurements, and disseminating fan tools by working with energy practitioners directly where possible and publishing the results of this research and the tools developed on a web-site. The final report consists of five sections listed below. Each section includes its related

Xu, Tengfang; Bechu, Olivier; Carrie, Remi; Dickerhoff, Darryl; Fisk, William; Franconi, Ellen; Kristiansen, Oyvind; Levinson, Ronnen; McWilliams, Jennifer; Wang, Duo; Modera, Mark; Webster, Tom; Ring, Erik; Zhang, Qiang; Huizenga, Charlie; Bauman, Fred; Arens, Ed

1999-12-01T23:59:59.000Z

411

Cooling Systems | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

heat is drawn out of the air and the cooled air is blown into the space by the cooler's fan. Air Conditioning Air conditioners, which employ the same operating principles and...

412

Study of the effects of ambient conditions upon the performance of fan powered, infrared, natural gas burners. Quarterly report, April 1, 1996 - June 30, 1996  

DOE Green Energy (OSTI)

A porous radiant burner testing facility consisting of a commercial deep-fat fryer, an FTIR based spectral radiance measurement system, a set of flue gas analysis components, and a fuel gas mixing station was constructed. The measurement capabilities of the system were tested using methane and the test results were found to be consistent with the literature. Following the validation of the measurement system, various gas mixtures were tested to study the effect of gas compositions have on burner performance. Results indicated that the emissions vary with fuel gas composition and air/fuel ratio. The maximum radiant efficiency of the burner was obtained close to air/fuel ratio of 1.

Bai, T.; Yeboah, Y.D.; Sampath, R.

1996-07-01T23:59:59.000Z

413

Fuel cell powered irrigation system  

SciTech Connect

Set out herein is a fuel cell power plant for use with irrigation systems wherein the fuel cell is utilized to generate electric current to drive a pump motor. This pump motor drives a first water pump which receives water for distribution through a traveling irrigation system, the output of the first pump first conveyed into a condenser heat exchanger connected to a steam engine or turbine cycle. The fuel cell itself is contained within a boiler assembly and the heat of production of the electric power is used to generate steam which is sent to the steam engine. In the course of cooling the condenser gases of the steam engine the irrigating water is passed through a second pump driven by the steam engine and it is through this second pump that the pressure is raised sufficiently to allow for the necessary spraying fans. To improve the condenser efficiency part of the condensate or the ullage thereof is connected to one of the spray heads on the irrigation system in a venturi nozzle which thereby lowers the back pressure thereof. The lower portion of the condenser or the liquid part thereof is fed back through yet another condenser pump to the boiler to be regenerated into steam.

Jacobi, E.F.; Madden, M.R.

1982-01-12T23:59:59.000Z

414

Integrated Ice Storage/Sprinkler HVAC System Sharply Cuts Energy Costs and Air-Distribution First Costs  

E-Print Network (OSTI)

Integrated ice thermal storage/sprinkler HVAC systems developed and applied by the author in several commercial applications shift a major portion of electric utility demand to cheaper off-peak hours, while also reducing significantly the first cost of distribution ductwork. Savings of up to 80% in primary duct and air handler costs (compared to a traditional all-air HVAC system) partially offset the first cost of ice storage equipment, which in turn permits a 50% reduction in utility energy costs for air conditioning in some facilities. The basic ice storage/sprinkler HVAC system is described as well as optional subsystems, such as cogeneration, that are cost-effective under certain conditions. The system's design parameters, psychrometric process, and thermodynamic characteristics are presented and two installations are described, a 223,000-sq ft shopping center and a 150,000-sq ft, two-story retail store. Reductions in the size and first cost of primary air-handling equipment and ductwork are achieved by distributing a small quantity (0.1 to 0.2 cfm/sq ft) of very dry, 40°F primary air. All dehumidification is handled by the ice-chilled primary air, which is distributed in variable, volume, determined by the space dehumidification requirement, to fan-coil induction terminal units. The primary air is mixed with fan-induced room air in the terminals prior to distribution to the space at a constant volume. The fan-induction terminals contain cooling coils connected to the integrated sprinkler system, which circulates chilled water from the central plant through the coils when additional sensible cooling is required. This chilled water is at a thermodynamically efficient elevated temperature (58-68°F), since it handles sensible cooling load only.

Meckler, G.

1986-01-01T23:59:59.000Z

415

Solar heating system final design package  

DOE Green Energy (OSTI)

Contemporary Systems has taken its Series V Solar Heating System and developed it to a degree acceptable by local codes and regulatory agencies. The system is composed of the Series V warm air collector, the LCU-110 logic control unit and the USU-A universal switching and transport unit. The collector was originally conceived and designed as an integrated roof/wall system and provides a dual function in the structure. The collector serves both as a solar energy conversion system and as a structural weather resistant skin. The collector can be fabricated in any length from 12 to 24 feet. This provides maximum flexibility in design and installation. The LCU-110 control unit provides totally automatic control over the operation of the system. It receives input data from sensor probes in collectors, storage and living space. The logic is designed so as to make maximum use of solar energy and minimize use of conventional energy. The USU-A transport and switching unit is a high-efficiency air-handling system equipped with gear motor valves that respond to outputs from the control system. The fan unit is designed for maximum durability and efficiency in operation, and has permanently lubricated ball bearings and excellent air-handling efficiency.

Not Available

1979-05-01T23:59:59.000Z

416

ANNUAL REPORT, ACCELERATOR and FUSION RESEARCH DIVISION. FISCAL YEAR 1978  

E-Print Network (OSTI)

Accelerator Conceptual Design, HI-FAN-58, 9/6/78. L.J.and Example Design of 1 MJ RF Linac System, HI-FAN-45, (LBL-

Lofgren, E.J.

2010-01-01T23:59:59.000Z

417

NIST Manuscript Publication Search  

Science Conference Proceedings (OSTI)

... In 4 of the 11 cases, the heating and air-conditioning system fan was operating. One test case was performed with an attic fan operating. ...

2003-08-01T23:59:59.000Z

418

Buildings Energy Data Book: 5.5 Thermal Distribution Systems  

Buildings Energy Data Book (EERE)

CAV Packaged CAV Condenser Fan 0.3 0.2 Cooling Tower Fan 0.2 0.1 0.2 0.0 Condenser Water Pump 0.2 0.3 0.3 0.0 Chilled Water Pump 0.2 0.1 0.2 0.0 Supply & Return Fans 0.7 0.5...

419

Adhesive Anchor Failure in Boston's Big Dig Tunnel System  

Science Conference Proceedings (OSTI)

Failure Analysis Case Studies from Refinery and Petrochemical Pilot Plants ... Failure of Electrical Submersible Pump of Oil Reservoir · Fan Blade Fracture in a  ...

420

Residential Forced Air System Cabinet Leakage and Blower Performance  

E-Print Network (OSTI)

CA.   CEC (2008b).  Residential Alternative Calculation Standard for Air Handlers in Residential Space Conditioning of Standards Options for Residential Air Handler Fans.   

Walker, Iain S.

2010-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


421

Computer Modeling VRF Heat Pumps in Commercial Buildings using EnergyPlus  

Science Conference Proceedings (OSTI)

Variable Refrigerant Flow (VRF) heat pumps are increasingly used in commercial buildings in the United States. Monitored energy use of field installations have shown, in some cases, savings exceeding 30% compared to conventional heating, ventilating, and air-conditioning (HVAC) systems. A simulation study was conducted to identify the installation or operational characteristics that lead to energy savings for VRF systems. The study used the Department of Energy EnergyPlus? building simulation software and four reference building models. Computer simulations were performed in eight U.S. climate zones. The baseline reference HVAC system incorporated packaged single-zone direct-expansion cooling with gas heating (PSZ-AC) or variable-air-volume systems (VAV with reheat). An alternate baseline HVAC system using a heat pump (PSZ-HP) was included for some buildings to directly compare gas and electric heating results. These baseline systems were compared to a VRF heat pump model to identify differences in energy use. VRF systems combine multiple indoor units with one or more outdoor unit(s). These systems move refrigerant between the outdoor and indoor units which eliminates the need for duct work in most cases. Since many applications install duct work in unconditioned spaces, this leads to installation differences between VRF systems and conventional HVAC systems. To characterize installation differences, a duct heat gain model was included to identify the energy impacts of installing ducts in unconditioned spaces. The configuration of variable refrigerant flow heat pumps will ultimately eliminate or significantly reduce energy use due to duct heat transfer. Fan energy is also studied to identify savings associated with non-ducted VRF terminal units. VRF systems incorporate a variable-speed compressor which may lead to operational differences compared to single-speed compression systems. To characterize operational differences, the computer model performance curves used to simulate cooling operation are also evaluated. The information in this paper is intended to provide a relative difference in system energy use and compare various installation practices that can impact performance. Comparative results of VRF versus conventional HVAC systems include energy use differences due to duct location, differences in fan energy when ducts are eliminated, and differences associated with electric versus fossil fuel type heating systems.

Raustad, Richard

2013-06-01T23:59:59.000Z

422

Lighting system combining daylight concentrators and an artificial source  

DOE Patents (OSTI)

A combined lighting system for a building interior includes a stack of luminescent solar concentrators (LSC), an optical conduit made of preferably optical fibers for transmitting daylight from the LSC stack, a collimating lens set at an angle, a fixture for receiving the daylight at one end and for distributing the daylight as illumination inside the building, an artificial light source at the other end of the fixture for directing artifical light into the fixture for distribution as illumination inside the building, an automatic dimmer/brightener for the artificial light source, and a daylight sensor positioned near to the LSC stack for controlling the automatic dimmer/brightener in response to the daylight sensed. The system also has a reflector positioned behind the artificial light source and a fan for exhausting heated air out of the fixture during summer and for forcing heated air into the fixture for passage into the building interior during winter.

Bornstein, Jonathan G. (Miami, FL); Friedman, Peter S. (Toledo, OH)

1985-01-01T23:59:59.000Z

423

96 ASHRAE Transactions: Research Current duct design methods for variable air volume  

E-Print Network (OSTI)

96 ASHRAE Transactions: Research ABSTRACT Current duct design methods for variable air volume (VAV in the 1997 ASHRAE Handbook--Fundamentals (ASHRAE 1997): equal friction, static regain, and the T Systems Taecheol Kim Jeffrey D. Spitler, Ph.D., P.E. Ronald D. Delahoussaye, Ph.D. Member ASHRAE Taecheol

424

Effect of building airtightness and fan size on the performance of mechanical ventilation systems in new U.S. houses: a critique of ASHRAE standard 62.2-2003  

E-Print Network (OSTI)

easier to incorporate air sealing in new construction thanair quality and should be (but seldom is) eliminated by sealing

Roberson, J.

2004-01-01T23:59:59.000Z

425

Effect of building airtightness and fan size on the performance of mechanical ventilation systems in new U.S. houses: a critique of ASHRAE standard 62.2-2003  

E-Print Network (OSTI)

and Infiltration. Handbook: Fundamentals. American Societyand Ventilation. Handbook: Fundamentals. American Society ofand Ventilation. Handbook: Fundamentals. American Society of

Roberson, J.

2004-01-01T23:59:59.000Z

426

Effect of building airtightness and fan size on the performance of mechanical ventilation systems in new U.S. houses: a critique of ASHRAE standard 62.2-2003  

E-Print Network (OSTI)

of Heating, Refrigerating and Air- Conditioning Engineers.Refrigerating and Air-Conditioning Engineers, Inc. , AtlantaRefrigerating and Air-Conditioning Engineers, Inc. , Atlanta

Roberson, J.

2004-01-01T23:59:59.000Z

427

Effect of building airtightness and fan size on the performance of mechanical ventilation systems in new U.S. houses: a critique of ASHRAE standard 62.2-2003  

E-Print Network (OSTI)

Vol 22, No 6. pg 10-11. 2003. ASHRAE 62.2 Recommended for6, 7, 10, 33, 37. ANSI/ASHRAE. 1988 (RA 94). Standard 119–Inc. , Atlanta GA. ANSI/ASHRAE. 1993 (RA 2001). Standard

Roberson, J.

2004-01-01T23:59:59.000Z

428

Effect of building airtightness and fan size on the performance of mechanical ventilation systems in new U.S. houses: a critique of ASHRAE standard 62.2-2003  

E-Print Network (OSTI)

Centre. Berkshire GB EERE. 2004. Building Technologiesand Renewable Energy (EERE) sponsors the Building AmericaBarley 2001, Andrews 2002, EERE 2004, Rudd 2004). In fact,

Roberson, J.

2004-01-01T23:59:59.000Z

429

Effect of building airtightness and fan size on the performance of mechanical ventilation systems in new U.S. houses: a critique of ASHRAE standard 62.2-2003  

E-Print Network (OSTI)

pg 4. 2000c. Industry News: Vermont to Require Mechanicalpgs 816-827. ICCI. 2003. Vermont Residential Building EnergyNew Construction in Vermont: A Review of Codes, Standards,

Roberson, J.

2004-01-01T23:59:59.000Z

430

Effect of building airtightness and fan size on the performance of mechanical ventilation systems in new U.S. houses: a critique of ASHRAE standard 62.2-2003  

E-Print Network (OSTI)

2002. When Does a House Need Passive Air Inlets? June. VolStudy on Passive Ventilation in Airtight Houses in Coldsupply. Because houses are so tight, passive vents are a

Roberson, J.

2004-01-01T23:59:59.000Z

431

Energy efficiency of a dynamic glazing system  

SciTech Connect

The reduction of air-conditioning energy consumptions is one of the main indicators to act on when improving the energy efficiency in buildings. In the case of advanced technological buildings, a meaningful contribution to the thermal loads and the energy consumptions reduction could depend on the correct configuration and management of the envelope systems. In recent years, the architectural trend toward highly transparent all-glass buildings presents a unique challenge and opportunity to advance the market for emerging, smart, dynamic window and dimmable daylighting control technologies (). A prototype dynamic glazing system was developed and tested at ITC-CNR; it is aimed at actively responding to the external environmental loads. Both an experimental campaign and analyses by theoretical models were carried out, aimed at evaluating the possible configurations depending on different weather conditions in several possible places. Therefore, the analytical models of the building-plant system were defined by using a dynamic energy simulation software (EnergyPlus). The variables that determine the system performance, also influenced by the boundary conditions, were analysed, such as U- and g-value; they concern both the morphology of the envelope system, such as dimensions, shading and glazing type, gap airflow thickness, in-gap airflow rate, and management, in terms of control algorithm parameters tuning fan and shading systems, as a function of the weather conditions. The configuration able to provide the best performances was finally identified by also assessing such performances, integrating the dynamic system in several building types and under different weather conditions. The dynamic envelope system prototype has become a commercial product with some applications in facade systems, curtain walls and windows. The paper describes the methodological approach to prototype development and the main results obtained, including simulations of possible applications on real buildings. (author)

Lollini, R. [Institute for Renewable Energy, EURAC Research, Viale Druso 1, I-39100 Bolzano (Italy); Danza, L.; Meroni, I. [ITC-CNR, Construction Technologies Institute - Italian National Research Council, Via Lombardia, 49 - 20098 San Giuliano Milanese (MI) (Italy)

2010-04-15T23:59:59.000Z

432

Energy Efficient Building Ventilation Systems: Innovative Building-Integrated Enthalpy Recovery  

Science Conference Proceedings (OSTI)

BEETIT Project: A2 is developing a building moisture and heat exchange technology that leverages a new material and design to create healthy buildings with lower energy use. Commercial building owners/operators are demanding buildings with greater energy efficiency and healthier indoor environments. A2 is developing a membrane-based heat and moisture exchanger that controls humidity by transferring the water vapor in the incoming fresh air to the drier air leaving the building. Unlike conventional systems, A2 locates the heat and moisture exchanger within the depths of the building’s wall to slow down the air flow and increase the surface area that captures humidity, but with less fan power. The system’s integration into the wall reduces the size and demand on the air conditioning equipment and increases liable floor area flexibility.

None

2010-10-15T23:59:59.000Z

433

BOA II: Asbestos Pipe-Insulation Removal Robot System. Innovative Technology Summary Report.  

Science Conference Proceedings (OSTI)

The objective of this task is to develop and demonstrate a mechanical, asbestos-removal system that can be remotely operated without a containment area. The technology, known as BOA, consists of a pipe-crawler removal head and a boom vehicle system with dual robots. BOA's removal head can be remotely placed on the outside of the pipe and can crawl along the pipe, removing lagging and insulation. The lagging and insulation is cut using a hybrid endmill water-jet cutter and then diced into 2-inch cube sections of ACM. These ACM sections are then removed from the pipe using a set of blasting fan- spray nozzles, vacuumed off through a vacuum hose, and bagged. Careful attention to vacuum and entrapment air flow ensures that the system can operate without a containment area while meeting local and federal standards for fiber count.

None

2001-09-01T23:59:59.000Z

434

Thermodynamic modeling and optimization of a screw compressor chiller and cooling tower system  

E-Print Network (OSTI)

This thesis presents a thermodynamic model for a screw chiller and cooling tower system for the purpose of developing an optimized control algorithm for the chiller plant. The thermodynamic chiller model is drawn from the thermodynamic models developed by Gordon and Ng (1996). However, the entropy production in the compressor is empirically related to the pressure difference measured across the compressor. The thermodynamic cooling tower model is the Baker & Shryock cooling tower model that is presented in ASHRAE Handbook - HVAC Systems and Equipment (1992). The models are coupled to form a chiller plant model which can be used to determine the optimal performance. Two correlations are then required to optimize the system: a wet-bulb/setpoint correlation and a fan speed/pump speed correlation. Using these correlations, a "quasi-optimal" operation can be achieved which will save 17% of the energy consumed by the chiller plant.

Graves, Rhett David

2003-12-01T23:59:59.000Z

435

A System for Smart Home Control of Appliances based on Timer and Speech Interaction  

E-Print Network (OSTI)

The main objective of this work is to design and construct a microcomputer based system: to control electric appliances such as light, fan, heater, washing machine, motor, TV, etc. The paper discusses two major approaches to control home appliances. The first involves controlling home appliances using timer option. The second approach is to control home appliances using voice command. Moreover, it is also possible to control appliances using Graphical User Interface. The parallel port is used to transfer data from computer to the particular device to be controlled. An interface box is designed to connect the high power loads to the parallel port. This system will play an important role for the elderly and physically disable people to control their home appliances in intuitive and flexible way. We have developed a system, which is able to control eight electric appliances properly in these three modes.

Haque, S M Anamul; Islam, Md Ashraful

2010-01-01T23:59:59.000Z

436

Final Report: Fan Filter Unit Project  

NLE Websites -- All DOE Office Websites (Extended Search)

61684 61684 Demonstration of Advanced Filtration Technologies: Developing Energy-rebate Criteria through Performing Standard Laboratory Tests and Statistical Analyses Final Report (LBNL- 61684) To California Energy Commission 2007 Tengfang Xu and Duo Wang 2 Disclaimer This document was prepared as an account of work sponsored by the United States Government and California Energy Commission. While this document is believed to contain correct information, neither the United States Government nor any agency thereof, nor California Energy Commission, nor The Regents of the University of California, nor any of their employees, makes any warranty, express or implied, or assumes any legal responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or

437

Introduction of a Cooling Fan Efficiency Index  

E-Print Network (OSTI)

of the cooling effect measured with the thermal manikin andThe mea- sured cooling effect with the thermal manikin isby a thermal manikin to quantify the cooling effects of air

Schiavon, Stefano; Melikov, Arsen

2009-01-01T23:59:59.000Z

438

Introduction of a Cooling Fan Efficiency Index  

E-Print Network (OSTI)

Refrigerating and Air-Conditioning Engineers, Inc. (Refrigerating and Air-Conditioning Engineers, Inc. (Refrigerating and Air-Conditioning Engineers, Inc. (

Schiavon, Stefano; Melikov, Arsen

2009-01-01T23:59:59.000Z

439

Experimental investigation of an aspirated fan stage  

E-Print Network (OSTI)

This thesis focuses on the use of aspiration on compressor blade design. The pressure ratio can be significantly increased by controlling the development of the blade and endwall boundary layers. This concept is validated ...

Schuler, Brian Joseph, 1974-

2001-01-01T23:59:59.000Z

440

Re-design of a portable fan.  

E-Print Network (OSTI)

?? Abstract This master’s thesis is a project of 20p made in accordance with the requirements set by Halmstad University for a Master’s degree in… (more)

Ivegren, Erica

2007-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


441

Filter-Analyzer Neutron Spectrometer (FANS)  

Science Conference Proceedings (OSTI)

... Soc., Div. Fuel Chem ... H. Kabbour, and CC Ahn, "Hydrogen Adsorption in MOF-74 Studied by Inelastic Neutron Scattering", in Life Cycle Analysis for ...

442

My Faculty Advisor is... Dr. Kent Fanning  

E-Print Network (OSTI)

and absorption of color dissolved organic matter (CDOM) and nutrients in Kings Bay, Crystal River up in our rivers and oceans. Marine life suffer from continuous exposure to these harmful chemical

Meyers, Steven D.

443

Filter-Analyzer Neutron Spectrometer (FANS)  

Science Conference Proceedings (OSTI)

... J. Hwang, "Probing the Unusual Proton and Anion Mobility of LiBH ... Analysis of the Inelastic Neutron Scattering Spectra of Electron Donor-Acceptor ...

444

Vehicle cabin cooling system for capturing and exhausting heated boundary layer air from inner surfaces of solar heated windows  

DOE Patents (OSTI)

The cabin cooling system includes a cooling duct positioned proximate and above upper edges of one or more windows of a vehicle to exhaust hot air as the air is heated by inner surfaces of the windows and forms thin boundary layers of heated air adjacent the heated windows. The cabin cooling system includes at least one fan to draw the hot air into the cooling duct at a flow rate that captures the hot air in the boundary layer without capturing a significant portion of the cooler cabin interior air and to discharge the hot air at a point outside the vehicle cabin, such as the vehicle trunk. In a preferred embodiment, the cooling duct has a cross-sectional area that gradually increases from a distal point to a proximal point to the fan inlet to develop a substantially uniform pressure drop along the length of the cooling duct. Correspondingly, this cross-sectional configuration develops a uniform suction pressure and uniform flow rate at the upper edge of the window to capture the hot air in the boundary layer adjacent each window.

Farrington, Robert B. (Golden, CO); Anderson, Ren (Broomfield, CO)

2001-01-01T23:59:59.000Z

445

Load calculation and system evaluation for electric vehicle climate control  

DOE Green Energy (OSTI)

Providing air conditioning for electric vehicles (EVs) represents an important challenge, because vapor compression air conditioners, which are common in gasoline powered vehicles, may consume a substantial part of the total energy stored in the EV battery. This report consists of two major parts. The first part is a cooling and heating load calculation for electric vehicles. The second part is an evaluation of several systems that can be used to provide the desired cooling and heating in EVs. Four cases are studied. Short range and full range EVs are each analyzed twice, first with the regular vehicle equipment, and then with a fan and heat reflecting windows, to reduce hot soak. Recent legislation has allowed the use of combustion heating whenever the ambient temperature drops below 5{degrees}C. This has simplified the problem of heating, and made cooling the most important problem. Therefore, systems described in this project are designed for cooling, and their applicability to heating at temperatures above 5{degrees}C is described. If the air conditioner systems cannot be used to cover the whole heating load at 5{degrees}C, then the vehicle requires a complementary heating system (most likely a heat recovery system or electric resistance heating). Air conditioners are ranked according to their overall weight. The overall weight is calculated by adding the system weight and the weight of the battery necessary to provide energy for system operation.

Aceves-Saborio, S.; Comfort, W.J. III

1993-10-27T23:59:59.000Z

446

Home Energy Article: A Systems Approach to Retrofitting Residential HVAC Systems  

E-Print Network (OSTI)

The sealing included air-sealing the attic floor plane (2air circulation fan. Other recommendations about sealing andaerosol sealing. The supply ducts were sealed to 4% of air

McWilliams, Jennifer A.; Walker, Iain S.

2005-01-01T23:59:59.000Z

447

Best Practices for Energy Efficient Cleanrooms Efficient HVAC Systems: Variable-Speed-Drive Chillers  

E-Print Network (OSTI)

sizing ? Cooling tower and condenser optimization ? Controland cooling tower or condenser fans. Figure 1 and Figure 2those with evaporative condensers are more efficient than

Xu, Tengfang

2005-01-01T23:59:59.000Z

448

Best Practice for Energy Efficient Cleanrooms: Control of Chilled Water System  

E-Print Network (OSTI)

MUAH + RCU Fans Pumps Cooling Towers Figure 1. Benchmarkedcondenser water pumps, and cooling towers for water-cooledRight sizing ? Cooling tower and condenser optimization ?

Xu, Tengfang

2005-01-01T23:59:59.000Z

449

Section 5.2.2 Air Distribution Systems: Greening Federal Facilities...  

NLE Websites -- All DOE Office Websites (Extended Search)

and yield substantial energy savings. Small in- creases in duct diameter can yield large pressure drop and fan energy savings, because the pressure drop in ducts is proportional...

450

Prototype of time digitizing system for BESIII endcap TOF upgrade  

E-Print Network (OSTI)

The prototype of time digitizing system for the upgrade of BESIII endcap TOF (ETOF) is introduced in this paper. The ETOF readout electronics has a formation of distributed architecture that hit signal from multi-gap resistive plate chamber (MRPC) is signaled as LVDS by front-end electronics (FEE) and sent to the back-end time digitizing system via long shield differential twisted pair cables. The ETOF digitizing system consists of 2 VME crates each of which contains modules of time digitizing, clock, trigger and fast control etc. The time digitizing module (TDIG) of this prototype can support up to 72 electrical channels of hit information measurement. The fast control (FCTL) module can operate at barrel or endcap mode. The barrel FCTL fans fast control signals from the trigger system out to endcap FCTLs, merges data from endcaps and transfers to the trigger system. Without modifying the barrel TOF structure, this time digitizing architecture benefits for improving ETOF performance without degrading barrel TOF measuring. Lab experiments show that the time resolution of this digitizing system can be less than 20ps, and the data throughput to DAQ can be about 92Mbps. Beam experiments show that the complete time resolution can be less than 45ps.

Cao Ping; Sun Wei-Jia; Ji Xiao-Lu; Fan Huan-Huan; Wang Si-Yu; Liu Shu-Bin; An Qi

2013-05-30T23:59:59.000Z

451

Case Studies of Systems Integration through Energy Simulation During Early Design Phase  

E-Print Network (OSTI)

The paper presents two case studies, a commercial & a community project, in Houston Texas, where energy simulation and a decision matrix were used to solve budget conflicts and meet LEED EA-1 requirements. The first case study consists of the analysis of three different direct-expansion (DX) systems in an underfloor air distribution (UFAD) configuration for an office building with an unusually large footprint. Of the three options, only two could meet EA-1 pre-requisite for LEED-NC certification while meeting the project budget. The second case study involves analysis of a 120,000 sf. Community recreation center with multiple space types and operation schedules. The analysis employed different combinations of energy recovery systems, efficient lighting package, skylights and large efficient ceiling fans. While all the options met LEED-NC EA-1 prerequisite, each had a different payback time. Finally a combination of strategies was used for optimum payback and energy efficiency.

Upadhyaya, K.; McLean, D.

2008-12-01T23:59:59.000Z

452

Quantitative troubleshooting of industrial exhaust ventilation systems  

SciTech Connect

This article proposes two troubleshooting tools that may allow precise and accurate assessment of changes to ventilation systems of any type. Both are useful in discovering and quantifying most modifications that affect the distribution of airflows among the branches and static pressures throughout the system. The approaches are derived from energy balance considerations, using power loss coefficients (X) computed for any contiguous section of the system from the duct velocities and static pressures measured at that section`s inlets and outlets. The value of X for a given portion of the system should be nearly constant with changes in airflow and with modifications to other portions of the system. Responsiveness to local modifications and insensitivity to changes elsewhere in the system - including gross changes in fan performance - make X coefficients a valuable troubleshooting tool. Static pressure ratios within a given branch are functionally related to ratios of X coefficients. Therefore, they vary with modifications to the branch and are highly insensitive to changes outside that branch. Unlike X coefficients, determination of static pressure ratios does not require velocity traverses, making them faster and easier to determine than X values. On the other hand, values of X are more universally applicable and have direct physical significance. Use of both static pressure ratios and X coefficients are described in a suggested troubleshooting procedure. Systematic measurement errors have surprisingly little impact on the usefulness of values of X or static pressure ratios. The major impediment to using either tool is the necessity for {open_quotes}baseline{close_quotes} measurements, which are often unavailable. On the other hand, a baseline for future comparisons can be created piecemeal, beginning at any time and extending over any period of time. 11 refs., 8 figs., 8 tabs.

Guffey, S.E. [Univ. of Washington, Seattle, WA (United States)

1994-04-01T23:59:59.000Z

453

Prototype Energy Retrieval and Solar (PERS) System : Final Report.  

DOE Green Energy (OSTI)

The PERS System, which provides both heating and cooling for the substation Control House, has several different modes of operation. During the winter, heat from the transformer is recovered by a heat pump and is transferred to water circulating through a fan coil unit in the Control House forced air system. In addition, banks of tubular collectors mounted on the roof of the Control House can provide direct solar heating. During the summer, the solar collector array is used to drive a 15-ton absorption air conditioner which cools water in a 4300-gallon storage tank. Mechanical difficulaties were encountered, performance of components was not always satisfactory, and a need for modifications in the system emerged. During the winter testing period in December 1978, the heat recovery system performed with an average Coefficient of Performance (COP) of 2.75, as compared to the design goal of 4.6. The absorption chiller, however, performed quite well during the summer testing period in August, 1978. The coefficient of performance ranged from 0.598 to 0.622 on a daily basis, comparing favorably with the anticipated goal of a COP of 0.74. The overall solar-assisted absorption chiller system performed with a COP ranging from 2.80 to 3.57, with the absorption chiller functioning at even relatively low collector temperatures.

Guddat, Robert O.

1981-05-01T23:59:59.000Z

454

Residential duct system leakage; Magnitude, impacts, and potential for reduction  

Science Conference Proceedings (OSTI)

This paper discusses the issues associated with leakage in residential air distribution systems, touching on the prevalence of duct leakage, the impacts of duct leakage, and on the techniques available for sealing duct systems. The issues examined in detail are: present techniques for measuring the leakage area of ducts existing data bases of duct leakage area measurements, the impacts of duct leakage on space-conditioning energy consumption and peak demand, and the ventilation impacts of duct leakage. The paper also includes a brief discussion of techniques for sealing duct systems in the field. The results derived from duct leakage are and driving pressure measurements indicate that in regions in which distribution systems pass through unconditioned spaces, air infiltration rates will typically double when the distribution fan is turned on, and that the average annual air infiltration rate is increased by 30% to 70% due to the existence of the distribution system. Estimates based upon a simplified analysis of leakage-induced energy losses also indicate the peak electricity demands due to duct leakage can be as high as 4 kW in Sacramento, California, and West Palm Beach, Florida, and that peak loads on the order of 1 to 2 kW are highly likely in these locations. Both peak loads and annual energy impacts are found to be strongly dependent on the location of the return duct, and attic return costing approximately 1500 kWh more energy than a crawlspace return in the two climates examined.

Modera, M.P. (Lawrence Berkeley Lab., Berkeley, CA (US))

1989-01-01T23:59:59.000Z

455

Meeting Residential Ventilation Standards Through Dynamic Control of Ventilation Systems  

SciTech Connect

Existing ventilation standards, including American Society of Heating, Refrigerating, and Air-conditioning Engineers (ASHRAE) Standard 62.2, specify continuous operation of a defined mechanical ventilation system to provide minimum ventilation, with time-based intermittent operation as an option. This requirement ignores several factors and concerns including: other equipment such as household exhaust fans that might incidentally provide ventilation, negative impacts of ventilation when outdoor pollutant levels are high, the importance of minimizing energy use particularly during times of peak electricity demand, and how the energy used to condition air as part of ventilation system operation changes with outdoor conditions. Dynamic control of ventilation systems can provide ventilation equivalent to or better than what is required by standards while minimizing energy costs and can also add value by shifting load during peak times and reducing intake of outdoor air contaminants. This article describes the logic that enables dynamic control of whole-house ventilation systems to meet the intent of ventilation standards and demonstrates the dynamic ventilation system control concept through simulations and field tests of the Residential Integrated Ventilation-Energy Controller (RIVEC).

Sherman, Max H.; Walker, Iain S.

2011-04-01T23:59:59.000Z

456

DOE-1 BDL SUMMARY. DOE-1 GROUP.  

E-Print Network (OSTI)

SYSTEM-CONTROL SYSTEM-FANS SYSTEM DESIGN-HEAT-TEMP HEAT-SYSTEM-AIR SYSTEM-FANS Keyword DESIGN-HEAT-TEMP HEAT-TEMP-AIR SYSTEM-FANS HEAT-TEMP-SCHED DESIGN-COOL-TEMP COOL-TEMP-

Authors, Various

2011-01-01T23:59:59.000Z

457

Optimizing Process Loads in Industrial Cogeneration Energy Systems  

E-Print Network (OSTI)

Optimum dispatch of energy supply systems can result in large savings in industrial facilities. Identifying the configuration of available equipment, and its loading to minimize total energy consumption to satisfy given load demands, has very high payback potential. This paper discusses an approach to determine integrated energy supply and end use optimum equipment dispatch to simultaneously satisfy given power, process steam and additional "end energy" product needs such as compressed fluids, chemical unit production, etc. Techniques applied to power generation and industrial cogeneration are extended to solving this trigeneration problem where the optimum dispatch of the final load devices (i.e. compressors, fans, pumps, etc.) are an integral part of the total energy system optimization. An example industrial trigeneration system is discussed to illustrate the application and procedures. The methods of considering alternate energy sources, for end use optimization with export power and steam generation will be illustrated. The savings associated with operations optimization readily justify the hardware and software costs required for implementation of Optimization Energy Management Systems (OEMS). An OEMS capability for this application is briefly discussed.

Ahner, D. J.; Babson, P. E.

1995-04-01T23:59:59.000Z

458

Scaling and Optimization of Magnetic Refrigeration for Commercial Building HVAC Systems Greater than 175 kW in Capacity  

Science Conference Proceedings (OSTI)

Heating, ventilation, air-conditioning and refrigeration (HVACR) account for approximately one- third of building energy consumption. Magnetic refrigeration presents an opportunity for significant energy savings and emissions reduction for serving the building heating, cooling, and refrigeration loads. In this paper, we have examined the magnet and MCE material requirements for scaling magnetic refrigeration systems for commercial building cooling applications. Scaling relationships governing the resources required for magnetic refrigeration systems have been developed. As system refrigeration capacity increases, the use of superconducting magnet systems becomes more applicable, and a comparison is presented of system requirements for permanent and superconducting (SC) magnetization systems. Included in this analysis is an investigation of the ability of superconducting magnet based systems to overcome the parasitic power penalty of the cryocooler used to keep SC windings at cryogenic temperatures. Scaling relationships were used to develop the initial specification for a SC magnet-based active magnetic regeneration (AMR) system. An optimized superconducting magnet was designed to support this system. In this analysis, we show that the SC magnet system consisting of two 0.38 m3 regenerators is capable of producing 285 kW of cooling power with a T of 28 K. A system COP of 4.02 including cryocooler and fan losses which illustrates that an SC magnet-based system can operate with efficiency comparable to traditional systems and deliver large cooling powers of 285.4 kW (81.2 Tons).

Abdelaziz, Omar [ORNL; West, David L [ORNL; Mallow, Anne M [ORNL

2012-01-01T23:59:59.000Z

459

Reliability and maintainability study of select solar-energy-system components in the National Solar Data Network. Final subcontract report  

Science Conference Proceedings (OSTI)

This study reports on the reliability and maintainability of select solar energy system components evaluated in 16 solar heating and cooling systems over a one-year period. The systems evaluated were instrumented sites from the National Solar Data Network (NSDN). A complete description and system schematic for each site is provided. The study period was generally between October 1981 to October 1982. The report provides quantitative R and M data (e.g., Failure Rate and Mean Time Between Failures) on pumps, motors and fans from the selected NSDN sites, along with conclusions and recommendations based on comparative data for other components. In summary, pumps, valves, and heat exchangers in solar heating and cooling (SHAC) systems appear to be very reliable and show failure rates comparable to other mechanical system applications. Control systems typically used in SHAC systems appear to be the least reliable but still fall within the range of failures exhibited by other mechanical systems. Evidence suggests that piping leaks in SHAC systems occur at three times the rate of other mechanical systems. Recommendations are provided on other areas of research necessary to determine the useful life of SHAC system components. Finally, an appendix to this report describes actual failures encountered in the 16 systems evaluated.

Kendall, P.W.; Logee, T.L.; Raymond, M.G.

1983-06-01T23:59:59.000Z

460

Knowing fans, knowing music : an exploration of fan interaction on Twitter.  

E-Print Network (OSTI)

??In this thesis, I examine what "knowing music" means to participants in online social musicking activities, along with the role Twitter plays in this process.… (more)

McCollum, Nick

2011-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


461

Assessment of propfan propulsion systems for reduced environmental impact  

E-Print Network (OSTI)

Current aircraft engine designs tend towards higher bypass ratio, low-speed fan designs for improved fuel burn, reduced emissions and noise. Alternative propulsion concepts include counter-rotating propfans (CRPs) which ...

Peters, Andreas, S.M. Massachusetts Institute of Technology

2010-01-01T23:59:59.000Z

462

POWER SYSTEMS DEVELOPMENT FACILITY  

Science Conference Proceedings (OSTI)

This report discusses test campaign GCT3 of the Halliburton KBR transport reactor train with a Siemens Westinghouse Power Corporation (Siemens Westinghouse) particle filter system at the Power Systems Development Facility (PSDF) located in Wilsonville, Alabama. The transport reactor is an advanced circulating fluidized-bed reactor designed to operate as either a combustor or a gasifier using one of two possible particulate control devices (PCDs). The transport reactor was operated as a pressurized gasifier during GCT3. GCT3 was planned as a 250-hour test run to commission the loop seal and continue the characterization of the limits of operational parameter variations using a blend of several Powder River Basin coals and Bucyrus limestone from Ohio. The primary test objectives were: (1) Loop Seal Commissioning--Evaluate the operational stability of the loop seal with sand and limestone as a bed material at different solids circulation rates and establish a maximum solids circulation rate through the loop seal with the inert bed. (2) Loop Seal Operations--Evaluate the loop seal operational stability during coal feed operations and establish maximum solids circulation rate. Secondary objectives included the continuation of reactor characterization, including: (1) Operational Stability--Characterize the reactor loop and PCD operations with short-term tests by varying coal feed, air/coal ratio, riser velocity, solids circulation rate, system pressure, and air distribution. (2) Reactor Operations--Study the devolatilization and tar cracking effects from transient conditions during transition from start-up burner to coal. Evaluate the effect of process operations on heat release, heat transfer, and accelerated fuel particle heat-up rates. Study the effect of changes in reactor conditions on transient temperature profiles, pressure balance, and product gas composition. (3) Effects of Reactor Conditions on Syngas Composition--Evaluate the effect of air distribution, steam/coal ratio, solids circulation rate, and reactor temperature on CO/CO{sub 2} ratio, H{sub 2}/converted carbon ratio, gasification rates, carbon conversion, and cold and hot gas efficiencies. Test run GCT3 was started on December 1, 2000, with the startup of the thermal oxidizer fan, and was completed on February 1, 2001. This test was conducted in two parts; the loop seal was commissioned during the first part of this test run from December 1 through 15, which consisted of hot inert solids circulation testing. These initial tests provided preliminary data necessary to understand different parameters associated with the operation and performance of the loop seal. The loop seal was tested with coal feed during the second part of the test run and additional data was gathered to analyze reactor operations and to identify necessary modifications to improve equipment and process performance. In the second part of GCT3, the gasification portion of the test, from January 20 to February 1, 2001, the mixing zone and riser temperatures were varied between 1,675 and 1,825 F at pressures ranging from 200 to 240 psig. There were 306 hours of solid circulation and 184 hours of coal feed attained in GCT3.

Unknown

2002-05-01T23:59:59.000Z

463

Spray booth with energy saving and fire protection systems  

SciTech Connect

This invention teaches an improved exhaust system to be used with a paint spray booth and having a continuously operating power exhaust fan. The exhaust system has a damper that is opened when spraying actively is taking place in the spray booth and that is closed when there is no spraying actively taking place in the spray booth. A control switch is mounted in any of several locations to determine when the spray gun is in use or is not in use. Thus, the control switch is actuated when the spray gun is hung up thus indicating a nonuse condition of the spray system; whereupon use of the spray gun lifts the gun from the hook to indicate spraying activity. A motor drives the damper to the opened position; and a spring biases the damper to the closed position. A timer is also used to delay the closing of the damper until between twenty and possibly two hundred seconds have lapsed after spraying activity has terminated. This purges the spray booth while yet allows for automatic damper control under normal spraying sequences of use and nonuse. A fire sensing switch is used to deenergize the damper motor to allow the damper to be closed in the event of a fire.

Napadow, S.C.

1980-09-23T23:59:59.000Z

464

Building Energy Software Tools Directory: VentAir 62  

NLE Websites -- All DOE Office Websites (Extended Search)

VentAir 62 VentAir 62 VentAir 62 logo. A ventilation airflow calculator that allows easy, accurate compliance with ASHRAE Standard 62-89. The program automates the cumbersome calculations presented by the Standard's Equation 6-1. The Windows-based program helps building designers design multiple-space ventilation systems that meet the requirements of the Standard. This tool analyzes space and system information from the VAV terminal and air handler unit schedules, calculates ventilation airflow requirements (space minimums and system-level required minimum), and provides additional or revised information for the VAV and AHU schedules. Keywords ventilation design, ASHRAE Standard 62 Validation/Testing N/A Expertise Required Knowledge of ASHRAE Standard 62 requirements and ventilation design.

465

Air-Cooled Condensers in Next-Generation Conversion Systems Geothermal Lab  

Open Energy Info (EERE)

Air-Cooled Condensers in Next-Generation Conversion Systems Geothermal Lab Air-Cooled Condensers in Next-Generation Conversion Systems Geothermal Lab Call Project Jump to: navigation, search Last modified on July 22, 2011. Project Title Air-Cooled Condensers in Next-Generation Conversion Systems Project Type / Topic 1 Laboratory Call for Submission of Applications for Research, Development and Analysis of Geothermal Technologies Project Type / Topic 2 Air-Cooling Project Description As the geothermal industry moves to use geothermal resources that are more expensive to develop, there will be increased incentive to use more efficient power plants. Because of increasing demand on finite supplies of water, this next generation of more efficient plants will likely need to reject heat sensibly to the ambient (air-cooling). This will be especially true in western states having higher grade Enhanced Geothermal Systems (EGS) resources, as well as most hydrothermal resources. If one had a choice, an evaporative heat rejection system would be selected because it would provide both cost and performance advantages. The evaporative system, however, consumes a significant amount of water during heat rejection that would require makeup. Though they use no water, air-cooling systems have higher capital costs, reduced power output (heat is rejected at a higher temperature), lower power sales due to higher parasitics (fan power), and greater variability in power output (because of large variation in the dry-bulb temperature).

466

High-performance dehumidifier for solar desiccant cooling systems  

DOE Green Energy (OSTI)

An advanced-design, one-tenth-scale dehumidifier for use in residential solar desiccant-cooling systems has been built and tested. The new dehumidifier was designed using a parallel-passage geometry, where air flows through channels formed by walls coated with fine-ground silica gel desiccant. This concept has a high heat and mass transfer effectiveness and promises to double the coefficient of performance of the desiccant cooling system to 1.1 kW cooling output/kW thermal input. The parallel-passage design was found to have very low pressure drop, typically 20 Pa (.08 in. water) at design conditions. The low fan power required to drive such low pressure drop components indicates that electrical COP's in the range of 8.0 to 8.2 kW cooling output/kW electrical input are possible. Results presented include parametric studies of the effect of conditions such as temperature and humidity and design parameters such as desiccant particle size and channel spacing on dehumidifier performance.

Schlepp, D.

1983-05-01T23:59:59.000Z

467

Improving the Water Efficiency of Cooling Production System  

E-Print Network (OSTI)

For most of the time, cooling towers (CTs) of cooling systems operate under partial load conditions and by regulating the air circulation with a variable frequency drive (VFD), significant reduction in the fan power can be achieved. In Kuwait and other counties of Arabian Peninsula, reduced airflow can lead to reduction in water consumption as well, since during the summer season, the dry bulb temperature of the ambient air is higher than the incoming hot water temperature, and the air undergoes sensible cooling. This paper presents the findings of a study conducted in the Avenues mall, Kuwait. Initially, the CTs operated only at high speed, and on a typical summer day nearly one fourth of the make-up water was used for self cooling of air. The study based on measured data revealed that the use of VFD can reduce the water wastage for self-cooling of air by as much as 75% and overall water consumption by 18.6% while keeping the cooling system performance at design level.

Maheshwari, G.; Al-Hadban, Y.; Al-Taqi, H. H.; Alasseri, R.

2010-01-01T23:59:59.000Z

468

Advanced Building Efficiency Testbed Initiative/Intelligent Workplace Energy Supply System; ABETI/IWESS  

DOE Green Energy (OSTI)

ABETI/IWESS is a project carried out by Carnegie Mellon's Center for Building Performance and Diagnostics, the CBPD, supported by the U.S. Department of Energy/EERE, to design, procure, install, operate, and evaluate an energy supply system, an ESS, that will provide power, cooling, heating and ventilation for CBPD's Intelligent Workplace, the IW. The energy sources for this system, the IWESS, are solar radiation and bioDiesel fuel. The components of this overall system are: (1) a solar driven cooling and heating system for the IW comprising solar receivers, an absorption chiller, heat recovery exchanger, and circulation pump; (2) a bioDiesel fueled engine generator with heat recovery exchangers, one on the exhaust to provide steam and the other on the engine coolant to provide heated water; (3) a ventilation system including an enthalpy recovery wheel, an air based heat pump, an active desiccant wheel, and an air circulation fan; and (4) various convective and radiant cooling/heating units and ventilation air diffusers distributed throughout the IW. The goal of the ABETI/IWESS project is to demonstrate an energy supply system for a building space that will provide a healthy, comfortable environment for the occupants and that will reduce the quantity of energy consumed in the operation of a building space by a factor of 2 less than that of a conventional energy supply for power, cooling, heating, and ventilation based on utility power and natural gas fuel for heating.

David Archer; Frederik Betz; Yun Gu; Rong Li; Flore Marion; Sophie Masson; Ming Qu; Viraj Srivastava; Hongxi Yin; Chaoqin Zhai; Rui Zhang; Elisabeth Aslanian; Berangere Lartigue

2008-05-31T23:59:59.000Z

469

Buildings Energy Data Book: 9.4 High Performance Buildings  

Buildings Energy Data Book (EERE)

5 5 Case Study, The Thermal Test Facility, National Renewable Energy Laboratory, Golden, Colorado (Office/Laboratory) Building Design Floor Area: 10,000 SF Floors(1): 2 Aspect Ratio: 1.75 Offices Laboratories Conference Room Mechanical Level Shell Windows Material U-factor SHGC(2) Viewing Windows: Double Pane, Grey Tint, Low-e 0.42 0.44 Clerestory Windows: Double Pane, Clear, Low-e 0.45 0.65 Window Area(SF) North 38 South(3) 1,134 East 56 West 56 Wall/Roof Material Effective R-Value North Wall Concrete Slab/Rigid Polystyrene 5.0 South/East/West Steel Studs/Batt Insulation/Concrete 23.0 Roof: Built-up/Polyisocianurate Covering/Steel Supports 23.0 HVAC VAV air handling unit Hot water supply paralell VAV boxes Direct and Indirect evaporative cooling system Single zone roof top unit(4) Hot Water Coil(4)

470

Dakota Electric Association - Commercial and Industrial Energy Efficiency  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Dakota Electric Association - Commercial and Industrial Energy Dakota Electric Association - Commercial and Industrial Energy Efficiency Rebate Program Dakota Electric Association - Commercial and Industrial Energy Efficiency Rebate Program < Back Eligibility Agricultural Commercial Industrial Savings Category Heating & Cooling Commercial Heating & Cooling Cooling Other Heat Pumps Appliances & Electronics Commercial Lighting Lighting Manufacturing Water Heating Maximum Rebate $100,000 Building Measures: 50% of project cost up to $20,000 Central Air Conditioning: $1,500 Compressed Air Evaluation: $2,000 - $15,000 depending on HP Program Info State Minnesota Program Type Utility Rebate Program Rebate Amount HVAC Chillers: $10 - $20/Ton, plus $2/ton, per 0.1 above base efficiency Cooling Towers: $3/nominal tower ton Air Handling Systems (VAV): $170/VAV Box

471

Robust, accurate, and non-contacting vibration measurement systems: Summary of comparison measurements of the robust laser interferometer and typical accelerometer systems. Volume 1  

Science Conference Proceedings (OSTI)

Epoch Engineering, Incorporated (EEI) has completed a series of vibration measurements comparing their newly-developed Robust Laser Interferometer (RLI) with accelerometer-based instrumentation systems. EEI has successfully demonstrated, on several pieces of commonplace machinery, that non-contact, line-of-sight measurements are practical and yield results equal to or, in some cases, better than customary field implementations of accelerometers. The demonstration included analysis and comparison of such phenomena as nonlinearity, transverse sensitivity, harmonics, and signal-to-noise ratio. Fast Fourier Transformations were performed on the accelerometer and the laser system outputs to provide a comparison basis. The RLI was demonstrated, within the limits of the task, to be a viable, line-of-sight, non-contact alternative to accelerometer systems. Several different kinds of machinery were instrumented and compared, including a small pump, a gear-driven cement mixer, a rotor kit, and two small fans. Known machinery vibration sources were verified and RLI system output file formats were verified to be compatible with commercial computer programs used for vibration monitoring and trend analysis. The RLI was also observed to be less subject to electromagnetic interference (EMI) and more capable at very low frequencies.

Goodenow, T.C.; Shipman, R.L.; Holland, H.M. [Epoch Engineering, Inc., Gaithersburg, MD (United States)

1995-06-01T23:59:59.000Z

472

Robust, accurate, and non-contacting vibration measurement systems: Supplemental appendices presenting comparison measurements of the robust laser interferometer and typical accelerometer systems. Volume 2  

Science Conference Proceedings (OSTI)

Epoch Engineering, Incorporated (EEI) has completed a series of vibration measurements comparing their newly-developed Robust Laser Interferometer (RLI) with accelerometer-based instrumentation systems. EEI has successfully demonstrated, on several pieces of commonplace machinery, that non-contact, line-of-sight measurements are practical and yield results equal to or, in some cases, better than customary field implementations of accelerometers. The demonstration included analysis and comparison of such phenomena as nonlinearity, transverse sensitivity, harmonics, and signal-to-noise ratio. Fast Fourier Transformations were performed on the accelerometer and the laser system outputs to provide a comparison basis. The RLI was demonstrated, within the limits o the task, to be a viable, line-of-sight, non-contact alternative to accelerometer systems. Several different kinds of machinery were instrumented and. compared, including a small pump, a gear-driven cement mixer, a rotor kit, and two small fans. Known machinery vibration sources were verified and RLI system output file formats were verified to be compatible with commercial computer programs used for vibration monitoring and trend analysis. The RLI was also observed to be less subject to electromagnetic interference (EMI) and more capable at very low frequencies. This document, Volume 2, provides the appendices to this report.

Goodenow, T.C.; Shipman, R.L.; Holland, H.M. [Epoch Engineering, Inc., Gaithersburg, MD (United States)

1995-06-01T23:59:59.000Z

473

A comparison of central and individual systems for space conditioning and domestic hot water in new multifamily buildings  

SciTech Connect

This report compares the energy performance and life-cycle cost of central and individual heating, ventilating, and air-conditioning (HVAC) systems as well as domestic hot water (DHW) systems in new multifamily buildings. The different systems were analyzed by using DOE-2.1C to model prototypical apartment buildings in Chicago and Atlanta with Weather Year for Energy Calculation weather data. The building is equipped with either a central chiller and gas-fired boiler, which supply four-pipe fan coils in each apartment, or is conditioned by individual packaged terminal air conditioners in each apartment. The building with central HVAC also has a central, gas-fired domestic hot water system; the building with individual units has electric water heaters in each apartment. The individual systems were modeled with and without a setback thermostat. The use of natural gas for space and water heating and the more efficient central chiller resulted in an annual energy cost savings for the central system in both cities. A life-cycle cost comparison of system types shows that apartment buildings with as few as five units in Chicago and as few as 30 units in Atlanta should be designed with central HVAC and DHW systems.

Byrne, S.J. (Lawrence Berkeley Lab., Berkeley, CA (US)); Fay, J.M. (Gas Research Inst., Chicago, IL (US))

1989-01-01T23:59:59.000Z

474

Modeling energy consumption of residential furnaces and boilers in U.S. homes  

E-Print Network (OSTI)

is standard in HVAC design and fan selection books 6 . Theof modulating design options. The cooling fan curve passesfan curve and the duct system curve. We calculated the furnace fuel consumption for each design

Lutz, James; Dunham-Whitehead, Camilla; Lekov, Alex; McMahon, James

2004-01-01T23:59:59.000Z

475

U.S. Department of Energy Categorical Exclusion ...  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Condenser A-773000-HVAC-CDU-819-515. The system return ducting has an in line booster fan, A-773000-HVAC-FAN-819-502, that is out of service and no longer needed. WO 1175556...

476

U.S. Department of Energy Categorical Exclusion ...  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Condenser A-773000-HVAC- CDU-819-515. The system return ducting has an in-line booster fan, A-773000-HVAC-FAN-819-502, that is out of service and no longer needed. WO 1175556...

477

Commercial Thermal Distribution Systems FINAL REPORT  

E-Print Network (OSTI)

by the Lawrence Berkeley National Laboratory (LBNL) and Center for Environmental Design Research (CEDR Offerman of IEESF, and Graham Carter of Ove Arup, Cliff Federspiel and Nora Watanabe (CEDR) for their contributions to the CEDR project on fan research. #12;LBNL-44320 Disclaimer This document was prepared

478

Improving Building Control and System Operation Through the Continuous Commissioning® Process: A Case Study  

E-Print Network (OSTI)

Utilization of the Continuous Commissioning® process is presented in the case of the Consolidated Mission Support Center office building at Travis Air Force Base in Travis, California. The CC® process was applied to the building in early 2003. The examination of the heating, ventilating, and airconditioning (HVAC) and control systems revealed several areas where considerable improvement could be made, including air handling unit (AHU) operational parameters, terminal box and water loop operation, and Energy Management and Control System (EMCS) functionality. It also aided in the identification of mechanical systems needing repair. The optimization of the HVAC systems and advanced utilization of the EMCS reduced the combined heating and cooling energy consumption by 26% without capital intensive upgrades. Cooling energy decreased by 10%, heating energy was cut by over 40%, and fan power decreased by 28%. A hidden benefit to the implementation of the CC® process is the reduction in the human capital required to operate the building. Prior to commissioning, significant time was spent changing system operating setpoints in an attempt to save energy. These efforts are no longer required.

Redmann, N.; Liu, M.

2003-01-01T23:59:59.000Z

479

Dynamic Thermal Management for High-Performance Storage Systems  

Science Conference Proceedings (OSTI)

Thermal-aware design of disk drives is important because high temperatures can cause reliability problems. Dynamic Thermal Management (DTM) techniques have been proposed to operate the disk at the average case temperature, rather than at the worse case by modulating the activities to avoid thermal emergencies. The thermal emergencies can be caused by unexpected events, such as fan-breaks, increased inlet air temperature, etc. One of the DTM techniques is a delay-based approach that adjusts the disk seek activities, cooling down the disk drives. Even if such a DTM approach could overcome thermal emergencies without stopping disk activity, it suffers from long delays when servicing the requests. Thus, in this chapter, we investigate the possibility of using a multispeed disk-drive (called dynamic rotations per minute (DRPM)) that dynamically modulates the rotational speed of the platter for implementing the DTM technique. Using a detailed performance and thermal simulator of a storage system, we evaluate two possible DTM policies (- time-based and watermark-based) with a DRPM disk-drive and observe that dynamic RPM modulation is effective in avoiding thermal emergencies. However, we find that the time taken to transition between different rotational speeds of the disk is critical for the effectiveness of the DRPM based DTM techniques.

Kim, Youngjae [ORNL; Gurumurthi, Dr Sudhanva [University of Virginia; Sivasubramaniam, Anand [Pennsylvania State University

2012-01-01T23:59:59.000Z

480

A computer simulation appraisal of non-residential low energy cooling systems in California  

SciTech Connect

An appraisal of the potential performance of different Low Energy Cooling (LEC) systems in nonresidential buildings in California is being conducted using computer simulation. The paper presents results from the first phase of the study, which addressed the systems that can be modeled, with the DOE-2.1E simulation program. The following LEC technologies were simulated as variants of a conventional variable-air-volume system with vapor compression cooling and mixing ventilation in the occupied spaces: Air-side indirect and indirect/direct evaporative pre-cooling. Cool beams. Displacement ventilation. Results are presented for four populous climates, represented by Oakland, Sacramento, Pasadena and San Diego. The greatest energy savings are obtained from a combination of displacement ventilation and air-side indirect/direct evaporative pre-cooling. Cool beam systems have the lowest peak demand but do not reduce energy consumption significantly because the reduction in fan energy is offse t by a reduction in air-side free cooling. Overall, the results indicate significant opportunities for LEC technologies to reduce energy consumption and demand in nonresidential new construction and retrofit.

Bourassa, Norman; Haves, Philip; Huang, Joe

2002-05-17T23:59:59.000Z

Note: This page contains sample records for the topic "vav system fan" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.