Powered by Deep Web Technologies
Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


1

Method and apparatus for set point control for steam temperatures for start-up of the turbine and steam generator in unit power plants  

SciTech Connect

A method and apparatus are described for controlling the set point for steam temperatures for cold start-up of a steam generator-turbine unit wherein inlet steam temperature and turbine load absorption are steadily and substantially simultaneously increased in accordance with a predetermined relationship so as to reach their final values substantially synchronously.

Bloch, H.; Salm, M.

1978-05-23T23:59:59.000Z

2

Cooled, temperature controlled electrometer  

DOE Patents (OSTI)

A cooled, temperature controlled electrometer for the measurement of small currents. The device employs a thermal transfer system to remove heat from the electrometer circuit and its environment and dissipate it to the external environment by means of a heat sink. The operation of the thermal transfer system is governed by a temperature regulation circuit which activates the thermal transfer system when the temperature of the electrometer circuit and its environment exceeds a level previously inputted to the external variable temperature control circuit. The variable temperature control circuit functions as subpart of the temperature control circuit. To provide temperature stability and uniformity, the electrometer circuit is enclosed by an insulated housing.

Morgan, John P. (Idaho Falls, ID)

1992-01-01T23:59:59.000Z

3

Automatic temperature control  

Science Conference Proceedings (OSTI)

An automatic temperature control system is described for maintaining a preset temperature in an enclosed space in a building, comprising: heating and cooling means for conditioning the air in the enclosed space to maintain the preset temperature; exterior thermostat means outside the building for sensing ambient exterior temperature levels; interior thermostat means in the enclosed space, preset to the preset temperature to be maintained and connected with the heating and cooling means to energize the means for heating or cooling, as appropriate, when the preset temperature is reached; means defining a heat sink containing a volume of air heated by solar radiation, the volume of the heat sink being such that the temperature level therein is not affected by minor or temporary ambient temperature fluctuations; and heat sink thermostat means in the heat sink sensing the temperature in the heat sink, the heat sink thermostat means being connected in tandem with the exterior thermostat means and operative with the exterior thermostat means to switch the interior thermostat means to either a first readiness state for heating or a second readiness state for cooling, depending upon which mode is indicated by both the exterior and heat sink thermostat means, whereby the system automatically switches between heating and cooling, as required, in response to a comparison of exterior and heat sink temperatures.

Sheridan, J.P.

1986-07-22T23:59:59.000Z

4

Thermionic Converter Temperature Controller  

DOE Patents (OSTI)

A method and apparatus for controlling the temperature of a thermionic reactor over a wide range of operating power, including a thermionic reactor having a plurality of integral cesium reservoirs, a honeycomb material disposed about the reactor which has a plurality of separated cavities, a solid sheath disposed about the honeycomb material and having an opening therein communicating with the honeycomb material and cavities thereof, and a shell disposed about the sheath for creating a coolant annulus therewith so that the coolant in the annulus may fill the cavities and permit nucleate boiling during the operation of the reactor.

Shaner,B. J.; Wolf, Joseph H.; Johnson, Robert G. R.

1999-08-23T23:59:59.000Z

5

Thermionic converter temperature controller  

DOE Patents (OSTI)

A method and apparatus for controlling the temperature of a thermionic reactor over a wide range of operating power, including a thermionic reactor having a plurality of integral cesium reservoirs, a honeycomb material disposed about the reactor which has a plurality of separated cavities, a solid sheath disposed about the honeycomb material and having an opening therein communicating with the honeycomb material and cavities thereof, and a shell disposed about the sheath for creating a coolant annulus therewith so that the coolant in the annulus may fill the cavities and permit nucleate boiling during the operation of the reactor.

Shaner, Benjamin J. (McMurray, PA); Wolf, Joseph H. (Pittsburgh, PA); Johnson, Robert G. R. (Trafford, PA)

2001-04-24T23:59:59.000Z

6

Air Handling Unit Supply Air Temperature Optimization During Economizer Cycles  

E-Print Network (OSTI)

Most air handling units (AHUs) in commercial buildings have an air economizer cycle for free cooling under certain outside air conditions. During the economizer cycle, the outside air and return air dampers are modulated to seek mixing air temperature at supply air temperature setpoint. Mechanical cooling is always required when outside air temperature is higher than the supply air temperature setpoint. Generally the supply air temperature setpoint is set at 55°F for space humidity control. Actually the dehumidification is not necessary when outside air dew point is less than 55°F. Meanwhile the space may have less cooling load due to envelope heat loss and/or occupant schedule. These provide an opportunity to use higher supply air temperature to reduce or eliminate mechanical cooling and terminal box reheat. On the other hand the higher supply air temperature will require higher air flow as well as higher fan power. Therefore the supply air temperature has to be optimized to minimize the combined energy for fan, cooling and heating energy. In this paper a simple energy consumption model is established for AHU systems during the economizer and then a optimal supply air temperature control is developed to minimize the total cost of the mechanical cooling and the fan motor power. This paper presents AHU system energy modeling, supply air temperature optimization, and simulated energy savings.

Xu, K.; Liu, M.; Wang, G.; Wang, Z.

2007-01-01T23:59:59.000Z

7

Dual flow--temperature--humidity control system operating manual  

SciTech Connect

The manual contains operating, maintenance, and troubleshooting procedures for a dual flow--temperature--humidity control system used at the Lawrence Livermore Laboratory to prepare test atmospheres for industrial hygiene and air pollution studies. The system consists of two basic components: a commercially available temperature/humidity indicator unit and a specially built dual flow--temperature--humidity control module that provides two air sources controlled at the same conditions of flow, temperature, and relative humidity.

Nelson, G.O.; Taylor, R.D.

1978-12-15T23:59:59.000Z

8

A Homogenized Historical Temperature Extreme Dataset for the United States  

Science Conference Proceedings (OSTI)

A subset of stations from the daily U.S. Historical Climatology Network (HCN) is used as a basis for a historical database of temperature extreme occurrence in the United States. The dataset focuses on daily temperature occurrences that exceed (...

Arthur T. DeGaetano; Robert J. Allen; Kevin P. Gallo

2002-09-01T23:59:59.000Z

9

Verification of a level-3 diesel emissions control strategy for transport refrigeration units.  

E-Print Network (OSTI)

??Transport Refrigeration Units (TRUs) are refrigeration systems used to control the environment of temperature sensitive products while they are being transported from one place to… (more)

Shewalla, Umesh.

2010-01-01T23:59:59.000Z

10

Construction of Stratospheric Temperature Data Records from Stratospheric Sounding Units  

Science Conference Proceedings (OSTI)

In recognizing the importance of Stratospheric Sounding Unit (SSU) onboard historical NOAA polar-orbiting satellites in assessment of long-term stratospheric temperature changes and limitations in previous available SSU datasets, this study ...

Likun Wang; Cheng-Zhi Zou; Haifeng Qian

2012-04-01T23:59:59.000Z

11

METHOD OF CONTROLLING TEMPERATURE OF A THERMOELECTRIC ...  

A method of controlling the temperature of a thermoelectric generator ... Advanced Materials; Biomass and Biofuels; Building Energy Efficiency; Electricity Transmission;

12

Automated flow-temperature-humidity control system  

SciTech Connect

An automated system that controls air flow, temperature, and humidity was developed from a commercially available temperature-humidity indicator and a specially built flow-temperature-humidity control module. Parameters are set using direct-reading dials on the control module. The air flow is maintained using a mass-flow controller while process controllers connected to the indicator regulate humidity and temperature. The system will run indefinitely without need for operator intervention. If the module and indicator are calibrated properly, accurate air flows (+-2% of full scale), temperatures (+-0.3/sup 0/C), and humidities (+-2% RH) can be achieved.

Nelson, G.O.; Taylor, R.D.

1980-10-01T23:59:59.000Z

13

Supply Fan Control for Constant Air Volume Air Handling Units  

E-Print Network (OSTI)

Since terminal boxes do not have a modulation damper in constant volume (CV) air handling unit (AHU) systems, zone reheat coils have to be modulated to maintain the space temperature with constant supply airflow. This conventional control sequence causes a significant amount of reheat and constant fan power under partial load conditions. Variable Frequency Drives (VFDs) can be installed on these constant air volume systems. The fan speed can be modulated based on the maximum zone load. This paper present the procedure to control the supply fan speed and analyzes the thermal performance and major fan energy and thermal energy savings without expensive VAV retrofit through the actual system operation.

Cho, Y.; Wang, G.; Liu, M.

2007-01-01T23:59:59.000Z

14

Department of Mechanical and Nuclear Engineering Fall 2010 Breather-less Electronic Control Unit (ECU) Housing  

E-Print Network (OSTI)

Control Unit (ECU) Housing Overview Mando's current ECU housing design has a breather-hole to balance the variation in temperature found inside and outside of the housing unit. Mando's customers are concerned that debris and contaminates are entering the housing unit and damaging the ECU, so they would like to remove

Demirel, Melik C.

15

Wireless Temperature Sensors for Improved HVAC Control  

NLE Websites -- All DOE Office Websites (Extended Search)

reliable, and affordable and affordable Wireless Temperature Sensors for Improved HVAC Control An assessment of wireless sensor technology Executive Summary This Technology...

16

Instrumentation and Control Solutions for Optimizing Steam Temperature Control  

Science Conference Proceedings (OSTI)

The Electric Power Research Institute and Southern Company are executing a comprehensive program to improve main steam temperature control on drum boilers. The program includes assessing and improving the performance of instrumentation, control valves, proportional-integral-derivative control strategies, controller tuning, model predictive control (MPC), and operational aspects affecting steam temperature control. Substantial plant testing, data analysis, and other work have been conducted to date. This ...

2011-12-23T23:59:59.000Z

17

Variable temperature seat climate control system  

DOE Patents (OSTI)

A temperature climate control system comprises a variable temperature seat, at least one heat pump, at least one heat pump temperature sensor, and a controller. Each heat pump comprises a number of Peltier thermoelectric modules for temperature conditioning the air in a main heat exchanger and a main exchanger fan for passing the conditioned air from the main exchanger to the variable temperature seat. The Peltier modules and each main fan may be manually adjusted via a control switch or a control signal. Additionally, the temperature climate control system may comprise a number of additional temperature sensors to monitor the temperature of the ambient air surrounding the occupant as well as the temperature of the conditioned air directed to the occupant. The controller is configured to automatically regulate the operation of the Peltier modules and/or each main fan according to a temperature climate control logic designed both to maximize occupant comfort during normal operation, and minimize possible equipment damage, occupant discomfort, or occupant injury in the event of a heat pump malfunction.

Karunasiri, Tissa R. (Van Nuys, CA); Gallup, David F. (Pasadena, CA); Noles, David R. (Glendale, CA); Gregory, Christian T. (Alhambra, CA)

1997-05-06T23:59:59.000Z

18

Temperature-controlled molecular depolarization gates in nuclear magnetic resonance  

SciTech Connect

Down the drain: Cryptophane cages in combination with selective radiofrequency spin labeling can be used as molecular 'transpletor' units for transferring depletion of spin polarization from a hyperpolarized 'source' spin ensemble to a 'drain' ensemble. The flow of nuclei through the gate is adjustable by the ambient temperature, thereby enabling controlled consumption of hyperpolarization.

Schroder, Leif; Schroder, Leif; Chavez, Lana; Meldrum, Tyler; Smith, Monica; Lowery, Thomas J.; E. Wemmer, David; Pines, Alexander

2008-02-27T23:59:59.000Z

19

Operating high temperature (1000/sup 0/C) electrolysis demonstration unit  

SciTech Connect

Phase I of the BNL Fusion Synfuel Demonstration Program has been the successful construction and demonstration of a 100-W electrically-heated, high-temperature electrolysis unit operating at a temperature of 1000/sup 0/C. The high-temperature electrolyzer demonstration unit consists of 34 yttria-stabilized zirconia tubes contained in a 15-cm (od), 30-cm long INCONEL pressure vessel. The tubes are 25-cm long (active length), 0.64-cm (od), and coated on the inside with platinum to form the oxygen electrode and coated on the outside with nickel to form the hydrogen electrode. The 1000/sup 0/C steam is raised by electrically heating water. The system is designed to produce approx. 6 cc/s of hydrogen.

Horn, F.L.; Powell, J.R.; Fillo, J.A.

1981-01-01T23:59:59.000Z

20

Inferential control -- Part 1: Crude unit advanced controls pass accuracy and repeatability tests  

Science Conference Proceedings (OSTI)

An inferential model is one that provides a quality for which an analyzer is not available. This type of model uses readily available physical measurements -- such as temperatures, pressures, and flow rates -- to infer a quality such as kerosine flash point. The No. 2 crude distillation unit (CDU-2) at Singapore Refining Co. Pte. Ltd.'s Pulau Merlimau refinery has a nominal 130,000 b/d capacity. It produces naphtha, kerosine, diesel, and residue products from a wide range of crude blends. Over the past 12 months, extensive advanced control applications have been implemented on the unit. This first of two articles will describe the control system and its implementation. The second will outline the project's achievements, including reduced quality giveaway and increased profits. The paper describes background of the company and unit, the process, project implementation, the Infer model, model tuning, closed-loop control, feed rate maximization, and economic monitoring.

San, Y.P. (Singapore Refining Co. Ptd. Ltd., Pulau Merlimau (Singapore)); Landells, K.C.; Mackay, D.C. (BP Oil International, London (United Kingdom))

1994-11-28T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


21

The Temperature and Relative Humidity Control in Cushing Library  

E-Print Network (OSTI)

Cushing Library located on TAMU campus is a special building, which needs precise temperature and relative humidity control, because it stores a number of rare collections and memorial books. There are five air-handling units (AHUs) serving the building. This paper will concentrate the unit, which serves the book stacks. This AHU is a multiple zone, constant air volume (MZCAV) system, with reheat and direct digital control (DDC). It has a standard cooling coil, glycol cooling coil, steam humidifier, and heat recovery. The chilled water to the standard cooling coil is served by the chilled water loop on the campus. There is a glycol chiller for the glycol cooling coil for added dehumidification ability. Because of programming problems and hardware problems, the relative humidity was not controlling properly. In this paper, the new control program for temperature and relative humidity control is implemented and the energy savings from the new control program is estimated. The temperature and relative humidity are now under control.

Liu, C.; Deng, S.; Claridge, D. E.; Turner, W. D.; Bruner, H., Jr.

2002-01-01T23:59:59.000Z

22

Sensor Control Unit Light Submitted by:  

E-Print Network (OSTI)

With the growing need to conserve energy, more people are becoming conscious of energy consumption and are looking for ways to reduce costly waste associated with electricity. Though most consumers do not think about lighting until the light bulb fails or the power goes out, expenses incurred due to lighting have been found to be a large part of overall energy consumption and lighting has now become the focus of efforts aimed at reducing the high cost of electricity. The purpose of our project is to design an Automatic Light Control Device (ALCD) to help curb the high cost of internal lighting while creating a convenient effortlessly lighted environment for the consumer. Today, energy saving devices, such as occupancy or motion sensors, is used by a multiple of people for the conservation of power. Motion detectors cause lights to turn on after entering the room and off after no movement is detected for a certain amount of time. This unit is efficient; however, energy is loss due to the presence and absence of movement in a particular room by the sensor continuously activating on or off. Unneeded cycling uses more power and defeats the intended purpose of saving energy. The ALCD will save energy by eliminating false conditions, thereby minimizing light

Professor Joseph Picone; Ece Senior Design I; John Thompson; Marshalia Green; Brad Lowe; Lutrisha Johnson; Automatic Light Control Device

2001-01-01T23:59:59.000Z

23

Performance of ECM controlled VAV fan powered terminal units  

E-Print Network (OSTI)

Empirical performance models of fan airflow, primary airflow and power consumption were developed for series and parallel variable air volume fan powered terminal units. An experimental setup and test procedure were created to test the terminal units at typical design pressures and airflows. Each terminal unit observed in this study used an 8 in (20.3 cm) primary air inlet. Two fan motor control methods were considered. The primary control of interest was the electronically commutated motor (ECM) controller. Data collected were compared with previous research regarding silicon rectified control (SCR) units. Generalized models were developed for both series and parallel terminal units. Coefficients for performance models were then compared with comparable SCR controlled units. Non-linear statistical modeling was performed using SPSS software (2008). In addition to airflow and power consumption modeling, power quality was also quantified. Relationships between real power (watts) and apparent power (VA) were presented as well as harmonic frequencies and total harmonic distortion. Power quality was recorded for each ECM controlled terminal unit tested. Additional tests were also made to SCR controlled terminal units used in previous research (Furr 2006). The airflow and power consumption performance models had an R2 equal to 0.990 or greater for every terminal unit tested. An air leakage model was employed to account for leakage in the parallel designed VAV terminal units when the internal fan was turned off. For the leakage model, both ECM and SCR controlled units achieved an R2 greater than or equal to 0.918.

Cramlet, Andrew Charles

2008-08-01T23:59:59.000Z

24

Control and Room Temperature Optimization of Energy Efficient Buildings  

SciTech Connect

The building sector consumes a large part of the energy used in the United States and is responsible for nearly 40% of greenhouse gas emissions. It is therefore economically and environmentally important to reduce the building energy consumption to realize massive energy savings. In this paper, a method to control room temperature in buildings is proposed. The approach is based on a distributed parameter model represented by a three dimensional (3D) heat equation in a room with heater/cooler located at ceiling. The latter is resolved using finite element methods, and results in a model for room temperature with thousands of states. The latter is not amenable to control design. A reduced order model of only few states is then derived using Proper Orthogonal Decomposition (POD). A Linear Quadratic Regulator (LQR) is computed based on the reduced model, and applied to the full order model to control room temperature.

Djouadi, Seddik M [ORNL; Kuruganti, Phani Teja [ORNL

2012-01-01T23:59:59.000Z

25

Monthly Precipitation-Temperature Relations and Temperature Prediction over the United States  

Science Conference Proceedings (OSTI)

The monthly mean precipitation-air temperature (MMP-MMAT) relation over the United States has been examined by analyzing the observed MMP and MMAT during the period of 1931–87. The authors’ main purpose is to examine the possibility of using MMP ...

Jin Huang; Huug M. van den Dool

1993-06-01T23:59:59.000Z

26

Optimal Outside Air Control for Air Handling Units with Humidity Control  

E-Print Network (OSTI)

Most air handling units (AHUs) in commercial buildings have the (air) economizer cycle to use outside air for free cooling under certain outside air conditions. Ideally the economizer cycle is enabled if outside air enthalpy is less than return air enthalpy. During the economizer cycle, outside air flow is modulated to seek mixed air temperature at a supply air temperature set point. Since the outside air may be dry during the economizer cycle, humidification is required for AHUs with humidity control. As a result, the economizer cycle saves cooling energy but requires excessive steam for humidification. Therefore the economizer cycle may not be economical. An optimal outside air control method is developed to minimize the total cost of mechanical cooling and steam humidification. The impacts of chilled water price, steam price, and space minimum humidity set point are analyzed. Finally the optimal outside air control zones are presented on a psychrometric chart under differential energy price ratios and minimum indoor humidity set points.

Wang, G.; Liu, M.

2006-01-01T23:59:59.000Z

27

Precision control of high temperature furnaces  

DOE Patents (OSTI)

It is an object of the present invention to provide precision control of high temperature furnaces. It is another object of the present invention to combine the power of two power supplies of greatly differing output capacities in a single furnace. This invention combines two power supplies to control a furnace. A main power supply heats the furnace in the traditional manner, while the power from the auxiliary supply is introduced as a current flow through charged particles existing due to ionized gas or thermionic emission. The main power supply provides the bulk heating power and the auxiliary supply provides a precise and fast power source such that the precision of the total power delivered to the furnace is improved. Further, this invention comprises a means for high speed measurement of temperature of the process by the method of measuring the amount of current flow in a deliberately induced charged particle current.

Pollock, G.G.

1994-12-31T23:59:59.000Z

28

Flow-temperature-humidity control system operating manual. [Controlled atmospheres for industrial hygiene and air pollution studies  

SciTech Connect

A manual containing operating, maintenance, and troubleshooting procedures for the flow-temperature-humidity control system used at the Lawrence Livermore Laboratory to prepare test atmospheres for industrial hygiene and air pollution studies is presented. The system consists of two basic components: a commercially available temperature/humidity indicator unit and a specially built flow-temperature-humidity control module. Procedures are given for using the control system with a vapor generation system or with a trace-gas flowmeter to add vapor or a trace gas to the airstream after it leaves the control module.

Nelson, G.O.; Taylor, R.D.

1978-11-16T23:59:59.000Z

29

Quick setup of unit test for accelerator controls system  

SciTech Connect

Testing a single hardware unit of an accelerator control system often requires the setup of a program with graphical user interface. Developing a dedicated application for a specific hardware unit test could be time consuming and the application may become obsolete after the unit tests. This paper documents a methodology for quick design and setup of an interface focused on performing unit tests of accelerator equipment with minimum programming work. The method has three components. The first is a generic accelerator device object (ADO) manager which can be used to setup, store, and log testing controls parameters for any unit testing system. The second involves the design of a TAPE (Tool for Automated Procedure Execution) sequence file that specifies and implements all te testing and control logic. The sting third is the design of a PET (parameter editing tool) page that provides the unit tester with all the necessary control parameters required for testing. This approach has been used for testing the horizontal plane of the Stochastic Cooling Motion Control System at RHIC.

Fu, W.; D'Ottavio, T.; Gassner, D.; Nemesure, S.; Morris, J.

2011-03-28T23:59:59.000Z

30

The Geographical Distribution and Seasonality of Persistence in Monthly Mean Air Temperatures over the United States  

Science Conference Proceedings (OSTI)

Eighty years of monthly mean station temperatures are used to evaluate the persistence of monthly air temperature anomalies over the United States. The geographical and seasonal dependence of the monthly persistence are described in term of the ...

H. M. van den Dool; W. H. Klein; J. E. Walsh

1986-03-01T23:59:59.000Z

31

Observational Evidence for Reduction of Daily Maximum Temperature by Croplands in the Midwest United States  

Science Conference Proceedings (OSTI)

Climate model simulations have shown that conversion of natural forest vegetation to croplands in the United States cooled climate. The cooling was greater for daily maximum temperature than for daily minimum temperature, resulting in a reduced ...

Gordon B. Bonan

2001-06-01T23:59:59.000Z

32

The Signature of ENSO in Global Temperature and Precipitation Fields Derived from the Microwave Sounding Unit  

Science Conference Proceedings (OSTI)

Global temperature anomalies associated with ENSO are investigated, making use of a 13-year record of gridded temperature and precipitation data from the microwave sounding unit (MSU). The warm phase of the ENSO cycle during this period was ...

Elena Yulaeva; John M. Wallace

1994-11-01T23:59:59.000Z

33

Tube skin temperature prediction of catalytic reforming unit (CRU) heaters  

Science Conference Proceedings (OSTI)

The maximum duty of reformer heaters is governed by the occurance of maximum tube skin temperature of the heaters. The value of maximum tube skin temperatures of the heaters must not exceed theirs' maximum allowable design temperature. The paper highlights ... Keywords: coke formation, finite element, simulations, tube furnance

Suzana Yusup; Nguyen Duy Vinh; Nurhayati Mellon; Abdullah Hassan

2006-10-01T23:59:59.000Z

34

High temperature solid oxide fuel cell: Customer test units  

DOE Green Energy (OSTI)

There are three 25-kW class SOFC customer test unit programs; two are in Japan (utility joint ventures), one for Southern California Edison Co. The two in Japan are described: Startup, testing, modifications, and operational performance are discussed.

Ray, E.R.; Veyo, S.E.

1993-11-01T23:59:59.000Z

35

Predictive control of supply temperature in district heating systems  

E-Print Network (OSTI)

Predictive control of supply temperature in district heating systems Torben Skov Nielsen Henrik This report considers a new concept for controlling the supply temperature in district heating systems using stochastic modelling, prediction and control. A district heating systems is a di#30;cult system to control

36

Economic Evaluation of Particulate Control Technologies: Volume 1: New Units  

Science Conference Proceedings (OSTI)

Baghouses (reverse-gas, shake-deflate, and pulse-jet) and electrostatic precipitators are the principal options for controlling particulate emissions at coal-fired power plants. This report provides the latest cost information and cost models for determining the capital and O&M costs of the two technologies for various design conditions in new units.

1992-09-01T23:59:59.000Z

37

Controlled Temperature Shape Rolling of Alloy 718  

Science Conference Proceedings (OSTI)

Incentive. Program (IMIP) to develop a bar mill for high temperature alloys .... and energy can be saved and that tool life ... enough to achieve steady-state.

38

Surface Temperatures of Insulated Glazing Units: Infrared Thermography Laboratory Measurements  

NLE Websites -- All DOE Office Websites (Extended Search)

Infrared Thermography Measurements of Window Thermal Test Specimen Infrared Thermography Measurements of Window Thermal Test Specimen Surface Temperatures Brent T. Griffith ASHRAE Member, Howdy Goudey, and Dariush Arasteh P.E. ASHRAE Member Building Technologies Program Environment Energy Technologies Division Lawrence Berkeley National Laboratory University of California Berkeley CA 94720 USA August 2, 2001 This work was supported by the Assistant Secretary for Energy Efficiency and Renewable Energy, Office of Building Technology, State and Community Programs, Office of Building Systems of the U.S. Department of Energy under Contract No. DE-AC03-76SF00098. Surface Temperatures of Window Specimens: Infrared Thermography Laboratory Measurements Brent T. Griffith 1 , Howdy Goudey, and Dariush Arasteh

39

Factors Influencing the Cold-Season Diurnal Temperature Range in the United States  

Science Conference Proceedings (OSTI)

This study examines the contributions of sunshine duration, snow cover extent, and the atmospheric circulation to variations of the cold-season diurnal temperature range (DTR) in eight regions of the contiguous United States. The goal of the ...

Imke Durre; John M. Wallace

2001-08-01T23:59:59.000Z

40

An Assessment of Operational TIROS–N Temperature Retrievals over the United States  

Science Conference Proceedings (OSTI)

For a 14-day period in late March and early April 1979, TIROS-N operational soundings have been compared with independent temperature analyses produced by the National Meteorological Center. Over the United States and southern Canada, analyzed ...

Thomas W. Schlatter

1981-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


41

Difficulties in Obtaining Reliable Temperature Trends: Reconciling the Surface and Satellite Microwave Sounding Unit Records  

Science Conference Proceedings (OSTI)

A chronic difficulty in obtaining reliable climate records from satellites has been changes in instruments, platforms, equator-crossing times, and algorithms. The microwave sounding unit (MSU) tropospheric temperature record has overcome some of ...

James W. Hurrell; Kevin E. Trenberth

1998-05-01T23:59:59.000Z

42

Reconciling the Spatial Distribution of the Surface Temperature Trends in the Southeastern United States  

Science Conference Proceedings (OSTI)

This study attempts to explain the considerable spatial heterogeneity in the observed linear trends of monthly mean maximum and minimum temperatures (Tmax and Tmin) from station observations in the southeastern (SE) United States (specifically ...

V. Misra; J.-P. Michael; R. Boyles; E. P. Chassignet; M. Griffin; J. J. O’Brien

2012-05-01T23:59:59.000Z

43

Comparison of Tropospheric Temperature Derived from the Microwave Sounding Unit and the National Meteorological Center Analysis  

Science Conference Proceedings (OSTI)

The Microwave Sounding Units (MSU) aboard the NOAA series of polar-orbiting satellites (TIROS-N to NOAA-12) have provided stable and precise measurements of vertically integrated atmospheric temperature since December 1978. Comparisons are made ...

Alan N. Basist; Chester F. Ropelewski; Norman C. Grody

1995-04-01T23:59:59.000Z

44

Error Structure and Atmospheric Temperature Trends in Observations from the Microwave Sounding Unit  

Science Conference Proceedings (OSTI)

The Microwave Sounding Unit (MSU) onboard the National Oceanic and Atmospheric Administration polar-orbiting satellites measures the atmospheric temperature from the surface to the lower stratosphere under all weather conditions, excluding ...

Cheng-Zhi Zou; Mei Gao; Mitchell D. Goldberg

2009-04-01T23:59:59.000Z

45

Recent Trends in Maximum and Minimum Temperature Threshold Exceedences in the Northeastern United States  

Science Conference Proceedings (OSTI)

Changes in the annual number of daily maximum and minimum temperature threshold exceedences between 1951 and 1993 are assessed at a network of 22 primarily rural sites in the northeastern United States. After adjusting the annual time series for ...

Arthur T. DeGaetano

1996-07-01T23:59:59.000Z

46

Verification of Surface Temperature Forecasts from the National Digital Forecast Database over the Western United States  

Science Conference Proceedings (OSTI)

Experimental gridded forecasts of surface temperature issued by National Weather Service offices in the western United States during the 2003/04 winter season (18 November 2003–29 February 2004) are evaluated relative to surface observations and ...

David T. Myrick; John D. Horel

2006-10-01T23:59:59.000Z

47

Biennial Variations in Surface Temperature over the United States as Revealed by Singular Decomposition  

Science Conference Proceedings (OSTI)

Surface temperature variations over the contiguous United States during the period 1931–75 are examined using mean monthly averages for the 344 climate divisions. This data matrix is decomposed into orthogonal components using the method of ...

Eugene M. Rasmusson; Phillip A. Arkin; Wen-Yuan Chen; John B. Jalickee

1981-03-01T23:59:59.000Z

48

Decreasing Diurnal Temperature Range in the United States and Canada from 1941 through 1980  

Science Conference Proceedings (OSTI)

An appreciable number of nonurban stations in the United States and Canada have been identified with statistically significant (at the 90% level) decreasing trends in the monthly mean diurnal temperature range between 1941–80. The percentage of ...

T. R. Karl; G. Kukla; J. Gavin

1984-11-01T23:59:59.000Z

49

Optimal control of a bleed air temperature regulation system.  

E-Print Network (OSTI)

??This thesis investigates temperature control of an aircraft engine bleed air system, aiming at reducing ram air usage to reduce fuel consumption while maintaining fast… (more)

Shang, Lan

2007-01-01T23:59:59.000Z

50

High performance internal reforming unit for high temperature fuel cells  

DOE Patents (OSTI)

A fuel reformer having an enclosure with first and second opposing surfaces, a sidewall connecting the first and second opposing surfaces and an inlet port and an outlet port in the sidewall. A plate assembly supporting a catalyst and baffles are also disposed in the enclosure. A main baffle extends into the enclosure from a point of the sidewall between the inlet and outlet ports. The main baffle cooperates with the enclosure and the plate assembly to establish a path for the flow of fuel gas through the reformer from the inlet port to the outlet port. At least a first directing baffle extends in the enclosure from one of the sidewall and the main baffle and cooperates with the plate assembly and the enclosure to alter the gas flow path. Desired graded catalyst loading pattern has been defined for optimized thermal management for the internal reforming high temperature fuel cells so as to achieve high cell performance.

Ma, Zhiwen (Sandy Hook, CT); Venkataraman, Ramakrishnan (New Milford, CT); Novacco, Lawrence J. (Brookfield, CT)

2008-10-07T23:59:59.000Z

51

Complex Quality Control of Significant Level Rawinsonde Temperatures  

Science Conference Proceedings (OSTI)

Rawinsonde heights and temperatures have been quality controlled using complex quality control at the National Centers for Atmospheric Prediction since December 1988 when an algorithm using only hydrostatic checking was introduced for the ...

William G. Collins

1998-02-01T23:59:59.000Z

52

Southeastern United States Daily Temperature Ranges Associated with the El Niño–Southern Oscillation  

Science Conference Proceedings (OSTI)

The daily temperature range (DTR), daily maximum minus minimum temperature, at 290 Southeast United States stations is examined with respect to the warm and cold phases of the El Niño–Southern Oscillation (ENSO) for the period of 1948–2009. A ...

Daniel M. Gilford; Shawn R. Smith; Melissa L. Griffin; Anthony Arguez

53

Thermostat response and room temperature control  

Science Conference Proceedings (OSTI)

This article examines the impact to thermal comfort of the operation of the room thermostat. The topics of the article include types of thermostat response, reset response, proportional response, digital systems, system response, verification of building temperatures, thermal comfort analysis, and productivity costs of implementing mandated setpoints.

Int-Hout, D. (Carrier Corp., Syracuse, NY (United States))

1994-01-01T23:59:59.000Z

54

CONTROL OF SUPPLY TEMPERATURE IN DISTRICT HEATING SYSTEMS  

E-Print Network (OSTI)

CONTROL OF SUPPLY TEMPERATURE IN DISTRICT HEATING SYSTEMS T.S. Nielsen, H. Madsen Informatics the supply temperature in district heating systems using stochastic modelling, prediction and control at Roskilde Varmeforsyning. The results obtained for the Roskilde district heating utility are evaluated

55

Self-Correcting HVAC Controls: Algorithms for Sensors and Dampers in Air-Handling Units  

SciTech Connect

This report documents the self-correction algorithms developed in the Self-Correcting Heating, Ventilating and Air-Conditioning (HVAC) Controls project funded jointly by the Bonneville Power Administration and the Building Technologies Program of the U.S. Department of Energy. The algorithms address faults for temperature sensors, humidity sensors, and dampers in air-handling units and correction of persistent manual overrides of automated control systems. All faults considered create energy waste when left uncorrected as is frequently the case in actual systems.

Fernandez, Nicholas; Brambley, Michael R.; Katipamula, Srinivas

2009-12-31T23:59:59.000Z

56

The Main Steam Temperature Cascade Control of High Order Differential of Feedback Controller  

Science Conference Proceedings (OSTI)

The main steam temperature of boiler is a big time-lag signal, and the great change of its dynamic characteristics occurs with the load change. In addition, the main steam temperature control is particularly significant for the safety and economic operation ... Keywords: main steam temperature, high order differentiator, high order differential feedback controller, cascade control

Xue Wei; Mu Jingjing; Jia Hongyan; Ye Fei

2010-10-01T23:59:59.000Z

57

A Daily Soil Temperature Dataset and Soil Temperature Climatology of the Contiguous United States  

Science Conference Proceedings (OSTI)

Although affected by atmospheric circulations, variations in soil temperature result primarily from the radiation and sensible and latent heat exchanges at the surface and heat transfer in the soils of different thermal properties. Thus, soil ...

Qi Hu; Song Feng

2003-08-01T23:59:59.000Z

58

Nonlinear robust temperature-humidity control in livestock buildings  

Science Conference Proceedings (OSTI)

The physical environment of farm animals inside livestock buildings is primarily characterised by hygro-thermal parameters and air quality. These parameters are influenced by the interaction with the outdoor situation on one hand, and the livestock, ... Keywords: Humidity control, Livestock buildings, Robust control, Temperature control

A. G. Soldatos; K. G. Arvanitis; P. I. Daskalov; G. D. Pasgianos; N. A. Sigrimis

2005-12-01T23:59:59.000Z

59

A Comparison of SNOTEL and GHCN/CRU Surface Temperatures with Free-Air Temperatures at High Elevations in the Western United States: Data Compatibility and Trends  

Science Conference Proceedings (OSTI)

This paper compares high-elevation surface temperatures based on the Global Historical Climate Network/Climatic Research Unit (GHCN/CRU) and snow telemetry (SNOTEL) datasets, with simultaneous free-air equivalent temperatures, interpolated from ...

N. C. Pepin; M. Losleben; M. Hartman; K. Chowanski

2005-06-01T23:59:59.000Z

60

Characteristics of Temperature Depressions Associated with Snow Cover across the Northeast United States  

Science Conference Proceedings (OSTI)

Daily snow cover and temperature data are collected for a network of 91 stations covering the northeast United States and the association between the two is explored. Observations are examined for the six-month winter season, November?April, for ...

Daniel J. Leathers; Andrew W. Ellis; David A. Robinson

1995-02-01T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


61

Recent Temperature Changes during Overcast and Clear Skies in the United States  

Science Conference Proceedings (OSTI)

A network of 14 nonurban stations was used as a first step toward understanding the character of change of daily temperature between 1948 and 1983 across the United States. Overall, in the eastern two-thirds of the country more stations tend to ...

T. R. Karl; G. Kukla; J. Gavin

1987-06-01T23:59:59.000Z

62

Variability Common to Global Sea-Surface Temperatures and Runoff in the Conterminous United States  

Science Conference Proceedings (OSTI)

Singular value decomposition (SVD) is used to identify the variability common to global sea-surface temperatures (SSTs) and water-balance-modeled water-year (WY) runoff in the conterminous United States (US) for the 1900 through 2012 period. Two ...

Gregory J. McCabe; David M. Wolock

63

An Example of Temperature Structure Differences in Two Cyclone Systems Derived from the Advanced Microwave Sounder Unit  

Science Conference Proceedings (OSTI)

The Advanced Microwave Sounding Unit (AMSU) has better horizontal resolution and vertical temperature sounding abilities than its predecessor, the Microwave Sounding Unit (MSU). Those improved capabilities are demonstrated with observations of ...

John A. Knaff; Raymond M. Zehr; Mitchell D. Goldberg; Stanley Q. Kidder

2000-08-01T23:59:59.000Z

64

Temperature control system for a J-module heat exchanger  

DOE Patents (OSTI)

The level of primary fluid is controlled to change the effective heat transfer area of a heat exchanger utilized in a liquid metal nuclear power plant to eliminate the need for liquid metal control valves to regulate the flow of primary fluid and the temperature of the effluent secondary fluid.

Basdekas, Demetrios L. (Rockville, PA); Macrae, George (Murrysville, PA); Walsh, Joseph M. (Pittsburgh, PA)

1978-01-01T23:59:59.000Z

65

Analysis and control of a nonlinear boiler-turbine unit Wen Tan a,*,1  

E-Print Network (OSTI)

Analysis and control of a nonlinear boiler-turbine unit Wen Tan a,*,1 , Horacio J. Marquez b, and the concept is applied to a boiler-turbine unit to analyze its dynamics. It is shown that the unit shows. Keywords: Boiler-turbine unit; Nonlinearity measure; Gap metric; Anti-windup bumpless transfer techniques

Marquez, Horacio J.

66

EFFECT OF TEMPERATURE AND HUMIDITY ON FORMALDEHYDE EMISSIONS IN TEMPORARY HOUSING UNITS  

SciTech Connect

The effect of temperature and humidity on formaldehyde emissions from samples collected from temporary housing units (THUs) was studied. The THUs were supplied by the U.S Federal Emergency Management Administration (FEMA) to families that lost their homes in Louisiana and Mississippi during the Hurricane Katrina and Rita disasters. Based on a previous study 1, 2, four of the composite wood surface materials that dominated contributions to indoor formaldehyde were selected to analyze the effects of temperature and humidity on the emission factors. Humidity equilibration experiments were carried out on two of the samples to determine how long the samples take to equilibrate with the surrounding environmental conditions. Small chamber experiments were then conducted to measure emission factors for the four surface materials at various temperature and humidity conditions. The samples were analyzed for formaldehyde via high performance liquid chromatography. The experiments showed that increases in temperature or humidity contributed to an increase in emission factors. A linear regression model was built using natural log of percentage relative humidity (RH) and inverse of temperature (in K) as predictor variables, and natural log of emission factors as the target variable. The coefficients of both inverse temperature and log relative humidity with log emission factor were found to be statistically significant for all the samples at the 95percent confidence level. This study should assist to retrospectively estimate indoor formaldehyde exposures of occupants of temporary housing units (THUs).

Parthasarathy, Srinandini; Maddalena, Randy L.; Russell, Marion L.; Apte, Michael G.

2010-04-01T23:59:59.000Z

67

Measurement of Temperature and Velocity Fields in a Heater Unit by Liquid Crystal Thermometry and Particle Image Velocimetry  

Science Conference Proceedings (OSTI)

Temperature and velocity fields in a heating unit for automobiles are measured through a model experiment in water tunnel using flow visualizations and image analysis to investigate the mixing mechanism of the flow that has passed through the heater ... Keywords: flow measurement, flow visualization, heater unit, liquid crystal, particle image velocimetry, temperature measurement

N. Fujisawa; H. Ikeda; R. Saito; M. Yokota

2000-08-01T23:59:59.000Z

68

The Detector Control Unit An ASIC for the monitoring of the CMS silicon tracker  

E-Print Network (OSTI)

The Detector Control Unit (DCU) is an ASIC developed as the central building block of a monitoring system for the CMS Tracker. Leakage currents in the Silicon detectors, power supply voltages of the readout electronics and local temperatures will be monitored in order to guarantee safe operating conditions during the 10-years lifetime in the LHC environment. All these measurements can be performed by an A/D converter preceded by an analog multiplexer and properly interfaced to the central control system. The requirements in terms of radiation tolerance, low-power dissipation and integration with the rest of the system led to the design of a custom integrated circuit. Its structure and characteristics are described in this paper. (6 refs).

Magazzù, G; Moreira, P

2004-01-01T23:59:59.000Z

69

Room Temperature Control During Season Switchover with Single Duct Variable Air Volume System Without Reheat  

E-Print Network (OSTI)

The Langford “A” building houses the College of Architecture on TAMU campus. There are ten singleduct variable air volume (VAV) air-handling units (AHUs) without reheat serving the building. The local pneumatic thermostats modulate the dampers of VAV boxes to maintain room temperature at their setpoints. The thermostat action is switched from direct acting (DA) to reverse acting (RA) when the season changes from fall to winter and vice versa from winter to spring, based on the out side air temperature, when season changes. This results in various parts of the building ether too cold or too hot during the season change. This paper presents that the thermostat action will be switched according to cooling loads or discharge air temperature, instead of outside air temperature. For the interior zone, thermostat action does not need to be switched at all. The comfort is improved and savings is achieved by the new control scheme. Because some air-handling units (AHUs) serve both interior and exterior zones, this system never worked as intended. The system must be modified to have zone reheat and the AHUs discharge air temperature is set below dew point for humidity control.

Liu, C.; Deng, S.; Claridge, D. E.; Turner, W. D.; Bruner, H.

2003-01-01T23:59:59.000Z

70

Improvement of air handling unit control performance using reinforcement learning  

Science Conference Proceedings (OSTI)

Most common applications using neural networks for control problems are the automatic controls using the artificial perceptual function. These control mechanisms are similar to those of the intelligent and pattern recognition control of an adaptive method ...

Sangjo Youk; Moonseong Kim; Yangsok Kim; Gilcheol Park

2006-08-01T23:59:59.000Z

71

Coordinated controller tuning of a boiler turbine unit with new binary particle swarm optimization algorithm  

Science Conference Proceedings (OSTI)

Coordinated controller tuning of the boiler turbine unit is a challenging task due to the nonlinear and coupling characteristics of the system. In this paper, a new variant of binary particle swarm optimization (PSO) algorithm, called probability based ... Keywords: Coordinated control, boiler turbine unit, controller tuning, particle swarm optimization (PSO), probability based binary particle swarm optimization (PBPSO)

Muhammad Ilyas Menhas; Ling Wang; Min-Rui Fei; Cheng-Xi Ma

2011-05-01T23:59:59.000Z

72

A plug and play framework for an HVAC air handling unit and temperature sensor auto recognition technique.  

E-Print Network (OSTI)

??A plug and play framework for an HVAC air handling unit control system is proposed in this study. This is the foundation and the first… (more)

Zhou, Xiaohui

2010-01-01T23:59:59.000Z

73

Exploring Maximum Humidity Control and Energy Conservation Opportunities with Single Duct Single Zone Air-Handling Units  

E-Print Network (OSTI)

Humidity control for single-duct single-zone (SDSZ) constant volume air handling units is known to be a challenge. The operation of these systems is governed by space temperature only. Under mild weather conditions, discharge air temperature can get much higher than the space dew point and the dehumidification capability of the system is diminished. Buildings served by this type of air handler often experience exceptionally high humidity levels under humid weather conditions. Many potential solutions and improvements exist. However, these solutions require system modifications or upgrades and therefore are less attractive to some facility owners. A Critical Humidity Control Program (CHCP) was developed to change the normal control sequence of the air-handling units during high humidity periods to help improve the moisture removal capability of the system. The program was not designed to solve the problem completely, but the overall humidity levels can be lowered and controlled within a reasonably low range (58% - 65%) for a significant part of the high humidity seasons. This approach is relatively easy to implement and does not require any hardware changes. This paper also summarizes various potential solutions to improve humidity control for SDSZ units. The advantages and disadvantages for each solution are compared.

Zhou, J.; Wei, G.; Turner, W. D.; Deng, S.; Claridge, D.

2006-01-01T23:59:59.000Z

74

Application of Phasor Measurement Units for Controlled System Separation  

Science Conference Proceedings (OSTI)

Controlled system separation is considered the final line of defense to save a power transmission system against a catastrophic blackout under severe disturbances8212for example, cascading failures. In a controlled manner, the system is separated into sustainable electrical islands, which can be resynchronized later to restore the system. This technical report gives an overview of controlled system separation and then proposes a practical controlled system separation scheme utilizing phasor measurement u...

2009-11-25T23:59:59.000Z

75

Temperature Evolution and Oxide Growth in Waterwall Tubes of Supercritical Units  

SciTech Connect

In order to understand the failures in some waterwall tubes of supercritical steam boilers, an analysis is required to estimate the temperature of the waterwall tubes and the oxide growth in these tubes. A review on the thermophysical properties of oxide grown in waterwall tubes was conducted. Specimens of waterwall tubes associated with thermal fatigue cracking were obtained and microstructural analyses, using metallographic and electron-optical techniques such as SEM and electron-probe microanalysis, were performed. A computer model is being developed to estimate the maximum temperature in waterwall tubes by considering several phenomena that take place in supercritical units. The comprehensive model includes the following boiler operation features and phenomena: oxide growth, distribution of the heat flux on the waterwall tube as a function of height distance, variation of steam flow rate due to load variation, variation of heat flux due to load variation, and variation of the heat transfer coefficient with steam conditions and furnace heat flux. The model will handle the transition subcritical-to-supercritical and will account for the heat transfer deterioration phenomena in tubes. The tube regions with deteriorated heat transfer regimes will be identified. The temperatures of steam, metal, and oxide will be obtained as a function of the height distance in the boiler. The mixing effects of the steam from different waterwall tubes and subsequent fluid dynamics effects on the heat transfer will be considered. The new model will enable the prediction of the maximum metal temperature for realistic boiler operation schedule, which include transitions from full-to-low loads. Based on the estimated data for the steam temperature, metal temperature, and oxide thickness, regions of the waterwall tubes that are exposed to the most severe conditions will be identified.

Sabau, Adrian S [ORNL; Wright, Ian G [ORNL; Zhang, Wei [ORNL; Pint, Bruce A [ORNL; Unocic, Kinga A [ORNL

2010-01-01T23:59:59.000Z

76

Temperature Control of Continued Hyperthermic Celiac Perfusion Based on Generalized Predictive Self-Tuning Control  

Science Conference Proceedings (OSTI)

On the basis of the characteristic and requirement of the continued hyperthermic celiac perfusion (CHCP) temperature process. A model is set up, the generalized predictive self-tuning control (GPSC) algorithm is used to control the whole system to get ... Keywords: CHCP, GPSC, Modeling

Xing-hui Zhang; Hui-min Jiang; Zhao-lin Gu; Zeng-qiang Chen

2008-10-01T23:59:59.000Z

77

Impact of Sea Surface Temperature and Soil Moisture on Summer Precipitation in the United States Based on Observational Data  

Science Conference Proceedings (OSTI)

This study examines the impact of sea surface temperature (SST) and soil moisture on summer precipitation over two regions of the United States (the upper Mississippi River basin and the Great Plains) based on data from observation and observation-...

Rui Mei; Guiling Wang

2011-10-01T23:59:59.000Z

78

ENSO Influence on Intraseasonal Extreme Rainfall and Temperature Frequencies in the Contiguous United States: Implications for Long-Range Predictability  

Science Conference Proceedings (OSTI)

Potential ENSO-related predictability of wintertime daily extreme precipitation and temperature frequencies is investigated. This is done empirically using six decades of daily data at 168 stations distributed over the contiguous United States. ...

Alexander Gershunov

1998-12-01T23:59:59.000Z

79

Dependence of Extreme Daily Maximum Temperatures on Antecedent Soil Moisture in the Contiguous United States during Summer  

Science Conference Proceedings (OSTI)

The paper presents an analysis of the dependence of summertime daily maximum temperature on antecedent soil moisture using daily surface observations from a selection of stations in the contiguous United States and daily time series of soil ...

Imke Durre; John M. Wallace; Dennis P. Lettenmaier

2000-07-01T23:59:59.000Z

80

Observations of the Relationship between 700-mb Temperatures and Severe Weather Reports across the Contiguous United States  

Science Conference Proceedings (OSTI)

The relationship between 700-mb temperatures and convective severe storm reports is examined using data from 1993 to 2006 for the contiguous United States. Severe storm reports are used as a rough “proxy” for the occurrence of deep moist ...

Matthew J. Bunkers; John R. Wetenkamp Jr.; Jeffrey J. Schild; Anthony Fischer

2010-04-01T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


81

Robust Controller Design for Simultaneous Control of Throttle Pressure and Megawatt Output in a Power Plant Unit  

Science Conference Proceedings (OSTI)

Recently proposed (( and (-synthesis controller design methodologies permit the design of high-performance control systems for plants that are difficult to model accurately. The work summarized in this report assesses the benefits of the (( and (-synthesis controllers for the simultaneous control of throttle pressure and megawatt output in a power plant unit, while also serving to clarify the (( and (-synthesis design methods by an example.

1999-02-25T23:59:59.000Z

82

Microprocessor-controlled photovoltaic-array loading unit  

DOE Green Energy (OSTI)

Described is a microprocessor-controlled test system in operation at the Photovoltaics Advanced Systems Test Facility located at Sandia National Laboratories. The test system is designed to measure the total energy output of photovoltaic arrays. The theory, installation, operation, and calibration of the test system are described.

Russell, D.F.

1982-08-01T23:59:59.000Z

83

Design and implementation of portable data acquisition unit in process control and supervision applications  

Science Conference Proceedings (OSTI)

Paper deals with design and implementation of portable data acquisition unit based on 8-bit microcontroller Freescale 68HC908GP32 in process control and supervision applications. Its hardware design is adopted to fulfill high reliability and immunity ... Keywords: 68HC908GP32, Matlab, control web, data acquisition, process control, program libraries

Petr Dostálek; Vladimír Vasek; Jan Dolinay

2008-09-01T23:59:59.000Z

84

Climatic Controls and Spatial Variations of Precipitation in the Western United States  

Science Conference Proceedings (OSTI)

The western United States is characterized by complex seasonal precipitation regimes due to the hierarchy of climatic controls that operate at different spatial scales. A climatology of month to month changes in precipitation, using data from ...

Cary J. Mock

1996-05-01T23:59:59.000Z

85

Development of an Accurate Feed-Forward Temperature Control Tankless Water Heater  

SciTech Connect

The following document is the final report for DE-FC26-05NT42327: Development of an Accurate Feed-Forward Temperature Control Tankless Water Heater. This work was carried out under a cooperative agreement from the Department of Energy's National Energy Technology Laboratory, with additional funding from Keltech, Inc. The objective of the project was to improve the temperature control performance of an electric tankless water heater (TWH). The reason for doing this is to minimize or eliminate one of the barriers to wider adoption of the TWH. TWH use less energy than typical (storage) water heaters because of the elimination of standby losses, so wider adoption will lead to reduced energy consumption. The project was carried out by Building Solutions, Inc. (BSI), a small business based in Omaha, Nebraska. BSI partnered with Keltech, Inc., a manufacturer of electric tankless water heaters based in Delton, Michigan. Additional work was carried out by the University of Nebraska and Mike Coward. A background study revealed several advantages and disadvantages to TWH. Besides using less energy than storage heaters, TWH provide an endless supply of hot water, have a longer life, use less floor space, can be used at point-of-use, and are suitable as boosters to enable alternative water heating technologies, such as solar or heat-pump water heaters. Their disadvantages are their higher cost, large instantaneous power requirement, and poor temperature control. A test method was developed to quantify performance under a representative range of disturbances to flow rate and inlet temperature. A device capable of conducting this test was designed and built. Some heaters currently on the market were tested, and were found to perform quite poorly. A new controller was designed using model predictive control (MPC). This control method required an accurate dynamic model to be created and required significant tuning to the controller before good control was achieved. The MPC design was then implemented on a prototype heater that was being developed simultaneously with the controller development. (The prototype's geometry and components are based on a currently marketed heater, but several improvements have been made.) The MPC's temperature control performance was a vast improvement over the existing controller. With a benchmark for superior control performance established, five additional control methods were tested. One problem with MPC control is that it was found to be extremely difficult to implement in a TWH, so that it is unlikely to be widely adopted by manufacturers. Therefore the five additional control methods were selected based on their simplicity; each could be implemented by a typical manufacturer. It was found that one of these methods performed as well as MPC, or even better under many circumstances. This method uses a Feedback-Compensated Feed-Forward algorithm that was developed for this project. Due to its simplicity and excellent performance this method was selected as the controller of choice. A final higher-capacity prototype heater that uses Feedback-Compensated Feed-Forward control was constructed. This prototype has many improvements over the currently marketed heaters: (1) excellent control; (2) a modular design that allows for different capacity heaters to be built easily; (3) built-in fault detection and diagnosis; (4) a secondary remote user-interface; and (5) a TRIAC switching algorithm that will minimize 'flicker factor'. The design and engineering of this prototype unit will allow it to be built without an increase in cost, compared with the currently marketed heater. A design rendering of the new product is shown below. It will be launched with a new marketing campaign by Keltech in early 2009.

David Yuill

2008-06-30T23:59:59.000Z

86

Based on embedded database greenhouse temperature and humidity intelligent control system  

Science Conference Proceedings (OSTI)

The article based on embedded database of greenhouse temperature and humidity control system intelligent. Put forward by embedded database system set up in an ideal environment for data greenhouse temperature and humidity control, greenhouse crops in ... Keywords: control, data filtering, embedded database, greenhouse, microcontrollers, temperature and humidity

Sun Rong-gao; Wan Zhong; Sun De-chao

2009-01-01T23:59:59.000Z

87

Origins and Levels of Monthly and Seasonal Forecast Skill for United States Surface Air Temperatures Determined by Canonical Correlation Analysis  

Science Conference Proceedings (OSTI)

Statistical techniques have been used to study the ability of SLP, SST and a form of persistence to forecast cold/warm season air temperatures over the United States and to determine the space–time evolution of these fields that give rise to ...

T. P. Barnett; R. Preisendorfer

1987-09-01T23:59:59.000Z

88

A field programmable gate array unit for the diagnosis and control of neoclassical tearing modes on MAST  

E-Print Network (OSTI)

A field programmable gate array unit for the diagnosis and control of neoclassical tearing modes OF SCIENTIFIC INSTRUMENTS 83, 10E312 (2012) A field programmable gate array unit for the diagnosis and control, University of York, York YO10 5DD, United Kingdom 2 EURATOM/CCFE Fusion Association, Culham Science Centre

89

Changes in 20th century extreme temperature and precipitation over the western United States based on observations and regional climate model simulations  

Science Conference Proceedings (OSTI)

Trends in extreme temperature and precipitation in two regional climate model simulations forced by two global climate models are compared with observed trends over the western United States. The observed temperature extremes show substantial and ...

Valérie Dulière; Yongxin Zhang; Eric P. Salathé Jr.

90

Surface Water Temperatures At Shore Stations, United States West Coast 1974  

E-Print Network (OSTI)

that monitors the cooling intake water for the generators.takes daily water temperatures at the intake pipe to theirof hot water is outside the bay, the intake temperatures are

Scripps Institution of Oceanography

1977-01-01T23:59:59.000Z

91

Surface Water Temperatures At Shore Stations, United States West Coast 1973  

E-Print Network (OSTI)

that monitors the cooling intake water for the generators.takes daily water temperatures at the intake pipe to theirof hot water is outside the bay, the intake temperatures are

Scripps Institution of Oceanography

1975-01-01T23:59:59.000Z

92

Experience in the installation of a microprocessor system for controlling converter units of the Vyborg substation  

SciTech Connect

The experience in the installation of modern digital systems for controlling converter units at the Vyborg converter substation on the basis of advanced microprocessor devices is considered. It is shown that debugging of a control and protection system on mathematical and physical models does not guarantee optimum control of actual converter devices. Examples of advancing the control and protection system are described, the necessity for which has become obvious in tests of actual equipment. Comparison of oscillograms of processes before optimization of the control system and after its optimization and adjustment shows that the digital control system makes it possible to improve substantially the algorithms of control and protection in the short term and without changing the hardware component.

Gusakovskii, K. B.; Zmaznov, E. Yu.; Katantsev, S. V.; Mazurenko, A. K.; Mestergazi, V. A.; Prochan, G. G.; Funtikova, S. F. [High Voltage Direct Current Power Transmission Research Institute (NIIPT) (Russian Federation)

2006-01-15T23:59:59.000Z

93

Urban Influences on Surface Temperatures in the Southwestern United States during Recent Decades  

Science Conference Proceedings (OSTI)

Trends of surface temperature at rapidly growing urban sites during the last three to five decades are compared to those at non-urban sites, temperatures at 70 kPa, and sea surface temperature at a coastal Pacific station. Significant urban heat ...

Daniel R. Cayan; Arthur V. Douglas

1984-11-01T23:59:59.000Z

94

Genetic-Algorithm-Based Adaptive Control of Superheat Steam Temperature on a Power Plant Boiler  

Science Conference Proceedings (OSTI)

Superheat steam temperature control is critical to the normal and optimal operation of a power plant. Usually, cascade Proportional Integral Derivative (PID) control system is introduced to regulate the superheat temperature with the PID parameters fixed ... Keywords: Genetic Algorithm, Adaptive Control, Recursive Least Squares, Robustness

Yonghong Huang; Xuejun Yang

2008-12-01T23:59:59.000Z

95

Modeling of Electronically Commutated Motor Controlled Fan-powered Terminal Units  

E-Print Network (OSTI)

Empirical models of airflow and power consumption were developed for series and parallel variable air volume fan powered terminal units (FPTUs). An experimental setup and test procedure were developed to test the terminal units over typical operating ranges. The terminal units in this study used either an 8 in. (20.32 cm) or a 12 in. (30.48 cm) primary air inlet. All terminal units utilized electronically commutated motor (ECM) controllers. Data collected were compared against previous data collected for silicon controlled rectifier (SCR) units. Generalized models were developed for both series and parallel units, and compared against models developed for SCR units. In addition to the performance modeling, power factor and power quality data were also collected for each terminal unit. The power quality analysis included recording and analyzing harmonic distortion for current, voltage, and power up to the 25th harmonic. The total harmonic distortion (THD) was also recorded and presented. For the series terminal units, models were developed for fan airflow, fan power, and primary airflow. The models for fan airflow all had R2 values above 0.987. The models for fan power all had R2 values above 0.968. The models for primary airflow all had R2 values above 0.895. For the parallel terminal units, models were developed for leakage, fan airflow, fan power, and primary airflow. All of the leakage models had R2 values above 0.826. All of the fan airflow models had R2 values above 0.955. All of the fan power models had R2 values above 0.922. All of the primary airflow models had R2 values above 0.872. The real power THD was below 1.5 percent for both series and parallel FPTUs. The current THD ranged from 84 percent to 172 percent for series FPTUs and from 83 percent to 183 percent for parallel FPTUs. The voltage THD was below 1.4 percent for both series and parallel FPTUs. The performance models developed will help improve the accuracy of building energy simulation programs for heating, ventilation, and air conditioning (HVAC) systems utilizing ECM controlled FPTUs. Increasing the accuracy of these simulations will allow HVAC system designers to better optimize their designs for specific building types in a wide variety of climates.

Edmondson, Jacob Lee

2009-12-01T23:59:59.000Z

96

Model reference adaptive temperature control of the electromagnetic oven process in manufacturing process  

Science Conference Proceedings (OSTI)

Nowadays, the electromagnetic ovens are used for heating the component assembly of electronic manufacturing. The control systems of the electromagnetic ovens are feedback control system and PID controller are used to control their temperature. This process ... Keywords: control theory, response optimization and model reference adaptive system

Jiraphon Srisertpol; Supot Phungphimai

2010-02-01T23:59:59.000Z

97

Optimal Terminal Box Control for Single Duct Air-Handling Units  

E-Print Network (OSTI)

Terminal boxes maintain room temperature by modulating supply air temperature and airflow in building HVAC systems. Terminal boxes with conventional control sequences often supply inadequate airflow to a conditioned space, resulting in occupant discomfort, or provide excessive airflow that wastes significant reheat energy. In this study, an optimal terminal box airflow control sequence was developed to improve indoor ventilation and reduce energy consumption. The developed control sequence was applied in an office building air conditioning system. Improvements in indoor thermal comfort and energy reduction were verified through measurement. The results show that the optimal control sequence can stably maintain thermal environment, satisfy comfort standards and reduce energy consumption compared to the conventional control sequence.

Cho, Y.; Vondal, J.; Wang, G.; Liu, M.

2006-01-01T23:59:59.000Z

98

Effects of Temperature and Precipitation Variability on Snowpack Trends in the Western United States  

Science Conference Proceedings (OSTI)

Recent studies have shown substantial declines in snow water equivalent (SWE) over much of the western United States in the last half century, as well as trends toward earlier spring snowmelt and peak spring streamflows. These trends are ...

Alan F. Hamlet; Philip W. Mote; Martyn P. Clark; Dennis P. Lettenmaier

2005-11-01T23:59:59.000Z

99

The Identification of 10- to 20-Year Temperature and Precipitation Fluctuations in the Contiguous United States  

Science Conference Proceedings (OSTI)

A potentially fruitful approach to assessing society's sensitivity to climate change is to study the impacts, perceptions and adjustments of recent climate fluctuations. We set out to determine if the recent (1931–82) United States climate record ...

Thomas R. Karl; William E. Riebsame

1984-06-01T23:59:59.000Z

100

NETL: Mercury Emissions Control Technologies - Enhanced High Temperature  

NLE Websites -- All DOE Office Websites (Extended Search)

Enhanced High Temperature Mercury Oxidation and Enhanced High Temperature Mercury Oxidation and In-Situ Active Carbon Generation for Low Cost Mercury Capture Mercury oxidation phenomenon and the studies of this phenomenon have generally focused on lower temperatures, typically below 650°F. This has been based on the mercury vapor equilibrium speciation curve. The baseline extents of mercury oxidation as reported in the ICR dataset and observed during subsequent tests has shown a tremendous amount of scatter. The objective of this project is to examine, establish and demonstrate the effect of higher temperature kinetics on mercury oxidation rates. Further, it is the objective of this project to demonstrate how the inherent mercury oxidation kinetics can be influenced to dramatically increase the mercury oxidation.

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


101

Quality Controls for Profiler Measurements of Winds and RASS Temperatures  

Science Conference Proceedings (OSTI)

A new method for estimating winds and radio acoustic sounding system temperatures from radar Doppler measurements for the new NOAA wind profilers is described. This method emphasizes the quality of 6-min measurements prior to the computation of ...

B. L. Weber; D. B. Wuertz; D. C. Welsh; R. McPeek

1993-08-01T23:59:59.000Z

102

Surface Water Temperatures At Shore Stations, United States West Coast 1975 - 1976  

E-Print Network (OSTI)

that monitors the cooling intake water for the generators.Thermograph record of intake water at Pacific Gas andtakes daily water temperatures at the intake pipe to their

Scripps Institution of Oceanography

1978-01-01T23:59:59.000Z

103

HVAC Room Temperature Prediction Control Based on Neural Network Model  

Science Conference Proceedings (OSTI)

HVAC (Heating Ventilating &Air-conditioning) system is a nonlinear complex system with delay. It is very difficult to build a mathematical model of HVAC and implement model-based control. Since a BP (Back Propagation) neural network can fully approximate ... Keywords: BP neural network, predictive control, HVAC, least squares method

Shujiang Li, Shuang Ren, Xiangdong Wang

2013-01-01T23:59:59.000Z

104

Thermostat means adaptively controlling the amount of overshoot or undershoot of space temperature  

Science Conference Proceedings (OSTI)

This patent describes a clock thermostat adaptively controlling the amount of overshoot or undershoot of space temperature due to changes in the current temperature setpoint of the thermostat means, including: microcomputer means including real time clock and memory; data input means connected to the microcomputer to input a sequence of desired heat and cool control temperature setpoints and times for a desired temperature control by the thermostat; temperature sensor including connection to monitor temperature at the thermostat means; connection means connected to microcomputer to communicate a temperature at sensor means to the microcomputer; thermostat means further including output switch adapted to control heating and cooling equipment by thermostat means; microcomputer means and memory means including overshoot-undershoot correction program means which is operable to adjust a ramprate slope of a current temperature setpoint of thermostat means; overshoot-undershoot correction program and the memory means providing a ramprate slope that reduces an overshoot-undershoot of space temperature due to a change in current temperature setpoint; and overshoot-undershoot correction program means and memory means creating a new ramprate slope after a temperature setpoint change to progressively adjust the ramprate slope of the thermostat to limit the amount of overshoot-undershoot of the space temperature to an acceptable level.

Beckey, T.J.

1987-06-16T23:59:59.000Z

105

Evaluation of Satellite Estimates of Land Surface Temperature from GOES over the United States  

Science Conference Proceedings (OSTI)

A comprehensive evaluation of split-window and triple-window algorithms to estimate land surface temperature (LST) from Geostationary Operational Environmental Satellites (GOES) that were previously described by Sun and Pinker is presented. The ...

Rachel T. Pinker; Donglian Sun; Meng-Pai Hung; Chuan Li; Jeffrey B. Basara

2009-01-01T23:59:59.000Z

106

Production of Temporally Consistent Gridded Precipitation and Temperature Fields for the Continental United States  

Science Conference Proceedings (OSTI)

The availability of long-term gridded datasets of precipitation, temperature, and other surface meteorological variables offers the potential for deriving a range of land surface conditions that have not been directly observed. These include, for ...

Alan F. Hamlet; Dennis P. Lettenmaier

2005-06-01T23:59:59.000Z

107

Distinguishing Pronounced Droughts in the Southwestern United States: Seasonality and Effects of Warmer Temperatures  

Science Conference Proceedings (OSTI)

Higher temperatures increase the moisture-holding capacity of the atmosphere and can lead to greater atmospheric demand for evapotranspiration, especially during warmer seasons of the year. Increases in precipitation or atmospheric humidity ...

Jeremy L. Weiss; Christopher L. Castro; Jonathan T. Overpeck

2009-11-01T23:59:59.000Z

108

Surface Water Temperatures, Salinities and Densities At Shore Stations, United States West Coast 1991  

E-Print Network (OSTI)

off tlw rocks near the water intake for the laboratory. T hthat monitors the cooling intake water for the gen- erators.of hot water is outside the bay, the intake temperatures are

Scripps Institution of Oceanography

1992-01-01T23:59:59.000Z

109

Surface Water Temperatures, Salinities and Densities At Shore Stations, United States West Coast 1990  

E-Print Network (OSTI)

off the rocks near the water intake for the laboratory. Thethat monitors the cooling intake water for the generators.of hot water is outside the bay, the intake temperatures

Scripps Institution of Oceanography

1991-01-01T23:59:59.000Z

110

Surface Water Temperatures, Salinities and Densities At Shore Stations, United States West Coast 1992  

E-Print Network (OSTI)

off the rocks near the water intake for the laboratory. Thethat monitors the cooling intake water for the gen­ erators.of hot water is outside the bay, the intake temperatures are

Scripps Institution of Oceanography

1993-01-01T23:59:59.000Z

111

Surface Water Temperatures, Salinities and Densities At Shore Stations, United States West Coast 1993  

E-Print Network (OSTI)

off the rocks near the water intake for the laboratory. T hthat monitors the cooling intake water for the generators.of hot water is outside the bay, the intake temperatures are

Scripps Institution of Oceanography

1994-01-01T23:59:59.000Z

112

Relations between Temperature and Residential Natural Gas Consumption in the Central and Eastern United States  

Science Conference Proceedings (OSTI)

The increased U.S. natural gas price volatility since the mid-to-late-1980s deregulation generally is attributed to the deregulated market being more sensitive to temperature-related residential demand. This study therefore quantifies relations ...

Reed P. Timmer; Peter J. Lamb

2007-11-01T23:59:59.000Z

113

Objective Winter Temperature Forecasts: An Update and Extension to the Western United States  

Science Conference Proceedings (OSTI)

This study expands on previous studies (Harnack and Landsberg, 1978; Harnack, 1979) in that objective, statistical winter temperature forecast models are tested and verified for three additional winters (1979–81); models have been formulated and ...

Robert P. Harnack

1982-04-01T23:59:59.000Z

114

Bottom Temperatures Related to Gulf Stream Displacement off the Southeast United States Shelf  

Science Conference Proceedings (OSTI)

Bottom temperature time series recorded beneath the Gulf Stream at 265 and 589 m depth off the Georgia coast are compared with simultaneous time series of main thermocline depth determined from inverted echo sounder and bottom pressure gauge ...

Li Li; Mark Wimbush

1985-03-01T23:59:59.000Z

115

Smart Interpolation of Annually Averaged Air Temperature in the United States  

Science Conference Proceedings (OSTI)

Two “smart” interpolation procedures are presented and assessed with respect to their ability to estimate annual-average air temperatures at unsampled points in space from available station averages. Smart approaches examined here improve upon ...

Cort J. Willmott; Kenji Matsuura

1995-12-01T23:59:59.000Z

116

Detection and Attribution of Temperature Changes in the Mountainous Western United States  

Science Conference Proceedings (OSTI)

Large changes in the hydrology of the western United States have been observed since the mid-twentieth century. These include a reduction in the amount of precipitation arriving as snow, a decline in snowpack at low and midelevations, and a shift ...

Céline Bonfils; Benjamin D. Santer; David W. Pierce; Hugo G. Hidalgo; Govindasamy Bala; Tapash Das; Tim P. Barnett; Daniel R. Cayan; Charles Doutriaux; Andrew W. Wood; Art Mirin; Toru Nozawa

2008-12-01T23:59:59.000Z

117

On-Chip Hotplate for Temperature Control of Cmos Saw Resonators  

E-Print Network (OSTI)

Due to the sensitivity of the piezoelectric layer in surface acoustic wave (SAW) resonators to temperature, a method of achieving device stability as a function of temperature is required. This work presents the design, modeling and characterization of integrated dual-serpentine polysilicon resistors as a method for temperature control of CMOS SAW resonators. The design employs the oven control temperature stabilization scheme where the device's temperature is elevated to higher than Tmax to maintain constant device temperature. The efficiency of the polysilicon resistor as a heating element was verified through a 1-D partial differential equation model, 3-D CoventorWare finite element simulations and measurements using Compix thermal camera. To verify that the on-chip hotplate is effective as a temperature control method, both DC and RF measurements of the heater together with the resonator were conducted. Experimental results have indicated that the TCF of the CMOS SAW resonator of -97.2 ppm/deg C has been ...

Nordin, Anis; Zaghloul, Mona

2008-01-01T23:59:59.000Z

118

Solar energy controlled-environment agriculture in the United States and in Saudi Arabia  

Science Conference Proceedings (OSTI)

A number of greenhouse designs proposed for use in hot climates to reduce the temperature by essentially passive means are illustrated. The project plans of the SOLERAS, solar-powered, controlled-environment agriculture are outlined. The water desalination technology being evaluated is reverse osmosis. The solar collection technologies include flat-plate thermal collectors, solar ponds, photovoltaics, and wind turbines. (MHR)

Luft, W.; Froechtenigt, J.

1981-11-01T23:59:59.000Z

119

Method of controlling temperature of a thermoelectric generator in an exhaust system  

DOE Patents (OSTI)

A method of controlling the temperature of a thermoelectric generator (TEG) in an exhaust system of an engine is provided. The method includes determining the temperature of the heated side of the TEG, determining exhaust gas flow rate through the TEG, and determining the exhaust gas temperature through the TEG. A rate of change in temperature of the heated side of the TEG is predicted based on the determined temperature, the determined exhaust gas flow rate, and the determined exhaust gas temperature through the TEG. Using the predicted rate of change of temperature of the heated side, exhaust gas flow rate through the TEG is calculated that will result in a maximum temperature of the heated side of the TEG less than a predetermined critical temperature given the predicted rate of change in temperature of the heated side of the TEG. A corresponding apparatus is provided.

Prior, Gregory P; Reynolds, Michael G; Cowgill, Joshua D

2013-05-21T23:59:59.000Z

120

The evolution of NOx control policy for coal-fired power plants in the United States  

Science Conference Proceedings (OSTI)

Emissions of nitrogen oxides (NOx) contribute to formation of particulate matter and ozone, and also to acidification of the environment. The electricity sector is responsible for about 20% of NOx emissions in the United States, and the sector has been the target of both prescriptive (command-and-control) and flexible (cap-and-trade) approaches to regulation. The paper summarises the major NOx control policies affecting this sector in the USA, and provides some perspectives as to their effectiveness. While both prescriptive and flexible approaches continue to play an important role, significant new proposals have wholly embraced a cap-and-trade approach. 20 refs., 7 figs., 2 tabs.

Dallas Burtraw; David A. Evans

2003-12-15T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


121

Energy Savings and Economics of Advanced Control Strategies for Packaged Air-Conditioning Units with Gas Heat  

SciTech Connect

Pacific Northwest National Laboratory (PNNL) with funding from the U.S. Department of Energy's Building Technologies Program (BTP) evaluated a number of control strategies that can be implemented in a controller, to improve the operational efficiency of the packaged air conditioning units. The two primary objectives of this research project are: (1) determine the magnitude of energy savings achievable by retrofitting existing packaged air conditioning units with advanced control strategies not ordinarily used for packaged units and (2) estimating what the installed cost of a replacement control with the desired features should be in various regions of the U.S. This document reports results of the study.

Wang, Weimin; Katipamula, Srinivas; Huang, Yunzhi; Brambley, Michael R.

2011-12-31T23:59:59.000Z

122

District space heating potential of low temperature hydrothermal geothermal resources in the southwestern United States. Technical report  

DOE Green Energy (OSTI)

A computer simulation model (GIRORA-Nonelectric) is developed to study the economics of district space heating using geothermal energy. GIRORA-Nonelectric is a discounted cashflow investment model which evaluates the financial return on investment for space heating. This model consists of two major submodels: the exploration for and development of a geothermal anomaly by a geothermal producer, and the purchase of geothermal fluid by a district heating unit. The primary output of the model is a calculated rate of return on investment earned by the geothermal producer. The results of the sensitivity analysis of the model subject to changes in physical and economic parameters are given in this report. Using the results of the economic analysis and technological screening criteria, all the low temperature geothermal sites in Southwestern United States are examined for economic viability for space heating application. The methodology adopted and the results are given.

McDevitt, P.K.; Rao, C.R.

1978-10-01T23:59:59.000Z

123

Understanding and controlling low-temperature aging of nanocrystalline materials.  

SciTech Connect

Nanocrystalline copper lms were created by both repetitive high-energy pulsed power, to produce material without internal nanotwins; and pulsed laser deposition, to produce nan- otwins. Samples of these lms were indented at ambient (298K) and cryogenic temperatures by immersion in liquid nitrogen (77K) and helium (4K). The indented samples were sectioned through the indented regions and imaged in a scanning electron microscope. Extensive grain growth was observed in the lms that contained nanotwins and were indented cryogenically. The lms that either lacked twins, or were indented under ambient conditions, were found to exhibit no substantial grain growth by visual inspection. Precession transmission elec- tron microscopy was used to con rm these ndings quantitatively, and show that 3 and 7 boundaries proliferate during grain growth, implying that these interface types play a key role in governing the extensive grain growth observed here. Molecular dynamics sim- ulations of the motion of individual grain boundaries demonstrate that speci c classes of boundaries - notably 3 and 7 - exhibit anti- or a-thermal migration, meaning that their mobilities either increase or do not change signi cantly with decreasing temperature. An in-situ cryogenic indentation capability was developed and implemented in a transmission electron microscope. Preliminary results do not show extensive cryogenic grain growth in indented copper lms. This discrepancy could arise from the signi cant di erences in con g- uration and loading of the specimen between the two approaches, and further research and development of this capability is needed.

Battaile, Corbett Chandler; Boyce, Brad Lee; Brons, Justin G.; Foiles, Stephen Martin; Hattar, Khalid Mikhiel; Holm, Elizabeth Ann; Padilla, Henry A.,; Sharon, John Anthony; Thompson, Gregory B.

2013-10-01T23:59:59.000Z

124

ARIZONA COOPERATIVE FISH AND WILDLIFE RESEARCH UNIT OCTOBER 2005 Upper Temperature Tolerance of Loach  

E-Print Network (OSTI)

tolerance. Furthermore, the results of a low-cost method may be useful for identifying the range (45% protein), and 2 parts tropical fish flakes made from brine shrimp, bloodmeal, and spirulina (40 costs associated with remaining at temperatures close to the upper thermal limit for a long period

Bonar, Scott A.

125

Adaptive temperature control system for the supply of steam to a steam turbine  

SciTech Connect

A combined-cycle steam turbine power generating plant is described including a heat recovery steam generator for outputting steam at an instantaneous temperature and pressure, and a steam turbine having rotor expanding steam therethrough from the steam generator; means providing a signal representative of the temperature of the rotor of the turbine; and means for controlling the generation of steam by the steam generator to control the temperature of steam in accordance with a predetermined temperature gradient, the combination of: function generator means responsive to a signal representative of steam turbine throttle pressure for providing a throttle pressure related steam limit temperature according to a constant enthalpy characteristic; bias means responsive to the rotor temperature representative signal for providing a bias signal in excess of the rotor temperature signal by a predetermined amount; means responsive to the larger of the limit temperature signal and the bias signal for controlling the generation of steam by the steam generator to control the temperature of steam to iteratively raise the temperature of the rotor in accordance with the constant enthalpy characteristic and the bias signal during soaking.

Martens, A.; Myers, G.A.

1986-05-20T23:59:59.000Z

126

Analysis of air-temperature measurements from the Three Mile Island Unit 2 reactor building  

DOE Green Energy (OSTI)

The performance of the ambient air resistance temperature detectors (RTDs) just after the hydrogen burn in the TMI-2 Reactor Building is examined. The performance of the sensors is compared with physical models of the sensor/ambient air system. With one exception, the RTD data appear to be valid for the period examined. Based on the data, the hydrogen burn ended considerably before the first data points were recorded.

Fryer, M.O.

1983-04-01T23:59:59.000Z

127

Quality Control for USDA NRCS SM–ST Network Soil Temperatures: A Method and a Dataset  

Science Conference Proceedings (OSTI)

In 1991, the U.S. Department of Agriculture (USDA) Natural Resources Conservation Service (NRCS) established its Soil Moisture–Soil Temperature (SM–ST) Pilot Network consisting of 21 stations in 19 states in the contiguous United States. At each ...

Qi Hu; Song Feng; Garry Schaefer

2002-06-01T23:59:59.000Z

128

Development of a digital control unit to displace diesel fuel with natural gas  

DOE Green Energy (OSTI)

Full Circle Engineering (FCE), supported by the Colorado School of Mines (CSM), proposed a Small Business CRADA with Allied Signal Federal Manufacturing & Technologies/Kansas City (FM&T/KC) for the development of a fumigation digital control unit (DCU) that would allow the displacement of diesel fuel with natural gas. Nationwide, diesel trucks and buses consumed over 21 billion gallons of fuel in 1992. The development of systems that allow the use of alternative fuels, natural gas in particular, for transportation would significantly reduce emissions and pollutants. It would also help implement DOE`s mandate for energy security (use of domestic fuels) required by the Energy Policy Act (EPACT).

Talbott, A.D. [AlliedSignal FM& T, Kansas City, MO (United States)]|[Full Circle Engineering, Northglenn, CO (United States)

1997-03-01T23:59:59.000Z

129

Control of Combustion Processes in an Internal Combustion Engine by Low-Temperature Plasma  

Science Conference Proceedings (OSTI)

A new method of operation of internal combustion engines enhances power and reduces fuel consumption and exhaust toxicity. Low-temperature plasma control combines working processes of thermal engines and steam machines into a single process.

E. A. Olenev

2002-07-01T23:59:59.000Z

130

Mechanisms Controlling Variability of the Interhemispheric Sea Surface Temperature Gradient in the Tropical Atlantic  

Science Conference Proceedings (OSTI)

The seasonal evolution of sea surface temperature (SST) fields in the tropical Atlantic is explored for composites of extremely STRONG and WEAK northward SST gradients, because these are known to control the basinwide pressure gradient, latitude ...

Richard G. Wagner

1996-09-01T23:59:59.000Z

131

A Semiautomated Approach for Quality Controlling Large Historical Ocean Temperature Archives  

Science Conference Proceedings (OSTI)

This paper describes a method consisting of both automated statistical screening and manual quality control through expert visual inspection, which produces a historical ocean temperature archive of high quality—that is, nearly all profiles are ...

Ann Gronell; Susan E. Wijffels

2008-06-01T23:59:59.000Z

132

Heat recovery steam generator outlet temperature control system for a combined cycle power plant  

Science Conference Proceedings (OSTI)

This patent describes a command cycle electrical power plant including: a steam turbine and at least one set comprising a gas turbine, an afterburner and a heat recovery steam generator having an attemperator for supplying from an outlet thereof to the steam turbine superheated steam under steam turbine operating conditions requiring predetermined superheated steam temperature, flow and pressure; with the gas turbine and steam turbine each generating megawatts in accordance with a plant load demand; master control means being provided for controlling the steam turbine and the heat recovery steam generator so as to establish the steam operating conditions; the combination of: first control means responsive to the gas inlet temperature of the heat recovery steam generator and to the plant load demand for controlling the firing of the afterburner; second control means responsive to the superheated steam predetermined temperature and to superheated steam temperature from the outlet for controlling the attemperator between a closed and an open position; the first and second control means being operated concurrently to maintain the superheated steam outlet temperature while controlling the load of the gas turbine independently of the steam turbine operating conditions.

Martens, A.; Myers, G.A.; McCarty, W.L.; Wescott, K.R.

1986-04-01T23:59:59.000Z

133

MULTI-PHASE HIGH TEMPERATURE ALLOYS AND PROGRESS IN CONTROLLED OXIDATION FOR FUNCTIONAL AND PROTECTIVE SURFACES  

E-Print Network (OSTI)

-phase strengthened Fe-base alloys for improved elevated temperature strength in fossil energy system components-temperature strength is a major issue for hot components in advanced fossil energy conversion and combustion systems-containing environments such as those encountered in advanced fossil energy steam plants. Controlled Oxidation for Near

134

Unit Conversions  

Science Conference Proceedings (OSTI)

... volume flow units, which contain "atm", assume that the gas is: ideal; at a pressure of 101325 Pa; at a temperature of 0 °C. Be aware that the unit "atm ...

2012-10-02T23:59:59.000Z

135

AISI/DOE Advanced Process Control Program Vol. 6 of 6: Temperature Measurement of Galvanneal Steel  

SciTech Connect

This report describes the successful completion of the development of an accurate in-process measurement instrument for galvanneal steel surface temperatures. This achievement results from a joint research effort that is a part of the American Iron and Steel Institute's (AISI) Advanced Process Control Program, a collaboration between the U.S> Department of Energy and fifteen North American Steelmakers. This three-year project entitled ''Temperature Measurement of Galvanneal Steel'' uses phosphor thermography, and outgrowth of Uranium enrichment research at Oak Ridge facilities. Temperature is the controlling factor regarding the distribution of iron and zinc in the galvanneal strip coating, which in turn determines the desired product properties

S.W. Allison; D.L. Beshears; W.W. Manges

1999-06-30T23:59:59.000Z

136

Greenhouse air temperature predictive control using the particle swarm optimisation algorithm  

Science Conference Proceedings (OSTI)

The particle swarm optimisation algorithm is proposed as a new method to design a model-based predictive greenhouse air temperature controller subject to restrictions. Its performance is compared with the ones obtained by using genetic and sequential ... Keywords: Agriculture, Greenhouse climate, Model predictive control, Particle swarm optimisation algorithms

J. P. Coelho; P. B. de Moura Oliveira; J. Boaventura Cunha

2005-12-01T23:59:59.000Z

137

Power conversion unit studies for the next generation nuclear plant coupled to a high-temperature steam electrolysis facility  

E-Print Network (OSTI)

The Department of Energy and the Idaho National Laboratory are developing a Next Generation Nuclear Plant (NGNP) to serve as a demonstration of state-of-the-art nuclear technology. The purpose of the demonstration is two fold: 1) efficient low cost energy generation and 2) hydrogen production. Although a next generation plant could be developed as a single-purpose facility, early designs are expected to be dual-purpose. While hydrogen production and advanced energy cycles are still in their early stages of development, research towards coupling a high temperature reactor, electrical generation and hydrogen production is under way. Many aspects of the NGNP must be researched and developed to make recommendations on the final design of the plant. Parameters such as working conditions, cycle components, working fluids, and power conversion unit configurations must be understood. Three configurations of the power conversion unit were modeled using the process code HYSYS; a three-shaft design with 3 turbines and 4 compressors, a combined cycle with a Brayton top cycle and a Rankine bottoming cycle, and a reheated cycle with 3 stages of reheat were investigated. A high temperature steam electrolysis hydrogen production plant was coupled to the reactor and power conversion unit by means of an intermediate heat transport loop. Helium, CO2, and an 80% nitrogen, 20% helium mixture (by weight) were studied to determine the best working fluid in terms cycle efficiency and development cost. In each of these configurations the relative heat exchanger size and turbomachinery work were estimated for the different working fluids. Parametric studies away from the baseline values of the three-shaft and combined cycles were performed to determine the effect of varying conditions in the cycle. Recommendations on the optimal working fluid for each configuration were made. The helium working fluid produced the highest overall plant efficiency for the three-shaft and reheat cycle; however, the nitrogen-helium mixture produced similar efficiency with smaller component sizes. The CO2 working fluid is recommend in the combined cycle configuration.

Barner, Robert Buckner

2006-12-01T23:59:59.000Z

138

Solar powered automatic turn-on control (spa-toc) unit and method  

SciTech Connect

Orderly control of power applied by a photovoltaic solar panel d.c. source to a load is attained despite varying long and short term solar conditions by coupling power from the panel to an inverter in response to the panel voltage exceeding a predetermined level and preventing coupling of power from the panel to the inverter in response to the panel voltage being less than a predetermined level. The switching frequency of the inverter is controlled in response to the panel voltage so that approximately maximum power which the panel is capable of generating is supplied to the inverter for the incident solar energy on the panel at a given temperature. Power is supplied to the inverter by a series switch between the panel and inverter. The switch is activated into a conducting state in response to the panel voltage exceeding a predetermined value. The panel voltage controls the turn-on and turn-off levels of the series switch by a hysteresis effect, provided by connecting a dummy power dissipating load in shunt with the panel while the series switch is cut off. The dummy load has a value causing the panel output voltage to be less than the voltage for maximum panel output power. A similar series switch and hysteresis control is provided for control circuitry for the inverter. The series switch for supplying power to the control circuitry can be activated in response to the same voltage which activates the series switch for the inverter, or in response to a different voltage level.

Baker, R.H.

1982-06-01T23:59:59.000Z

139

Temperature controlled multiple pass absorption cell for gas phase chemical kinetics studies  

Science Conference Proceedings (OSTI)

The application of a Herriott-type optical multiple pass cell for absorption detection of transient species in temperature controlled laser pump-probe kinetics experiments is described. Using reaction initiation by laser photolysis in combination with reaction monitoring by absorption of a multiple pass laser allows confinement of the probed reaction volume to the temperature controlled region of a slow flow reactor. For transient measurements, this apparatus provides enhanced sensitivity from increased path length and accurate temperature control by limiting the pump-probe interaction volume. In addition, for a polarized probe laser, a simple arrangement using a polarizing beam splitter and a {lambda}/4 plate allows doubling of the path length. {copyright} {ital 1997 American Institute of Physics.}

Pilgrim, J.S.; Jennings, R.T.; Taatjes, C.A. [Combustion Research Facility, Sandia National Laboratories, Livermore, California 94551-0969 (United States)

1997-04-01T23:59:59.000Z

140

A Particle Swarm Optimization Approach for Optimal Design of PID Controller for Temperature Control in HVAC  

Science Conference Proceedings (OSTI)

Particle swarm optimization (PSO) is a novel evolutionary algorithm which has a better convergence rate and computation precision compared with other evolutionary algorithms. From the perspective of optimization, the self-tuning of PID controller parameters ... Keywords: PSO, PID, HVAC, Optimization, Particle Swarm Optimization

Zhang Jun; Zhang Kanyu

2011-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


141

Room-temperature electric-field controlled spin dynamics in ,,110... InAs quantum wells  

E-Print Network (OSTI)

Room-temperature electric-field controlled spin dynamics in ,,110... InAs quantum wells K. C. Halla pseudomagnetic fields exceeding 1 T when only 140 mV is applied across a single quantum well. Using this large­11 and the influence of the Rashba pseudomagnetic fields on the electron spin relaxation time in GaAs quantum wells

Flatte, Michael E.

142

The Design and Application of the Water Temperature Control System for Large Aquaculture Pond  

Science Conference Proceedings (OSTI)

Because the traditional cooling methods such as ice cooling and natural convection cooling can not meet the special requirements of ornamental fish breeding, the way based on mechanical refrigeration, heat exchange system, water supply system and automatic ... Keywords: aquaculture pond for ornamental fish, water temperature automatic control, mechanical refrigeration, plate exchanger, water supply system

Chen Shuai; Zhong Ke; Cai Yingling

2011-01-01T23:59:59.000Z

143

Active Fault Controls At High-Temperature Geothermal Sites- Prospecting For  

Open Energy Info (EERE)

Page Page Edit History Facebook icon Twitter icon » Active Fault Controls At High-Temperature Geothermal Sites- Prospecting For New Faults Jump to: navigation, search GEOTHERMAL ENERGYGeothermal Home Conference Paper: Active Fault Controls At High-Temperature Geothermal Sites- Prospecting For New Faults Details Activities (1) Areas (1) Regions (0) Abstract: Our previous studies found spatial associations between seismically active faults and high-temperature geothermal resources in the western Basin and Range, suggesting that recency of fault movement may be a useful criterion for resource exploration. We have developed a simple conceptual model in which recently active (Holocene) faults are preferred conduits for migration of thermal water from deep crustal depths, and we

144

Temperature control in a 30 stage, 5-cm Centrifugal Contactor Pilot Plant  

Science Conference Proceedings (OSTI)

Temperature profile testing was performed using a 30 stage 5-cm centrifugal contactor pilot plant. These tests were performed to evaluate the ability to control process temperature by adjusting feed solution temperatures. This would eliminate the need for complex jacketed heat exchanger installation on the centrifugal contactors. Thermocouples were installed on the inlet and outlets of each stage, as well as directly in the mixing zone of several of the contactor stages. Lamp oil, a commercially available alkane mixture of C14 to C18 chains, and tap water adjusted to pH 2 with nitric acid were the solution feeds for the temperature profile testing. Temperature data profiles for an array of total throughputs and contactor rpm values for both single-phase and two-phase systems were collected with selected profiles. The total throughput ranged from 0.5-1.4 L/min with rotor speeds from 3500-4000 rpm. Inlet solution temperatures ranging from ambient up to 50 °C were tested. Results of the two-phase temperature profile testing are detailed

Jack D. Law; Troy G. Garn; David H. Meikrantz

2009-09-01T23:59:59.000Z

145

NON-SOOTING, LOW FLAME TEMPERATURE MIXING-CONTROLLED DI DIESEL COMBUSTION  

DOE Green Energy (OSTI)

Methods of producing non-sooting, low flame temperature diesel combustion were investigated in an optically-accessible, quiescent constant-volume combustion vessel under mixing-controlled diesel combustion conditions. Combustion and soot processes of single, isolated fuel jets were studied after auto-ignition and transient premixed combustion and while the injector was fully-open (i.e. during the mixing-controlled phase of heat release for diesel combustion). The investigation showed that small injector tip orifices could be used to produce non-sooting and low flame temperature combustion simultaneously. The use of small orifices was shown to enable non-sooting and low flame temperature combustion in two different ways as summarized below. A more detailed description of the experimental methods and results is provided in Ref. [1-3]. First, using an injector tip with a 50 micron orifice and ambient oxygen concentrations as low as 10% (simulating the use of extensive EGR), a fuel jet was non-sooting at typical diesel ambient temperatures (1000 K). Second, using the same injector tip at a reduced ambient gas temperature (850 K), but with 21% oxygen, it was shown that non-sooting, mixing-controlled combustion occurred at the lift-off length in a fuel-air mixture with a cross-sectional average equivalence ratio of approximately 0.6-suggesting that the quasi-steady combustion was fuel-lean and thereby avoided the formation of a diffusion flame. The adiabatic flame temperature with reduced ambient oxygen concentration or fuel-lean combustion was approximately 2000 K, compared to typical diesel flame temperatures that exceed 2600 K. The 50 micron orifice results above were obtained using a No.2 diesel fuel. However, using an oxygenated fuel (20 wt% oxygen), the investigation showed that the same low temperature combustion, either with reduced ambient oxygen concentration or fuel-lean combustion, was realized with a 100 micron orifice. Although these single, isolated jets do not have jet-jet interactions that would occur in realistic engines, the results are useful for understanding limiting-case behavior of single-jet mixing and combustion during an injection event. The non-sooting and low flame temperature mixing-controlled combustion realized using small orifice tips suggests that the use of small orifices offers the potential for a simultaneous soot and NOx reduction in an engine, much like diesel HCCI combustion. However, further research is needed to determine whether these methods could be successfully implemented in real engines.

Pickett, L; Siebers, D

2003-08-24T23:59:59.000Z

146

Mathematical Modeling of Perfect Decoupled Control System and Its Application: A Reverse Osmosis Desalination Industrial-Scale Unit  

E-Print Network (OSTI)

This short paper outlines the computer simulation using real data of a decoupled control system for a desalination unit. The control strategy incorporated a perfect decoupled controller for the control of the fresh water flow and conductivity. The model was estimated using real data and empirical tools instead of mass balances. The success is demonstrated in the reduction of wide fluctuations in the variables of the process and decreasing of the sensibility to the changes of pressure and/or pH and allows predicting problems of quality of water and waste of energy in the future. 1.

C. Riverol; V. Pilipovik

2004-01-01T23:59:59.000Z

147

Synoptic Climatology of Monthly Mean Surface Temperature in the Unit States during Summer in Relation to the Surrounding 700-mb Height Field  

Science Conference Proceedings (OSTI)

The synoptic climatology of monthly mean temperature at 109 surface stations in the contiguous United States relative to 700-mb heights at 133 grid points is assessed. Two methods are used based on data for 102 summer months from June 1948 to ...

Joann M. Kline; William H. Klein

1986-07-01T23:59:59.000Z

148

Selected data for low-temperature (less than 90{sup 0}C) geothermal systems in the United States: reference data for US Geological Survey Circular 892  

DOE Green Energy (OSTI)

Supporting data are presented for the 1982 low-temperature geothermal resource assessment of the United States. Data are presented for 2072 geothermal sites which are representative of 1168 low-temperature geothermal systems identified in 26 States. The low-temperature geothermal systems consist of 978 isolated hydrothermal-convection systems, 148 delineated-area hydrothermal-convection systems, and 42 delineated-area conduction-dominated systems. The basic data and estimates of reservoir conditions are presented for each geothermal system, and energy estimates are given for the accessible resource base, resource, and beneficial heat for each isolated system.

Reed, M.J.; Mariner, R.H.; Brook, C.A.; Sorey, M.L.

1983-12-15T23:59:59.000Z

149

Direct Nyquist array design of PID controllers for boiler-turbine units based on gain and phase margins  

Science Conference Proceedings (OSTI)

In this paper, a direct Nyquist array (DNA) method for the design of PID controllers for multivariable boiler-turbine units with specifications of gain and phase margins is proposed. The essential objective is to propose a method for the design and auto-tuning ...

Hui Pan; Minrui Fei; Ling Wang; Kang Li; Lin Qian

2012-03-01T23:59:59.000Z

150

Control system for single shaft combined cycle gas and steam turbine unit  

SciTech Connect

This patent describes a method for starting and controlling a combined cycle turbine of the type having a gas turbine with a fuel flow control valve and a steam turbine with at least one steam control valve both disposed on a single shaft and having a heat recovery steam generator heated by the gas turbine and connected to supply steam to the steam control valve, the combined cycle turbine having a unified control system and driving a load, and also having an auxiliary steam source connected to the steam control valve. It comprises controlling of steam from the auxiliary steam source with the steam control valve to crank the combined cycle turbine for starting, initiating and controlling fuel flow to the gas turbine with the fuel flow control valve and initiating combustion, controlling initial acceleration of the combined cycle turbine with the steam control valve on auxiliary steam, coordinating control of the combined cycle turbine by the steam control valve and the fuel control valve with the unified control system, transferring acceleration control during a smooth acceleration phase of the combined cycle turbine by the steam control valve and the fuel control valve with the unified control system, transferring acceleration control during a smooth acceleration phase of the combined cycle turbine to the fuel flow control valve and gradually reducing the opening of the steam control valve to a minimum value when the turbine reaches rated speed.

Moore, J.H.; Kure-Jensen, J.; Rowen, W.I.

1991-08-27T23:59:59.000Z

151

Links to on-line unit conversions  

Science Conference Proceedings (OSTI)

... Basic physical quantities. General unit, currency, and temperature conversion. ... Many conversions, including unusual and ancient units. ...

152

An Active Gain-control System for Avalanche Photo-Diodes under Moderate Temperature Variations  

E-Print Network (OSTI)

Avalanche photodiodes (APDs) are promising light sensor for various fields of experimental physics. It has been argued, however, that variation of APD gain with temperature could be a serious problem preventing APDs from replacing traditional photomultiplier tubes (PMTs) in some applications. Here we develop an active gain-control system to keep the APD gain stable under moderate temperature variations. As a performance demonstration of the proposed system, we have tested the response of a scintillation photon detector consisting of a 5x5 mm^2 reverse-type APD optically coupled with a CsI(Tl) crystal. We show that the APD gain was successfully controlled under a temperature variation of DT = 20deg, within a time-cycle of 6000 sec. The best FWHM energy resolution of 6.1+-0.2 % was obtained for 662 keV gamma-rays, and the energy threshold was as low as 6.5 keV, by integrating data from +20deg - 0deg cycles. The corresponding values for -20deg - 0deg cycles were 6.9+-0.2 % and 5.2 keV, respectively. These results are comparable, or only slightly worse than that obtained at a fixed temperature. Our results suggest new potential uses for APDs in various space researches and nuclear physics. As examples, we briefly introduce the NeXT and Cute-1.7 satellite missions that will carry the APDs as scientific instruments for the first time.

J. Kataoka; R. Sato; T. Ikagawa; J. Kotoku; Y. Kuramoto; Y. Tsubuku; T. Saito; Y. Yatsu; N. Kawai; Y. Ishikawa; N. Kawabata

2006-02-17T23:59:59.000Z

153

Prediction of Summer Maximum and Minimum Temperature over the Central and Western United States: The Roles of Soil Moisture and Sea Surface Temperature  

Science Conference Proceedings (OSTI)

A statistical model based on canonical correlation analysis (CCA) was used to explore climatic associations and predictability of June–August (JJA) maximum and minimum surface air temperatures (Tmax and Tmin) as well as the frequency of Tmax ...

Eric J. Alfaro; Alexander Gershunov; Daniel Cayan

2006-04-01T23:59:59.000Z

154

Hemispheric Anomalies of 700 mb Height Related to Mean Temperature for Fall, Winter and Spring in the United States  

Science Conference Proceedings (OSTI)

Zonally averaged composite anomalies of 700 mb height for years preceding and during four warm winters in the contiguous United States show generally positive anomalies over subtropical and middle latitudes and generally negative anomalies over ...

Carl O. Erickson

1984-03-01T23:59:59.000Z

155

A field programmable gate array unit for the diagnosis and control of neoclassical tearing modes on MAST  

Science Conference Proceedings (OSTI)

A real-time system has been developed to trigger both the MAST Thomson scattering (TS) system and the plasma control system on the phase and amplitude of neoclassical tearing modes (NTMs), extending the capabilities of the original system. This triggering system determines the phase and amplitude of a given NTM using magnetic coils at different toroidal locations. Real-time processing of the raw magnetic data occurs on a low cost field programmable gate array (FPGA) based unit which permits triggering of the TS lasers on specific amplitudes and phases of NTM evolution. The MAST plasma control system can receive a separate trigger from the FPGA unit that initiates a vertical shift of the MAST magnetic axis. Such shifts have fully removed m/n= 2/1 NTMs instabilities on a number of MAST discharges.

O'Gorman, T.; Gibson, K. J.; Snape, J. A. [York Plasma Institute, Department of Physics, University of York, York YO10 5DD (United Kingdom); Naylor, G.; Huang, B.; McArdle, G. J.; Scannell, R.; Shibaev, S.; Thomas-Davies, N. [EURATOM/CCFE Fusion Association, Culham Science Centre, Oxfordshire OX14 3DB (United Kingdom)

2012-10-15T23:59:59.000Z

156

Design of Decision Making Unit for Neuro-fuzzy Control of Dynamic Systems  

Science Conference Proceedings (OSTI)

In this work is presented a design and implementation of an intelligent controller applied to dynamic systems. The main objective is to design a management intelligent system that acts in the controllers of Direct current machine (DC) and thermo-eletric ... Keywords: Fuzzy Logic, Neural Networks, Neuro-fuzzy Control, Systems Modeling, DC Drives, Thermo electric drives

Joao Viana da_Fonseca Neto; Gustavo Araujo de Andrade

2011-03-01T23:59:59.000Z

157

Regulatory Networks Controlling Plant Cold Acclimation or Low Temperature Regulatory Networks Controlling Cold Acclimation in Arabidopsis (2011 JGI User Meeting)  

Science Conference Proceedings (OSTI)

The U.S. Department of Energy Joint Genome Institute (JGI) invited scientists interested in the application of genomics to bioenergy and environmental issues, as well as all current and prospective users and collaborators, to attend the annual DOE JGI Genomics of Energy & Environment Meeting held March 22-24, 2011 in Walnut Creek, Calif. The emphasis of this meeting was on the genomics of renewable energy strategies, carbon cycling, environmental gene discovery, and engineering of fuel-producing organisms. The meeting features presentations by leading scientists advancing these topics. Mike Thomashow of Michigan State University gives a presentation on on "Low Temperature Regulatory Networks Controlling Cold Acclimation in Arabidopsis" at the 6th annual Genomics of Energy & Environment Meeting on March 23, 2011. «

Thomashow, Mike

2011-03-23T23:59:59.000Z

158

Optimal control system design of an acid gas removal unit for an IGCC power plants with CO2 capture  

Science Conference Proceedings (OSTI)

Future IGCC plants with CO{sub 2} capture should be operated optimally in the face of disturbances without violating operational and environmental constraints. To achieve this goal, a systematic approach is taken in this work to design the control system of a selective, dual-stage Selexol-based acid gas removal (AGR) unit for a commercial-scale integrated gasification combined cycle (IGCC) power plant with pre-combustion CO{sub 2} capture. The control system design is performed in two stages with the objective of minimizing the auxiliary power while satisfying operational and environmental constraints in the presence of measured and unmeasured disturbances. In the first stage of the control system design, a top-down analysis is used to analyze degrees of freedom, define an operational objective, identify important disturbances and operational/environmental constraints, and select the control variables. With the degrees of freedom, the process is optimized with relation to the operational objective at nominal operation as well as under the disturbances identified. Operational and environmental constraints active at all operations are chosen as control variables. From the results of the optimization studies, self-optimizing control variables are identified for further examination. Several methods are explored in this work for the selection of these self-optimizing control variables. Modifications made to the existing methods will be discussed in this presentation. Due to the very large number of candidate sets available for control variables and due to the complexity of the underlying optimization problem, solution of this problem is computationally expensive. For reducing the computation time, parallel computing is performed using the Distributed Computing Server (DCS®) and the Parallel Computing® toolbox from Mathworks®. The second stage is a bottom-up design of the control layers used for the operation of the process. First, the regulatory control layer is designed followed by the supervisory control layer. Finally, an optimization layer is designed. In this paper, the proposed two-stage control system design approach is applied to the AGR unit for an IGCC power plant with CO{sub 2} capture. Aspen Plus Dynamics® is used to develop the dynamic AGR process model while MATLAB is used to perform the control system design and for implementation of model predictive control (MPC).

Jones, D.; Bhattacharyya, D.; Turton, R.; Zitney, S.

2012-01-01T23:59:59.000Z

159

Modeling of ECM Controlled Series Fan-powered VAV Terminal Units  

E-Print Network (OSTI)

Semi-empirical models for series fan-powered variable air volume terminal units (FPTUs) were developed based on models of the primary, plenum, fan airflow and the fan power consumption. The experimental setups and test procedures were developed respectively for primary, plenum and fan airflow to test each component of the FPTUs at typical design pressures and airflows. Two sizes of the terminal units from three manufacturers were used in this study. All of the FPTUs were equipped with electronically commutated motors (ECM). Data provided by the models were compared against the data from previous experiments to prove the models’ validity. Regression modeling was performed by using SigmaStat. The model of primary airflow had an R2 above 0.948 for all the terminal units evaluated while the plenum airflow model had an R2 above 0.99. For all the terminal units, the R2 of the fan airflow model was ranged from 0.973 to 0.998. Except for one fan, the fan power consumption model was able to characterize the power performance and had an R2 above 0.986. By combining the airflow and power models, the model for series FPTU was developed. Verification was made to prove the FPTU model’s validity by comparing the measured and predicted data of airflow and power consumption. Correction factors were used in the primary airflow model to compensate for the difference caused by large measurement errors and the system effects. The predicted values were consistent with measurements and no offset was needed in the primary airflow model. Generally, the newly established model was able to describe the airflow performance as well as power consumption of series FPTUs without adding complexity.

Yin, Peng

2010-08-01T23:59:59.000Z

160

The Relationship of Soil Moisture Parameterizations to Subsequent Seasonal and Monthly Mean Temperature in the United States  

Science Conference Proceedings (OSTI)

The water content parameter and the moisture anomaly index, both derived from the Palmer Drought Severity model, were correlated against subsequent mean monthly and seasonal (three-month means) temperatures for 344 climatic divisions in the ...

Thomas R. Karl

1986-04-01T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


161

Assessment of Urban Versus Rural In Situ Surface Temperatures in the Contiguous United States: No Difference Found  

Science Conference Proceedings (OSTI)

All analyses of the impact of urban heat islands (UHIs) on in situ temperature observations suffer from inhomogeneities or biases in the data. These inhomogeneities make urban heat island analyses difficult and can lead to erroneous conclusions. ...

Thomas C. Peterson

2003-09-01T23:59:59.000Z

162

Comparison of Tropospheric Temperatures Derived from the NCEP/NCAR Reanalysis, NCEP Operational Analysis, and the Microwave Sounding Unit  

Science Conference Proceedings (OSTI)

The Climate Prediction Center has used atmospheric temperatures for data analysis from the National Centers for Environmental Prediction (NCEP) model since 1979. Unfortunately, model changes have adversely affected the stability of the ...

Alan N. Basist; Muthuvel Chelliah

1997-07-01T23:59:59.000Z

163

Controlling a rabbet load and air/oil seal temperatures in a turbine  

DOE Patents (OSTI)

During a standard fired shutdown of a turbine, a loaded rabbet joint between the fourth stage wheel and the aft shaft of the machine can become unloaded causing a gap to occur due to a thermal mismatch at the rabbet joint with the bearing blower turned on. An open or unloaded rabbet could cause the parts to move relative to each other and therefore cause the rotor to lose balance. If the bearing blower is turned off during a shutdown, the forward air/oil seal temperature may exceed maximum design practice criterion due to "soak-back." An air/oil seal temperature above the established maximum design limits could cause a bearing fire to occur, with catastrophic consequences to the machine. By controlling the bearing blower according to an optimized blower profile, the rabbet load can be maintained, and the air/oil seal temperature can be maintained below the established limits. A blower profile is determined according to a thermodynamic model of the system.

Schmidt, Mark Christopher (Niskayuna, NY)

2002-01-01T23:59:59.000Z

164

System and method for monitoring and controlling stator winding temperature in a de-energized AC motor  

Science Conference Proceedings (OSTI)

A system and method for measuring and controlling stator winding temperature in an AC motor while idling is disclosed. The system includes a circuit having an input connectable to an AC source and an output connectable to an input terminal of a multi-phase AC motor. The circuit further includes a plurality of switching devices to control current flow and terminal voltages in the multi-phase AC motor and a controller connected to the circuit. The controller is configured to activate the plurality of switching devices to create a DC signal in an output of the motor control device corresponding to an input to the multi-phase AC motor, determine or estimate a stator winding resistance of the multi-phase AC motor based on the DC signal, and estimate a stator temperature from the stator winding resistance. Temperature can then be controlled and regulated by DC injection into the stator windings.

Lu, Bin (Kenosha, WI); Luebke, Charles John (Sussex, WI); Habetler, Thomas G. (Snellville, GA); Zhang, Pinjia (Atlanta, GA); Becker, Scott K. (Oak Creek, WI)

2011-12-27T23:59:59.000Z

165

Integration of Advanced Emissions Controls to Produce Next-Generation Circulating Fluid Bed Coal Generating Unit (withdrawn prior to award)  

NLE Websites -- All DOE Office Websites (Extended Search)

contacts contacts Brad tomer Director Office of Major Demonstrations National Energy Technology Laboratory 3610 Collins Ferry Road P.O. Box 880 Morgantown, WV 26507-0880 304-285-4692 brad.tomer@netl.doe.gov PaRtIcIPant Colorado Springs Utilities Colorado Springs, CO aDDItIonaL tEaM MEMBERs Foster Wheeler Power Group, Inc. Clinton, NJ IntegratIon of advanced emIssIons controls to Produce next-generatIon cIrculatIng fluId Bed coal generatIng unIt (wIthdrawn PrIor to award) Project Description Colorado Springs Utilities (Springs Utilities) and Foster Wheeler are planning a joint demonstration of an advanced coal-fired electric power plant using advanced, low-cost emission control systems to produce exceedingly low emissions. Multi- layered emission controls will be

166

A Two-Stage Quality Control Method for 2-m Temperature Observations Using Biweight Means and a Progressive EOF Analysis  

Science Conference Proceedings (OSTI)

The relatively smooth terrain embedded in the numerical model creates an elevation difference against the actual terrain, which in turn makes the quality control of 2-m temperature difficult when forecast or analysis fields are utilized in the ...

Zhifang Xu; Yi Wang; Guangzhou Fan

2013-02-01T23:59:59.000Z

167

On the control of the residual circulation and stratospheric temperatures in the Arctic by planetary wave coupling  

Science Conference Proceedings (OSTI)

It is well established that interannual variability of eddy (meridional) heat flux near the tropopause controls the variability of Arctic lower-stratospheric temperatures during spring via a modification of the strength of the residual ...

Tiffany A. Shaw; Judith Perlwitz

168

Control of the radiant flux of high-temperature solar-energy installations with respect to two parameters  

SciTech Connect

The simultaneous control of both the power level and energy density level at the center of the focal plane of a high-temperature solar-energy installation with a paraboloid concentrator is considered.

Afyan, V.V.; Vartanyan, A.V.

1978-01-01T23:59:59.000Z

169

Multiple sample characterization of coals and other substances by controlled-atmosphere programmed temperature oxidation  

DOE Patents (OSTI)

A furnace with two hot zones holds multiple analysis tubes. Each tube has a separable sample-packing section positioned in the first hot zone and a catalyst-packing section positioned in the second hot zone. A mass flow controller is connected to an inlet of each sample tube, and gas is supplied to the mass flow controller. Oxygen is supplied through a mass flow controller to each tube to either or both of an inlet of the first tube and an intermediate portion between the tube sections to intermingle with and oxidize the entrained gases evolved from the sample. Oxidation of those gases is completed in the catalyst in each second tube section. A thermocouple within a sample reduces furnace temperature when an exothermic condition is sensed within the sample. Oxidized gases flow from outlets of the tubes to individual gas cells. The cells are sequentially aligned with an infrared detector, which senses the composition and quantities of the gas components. Each elongated cell is tapered inward toward the center from cell windows at the ends. Volume is reduced from a conventional cell, while permitting maximum interaction of gas with the light beam. Reduced volume and angulation of the cell inlets provide rapid purgings of the cell, providing shorter cycles between detections. For coal and other high molecular weight samples, from 50% to 100% oxygen is introduced to the tubes.

LaCount, Robert B. (403 Arbor Ct., Waynesburg, PA 15370)

1993-01-01T23:59:59.000Z

170

Draft audit report, human factors engineering control room design review: Saint Lucie Nuclear Power Plant, Unit No. 2  

SciTech Connect

A human factors engineering preliminary design review of the Saint Lucie Unit 2 control room was performed at the site on August 3 through August 7, 1981. This design review was carried out by a team from the Human Factors Engineering Branch, Division of Human Factors Safety. This report was prepared on the basis of the HFEB's review of the applicant's Preliminary Design Assessment and the human factors engineering design review/audit performed at the site. The review team included human factors consultants from BioTechnology, Inc., Falls Church, Virginia, and from Lawrence Livermore National Laboratory (University of California), Livermore, California.

Peterson, L.R.; Lappa, D.A.; Moore, J.W.

1981-09-03T23:59:59.000Z

171

Cyclone Boiler Field Testing of Advanced Layered NOx Control Technology in Sioux Unit 1  

SciTech Connect

A four week testing program was completed during this project to assess the ability of the combination of deep staging, Rich Reagent Injection (RRI), and Selective Non-Catalytic Reduction (SNCR) to reduce NOx emissions below 0.15 lb/MBtu in a cyclone fired boiler. The host site for the tests was AmerenUE's Sioux Unit 1, a 500 MW cyclone fired boiler located near St. Louis, MO. Reaction Engineering International (REI) led the project team including AmerenUE, FuelTech Inc., and the Electric Power Research Institute (EPRI). This layered approach to NOx reduction is termed the Advanced Layered Technology Approach (ALTA). Installed RRI and SNCR port locations were guided by computational fluid dynamics (CFD) based modeling conducted by REI. During the parametric testing, NOx emissions of 0.12 lb/MBtu were achieved consistently from overfire air (OFA)-only baseline NOx emissions of 0.25 lb/MBtu or less, when firing the typical 80/20 fuel blend of Powder River Basin (PRB) and Illinois No.6 coals. From OFA-only baseline levels of 0.20 lb/MBtu, NOx emissions of 0.12 lb/MBtu were also achieved, but at significantly reduced urea flow rates. Under the deeply staged conditions that were tested, RRI performance was observed to degrade as higher blends of Illinois No.6 were used. NOx emissions achieved with ALTA while firing a 60/40 blend were approximately 0.15 lb/MBtu. NOx emissions while firing 100% Illinois No.6 were approximately 0.165 lb/MBtu. Based on the performance results of these tests, economics analyses of the application of ALTA to a nominal 500 MW cyclone unit show that the levelized cost to achieve 0.15 lb/MBtu is well below 75% of the cost of a state of the art SCR.

Marc A. Cremer; Bradley R. Adams

2006-06-30T23:59:59.000Z

172

Public agency cost savings from standardizing energy management temperature control systems  

SciTech Connect

In 1992, the city of Phoenix, AZ, standardized its energy management temperature control systems (EMTCS) in the construction of a 5-year series of projects that included a new library, city hall, renovated art museum, a museum of science and technology, a parking garage, and a rebuilt municipal building. This article presents an evaluation of the city`s philosophy for the standardization of EMTCS equipment, the issue of interconnectibility, and development and procurement guidance. Our research indicates that the perception that front-end costs increase when EMTCS work is not bid competitively is exaggerated. We also found that it is easier for private businesses to make sole source procurement decisions than it is for governments, because businesses are not constrained by laws that require awarding contracts to the lowest bidder. 1 tab.

Mayo, R.E.; Badger, W.W.; Bashford, H.H.

1995-04-01T23:59:59.000Z

173

Material Control and Accounting Design Considerations for High-Temperature Gas Reactors  

Science Conference Proceedings (OSTI)

The subject of this report is domestic safeguards and security by design (2SBD) for high-temperature gas reactors, focusing on material control and accountability (MC&A). The motivation for the report is to provide 2SBD support to the Next Generation Nuclear Plant (NGNP) project, which was launched by Congress in 2005. This introductory section will provide some background on the NGNP project and an overview of the 2SBD concept. The remaining chapters focus specifically on design aspects of the candidate high-temperature gas reactors (HTGRs) relevant to MC&A, Nuclear Regulatory Commission (NRC) requirements, and proposed MC&A approaches for the two major HTGR reactor types: pebble bed and prismatic. Of the prismatic type, two candidates are under consideration: (1) GA's GT-MHR (Gas Turbine-Modular Helium Reactor), and (2) the Modular High-Temperature Reactor (M-HTR), a derivative of Areva's Antares reactor. The future of the pebble-bed modular reactor (PBMR) for NGNP is uncertain, as the PBMR consortium partners (Westinghouse, PBMR [Pty] and The Shaw Group) were unable to agree on the path forward for NGNP during 2010. However, during the technology assessment of the conceptual design phase (Phase 1) of the NGNP project, AREVA provided design information and technology assessment of their pebble bed fueled plant design called the HTR-Module concept. AREVA does not intend to pursue this design for NGNP, preferring instead a modular reactor based on the prismatic Antares concept. Since MC&A relevant design information is available for both pebble concepts, the pebble-bed HTGRs considered in this report are: (1) Westinghouse PBMR; and (2) AREVA HTR-Module. The DOE Office of Nuclear Energy (DOE-NE) sponsors the Fuel Cycle Research and Development program (FCR&D), which contains an element specifically focused on the domestic (or state) aspects of SBD. This Material Protection, Control and Accountancy Technology (MPACT) program supports the present work summarized in this report, namely the development of guidance to support the consideration of MC&A in the design of both pebble-bed and prismatic-fueled HTGRs. The objective is to identify and incorporate design features into the facility design that will cost effectively aid in making MC&A more effective and efficient, with minimum impact on operations. The theft of nuclear material is addressed through both MC&A and physical protection, while the threat of sabotage is addressed principally through physical protection.

Trond Bjornard; John Hockert

2011-08-01T23:59:59.000Z

174

Controlling Deformation in Elastic and Viscoelastic Beams Due to Temperature and Moisture Changes Using Piezoelectric Actuator  

E-Print Network (OSTI)

This thesis analyzes the implementation of surface bonded piezoelectric actuators to control or minimize the deformation in elastic or viscoelastic cantilever beams due to simultaneous heat and moisture diffusion. The problem is addressed in the context of linearized elasticity and linearized viscoelasticity. The constitutive equations are derived from the balance laws for mass, linear and angular momenta, energy, entropy and the second law of thermodynamics. The constitutive equations for linearized elasticity are then obtained as a consequence of small deformation assumption. The temperature and moisture induced deformation is introduced through the coefficient of thermal expansion CTE and coefficient of moisture expansion CME. The constitutive equations for linearized viscoelasticity are obtained by correspondence principle. The coupled temperature and moisture diffusion equations are obtained as a consequence of Clausius-Duhem inequality. The extent of coupling between heat conduction and moisture diffusion phenomena is studied by varying the ratio of their diffusivities and a non-dimensional coupling parameter. The effect of coupled unsteady heat conduction and moisture diffusion phenomena on the short and long term response characteristics of the beam such as displacement, stress and strain fields is studied. Based on these response characteristics, the magnitude of external actuating voltage required to minimize deformation is predicted. This is followed by a comparative study of the field variables in cases of actuated and unactuated beams. Four materials are chosen for this study; aluminium, epoxy, carbon fiber reinforced polymer with fiber volume fraction of 60 percent, and an epoxy-like viscoelastic material. The viscoelastic material is assumed to be thermorheologically simple. The shift factor is assumed to be a linear function of temperature and moisture fields. To address this problem numerically, a finite difference formulation is presented for the field equations and boundary conditions. This numerical scheme is validated by solving the problem of uniformly loaded cantilever beam and comparing the results with the analytical solution known a priori. The results obtained numerically are validated by comparison with experimental results. It is observed that the under the effect of external actuation, the stress and displacement fields are largely minimized in all four cases chosen for study. The bending in the unactuated viscoelastic beam is more pronounced than bending in the unactuated elastic beam. This is due to the softening of the material with time due to evolving temperature and moisture fields. However, relatively lesser external actuating voltage is necessary to minimize bending in the former case compared to the latter. The magnitude of actuating electric field required in the piezoelectric layer suggests a need to address the problem with in a non-linear framework, no such attempt is made in this study.

Kuravi, Ramachandra Srinivasa Chaitanya

2011-05-01T23:59:59.000Z

175

Rooftop Unit Suite: RTU Challenge, RTU Advanced Controls and RTU Smart Monitoring and Diagnostic System  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Suite of Projects Suite of Projects RTU Suite: RTU Challenge, RTU Advanced Controls and RTU Smart Monitoring and Diagnostic System Michael Brambley, Ph.D. Pacific Northwest National Laboratory Michael.Brambley@pnnl.gov (509) 375-6875 April 4, 2013 2 | Building Technologies Office eere.energy.gov * Packaged air conditioners and heat pumps (RTUs) are used in about 58% of all cooled commercial buildings, serving about 69% of the cooled commercial building floor space (EIA 2003) - Navigant estimates that packaged air conditioners

176

Rooftop Unit Suite: RTU Challenge, RTU Advanced Controls and RTU Smart Monitoring and Diagnostic System  

NLE Websites -- All DOE Office Websites (Extended Search)

Suite of Projects Suite of Projects RTU Suite: RTU Challenge, RTU Advanced Controls and RTU Smart Monitoring and Diagnostic System Michael Brambley, Ph.D. Pacific Northwest National Laboratory Michael.Brambley@pnnl.gov (509) 375-6875 April 4, 2013 2 | Building Technologies Office eere.energy.gov * Packaged air conditioners and heat pumps (RTUs) are used in about 58% of all cooled commercial buildings, serving about 69% of the cooled commercial building floor space (EIA 2003) - Navigant estimates that packaged air conditioners

177

Evaluation of ceramic filters for high-temperature/high-pressure fine particulate control. Final report Dec 75-Jun 76  

SciTech Connect

High temperature gas turbines used to generate electric power require gas streams virtually free of particulate matter. Gas streams from high temperature, high pressure coal processes, such as low Btu gasification and pressurized fluidized bed combustion, require considerable particulate removal. In order to maintain high thermal efficiency the particulate clean-up must be done at the high temperatures of the process. Many new concepts for fine particulate control at elevated temperatures are presently being proposed. One such concept utilizes ceramic membrane filters. The report gives results of a study to analyze and evaluate ceramic membrane filters as a new, fine particulate (<3 um) control concept for high-temperature (approx. 900/sup 0/C), high-pressure processes. Several ceramic filters were identified as potential candidates for fine particulate removal. There does not seem to be any inherent material limitation to high-temperature operation; however, no evidence of high-temperature filter application was found. The filters typically are 2-6 mm thick, cylindrical, and available with various pore sizes, increasing upward from 0.5 um. These elements may be suitable for fine particulate control in hot gas streams. The most promising, although undeveloped, idea for a ceramic filter is to use ceramic honeycomb monoliths similar to those available for catalyst supports and heat exchangers. The walls of the monoliths are about 0.2-0.4 mm thick and of varying pore size and porosity. Geometric configurations are available which would force the gas to flow through the membrane walls. Pressure losses would be very small relative to those of standard ceramic filter elements. The application of ceramic monoliths to high-temperature fine particulate control appears very promising. It is strongly recommended that this concept be investigated further.

Poe, G.G.; Evans, R.M.; Bonnett, W.S.; Waterland, L.R.

1977-02-01T23:59:59.000Z

178

Emissions of Transport Refrigeration Units with CARB Diesel, Gas-to-Liquid Diesel, and Emissions Control Devices  

Science Conference Proceedings (OSTI)

A novel in situ method was used to measure emissions and fuel consumption of transport refrigeration units (TRUs). The test matrix included two fuels, two exhaust configurations, and two TRU engine operating speeds. Test fuels were California ultra low sulfur diesel and gas-to-liquid (GTL) diesel. Exhaust configurations were a stock muffler and a Thermo King pDPF diesel particulate filter. The TRU engine operating speeds were high and low, controlled by the TRU user interface. Results indicate that GTL diesel fuel reduces all regulated emissions at high and low engine speeds. Application of a Thermo King pDPF reduced regulated emissions, sometimes almost entirely. The application of both GTL diesel and a Thermo King pDPF reduced regulated emissions at high engine speed, but showed an increase in oxides of nitrogen at low engine speed.

Barnitt, R. A.; Chernich, D.; Burnitzki, M.; Oshinuga, A.; Miyasato, M.; Lucht, E.; van der Merwe, D.; Schaberg, P.

2010-05-01T23:59:59.000Z

179

Supercritical Boiler Tube Wall Temperature Test Base on the Power Plant Control System Database  

Science Conference Proceedings (OSTI)

In order to precisely learn the working condition of 600MW supercritical boiler, new temperature measuring points are set on the super-heater tube wall inner the flue. Since the working condition of 600MW supercritical boiler is quite severe, the temperature ... Keywords: supercritical boiler, database, temperature test, super-heater

Yu Yanzhi; Zhang Liangbo; Xu Haichuan; Chen Duogang; Dong Gongjun; Shen Bo; Liu Sheng

2010-06-01T23:59:59.000Z

180

Improvement of TEOS-chemical mechanical polishing performance by control of slurry temperature  

Science Conference Proceedings (OSTI)

Effects of slurry temperature on the chemical mechanical polishing (CMP) performance of tetra-ethyl ortho-silicate (TEOS) film with silica and ceria slurries were investigated. The change of slurry properties as a function of different slurry temperatures ... Keywords: Chemical mechanical polishing, Planarity, Removal rate, Slurry temperature, Tetra-ethyl ortho-silicate

Nam-Hoon Kim; Pil-Ju Ko; Yong-Jin Seo; Woo-Sun Lee

2006-02-01T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


181

A Thermostat Fuzzy Control System Based on MCU  

Science Conference Proceedings (OSTI)

A thermostat is an automatic temperature control unit, which operating environment is featuring by non-linear, inertial and time-variant. Traditional control can not achieve satisfied performance. As one large embranchment of non-linear control, fuzzy ...

Chenluan Wang

2009-11-01T23:59:59.000Z

182

Design and experience with the WS/HS assembly movement using labview VIS, national instrument motion controllers, and compumotor electronic drive units and motors  

SciTech Connect

The Low-Energy Demonstration Accelerator (LEDA), designed and built at the Los Alamos National Laboratory, is part of the Accelerator Production of Tritium (APT) program and provides a platform for measuring high-power proton beam-halo formation. The technique used for measuring the beam halo employs nine combination Wire Scanner and Halo Scraper (WS/HS) devices. This paper will focus on the experience gained in the use of National Instrument (NI) LabVIEW VIs and motion controllers, and Compumotor electronic drive units and motors. The base configuration couples a Compumotor motor driven by a Parker-Hannifin Gemini GT Drive unit. The drive unit is controlled by a NI PXI-7344 controller card, which in turn is controlled by a PC running custom built NI LabVIEW VIs. The function of the control VI's is to interpret instructions from the main control system, the Experimental Physics and Industrial Control System (EPICS), and carry out the corresponding motion commands. The main control VI has to run all nineteen WS/HS motor axes used in the accelerator. A basic discussion of the main accelerator control system, EPICs which is hosted on a VXI platform, and its interface with the PC based LabVIEW motion control software will be included.

Day, L. A. (Lisa A.); Gilpatrick, J. D. (John Douglas); Gruchalla, M. (Michael); Martinez, D. G. (Derwin G.); O' Hara, J. F. (James F.); Shurter, R. B. (Robert B.); Stettler, M. W. (Matthew W.); Valdiviez, R. (Robert); Barr, D. S. (Dean S.)

2001-01-01T23:59:59.000Z

183

Driving Down HB-LED Costs: Implementation of Process Simulation Tools and Temperature Control Methods of High Yield MOCVD Growth  

SciTech Connect

The overall objective of this multi-faceted program is to develop epitaxial growth systems that meet a goal of 75% (4X) cost reduction in the epitaxy phase of HB-LED manufacture. A 75% reduction in yielded epitaxy cost is necessary in order to achieve the cost goals for widespread penetration of HB-LEDâ??s into back-lighting units (BLU) for LCD panels and ultimately for solid-state lighting (SSL). To do this, the program will address significant improvements in overall equipment Cost of Ownership, or CoO. CoO is a model that includes all costs associated with the epitaxy portion of production. These aspects include cost of yield, capital cost, operational costs, and maintenance costs. We divide the program into three phases where later phases will incorporate the gains of prior phases. Phase one activities are enabling technologies. In collaboration with Sandia National Laboratories we develop a Fluent-compatible chemistry predictive model and a set of mid-infrared and near-ultraviolet pyrometer monitoring tools. Where previously the modeling of the reactor dynamics were studied within FLUENT alone, here, FLUENT and Chemkin are integrated into a comprehensive model of fluid dynamics and the most advanced transport equations developed for Chemkin. Specifically, the Chemkin model offered the key reaction terms for gas-phase nucleation, a key consideration in the optimization of the MOCVD process. This new predictive model is used to design new MOCVD reactors with optimized growth conditions and the newly developed pyrometers are used monitor and control the MOCVD process temperature to within 0.5°C run-to-run and within each wafer. This portion of the grant is in collaboration with partners at Sandia National Laboratories. Phase two activities are continuous improvement projects which extend the current reactor platform along the lines of improved operational efficiency, improved systems control for throughput, and carrier modifications for increased yield. Programmatically, improvements made in Phase I are applied to developments of Phase II when applicable. Phase three is the culmination of the individual tasks from both phases one and two applied to proposed production platforms. We selectively combine previously demonstrated tasks and other options to develop a high-volume production-worthy MOCVD system demonstrating >3x throughput, 1.3x capital efficiency, and 0.7x cost of ownership. In a parallel demonstration we validate the concept of an improved, larger deposition system which utilizes the predictive modeling of chemistry-based flow analysis and extensions of the improvements demonstrated on the current platforms. This validation includes the build and testing of a prototype version of the hardware and demonstration of 69% reduction in the cost of ownership. Also, in this phase we present a stand-alone project to develop a high-temperature system which improves source efficiency by 30% while concurrently increasing growth rate by 1.3x. The material quality is held to the same material quality specifications of our existing baseline processes. The merits of other line item tasks in phase three are discussed for inclusion on next-generation platforms.

William Quinn

2012-04-30T23:59:59.000Z

184

Controlling fuel and diluent gas flow for a diesel engine operating in the fuel rich low-temperature-combustion mode  

E-Print Network (OSTI)

The flow of a diluent gas supplied to a motoring engine was controlled at a diluent to air mass flow ratios of 10%, 30%, 50%, and 70%. This arrangement was a significant set up for running the engine in the Low-Temperature ...

Lopez, David M

2007-01-01T23:59:59.000Z

185

Control system for fluid heated steam generator  

DOE Patents (OSTI)

A control system for controlling the location of the nucleate-boiling region in a fluid heated steam generator comprises means for measuring the temperature gradient (change in temperature per unit length) of the heating fluid along the steam generator; means for determining a control variable in accordance with a predetermined function of temperature gradients and for generating a control signal in response thereto; and means for adjusting the feedwater flow rate in accordance with the control signal.

Boland, James F. (Bonneville County, ID); Koenig, John F. (Idaho Falls, ID)

1985-01-01T23:59:59.000Z

186

Control system for fluid heated steam generator  

DOE Patents (OSTI)

A control system for controlling the location of the nucleate-boiling region in a fluid heated steam generator comprises means for measuring the temperature gradient (change in temperature per unit length) of the heating fluid along the steam generator; means for determining a control variable in accordance with a predetermined function of temperature gradients and for generating a control signal in response thereto; and means for adjusting the feedwater flow rate in accordance with the control signal.

Boland, J.F.; Koenig, J.F.

1984-05-29T23:59:59.000Z

187

Controlled temperature expansion in oxygen production by molten alkali metal salts  

SciTech Connect

A continuous process is set forth for the production of oxygen from an oxygen containing gas stream, such as air, by contacting a feed gas stream with a molten solution of an oxygen acceptor to oxidize the acceptor and cyclically regenerating the oxidized acceptor by releasing oxygen from the acceptor wherein the oxygen-depleted gas stream from the contact zone is treated sequentially to temperature reduction by heat exchange against the feed stream so as to condense out entrained oxygen acceptor for recycle to the process, combustion of the gas stream with fuel to elevate its temperature and expansion of the combusted high temperature gas stream in a turbine to recover power.

Erickson, Donald C. (Annapolis)

1985-06-04T23:59:59.000Z

188

Air Pollution Control Regulations: No. 13- Particulate Emissions from Fossil Fuel Fired Steam or Hot Water Generating Units (Rhode Island)  

Energy.gov (U.S. Department of Energy (DOE))

The purpose of this regulation is to limit emissions of particulate matter from fossil fuel fired and wood-fired steam or hot water generating units.

189

Controlled temperature expansion in oxygen production by molten alkali metal salts  

DOE Patents (OSTI)

A continuous process is set forth for the production of oxygen from an oxygen containing gas stream, such as air, by contacting a feed gas stream with a molten solution of an oxygen acceptor to oxidize the acceptor and cyclically regenerating the oxidized acceptor by releasing oxygen from the acceptor wherein the oxygen-depleted gas stream from the contact zone is treated sequentially to temperature reduction by heat exchange against the feed stream so as to condense out entrained oxygen acceptor for recycle to the process, combustion of the gas stream with fuel to elevate its temperature and expansion of the combusted high temperature gas stream in a turbine to recover power. 1 fig.

Erickson, D.C.

1985-06-04T23:59:59.000Z

190

Influence of climate model biases and daily-scale temperature and precipitation events on hydrological impacts assessment: A case study of the United States  

Science Conference Proceedings (OSTI)

The Intergovernmental Panel on Climate Change's Fourth Assessment Report concludes that climate change is now unequivocal, and associated increases in evaporation and atmospheric water content could intensify the hydrological cycle. However, the biases and coarse spatial resolution of global climate models limit their usefulness in hydrological impact assessment. In order to reduce these limitations, we use a high-resolution regional climate model (RegCM3) to drive a hydrological model (variable infiltration capacity) for the full contiguous United States. The simulations cover 1961-1990 in the historic period and 2071-2100 in the future (A2) period. A quantile-based bias correction technique is applied to the times series of RegCM3-simulated precipitation and temperature. Our results show that biases in the RegCM3 fields not only affect the magnitude of hydrometeorological variables in the baseline hydrological simulation, but they also affect the response of hydrological variables to projected future anthropogenic increases in greenhouse forcing. Further, we find that changes in the intensity and occurrence of severe wet and hot events are critical in determining the sign of hydrologic change. These results have important implications for the assessment of potential future hydrologic changes, as well as for developing approaches for quantitative impacts assessment.

Ashfaq, Moetasim [ORNL; Bowling, Laura C. [Purdue University; Cherkauer, Keith [Purdue University; Pal, Jeremy [Loyola University; Diffenbaugh, Noah [Stanford University

2010-01-01T23:59:59.000Z

191

Temperature and combustion quality control in power station boilers using artificial neural networks  

Science Conference Proceedings (OSTI)

The classification is an important domain in boiler flame image processing and is a preliminary step toward detection, recognition and understanding of combustion condition. In this paper, Back Propagation Algorithm (BPA) is introduced for boiler flame ... Keywords: Back Propagation Algorithm, Fisher's linear discriminant analysis, combustion quality, features, flame colour, image processing, temperature identification

K. Sujatha; N. Pappa

2010-09-01T23:59:59.000Z

192

ORIGINAL PAPER Two methods of temperature control for single-molecule  

E-Print Network (OSTI)

Abstract Modern single-molecule biophysical experi- ments require high numerical aperture oil heat pump mounted on an objective collar with a proportional­integral­differential (PID) feedback by the power of the heat- pump and the ability of the objective to withstand large and sudden temperature

Berry, Richard

193

Controllable Atomic Scale Patterning of Freestanding Monolayer Graphene at Elevated Temperature  

E-Print Network (OSTI)

cross-sections for graphene knock-on damage and STEM imaging. Two threshold voltages 140 kV (red line are multiple times. Figure S3. High-resolution STEM imaging of graphene at 700 °C using 300 kV electrons (outlined by red lines). (b) at room temperature, scanning electron beam on graphene induced contamination

Dunin-Borkowski, Rafal E.

194

Unit Conversion  

Science Conference Proceedings (OSTI)

Unit Conversion. ... Unit Conversion Example. "If you have an amount of unit of A, how much is that in unit B?"; Dimensional Analysis; ...

2012-12-04T23:59:59.000Z

195

Survey Automatic control in microelectronics manufacturing: Practices, challenges, and possibilities  

Science Conference Proceedings (OSTI)

Advances in modeling and control will be required to meet future technical challenges in microelectronics manufacturing. The implementation of closed-loop control on key unit operations has been limited due to a dearth of suitable in situ measurements, ... Keywords: End point control, Factory automation, Microelectronics manufacturing, Predictive control, Process control, Quality control, Sensors, Temperature control

Thomas F. Edgar; Stephanie W. Butler; W.Jarrett Campbell; Carlos Pfeiffer; Christopher Bode; Sung Bo Hwang; K. S. Balakrishnan; J. Hahn

2000-11-01T23:59:59.000Z

196

HRP-EVALUATION OF HEAT REMOVAL METHODS FOR CONTROLLING TEMPERATURES OF AN ORR SLURRY BOMB  

SciTech Connect

Two methods were evaluated for removal of 1 to 5 kilowatts from a 1-in.- diam. by 10 in. long bomb to be (W-7405-eng-261. 8O(ph OTS); 70(mf OTS). maintained at 250 to 300 deg C. Conductance control, varying the composition of a helium--air mixture in a 8 mil annulus to give a controlled conduction heat transfer resistance, gave a simple, smooth, flexible control method. Use of water sprayed into air gave the required range of heat fluxes, but sometimes gave uncontrollable instabilities due to progressive vapor binding. (auth)

Holmes, J.M.

1958-06-16T23:59:59.000Z

197

The Coordinated Control of a Central Air Conditioning System Based on Variable Chilled Water Temperature and Variable Chilled Water Flow  

E-Print Network (OSTI)

At present, regulation of water flow by means of pump frequency conversion is one of the major methods for power-saving in central air conditioning systems. In this article, optimization regulation for central air conditioning system on the basis of coordinative optimization control for variable chilled water temperature and variable chilled water flow to obtain better power savings is put forward. According to typical meteorological year data, hourly air conditioning load of whole year for every typical room has been calculated with the transmission function method. In order to guarantee each typical room, the highest cooling load rate is used as an input parameter for optimization calculation. Based on the surface cooler check model, the smallest energy consumption of chiller and chiller water pump was taken as the objective function of the optimization model. The performance characteristics of a chiller, water pump, regulation valve and pipeline are taken into account, and the optimization chilled water temperature and chilled water flow were carried out. The case study for a commercial building in Guangzhou showed that the annual power consumption of the chillers and pumps of the air conditioning system is lower by 17% only with employment of variable water flow regulation by pump frequency conversion. In the case of optimization control with coordinative control of variable chilled water temperature and variable chilled water flow, the annual power consumption of the chillers and pumps of the air conditioning system is reduced by 22% in presence of remarkable power saving effects. Increasing the chilled water temperature will reduce the dehumidified capability of the air cooler, and the indoor relative humidity will increase. The simulation showed that the adjustment optimized process meets the comfort of each typical room. The lower the cooling load rate is, the more obvious the effect of power-saving is. The highest power-saving rate appears in December, which is 36.7%. Meanwhile, the least rate appears in July, which is only 14.5%.

Liu, J.; Mai, Y.; Liu, X.

2006-01-01T23:59:59.000Z

198

united stadium. united station.  

E-Print Network (OSTI)

??DC United is one of Major League Soccerâs most decorated franchises, yet it still plays its home games within the crumbling confines of RFK Stadium.… (more)

Groff, David R.

2011-01-01T23:59:59.000Z

199

Precision control of high temperature furnaces using an auxiliary power supply and charged particle current flow  

DOE Patents (OSTI)

Two power supplies are combined to control a furnace. A main power supply heats the furnace in the traditional manner, while the power from the auxiliary supply is introduced as a current flow through charged particles existing due to ionized gas or thermionic emission. The main power supply provides the bulk heating power and the auxiliary supply provides a precise and fast power source such that the precision of the total power delivered to the furnace is improved. 5 figs.

Pollock, G.G.

1997-01-28T23:59:59.000Z

200

Precision control of high temperature furnaces using an auxiliary power supply and charged practice current flow  

DOE Patents (OSTI)

Two power supplies are combined to control a furnace. A main power supply heats the furnace in the traditional manner, while the power from the auxiliary supply is introduced as a current flow through charged particles existing due to ionized gas or thermionic emission. The main power supply provides the bulk heating power and the auxiliary supply provides a precise and fast power source such that the precision of the total power delivered to the furnace is improved.

Pollock, George G. (San Ramon, CA)

1997-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


201

Temperature and vital effect controls on Bamboo coral (Isididae) isotopegeochemistry: A test of the "lines method"  

SciTech Connect

Deep-sea bamboo corals hold promise as long-term climatic archives, yet little information exists linking bamboo coral geochemistry to measured environmental parameters. This study focuses on a suite of 10 bamboo corals collected from the Pacific and Atlantic basins (250-2136 m water depth) to investigate coral longevity, growth rates, and isotopic signatures. Calcite samples for stable isotopes and radiocarbon were collected from the base the corals, where the entire history of growth is recorded. In three of the coral specimens, samples were also taken from an upper branch for comparison. Radiocarbon and growth band width analyses indicate that the skeletal calcite precipitates from ambient dissolved inorganic carbon and that the corals live for 150-300 years, with extension rates of 9-128 {micro}m/yr. A linear relationship between coral calcite {delta}{sup 18}O and {delta}{sup 13}C indicates that the isotopic composition is influenced by vital effects ({delta}{sup 18}O:{delta}{sup 13}C slope of 0.17-0.47). As with scleractinian deep-sea corals, the intercept from a linear regression of {delta}{sup 18}O versus {delta}{sup 13}C is a function of temperature, such that a reliable paleotemperature proxy can be obtained, using the 'lines method.' Although the coral calcite {delta}{sup 18}O:{delta}{sup 13}C slope is maintained throughout the coral base ontogeny, the branches and central cores of the bases exhibit {delta}{sup 18}O:{delta}{sup 13}C values that are shifted far from equilibrium. We find that a reliable intercept value can be derived from the {delta}{sup 18}O:{delta}{sup 13}C regression of multiple samples distributed throughout one specimen or from multiple samples within individual growth bands.

Hill, T M; Spero, H J; Guilderson, T P; LaVigne, M; Clague, D; Macalello, S; Jang, N

2011-03-01T23:59:59.000Z

202

Implementation of Real-Time Quality Control Procedures by Means of a Probabilistic Estimate of Seawater Temperature and Its Temporal Evolution  

Science Conference Proceedings (OSTI)

Near-real-time quality control procedures for temperature profiles collected from ships of opportunity were implemented during the 1980s in oceans across the world and from the 1990s in the Mediterranean. In this sea, the procedures were ...

Giuseppe M. R. Manzella; Marco Gambetta

2013-03-01T23:59:59.000Z

203

A Model to Estimate the Time of Observation Bias Associated with Monthly Mean Maximum, Minimum and Mean Temperatures for the United States  

Science Conference Proceedings (OSTI)

Hourly data for 79 stations in the United States are used to develop an empirical model which can be used to estimate the time of observation bias associated with different observation schedules. The model is developed for both maximum and ...

Thomas R. Karl; Claude N. Williams Jr.; Pamela J. Young; Wayne M. Wendland

1986-02-01T23:59:59.000Z

204

IT enabled redesign of export procedure for high-value pharmaceutical product under temperature control: the case of drug living lab  

Science Conference Proceedings (OSTI)

In this paper, we analyze and redesign the export procedure for shipping a high-value pharmaceutical product in a strict temperature-controlled logistics environment (cold chain) from Ireland to the US using the e3-control methodology. The ... Keywords: G2B, business process redesign, case study, export procedure, redesign methodology

Jianwei Liu; Allen Higgins; Yao-Hua Tan

2010-05-01T23:59:59.000Z

205

Modulation and SSR tests performed on the BPA 500 kV thyristor controlled series capacitor unit at Slatt substation  

SciTech Connect

Field experience is reported for a thyristor controlled series capacitor (TCSC) recently commissioned at BPA`s Slatt substation. Subsynchronous resonance tests show that TCSC interactions with shaft dynamics of PGE`s Boardman steam generator are well understood and are effectively avoided by normal TCSC valve firing logic. Modulation tests, performed with the Boardman plant off line, show that the TCSC can be a powerful and responsive actuator for swing damping. Security considerations did not permit lightly damped operation of the controlled plant. Close analysis indicates that the TCSC damping contribution, though small, was measurable. The best estimate is that damping for the McNary mode is 7.33% and 8.55%, for the TCSC damper loop open and closed respectively. TCSC testing and monitoring is facilitated by an advanced interactive measurement network representing BPA`s approach to the information requirements of major control systems.

Hauer, J.F. [Pacific Northwest Lab., Richland, WA (United States); Mittelstadt, W.A. [Bonneville Power Administration, Portland, OR (United States); Piwko, R.J. [General Electric Co., Schenectady, NY (United States); Damsky, B.L. [Electric Power Research Inst., Palo Alto, CA (United States); Eden, J.D. [Portland General Electric, OR (United States)

1996-05-01T23:59:59.000Z

206

Impact of Solar Control PVB Glass on Vehicle Interior Temperatures, Air-Conditioning Capacity, Fuel Consumption, and Vehicle Range  

DOE Green Energy (OSTI)

The objective of the study was to assess the impact of Saflex1 S-series Solar Control PVB (polyvinyl butyral) configurations on conventional vehicle fuel economy and electric vehicle (EV) range. The approach included outdoor vehicle thermal soak testing, RadTherm cool-down analysis, and vehicle simulations. Thermal soak tests were conducted at the National Renewable Energy Laboratory's Vehicle Testing and Integration Facility in Golden, Colorado. The test results quantified interior temperature reductions and were used to generate initial conditions for the RadTherm cool-down analysis. The RadTherm model determined the potential reduction in air-conditioning (A/C) capacity, which was used to calculate the A/C load for the vehicle simulations. The vehicle simulation tool identified the potential reduction in fuel consumption or improvement in EV range between a baseline and modified configurations for the city and highway drive cycles. The thermal analysis determined a potential 4.0% reduction in A/C power for the Saflex Solar PVB solar control configuration. The reduction in A/C power improved the vehicle range of EVs and fuel economy of conventional vehicles and plug-in hybrid electric vehicles.

Rugh, J.; Chaney, L.; Venson, T.; Ramroth, L.; Rose, M.

2013-04-01T23:59:59.000Z

207

Remote Sensing of Temperature Profiles from a Combination of Observations from the Satellite-Based Microwave Sounding Unit and the Ground-Based Profiler  

Science Conference Proceedings (OSTI)

Temperature profiles are derived from ground- and satellite-based microwave radiometric observations. Data taken by the NOAA Profiler during December 1981 to December 1982, at Stapleton International Airport, Denver, Colorado, are combined with ...

Ed R. Westwater; Wang Zhenhui; Norman C. Grody; Larry M. McMillin

1985-06-01T23:59:59.000Z

208

The Vertical Profile of Wind and Temperature in Cyclones and Anticyclones over the Eastern Two-Thirds of the United States: A Climatology  

Science Conference Proceedings (OSTI)

A climatological analysis, based upon operational surface and upper-air data from 1957 to 1994, of the wind and temperature profiles composited with respect to each quadrant of surface cyclones and anticyclones, is presented for the eastern two-...

Howard B. Bluestein; Peter C. Banacos

2002-03-01T23:59:59.000Z

209

The Effects of Data Gaps on the Calculated Monthly Mean Maximum and Minimum Temperatures in the Continental United States: A Spatial and Temporal Study  

Science Conference Proceedings (OSTI)

Gaps in otherwise regularly scheduled observations are often referred to as missing data. This paper explores the spatial and temporal impacts that data gaps in the recorded daily maximum and minimum temperatures have on the calculated monthly ...

David E. Stooksbury; Craig D. Idso; Kenneth G. Hubbard

1999-05-01T23:59:59.000Z

210

Response of the SPND measurement system to temperature during the Three Mile Island Unit 2 accident. [Self-Powered Neutron Detector  

SciTech Connect

The Self-Powered Neutron Detector (SPND) Measuring System is evaluated to determine its ability to indicate temperatures of the fuel rods in the TMI-2 reactor core during the accident. It is concluded for the following reasons that the SPND Measuring System did not provide fuel rod temperatures during the accident: the heat transfer characteristics vary over a range of five octaves; within the range of 1200 to 1800/sup 0/F, the SPND responds to temperature from convection radiation from the fuel rods and self-heating from the gamma flux; within the range of 1200 to 1800/sup 0/F, the signal cable introduces masking signals that are a function of gamma heating, integrated temperature over the cable, and core water level velocity; the data system's worst-case signal-to-noise ratio from aliasing is 0dB; and the recorder system's worst-case signal-to-noise ratio from aliasing is -24dB.

Wilde, N.; Morrison, J.L. Jr.

1981-12-01T23:59:59.000Z

211

Towards a Self-Consistent and Controllable Graviton Flux A new Strategy to Compare Different-Dimensional Fluxes via Unit Scale Reference  

E-Print Network (OSTI)

-Dimensional Fluxes via Unit Scale Reference Bernd Binder http://www.quanics.com/, Germany, 88679 Salem, P.O. Box 1247 should intersect at the unit scale since any power of 1 is 1. The basic reference and gravitational unit scale is given by a Kepler dynamics with unit radius and unit angular velocity that can be assigned

Binder, Bernd

212

Legend Units  

Science Conference Proceedings (OSTI)

... Syntax: LEGEND UNIT units> where is an integer number or parameter in the range 1 to 100 that specifies the legend identifier; and ...

2013-11-27T23:59:59.000Z

213

Temperature Variability over Africa  

Science Conference Proceedings (OSTI)

The variation of near-surface air temperature anomalies in Africa between 1979 and 2010 is investigated primarily using Microwave Sounding Unit (MSU) total lower-tropospheric temperature data from the Remote Sensing Systems (RSS) and the ...

Jennifer M. Collins

2011-07-01T23:59:59.000Z

214

Climatic Temperature Normals  

Science Conference Proceedings (OSTI)

The published 1951–80 daily normals of maximum and minimum temperatures were prepared by interpolating between average monthly values. This study compares the published normal and 30-yr average daily temperatures in the eastern half of the United ...

Nathaniel B. Guttman; Marc S. Plantico

1987-10-01T23:59:59.000Z

215

Comparison of resource assessment methods and geologic controls--deep natural gas plays and zones, United States and Russia  

Science Conference Proceedings (OSTI)

Deep (greater than 4.5 km--15,000 ft) conventional natural gas resources will play an important role in the future energy needs of the United States and Russia. Deep sedimentary basins are widespread in these countries and have formed in a variety of depositional and tectonic settings. Significant volumes of undiscovered deep natural gas are in the Gulf Coast, Anadarko, Permian, and Rocky Mountain basins of the U.S., and in the Timan-Pechora, West Siberia, East Siberia, and North and South Caspian basins of the former Soviet Union. Deep natural gas resources are regularly assessed by the All-Russia Petroleum Research Exploration Institute (VNIGRI) and the U.S. Geological Survey (USGS) as part of their normal research activities. Both VNIGRI and the USGS employ similar assessment methods involving play (or zone) analysis using geological data and based on an analysis of confirmed and hypothetical plays using field-size distributions, discovery-process models, and statistical estimation procedures that yield probabilistic estimates of undiscovered accumulations. Resource estimates for the deep structural and statigraphic plays of the Anadarko basin and deep Paleozoic zones in the Timan-Pechora basin are compared and contrasted using both methods. Differences in results of assessments between VNIGRI and USGS arise due to (1) the way in which plays/zones are defined, (2) different geochemical models for hydrocarbon generation as applied to hypothetical plays, (3) variations in the ways in which statistical estimation procedures are applied to plays and regions, and (4) differences in economic and technologic assumptions, reserve growth calculations, and accumulation size limits and ranges.

Dyman, T.S. (Geological Survey, Denver, CO (United States)); Belonin, M.D. (All-Russia Petroleum Research Exploration Inst., St. Petersburg (Russian Federation)) (and others)

1996-01-01T23:59:59.000Z

216

Estimates of Rainfall over the United Kingdom and Surrounding Seas from the SSM/I Using the Polarization Corrected Temperature Algorithm  

Science Conference Proceedings (OSTI)

The 85-GHz polarization corrected temperature (PCT85) algorithm, using the V85 and H85 channels of the SSM/I sensor, is evaluated for estimation of midlatitude rainfall. The algorithm ? parameter and rain/no-rain thresholds are examined and found ...

Martin C. Todd; John O. Bailey

1995-06-01T23:59:59.000Z

217

Analysis of Model-Calculated Soil Moisture over the United States (1931–1993) and Applications to Long-Range Temperature Forecasts  

Science Conference Proceedings (OSTI)

A long time series of monthly soil moisture data during the period of 1931–1993 over the entire U.S. continent has been created with a one-layer soil moisture model. The model is based on the water budget in the soil and uses monthly temperature ...

Jin Huang; Huug M. van den Dool; Konstantine P. Georgarakos

1996-06-01T23:59:59.000Z

218

Selected data for hydrothermal-convection systems in the United States with estimated temperatures greater than or equal to 90/sup 0/C: back-up data for US Geological Survey Circular 790  

DOE Green Energy (OSTI)

A compilation of data used in determining the accessible resource base for identified hydrothermal convection systems greater than or equal to 90/sup 0/C in the United States are presented. Geographic, geologic, chemical, isotopic, volumetric, and bibliographic data and calculated thermal energy contents are listed for all vapor-dominated and hot-water systems with estimated reservoir temperatures greater than or equal to 90/sup 0/C and reservoir depths less than 3 km known to the authors in mid 1978. Data presented here is stored in the US Geological Survey's geothermal computer file GEOTHERM. Data for individual hydrothermal convection systems in each state are arranged geographically from north to south and west to east without regard to the type or temperature of the system. Locations of the systems and corresponding reference numbers are shown on map 1 accompanying US Geological Survey Circular 790.

Mariner, R.H.; Brook, C.A.; Swanson, J.R.; Mabey, D.R.

1978-12-01T23:59:59.000Z

219

Combined cycle electric power plant and heat recovery steam generator having improved multi-loop temperature control of the steam generated  

SciTech Connect

A combined cycle electric power plant is described that includes gas and steam turbines and a steam generator for recovering the heat in the exhaust gases exited from the gas turbine and for using the recovered heat to produce and supply steam to the steam turbine. The steam generator includes a superheater tube and a steam drum from which heated steam is directed through the superheater to be additionally heated into superheated steam by the exhaust gas turbine gases. An afterburner serves to further heat the exhaust gas turbine gases passed to the superheater tube and a bypass conduit is disposed about the superheater tube whereby a variable steam flow determined by a bypass valve disposed in the bypass conduit may be directed about the superheater tube to be mixed with the superheated steam therefrom, whereby the temperature of the superheated steam supplied to the steam turbine may be accurately controlled. Steam temperature control means includes a first control loop responsive to the superheated steam temperature for regulating the position of the bypass valve with respect to a first setpoint, and a second control loop responsive to the superheated steam temperature for controlling the fuel supply to the afterburner with respect to a second setpoint varying in accordance with the bypass valve position. In particular, as the bypass valve position increases, the second setpoint, originally higher, is lowered toward a value substantially equal to that of the first setpoint.

Martz, L.F.; Plotnick, R.J.

1976-08-17T23:59:59.000Z

220

Luminant Martin Lake Unit 3 Intelligent Sootblowing Test Report  

Science Conference Proceedings (OSTI)

A Clyde Bergemann Intelligent Sootblowing (ISB) system was recently installed at Luminant's Martin Lake Unit 3. This report compares the performance of the new ISB system to that of the previous boiler cleaning control system. Criteria monitored during the test included overall heat flux, cleanliness factors from thermodynamic modeling, ash weight, emissions, gas temperatures, and the number of daily sootblower and wallblower operations.

2009-05-01T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


221

p-Hydroxyphenyl (H) Units Lower the Degree of Polymerization in Lignin: Chemical Control in Lignin Biosynthesis  

Science Conference Proceedings (OSTI)

Lignin, composed predominantly of p-hydroxyphenyl (H), guaiacyl (G) and syringyl (S) subunits, is a major component of plant cell walls that imparts resistance toward chemical and microbial deconstruction of plant biomass, rendering its conversion inefficient and costly. Previous studies have shown that alterating lignin composition, i.e., the relative abundance of H, G and S subunits, promises more efficient extraction of sugars from plant biomass. Smaller and less branched lignin chains are more easily extracted during pretreatment, making cellulose more readily degradable. Here, using density functional theory calculations, we show that the incorporation of H subunits into lignin via b-b and b-5 interunit linkages reduces the degree of polymerization in lignin. Frontier molecular orbital analyses of lignin dimers and trimers show that H as a terminal subunit on a growing lignin polymer linked via b-b and b-5 linkage cannot undergo radical formation, preventing further chain growth by endwise polymerization resulting in lignin polymers with lower degree of polymerization. These results indicate that, for endwise polymerization in lignin synthesis, there exists a chemical control that may lay a significant role in determining the structure of lignin.

Sangha, A. K.; Parks, J. M.; Davis, M. F.; Smith, J. C.

2013-01-01T23:59:59.000Z

222

English Units  

Science Conference Proceedings (OSTI)

English Units. A, B, C, D, E, F, G, H, I, J. 1, Steam Point Calculator: English Units, ... 6, Height of steam point apparatus above ground (ft.), 0, ft. ...

2011-12-22T23:59:59.000Z

223

Performance of microprocessor controllers  

SciTech Connect

United States animal production systems are at the threshold of a major new method for daily management of environmental control -- the integrated microprocessor-based environmental control system. Widespread adoption of this technology has the potential for dramatic improvement in production efficiencies through lower management costs, improved energy savings, and better feed conversion efficiencies. However, the technical problems of transient surge protection and appropriate mechanical backup systems have not been adequately addressed by the industry. The goals of this research were to identify the degree to which transient surge protection was being provided by current manufacturers, and to illustrate the implementation of microprocessor environmental control systems with mechanical backup. Transient open circuit over-voltage tests (ANSI/IEEE C62.41-1980) were performed on 16 environmental control units: a maximum of 800 V spike was applied to the power supplies, and up to 100 V spike applied to temperature sensor lines. Under these relatively mild tests, no failures were noted due to power supply transients, but three units failed when subjected to transients on their temperature sensor lines. Mechanical backup systems were designed to provide essential life-support during critical conditions of extreme outside conditions and extreme animal densities. The design and installation of environmental control systems for (1) a gestation unit and (2) a broiler house was performed. An overview of the process, and difficulties noted, is presented. Both systems incorporated mechanical backups. 20 refs.

Gates, R.S.; Turner, L.W.; Overhults, D.G. (Kentucky Univ., Lexington, KY (United States). Dept. of Agricultural Engineering)

1992-01-01T23:59:59.000Z

224

Control of water infiltration into near surface LLW disposal units. Progress report on field experiments at a humid region site, Beltsville, Maryland: Volume 8  

SciTech Connect

This study`s objective is to assess means for controlling water infiltration through waste disposal unit covers in humid regions. Experimental work is being performed in large-scale lysimeters 21.34 m x 13.72 m x 3.05 m (75 ft x 45 ft x 10 ft) at Beltsville, Maryland. Results of the assessment are applicable to disposal of low-level radioactive waste (LLW), uranium mill tailings, hazardous waste, and sanitary landfills. Three kinds of waste disposal unit covers or barriers to water infiltration are being investigated: (1) resistive layer barrier, (2) conductive layer barrier, and (3) bioengineering management. The resistive layer barrier consists of compacted earthen material (e.g., clay). The conductive layer barrier consists of a conductive layer in conjunction with a capillary break. As long as unsaturated flow conditions are maintained, the conductive layer will wick water around the capillary break. Below-grade layered covers such as (1) and (2) will fail if there is appreciable subsidence of the cover, and remedial action for this kind of failure will be difficult. A surface cover, called bioengineering management, is meant to overcome this problem. The bioengineering management surface barrier is easily repairable if damaged by subsidence; therefore, it could be the system of choice under active subsidence conditions. The bioengineering management procedure also has been shown to be effective in dewatering saturated trenches and could be used for remedial action efforts. After cessation of subsidence, that procedure could be replaced by a resistive layer barrier or, perhaps even better, by a resistive layer barrier/conductive layer barrier system. The latter system would then give long-term effective protection against water entry into waste without institutional care.

Schulz, R.K. [California Univ., Los Angeles, CA (United States); Ridky, R.W. [Maryland Univ., College Park, MD (United States). Dept. of Geology; O`Donnell, E. [Nuclear Regulatory Commission, Washington, DC (United States)

1995-04-01T23:59:59.000Z

225

Relative Controls of Asian–Pacific Summer Climate by Asian Land and Tropical–North Pacific Sea Surface Temperature  

Science Conference Proceedings (OSTI)

The dominant pattern of summertime tropical and North Pacific sea surface temperature (SST) is characterized by an out-of-phase relationship between the tropics and the extratropics. This pattern, defined as the tropical–North Pacific mode (TNPM) ...

Ping Zhao; Song Yang; Maoqiu Jian; Junming Chen

2011-08-01T23:59:59.000Z

226

Application of linear multiple model predictive control (MMPC) framework towards dynamic maximazation of oxygen yield in an elevated-pressure air separation unit  

SciTech Connect

In a typical air separation unit (ASU) utilizing either a simple gaseous oxygen (GOX) cycle or a pumped liquid oxygen (PLOX) cycle, the flowrate of liquid nitrogen (LN2) stream connecting high-pressure and low-pressure ASU columns plays an important role in the total oxygen yield. It has been observed that this yield reaches a maximum at a certain optimal flowrate of LN2 stream. At nominal full-load operation, the flowrate of LN2 stream is maintained near this optimum value, whereas at part-load conditions this flowrate is typically modified in proportion with the load-change (oxygen demand) through a ratio/feed-forward controller. Due to nonlinearity in the entire ASU process, the ratio-modified LN2 flowrate does not guarantee an optimal oxygen yield at part-load conditions. This is further exacerbated when process disturbances in form of “cold-box” heat-leaks enter the system. To address this problem of dynamically maximizing the oxygen yield while the ASU undergoes a load-change and/or a process disturbance, a multiple model predictive control (MMPC) algorithm is proposed. This approach has been used in previous studies to handle large ramp-rates of oxygen demand posed by the gasifier in an IGCC plant. In this study, the proposed algorithm uses linear step-response “blackbox” models surrounding the operating points corresponding to maximum oxygen yield points at different loads. It has been shown that at any operating point of the ASU, the MMPC algorithm, through model-weight calculation based on plant measurements, naturally and continuously selects the dominant model(s) corresponding to the current plant state, while making control-move decisions that approach the maximum oxygen yield point. This dynamically facilitates less energy consumption in form of compressed feed-air compared to a simple ratio control during load-swings. In addition, since a linear optimization problem is solved at each time step, the approach involves much less computational cost compared to a firstprinciple based nonlinear MPC. Introduction

Mahapatra, P.; Zitney, S.; Bequette, B. Wayne

2012-01-01T23:59:59.000Z

227

Ultrasonic Phased Array Assessment of the Interference Fit and Leak Path of the North Anna Unit 2 Control Rod Drive Mechanism Nozzle 63 with Destructive Validation  

SciTech Connect

The objective of this investigation was to evaluate the efficacy of ultrasonic testing (UT) for primary water leak path assessments of reactor pressure vessel (RPV) upper head penetrations. Operating reactors have experienced leakage when stress corrosion cracking of nickel-based alloy penetrations allowed primary water into the annulus of the interference fit between the penetration and the low-alloy steel RPV head. In this investigation, UT leak path data were acquired for an Alloy 600 control rod drive mechanism nozzle penetration, referred to as Nozzle 63, which was removed from the North Anna Unit 2 reactor when the RPV head was replaced in 2002. In-service inspection prior to the head replacement indicated that Nozzle 63 had a probable leakage path through the interference fit region. Nozzle 63 was examined using a phased-array UT probe with a 5.0-MHz, eight-element annular array. Immersion data were acquired from the nozzle inner diameter surface. The UT data were interpreted by comparing to responses measured on a mockup penetration with known features. Following acquisition of the UT data, Nozzle 63 was destructively examined to determine if the features identified in the UT examination, including leakage paths and crystalline boric acid deposits, could be visually confirmed. Additional measurements of boric acid deposit thickness and low-alloy steel wastage were made to assess how these factors affect the UT response. The implications of these findings for interpreting UT leak path data are described.

Crawford, Susan L.; Cinson, Anthony D.; MacFarlan, Paul J.; Hanson, Brady D.; Mathews, Royce

2012-08-01T23:59:59.000Z

228

Externally controlled pressure and temperature microreactor for in situ x-ray diffraction, visual and spectroscopic reaction investigations under supercritical and subcritial conditions  

SciTech Connect

A microreactor has been developed for in situ, spectroscopic investigations of materials and reaction processes with full external pressure and temperature control from ambient conditions to 400 C and 310 bar. The sample chamber is in direct contact with an external manifold, whereby gases, liquids or fluids can be injected and their activities controlled prior to and under investigation conditions. The microreactor employs high strength, single crystal moissanite windows which allow direct probe beam interaction with a sample to investigate in situ reaction processes and other materials properties. The relatively large volume of the cell, along with full optical accessibility and external temperature and pressure control, make this reaction cell well suited for experimental investigations involving any combination of gas, fluid, and solid interactions. The microreactor's capabilities are demonstrated through an in situ x-ray diffraction study of the conversion of a meta-serpentine sample to magnesite under high pressure and temperature. Serpentine is one of the mineral candidates for the implementation of mineral carbonation, an intriguing carbon sequestration candidate technology.

Diefenbacher, J.; McKelvy, M.; Chizemeshya, A.V.; Wolf, G.H. (ASU)

2010-07-13T23:59:59.000Z

229

Improved efficiency and precise temperature control of low-frequency induction-heating pure iron vapor source on ECR ion source  

SciTech Connect

Multiply charged ions to be used prospectively are produced from solid pure material in an electron cyclotron resonance ion source (ECRIS). Recently a pure iron source is also required for the production of caged iron ions in the fullerene in order to control cells in vivo in bio-nano science and technology. We adopt directly heating iron rod by induction heating (IH) because it has non-contact with insulated materials which are impurity gas sources. We choose molybdenum wire for the IH coils because it doesn't need water cooling. To improve power efficiency and temperature control, we propose to the new circuit without previously using the serial and parallel dummy coils (SPD) for matching and safety. We made the circuit consisted of inductively coupled coils which are thin-flat and helix shape, and which insulates the IH power source from the evaporator. This coupling coils circuit, i.e. insulated induction heating coil transformer (IHCT), can be move mechanically. The secondary current can be adjusted precisely and continuously. Heating efficiency by using the IHCT is much higher than those of previous experiments by using the SPD, because leakage flux is decreased and matching is improved simultaneously. We are able to adjust the temperature in heating the vapor source around melting point. And then the vapor pressure can be controlled precisely by using the IHCT. We can control {+-}10K around 1500 Degree-Sign C by this method, and also recognize to controlling iron vapor flux experimentally in the extreme low pressures. Now we come into next stage of developing induction heating vapor source for materials with furthermore high temperature melting points above 2000K with the IHCT, and then apply it in our ECRIS.

Kato, Y.; Takenaka, T.; Yano, K.; Kiriyama, R.; Kurisu, Y.; Nozaki, D.; Muramatsu, M.; Kitagawa, A.; Uchida, T.; Yoshida, Y.; Sato, F.; Iida, T. [Osaka Univ., 2-1 Yamadaoka, Suita, Osaka, 565-0871 (Japan); National Institute of Radiological Science (NIRS), 4-9-1 Anagawa, Inage, Chiba, 263-8555 (Japan); Bio-Nano Electronics Research Centre, Toyo Univ., 2100 Kuzirai, Kawagoe, Saitama, 350-8585 (Japan); Osaka Univ., 2-1 Yamadaoka, Suita, Osaka, 565-0871 (Japan)

2012-11-06T23:59:59.000Z

230

Thermal and Geometric Controls on the Rate of Surface Air Temperature Changes in a Medium-Sized, Midlatitude City  

Science Conference Proceedings (OSTI)

Gradual cooling in the evening forms a wintertime nocturnal urban heat island. This work, with a mesoscale model involving urban canopy physics, is an examination of how four thermal and geometric controls—anthropogenic heat QF, heat capacity C, ...

Tomohiko Tomita; Hiroyuki Kusaka; Ryo Akiyoshi; Yoshiyuki Imasato

2007-02-01T23:59:59.000Z

231

DOE-HDBK-1122-99; Radiological Control Technician Training  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Unit Analysis & Conversion Unit Analysis & Conversion Study Guide 1.02-1 Course Title: Radiological Control Technician Module Title: Unit Analysis & Conversion Module Number: 1.02 Objectives: 1.02.01 Identify the commonly used unit systems of measurement and the base units for mass, length, and time in each system. 1.02.02 Identify the values and abbreviations for SI prefixes. 1.02.03 Given a measurement and the appropriate conversion factor(s) or conversion factor table, convert the measurement to the specified units. 1.02.04 Using the formula provided, convert a given temperature measurement to specified units. INTRODUCTION A working knowledge of the unit analysis and conversion process is necessary for the Radiological Control Technician. It is useful for air and water sample activity

232

Surface Temperature of IGUs  

NLE Websites -- All DOE Office Websites (Extended Search)

117 117 Surface Temperatures of Insulated Glazing Units: Infrared Thermography Laboratory Measurements Brent T. Griffith, Daniel Türler, and Dariush Arasteh Building Technologies Program Environmental Energy Technologies Division Lawrence Berkeley National Laboratory University of California Berkeley, CA 94720 USA Fax: 510-486-6046, email: D_Arasteh@lbl.gov Abstract Data are presented for the distribution of surface temperatures on the warm-side surface of seven different insulated glazing units. Surface temperatures are measured using infrared thermography and an external referencing technique. This technique allows detailed mapping of surface temperatures that is non-intrusive. The glazings were placed between warm and cold environmental chambers that were operated at conditions

233

Metric Units  

Science Conference Proceedings (OSTI)

... A, B, C, D, E, F, G, H, I, J. 1, Steam Point Calculator: Metric Units, Elevation Converter, ... 6, Height of steam point apparatus above ground (m), 0, m, ...

2011-12-22T23:59:59.000Z

234

United States  

Office of Legacy Management (LM)

- I - I United States Department of Energy D lSCk Al M E R "This book was prepared as an account of work sponsored by an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise, does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency

235

Single-Duct Constant Air Volume System Supply Air Temperature Reset: Using Return Air Temperature or Outside Air Temperature?  

E-Print Network (OSTI)

The supply air temperature set point for a singleduct constant air volume air handling unit (AHU) system is often reset based on either return air temperature or outside air temperature in order to reduce simultaneous cooling and heating energy consumption. Both reset strategies make engineering sense as long as the reset schedules are reasonable. Quite often the decision to use one over the other is made with the assumption that they will all achieve some sorts of energy savings. However, the impact of these two strategies on AHU energy consumption could be very different. A comparison of these two commonly used supply air temperature reset strategies for a single-duct constant air volume system is presented in this paper. It is shown that from either the building energy consumption or building comfort point of view, the reset strategy based on outside air temperature is inherently better than that based on return air temperature. Significant amount of heating energy savings can be achieved by switching from return air temperature based reset to outside air temperature based reset. The reset strategy can also benefit variable air volume (VAV) AHUs. An improved supply air temperature set point reset control strategy is proposed by combining and staging the outside air and return air temperature based resets.

Wei, G.; Turner, W. D.; Claridge, D.; Liu, M.

2002-01-01T23:59:59.000Z

236

Window solar heating unit  

SciTech Connect

The unit may be mounted either in a window or between the studs of a building that is to be supplied with solar heat. The bottom of the unit extends farther from the building than the top and is wider than the top of the unit such that the transparent side away from the building has an arcuate form and is gradually flared outwardly in a downward direction to increase the exposure to the sun during the day. A plurality of absorptive tubes within the unit are slanted from the upper portion of the unit downwardly and outwardly to the front arcuate portion of the bottom. Openings between the unit and the building are provided for air flow, and a thermostatically controlled fan is mounted in one of the openings. A baffle is mounted between the absorptive tubes and the mounting side of the solar heating unit, and the surfaces of the baffle and the absorptive tubes are painted a dull black for absorbing heat transmitted from the sun through the transparent, slanting side.

Davis, E.J.

1978-09-12T23:59:59.000Z

237

Temperature decoupling control of double-level air flow field dynamic vacuum system based on neural network and prediction principle  

Science Conference Proceedings (OSTI)

Double-level air flow field dynamic vacuum (DAFDV) system is a strong coupling, large time-delay, and nonlinear multi-input-multi-output system. Decoupling and overcoming the impact of time-delay are two keys to obtain rapid, accurate and independent ... Keywords: ASSAVP, BP, DAFDV, Decoupling control, Double-level air flow field, EBTC, HX, IPSO, MIMO, Neural networks, OIF, PID, Particle swarm optimization, Prediction, RBF, SISO, TITO, WBTC

Li Jinyang; Meng Xiaofeng

2013-04-01T23:59:59.000Z

238

The Effects of Test Temperature, Temper, and Alloyed Copper on the Hydrogen-Controlled Crack Growth Rate of an Al-Zn-Mg-(Cu) Alloy  

DOE Green Energy (OSTI)

The hydrogen embrittlement controlled stage II crack growth rate of AA 7050 (6.09 wt.% Zn, 2.14 wt% Mg, 2.19 wt.% Cu) was investigated as a function of temper and alloyed copper level in a humid air environment at various temperatures. Three tempers representing the underaged, peak aged, and overaged conditions were tested in 90% relative humidity (RH) air at temperatures between 25 and 90 C. At all test temperatures, an increased degree of aging (from underaged to overaged) produced slower stage II crack growth rates. The stage II crack growth rate of each alloy and temper displayed Arrhenius-type temperature dependence with activation energies between 58 and 99 kJ/mol. For both the normal copper and low copper alloys, the fracture path was predominantly intergranular at all test temperatures (25-90 C) in each temper investigated. Comparison of the stage II crack growth rates for normal (2.19 wt.%) and low (0.06 wt.%) copper alloys in the peak aged and overaged tempers showed the beneficial effect of copper additions on stage II crack growth rate in humid air. In the 2.19 wt.% copper alloy, the significant decrease ({approx} 10 times at 25 C) in stage II crack growth rate upon overaging is attributed to an increase in the apparent activation energy for crack growth. IN the 0.06 wt.% copper alloy, overaging did not increase the activation energy for crack growth but did lower the pre-exponential factor, {nu}{sub 0}, resulting in a modest ({approx} 2.5 times at 25 C) decrease in crack growth rate. These results indicate that alloyed copper and thermal aging affect the kinetic factors that govern stage II crack growth rate. Overaged, copper bearing alloys are not intrinsically immune to hydrogen environment assisted cracking but are more resistant due to an increased apparent activation energy for stage II crack growth.

G.A. Young, Jr.; J.R. Scully

2000-09-17T23:59:59.000Z

239

Two-stage Ignition as an Indicator of Low Temperature Combustion in a Late Injection Pre-mixed Compression Ignition Control Strategy  

E-Print Network (OSTI)

Internal combustion engines have dealt with increasingly restricted emissions requirements. After-treatment devices are successful in bringing emissions into compliance, but in-cylinder combustion control can reduce their burden by reducing engine out emissions. For example, oxides of nitrogen (NOx) are diesel combustion exhaust species that are notoriously difficult to remove by after-treatment. In-cylinder conditions can be controlled for low levels of NOx, but this produces high levels of soot potentially leading to increased particulate matter (PM). The simultaneous reduction of NOx and PM can be realized through a combustion process known as low temperature combustion (LTC). In this study, the typical definition of LTC as the defeat of the inverse relationship between soot and NOx is not applicable as a return to the soot-NOx tradeoff is observed with increasing exhaust gas recirculation (EGR). It is postulated that this effect is the result of an increase in the hot ignition equivalence ratio, moving the combustion event into a slightly higher soot formation region. This is important because a simple emissions based definition of LTC is no longer helpful. In this study, the manifestation of LTC in the calculated heat release profile is investigated. The conditions classified as LTC undergo a two-stage ignition process. Two-stage ignition is characterized by an initial cool-flame reaction followed by typical hot ignition. In traditional combustion conditions, the ignition is fast enough that a cool-flame is not observed. By controlling initial conditions (pressure, temperature, and composition), the creation and duration of the cool-flame event is predictable. Further, the effect that injection timing and the exhaust gas recirculation level have on the controlling factors of the cool-flame reaction is well correlated to the duration of the cool-flame event. These two results allow the postulation that the presence of a sufficiently long cool-flame reaction indicates a combustion event that can be classified as low temperature combustion. A potential method for identifying low temperature combustion events using only the rate of heat release profile is theorized. This study employed high levels of EGR and late injection timing to realize the LTC mode of ordinary petroleum diesel fuel. Under these conditions, and based on a 90 percent reduction in nitric oxide and no increase in smoke output relative to the chosen baseline condition, a two part criteria is developed that identifies the LTC classified conditions. The criteria are as follow: the combustion event of conventional petroleum diesel fuel must show a two-stage ignition process; the first stage (cool-flame reaction) must consume at least 2 percent of the normalized fuel energy before the hot ignition commences.

Bittle, Joshua

2010-12-01T23:59:59.000Z

240

United States  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

BP Energy Company BP Energy Company OE Docket No. EA- 3 14 Order Authorizing Electricity Exports to Mexico Order No. EA-3 14 February 22,2007 BP Energy Company Order No. EA-314 I. BACKGROUND Exports of electricity from the United States to a foreign country are regulated by the Department of Energy (DOE) pursuant to sections 301(b) and 402(Q of the Department of Energy Organization Act (42 U.S.C. 7 15 l(b), 7172(f)) and require authorization under section 202(e) of the Federal Power Act (FPA) (16 U.S.C.S24a(e)) . On May 22,2006, BP Energy Company (BP Energy) applied to DOE for an authorization to transmit electric energy from the United States to Mexico as a power marketer. BP Energy proposes to purchase surplus electric energy from electric utilities and other suppliers within the United States and to export that energy to ~Mexico. The cnergy

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


241

United States  

Office of Legacy Management (LM)

Office of Research and EPA 600/R-941209 Environmental Protection Development January 1993 Agency Washington, DC 20460 Offsite Environmental 57,,7 Monitoring Report Radiation Monitoring Around United States Nuclear Test Areas, Calendar Year 1992 UNITED STATES ENVIRONMENTAL PROTECTION AGENCY OFFICE OF RESEARCH AND DEVELOPMENT ENVIRONMENTAL MONITORING SYSTEMS LABORATORY-LAS VEGAS P.O. BOX 93478 LAS VEGAS. NEVADA 891 93-3478 702/798-2100 Dear Reader: Since 1954, the U.S. Environmental Protection Agency (EPA) and its predecessor the U.S, Public Health Service (PHs) has conducted radiological monitoring in the offsite areas around United States nuclear test areas. The primary objective of this monitoring has been the protection of the health and safety of

242

Battery monitoring and charger control system  

SciTech Connect

A battery cell controlled charging system, consisting of a display unit, battery cell probes, a battery charger and circuitry for controlling the charger, monitors the specific gravity, electrolyte level and temperature control of each cell in a multi-cell lead-acid battery and uses the information to automatically charge the battery when a cell or cells become out of specification while restricting overcharging which is damaging to cells.

Barry, G.H.; Dahl, E.A.

1983-06-14T23:59:59.000Z

243

Adaptive vibration control using synchronous demodulation with ...  

Adaptive vibration control using synchronous demodulation with machine tool controller motor commutation United States Patent

244

A cost-effectiveness analysis of alternative ozone control strategies : flexible nitrogen oxide (NOx) abatement from power plants in the eastern United States  

E-Print Network (OSTI)

Ozone formation is a complex, non-linear process that depends on the atmospheric concentrations of its precursors, nitrogen oxide (NOx) and Volatile Organic Compounds (VOC), as well as on temperature and the available ...

Sun, Lin, S.M. Massachusetts Institute of Technology

2009-01-01T23:59:59.000Z

245

United States  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

E-T Global Energy, LLC E-T Global Energy, LLC OE Docket No. EA-381 Order Authorizing Electricity Exports to Mexico Order No. EA-381 June 10, 2011 I. BACKGROUND E-T Global Energy, LLC Order No. EA-381 Exports of electricity from the United States to a foreign country are regulated by the Department of Energy (DOE) pursuant to sections 301(b) and 402(f) of the Department ofEnergy Organization Act (42 U.S.C. 7151(b), 7172(f)) and require authorization under section 202(e) ofthe Federal Power Act (FPA) (16 U.S.C.824a(e)) 1 * On May 10,2011, DOE received an application from E-T Global Energy, LLC (E-T Global) for authority to transmit electric energy from the United States to Mexico for five years as a power marketer using existing international transmission facilities. E-

246

United States  

Office of Legacy Management (LM)

WASHINGTON, TUESDAY, JUNE 28, 1983 @nngmeional Ruord United States of America .__ -- . . ,- PROCEEDINGS AND DEBATES OF THE 9@ CONGRESS, FIRST SESSION United States Government Printing Office SUPERINTENDENT OF DOCUMENTS Washmgton, D C 20402 OFFICIAL BUSINESS Penalty Ior pwate use. $xX Congresstonal Record (USPS 087-390) Postage and Fees Pad U S Government Prlnhng 0ffv.X 375 SECOND CLASS NEWSPAPER H.4578 ' C.QNGRESSIONAL RECORD - HOUSE June 28, 1983 H.J. Res. 273: Mr. BOUND. Mr. W~.XMAN. Mr. OBERSTAR, Mr. BEDELL. Mr. BONER of Tennessee, Mr. OWENS. Mr. DAUB, Mr. CONTE. Mr. RAHALL; Mr. GRAY, Mr. VANDER JACT. Mr. TRAKLER, and Mr. Vxrrro. H. Con. Res. 107: Mr. KASICH. Mr. AUCOIN. Mr. CARPER, and Mr. SIZHFIJER. H. Con. Res. 118: Mr. FISH. Mr. LANTOS.

247

United States  

Office of Legacy Management (LM)

ongrees;ional Record ongrees;ional Record United States of America __._ -.. I. :- PROCEEDINGS AND DEBATES OF THE 9tth CONGRESS, FIRST SESSION United States Government Printing Office SUPERINTENDENT OF DOCUMENTS Washmcqton. Cl C 20402 OFFICIAL BUSINESS Penalty Ior pwate use. $300 Congressmal Record (USPS 087-390) Postage and Fees Pad U S Governme3n:jPnntmg OfIce SECOND CLASS NEWSPAPER H.4578 ' June 28, 1983 -: I H.J. Res. 273: Mr. BOLAND, Mr. WA-. Mr. OBERSTAFC, M' r. BEDELL, Mr. BONER of Tennessee, Mr. OWENS. Mr. DAUB. Mr. CONTE. Mr. RAHALL,. Mr. GRAY, Mr. VANDER JAGT. Mr. TRAKLER. and Mr. VENTO. H. Con. Res. iO7: Mr. KASICH. Mr. ALCOIN. Mr. CARPER. and Mr. SCHEUER. H. Con. Res. 118: Mr. FISH, Mr. LANTOS. Mr. KILDEE. Mr. SOLARZ Mr. Bmrr, Mr. BELWLL, Mr. RANG~L, Mr. DYMALLY. Mr.

248

Soil moisture surpasses elevated CO2 and temperature as a control on soil carbon dynamics in a multi-factor climate change experiment  

SciTech Connect

Some single-factor experiments suggest that elevated CO2 concentrations can increase soil carbon, but few experiments have examined the effects of interacting environmental factors on soil carbon dynamics. We undertook studies of soil carbon and nitrogen in a multi-factor (CO2 x temperature x soil moisture) climate change experiment on a constructed old-field ecosystem. After four growing seasons, elevated CO2 had no measurable effect on carbon and nitrogen concentrations in whole soil, particulate organic matter (POM), and mineral-associated organic matter (MOM). Analysis of stable carbon isotopes, under elevated CO2, indicated between 14 and 19% new soil carbon under two different watering treatments with as much as 48% new carbon in POM. Despite significant belowground inputs of new organic matter, soil carbon concentrations and stocks in POM declined over four years under soil moisture conditions that corresponded to prevailing precipitation inputs (1,300 mm yr-1). Changes over time in soil carbon and nitrogen under a drought treatment (approximately 20% lower soil water content) were not statistically significant. Reduced soil moisture lowered soil CO2 efflux and slowed soil carbon cycling in the POM pool. In this experiment, soil moisture (produced by different watering treatments) was more important than elevated CO2 and temperature as a control on soil carbon dynamics.

Garten Jr, Charles T [ORNL; Classen, Aimee T [ORNL; Norby, Richard J [ORNL

2009-01-01T23:59:59.000Z

249

United States  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

5 5 United States Department of Energy Southeastern Power Administration Wholesale Power Rate Schedule CC-1-I Availability: This rate schedule shall be available to public bodies and cooperatives served through the facilities of Carolina Power & Light Company, Western Division (hereinafter called the Customers). Applicability: This rate schedule shall be applicable to electric capacity and energy available from the Dale Hollow, Center Hill, Wolf Creek, Cheatham, Old Hickory, Barkley, J. Percy Priest, and Cordell Hull Projects (all of such projects being hereinafter called collectively the "Cumberland Projects") and sold in wholesale quantities. Character of Service: The electric capacity and energy supplied hereunder will be three-phase alternating

250

IEP - Advanced NOx Emissions Control: Control Technology  

NLE Websites -- All DOE Office Websites (Extended Search)

forms at high temperatures during fossil fuel combustion (see How NOx is Formed ). The primary sources of NOx emissions in the United States are motor vehicles, power plants,...

251

United States  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Tenaslta Power Services Co. Tenaslta Power Services Co. OE Docket No. EA-243-A Order Authorizing Electricity Exports to Canada Order No. EA-243-A March 1,2007 Tenaska Power Services Co. Order No. EA-243-A I. BACKGROUND Exports of elcctricity from the United States to a foreign country are regulated by the Department of Energy (DOE) pursuant to sections 30 I(b) and 402(f) of the Departrncnt of' Energy Organizatio~l Act (42 U, S.C. 7 15 1 (b), 7 1 72Cf)) and rcquirc authorization under section 202(e) of the Federal Power Act (FPA) ( Z 6 U. s.c.824a(e)j1. On August 16,2001, DOE issued Order No. EA-243 authorizing Tenaska Power Scrvices Co. (Tenaska) to transmit electric cncrgy from the United States to Canada as a power marketer. That authority expired on August 16,2003. On August 14,2006, Teilaska applied to renew the electricity export authority

252

United States  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

TexMex Energy, LLC TexMex Energy, LLC OE Docket No. EA-294-A Order Authorizing Electricity Exports to Mexico Order No. EA-294-A February 22, 2007 TexMex Energy, LLC Order No. EA-294-A I. BACKGROUND Exports of electricity from the United States to a foreign count~y are regulated by the Department of Energy (DOE) pursuant to sections 301(b) and 402(f) of the Department of Energy Organization Act (42 U.S.C. 7 15 1 (b), 71 72(f)) and require authorization under section 202(e) of the Federal Power Act (FPA) (16 U.S.C.824a(e)) . On August 25,2004, DOE issued Order No. EA-294 authorizing TexMex Energy LLC (TexMex) to transmit electric energy fiom the United States to Mexico as a power marketer. That authority expired on August 25, 2006. On September 8, 2006, TexMex applied to renew the electricity export authority

253

United States  

Gasoline and Diesel Fuel Update (EIA)

United States United States Coal ................................................ 4,367 4,077 4,747 4,181 4,473 4,125 4,983 4,330 4,414 4,003 4,796 4,178 4,344 4,479 4,348 Natural Gas .................................... 2,802 2,843 3,694 2,863 2,713 2,880 3,636 2,707 2,792 2,972 3,815 2,849 3,052 2,986 3,109 Petroleum (a) .................................. 74 73 81 67 73 70 75 66 75 70 76 66 74 71 71 Other Gases ................................... 32 33 36 32 32 34 37 33 33 35 39 34 33 34 35 Nuclear ........................................... 2,176 2,044 2,257 2,170 2,106 2,037 2,167 2,010 2,144 2,074 2,206 2,055 2,162 2,080 2,120 Renewable Energy Sources: Conventional Hydropower ........... 736 886 716 633 765 887 708 646 767 919 729 659 742 751 768 Wind ............................................ 491 520 353 449 477 521 379 475

254

Environmental Controls on the Surface Energy Budget over a Large Southern Inland Water in the United States: An Analysis of One-Year Eddy Covariance Flux Data  

Science Conference Proceedings (OSTI)

The authors analyzed the surface energy fluxes that were measured by an eddy covariance system over the Ross Barnett Reservoir in Mississippi for a 1-yr period in 2008. On a monthly basis over the course of the year, positive vertical temperature ...

Heping Liu; Qianyu Zhang; Gordon Dowler

2012-12-01T23:59:59.000Z

255

United States  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Bangor Hydro-Electric Company Bangor Hydro-Electric Company OE Docket No. PP-89-1 Amendment to Presidential Permit Order No. PP-89-1 December 30,2005 PRESIDENTIAL PERMIT AMENDMENT Bangor Hydro-Electric Company Order No. PP-89-1 I. BACKGROUND The Department of Energy (DOE) has responsibility for implementing Executive Order (E.O.) 10485, as amended by E.O. 12038, which requires the issuance of a Presidential permit by DOE before electric trans~nission facilities may be constructed, operated, maintained, or connected at the borders of the United States. DOE may issue such a permit if it determines that the permit is in the public interest and after obtaining favorable recommendations from the U.S. Departments of State and Defense. On December 16, 1988, Bangor Hydro-Electric Company (BHE) applied to DOE

256

United States  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

7 7 United States Department of Energy Southeastern Power Administration Wholesale Power Rate Schedule CTV-1-H Availability: This rate schedule shall be available to the Tennessee Valley Authority (hereinafter called TVA). Applicability: This rate schedule shall be applicable to electric capacity and energy generated at the Dale Hollow, Center Hill, Wolf Creek, Old Hickory, Cheatham, Barkley, J. Percy Priest, and Cordell Hull Projects (all of such projects being hereafter called collectively the "Cumberland Projects") and the Laurel Project sold under agreement between the Department of Energy and TVA. Character of Service: The electric capacity and energy supplied hereunder will be three-phase alternating current at a frequency of approximately 60 hertz at the outgoing terminals of the Cumberland

257

United States  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

United States Department of Energy Southeastern Power Administration Wholesale Power Rate Schedule CTVI-1-A Availability: This rate schedule shall be available to customers (hereinafter called the Customer) who are or were formerly in the Tennessee Valley Authority (hereinafter called TVA) service area. Applicability: This rate schedule shall be applicable to electric capacity and energy generated at the Dale Hollow, Center Hill, Wolf Creek, Old Hickory, Cheatham, Barkley, J. Percy Priest, and Cordell Hull Projects (all of such projects being hereafter called collectively the "Cumberland Projects") and the Laurel Project sold under agreement between the Department of Energy and the Customer. Character of Service: The electric capacity and energy supplied hereunder will be three-phase alternating

258

UNITED STATES  

Office of Legacy Management (LM)

f).~<~~ \--\c :y-,ai F p"- KG f).~<~~ \--\c :y-,ai F p"- KG WASHINOTDN 28.0. C. ' -lr ' \ ' ' --- ".I ?--" ' z I. .~;-4.' J frr*o& 2 ii, - - -4 70-147 LRL:JCD JAN !! 8 1958 Oregon Metallurgical Corporation P. 0. Box 484 Albany, Oregon Attention: Mr. Stephen M. Shelton General Manager Gentlemen: Enclosed is Special Nuclear Material License No. SNM-144, as amended. Very 33uly yours, r:; I,;, ll)~gQ""d".- Lyall Johnson Chief, Licensing Branch Division of Licensing & Regulation Enclosure: SNM-144, as amended Distribution: bRO0 Attn: Dr. H.M.Roth DFMusser NMM MMMann INS JCRyan FIN (2) HSteele LRL SRGustavson LRL Document room Formal file Suppl. file Br & Div rf's ' .b liwwArry s/VW- ' q+ ' yj/ 2; 2-' , COP' 1 J JAM01958 -- UNITED STATES ATOMIC ENERGY COMMISSION

259

United States  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

United States Department of Energy Southeastern Power Administration Wholesale Power Rate Schedule JW-2-F Availability: This rate schedule shall be available to the Florida Power Corporation (or Progress Energy Florida, hereinafter called the Company). Applicability: This rate schedule shall be applicable to electric energy generated at the Jim Woodruff Project (hereinafter called the Project) and sold to the Company in wholesale quantities. Points of Delivery: Power sold to the Company by the Government will be delivered at the connection of the Company's transmission system with the Project bus. Character of Service: Electric power delivered to the Company will be three-phase alternating current at a nominal frequency of 60 cycles per second.

260

Passive environmental temperature control system  

DOE Patents (OSTI)

Passive environmental heating and cooling systems are described, which utilize heat pipes to transmit heat to or from a thermal reservoir. In a solar heating system, a heat pipe is utilized to carry heat from a solar heat absorber plate that receives sunlight, through a thermal insulation barrier, to a heat storage wall, with the outer end of the pipe which is in contact with the solar absorber being lower than the inner end. The inclining of the heat pipe assures that the portion of working fluid, such as Freon, which is in a liquid phase will fall by gravity to the outer end of the pipe, thereby assuring diode action that prevents the reverse transfer of heat from the reservoir to the outside on cool nights. In a cooling system, the outer end of the pipe which connects to a heat dissipator, is higher than the inner end that is coupled to a cold reservoir, to allow heat transfer only out of the reservoir to the heat dissipator, and not in the reverse direction.

Corliss, John M. (Columbus, OH); Stickford, George H. (Columbus, OH)

1981-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


261

Dynamic Modeling in Solid-Oxide Fuel Cells Controller Design  

SciTech Connect

In this paper, a dynamic model of the solid-oxide fuel cell (SOFC) power unit is developed for the purpose of designing a controller to regulate fuel flow rate, fuel temperature, air flow rate, and air temperature to maintain the SOFC stack temperature, fuel utilization rate, and voltage within operation limits. A lumped model is used to consider the thermal dynamics and the electro-chemial dynamics inside an SOFC power unit. The fluid dynamics at the fuel and air inlets are considered by using the in-flow ramp-rates.

Lu, Ning; Li, Qinghe; Sun, Xin; Khaleel, Mohammad A.

2007-06-28T23:59:59.000Z

262

DOE-HDBK-1122-99; Radiological Control Technician Training  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Unit Analysis & Conversion Unit Analysis & Conversion Instructor's Guide 1.02-1 Course Title: Radiological Control Technician Module Title: Unit Analysis & Conversion Module Number: 1.02 Objectives: 1.02.01 Identify the commonly used unit systems of measurement and the base units for mass, length, and time in each system. 1.02.02 Identify the values and abbreviations for SI prefixes. 1.02.03 Given a measurement and the appropriate conversion factor(s) or conversion factor table, convert the measurement to the specified units. 1.02.04 Using the formula provided, convert a given temperature measurement to specified units. References: 1. "Health Physics and Radiological Health Handbook"; Scinta, Inc; 1989. 2. DOE-HDBK-1010-92 (June 1992) "Classical Physics" DOE Fundamental Handbook; US

263

Pacific North American Teleconnection Controls on Precipitation Isotopes (?18O) across the Contiguous United States and Adjacent Regions: A GCM-based Analysis  

Science Conference Proceedings (OSTI)

The Pacific North American (PNA) teleconnection pattern has a strong influence on winter North American climate, but much less is known about how the PNA pattern controls precipitation isotopes (e.g., ?18O) across the USA. In this study, we use an ...

Zhongfang Liu; Kei Yoshmura; Gabriel J. Bowen; Jeffrey M. Welker

264

United States Government Memorandum  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Department of Energy United States Government Memorandum DATE: January 26, 2007 Audit Report Number: OAS-L-07-05 REPLY TO ATTN OF: IG-34 (A06GT035) SUBJECT: Report on "The Department of Energy's Implementation of Revised OMB Circular No. A-123" TO: Acting Chief Financial Officer, CF-1 INTRODUCTION AND OBJECTIVE The Office of Management arid Budget's (OMB) revised Circular No. A-123 (Circular) requires Federal agencies to assess the adequacy of their internal controls. Beginning in Fiscal Year (FY) 2006, the Circular requires agencies to strengthen their assessment, documentation and testing of internal controls over financial reporting and prepare an annual assurance statement on the operating effectiveness of those controls. In August 2005, the Department of Energy's

265

Superfund record of decision (EPA Region 1): Fort Devens Sudbury Training Annex, source control operable unit, Middlesex County, MA, September 29, 1995  

Science Conference Proceedings (OSTI)

This Record of Decision (ROD) document presents the selected source control (SC) remedial action at areas of contamination (AOCs) A7 and A9 at the Fort Devens Sudbury Training Annex (Annex), Middlesex County, Massachusetts. The major components of the selected remedy for AOCs A7 and A9 include: Excavation and off-site treatment and disposal of laboratory waste at AOC A7; Excavation of contaminated soil from AOC A9 and consolidation at AOC A7; Consolidation of contaminated soil and solid waste at AOC A7 to within the limits of the landfill cap; Construction of a Resource Conservation and Recovery Act (RCRA) Subtitle C landfill cap at AOC A7; Environmental monitoring and operation and maintenance (O&M) at AOC A7; Institutional controls at AOC A7 to limit future site use and to restrict site access; and Five-year reviews at AOC A7.

NONE

1996-03-01T23:59:59.000Z

266

High Temperature Interfacial Superconductivity - Energy Innovation ...  

Cuprate superconductors exhibit relatively high transition temperatures, but their unit cells are complex and large. Localizing a superconducting layer to a small ...

267

Liquid phase low temperature method for production of methanol ...  

Liquid phase low temperature method for production of methanol from synthesis gas and catalyst formulations therefor United States Patent

268

Definition: British thermal unit | Open Energy Information  

Open Energy Info (EERE)

thermal unit thermal unit Jump to: navigation, search Dictionary.png British thermal unit The amount of heat required to raise the temperature of one pound of water one degree Fahrenheit; often used as a unit of measure for the energy content of fuels.[1][2] View on Wikipedia Wikipedia Definition The British thermal unit (BTU or Btu) is a traditional unit of energy equal to about 1055 joules. It is the amount of energy needed to cool or heat one pound of water by one degree Fahrenheit. In scientific contexts the BTU has largely been replaced by the SI unit of energy, the joule. The unit is most often used as a measure of power (as BTU/h) in the power, steam generation, heating, and air conditioning industries, and also as a measure of agricultural energy production (BTU/kg). It is still used

269

Specification of United States Summer Season Precipitation  

Science Conference Proceedings (OSTI)

The specification of summer season precipitation in the contiguous United States from summer season fields of 700 mb height, sea level pressure (SLP) and Pacific sea surface temperature (SST) was carried out using stepwise multiple linear ...

John R. Lanzante; Robert P. Harnack

1982-12-01T23:59:59.000Z

270

Rooftop Membrane Temperature Reductions with Green Roof Technology in South-Central Texas  

E-Print Network (OSTI)

Early green roof cooling and energy reduction research in North America took place in Canada and the northern latitudes of the United States, where green roofs reduced rooftop temperatures by 70% to 90%. Less is known about green roof technology in the southern Untied States; where energy demand for cooling buildings is high, and the urban heat island effect is more pronounced. This paper reports early findings for rooftop membrane temperature reductions from 11.6-cm-deep modular green roof trays, typical of large-scaled, low-maintenance applications. Measurements observed during May, 2010 reveal that temperatures below the modular planted green roof units were 82% to 91.6% cooler compared to the surface temperatures of the control roof membrane. These findings on low-input modular green roof trays reinforce other research findings that indicate green roof technology can dramatically reduce and modify temperatures on roof deck surfaces during peak energy demand periods in hot sunny climates.

Dvorak, B.

2010-08-01T23:59:59.000Z

271

United States Government Memorandum  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Department of Energy Department of Energy United States Government Memorandum DATE: March 21, 2008 Audit Report Number: OAS-L-08-08 REPLY TO ATTN OF: IG-321 (A07LV042) SUBJECT: Audit Report on "Accountability of Sensitive and High Risk Property at the Nevada Site Office" TO: Acting Manager, Nevada Site Office INTRODUCTION AND OBJECTIVE and control over sensitive and high risk property because of the vulnerability to loss, theft or misuse and its potential impact on national security interests or proliferation concerns. Items such as portable and desktop computers, ammunition. and firearms are examples of sensitive property. In addition, federal regulations require that Departmental organizations and designated contractors account for and control govemroent-owned high risk property, such as body armor and gas masks,

272

Seasonal Cycle Shifts in Hydroclimatology over the Western United States  

Science Conference Proceedings (OSTI)

Analyses of streamflow, snow mass temperature, and precipitation in snowmelt-dominated river basins in the western United States indicate an advance in the timing of peak spring season flows over the past 50 years. Warm temperature spells in ...

Satish Kumar Regonda; Balaji Rajagopalan; Martyn Clark; John Pitlick

2005-01-01T23:59:59.000Z

273

Energy Management in Olefins Units  

E-Print Network (OSTI)

The previous generations of olefin units were typically importers of utilities such as high pressure steam and electricity. But, in the new generation of units, diligent energy conservation efforts have reduced the high pressure steam demand to the point where waste heat from pyrolysis generates more than enough steam to power the olefins unit recovery section. Furthermore, incorporating gas turbine driven electrical generators or process compressors adds to the utility export potential of the unit. It is necessary, therefore, to consider utility export as a valuable byproduct of olefins production and incorporate it within the utility network of the petrochemical complex. As with any byproduct of a process, it is necessary to be able to control its production and distribution.

Wells, T. A.

1982-01-01T23:59:59.000Z

274

Feasibility Study of Using High-Temperature Raman Spectroscopy for On-Line Monitoring and Product Control of the Glass Vitrification Process  

SciTech Connect

A pulse-gating Raman spectroscopy setup was developed in this project. The setup was capable of performing in-situ high-temperature Raman measurements for glasses at temperatures as high as 1412 C. In the literature, high-temperature Raman measurements have only been performed on thin films of glass to minimize black-body radiation effects. The pulse-gating Raman setup allows making high-temperature measurements for bulk melts while effectively minimizing black-body radiation effects. A good correlation was found between certain Raman characteristic parameters and glass melt temperature for sodium silicate glasses measured in this project. Comparisons were made between the high-temperature Raman data from this study and literature data. The results suggest that an optimization of the pulse-gating Raman setup is necessary to further improve data quality (i.e., to obtain data with a higher signal-to-noise ratio). An W confocal Raman microspectrometer with continuous wave laser excitation using a 325 nm excitation line was evaluated selectively using a transparent silicate glass ad a deep-colored high-level waste glass in a bulk quantity. The data were successfully collected at temperatures as high as approximately 1500 C. The results demonstrated that the UV excitation line can be used for high-temperature Raman measurements of molten glasses without black-body radiation interference from the melt for both transparent and deep-color glasses. Further studies are needed to select the best laser system that can be used to develop high-temperature Raman glass databases.

Windisch, C.F. Jr.; Piepel, G.F.; Li, H.; Elliott, M.L.; Su, Y.

1999-01-04T23:59:59.000Z

275

Nomination Form DEPARTMENT / UNIT  

E-Print Network (OSTI)

Nomination Form DEPARTMENT / UNIT: CAMPUS ADDRESS: CLASSIFICATION / TITLE: DEPARTMENT EMAIL ADDRESS: DEPARTMENT TELEPHONE: 2011 FRANKLIN STAFF SERVICE AWARDS START DATE IN DEPARTMENT / UNIT: ACTUAL NUMBER MEMBER DEADLINE: FRIDAY MARCH 4, 2011 ADDITIONAL COMMENTS: Signature of Head / Director of Nominee's Unit

Arnold, Jonathan

276

Unit Outline Training Guide  

E-Print Network (OSTI)

Unit Outline Builder Training Guide Document Status: Final Revision Number: 6.0 Revision Date: 14 Approved #12;Online Unit Outline Builder Training Guide Curtin University of Technology Page 2 TABLE................................................................................................................. 4 4. Log in and Select a Unit Outline

277

Nomination Form DEPARTMENT / UNIT  

E-Print Network (OSTI)

Nomination Form DEPARTMENT / UNIT: CAMPUS ADDRESS: CLASSIFICATION / TITLE: DEPARTMENT EMAIL ADDRESS: DEPARTMENT TELEPHONE: 2013 FRANKLIN STAFF SERVICE AWARDS START DATE IN DEPARTMENT / UNIT: ACTUAL NUMBER MEMBER DEADLINE: MARCH 5, 2013 ADDITIONAL COMMENTS: Signature of Head / Director of Nominee's Unit

Arnold, Jonathan

278

Nomination Form DEPARTMENT / UNIT  

E-Print Network (OSTI)

Nomination Form DEPARTMENT / UNIT: CAMPUS ADDRESS: CLASSIFICATION / TITLE: DEPARTMENT EMAIL ADDRESS: DEPARTMENT TELEPHONE: 2012 FRANKLIN STAFF SERVICE AWARDS START DATE IN DEPARTMENT / UNIT: ACTUAL NUMBER MEMBER DEADLINE: FRIDAY MARCH 2, 2012 ADDITIONAL COMMENTS: Signature of Head / Director of Nominee's Unit

Arnold, Jonathan

279

Nomination Form DEPARTMENT / UNIT  

E-Print Network (OSTI)

Nomination Form DEPARTMENT / UNIT: CAMPUS ADDRESS: CLASSIFICATION / TITLE: DEPARTMENT EMAIL ADDRESS: DEPARTMENT TELEPHONE: 2014 FRANKLIN STAFF SERVICE AWARDS START DATE IN DEPARTMENT / UNIT: ACTUAL NUMBER MEMBER DEADLINE: MARCH 7, 2014 ADDITIONAL COMMENTS: Signature of Head / Director of Nominee's Unit

Arnold, Jonathan

280

Efficiency United (Gas) - Commercial Efficiency Program | Department of  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Efficiency United (Gas) - Commercial Efficiency Program Efficiency United (Gas) - Commercial Efficiency Program Efficiency United (Gas) - Commercial Efficiency Program < Back Eligibility Commercial Industrial Savings Category Heating & Cooling Commercial Heating & Cooling Heating Home Weatherization Commercial Weatherization Appliances & Electronics Other Construction Manufacturing Water Heating Maximum Rebate See Page Four of Utility Application: $100-$50,000/customer/year depending on utility and remaining funding Custom:40% of project cost Program Info State Michigan Program Type Utility Rebate Program Rebate Amount Trap Repair or Replacement: $50/unit Boilers: $1-$1.50/MBH Furnace Replacement: $1.50/MBH or $150/unit Boiler Modulation Burner Control Retrofit: $1000/unit Boiler Water Reset Control: $300/unit

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


281

Radiance Temperature  

Science Conference Proceedings (OSTI)

... Temperature using Detectors Calibrated for Absolute Spectral Power Response, HW ... A Third Generation Water Bath Based Blackbody Source, JB ...

2013-06-27T23:59:59.000Z

282

Apparatus and method for controlling a heat pump water heater  

Science Conference Proceedings (OSTI)

A method and apparatus for controlling the operation of an add-on heat pump water heater unit is disclosed. A combination of a thermally conductive tube having a flattened portion and a thermostat mounted thereto is utilized to sense the temperature level of water in a tank to which the heater unit is connected. The tube and thermostat are additionally insulated from the ambient. A circulating pump is provided and connected to the water thermostat such that the pump is energized only when it is necessary to operate the heat energy adding unit.

Whitwell, R. J.; Schafer, J. P.

1984-01-08T23:59:59.000Z

283

NETL: Advanced NOx Emissions Control: Control Technology - SCNR Field  

NLE Websites -- All DOE Office Websites (Extended Search)

SNCR Field Demonstration SNCR Field Demonstration American Electric Power (AEP), in conjunction with the U.S. Department of Energy, FuelTech, the Ohio Coal Development Office, and fourteen EPRI member utilities, performed a full-scale demonstration of a urea-based Selective Non-Catalytic Reduction (SNCR) system at Cardinal Unit 1. Cardinal Unit 1 is a 600MWe opposed-wall dry bottom pulverized coal-fired boiler that began service in 1967. This unit burns eastern bituminous high-sulfur coal, (3.72%S). This unit was retrofitted with low NOx burners (LNB's) during its scheduled fall 1998 outage and the SNCR system was installed concurrently. SNCR is a post-combustion NOx control process developed to reduce NOx emissions from fossil-fuel combustion systems. SNCR processes involve the injection of a chemical containing nitrogen into the combustion products, where the temperature is in the range of 1600°F - 2200°F (870°C - 1205°C). In this temperature range, the chemical reacts selectively with NOx in the presence of oxygen, forming primarily nitrogen and water. Although a number of chemicals have been investigated and implemented for SNCR NOx reduction, urea and ammonia have been most widely used for full-scale applications.

284

Acoustic Imaging Evaluation of Juvenile Salmonid Behavior in the Immediate Forebay of the Water Temperature Control Tower at Cougar Dam, 2010  

Science Conference Proceedings (OSTI)

This report presents the results of an evaluation of juvenile Chinook salmon (Oncorhynchus tshawytscha) behavior at Cougar Dam on the south fork of the McKenzie River in Oregon in 2010. The study was conducted by the Pacific Northwest National Laboratory for the U.S. Army Corps of Engineers (USACE). The overall goal of the study was to characterize juvenile salmonid behavior and movement patterns in the immediate forebay of the Water Temperature Control (WTC) tower of the dam for USACE and fisheries resource managers use in making decisions about bioengineering designs for long-term structures and/or operations to facilitate safe downstream passage for juvenile salmonids. We collected acoustic imaging (Dual-Frequency Identification Sonar; DIDSON) data from March 1, 2010, through January 31, 2011. Juvenile salmonids (hereafter, called 'fish') were present in the immediate forebay of the WTC tower throughout the study. Fish abundance index was low in early spring (fish per sample-day), increased in late April, and peaked on May 19 (6,039 fish). A second peak was observed on June 6 (2904 fish). Fish abundance index decreased in early June and remained low in the summer months (fish per sample-day). During the fall and winter, fish numbers varied with a peak on November 10 (1881 fish) and a minimum on December 7 (12 fish). A second, smaller, peak occurred on December 22 (607 fish). A univariate statistical analysis indicated fish abundance index (log10-transformed) was significantly (Pfish abundance (log-transformed index values) using two independent variables of mean forebay elevation and the log10 of the forebay elevation range. From the approximate fish length measurements made using the DIDSON imaging software, the average fish length during early spring 2010 was 214 {+-} 86 mm (standard deviation). From May through early November, the average fish length remained relatively consistent (132 {+-} 54 mm), after which average lengths increased to 295 {+-} 148 mm for mid-November though early December. From mid-December through January the average fish length decreased to 151 {+-} 76 mm. Milling in front of the WTC tower was the most common fish behavior observed throughout the study period. Traversing along the front of the tower, east-to-west and west-to-east, was the next common behavior. The percentage of fish events showing movement from the forebay to the tower or from the tower to the forebay was generally low throughout the spring, summer, and early fall (0 to 30% for both directions combined, March through early November). From mid-November 2010 through the end of the study (January 31, 2011), the combined percentages of fish moving into and out of the tower were higher (25 to 70%) than during previous months of the study. Schooling behavior was most distinct in the spring. Schooling events were present in 30 to 96% of the fish events during that period, with a peak on May 19. Schooling events were also present in the summer, but at lower numbers. With the exception of some schooling in mid-December, few to no schooling events were observed in the fall and winter months. Diel distributions for schooling fish during spring and fall months indicate schooling was concentrated during daylight hours and no schooling was observed at night. However, in December, schooling occurred at night, after midnight, and during daylight hours. Predator activity, most likely bull trout or rainbow trout according to a USACE biologist, was observed during late spring, when fish abundance index and schooling were highest for the year, and again in the fall months when fish events increased from a summer low. No predator activity was observed in the summer, and little activity occurred during the winter months.

Khan, Fenton; Johnson, Gary E.; Royer, Ida M.; Phillips, Nathan RJ; Hughes, James S.; Fischer, Eric S.; Ham, Kenneth D.; Ploskey, Gene R.

2012-04-01T23:59:59.000Z

285

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

. . . .... ...... ..... .. . .. . . .. . , . . . . ..- - --. -- -. , . . DOEF 1325,8 (08.93) United States Government Department of Energy memorandum DATE: August 13, 2007 1 Audit Report Number: OAS-L-07-21 REPLY TO ATTN OF: IG-32 (A06PR047) SUBJECT: Audit of Executive Compensation at Selected National Nuclear Security Administration Sites TO: Director, Policy and Internal Controls Management, NA-66 INTRODUCTION AND OBJECTIVE As part of a Department of Energy-wide audit of executive compensation, we reviewed fourN* Lti nai-.AL 4 ... :.. ,._*i Amiinistration (NiNSA)SsitCe. Speuiiiu-~l we reviewed executive cormpeisation costs incurred and claimed for Fiscal Years 2003, 2004, and 2005 at Los Alamos National Laboratory (LANL), Lawrence Livermore National Laboratory (LLNL), Sandia National Laboratories, and the Y-12

286

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

4 DOE F 1325.8 (08-93) United States Government Department of Energy memorandum DATE: April 23, 2004 Audit Report Number: OAS-L-04-16 REPLY TO ATTN OF: IG-35 (A04YT023) SUBJECT: Audit Report on "Modernization Activities at the Y-12 National Security Complex" TO: Richard Speidel, Director, Policy and Internal Controls Management, NA-66 INTRODUCTION AND OBJECTIVE As part of the National Nuclear Security Administration's (NNSA) nuclear weapons complex, the Y-12 National Security Complex (Y-12) performs critical roles in strengthening national security and reducing the global threat from weapons of mass destruction. The Y-12 modernization plan (plan) seeks to foster the development of a physical plant that is efficient and effective in serving its national security missions. The

287

United States Government Memorandum  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

8/16/07 09:15 FAX 301 903 4656 CAPITAL REGION 8/16/07 09:15 FAX 301 903 4656 CAPITAL REGION * 002 DOE F 1325.8 (08-93) Department of Energy United States Government Memorandum DATE: August 15, 2007 Audit Report Number: OAS-L-07-22 REPLY TO ATTN OF: IG-34 (A06GT006) SUBJECT: Report on "Hazardous Chemicals Inventory Management at the Savannah River Site" TO: Manager, Savannah River Operations Office BACKGROUND The Savannah River Site (Savannah River) maintains large inventories of hazardous chemicals for its scientific, environmental cleanup and production operations. Many of these chemicals are known carcinogens; some are corrosive, while others are highly flammable. As such, these chemicals can pose serious health and safety risks to workers and members of the public, the environment, and to emergency first responders if not properly managed and controlled.

288

Coordinated Control of HVAC Systems  

E-Print Network (OSTI)

This paper describes the development of new control logic for starting and stopping energy-intensive equipment in buildings such as staged air-conditioning units. The concept is to use pulse-width modulation (PWM) instead of level-crossing logic. A finite state machine is used to handle the case where a single unit has multiple stages of operation. An optimized coordinator determines the phase of the PWM signals of each unit so that peak demand for power is minimized over each PWM period. Control logic for the PWM function was developed so that the phase could be manipulated by the coordinator. Computer simulations were used to assess the performance of the new strategy and to compare it to levelcrossing logic. The following five metrics were used to assess the performance: 1) magnitude of the control error, 2) start/stop frequency, 3) average power consumption, 4) standard deviation of the power consumption, 5) peak power consumption. The computer simulations showed that the new strategy could reduce peak power consumption by 20% relative to level-crossing logic. The computer simulations also showed that the new strategy increased the magnitude of the space temperature control error by 11% and increased the number of start/stop operations by 27% relative to level-crossing logic.

Federspiel, C.; Lanning, S. D.; Li, H.; Auslander, D. M.

2001-01-01T23:59:59.000Z

289

Noise Analysis of Statham Temperature Chamber  

SciTech Connect

A procedure is described to subdue the noise made by the LN2 control valve on a Statham Temperature Chamber.

Mielke, R. L.

1973-01-15T23:59:59.000Z

290

Best Practice for Energy Efficient Cleanrooms: Fan-Filter Units  

E-Print Network (OSTI)

control F iltra ti on ? Fan Efficiency ? Right Sizing ?Energy Performance of Fan-Filte r Units, Version 1.3 (2005),RP36.1 (Draft). Testing Fan-Filter Units. Draft Recommended

Xu, Tengfang

2005-01-01T23:59:59.000Z

291

United Energy | Open Energy Information  

Open Energy Info (EERE)

United Energy United Energy Name United Energy Address 284, Old Deal Rd Place Eatontown, New Jersey Zip 07722 Sector Solar Product Energy Efficiency, Renewable Energy Year founded 2009 Number of employees 1-10 Phone number 201-697-8770 Website http://www.unitedenergypro.com Coordinates 40.2785975°, -74.0359722° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":40.2785975,"lon":-74.0359722,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

292

External vs. body temperature  

NLE Websites -- All DOE Office Websites (Extended Search)

External vs. body temperature External vs. body temperature Name: jacqui Location: N/A Country: N/A Date: N/A Question: If one's internal body temperature is approximately 98.6, WHY when the external temperature is 98.6 do we feel hot? Since both temperatures are "balanced", shouldn't we feel comfortable? I am assuming here that humidity levels are controlled, and play no factor in the external temperature. Replies: First of all, skin temperature is lower than 98.6F; 98.6F is internal body temperature, so air at 98.6F is hotter than skin. But more important, it is the nervous system, and the cells in your skin that your brain uses to detect temperature that determine whether you "feel" hot or not, not whether the air is hotter than your skin. These are set so that you feel hot when the air is actually colder than your skin. Why? They are probably set to make you feel hot whenever the air is warm enough so that your body has some trouble getting rid of the excess heat it produces through metabolism. This insures that you take some actions to help your body cool off. Like drinking cool water, or reducing exercise

293

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

uq/Uu.3/uo U-L:i ' rAA OuL a uo oUu. 0tri.l± i m,.i,*, u". run.' r.yrcir V e.u uq/Uu.3/uo U-L:i ' rAA OuL a uo oUu. 0tri.l± i m,.i,*, u". run.' r.yrcir V e.u O000DOE F 1325.8 (08-93) Department of Energy United States Government Department of Energy Memorandum OFFICE OF INSPECTOR GENERAL DATE: March 31,2006 REPLY TO ATTN OF: IG-34 (A05TG028) Audit Report No.: OAS-L-06-10 SUBJECT: Report on Audit of "The Department's Information Technology Capital Planning and Investment Control Process" TO: Chief Information Officer, IM-1 INTRODUCTION AND OBJECTIVE Federal guidance requires that Agencies develop and implement capital planning and investment control (CPIC) processes to help ensure that their major information technology investments achieve intended outcomes, represent the best allocation of resources, and reach strategic goals and objectives. The Department of Energy

294

Acoustic Imaging Evaluation of Juvenile Salmonid Behavior in the Immediate Forebay of the Water Temperature Control Tower at Cougar Dam, 2010  

Science Conference Proceedings (OSTI)

This report presents the results of an evaluation of juvenile Chinook salmonid (Oncorhynchus tshawytscha) behavior in the immediate forebay of the Water Temperature Control (WTC) tower at Cougar Dam in 2010. The study was conducted by the Pacific Northwest National Laboratory for the U.S. Army Corps of Engineers. The overall goal of the study was to characterize juvenile salmonid behavior and movement patterns in the immediate forebay of the WTC tower for fisheries resource managers to use to make decisions on bioengineering designs for long-term structures and/or operations to facilitate safe downstream passage for juvenile salmonids. We collected acoustic imaging (Dual-Frequency Identification Sonar; DIDSON) data from February 1, 2010 through January 31, 2011 to evaluate juvenile salmonid behavior year-round in the immediate forebay surface layer of the WTC tower (within 20 m, depth 0-5 m). From October 28, 2010 through January 31, 2011 a BlueView acoustic camera was also deployed in an attempt to determine its usefulness for future studies as well as augment the DIDSON data. For the DIDSON data, we processed a total of 35 separate 24-h periods systematically covering every other week in the 12-month study. Two different 24-hour periods were processed for the BlueView data for the feasibility study. Juvenile salmonids were present in the immediate forebay of the WTC tower throughout 2010. The juvenile salmonid abundance index was low in the spring (fish per sample-day), began increasing in late April and peaked in mid-May. Fish abundance index began decreasing in early June and remained low in the summer months. Fish abundance increased again in the fall, starting in October, and peaked on November 8-9. A second peak occurred on December 22. Afterwards, abundance was low for the rest of the study (through January 2011). Average fish length for juvenile salmonids during early spring 2010 was 214 {+-} 86 mm (standard deviation). From May through early November, average fish length remained relatively consistent (132 {+-} 39 mm), after which average lengths increased to 294 {+-} 145 mm for mid-November though early December. Fish behavior analysis indicates milling in front of the intake tower was the most common behavior observed throughout the study period (>50% of total fish events). The next most common movement patterns were fish traversing along the front of the tower, east-to-west and west-to-east. The proportion of fish events seen moving into (forebay to tower) or out of (tower to forebay) the tower was generally low throughout the spring, summer, and early fall for both directions combined. From mid-December 2010 through the end of the study, the combined proportions of fish moving into and out of the tower were higher than previous months of this study. Schooling behavior was most distinct in the spring from late April through mid-June. Schooling events were present in 30 - 96% of the fish events during that period, with a peak in mid-May. Schooling events were also present in the summer, but at lower numbers. Diel distributions for schooling fish during spring, fall, and winter months indicate schooling was concentrated during daylight hours. No schooling was observed at night. Predator activity was observed during late spring, when fish abundance and schooling were highest for the year, and again in the fall months when fish events increased from a summer low. No predator activity was observed in the summer, and little activity occurred during the winter months. For the two days of BlueView data analyzed for vertical distribution in the forebay, a majority of fish (>50%) were present in the middle of the water column (10 - 20 m deep). Between 20 and 41 % of total fish abundance were found in the bottom of the water column (20 - 30 m deep). Few fish were observed in the top 10 m of the water column.

Khan, Fenton; Johnson, Gary E.; Royer, Ida M.; Phillips, Nathan RJ; Hughes, James S.; Fischer, Eric S.; Ploskey, Gene R.

2011-10-01T23:59:59.000Z

295

Acoustic Imaging Evaluation of Juvenile Salmonid Behavior in the Immediate Forebay of the Water Temperature Control Tower at Cougar Dam, 2010  

SciTech Connect

This report presents the results of an evaluation of juvenile Chinook salmonid (Oncorhynchus tshawytscha) behavior in the immediate forebay of the Water Temperature Control (WTC) tower at Cougar Dam in 2010. The study was conducted by the Pacific Northwest National Laboratory for the U.S. Army Corps of Engineers. The overall goal of the study was to characterize juvenile salmonid behavior and movement patterns in the immediate forebay of the WTC tower for fisheries resource managers to use to make decisions on bioengineering designs for long-term structures and/or operations to facilitate safe downstream passage for juvenile salmonids. We collected acoustic imaging (Dual-Frequency Identification Sonar; DIDSON) data from February 1, 2010 through January 31, 2011 to evaluate juvenile salmonid behavior year-round in the immediate forebay surface layer of the WTC tower (within 20 m, depth 0-5 m). From October 28, 2010 through January 31, 2011 a BlueView acoustic camera was also deployed in an attempt to determine its usefulness for future studies as well as augment the DIDSON data. For the DIDSON data, we processed a total of 35 separate 24-h periods systematically covering every other week in the 12-month study. Two different 24-hour periods were processed for the BlueView data for the feasibility study. Juvenile salmonids were present in the immediate forebay of the WTC tower throughout 2010. The juvenile salmonid abundance index was low in the spring (<200 fish per sample-day), began increasing in late April and peaked in mid-May. Fish abundance index began decreasing in early June and remained low in the summer months. Fish abundance increased again in the fall, starting in October, and peaked on November 8-9. A second peak occurred on December 22. Afterwards, abundance was low for the rest of the study (through January 2011). Average fish length for juvenile salmonids during early spring 2010 was 214 {+-} 86 mm (standard deviation). From May through early November, average fish length remained relatively consistent (132 {+-} 39 mm), after which average lengths increased to 294 {+-} 145 mm for mid-November though early December. Fish behavior analysis indicates milling in front of the intake tower was the most common behavior observed throughout the study period (>50% of total fish events). The next most common movement patterns were fish traversing along the front of the tower, east-to-west and west-to-east. The proportion of fish events seen moving into (forebay to tower) or out of (tower to forebay) the tower was generally low throughout the spring, summer, and early fall for both directions combined. From mid-December 2010 through the end of the study, the combined proportions of fish moving into and out of the tower were higher than previous months of this study. Schooling behavior was most distinct in the spring from late April through mid-June. Schooling events were present in 30 - 96% of the fish events during that period, with a peak in mid-May. Schooling events were also present in the summer, but at lower numbers. Diel distributions for schooling fish during spring, fall, and winter months indicate schooling was concentrated during daylight hours. No schooling was observed at night. Predator activity was observed during late spring, when fish abundance and schooling were highest for the year, and again in the fall months when fish events increased from a summer low. No predator activity was observed in the summer, and little activity occurred during the winter months. For the two days of BlueView data analyzed for vertical distribution in the forebay, a majority of fish (>50%) were present in the middle of the water column (10 - 20 m deep). Between 20 and 41 % of total fish abundance were found in the bottom of the water column (20 - 30 m deep). Few fish were observed in the top 10 m of the water column.

Khan, Fenton; Johnson, Gary E.; Royer, Ida M.; Phillips, Nathan RJ; Hughes, James S.; Fischer, Eric S.; Ploskey, Gene R.

2011-10-01T23:59:59.000Z

296

Acoustic Imaging Evaluation of Juvenile Salmonid Behavior in the Immediate Forebay of the Water Temperature Control Tower at Cougar Dam, 2010  

SciTech Connect

This report presents the results of an evaluation of juvenile Chinook salmon (Oncorhynchus tshawytscha) behavior at Cougar Dam on the south fork of the McKenzie River in Oregon in 2010. The study was conducted by the Pacific Northwest National Laboratory for the U.S. Army Corps of Engineers (USACE). The overall goal of the study was to characterize juvenile salmonid behavior and movement patterns in the immediate forebay of the Water Temperature Control (WTC) tower of the dam for USACE and fisheries resource managers use in making decisions about bioengineering designs for long-term structures and/or operations to facilitate safe downstream passage for juvenile salmonids. We collected acoustic imaging (Dual-Frequency Identification Sonar; DIDSON) data from March 1, 2010, through January 31, 2011. Juvenile salmonids (hereafter, called 'fish') were present in the immediate forebay of the WTC tower throughout the study. Fish abundance index was low in early spring (<200 fish per sample-day), increased in late April, and peaked on May 19 (6,039 fish). A second peak was observed on June 6 (2904 fish). Fish abundance index decreased in early June and remained low in the summer months (<100 fish per sample-day). During the fall and winter, fish numbers varied with a peak on November 10 (1881 fish) and a minimum on December 7 (12 fish). A second, smaller, peak occurred on December 22 (607 fish). A univariate statistical analysis indicated fish abundance index (log10-transformed) was significantly (P<0.05) positively correlated with forebay elevation, velocity over the WTC tower intake gate weirs, and river flows into the reservoir. A subsequent multiple regression analysis resulted in a model (R2=0.70) predicting fish abundance (log-transformed index values) using two independent variables of mean forebay elevation and the log10 of the forebay elevation range. From the approximate fish length measurements made using the DIDSON imaging software, the average fish length during early spring 2010 was 214 {+-} 86 mm (standard deviation). From May through early November, the average fish length remained relatively consistent (132 {+-} 54 mm), after which average lengths increased to 295 {+-} 148 mm for mid-November though early December. From mid-December through January the average fish length decreased to 151 {+-} 76 mm. Milling in front of the WTC tower was the most common fish behavior observed throughout the study period. Traversing along the front of the tower, east-to-west and west-to-east, was the next common behavior. The percentage of fish events showing movement from the forebay to the tower or from the tower to the forebay was generally low throughout the spring, summer, and early fall (0 to 30% for both directions combined, March through early November). From mid-November 2010 through the end of the study (January 31, 2011), the combined percentages of fish moving into and out of the tower were higher (25 to 70%) than during previous months of the study. Schooling behavior was most distinct in the spring. Schooling events were present in 30 to 96% of the fish events during that period, with a peak on May 19. Schooling events were also present in the summer, but at lower numbers. With the exception of some schooling in mid-December, few to no schooling events were observed in the fall and winter months. Diel distributions for schooling fish during spring and fall months indicate schooling was concentrated during daylight hours and no schooling was observed at night. However, in December, schooling occurred at night, after midnight, and during daylight hours. Predator activity, most likely bull trout or rainbow trout according to a USACE biologist, was observed during late spring, when fish abundance index and schooling were highest for the year, and again in the fall months when fish events increased from a summer low. No predator activity was observed in the summer, and little activity occurred during the winter months.

Khan, Fenton; Johnson, Gary E.; Royer, Ida M.; Phillips, Nathan RJ; Hughes, James S.; Fischer, Eric S.; Ham, Kenneth D.; Ploskey, Gene R.

2012-04-01T23:59:59.000Z

297

Solar heating unit  

SciTech Connect

A solar heating unit is disclosed for disposition exteriorly of a building window for heating the air within the space interiorly of the window embodying a casing with a transverse divider for creating a rear passage and a front passage which are in communication in their lower portions. The upper end of the rear passage connects with the forward end of a rearwardly extending lower duct having a cool air inlet at the rearward end thereof. The upper end of the front passage connects with the forward end of an upper duct progressing rearwardly above the lower duct and with there being a warm air outlet at the rearward extremity thereof. A heat exchanger is disposed within the front passage for impingement thereon of solar radiation passing through a transparent panel defining the front of said casing. A thermal responsive closure is provided at the upper end of said front passage for closing same when the temperature within the front passage has descended to a predetermined level.

Grisbrook, R.B.

1978-10-24T23:59:59.000Z

298

STATEMENT OF CONSIDERATIONS REQUEST BY UNITED TECHNOLOGIES CORPORATION (UNITED  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

RTGHTS TO INVENTIONS MADE UNDER RTGHTS TO INVENTIONS MADE UNDER COOPERATIVE AGREEMENT NUMBER DE-FC04-02AL67628, DOE WAIVER NO. W(A) 02-038. The Petitioner, United Technologies, acting through the United Technologies Research Center (UTRC), has requested a waiver of all domestic and foreign patent iights to inventions that may be conceived or first actually reduced to practice in the course of UTRC's work as the prime contractor under Cooperative Agreement Number DI-FC04- 02AL67628 entitled "On-Board Vehicle, Cost Effective, Hydrogen Enhancement Technology PEM Fuel Cells" with the U S. Department of Energy (DOE). The work to be done will be the development and fabrication of an integrated high temperature water gas shift reactor/hydrogen separator for use in a PEM fuel cell power

299

Nomination Form DEPARTMENT / UNIT  

E-Print Network (OSTI)

Nomination Form DEPARTMENT / UNIT: CAMPUS ADDRESS: JOB TITLE: DEPARTMENT EMAIL ADDRESS: DEPARTMENT TELEPHONE: 2014 FRANKLIN STAFF EXCELLENCE AWARDS START DATE IN DEPARTMENT / UNIT: Nominee Information NAME / RESEARCHPROFESSIONAL Signature of Head / Director of Nominee's Unit: NOMINATION PACKET DEADLINE: MARCH 7, 2014 PLEASE

Arnold, Jonathan

300

Nomination Form DEPARTMENT / UNIT  

E-Print Network (OSTI)

Nomination Form DEPARTMENT / UNIT: CAMPUS ADDRESS: JOB TITLE: DEPARTMENT EMAIL ADDRESS: DEPARTMENT TELEPHONE: 2012 FRANKLIN STAFF EXCELLENCE AWARDS START DATE IN DEPARTMENT / UNIT: Nominee Information NAME / RESEARCHPROFESSIONAL Signature of Head / Director of Nominee's Unit: NOMINATION PACKET DEADLINE: FRIDAY MARCH 2, 2012

Arnold, Jonathan

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


301

Nomination Form DEPARTMENT / UNIT  

E-Print Network (OSTI)

Nomination Form DEPARTMENT / UNIT: CAMPUS ADDRESS: JOB TITLE: DEPARTMENT EMAIL ADDRESS: DEPARTMENT TELEPHONE: 2011 FRANKLIN STAFF EXCELLENCE AWARDS START DATE IN DEPARTMENT / UNIT: Nominee Information NAME / RESEARCHPROFESSIONAL Signature of Head / Director of Nominee's Unit: NOMINATION PACKET DEADLINE: FRIDAY MARCH 4, 2011

Arnold, Jonathan

302

Nomination Form DEPARTMENT / UNIT  

E-Print Network (OSTI)

Nomination Form DEPARTMENT / UNIT: CAMPUS ADDRESS: JOB TITLE: DEPARTMENT EMAIL ADDRESS: DEPARTMENT TELEPHONE: 2013 FRANKLIN STAFF EXCELLENCE AWARDS START DATE IN DEPARTMENT / UNIT: Nominee Information NAME / RESEARCHPROFESSIONAL Signature of Head / Director of Nominee's Unit: NOMINATION PACKET DEADLINE: MARCH 5, 2013 PLEASE

Arnold, Jonathan

303

temperatures | OpenEI Community  

Open Energy Info (EERE)

temperatures temperatures Home Graham7781's picture Submitted by Graham7781(1992) Super contributor 18 January, 2013 - 15:46 U.S. Global Change Research Program publishes "National Climate Assessment" report for United States climate change drought OpenEI sea level rise temperatures U.S. Global Climate Change program The U.S. Global Change Research Program, established under the Department of Commerce in 2010, and partnered with NOAA, released an extensive National Climate Assessment report, projecting future climate changes in the United States under different scenarios. The 1,200 page report highlights some rather grim findings about the future of climate change. Here are 5 of the more disconcerting graphics from the report: 1. U.S. Average Temperatures Syndicate content

304

Long-Lead Seasonal Temperature Prediction Using Optimal Climate Normals  

Science Conference Proceedings (OSTI)

This study is intended to determine the spatially varying optimal time periods for calculating seasonal climate normals over the entire United States based on temperature data at 344 United States climate divisions during the period of 1931–1993. ...

Jin Huang; Huug M. van den Dool; Anthony G. Barnston

1996-04-01T23:59:59.000Z

305

Compact monolithic capacitive discharge unit  

DOE Patents (OSTI)

A compact monolithic capacitive discharge unit (CDU) is disclosed in which a thyristor switch and a flyback charging circuit are both sandwiched about a ceramic energy storage capacitor. The result is a compact rugged assembly which provides a low-inductance current discharge path. The flyback charging circuit preferably includes a low-temperature co-fired ceramic transformer. The CDU can further include one or more ceramic substrates for enclosing the thyristor switch and for holding various passive components used in the flyback charging circuit. A load such as a detonator can also be attached directly to the CDU.

Roesler, Alexander W. (Tijeras, NM); Vernon, George E. (Rio Rancho, NM); Hoke, Darren A. (Albuquerque, NM); De Marquis, Virginia K. (Tijeras, NM); Harris, Steven M. (Albuquerque, NM)

2007-06-26T23:59:59.000Z

306

Interim Project Results: United Parcel Service's Second-Generation...  

NLE Websites -- All DOE Office Websites (Extended Search)

Application for Each Engine and Truck Manufacturer Hybrid Drive Unit Transmission InverterControls Partners Brakes (ABS) Eaton Hybrid Electric System UPS' hybrid-electric...

307

Design Method for the Heating/Cooling Coil in the AHU Based on Fuzzy Logic - Part Two: Design of the Minimum Heat-Exchanging Unit  

E-Print Network (OSTI)

Considering a heating/cooling coil with adjustable heat-exchange area, an unequal type is put forward in this paper. Aiming at the application of such heat exchanger in an air-handling unit, restriction conditions are given for the minimum heat-exchanging unit in accordance with the requirement of control precision of indoor temperature and humidity. The structure adjustable heat exchanger improved the hydraulic adjusting characteristics of existing air handling units in the respective structure, and overcame the problems of existing air-handling units such as a narrow hydraulic adjusting range due to the rapid-opening performance of the continuous motor-driven value. As a result, such kind of heat exchanger is extremely suitable to fuzzy control.

Zhang, J.; Chen, Y.; Liang, Z.

2006-01-01T23:59:59.000Z

308

Fever and Body Temperature  

NLE Websites -- All DOE Office Websites (Extended Search)

Fever and Body Temperature Fever and Body Temperature Name: Ying Location: N/A Country: N/A Date: N/A Question: Hi, I have a few questions that I want to ask you: Why does your body chose to raise its temperature when you have a fever? Replies: Most bacteria and viruses that live in your body grow best at body temperature. They don't grow very well when the temperature is raised. When there are bacteria in your body they give off chemicals that signal white blood cells to come to try to eat them and also affect an area in your brain called the hypothalamus. This part of the brain controls alot of the automatic functions in your body and is also the site of your body's "thermostat". When the chemicals from the bacteria circulate through the hypothalamus it sets the body's temperature higher. This is called a fever. Your body kind of tries to "sweat out" the bacteria and kill them with a higher temperature. Some scientists question whether trying to bring down a fever is the best thing to do. If it isn't too high, some believe we should just let it work

309

Maintaining body temperature  

NLE Websites -- All DOE Office Websites (Extended Search)

Maintaining body temperature Maintaining body temperature Name: Jeff Location: N/A Country: N/A Date: N/A Question: What keeps the human body at a constant temperature of 98.6? Replies: Maintaining body temperature is very complex. It also takes a lot of energy. About 80% of the energy from the food you eat goes to maintaining body temperature. Basically, the chemical reactions of metabolism of stored food, especially fats, generate heat as a by product. This heat warms the body. The brain reads temperature and controls to some extent the rate of this metabolism. There are also many other mechanisms triggered by the brain to keep the core of your body warm, even if the periphery (skin) is cold. Blood vessels to the fingers and toes constrict, so that the cold air doesn't cool the blood too much, so that cooled blood doesn't cool down the heart and brain when it returns. In severe cases, your body will sacrifice a finger or a toe to keep you from dying of cold core temperature (frostbite: it saves your life!). Also the brain can order a lot of muscles to contract rapidly. This generates a lot of heat quickly, a response called shivering. There's much more to this exciting field of research.

310

A Review of Cooperative Temperature Data Validation  

Science Conference Proceedings (OSTI)

The network of about 5600 cooperative stations in the United States provides the baseline temperature data upon which most climatologies are based. Since the data serve between 40 000 and 50 000 primary users each year, and untold secondary users,...

Nathaniel B. Guttman; Robert G. Quayle

1990-04-01T23:59:59.000Z

311

Solar Eclipse Effect on Shelter Air Temperature  

Science Conference Proceedings (OSTI)

Decreases in shelter temperature during eclipse events were quantified on the basis of observations, numerical model simulations, and complements conceptual evaluations. Observations for the annular eclipse on 10 May 1994 over the United States ...

M. Segal; R. W. Turner; J. Prusa; R. J. Bitzer; S. V. Finley

1996-01-01T23:59:59.000Z

312

BSA 08-04: High Temperature Interfacial Superconductivity  

Cuprate superconductors exhibit relatively high transition temperatures, but their unit cells are complex and large. Localizing a superconducting layer to a small ...

313

CO2 Emissions - United Korea  

NLE Websites -- All DOE Office Websites (Extended Search)

Fossil Fuel CO2 Emissions Regional Centrally Planned Asia United Korea CO2 Emissions from United Korea Data graphic Data CO2 Emissions from United Korea...

314

TRENDS: TEMPERATURE  

NLE Websites -- All DOE Office Websites (Extended Search)

Historical Isotopic Temperature Record from the Vostok Ice Core Historical Isotopic Temperature Record from the Vostok Ice Core Graphics Digital Data J.R. Petit, D. Raynaud, and C. Lorius Laboratoire de Glaciogie et Géophysique de l'Environnement, CNRS, Saint Martin d'Hères Cedex, France J. Jouzel and G. Delaygue Laboratoire des Sciences du Climat et de l'Environnement (LSCE), CEA/CNRS, L'Orme des Merisiers, CEA Saclay, 91191 Gif-sur-Yvette Cedex, France N.I. Barkov Arctic and Antarctic Research Institute, Beringa Street 38, 199397 St. Petersburg, Russia V.M. Kotlyakov Institute of Geography, Staromonetny, per 29, Moscow 109017, Russia DOI: 10.3334/CDIAC/cli.006 Period of Record 420,000 years BP-present Methods Because isotopic fractions of the heavier oxygen-18 (18O) and deuterium (D) in snowfall are temperature-dependent and a strong spatial correlation

315

BNL United Way Campaign  

NLE Websites -- All DOE Office Websites (Extended Search)

about Long Island issues and challenges. Because we care, we come together to raise money towards The United Way of Long Island, which provides "services to children and...

316

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

'OQOl - United States Government - Department of Energy National Nuclear Security Administration memorandum January 19, 201 1 DATE. REPLY TO ATTN OF: Y12-60:Gorman SUBJECT ANNUAL...

317

UnitOverview  

NLE Websites -- All DOE Office Websites (Extended Search)

UNIT OVERVIEW A general overview of LHC physics, accelerator and detector design, and how data inform claims and reasoning begins with an exploration of the "Big Questions" that...

318

Redefining the SI Units  

Science Conference Proceedings (OSTI)

... and accuracy, simplify and normalize the unit definitions, and liberate the system from dependence on the prototype kilogram, an artifact adopted in ...

2013-06-24T23:59:59.000Z

319

Base unit definitions: Kilogram  

Science Conference Proceedings (OSTI)

... Unit of mass (kilogram), Abbreviations: CGPM, CIPM, BIPM. At the end of the 18th century, a kilogram was the mass of a cubic decimeter of water. ...

320

United States Patent  

NLE Websites -- All DOE Office Websites (Extended Search)

( 1 of 1 ) United States Patent 6,994,831 Gentile , et al. February 7, 2006 Oxidative tritium decontamination system Abstract The Oxidative Tritium Decontamination System, OTDS,...

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


321

" Million Housing Units, Final...  

U.S. Energy Information Administration (EIA) Indexed Site

0 Appliances in Homes in South Region, Divisions, and States, 2009" " Million Housing Units, Final" ,,"South Census Region" ,,,"South Atlantic Census Division",,,,,,"East South...

322

" Million Housing Units, Final...  

U.S. Energy Information Administration (EIA) Indexed Site

8 Home Appliances in Homes in Northeast Region, Divisions, and States, 2009" " Million Housing Units, Final" ,,"Northeast Census Region" ,,,"New England Census Division",,,"Middle...

323

Rooftop Unit Campaign  

NLE Websites -- All DOE Office Websites (Extended Search)

919-943-7291 April 4, 2013 BTO Program Review 2 | Building Technologies Office eere.energy.gov Purpose & Objectives - Problem Statement * Packaged rooftop units (RTUs)...

324

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

to this report. INTRODUCTION AND OBJECTIVE The European Laboratory for Particle Physics, CERN, in collaboration with the United States (U.S.) and other non-member states,...

325

United Illuminating | Open Energy Information  

Open Energy Info (EERE)

Illuminating Illuminating Jump to: navigation, search Logo: United Illuminating Name United Illuminating Address 157 Church St Place New Haven, Connecticut Zip 06510 Sector Services Product Green Power Marketer Website http://www.uinet.com/ Coordinates 41.3073289°, -72.9247896° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":41.3073289,"lon":-72.9247896,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

326

United Nations | Open Energy Information  

Open Energy Info (EERE)

Nations Nations Jump to: navigation, search Logo: United Nations Name United Nations Address UN Headquarters 1st Ave & 46th Street Place New York, NY Zip 10017 Region Northeast - NY NJ CT PA Area Year founded 1945 Website http://www.un.org/ Coordinates 40.7143528°, -74.0059731° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":40.7143528,"lon":-74.0059731,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

327

Summary Max Total Units  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Max Total Units Max Total Units *If All Splits, No Rack Units **If Only FW, AC Splits 1000 52 28 28 2000 87 59 35 3000 61 33 15 4000 61 33 15 Totals 261 153 93 ***Costs $1,957,500.00 $1,147,500.00 $697,500.00 Notes: added several refrigerants removed bins from analysis removed R-22 from list 1000lb, no Glycol, CO2 or ammonia Seawater R-404A only * includes seawater units ** no seawater units included *** Costs = (total units) X (estimate of $7500 per unit) 1000lb, air cooled split systems, fresh water Refrig Voltage Cond Unit IF-CU Combos 2 4 5 28 References Refrig Voltage C-U type Compressor HP R-404A 208/1/60 Hermetic SA 2.5 R-507 230/1/60 Hermetic MA 2.5 208/3/60 SemiHerm SA 1.5 230/3/60 SemiHerm MA 1.5 SemiHerm HA 1.5 1000lb, remote rack systems, fresh water Refrig/system Voltage Combos 12 2 24 References Refrig/system Voltage IF only

328

Composite stabilizer unit  

DOE Patents (OSTI)

This invention is comprised of an improved fin stabilized projectile including multiple stabilizer fins upon a stabilizer unit situated at the aft end of the projectile is provided, the improvement wherein the stabilizer fins are joined into the stabilizer unit by an injection molded engineering grade polymer.

Ebaugh, L.R.; Sadler, C.P.; Carter, G.D.

1990-12-31T23:59:59.000Z

329

Composite stabilizer unit  

DOE Patents (OSTI)

This invention is comprised of an improved fin stabilized projectile including multiple stabilizer fins upon a stabilizer unit situated at the aft end of the projectile is provided, the improvement wherein the stabilizer fins are joined into the stabilizer unit by an injection molded engineering grade polymer.

Ebaugh, L.R.; Sadler, C.P.; Carter, G.D.

1990-01-01T23:59:59.000Z

330

Composite stabilizer unit  

SciTech Connect

An improved fin stabilized projectile including multiple stabilizer fins upon a stabilizer unit situated at the aft end of the projectile is provided, the improvement wherein the stabilizer fins are joined into the stabillizer unit by an injection molded engineering grade polymer.

Ebaugh, Larry R. (Los Alamos, NM); Sadler, Collin P. (Los Alamos, NM); Carter, Gary D. (Espanola, NM)

1992-01-01T23:59:59.000Z

331

Associative list processing unit  

SciTech Connect

An associative list processing unit and method comprising employing a plurality of prioritized cell blocks and permitting inserts to occur in a single clock cycle if all of the cell blocks are not full. Also, an associative list processing unit and method comprising employing a plurality of prioritized cell blocks and using a tree of prioritized multiplexers descending from the plurality of cell blocks.

Hemmert, Karl Scott; Underwood, Keith D.

2013-01-29T23:59:59.000Z

332

Automated Sample collection and Analysis unit  

DOE Patents (OSTI)

Autoramp is an atmospheric radionuclide collection and analysis unit designed for unattended operation. A large volume of air passes through one of 31 filter cartridges which is then moved from a sampling chamber and past a bar code reader, to a shielded enclosure. The collected dust-borne radionuclides are counted with a high resolution germanium gamma-ray detector. An analysis is made and the results are transmitted to a central station that can also remotely control the unit.

Latner, Norman; Sanderson, Colin G.; Negro, Vincent C.

1999-03-31T23:59:59.000Z

333

High temperature turbine engine structure  

DOE Patents (OSTI)

A high temperature turbine engine includes a hybrid ceramic/metallic rotor member having ceramic/metal joint structure. The disclosed joint is able to endure higher temperatures than previously possible, and aids in controlling heat transfer in the rotor member.

Boyd, Gary L. (Tempe, AZ)

1990-01-01T23:59:59.000Z

334

Units: Cool Modules for HOT Languages  

E-Print Network (OSTI)

A module system ought to enable assembly-line programming using separate compilation and an expressive linking language. Separate compilation allows programmers to develop parts of a program independently. A linking language gives programmers precise control over the assembly of parts into a whole. This paper presents models of program units, MzScheme's module language for assembly-line programming. Units support separate compilation, independent module reuse, cyclic dependencies, hierarchical structuring, and dynamic linking. The models explain how to integrate units with untyped and typed languages such as Scheme and ML.

Matthew Flatt; Matthias Felleisen

1998-01-01T23:59:59.000Z

335

United States Record-Maximum/Minimum Daily Temperatures  

NLE Websites -- All DOE Office Websites (Extended Search)

North Carolina North Dakota Ohio Oklahoma Oregon Pennsylvania Rhode Island South Carolina South Dakota Tennessee Texas Utah Vermont Virginia Washington West Virginia Wisconsin Map...

336

Observed Vegetation–Climate Feedbacks in the United States  

Science Conference Proceedings (OSTI)

Observed vegetation feedbacks on temperature and precipitation are assessed across the United States using satellite-based fraction of photosynthetically active radiation (FPAR) and monthly climate data for the period of 1982–2000. This study ...

M. Notaro; Z. Liu; J. W. Williams

2006-03-01T23:59:59.000Z

337

UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION  

NLE Websites -- All DOE Office Websites (Extended Search)

water temperatures between 10C (50F) to 26C (79F). The southern boundary is the United States-Mexico maritime boundary. The northern boundary is defined as the position...

338

Secular Variations in Streamflow in the Western United States  

Science Conference Proceedings (OSTI)

Long-term streamflow series in the western United States were examined for evidence of secular changes related to climate. Streamflow series contained appreciable low-frequency variation related to the combined influence of temperature and ...

David M. Meko; Charles W. Stockton

1984-06-01T23:59:59.000Z

339

Interannual Climate Variability and Snowpack in the Western United States  

Science Conference Proceedings (OSTI)

An important part of the water supply in the western United States is derived from runoff fed by mountain snowmelt Snow accumulation responds to both precipitation and temperature variations, and forms an interesting climatic index, since it ...

Daniel R. Cayan

1996-05-01T23:59:59.000Z

340

Adjustment of GCM Precipitation Intensity over the United States  

Science Conference Proceedings (OSTI)

A regression equation is developed to adjust the simulated monthly averaged intensity of hourly precipitation over the continental United States using air temperature at the first model level (about 80 m above ground) simulated by a revised ...

Mingxuan Chen; Xubin Zeng; Robert E. Dickinson

1998-09-01T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


341

Control system for electric water heater with heat pump external heat source  

Science Conference Proceedings (OSTI)

A control system for an electric water heater operatively associated with an external heat source, such as a heat pump. The water heater includes a water storage tank provided with an electric tank heating unit having a tank thermostat which closes in response to water temperature in the tank, allowing a flow of current through the tank heating unit so as to turn it on to heat the water, and which opens when the tank thermostat has been satisfied, interrupting the current flow so as to turn the tank heating unit off. The control system as responsive to the initial current surge through the tank heating unit when the tank thermostat closes to interrupt the current flow to the tank heating unit so as to maintain the heating unit off and to turn on the external heat source and maintain it on until the tank thermostat opens. The initial current surge cleans the contacts of the tank thermostat by burning off any insulating oxide residues which may have formed on them. The control system includes means responsive to abnormal conditions which would prevent the external heat source from heating water effectively for turning off the external heat source and turning on the tank heating unit and maintaining the external heat source off and the tank heating unit on until the tank thermostat is satisfied.

Shaffer Jr., J. E.; Picarello, J. F.

1985-09-10T23:59:59.000Z

342

Preliminary Field Evaluation of Mercury Control Using Combustion Modifications  

Science Conference Proceedings (OSTI)

In this project EER conducted a preliminary field evaluation of the integrated approach for mercury (Hg) and NO{sub x} control. The approach enhanced the 'naturally occurring' Hg capture by fly ash through combustion optimization, increasing carbon in ash content, and lowering ESP temperature. The evaluation took place in Green Station Units 1 and 2 located near Henderson, Kentucky and operated by Western Kentucky Energy. Units 1 and 2 are equipped with cold-side ESPs and wet scrubbers. Green Station Units 1 and 2 typically fire two types of fuel: a bituminous coal and a blend of bituminous coals based on availability. Testing of Hg emissions in Unit 2 without reburning system in operation and at minimum OFA demonstrated that efficiencies of Hg reduction downstream of the ESP were 30-40%. Testing also demonstrated that OFA system operation at 22% air resulted in 10% incremental increase in Hg removal efficiency at the ESP outlet. About 80% of Hg in flue gas at ESP outlet was present in the oxidized form. Testing of Hg emissions under reburning conditions showed that Hg emissions decreased with LOI increase and ESP temperature decrease. Testing demonstrated that maximum Hg reduction downstream of ESP was 40-45% at ESP temperatures higher than 300 F and 60-80% at ESP temperatures lower than 300 F. The program objective to demonstrate 80% Hg removal at the ESP outlet has been met.

V. Lissianski; P. Maly; T. Marquez

2005-01-22T23:59:59.000Z

343

Next Generation Rooftop Unit  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Next Generation Rooftop Unit - Next Generation Rooftop Unit - CRADA Bo Shen Oak Ridge National Laboratory shenb@ornl.gov; 865-574-5745 April 3, 2013 ET R&D project in support of DOE/BTO Goal of 50% Reduction in Building Energy Use by 2030. CRADA project with Trane TOP US Commercial HVAC Equipment OEM 2 | Building Technologies Office eere.energy.gov Purpose & Objectives Problem Statement: half of all US commercial floor space cooled by packaged AC units, consumes more than 1.0 Quad source energy/year; highly efficient systems needed

344

Next Generation Rooftop Unit  

NLE Websites -- All DOE Office Websites (Extended Search)

Next Generation Rooftop Unit - Next Generation Rooftop Unit - CRADA Bo Shen Oak Ridge National Laboratory shenb@ornl.gov; 865-574-5745 April 3, 2013 ET R&D project in support of DOE/BTO Goal of 50% Reduction in Building Energy Use by 2030. CRADA project with Trane TOP US Commercial HVAC Equipment OEM 2 | Building Technologies Office eere.energy.gov Purpose & Objectives Problem Statement: half of all US commercial floor space cooled by packaged AC units, consumes more than 1.0 Quad source energy/year; highly efficient systems needed

345

Beamline Temperatures  

NLE Websites -- All DOE Office Websites (Extended Search)

Temperatures Temperatures Energy: 3.0000 GeV Current: 493.2242 mA Date: 11-Jan-2014 21:40:00 Beamline Temperatures Energy 3.0000 GeV Current 493.2 mA 11-Jan-2014 21:40:00 LN:MainTankLevel 124.4 in LN:MainTankPress 56.9 psi SPEAR-BL:B120HeFlow 15.4 l/min SPEAR-BL:B131HeFlow 22.2 l/min BL 4 BL02:LCW 0.0 ℃ BL02:M0_LCW 31.5 ℃ BL 4-1 BL04-1:BasePlate -14.0 ℃ BL04-1:Bottom1 46.0 ℃ BL04-1:Bottom2 47.0 ℃ BL04-1:Lower 32.0 ℃ BL04-1:Moly 46.0 ℃ BL04-1:ChinGuard1 31.0 ℃ BL04-1:ChinGuard2 31.0 ℃ BL04-1:FirstXtalA -167.0 ℃ BL04-1:FirstXtalB -172.0 ℃ BL04-1:Pad1 31.0 ℃ BL04-1:Pad2 31.0 ℃ BL04-1:SecondXtalA -177.0 ℃ BL04-1:SecondXtalB -175.0 ℃ BL 4-2 BL04-2:BasePlate -14.0 ℃ BL04-2:Bottom1 24.0 ℃ BL04-2:Bottom2 25.0 ℃

346

Seasonal Temperature Forecasts as Products of Antecedent Linear and Spatial Temperature Arrays  

Science Conference Proceedings (OSTI)

Our objective is to evaluate the potential for extracting the maximum information contained in antecedent temperature patterns that operationally could be used in formulating winter seasonal forecasts in the United States. In particular, ...

Merlin P. Lawson; Randall S. Cerveny

1985-08-01T23:59:59.000Z

347

United Cool Air  

Energy.gov (U.S. Department of Energy (DOE))

While our process may start with a "basic model" it is seldom that we fabricate more than a few units that are identical.  Therefore, the definition of "basic model" has a large impact on the...

348

" Million Housing Units, Final...  

U.S. Energy Information Administration (EIA) Indexed Site

the 2009 Poverty Guidelines for families published by the U.S. Department of Health and Human Services. 3Use of heating equipment for another housing unit also includes the use...

349

United States Government  

Office of Legacy Management (LM)

"- .-A*" (MQ) EfG (07-W) United States Government rrla.g-a Department of Energy memorandum DATE: tlEC 1 F: l??? REPLYTo EM-421 (W. A. W illiams , 903-8149) AJTN OF: SUBJECT:...

350

" Million Housing Units, Final...  

U.S. Energy Information Administration (EIA) Indexed Site

that do not contain a storage tank. The water is only heated as it passes through the heat exchanger. 3Use of a water heater for another housing unit also includes the use of...

351

" Million Housing Units, Final...  

U.S. Energy Information Administration (EIA) Indexed Site

that do not contain a storage tank. The water is only heated as it passes through the heat exchanger. 4Use of a water heater for another housing unit also includes the use of...

352

" Million Housing Units, Final...  

U.S. Energy Information Administration (EIA) Indexed Site

5 Appliances in U.S. Homes, by Household Income, 2009" " Million Housing Units, Final" ,,"Household Income" ,"Total U.S.1 (millions)",,,"Below Poverty Line2" ,,"Less than...

353

" Million Housing Units, Final...  

U.S. Energy Information Administration (EIA) Indexed Site

3 Appliances in U.S. Homes, by Year of Construction, 2009" " Million Housing Units, Final" ,,"Year of Construction" ,"Total U.S.1 (millions)" ,,"Before 1940","1940 to 1949","1950...

354

" Million Housing Units, Final...  

U.S. Energy Information Administration (EIA) Indexed Site

6 Appliances in U.S. Homes, by Climate Region, 2009" " Million Housing Units, Final" ,,"Climate Region2" ,"Total U.S.1 (millions)" ,,"Very Cold","Mixed- Humid","Mixed-Dry"...

355

Long-Lead Seasonal Temperature and Precipitation Prediction Using Tropical Pacific SST Consolidation Forecasts  

Science Conference Proceedings (OSTI)

Objective seasonal forecasts of temperature and precipitation for the conterminous United States are produced using tropical Pacific sea surface temperature forecasts for the Niño-3.4 region in conjunction with composites of observed temperature ...

R. W. Higgins; H-K. Kim; D. Unger

2004-09-01T23:59:59.000Z

356

Experiment Hazard Class 3 - High Temperatures  

NLE Websites -- All DOE Office Websites (Extended Search)

* RF and Microwave * UV Light Hydrogen * Hydrogen Electronics * Electrical Equipment * High Voltage Other * Other Class 3 - High Temperatures Applicability The hazard controls...

357

Hydro-Climatological Trends in the Continental United States, 1948-88  

Science Conference Proceedings (OSTI)

Spatial patterns in trends of four monthly variables: average temperature, precipitation, streamflow, and average of the daily temperature range were examined for the continental United States for the period 1948–88. The data used are a subset of ...

Dennis P. Lettenmaier; Eric F. Wood; James R. Wallis

1994-04-01T23:59:59.000Z

358

United Nations Foundation (UNF) | Open Energy Information  

Open Energy Info (EERE)

United Nations Foundation (UNF) United Nations Foundation (UNF) Jump to: navigation, search Logo: United Nations Foundation Name United Nations Foundation Address 1800 Massachusetts Avenue NW, Suite 400 Place Washington, DC Zip 20036 Region Northeast - NY NJ CT PA Area Coordinates 38.90879°, -77.042271° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":38.90879,"lon":-77.042271,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

359

Good Energies (United Kingdom) | Open Energy Information  

Open Energy Info (EERE)

United Kingdom) United Kingdom) Name Good Energies (United Kingdom) Address 2-5 Old Bond Street Place London, United Kingdom Zip W1S 4PD Product Global investor in renewable energy and energy efficiency industries Year founded 2001 Phone number +44 20 7659 3300 Website http://www.goodenergies.com/ Coordinates 51.5083291°, -0.1403335° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":51.5083291,"lon":-0.1403335,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

360

SER Temperature Coefficient  

SciTech Connect

Experimentally determine the overall isothermal temperature coefficient of the SER up to the design operating temperatures.

Johnson, J.L.

1959-12-31T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


361

Water heater control module  

DOE Patents (OSTI)

An advanced electric water heater control system that interfaces with a high temperature cut-off thermostat and an upper regulating thermostat. The system includes a control module that is electrically connected to the high-temperature cut-off thermostat and the upper regulating thermostat. The control module includes a switch to open or close the high-temperature cut-off thermostat and the upper regulating thermostat. The control module further includes circuitry configured to control said switch in response to a signal selected from the group of an autonomous signal, a communicated signal, and combinations thereof.

Hammerstrom, Donald J

2013-11-26T23:59:59.000Z

362

Second United Nations  

NLE Websites -- All DOE Office Websites (Extended Search)

Nations Nations . DISCLAIMER This report was prepared a s an account of work sponsored by an agency of the United States Government. Neither t h e United States Government nor any agency thereof, nor any of their employees, make any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof. The views and

363

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

.2/06 WED 17:02 FAX 423 241 3897 OIG .2/06 WED 17:02 FAX 423 241 3897 OIG -** HQ . 001 United States Government Department of Energy Department of Energy memorandum DATE: February 9, 2006 Audit Report Number: OAS-L-06-07 REPLY TO ATTN OF; IG-32 (A050R014) SUBJECT: Audit of "The Department's Management of United States Enrichment Corporation Site Services" TO: Manager, Portsmouth/Paducah Project Office INTRODUCTTON AND OBJECTIVE The Paducah Gaseous Diffusion Plant (Paducah), located in western Kentucky, was constructed by the Department of Energy (Department) in the early 1950s to enrich uranium for use in various military and commercial applications. The Department operated the plant until the Energy Policy Act of 1992 created the United States Enrichment Corporation (USEC) as a Government-owned

364

Efficient Hardware Looping Units for FPGAs  

Science Conference Proceedings (OSTI)

Looping operations impose a significant bottleneck to achieving better computational efficiency for embedded applications. To confront this problem in embedded computation either in the form of programmable processors or FSMD (Finite-State Machine with ... Keywords: FPGA, embedded system, high-level synthesis, hardware looping, control unit

Nikolaos Kavvadias; Konstantinos Masselos

2010-07-01T23:59:59.000Z

365

Beowawe Bottoming Binary Unit - Final Technical Report for EE0002856  

SciTech Connect

This binary plant is the first high-output refrigeration based waste heat recovery cycle in the industry. Its working fluid is environmentally friendly and as such, the permits that would be required with a butane based cycle are not necessary. The unit is modularized, meaning that the unit’s individual skids were assembled in another location and were shipped via truck to the plant site. This project proves the technical feasibility of using low temperature brine The development of the unit led to the realization of low temperature, high output, and environmentally friendly heat recovery systems through domestic research and engineering. The project generates additional renewable energy for Nevada, resulting in cleaner air and reduced carbon dioxide emissions. Royalty and tax payments to governmental agencies will increase, resulting in reduced financial pressure on local entities. The major components of the unit were sourced from American companies, resulting in increased economic activity throughout the country.

McDonald, Dale Edward

2013-02-12T23:59:59.000Z

366

C. Uniform Unit Pricing Regulation  

Science Conference Proceedings (OSTI)

... to permit retail stores that voluntarily provide unit pricing to present prices using various ... with requirements that specify that the unit price is to be ...

2013-10-25T23:59:59.000Z

367

United Biofuels | Open Energy Information  

Open Energy Info (EERE)

United Biofuels Jump to: navigation, search Name United Biofuels Place York, Pennsylvania Product Waste and animal fats to biofuel producer, switched to animal fats from soy in...

368

Exemplary Units Markup Language usage  

Science Conference Proceedings (OSTI)

Sample UnitsML tools and usage. ... Its usage is limited to demonstrating capabilities of plain XSLT processing with the data stored in UnitsML. ...

369

United States lubricant demand  

Science Conference Proceedings (OSTI)

This paper examines United States Lubricant Demand for Automotive and Industrial Lubricants by year from 1978 to 1992 and 1997. Projected total United States Lubricant Demand for 1988 is 2,725 million (or MM) gallons. Automotive oils are expected to account for 1,469MM gallons or (53.9%), greases 59MM gallons (or 2.2%), and Industrial oils will account for the remaining 1,197MM gallons (or 43.9%) in 1988. This proportional relationship between Automotive and Industrial is projected to remain relatively constant until 1992 and out to 1997. Projections for individual years between 1978 to 1992 and 1997 are summarized.

Solomon, L.K.; Pruitt, P.R.

1988-01-01T23:59:59.000Z

370

The Effect of Carbide Morphologies on Elevated Temperature ...  

Science Conference Proceedings (OSTI)

temperature control. Fatigue conditions were as follows: Load control. T = 850oC. ?? = 690 MPa ..... Instrumentation Center (MAIC) at the University of Florida for.

371

Solving Unit Commitment by a Unit Decommitment Method  

E-Print Network (OSTI)

demand, and operating constraints such as spinning reserve requirements, over a short time horizon of power unit i is generating in time period t pmin i pmax i : minimum maximum rated capacity of unit i rmax i : maximum reserve for unit i ripit : reserve available from unit i in time period t minrmax i

372

COOPERATIVE RESEARCH UNITS2009  

E-Print Network (OSTI)

. The CRU program expects to continue to work with cooperators in identify- ing high priority hiring actions Cooperators' Coalition (NCC) for the CRU program, which targets efforts in CRU to (i) find new ways to workCOOPERATIVE RESEARCH UNITS2009 Year In Review PROGRAM YEAR IN REVIEW In Fiscal Year (FY) 2009

373

Optimal Design of Remote Terminal Unit (RTU) for Wireless SCADA System for Energy Management  

Science Conference Proceedings (OSTI)

For energy deficit countries, the design of Supervisory Control and Data Acquisition (SCADA) based energy management systems for optimal distribution is of high interest. Such design involves development of Remote Terminal Unit (RTU) which is considered ... Keywords: Field Programmable Gate Array (FPGA), Programmable Logic Controller (PLC), Remote Terminal Unit (RTU), Supervisory Control and Data Acquisition (SCADA), Tele-Control Interface (TCI), Wireless Communication

Muhammad Aamir; Javier Poncela; Muhammad Aslam Uqaili; B. S. Chowdhry; Nishat Ahmad Khan

2013-04-01T23:59:59.000Z

374

Performance of Gas-Engine Driven Heat Pump Unit  

SciTech Connect

Air-conditioning (cooling) for buildings is the single largest use of electricity in the United States (U.S.). This drives summer peak electric demand in much of the U.S. Improved air-conditioning technology thus has the greatest potential impact on the electric grid compared to other technologies that use electricity. Thermally-activated technologies (TAT), such as natural gas engine-driven heat pumps (GHP), can provide overall peak load reduction and electric grid relief for summer peak demand. GHP offers an attractive opportunity for commercial building owners to reduce electric demand charges and operating expenses. Engine-driven systems have several potential advantages over conventional single-speed or single-capacity electric motor-driven units. Among them are variable speed operation, high part load efficiency, high temperature waste heat recovery from the engine, and reduced annual operating costs (SCGC 1998). Although gas engine-driven systems have been in use since the 1960s, current research is resulting in better performance, lower maintenance requirements, and longer operating lifetimes. Gas engine-driven systems are typically more expensive to purchase than comparable electric motor-driven systems, but they typically cost less to operate, especially for commercial building applications. Operating cost savings for commercial applications are primarily driven by electric demand charges. GHP operating costs are dominated by fuel costs, but also include maintenance costs. The reliability of gas cooling equipment has improved in the last few years and maintenance requirements have decreased (SCGC 1998, Yahagi et al. 2006). Another advantage of the GHP over electric motor-driven is the ability to use the heat rejected from the engine during heating operation. The recovered heat can be used to supplement the vapor compression cycle during heating or to supply other process loads, such as water heating. The use of the engine waste heat results in greater operating efficiency compared to conventional electric motor-driven units (SCGC 1998). In Japan, many hundreds of thousands of natural gas-driven heat pumps have been sold (typically 40,000 systems annually) (Yahagi et al. 2006). The goal of this program is to develop dependable and energy efficient GHPs suitable for U.S. commercial rooftop applications (the single largest commercial product segment). This study describes the laboratory performance evaluation of an integrated 10-ton GHP rooftop unit (a 900cc Daihatsu-Aisin natural gas engine) which uses R410A as the refrigerant (GEDAC No.23). ORNL Thermally-Activated Heat Pump (TAHP) Environmental Chambers were used to evaluate this unit in a controlled laboratory environment.

Abdi Zaltash; Randy Linkous; Randall Wetherington; Patrick Geoghegan; Ed Vineyard; Isaac Mahderekal; Robert Gaylord

2008-09-30T23:59:59.000Z

375

CDIAC Temperature Data Sets  

NLE Websites -- All DOE Office Websites (Extended Search)

Temperature CDIAC Climate Holdings Containing Temperature Data Global Data Sets Data Set Name Investigators Data TypeFormat Period of Record NASA GISS Surface Temperature...

376

High Temperatures & Electricity Demand  

E-Print Network (OSTI)

High Temperatures & Electricity Demand An Assessment of Supply Adequacy in California Trends.......................................................................................................1 HIGH TEMPERATURES AND ELECTRICITY DEMAND.....................................................................................................................7 SECTION I: HIGH TEMPERATURES AND ELECTRICITY DEMAND ..........................9 BACKGROUND

377

SciTech Connect: "high temperature superconductivity"  

Office of Scientific and Technical Information (OSTI)

high temperature superconductivity" Find high temperature superconductivity" Find How should I search Scitech Connect ... Basic or Advanced? Basic Search Advanced × Advanced Search Options Full Text: Bibliographic Data: Creator / Author: Name Name ORCID Title: Subject: Identifier Numbers: Research Org.: Sponsoring Org.: Site: All Alaska Power Administration, Juneau, Alaska (United States) Albany Research Center (ARC), Albany, OR (United States) Albuquerque Complex - NNSA Albuquerque Operations Office, Albuquerque, NM (United States) Amarillo National Resource Center for Plutonium, Amarillo, TX (United States) Ames Laboratory (AMES), Ames, IA (United States) Argonne National Laboratory (ANL), Argonne, IL (United States) Argonne National Laboratory-Advanced Photon Source (United States) Atlanta Regional Office,

378

Essentials of the SI: Base & derived units  

Science Conference Proceedings (OSTI)

... Table 1. SI base units. SI base unit. Base quantity, Name, Symbol. length, meter, m. ... Table 2. Examples of SI derived units. SI derived unit. ...

379

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

ng ng United States Government Department of Energy Memorandum OFFICE OF INSPECTOR GENERAL DATE: APR 18 2003 REPLY TO ATTN OF: IG-34 (A02PR010) Audit Report No.: OAS-L-03-15 SUBJECT: Audit of the Weatherization Assistance Program TO: Director, Weatherization and Intergovernmental Program, EE-2K The purpose of this report is to inform you of the results of our audit of the Weatherization Assistance Program. INTRODUCTION AND OBJECTIVE The Weatherization Assistance Program (Program) was established to increase energy efficiency in dwellings owned or occupied by low-income persons to reduce their residential energy expenditures and improve their health and safety. Since its inception in 1976, the Program has reported that approximately 5 million dwelling units owned or occupied by low-income individuals have been weatherized.

380

United States Government Department  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

OE r 1325.0 OE r 1325.0 (01.93) United States Government Department of memorandum DATE: March 23, 2006 Audit Report Number: OAS-L-06-09 REPLY TO ATTN OF: IG-32 (A060R040) SUBJECT: Audit of"The Department of Energy's Management of the Northeast Home Heating Oil Reserve" TO, Deputy Assistant Secrctary for Petroleum Reserves INTRODUCTION AND OBJECTIVE The Energy Act of 2000 authorized the Secretary of Energy to create a Northeast Home Heating Oil Reserve (Reserve). The Reserve was established as an "emergency buffer" to supplement commercial supplies should a severe supply disruption occur in the heavily heating oil-dependent northeast United States. The Reserve consists of 2 million barrels of emergency home heating oil, enough to provide Northeast consumers adequate supplies for approximately

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


381

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

United States Government United States Government Department of Energy Memorandum DATE: July 29, 2005 REPLY TO ATTN TO: IG-34 (A05HQ002) Audit Report No. OAS-L-05-10 SUBJECT: Agreed-Upon Procedures for Federal Payroll TO: Director, Office of Management, Budget, and Evaluation/Chief Financial Officer, ME-1 INTRODUCTION AND OBJECTIVE The Office of Management and Budget (OMB) Bulletin No. 01-02, "Audit Requirements for Federal Financial Statement," dated October 16, 2000, requires an annual audit of civilian payroll of executive departments and other Government agencies. Auditors are required to follow the agreed-upon procedures in Appendix I-1 of OMB Bulletin No. 01-02, to assess the reasonableness of life insurance, health benefits, and retirement withholdings and contributions.

382

UNITED STATES GOVERNMENT  

Office of Legacy Management (LM)

Menxmmhmz 9 Menxmmhmz 9 1 / UNITED STATES GOVERNMENT i TO : ThcFFles . mx.f I A. B. Piccct, +3lation section : DATE: .@.eti 16, 1949 SUBJECT: VISIT To HAVY OFfDHAlfCE DEPOT, EARIZ, B.J. FmmlTo ,sYmOL: DH:ARP . . : OnJuly 8,&g the uriterattendedameeting at the Navy Oxdnce Depot at Farle, Ii. J. for the purpose of advising the navy on i-adlatlon hazards involved In the dmping of contadnated AEC wastes at /?ea. " Presint were: J. Cook - Traffic & Transportation, AEC ~J.Moren- Utilifation, AEC ..J. Ccnmigl.io - Chief of Middlesex Operaticns A. PIhot -~Hadiation Section, AEC Captain Blossoin - Navy Captain hall - Navy ThefoSkndngwas agreedupcmby AFC andthe l&v. 1. 2. 3. 4. Contaminatedmaterial dnmied, I (loose in case of large contaminated units) loaded on truck&and lsonltored at'

383

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

uv /uu/u* ±.u.. J.OJ..L rAA , *. . uv /uu/u* ±.u.. J.OJ..L rAA , *. . 'A4 .. ± OO, I U444 flmI I.j102 ' -f- $I)002 EP<.1 (o-.vu) United States Government Department of Energy memorandum DATE: January 30, 2004 REP.YTO: IG-35 (A03DN039) Audit Report No.: OAS-L-04-10 SUBJECT: Audit of the Safeguards and Security Program at the Rocky Flats Environmental Technology Site To: Frazer Lockhart, Manager, Rocky Flats Field Office INTRODUCTION AND OBJECTIVE Because of the terrorist attacks against the United States on September 11, 2001, the Department of Energy (Department) instituted additional security requirements beyond those already in place for normal security operations. These "Security Conditions" requirements were established by Department Notice 473.8 (Notice). The requirements are based on

384

United States Environmental Monitoring  

Office of Legacy Management (LM)

EPA 60014-91/030 EPA 60014-91/030 Environmental Protection Systems Laboratory DOE/DP00539-063 Agency P.O. Box 93478 Las Vegas NV 891 93-3478 Research and Development Offsite Environmental Monitoring Report: 1 - 3 5 Radiation Monitorina Around * / (- P 7 1 United States ~ u c l g a r Test Areas Calendar Year 1990 This page intentionally left blank EPN60014-90 DOWDP Offsite Environmental Monitoring Report: Radiation Monitoring Around United States Nuclear Test Areas, Calendar Year 1990 Contributors: D.J. Chaloud, B.B. Dicey, D.G. Easterly, C.A. Fontana, R.W. Holloway, A.A. Mullen, V.E. Niemann, W.G. Phillips, D.D. Smith, N.R. Sunderland, D.J. Thome, and Nuclear Radiation Assessment Division Prepared for: U.S. Department of Energy under Interagency Agreement Number DE-A108-86-NV10522

385

l UNITED STATES GOVERNMENT  

Office of Legacy Management (LM)

UNITED STATES GOVERNMENT UNITED STATES GOVERNMENT lb 15 SUBJECT: THORFJM PROCURENENT PMF'N:TBU Jesse C. Johnson, Gtnager of IRaw Materials Operations3s.Office 3 R. W. Cook, Director of Production ~',LL:::+ I--- DATE: MAR ! 9 1951 The following list of suppliers of thorium and the amounts of materials procured from them by the Mew York Operations Office during calendar year 1950 is being supplied in accordance with Mr. Spelmanls telephone request of March 19. Thorium Lannett Bleachery iinde Air Products Co. Lindsey Light & Chemical Co. lliscellaneous NY0 Liscensing Division Rare Earths, Inc. Wolff-Alport Total - (kilograms) 179 38,2;2 -3 4,210 /vyeoi 4 -q- 2 : i ' \ iti 1 i 0 ;;\I:' --' I F 10 i;;;?/ \ --' L & ;:I :,- :,j( EZi 5 1 :' -I I ri _ I ' R i; .- . )- .i

386

Thermal insulated glazing unit  

SciTech Connect

An improved insulated glazing unit is provided which can attain about R5 to about R10 thermal performance at the center of the glass while having dimensions about the same as those of a conventional double glazed insulated glazing unit. An outer glazing and inner glazing are sealed to a spacer to form a gas impermeable space. One or more rigid, non-structural glazings are attached to the inside of the spacer to divide the space between the inner and outer glazings to provide insulating gaps between glazings of from about 0.20 inches to about 0.40 inches. One or more glazing surfaces facing each thermal gap are coated with a low emissivity coating. Finally, the thermal gaps are filled with a low conductance gas such as krypton gas.

Selkowitz, Stephen E. (Piedmont, CA); Arasteh, Dariush K. (Oakland, CA); Hartmann, John L. (Seattle, WA)

1991-01-01T23:59:59.000Z

387

Thermal insulated glazing unit  

DOE Patents (OSTI)

An improved insulated glazing unit is provided which can attain about R5 to about R10 thermal performance at the center of the glass while having dimensions about the same as those of a conventional double glazed insulated glazing unit. An outer glazing and inner glazing are sealed to a spacer to form a gas impermeable space. One or more rigid, non-structural glazings are attached to the inside of the spacer to divide the space between the inner and outer glazings to provide insulating gaps between glazings of from about 0.20 inches to about 0.40 inches. One or more glazing surfaces facing each thermal gap are coated with a low emissivity coating. Finally, the thermal gaps are filled with a low conductance gas such as krypton gas. 2 figs.

Selkowitz, S.E.; Arasteh, D.K.; Hartmann, J.L.

1988-04-05T23:59:59.000Z

388

Laser system preset unit  

DOE Patents (OSTI)

An electronic circuit is provided which may be used to preset a digital display unit of a Zeeman-effect layer interferometer system which derives distance measurements by comparing a reference signal to a Doppler signal generated at the output of the interferometer laser head. The circuit presets dimensional offsets in the interferometer digital display by electronically inducing a variation in either the Doppler signal or the reference signal, depending upon the direction of the offset, to achieve the desired display preset.

Goodwin, William L. (Knoxville, TN)

1977-01-01T23:59:59.000Z

389

Hoechst plans Mexican unit  

SciTech Connect

Hoechst is considering plans to build its first ethoxylates project in Mexico, Mark Sijthoff, head of surfactants and auxiliaries for Hoechst`s specialty chemical business unit, tells CW. The company expects to make a decision on the 30,000-m.t./year project by the end of the year. Sijthoff would not disclose the site or where ethylene oxide (EO) feed would be obtained. The plan may depend on results of the privatization of Petroleos Mexicanos (Pemex), which is the only producer of EO in Mexico. Hoechst is part of a consortium bidding on the privatization. Sources say the unit will be built at Quimica Hoechst`s Coatzacoalcos site, close to Pemex`s EO plants at Cangregera and Morelos. A planned EO expansion at Morelos will probably move ahead when the sell-off is completed. Sijthoff says that Hoechst is also looking at improving its US surfactants position, although the company has no plans to expand ethoxylates, as there is {open_quotes}plenty of capacity.{close_quotes} Hoechst started up a 150-million lbs/year plant at Clear Lake, TX last year, ending a tolling agreement with Union Carbide. In addition, Rhone-Poulenc recently started a unit at Marcus Hook, PA, and Condea Vista is doubling its ethoxylation capacity at Lake Charles, LA. Meanwhile, Hoechst is still considering construction of 30,000-m.t./year ethoxylation plant in India or China. A decision is expected later this year.

Wood, A.; Alperowicz, N.

1996-05-22T23:59:59.000Z

390

Adaptive Fuzzy PID Control for Boiler Deaerator  

Science Conference Proceedings (OSTI)

The boiler deaerator temperature control system is a non-linear, time-varying, delay control process. It can not achieve satisfying effect using traditional control algorithm to control deaerator water temperature, the paper proposes an adaptive fuzzy ... Keywords: Deaerator, Adaptive, Fuzzy control, PID control

Lei Jinli

2012-08-01T23:59:59.000Z

391

Materials Reliability Program: Effects of Dissolved Hydrogen, Temperature, and Hydrogen Peroxide on Low Temperature Crack Propagation (LTCP) Fracture Resistance of Weld Metals 182, 52, and 152 (MRP-209)  

Science Conference Proceedings (OSTI)

Primary Water Stress Corrosion Cracking (PWSCC) of Alloy 600 nozzles and its weld metals 182 and 82 was first experienced domestically in control rod drive mechanisms at Oconee units and in reactor vessel hot leg nozzles at V.C. Summer station. Publications by Bettis Laboratory have shown nickel-base alloys X-750 and 690 and weld metals 82 and 52 to be susceptible to a reduction in fracture resistance thought to be due to a hydrogen cracking mechanism called low temperature crack propagation (LTCP). Thes...

2007-12-13T23:59:59.000Z

392

Mathematical structure of unit systems  

E-Print Network (OSTI)

We investigate the mathematical structure of unit systems and the relations between them. Looking over the entire set of unit systems, we can find a mathematical structure that is called preorder (or quasi-order). For some pair of unit systems, there exists a relation of preorder such that one unit system is transferable to the other unit system. The transfer (or conversion) is possible only when all of the quantities distinguishable in the latter system are always distinguishable in the former system. By utilizing this structure, we can systematically compare the representations in different unit systems. Especially, the equivalence class of unit systems (EUS) plays an important role because the representations of physical quantities and equations are of the same form in unit systems belonging to an EUS. The dimension of quantities is uniquely defined in each EUS. The EUS's form a partially ordered set. Using these mathematical structures, unit systems and EUS's are systematically classified and organized as a hierarchical tree.

Masao Kitano

2013-05-04T23:59:59.000Z

393

Heater/cooler unit  

SciTech Connect

Air conditioning apparatus especially adapted for cooling adjacent rooms in a motel, hotel, hospital or like structure is described comprising: a first evaporator disposed in one room; a second evaporator disposed in an adjacent room; a condenser disposed outside the rooms but in fluid communication with both the first and second evaporators; a compressor disposed outside the rooms but in fluid communication with the condenser and with a return side of the first and second evaporators; control means for controlling the fluid flow through each evaporator, the control means permitting fluid flow through the first evaporator to be controlled independently of fluid flow through the second evaporator; and a housing exposed to the atmosphere through the exterior wall of the structure and forming a portion of the common interior wall of the rooms, the evaporators, condenser, compressor, and control means being disposed within the housing.

Mintz, A.

1988-01-26T23:59:59.000Z

394

MODULAR CORE UNITS FOR A NEUTRONIC REACTOR  

DOE Patents (OSTI)

A modular core unit for use in a nuclear reactor is described. Many identical core modules can be placed next to each other to make up a complete core. Such a module includes a cylinder of moderator material surrounding a fuel- containing re-entrant coolant channel. The re-entrant channel provides for the circulation of coolant such as liquid sodium from one end of the core unit, through the fuel region, and back out through the same end as it entered. Thermal insulation surrounds the moderator exterior wall inducing heat to travel inwardly to the coolant channel. Spaces between units may be used to accommodate control rods and support structure, which may be cooled by a secondary gas coolant, independently of the main coolant. (AEC)

Gage, J.F. Jr.; Sherer, D.B.

1964-04-01T23:59:59.000Z

395

Temperature Profile Measurements in a Newly Constructed 30-Stage 5 cm Centrifugal Contactor pilot Plant  

Science Conference Proceedings (OSTI)

An annular centrifugal contactor pilot plant incorporating 30 stages of commercial 5 cm CINC V-02 units has been built and operated at INL during the past year. The pilot plant includes an automated process control and data acquisitioning system. The primary purpose of the pilot plant is to evaluate the performance of a large number of inter-connected centrifugal contactors and obtain temperature profile measurements within a 30-stage cascade. Additional solvent extraction flowsheet testing using stable surrogates is also being considered. Preliminary hydraulic testing was conducted with all 30 contactors interconnected for continuous counter-current flow. Hydraulic performance and system operational tests were conducted successfully but with higher single-stage rotor speeds found necessary to maintain steady interstage flow at flowrates of 1 L/min and higher. Initial temperature profile measurements were also completed in this configuration studying the performance during single aqueous and two-phase counter-current flow at ambient and elevated inlet solution temperatures. Temperature profile testing of two discreet sections of the cascade required additional feed and discharge connections. Lamp oil, a commercially available alkane mixture of C14 to C18 chains, and tap water adjusted to pH 2 were the solution feeds for all the testing described in this report. Numerous temperature profiles were completed using a newly constructed 30-stage centrifugal contactor pilot plant. The automated process control and data acquisition system worked very well throughout testing. Temperature data profiles for an array of total flowrates (FT) and contactor rpm values for both single-phase and two-phase systems have been collected with selected profiles and comparisons reported. Total flowrates (FT) ranged from 0.5-1.4 L/min with rotor speeds from 3500-4000 rpm. Solution inlet temperatures ranging from ambient up to 50° C were tested. Ambient temperature testing shows that a small amount of heat is added to the processed solution by the mechanical energy of the contactors. The temperature profiles match the ambient temperature of the laboratory but are nearly 10° C higher toward the middle of the cascade. Heated input solution testing provides temperature profiles with smaller temperature gradients and are more influenced by the temperature of the inlet solutions than the ambient laboratory temperature. The temperature effects of solution mixing, even at 4000 rpm, were insignificant in any of the studies conducted on lamp oil and water.

Troy G. Garn; Dave H. Meikrantz; Mitchell R. Greenhalgh; Jack D. Law

2008-09-01T23:59:59.000Z

396

United States of Agriculture  

E-Print Network (OSTI)

depend on vari- ous factors: engine temperature and load, aftertreatment de- vices and dilution-11545-2010 © Author(s) 2010. CC Attribution 3.0 License. Atmospheric Chemistry and Physics Impact of aftertreatment aftertreatment systems. One vehicle lacked exhaust aftertreatment devices, one ve- hicle was equipped

397

HVDC control system based on parallel digital signal processors  

Science Conference Proceedings (OSTI)

A numerical HVDC control system operating in real time has been developed for a simulator to be used for operator training. The control system, implemented with digital signal processors (DSPs), consists of typical HVDC control functions such as the synchronizing unit, the regulation unit, the protection unit, the firing unit, the tap changer and the reactive power regulation unit. Results from the steady-state and the transient performance validation tests carried out on the IREQ power system simulator are provided.

Maharsi, Y.; Do, V.Q.; Sood, V.K.; Casoria, S.; Belanger, J. [Hydro-Quebec, Varennes, Quebec (Canada)

1995-05-01T23:59:59.000Z

398

High temperature electronic gain device  

SciTech Connect

An integrated thermionic device suitable for use in high temperature, high radiation environments. Cathode and control electrodes are deposited on a first substrate facing an anode on a second substrate. The substrates are sealed to a refractory wall and evacuated to form an integrated triode vacuum tube.

McCormick, J. Byron (Los Alamos, NM); Depp, Steven W. (Los Alamos, NM); Hamilton, Douglas J. (Tucson, AZ); Kerwin, William J. (Tucson, AZ)

1979-01-01T23:59:59.000Z

399

United States of America  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

as a stand-alone, transmission-only company owns controls and operates more than 9,350 miles of transmission lines in the states of Wisconsin, Illinois, Minnesota and Michigan....

400

" Million U.S. Housing Units"  

U.S. Energy Information Administration (EIA) Indexed Site

3 Lighting Usage Indicators by Type of Housing Unit, 2005" " Million U.S. Housing Units" ,,"Type of Housing Unit" ,"Housing Units (millions)","Single-Family Units",,"Apartments in...

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


401

Million U.S. Housing Units Total...............................  

U.S. Energy Information Administration (EIA) Indexed Site

Attached 2 to 4 Units Table HC2.12 Home Electronics Usage Indicators by Type of Housing Unit, 2005 5 or More Units Mobile Homes Type of Housing Unit Housing Units (millions)...

402

Current Name Academic Unit Request  

E-Print Network (OSTI)

Current Name Academic Unit Request Department/College/School/Institute/Center Names: New or Changes This form is to be used to request new academic units (departments, colleges, schools, institutes, or centers) or to request changes to existing academic units. Complete the following and submit

Hart, Gus

403

Phasor Measurement Unit (PMU) Implementation and Applications  

Science Conference Proceedings (OSTI)

The effective operation of power systems in the present and the future depends to a large extent on how well the emerging challenges are met today. Power systems continue to be stressed as they are operated in many instances at or near their full capacities. In order to keep power systems operating securely and economically, it is necessary to further improve power and control system protection. Synchronized phasor measurements8212also known as phasor measurement units (PMUs)8212are ideal for monitoring ...

2007-10-31T23:59:59.000Z

404

Megnetic Field Based Phasor Measurement Unit (PMU)  

Science Conference Proceedings (OSTI)

Synchronous phasor measurements are critical for the wide area monitoring and control of a large interconnected power system. However, only a small number of Phasor Measurement Units (PMUs) have been installed in the North America, mostly because of the large installation and maintenance costs of a classical PMU that uses current transformers (CT) to obtain current signal and potential transformers (PT) to obtain voltage input signals. The classical PMUs use technology developed more than 20 years ago. I...

2009-03-31T23:59:59.000Z

405

Geothermal resources of the eastern United States  

DOE Green Energy (OSTI)

The resouces considered are exclusively hydrothermal, and the study was confined to the 35 states east of the Rocky Mountains, excluding the Dakotas. Resource definition in these areas is based entirely on data found in the literature and in the files of a number of state geological offices. The general geology of the eastern United States is outlined. Since the presence of geothermal resources in an area is governed by the area's geology, an attempt to define useful geothermal resources is facilitated by an understanding of the geology of the area being studied. Six relatively homogeneous eastern geologic regions are discussed. The known occurrences of geothermal energy in the eastern United States fall into four categories: warm spring systems, radioactive granite plutons beneath thick sediment covers, abnormally warm aquifers, and deep sedimentary basins with normal temperature gradients.

Renner, J.L.; Vaught, T.L.

1979-12-01T23:59:59.000Z

406

United Nations Environment Programme (UNEP) | Open Energy Information  

Open Energy Info (EERE)

United Nations Environment Programme (UNEP) United Nations Environment Programme (UNEP) (Redirected from United Nations Environment Programme) Jump to: navigation, search Logo: United Nations Environment Programme Name United Nations Environment Programme Address United Nations Avenue, Gigiri PO Box 30552, 00100 Place Nairobi, Kenya Phone number (254-20) 7621234 Coordinates -1.23224986037°, 36.815630436° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":-1.23224986037,"lon":36.815630436,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

407

High temperature interfacial superconductivity  

DOE Patents (OSTI)

High-temperature superconductivity confined to nanometer-scale interfaces has been a long standing goal because of potential applications in electronic devices. The spontaneous formation of a superconducting interface in bilayers consisting of an insulator (La.sub.2CuO.sub.4) and a metal (La.sub.1-xSr.sub.xCuO.sub.4), neither of which is superconducting per se, is described. Depending upon the layering sequence of the bilayers, T.sub.c may be either .about.15 K or .about.30 K. This highly robust phenomenon is confined to within 2-3 nm around the interface. After exposing the bilayer to ozone, T.sub.c exceeds 50 K and this enhanced superconductivity is also shown to originate from a 1 to 2 unit cell thick interfacial layer. The results demonstrate that engineering artificial heterostructures provides a novel, unconventional way to fabricate stable, quasi two-dimensional high T.sub.c phases and to significantly enhance superconducting properties in other superconductors. The superconducting interface may be implemented, for example, in SIS tunnel junctions or a SuFET.

Bozovic, Ivan (Mount Sinai, NY); Logvenov, Gennady (Port Jefferson Station, NY); Gozar, Adrian Mihai (Port Jefferson, NY)

2012-06-19T23:59:59.000Z

408

Gridpoint Predictions of High Temperature from a Mesoscale Model  

Science Conference Proceedings (OSTI)

Mesoscale model gridpoint temperature data from simulations in the southwestern United States during the summer of 1990 are compared with both observations and statistical guidance from large-scale models over a 32-day period. Although the raw ...

David J. Stensrud; Jon A. Skindlov

1996-03-01T23:59:59.000Z

409

A Method to Detect Inhomogeneities in Historical Dewpoint Temperature Series  

Science Conference Proceedings (OSTI)

Hourly dewpoint temperature data for the 1951–2006 period at 10 stations in the contiguous United States were investigated to determine if inhomogeneities in their records could be detected. At least three instrument changes are known to have ...

Paula J. Brown; Arthur T. DeGaetano

2009-11-01T23:59:59.000Z

410

Consensus Clustering of U.S. Temperature and Precipitation Data  

Science Conference Proceedings (OSTI)

A “consensus clustering” strategy is applied to long-term temperature and precipitation time series data for the purpose of delineating climate zones of the conterminous United States in a “data-driven” (as opposed to “rule-driven”) fashion. ...

Robert G. Fovell

1997-06-01T23:59:59.000Z

411

Verti Jack Pumping Unit evaluation  

Science Conference Proceedings (OSTI)

The Verti Jack Pumping Unit was tested primarily to establish the energy comsumption efficiency of the unit as compared with that of conventional pumping unit. Before the unit was field tested, extensive static testing was performed to determine the effect of the counterbalance system throughout the operational cycle. The field test included comparing the performance of the Verti Jack Unit and conventional pump jacks - a Bethlehem 16 and Cabot 25 pumping unit. The Verti Jack unit was operated at four different pumping conditions. The Verti Jack unit peformed satisfactorily during the testing. Only minor problems that could not be attributed to the design or operation of the unit were encountered. Changing the stroke length was difficult in the field, but such operational problems were expected in operating the first phototype and can be corrected on future models. During the higher pumping rate tests of the Verti Jack unit, the well ceased to deliver fluid quantities at rates adequate to the pumping rate. These data are shown in table 8. Therefore, evaluation data are based on theoretical pump performance and are presented in table 9. The data show that the Verti Jack is more efficient than the conventional units tested. The most direct comparison was the Verti Jack test at 36-inch stroke and 12 1/2 strokes per minute versus the Cabot unit at 37-inch stroke and 12 strokes per minute. In the comparison the Verti Jack operated about 24 percent more efficiently than the Cabot unit. Comparing the summation of all Verti Jack tests with that of all conventional unit tests, the Verti Jack operated about 15 percent more efficiently. Compared to the Cabot unit only, the Verti Jack was about 17 percent more energy efficient. 13 figs., 12 tabs.

Porter, R.; Spence, K.

1985-11-01T23:59:59.000Z

412

NETL: Combined Pressure, Temperature Contrast, and Surface-Enhanced  

NLE Websites -- All DOE Office Websites (Extended Search)

IEP – Post-Combustion CO2 Emissions Control Combined Pressure, Temperature Contrast, and Surface-Enhanced Separation of Carbon Dioxide (CO2) for Post-Combustion Carbon Capture Project No.: DE-FE0007531 Rice University is investigating CO2-capture cost-reduction opportunities by developing a novel gas absorption process. Specific project research topics include the following: Combining the absorber and stripper columns into a single, integrated unit. The use of vacuum stripping in combination with waste heatfor regeneration of carbon dioxide (CO2) absorbent. The use of a very high surface area ceramic foam gas-liquid contactor for enhanced mass transfer. Preparing surfaces of the ceramic foam gas-liquid contactor with basic and acidic functional groups to enhance mass transfer during gas absorption and stripping, respectively.

413

,. United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

i. 001 i. 001 DOE F 1325.8 (8-89) EFG (07-90) ,. United States Government Department of Energy memorandum DATE: September 11, 2003 REPLYTO: IG-34 (A03NE045) Audit Report No.: OAS-L-03-20 SUBJECT: Audit of Procurement Administration at the Oak Ridge National Laboratory TO: Director, Office of Management, Budget and Evaluation/Chief Financial Officer, ME-1 The purpose of this report is to inform you of the results of our survey of procurement administration at the Oak Ridge National Laboratory (Laboratory). This review was initiated in May 2003 and fieldwork was conducted through August 2003. Our review methodology is described in an attachment to this report. INTRODUCTION AND OBJECTIVE In Fiscal Year (FY) 2002, the Department of Energy's (Department) management contractors procured approximately $6.4 billion worth of goods and services from

414

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

31/07 THU 18:20 FAX 865 241 3897 OIG --- HQ 31/07 THU 18:20 FAX 865 241 3897 OIG --- HQ 00 DOE F 1325.8 (08&93) United States Government Department of Energy memorandum DATE: May 31, 2007 Audit Report Number: OAS-L-07-13 REPLY TO ATTN OF: IG-32 (A07RL048) SUBJECT: Audit of Safety Allegations Related to the Waste Treatment Plant at the Hanford Site TO: Manager, Office of River Protection INTRODUCTION AND OBJECTIVE The Department of Energy's (Department) Hanford Site is responsible for treating and preparing 53 million gallons of radioactive and chemically hazardous waste for disposal. Bechtel National, Inc. (Bechtel) is designing, building and commissioning the Waste Treatment Plant (Plant), a category II nuclear facility, which is comprised of a complex of treatment facilities to vitrify and immobilize radioactive waste into a

415

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

OEF 1325.8 OEF 1325.8 (U8-93) United States Government Department of Energy memorandum DATE: April 11, 2007 Audit Report Number: OAS-L-07-I1 REPLY TO ATTN OF: IG-32 (A07DN056) SUSJECT: Audit of the Department of Energy's Community and Regulatory Support Funding at the Richland Operations Office TO: Manager, Richland Operations Office INTRODUCTION AND OBJECTIVE The Department of Energy's (Department) Office of Environmental Management provided $60.1 million in Community and Regulatory Support funding in Fiscal Year (FY) 2005 to a number of Departm- nt sites. The funding is intended to be used for activities indirectly related to nuclear and hazardous waste cleanup, such as agreements with state regulatory agencies and transportation departments. During FY 2005, the Department's Richland

416

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

a . a . r-z . "*& ., . .. uoi UA o. --.- flI gj UUX DOE F 1325.8 (08.93) United States Government Department of Ene memorandum DATE: August 19, 2004 Audit Report Number: OAS-L-04-18 REPLY TO ATTN OF: IG-36 (A03IF009) SUBJECT: Audit of the "Revised Pit 9 Cleanup Project at the Idaho National Engineering and Environmental Laboratory" TO: Paul Golan, Acting Assistant Secretary, Office of Environmental Management INTRODUCTION AND OBJECTIVE The Idaho National Engineering and Environmental Laboratory's (iNEEL) subsurface disposal area was established in 1952 for disposal of solid radioactive waste and now encompasses an area of approximately 88 acres. Wastes from the INEEL and other Department of Energy (Department) sites, rmost notably Rocky Flats, were buried in

417

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

vu & . vu & . ,I / v a L U ; .8 " ',X v &..'*. "o uu V"x Ijo tf J ,*- , , i 4 w i tiJ U U 1 OEF S.a 135 (0B93) United States Government - Department of Energy memorandum DATE: February 27, 2007 REPLY TO Audit Repor Number: OAS-L-07-08 ATTN OF: IG-32 (A06ID015) SUBJECT: Audit of the "Design of the Engineered Barrier System at the Yucca Mountain Site" TO: Principal Deputy Director, Office of Civilian Radioactive Waste Management INTRODUCTION AND OBJECTrVE In accordance with the Nuclear Waste Policy Act of 1982, the Department of Energy's (Department) Office of Civilian Radioactive Waste Management (OCRWM) is responsible for designing, licensing, constructing, and operating a repository, known as Yucca Mountain, for the permanent disposal of spent nuclear fuel and high-level -

418

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

F 1325.8 F 1325.8 (08-93) United States Government Department of Energy memorandum DATE: August 13, 2007 . . Audit Report Number: OAS-L-07-18 REPLY TO ATTN OF: IG-32 (A07PR061) SUBJECT: Audit of Executive Compensation at Brookhaven National Laboratory TO: Manager, Brookhaven Site Office INTRODUCTION AND OBJECTIVE As part of a Department of Energy-wide audit of executive compensation, we reviewed executive compensation at the Office of Science's Brookhaven National La --- _ .r . . tc. av .... n . Ou audit covered executive cuupoci'A ;is in curred and claimed for Fiscal Years 2003, 2004, and 2005. Brookhaven Science Associates, LLC, operated Brookhaven under Department of Energy (Department) contract number DE-AC02-98CH10886. The amount of executive compensation that can be reimbursed to Department

419

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

')/06 MON 14:28 FAX 423 241 3897 OIG ')/06 MON 14:28 FAX 423 241 3897 OIG --- HQ 1o001 ,O " F 1325.8 (08-93) United States Government Department of Energy memorandum DATE: April 10, 2006 Audit Report No.: OAS-L-06-11 REPLY TO ATTN OF: IG-32 (A05ID043) SUBJECT: Audit of "Contract Transition Activities at the Idaho Operations Office" TO: Manager, Idaho Operations Office INTRODUCTION AND OBJECTIVE The Department of Energy's Idaho Operations Office has ongoing missions focused primarily in the areas of nuclear energy and environmental cleanup. From October 1, 1999 to February 1, 2005, Bechtel BWXT Idaho, LLC (Bechtel) managed facility operations for both of these missions. In Fiscal Year 2005, two separate contracts began in order to add focus and clarity to each respective mission. First, the Idaho National

420

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

-93) -93) United States Government Department of Energy memorandum DATE: July 12, 2007 Audit Report Number: OAS-L-07-15 REPLY TO ATnN OF: IG-32 (A07ID055) SUBJECr: Audit of the Idaho National Laboratory Facility Footprint Reduction TO: Manager, Idaho Operations Office INTRODUCTION AND OBJECTTVE On February 1, 2005, Battelle Energy Alliance, LLC (BEA) assumed responsibility for managing and operating the Idaho National Laboratory (INL) for the Department of Energy (Department) under a new 10 year contract. ThI m.ion for ,the L s to nntance the Nation's energy security by becoming the preeminent, internationally recognized nuclear energy research, development, and demonstration laboratory.. To accomplish this mission, BEA proposed aggressive infrastructure initiatives

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


421

United States Government Departmen  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

7/05 TUE 07:58 FAX 423 241 3897 OIG -** HQ @]002 7/05 TUE 07:58 FAX 423 241 3897 OIG -** HQ @]002 DOE F 1325.8 (08-93) United States Government Departmen of Energy memorandum DATE: December 20, 2005 Audit Report Number: OAS-L-06-03 REPLY TO A1TN OF; IG-36 (A05SR025) SUBJECT: Audit of "Defense Waste Processing Facility Operations at the Savannah River Site" TO: Jeffrey M. Allison, Manager, Savannah River Operations Office INTRODUCTION AND OBJECTIVE The Department of Energy's (Department) Savannah River Site stores approximately 36 million gallons of liquid, high-level radioactive waste in 49 underground waste storage tanks. The contents of the waste tanks are broadly characterized as either "sludge waste" or "salt waste". Sludge waste is insoluble and settles to the bottom of a waste tank, beneath a layer of liquid supernate. Salt

422

* United States Government  

Office of Legacy Management (LM)

-- -- DE;$r,e /q f-j * I3 - I * United States Government memorandum MAY 21 I991 DATE: REPLY TO Al-fN OF: 4ih55YhL Department of Energy JT:,i 5, f&A 0 ' - j4.~, ' -/ jl.a' \ A t -3 __..-_-. EM-421 SUBJECT: Elimination of the American Potash and Chemical Site The File TO: I have reviewed the attached site summary and elimination recommendation for the American Potash and Chemical Company Site in West Hanover, Massachusetts. I have determined that there is little likelihood of radioactive contamination at this site. Based on the above, the American Potash and Chemical Company site is hereby eliminated from further consideration under the Formerly Utilized Sites Remedial Action Program. W. Alexander Williams, PhD Designation and Certification Manager

423

United States Goveinment  

Office of Legacy Management (LM)

,325.B ,325.B jO8.93) United States Goveinment ~~~rntir-andu~rvi Depr?rtnient of Energy \L, IO' " 1' !ATE:' MAY i o 1995 ,' Kzb9. ":cz$ EM-421 (W.,A. Williams, 301-903-8149) SUBJECT: Records for the West Chicago Site .The File TO: After review.of the available r&rds concerning the former 'Lindsay Light and Chemical.Corhpany site in West Chicago, Illinois. I have determined that it is not necessary to transmit Department of Energy (DOE) records to the municipa,llty to inform public officials of the activities at this ~ site. This site has been licgnsed by the Nuclear Regulatory Commission (NRC) for many.years, and the nature of the. rare'earth and thorium production at the site, are well known. Remediation of this faci'lity ii~ being addressed by the current owner, 'the NRC, the U.S; Environmental

424

; United States Government  

Office of Legacy Management (LM)

Don F 1328.8 Don F 1328.8 . . .449J ' Em wm ; United States Government , % - memorandum L c*m Al.)G 2 9 a34 yz;; EM-421 (If. A. Willlams, 427-1719) lq,iMAL Department of Energy m5 MA, \i& SUBJECT: Elimination of the Sites from the Formerly Utllized Sites Remedial A&Ion Prograa ' a The File In 1990, with the assistance of Hr. Doug Tonkay and Ms. Htchelle L&is, I reviewed a number of sites that had fomerly provided goods and/or services to the Fernald faclllty as subcontractors. For 24 of.these sites, recoarwndations were ude to eliainate thm from further consideratton under Formerly Utilized Sites Reaedial Actlon Progrm (FUSRAP). In each case, I made or revlewed the evaluation, and, in each case, a handwritten evaluation was prepared. This is to provide a more

425

UNITED STATES GOVERNMENT  

Office of Legacy Management (LM)

'.... '|le , * f C. '.... '|le , * f C. Office Memorandum · UNITED STATES GOVERNMENT .-- J TO ' Leo Graup, Chief, DATE: September 29, 1958 Property Management Branch rFi0 : M. S. Weinstein Industrial Hygiene Branch, HASL SUBJBT: SURVEY AT HAIST PROPETIY SYMBOL: HSH:MSW. Thisl property was purchased during MED operation and used as a dumping ground for refinery residues generated by Linde Air Products during their period of participation in the refinery operations program. \It 2 consists of 10 acres in addition to a perpetual .ease- ment right to a strip of land, 10 feet wide and 3600 feet long. The area is located in North Tonawanda, New York near the Niagara River. Because of the growth of adjacent industries, this particular piece of property has appreciated in value. During its tenure as responsible property management office, Oak

426

United States Government  

Office of Legacy Management (LM)

OOE F 1325.8 OOE F 1325.8 - EFgzk3) United States Government tiemorandum 0 wt;? -J Department of Energy DATE: SEP 2 5 1992 REPLY TO Al-TN OF: EM-421 (W. A. W illiams, 903-8149) SUBJECT: Authorization for Remedial Action at Diamond Magnesium Site in Painesville, Ohio TO: L. Price, OR The former Diamond Magnesium Company site located at 720 Fairport-Nursery Road in Painesville, Ohio, is designated for remedial action under the Formerly Utilized Sites Remedial Action Program (FUSRAP). The site is owned by Uniroyal Chemical Company and by Lonza Chemical, Incorporated. This designation is based on the results of a radiological survey and conclusions from an authority review as noted in the attached Designation Summary. Copies of the radiological survey reports and the authority

427

United States Government  

Office of Legacy Management (LM)

Z&Et,? y-p . c' Z&Et,? y-p . c' )7q/ I cuq,~ United States Government Department of Energy memoranduin I " . : I ;/ ,I DATE: hufi 2 9 1594 \ ' - y:oTFq M-421 (W. A. Ylllius, 427-1719) ' ii Y - SIJWECT: Elimination of the Sites from the Formerly Utilfzed Sites Remedial Actjon Progru TO The File In 1990, with the assistance of Mr. reviewed a number of sites that had services to the Fernald facility as sites, recommendations were made to ___ _- _ consideration under Formerly Utiltzed Sites Remedial Action Program (FUSRAP). In each case, I made or reviewed the evaluation, and, in each case, a handwritten evaluation was prepared. This is to provide a more formal record of the decision on these sites and to ratify and confirm the prior elimination of each site froa FUSRAP.

428

United States Government  

Office of Legacy Management (LM)

DOE F t325.8 DOE F t325.8 (s8s) Dl? l 36-z EFG (07-90) United States Government m e m o randum Department of Energy DATE: LUG 2 ' 3 1394 ",cl,'," EM-421 (W. A. W illiams, 427-1719) SUBJECT: Elimination of the Sites from the Formerly Utilized Sites Remedial Action Program To' The File In 1990, with the assistance of M r. Doug Tonkay and Ms. M ichelle Landis, I reviewed a number of sites that had formerly provided goods and/or services to the Fernald facility as subcontractors. For 24 of these sites, recoamnendations were aade to eliminate them from further consideration under Formerly Utilized Sites Remedial Action Program (FUSRAP). In each case, I made or reviewed the evaluation, and, in each case, a handwritten evaluation was prepared. This is to provide a more

429

- United States Government  

Office of Legacy Management (LM)

8 8 my EFG (07.90) . - United States Government . * Department of. Energy * inemorandum DATE: DEC :! ;j 1993 REPLY TO ATTN OF: EM-421 (W.'A. W illiams, 903-8149) : NY 41 I .' 41 G I? SUBJECT: Elimination of the T itanium Alloy Manufacturing Co., Niagara Falls, New York TO: The F ile I have reviewed the attached site. summary and elimination recommendation for the T itanium Alloy Manufacturing Company. I have determined that the potential for radiological contamination is low because of the lim ited duration of the activities at the site. Further, at least some of the contractual activities at the site were licensed under the Atomic Energy Act, and the licensed activities are thereby disqualified from further consideration under the Department of Energy's Formerly Utilized Sites

430

United States Government  

Office of Legacy Management (LM)

UOEF 1325.8 UOEF 1325.8 (5831 , - a.. L . . L. . c ,, . . . t ,' <, .* -,. .--1^ a "-2 (J 7 , pe-;L, United States Government memorandum Departmen: of Energy DATEAUG 1 0 1984 REPLY TO Al-fN OF: NE-20 SUBJECT: Action Description Memorandum (ADM) Review: Wayne, New Jersey Proposed 1984 Remedial Actions at TO: File After reviewing all of the pertinent facts including the attached Action Description Memorandum (ADM), I have determined that the remedial action described in the subject ADM is an action which in and of itself will have a clearly insignificant impact on the quality of the human environment within the meaning of the National Environmental Policy Act (NEPA), 42 U.S.C. 4321 et seq. The Conference Report accompanying the Energy and Water Appropriation Act

431

United States Government  

Office of Legacy Management (LM)

I8 891 I8 891 EFG (07.90) United States Government m e m o randum bepartrne% of Energy -P ' ; N. A *I Pi id : DATE: AUG 3, 9 1994 REPLY TO Al-iN OF: EM-421 (W. A. W illiams, 427-1719) r, )' \, ! c ' d, ' t ' 3 ' 2 -L SUBJECT: Elimination of the Sites from the Formerly Utilized Sites Remedial Action Program To' The File In 1990, with the assistance of M r. Doug Tonlsay and Ms. M ichelle Landis, I reviewed a nmber of sites that had formerly provided goods and/or services to the Fernald facility as subcontractors. For 24 of.these sites, recommdations were made to eliminate them from further consideration under Formerly Utilized Sites Remedial Action Program (FUSRAP). In each case, I made or reviewed the evaluation, and, in each case, a handwritten evaluation was prepared. This is to provide a more

432

United States Government  

Office of Legacy Management (LM)

81278 81278 United States Government Department of Energy memorandum - ?71 S.EP 23 F; i: 54 DATE: SEP 1 8 1991 REPLY TO ATTNOF: EM-421 (P. Blom, 3-8148) SUBJECT: Approved Categorical Exclusion for Removal Actions at Elza Gate, Tennessee TO: Lester K. Price, OR Attached is a copy of the approved Categorical Exclusion (CX) for removal of contaminated material at the Elza Gate site in Tennessee. The removal action involves the removal of radioactive contaminated soil and concrete as well as the removal of Polychlorinated Biphenyl (PCB) contaminated soil. This CX was approved by Carol Borgstrom, Office of National Environmental Policy Act Oversight (EH-25), September 9, 1991. Paul F. Blom Off-Site Branch Division of Eastern Area Programs Office of Environmental Restoration

433

United States Government  

Office of Legacy Management (LM)

D;F&g,8 C-r-I 3-3 D;F&g,8 C-r-I 3-3 .*. United States Government . memorandum DATE: JUNZO 1994 -... REPLY TO A?TN OF: EM-421 (W. A. Williams, 903-8149) Authority Determination -- Combustion Engineering Site, Windsor, SUBJECT: Connecticut To' The File The attached review, documents the basis for determining whether the Department of Energy (DOE) has authority for taking remedial action at the Combustion Engineering (CE) Site in Windsor, Connecticut, under the Formerly Utilized Sites Remedial Action Program. CE was a prime contractor for the Atomic Energy Commission (AEC) and performed high-enriched uranium fuel fabrication work from 1955 to 1967. The services furnished at the CE site included some experimental work; however, it primarily consisted of fabrication of high-enriched uranium

434

United States Government  

Office of Legacy Management (LM)

DOEF1325.8 P4 0 * 1 - 1 DOEF1325.8 P4 0 * 1 - 1 - Iq \ b- United States Government memorandum pJ .T\ \b Department of Energy DATE: OCT 9 1984 REPLY TO NE-20 All-N OF: .- Authorizations for Actions Under the Formerly Utilized Sites Remedial Action SUBJECT: Program (FUSRAP) at the St. Louis Airport Storage Site, St. Louis, MO. and the W. R. Grace Site at Curtis Bay, Md. To: J. LaGrone, Manager Oak Ridge Operations Office St. Louis Airport Storage Site, MO The House and Senate Reports for the Energy and Water Development Appropriation Act (P.L. 98-360) directed the Department of Energy "...to take the necessary steps to consolidate and dispose of the waste material from the Latty Avenue site and nearby St. Louis Airport vicinity properties locally, by reacquiring, stabilizing, and using the old 21.7

435

United States Government  

Office of Legacy Management (LM)

ooc F r325.8 ooc F r325.8 imo, EFO ,ww United States Government memorandum Department of Energy -fw?w 81ua DATE: FEB 1 5 1991 l+Ks6 sUsJECT: Elimination of the Buflovak Company Site from FUSRAP ho: The File I have reiiewed the attached preliminary site summary and recommendation for the Buflovak Company site in Buffalo, New York. I have determined that there is little likelihood of contamination at this site. Based on the above, the Buflovak Company site is hereby eliminated from further consideration under the Formerly Utilized Sites Remedial Action Program. W. Alexander Williams Designation and Certification Manager Off-Site Branch Division of Eastern Area Programs Office of Environmental Restoration Attachment - I . b e e : W e s to n E M - 4 0 ( 3 ) E M - 4 2 ( 2 ) W illiams r

436

United States Attorney General  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

93, 5 U.S. Op. Off. Legal Counsel 1, 1981 WL 30865 (U.S.A.G.) 93, 5 U.S. Op. Off. Legal Counsel 1, 1981 WL 30865 (U.S.A.G.) United States Attorney General ***1 *293 January 16, 1981 **1 The President The White House Washington, D.C. 20500 MY DEAR MR. PRESIDENT: You have asked my opinion concerning the scope of currently existing legal and constitutional authorities for the continuance of government functions during a temporary lapse in appropriations, such as the Government sustained on October 1, 1980. As you know, some initial determination concerning the extent of these authorities had to be made in the waning hours of the last fiscal year in order to avoid extreme administrative confusion that might have arisen from Congress' failure timely to enact 11 of the 13 anticipated regular appropriations bills, FN;B1[FN1]FN;F1 or a

437

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

3/02 TUE 08:59 FAX 423 241 3897 OIG *-* HQ 00o2 3/02 TUE 08:59 FAX 423 241 3897 OIG *-* HQ 00o2 DOE F 132,.8 W.I: ((07.9u) United States Government Department of Energy Memorandum DATE: December 2, 2002 REPLY TO REPLY TO -36 (A02SR013) Audit Report No.: OAS-L-03-07 ATTN OF: SUBJECT: Audit of Subcontracting Practices at the Savannah River Site TO: Jeffrey M. Allison, Acting Manager, Savannah River Operations Office INTRODUCTION AND OBJECTIVE The Department of Energy (Department) has contracted with Westinghouse Savannah River Company, LLC (Westinghouse) to manage and operate the Savannah River Site (Savannah River) through September 30, 2006. As of August 2, 2002, Westinghouse had 534 open and active service procurements worth $100,000 or more each, with a total value of about $518 million, that it had awarded since October 1996.

438

United States Goverment  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

6/03 15:37 FAX 301 903 4656 _ CAPITAL REGION * FORS FIVEA 91002/004 6/03 15:37 FAX 301 903 4656 _ CAPITAL REGION * FORS FIVEA 91002/004 DOE-F 1325.8 (68-93) Depament of Energy United States Goverment Department of Energy Memorandum OFFICE OF .NSPECTOR GENERAL DATE: February 26, 2003 REPLY TO ATTN OF: IG-34 (A02CG004) Audit Report No.: OAS-L-03-11 SUBJECT: Audit of the Office of Science Infrastructure Modernization Initiatives TO: Acting Associate Director, Office of Laboratory Operations and Environment, Safety and Health, SC-80 The purpose of this report is to inform you of the results of our audit of the Office of Science's infrastructure modernization initiatives. The audit was performed between May and September 2002 at Departmental Headquarters, Brookhaven National Laboratory, and Argonne National Laboratory. The audit methodology is described in

439

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

w w f.b wr w f k--w .^^- - w w f.b wr w f k--w .^^- - - r - T- - * -* p -ldt - f f - - -J -vv- A n JV DOE F 1325.8 (08-93) United States Government ------- Department of Energy memorandum DATE: June 15, 2006 REPLY TO Audit Report Number: OAS-L-06-15 ATTN OF: IG-32 (A05SR029) SUBJECT Audit of "Storage Capacity of the Iligh Level Waste Tanks at the Savannah River TO: Manager, Savannah River Operations Office INTRODUCTION AND OBJECTIVE The Savannah River Site in South Carolina currently stores about 36 million gallons of waste in 49 active underground storag,* .ks. Twenty-two of these .anks do not meet Environmcntal Protection A&-.y (EPA) requirements ybr full secondary containment and must be emptied and closed by 2022 in accordance with a closure schedule approved by the EPA and the 5oith Carolina Department

440

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

0/02 WED 09:58 FAX 423 241 3897 OIG 0/02 WED 09:58 FAX 423 241 3897 OIG -.- +-+ HQ ]002 rFG (07-;1) United States Government Department of Energy Memorandum DATE: October 29, 2002 REPLY TO 1G-36 (A02DN028) Audit Report No.: OAS-L-03-01 ATTN OF; SUBJECT: Audit of Procurement at the Rocky Flats Environmental Technology Site TO: Eugene Schmitt, Manager, Rocky Flats Field Office ' INTRODUCTION AND OBJECTIVE The Department of Energy (Department) and its site contractor, Kaiser-Hill Company, LLC (Kaiser-Hill), contracted in January 2000 to close the Rocky Flats Environmental Technology Site (Rocky Flats) by a target date of December'15, 2006. As of May 2002, Kaiser-Hill had awarded 784 procurements worth more than $25,000 each, with a total value of about $368.6 million, to support the complex activities required for site closure.

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


441

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

uV,./ J.r./ i L .. * i. uV,./ J.r./ i L .. * i. 0 r '± J o ,. NL . Jurt -. rur.mO rI[ V Jg, ]VJUU"/UU4 DOE F 1325.8 (08-93) United States Government Department of Energy Memorandum OFFICE OF INSPECTOR GENERAL DATE: January 10, 2006 REPLY TO ATTN OF: IG-34 (A06GT029) Audit Report No.: OAS-L-06-06 SUBJECT: Review of the Independent Auditor's Report on The Institute for Genomic Research for the Year Ending December 31, 2004 * TO: Manager, Chicago Office INTRODUCTION AND OBJECTIVE The Institute for Genomic Research (Institute) in Rockville, Maryland is a not-for- profit center that studies areas such as plant, microbial and mammalian genomics. The Institute receives funding from seven Federal agencies to advance its research and development. As required by the Office of Management and Budget (0MB)

442

United States Government DATE:  

Office of Legacy Management (LM)

5oE(E;,8 ' 0 H .2+ L-1 5oE(E;,8 ' 0 H .2+ L-1 United States Government DATE: MAR 0 8 1994 REPLY TO AlTN OF: EM-421 (W. A. Williams, 903-8149) SUBJECT: Authority Determination -- Former Herring-Hall-Marvin Safe Co., Hamilton, Ohio TO: The File The attached review documents the basis for determining whether the Department of Energy (DOE) has authority for taking remedial action at the former Herring-Hall-Marvin Safe Co. facility in Hamilton, Ohio, under the Formerly Utilized Sites Remedial Action Program (FUSRAP). The facility was used for the shaping and machining of uranium metal by the Manhattan Engineer District (MED) during the Second World War. The following factors are significant in reaching a decision and are discussed in more detail in the attached authority review:

443

United States Government  

Office of Legacy Management (LM)

D;il$;,8 p! A . I I& - ' D;il$;,8 p! A . I I& - ' z United States Government &mtrne&' of Energy DATE: &uG 3, 9 394 REPLY TO AITN OF: EH-421 (W. A. Williams, 427-1719) SUBJECT: Elimination of the Sites from the Formerly Utilized Sites Remedial Action Program To' The File In 1990, with the assistance of Mr. Doug Toukay and Ms. Michelle Landis, I reviewed a number of sites that had formerly provided goods and/or services to the Fernald facility as subcontractors. For 24 of.these sites, recommdations were made to eliminate them from further consideration under Formerly Utilized Sites Remedial Action Program (FUSRAP). In each case, I made or reviewed the evaluation, and, in each case, a handwritten evaluation was prepared. This is to provide a more formal record of the decision on these sites and to ratify and confirm the

444

Unite2 States Government  

Office of Legacy Management (LM)

+39J +39J t% (3740~ - Unite2 States Government m e m o randuin L3 DATE: AU6 3, 9 %g4 REPLY TO All-N OF: m -421 (U. A. W illiams, 427-1719) -. - >' SUBJECT: Elimination of the Sites from the Formerly Utilized Sites Remedial Action Program To' The File In 1990, with the assistance of Hr. Doug Toukay and Ms. M ichelle Landis, I reviewed a number of sites that had formerly provided goods and/or services to the Fernald facility as subcontractors. For 24 of.these sites, recouwndations were made to eliminate them from further consideration under Formerly Utilized Sites Remedial Action Program (FUSRAP). In each case, I made or reviewed the evaluation, and, in each case, a handwritten evaluation was prepared. This is to provide a more formal record of the decision on these sites and to ratify and confirm the

445

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

LICE F 137: r.e Electr LICE F 137: r.e Electr onic Form App roved by CllR - 1010fJI2002 i/JI~~I United States Government Department of Energy Bonneville Power Admi istration memorandum DATE : REPLY TO AnN OF : KEPR-4 SUBJECT: Environmental Clearance Memorandum TO: Stephen Duncan Project Manager - TERS-3 Proposed Action: Removal of de-stabilized and downed trees resulting from a December 200 8 wind storm on the de-energized Lyons Ultra High Voltage Test Line NO.1. PP&A Project No.: PP&A 1309 Budget Information: Work Order # 184006 Categorical Exclusion Applied (from Subpart 0, 10 C.F.R. Part 1021): B 1.3 Routine maintenance/custodial services for buildings, structures, infrastructures, equipment. Location: Fee-owned ROW on the de-energized Lyons UHV Te st Line No .1 to the south of

446

United States Government Department  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

B.89) B.89) EFO (07-90) United States Government Department of Energ Memorandum SEP 24 20t DATE: REPLY TO: IG-34 (A04TG032) Audit Report No.: OAS-L-04-21 SUBJECT: Evaluation of "The Federal Energy Regulatory Commission's Cyber Security Program - 2004" TO: Chairman, Federal Energy Regulatory Commission The purpose of this report is to inform you of the results of our annual evaluation of the Federal Energy Regulatory Commission's unclassified cyber security program. This evaluation was initiated in June 2004 and our field work was conducted through September 2004. The evaluation methodology is described in the attachment to this report. Introduction and Objective The Commission's increasing reliance on information technology (IT) is consistent with satisfying the President's Management Agenda initiative of expanding electronic

447

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

/18/04 THU 11:31 FAX 423 241 3897 OIG -- /18/04 THU 11:31 FAX 423 241 3897 OIG -- + HQ 1002 DOE F 1325.8 (08-93) United States Government Department of Energy Memorandum DATE: March 17, 2004 Audit Report No. OAS-L-04-1 1 REPLY TO IG-36 (A04DN003) ATTN OF: SUBJECT; Audit of "Requests for Equitable Adjustment at the Rocky Flats Environmental Technology Site" TO: Frazer R. Lockhart, Manager, Rocky Flats Project Office INTRODUCTION AND OBJECTIVE Effective February 1, 2000, the Department of Energy's (Department) Rocky Flats Project Office (RFPO) and Kaiser-Hill Co., LLC (Kaiser-Hill), entered into a cost- plus-incentive-fee contract to close the Rocky Flats Environmental Technology Site (Rocky Flats) by December 15, 2006. Under the contract terms, Kaiser-Hlill's final incentive fee earned will be based on how well it meets established cost targets. For

448

United States Government  

Office of Legacy Management (LM)

. v-w. . v-w. ' ;H; (07.901 United States Government 0' ; Td 2, <.<~ Department of Energy ' m e m o randum DATE: REPLY TO Al-TN OF: EM-421 (W. A. W illiams, 903-8149) SUBJECT: Authorization for Remedial Action at Alba Craft Laboratory in Oxford, Ohio L. Price, OR TO: The former Alba Craft Laboratory site at lo-14 West Rose Avenue, Oxford, Ohio, is designated for remedial action under the Formerly Utilized Sites Remedial Action Program (FUSRAP). Dr. and M rs. Gilbert Pacey, of Oxford, Ohio, own the site. This designation is based on the results of a radiological survey and conclusions from an authority review as noted in the attached Designation Summary. Copies of the radiological survey letter report and the authority review are provided for your information.

449

UNITED STATES GOVERKMENT  

Office of Legacy Management (LM)

Ojice Memornndz~nz 0 Ojice Memornndz~nz 0 UNITED STATES GOVERKMENT By application dated ;!ay 11, 1959, as a~zen:ii:d Hay 25, 1959, the a--T+- I-r-- cant requests that its license SW-33 be amend,ed to authorizt? proced- ures for t>e CCLl-ect conversion of LT6 to '3$ and by applicaticn datzci June 29, 1959, a.3 n:odifizd July 15, 1059, the shipment of uranium rdioxide pellets. Based on our rexiew of the information finished by the applicant, it is hereby determined that the applicant is qualified, by training and experience, to use special nuclear material for the pwpose requested and that the ap@icant's procedures, facilities and equip- ment are adequate to protect health and minimize danger to life and property. It is, therefore, determined that ~NM-33 may be amended to

450

United States Government  

Office of Legacy Management (LM)

ocy F 1325.8 ocy F 1325.8 rcro1 . 6Fo0?-001 w 2 3-q United States Government Department of Energ) ~mc DATE: AUG 3,9 1994 y$Jf EH-421 (W. A. Yllliams, 427-1719) MA. \tQ SUBJECT: _ Elirinrtion of the Sites froa the Formerly Utilized Sites Remedial Action Program TQ The File In 1990, with the assistance of Hr. Doug Tonkay and Hr. Nlchelle Landis, I reviewed a number of sites that had fomerly provided goods and/or services to the Fernald facility as subcontractors. For 24 of.these sites, recomendations were made to eliminate them from further consideration under Forwrly Utilized Sites Remedial A&Ion Program (FUSRAP). In each case, I made or reviewed the evaluation, and, in each case, a handwritten evaluation was prepared. This is to provide a more formal record of the decision on these sites l hd to ratify and confim the

451

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

:)£ F 13 :)£ F 13 ;' 5 H e Etectroou: Form Approved by CGJR - 01120195 (n·/w! United States Government Department of Energy Bonneville Power Administration memorandum DATE: 0 I. 7 20D 9 REPLY TO AnN OF: KEP-4 SUBJECT: Environmental Clearance Memorandum TO : Robert Macy Project Manager - TELF-TPP-3 Proposed Action: Perform routine access road maintenance to the Rockdale Microwave site . Budget Information: Work Order #180709 PP&A Project No.: 1389 Categorical Exclusions Applied (from Subpart D, 10 C.F.R. Part 1021): B1.3, Routine maintenance activities .. .for structures, rights-of-way, infrastructures such as roads, equipment. .. routine maintenance activities, corrective .... are required to maintain ... infrastructures . ..in a condition suitable for a facility to be used for its designed purpose.

452

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

DOE:F 1325.8 7 DOE:F 1325.8 7 (08-93) United States Government Department of Energy memorandum DATE: April 10, 2006 REPLY TO ATTN OF: IG-32 (A05AL045) Audit Report Number: OAS-L-06-12 SUBJECT: Audit of Sandia National Laboratories' Safeguards and Security Path Forward Management Plan TO: Associate Administrator for Defense Nuclear Security INTRODUCTION AND OBJECTIVE From 2001 to 2003, approximately 500 security-related findings and observations were identified at Sandia National Laboratories (Sandia) by the Department of Energy's Office of Independent Oversight and Performance Assurance (OA), the National Nuclear Security Administration's (NNSA) Sandia Site Office (SSO), and Sandia's self assessments. Sandia senior management acknowledged the significance of the numerous findings and, in

453

. United States Government  

Office of Legacy Management (LM)

,:n5.5.8 ,:n5.5.8 ,849, EfG pw, . United States Government DATE: AUG 2 i994 y#J;; EM-421 (W. A. Williams, 427-1719) sUBJECT: -Elimination of the Robbins & Myers Site, Springfield, Ohio 11179 I The File TO: I have reviewed the attached elimination recommendation and the original historical records for the Myers & Robbins facility in Springfield, Ohio. I have determined that there is little likelihood of radioactive contamination at these sites. The only record of activity at this site by Department of Energy predecessors is an equipment test of a pump in March 1975. This test involved limited amounts of radioactive materials and there was a serious effort to decontaminate the equipment at the conclusion of the tests. Based on the above, the Myers & Robbins site in Springfield, Ohio, is

454

United States Government  

Office of Legacy Management (LM)

DOE F 1325.8 DOE F 1325.8 E&M&& +\A .wz United States Government Department of Energy DATE: RUG 3, 9 %g4 y;;;; EM-421 (W. A. W illiaas, 427-1719) "; :+ 1 SUBJECT: Elimination of the Sites from the Formerly Utilized Sites Remedial Action Program To' The File In 1990, with the assistance of M r. Doug Tohkay and Ms. M ichelle Landis, I reviewed a number of sites that had formerly provided goods and/or services to the Fernald facility as subcontractors. For 24 of.these sites, recomendations were made to eliminate then from further consideration under Formerly Utilized Sites Remedial Action Program (FUSRAP). In each case, I made or reviewed the evaluation, and, in each case, a handwritten evaluation was prepared. This is to provide a more formal record of the decision on these sites and to ratify and confirm the

455

Uniter+ States Government  

Office of Legacy Management (LM)

EFG (07-90) EFG (07-90) Uniter+ States Government ~L.aQ-i; Department of Energy inemorandum DATE: SEP 2 5 1992 REPLY TO Al-fN OF: EM-421 (W. A. W illiams, 903-8149) SUBJECT: Authorization for Remedial Action at the Former Dow Chemical Company Facility in M a d ison, Illinois TO: L. Price, OR The site of the Former Dow Chemical Company in M a d ison, Illinois, which is currently owned and operated by the Spectrulite Consortium, is designated for inclusion in the Formerly Utilized Sites Remedial Action Program (FUSRAP). This designation is based upon the results of a preliminary radiological survey and other information described in the attached Designation Summary. The authority determination and preliminary survey report also are attached for information. The site has been assigned a low priority under the FUSRAP protocol, as

456

United States Government  

Office of Legacy Management (LM)

# Xx i' # Xx i' !325 8 I c&egJw, i&l d, 4 -1 United States Government Department of Energy DATE; AUG 3, 9 !gg4 I REPLYTo m-421 (W. A. Williams, 427-1719) sy I AlTN OF: SUBJECT: Elimination of the Sites from the Formerly Utilized Sites Remedial Action Program To' The File In 1990, with the assistance of Mr. Doug Tonkay and Ms. Nichelle Landis, I reviewed a number of sites that had formerly provided goods a&/or services to the Fernald facility as subcontractors. For 24 of these sites, recoumendations were made to eliminate them from further consideration under Formerly Utilized Sites Remedial Action Program (FUSRAP). In each case, I made or reviewed the evaluation, and, in each case, a handwritten evaluation was prepared. This is to provide a more

457

United States Government  

Office of Legacy Management (LM)

EFS (07-W EFS (07-W United States Government memorandukn Department of Energy j ; I.-- ' -i;: /J DATE: j.gjG 2 9 1994 REPLY TO En-421 (W. A. Williams, 427-1719) AlTN OF: h p)\;--/ ;,;' J ( SUBJECT: Elimination of the Sites from the Formerly Utilized Sites Remedial Action Program To' The File In 1990, with the assistance of Ur. Doug Tonkay and Us. Michelle Landis, I reviewed a number of sites that had formerly provided goods and/or services to the Fernald facility as subcontractors. For 24 of.these sites, recoPraendations were made to eliminate them from further consideration under Formerly Utilized Sites Remedial Action Program (FUSRAP). In each case, I made or reviewed the evaluation, and, in each case, a handwritten evaluation was prepared. This is to provide a more

458

United States Government  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

nUnited States Government Department of Energy Bonneville Power Administration memorandum REPLY TO AnN OF: KEP-4 SUBJECT: Environmental Clearance Memorandum TO: Robert Macy Project Manager - TELF-TPP-3 Proposed Action: Access road improvement and bridge replacement for the Raver-Paul No. transmission line structure 18/1. Budget Information: Work Order # 00220048 PP&A Project No.: 954 Proposed by: Bonneville Power Administration (BPA) Categorical Exclusion Applied (from Subpart D, 10 C.F.R. Part 1021): B1.3, Routine maintenance activities .. .for structures, rights-of-way, infrastructures such as roads, equipment. .. routine maintenance activities, corrective ....are required to

459

Development of the severe accident management guidelines (SAMG) for Ulchin Nuclear Power Plant Unit 3, 4, 5 and 6  

SciTech Connect

This paper describes the development process of the severe accident management guidelines (SAMG) for Units 3, 4, 5 and 6 of Ulchin Nuclear Power Plant. The units are Korean Standard Nuclear Power (KSNP) plant, 1000 MWe class pressurized water reactor (PWR) with two loops of primary coolant system. The severe accident management guidelines for the units have been completed in 2002. The generic severe accident management guidance for Korean Standard Nuclear Power Plant has been used as the basis when developing Ulchin severe accident management guideline. Result of probabilistic safety assessment (PSA) for each unit was reviewed to integrate its insight into the SAMG. It indicates that each unit has a balanced design to any specific initiating events for core damage. Seven severe accident management strategies are applied in Ulchin SAMG. Seven strategies are (1) Inject into the steam generator (2) De-pressurize the RCS (3) Inject into the RCS (4) Inject into the containment (5) Control the fission product release into environment (6) Control the containment pressure and temperature and (7) Control hydrogen concentration in the containment. The range and capability of essential instrument for performing the strategies are assessed. Computational aids are developed to complement the unavailable instrument during the accident and to assist the operator's decision choosing strategies. To examine the ability of the SAMG to fulfill its intended function, small loss of coolant accident (SLOCA) with the failure of safety injection was selected as a reference scenario. The scenario was analyzed using MAAP code. The evaluation of the SAMG using this sequence has been successfully completed. (authors)

Kim, Hyeong T.; Yoo, Hojong; Lim, Hyuk Soon; Park, Jong W.; Lim, Woosang; Oh, Seung Jong [Korea Hydro and Nuclear Power Co., Ltd., 103-16 Munji-Dong, Yusung-Gu, Daejeon, 305-380 (Korea, Republic of); Chung, Chang Hyun [Seoul National University (Korea, Republic of); Lee, Byung Chul [Future and Challenges, Inc (Korea, Republic of)

2004-07-01T23:59:59.000Z

460

Quantifying Differences between 2-m Temperature Observations and Reanalysis Pressure-Level Temperatures in Northwestern North America  

Science Conference Proceedings (OSTI)

In northwestern North America, which is a large area with complex physiography, Climatic Research Unit (CRU) Time Series, version 2.1, (TS 2.1) gridded monthly mean 2-m temperatures are systematically lower than interpolated monthly averaged North ...

Christian Reuten; R. Dan Moore; Garry K. C. Clarke

2011-04-01T23:59:59.000Z

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


461

SYSTEMS AND METHODS FOR THE AUTONOMOUS CONTROL, AUTOMATED ...  

systems and methods for the autonomous control, automated guidance, and global coordination of moving process machinery united states patent application

462

Seasonal Prediction of North American Surface Air Temperatures Using Space–Time Principal Components  

Science Conference Proceedings (OSTI)

The statistical model proposed by Vautard et al. is applied to the seasonal prediction of surface air temperatures over North America (Canada and the United States). This model is based on sea surface temperature predictors filtered by ...

Robert Vautard; Guy Plaut; Risheng Wang; Gilbert Brunet

1999-02-01T23:59:59.000Z

463

Areally-Weighted Temperature and Precipitation Averages for Alaska, 1931–1977  

Science Conference Proceedings (OSTI)

Areally weighted time series of temperature and precipitation have been compiled for Alaska for the period 1931–1977. Correlations of the temperature values with those of the contiguous United States indicate that, at both the monthly and ...

Henry F. Diaz

1980-06-01T23:59:59.000Z

464

Reconstructed Annual Minimum Temperatures for the Gulf States, 1799–1988  

Science Conference Proceedings (OSTI)

A very long series of minimum winter temperatures for the United States Gulf Coast region was developed. A search was made through sources of archival data to locate early temperature records for the region. Records from a number of different ...

Robert D. Erhardt Jr.

1990-06-01T23:59:59.000Z

465

Methodology for Deriving Deep-Layer Mean Temperatures from Combined Satellite Infrared and Microwave Observations  

Science Conference Proceedings (OSTI)

Deep-layer mean temperatures from Microwave Sounding Unit (MSU) observations have been used by scientists to study trends and interannual variations of tropospheric and lower-stratospheric temperature. The spatial resolution of MSU deep-layer ...

Mitchell D. Goldberg; Larry M. McMillin

1999-01-01T23:59:59.000Z

466

Fossil Plant Instrumentation and Control Guidelines  

Science Conference Proceedings (OSTI)

Poor control loop performance can make a unit difficult and more costly to operate. Most control engineers and technicians will agree that controller tuning plays a major role in control loop performance, but few of them have actually received formal training and gained the experience necessary to tune and troubleshoot control loops effectively. A systematic approach to controller tuning is rarely followed, and ...

2012-12-12T23:59:59.000Z

467

REACTOR CONTROL DEVICE  

DOE Patents (OSTI)

A wholly mechanical compact control device is designed for automatically rendering the core of a fission reactor subcritical in response to core temperatures in excess of the design operating temperature limit. The control device comprises an expansible bellows interposed between the base of a channel in a reactor core and the inner end of a fuel cylinder therein which is normally resiliently urged inwardly. The bellows contains a working fluid which undergoes a liquid to vapor phase change at a temperature substantially equal to the design temperature limit. Hence, the bellows abruptiy expands at this limiting temperature to force the fuel cylinder outward and render the core subcritical. The control device is particularly applicable to aircraft propulsion reactor service. (AEC)

Graham, R.H.

1962-09-01T23:59:59.000Z

468

Thermoelectric refrigerator having improved temperature stabilization means  

DOE Patents (OSTI)

A control system for thermoelectric refrigerators is disclosed. The thermoelectric refrigerator includes at least one thermoelectric element that undergoes a first order change at a predetermined critical temperature. The element functions as a thermoelectric refrigerator element above the critical temperature, but discontinuously ceases to function as a thermoelectric refrigerator element below the critical temperature. One example of such an arrangement includes thermoelectric refrigerator elements which are superconductors. The transition temperature of one of the superconductor elements is selected as the temperature control point of the refrigerator. When the refrigerator attempts to cool below the point, the metals become superconductors losing their ability to perform as a thermoelectric refrigerator. An extremely accurate, first-order control is realized.

Falco, Charles M. (Woodridge, IL)

1982-01-01T23:59:59.000Z

469

High temperature size selective membranes  

DOE Green Energy (OSTI)

The objective of this research is to develop a high temperature size selective membrane capable of separating gas mixture components from each other based on molecular size, using a molecular sieving mechanism. The authors are evaluating two concepts: a composite of a carbon molecular sieve (CMS) with a tightly defined pore size distribution between 3 and 4 {angstrom}, and a microporous supporting matrix which provides mechanical strength and resistance to thermal degradation, and a sandwich of a CMS film between the porous supports. The high temperature membranes the authors are developing can be used to replace the current low-temperature unit operations for separating gaseous mixtures, especially hydrogen, from the products of the water gas shift reaction at high temperatures. Membranes that have a high selectivity and have both thermal and chemical stability would improve substantially the economics of the coal gasification process. These membranes can also improve other industrial processes such as the ammonia production and oil reform processes where hydrogen separation is crucial. Results of tests on a supported membrane and an unsupported carbon film are presented.

Yates, S.F.; Zhou, S.J.; Anderson, D.J.; Til, A.E. van

1994-10-01T23:59:59.000Z

470

Sanyal Temperature Classification | Open Energy Information  

Open Energy Info (EERE)

Sanyal Temperature Classification Sanyal Temperature Classification Jump to: navigation, search GEOTHERMAL ENERGYGeothermal Home Print PDF Sanyal Temperature Classification The information for this page was taken directly from Subir Sanyal's paper, Classification of Geothermal Systems: A Possible Scheme (Stanford, February 2, 2005) At the request of the United States Department of Energy, the author was asked by the Geothermal Energy Association (Washington, D.C.) to prepare a white paper on the subject (in connection with a new national assessment of geothermal resources). This paper offers a possible scheme in which geothermal resources are classified into seven categories based on temperature. This scheme is based not only on temperature but also according to a set of additional attributes important for practical utilization of geothermal

471

Ice maker safety control  

Science Conference Proceedings (OSTI)

In a refrigeration apparatus including an evaporator, a defrost heater for defrosting the evaporator, a defrost thermostat having a switch for de-energizing the defrost heater at a preselected high temperature of the evaporator, and an ice making apparatus having a mold, a mold heater, and a control circuit controllably energized the mold heater, a safety control for the ice making apparatus is described comprising: means for thermally coupling the defrost thermostat with the mold; and means electrically connecting the defrost thermostat switch with the control circuit for de-energizing the mold heater at a preselected high temperature of the mold to prevent overheating thereof.

Linstromberg, W.J.

1988-05-03T23:59:59.000Z

472

Air Pollution Control Regulations: No. 13 - Particulate Emissions...  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Pollution Control Regulations: No. 13 - Particulate Emissions from Fossil Fuel Fired Steam or Hot Water Generating Units (Rhode Island) Air Pollution Control Regulations: No. 13...

473

CVG-venalum Potline Control and Supervisory Integrated System ...  

Science Conference Proceedings (OSTI)

To fulfill these targets, CVG-Venalum developed an aluminum reduction pot control and supervisory integrated system (VEN-PCSIS). The central control unit of ...

474

Total U.S. Housing Units.................................  

U.S. Energy Information Administration (EIA) Indexed Site

Housing Units (millions) Single-Family Units Apartments in Buildings With-- Space Heating Usage Indicators Million U.S. Housing Units Detached Attached Energy Information...

475

Maximal Reliability for Unit-weighted Composites  

E-Print Network (OSTI)

Maximal Reliability for Unit-weighted Composites Peter M.Maximal Reliability for Unit-weighted Composites Althoughconsistency coefficient for a unit-weighted composite. The

Peter M. Bentler

2011-01-01T23:59:59.000Z

476

Collaborative Unit Construction in Korean: Pivot Turns  

E-Print Network (OSTI)

A. (1996). Interactional units in conversation: Syntactic,M. (2000). The construction of units in conversational talk.character of grammatical units in conversation: Conditional

Ju, Hee

2011-01-01T23:59:59.000Z

477

Unsuspected Pulmonary Embolism in Observation Unit Patients  

E-Print Network (OSTI)

department observation unit. Emerg Med Clin North Am. 2001;ED) managed acute care unit on ED overcrowding and emergencyof a chest pain observation unit compared with routine care.

Limkakeng, Alexander T.; Glickman, Seth W; Cairns, Charles B; Chandra, Abhinav

2009-01-01T23:59:59.000Z

478

United States Goverment  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

UO/J±0ou4 TcdJ ± O:S'. Aa. ou* o *.I. I 01j ' . UO/J±0ou4 TcdJ ± O:S'. Aa. ou* o *.I. I 01j ' . - - 00E F 1325,8 (08-93) United States Goverment Department of Energy memorandum DATE: August 13, 2007 Audit Report Number: OAS-L-07-19 REPLY TO ATTN OF: IG-32 (A07PR059) SUBJECT: Audit of Executive Compensation at Selected Office of Science Sites TO: Chief Operating, Officer, Office of Science INTRODUCTION AND OBJECTIVE As part of a Department of Energy-wide audit of executive compensation, we reviewed seven Office of Science sites. Specifically, we reviewed executive compensation costs incurred ~,r claim~.- fr- F".*l*- Y. rs 2003, 2 , and 2005 at - Argonne National Laboratory (Argonne), Brookhaven National Laboratory (Brookhaven), Lawrence Berkeley National Laboratory (LBNL), Oak Ridge Institute for Science and Education, Oak Ridge National Laboratory, Princeton Plasma Physics

479

United States Government Department  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

1/03 07:45 FAX 301 903 4656 CAPITAL REGION -* FORS FIVEA I002/004 1/03 07:45 FAX 301 903 4656 CAPITAL REGION -* FORS FIVEA I002/004 DOE F 1325 ' (8-69) EFO (07-90) United States Government Department of Eneray memorandum DATE: PR17 2003 Audit Report No.: OAS-L-03-14 REPLY TO ATTN OF: IG-34 (A03PT040) SUBJECT: Audit of the Office of Energy Efficiency and Renewable Energy's (EE) Grants, Subsidies, and Cost Sharing Arrangements TO: Assistant Secretary for Energy Efficiency and Renewable Energy, EE-1 The purpose of this report is to inform you of the results of our review of the Office of Energy Efficiency and Renewable Energy's (EE) incentive payments and cost-share arrangements. The review was initiated in February 2003, and fieldwork was conducted through April 2003 at Department of Energy (Department) Headquarters. Our methodology is described in the attachment to this report.

480

Second United Nations  

NLE Websites -- All DOE Office Websites (Extended Search)

i' i' Second United Nations t Jnternational Conference 1 , of Atomic Energy on the Peaceful Uses 4 i \ Confidential until official release during Conference ORIGINAL: ENGLISH METHODS O F PARTICLE DETECTION FOR HIGH-ENERGY PHYSICS EXPERIMENTS t * H. B r a d n e r and D. A. Glaser - INTRODUCTION J 1 % c Recent advances in our knowledge of t h e phenomena of high-energy physics and o'f the e l e m e n t a r y p a r t i c l e s h a s r e s u l t e d f r o m rapid advances in the technology of p a r t i c l e a c c e l e r a t o r s and the art of p a r t i c l e detection. cl'asses: (1) the "track-imaging" device in which one s e e s o r photographs t r a c k s which coincide with the a c t u a l path taken by the p a r t i c l e s , and ( 2 ) counting d e - v i c e s which give only an indication that the p a r t i c l e s p a s s somewhere in the

Note: This page contains sample records for the topic "temperature control unit" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


481