Powered by Deep Web Technologies
Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


1

Fire alarm system improvement  

SciTech Connect (OSTI)

This document contains the Fire Alarm System Test Procedure for Building 234-5Z, 200-West Area on the Hanford Reservation, Richland, Washington. This Acceptance Test Procedure (ATP) has been prepared to demonstrate that the modifications to the Fire Protection systems function as required by project criteria. The ATP will test the Fire Alarm Control Panels, Flow Alarm Pressure Switch, Heat Detectors, Smoke Detectors, Flow Switches, Manual Pull Stations, and Gong/Door by Pass Switches.

Hodge, S.G.

1994-10-01T23:59:59.000Z

2

False fire alarms have a negative impact on UW operations False (or nuisance) alarms are very disruptive to UW operations. The alarms  

E-Print Network [OSTI]

protection devices and upgrading old fire protection equipment with current technology. How construction. · Temporary impairment/removal of fire alarm devices ­ Confer with the University Fire Protection Engineer Fire Alarm Shop. · Fire watch requirements - Confer with the University Fire Protection Engineer (206

Wilcock, William

3

Project 93L-EWL-097, fire alarm system improvements, 300 Area  

SciTech Connect (OSTI)

This document contains the Acceptance Test Procedure (ATP) which will demonstrate that the modifications to the Fire Protection systems in the 338 Building function as intended. The ATP will test the fire alarm control panel, flow alarm pressure switch, post indicator valve tamper switch, heat detectors, flow switches, and fire alarm signaling devices.

Scott, M.V.

1995-01-01T23:59:59.000Z

4

Activate the nearest fire alarm pull station Call 911 to report the fire  

E-Print Network [OSTI]

, records and hazardous materials. o Shut off non-essential electrical equipment. o Wait for instructions, fumes or vapors: Do not pull fire alarms. Do not touch light switches or electrical equipment. Call UH. Provide your location and the location of the odor to the dispatcher. Provide as many details as possible

Azevedo, Ricardo

5

Fire Alarm Testing and Inspection Planning and Vendor Check In/Check Out Process  

E-Print Network [OSTI]

Fire Alarm Testing and Inspection Planning and Vendor Check In/Check Out Process DOCUMENT PURPOSE This process is used for fire alarm testing and inspection pre-work planning and vendor check in and check out ____________________________________________________ CHECK IN PRIOR TO TESTING NOTES _____ Central Monitoring (BSAC) notified of daily testing start time

Webb, Peter

6

Alarm Response Training | Y-12 National Security Complex  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

On Time: 4:04 min. View an introduction to our Alarm Response Training, which prepares and trains personnel responding to civilian nuclear and radiological security alarms...

7

Setting fires, false alarms, or vandalizing fire protection equipment is illegal. Any person found to be participating in these activities will be prosecuted to the full extent of the law and/or disciplined through the University's disciplinary procedures  

E-Print Network [OSTI]

Setting fires, false alarms, or vandalizing fire protection equipment is illegal. Any person found University fire safety equipment should contact the Campus University Police or Security. FIRES What should I do if I discover a fire? ACTIVATE THE FIRE ALARM SYSTEM by pulling one of the pull stations that re

Fernandez, Eduardo

8

Setting fires, false alarms, or vandalizing fire protection equipment is illegal. Any person found to be participating in these activities will be prosecuted to the full extent of the law and/or disciplined through the University's disciplinary procedures  

E-Print Network [OSTI]

Setting fires, false alarms, or vandalizing fire protection equipment is illegal. Any person found University fire safety equipment should contact the Campus University Police or Security. FIRES What should I do if I discover a fire? · ACTIVATE THE FIRE ALARM SYSTEM by pulling one of the nearest pull stations

Fernandez, Eduardo

9

An analysis of firefighter personal safety alarm effectiveness on the fire ground  

Science Journals Connector (OSTI)

For firefighters in the line of duty the last line of defense and chance for rescue oftentimes relies on the effectiveness of their Personal Alert Safety System (PASS) devices. When activated a PASS device emits an alarm signal to notify others that a firefighter is in distress. However there have been notable instances where PASS devices have confused rescue personnel or created a more hazardous situation for instance when noise interference originating from other objects is involved. This research compiles data from various sources for example firefighter near miss reports and National Institute for Occupational Safety and Health (NIOSH) fatality reports regarding PASS device effectiveness. The research will investigate the causes of confusion and danger as well as take a look at the situations where the device achieved its goal and was able to save a life. The implications of discovering how interfering noises can render PASS devices ineffective could save several lives in the future and ultimately lead to increased firefighter safety.

Kyle Ford; Mudeer Habeeb; Joelle Suits; Mustafa Abbasi; Ofodike Ezekoye

2013-01-01T23:59:59.000Z

10

Contained Firing Facility | National Nuclear Security Administration  

National Nuclear Security Administration (NNSA)

Contained Firing Facility | National Nuclear Security Administration Contained Firing Facility | National Nuclear Security Administration Our Mission Managing the Stockpile Preventing Proliferation Powering the Nuclear Navy Emergency Response Recapitalizing Our Infrastructure Continuing Management Reform Countering Nuclear Terrorism About Us Our Programs Our History Who We Are Our Leadership Our Locations Budget Our Operations Media Room Congressional Testimony Fact Sheets Newsletters Press Releases Speeches Events Social Media Video Gallery Photo Gallery NNSA Archive Federal Employment Apply for Our Jobs Our Jobs Working at NNSA Blog Contained Firing Facility Home > About Us > Our Programs > Defense Programs > Office of Research, Development, Test, and Evaluation > Office of Research and Development > Facilities > Contained Firing Facility

11

CRAD, Fire Protection - Oak Ridge National Laboratory High Flux...  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection - Oak Ridge National Laboratory High Flux Isotope Reactor CRAD, Fire Protection - Oak Ridge National Laboratory High Flux Isotope Reactor February 2006 A section of...

12

Forest fire near Los Alamos National Laboratory  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Forest fire near Los Alamos National Laboratory Forest fire near Los Alamos National Laboratory Forest fire near Los Alamos National Laboratory The Las Conchas fire burning in the Jemez Mountains approximately 12 miles southwest of the boundary of LANL has not entered Lab property at this time. June 26, 2011 Los Alamos National Laboratory sits on top of a once-remote mesa in northern New Mexico with the Jemez mountains as a backdrop to research and innovation covering multi-disciplines from bioscience, sustainable energy sources, to plasma physics and new materials. Los Alamos National Laboratory sits on top of a once-remote mesa in northern New Mexico with the Jemez mountains as a backdrop to research and innovation covering multi-disciplines from bioscience, sustainable energy sources, to plasma physics and new materials.

13

Sandia National Laboratories: National Fire Protection Association  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Fire Protection Association More California Gas Stations Can Provide Hydrogen than Previously Thought, Sandia Study Says On July 29, 2014, in Center for Infrastructure Research and...

14

An evaluation of various types of fire detection alarm systems to awaken the elderly  

E-Print Network [OSTI]

to represent the hearing perception of an ei ghty year old male, were presented to ten college student participarits. These three alarm systems represented a smoke detector located in the hallway; in the bedroom and the liallway; and in the bedroom...-Sand Frequency Analyses (SPL re . 0002 microPascal) Taken 10 Feet from Source in UNass Anechoic Chaarber 18 IV An Average Eighty Year Old Nale's Hearing Perception of the Average Smoke Def~ctor Alarm Signals Neasured by Nober, Peirce and Well, at a Distance...

Townley, Timothy Edward

2012-06-07T23:59:59.000Z

15

Technical evaluation of equipment maintenance on fire alarm detection, suppression, and signaling  

SciTech Connect (OSTI)

This document delineates the application of WHC-CM-4-3, Program E-2 to Fire Systems on the Hanford Site.

Korslund, S.M.

1994-10-01T23:59:59.000Z

16

E-Print Network 3.0 - automatic alarm dosimeter Sample Search...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

systems, and emergency lights. Firewatch... or to the fire alarm annunciatorcontrol panel for fire alarm systems. ... Source: Karsai, Istvan - Department of Biological...

17

Wildland Fire Management Plan for Brookhaven National Laboratory  

SciTech Connect (OSTI)

This Wildland Fire Management Plan (FMP) for Brookhaven National Lab (BNL) updates the 2003 plan incorporating changes necessary to comply with DOE Order 450.1 and DOE P 450.4, Federal Wildland Fire Management Policy and Program Review; Wildland and Prescribed Fire Management Policy and implementation Procedures Reference Guide. This current plan incorporates changes since the original draft of the FMP that result from new policies on the national level. This update also removes references and dependence on the U.S. Fish & Wildlife Service and Department of the Interior, fully transitioning Wildland Fire Management responsibilities to BNL. The Department of Energy policy for managing wildland fires requires that all areas, managed by the DOE and/or its various contractors, that can sustain fire must have a FMP that details fire management guidelines for operational procedures associated with wild fire, operational, and prescribed fires. Fire management plans provide guidance on fire preparedness, fire prevention, wildfire suppression, and the use of controlled, 'prescribed' fires and mechanical means to control the amount of available combustible material. Values reflected in the BNL Wildland FMP include protecting life and public safety; Lab properties, structures and improvements; cultural and historical sites; neighboring private and public properties; and endangered, threatened, and species of concern. Other values supported by the plan include the enhancement of fire-dependent ecosystems at BNL. This FMP will be reviewed periodically to ensure the fire program advances and evolves with the missions of the DOE and BNL. This Fire Management Plan is presented in a format that coverers all aspects specified by DOE guidance documents which are based on the national template for fire management plans adopted under the National Fire Plan. The DOE is one of the signatory agencies on the National Fire Plan. This FMP is to be used and implemented for the entire BNL site including the Upton Reserve and has been reviewed by, The Nature Conservancy, New York State Department of Environmental Conservation Forest Rangers, and DOE, as well as appropriate BNL emergency services personnel. The BNL Fire Department is the lead on wildfire suppression. However, the BNL Natural Resource Manager will be assigned to all wildland fires as technical resource advisor.

Green,T.

2009-10-23T23:59:59.000Z

18

CRAD, Fire Protection - Oak Ridge National Laboratory High Flux Isotope  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection - Oak Ridge National Laboratory High Flux Fire Protection - Oak Ridge National Laboratory High Flux Isotope Reactor CRAD, Fire Protection - Oak Ridge National Laboratory High Flux Isotope Reactor February 2006 A section of Appendix C to DOE G 226.1-2 "Federal Line Management Oversight of Department of Energy Nuclear Facilities." Consists of Criteria Review and Approach Documents (CRADs) used for a February 2006 Commencement of Operations assessment of the Fire Protection program at the Idaho National Laboratory, Idaho Accelerated Retrieval Project Phase II. CRADs provide a recommended approach and the types of information to gather to assess elements of a DOE contractor's programs. CRAD, Fire Protection - Oak Ridge National Laboratory High Flux Isotope Reactor More Documents & Publications

19

CRAD, Fire Protection - Los Alamos National Laboratory Waste  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection - Los Alamos National Laboratory Waste Fire Protection - Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility CRAD, Fire Protection - Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility A section of Appendix C to DOE G 226.1-2 "Federal Line Management Oversight of Department of Energy Nuclear Facilities." Consists of Criteria Review and Approach Documents (CRADs) used for an assessment of the Fire Protection Program portion of an Operational Readiness Review at the Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility. CRADs provide a recommended approach and the types of information to gather to assess elements of a DOE contractor's programs. CRAD, Fire Protection - Los Alamos National Laboratory Waste

20

Los Alamos National Laboratory: Las Conchas Fire Update | Department of  

Broader source: Energy.gov (indexed) [DOE]

Alamos National Laboratory: Las Conchas Fire Update Alamos National Laboratory: Las Conchas Fire Update Los Alamos National Laboratory: Las Conchas Fire Update June 29, 2011 - 10:33am Addthis Liisa O'Neill Liisa O'Neill Former New Media Specialist, Office of Public Affairs Many of you have asked for more information about the potential impact of the fire in New Mexico on the Energy Department's Los Alamos National Laboratory. We'd like to share the latest update from the lab below. You can also monitor the Laboratory's news site for the latest information. LANL Announces Closure for Thursday, June 30 Los Alamos, New Mexico, June 28, 2011, 7:00pm--Los Alamos National Laboratory tonight announced it will remain closed through Thursday, June 30 because of risks presented by the Las Conchas Fire and the mandatory

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


21

WILDLAND FIRE MANAGEMENT PLAN FOR BROOKHAVEN NATIONAL LABORATORY.  

SciTech Connect (OSTI)

This Wildland Fire Management Plan (FMP) for Brookhaven National Lab (BNL) and the Upton Ecological and Research Reserve (Upton Reserve) is based on the U.S. Fish & Wildlife Service (FWS) fire management planning procedures and was developed in cooperation with the Department of Energy (DOE) by Brookhaven Science Associates. As the Upton Reserve is contained within the BNL 5,265-acre site, it is logical that the plan applies to both the Upton Reserve and BNL. The Department of the Interior policy for managing wildland fires requires that all areas managed by FWS that can sustain fire must have an FMP that details fire management guidelines for operational procedures and specifies values to be protected or enhanced. Fire management plans provide guidance on fire preparedness, fire prevention, wildfire suppression, and the use of controlled, ''prescribed'' fires and mechanical means to control the amount of available combustible material. Values reflected in the BNL/Upton Reserve Wildland FMP include protecting life and public safety; Lab properties, structures and improvements; cultural and historical sites; neighboring private and public properties; and endangered and threatened species and species of concern. Other values supported by the plan include the enhancement of fire-dependent ecosystems at BNL and the Upton Reserve. This FMP will be reviewed periodically to ensure the fire program advances and evolves with the missions of FWS, BNL, and the Upton Reserve. This Fire Management Plan is a modified version of the Long Island National Wildlife Refuge Complex Fire plan (updated in 2000), which contains all FWS fire plan requirements and is presented in the format specified by the national template for fire management plans adopted under the National Fire Plan. The DOE is one of the signatory agencies on the National Fire Plan. FWS shall be, through an Interagency Agreement dated November 2000 (Appendix C), responsible for coordinating and implementing prescribed burns and fuel reduction projects in the Upton Reserve. Prescribed fire and fuel reduction in locations outside the Upton Reserve will be coordinated through the Natural Resource Management Program at BNL, and done in consultation with FWS. This FMP is to be used and implemented for the entire BNL site including the Upton Reserve and has been reviewed by FWS, The Nature Conservancy, New York State Department of Environmental Conservation Forest Rangers, and DOE, as well as appropriate BNL emergency services personnel.

ENVIRONMENTAL AND WASTE MANAGEMENT SERVICES DIVISION

2003-09-01T23:59:59.000Z

22

NNSA Celebrates Earth Week: Pantex 'greens' firing range | National Nuclear  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

'greens' firing range | National Nuclear 'greens' firing range | National Nuclear Security Administration Our Mission Managing the Stockpile Preventing Proliferation Powering the Nuclear Navy Emergency Response Recapitalizing Our Infrastructure Continuing Management Reform Countering Nuclear Terrorism About Us Our Programs Our History Who We Are Our Leadership Our Locations Budget Our Operations Media Room Congressional Testimony Fact Sheets Newsletters Press Releases Speeches Events Social Media Video Gallery Photo Gallery NNSA Archive Federal Employment Apply for Our Jobs Our Jobs Working at NNSA Blog Home > NNSA Blog > NNSA Celebrates Earth Week: Pantex 'greens' firing range NNSA Celebrates Earth Week: Pantex 'greens' firing range Posted By Greg Cunningham, Pantex The lead that flies at the Pantex Firing Range has to land somewhere, and

23

Xcel Energy implements an alarm management strategy  

SciTech Connect (OSTI)

Not so long ago, Xcel Energy's Pawnee Station, a 505 MW coal-fired generating station in Brush, Colorado, USA was commonly generating 300 to 400 alarms per 8-hour shift. The article describes how the alarm system was revised and improved by tackling alarm dead-bands, and rationalising alarms for routine events. Operators are trained to understand the functions of alarm management components, their use and response, and obtain feedback. Today the power station reports about one alarm per hour. 3 photos.

Bass, J.; Abreu, G. [Xcel Energy (United States)

2007-11-15T23:59:59.000Z

24

Audit Report, "Fire Protection Deficiencies at Los Alamos National Laboratory"  

SciTech Connect (OSTI)

The Department of Energy's Los Alamos National Laboratory (Los Alamos) maintains some of the Nation's most important national security assets, including nuclear materials. Many of Los Alamos' facilities are located in close proximity to one another, are occupied by large numbers of contract and Federal employees, and support activities ranging from nuclear weapons design to science-related activities. Safeguarding against fires, regardless of origin, is essential to protecting employees, surrounding communities, and national security assets. On June 1, 2006, Los Alamos National Security, LLC (LANS), became the managing and operating contractor for Los Alamos, under contract with the Department's National Nuclear Security Administration (NNSA). In preparation for assuming its management responsibilities at Los Alamos, LANS conducted walk-downs of the Laboratory's facilities to identify pre-existing deficiencies that could give rise to liability, obligation, loss or damage. The walk-downs, which identified 812 pre-existing fire protection deficiencies, were conducted by subject matter professionals, including fire protection experts. While the Los Alamos Site Office has overall responsibility for the effectiveness of the fire protection program, LANS, as the Laboratory's operating contractor, has a major, day-to-day role in minimizing fire-related risks. The issue of fire protection at Los Alamos is more than theoretical. In May 2000, the 'Cerro Grande' fire burned about 43,000 acres, including 7,700 acres of Laboratory property. Due to the risk posed by fire to the Laboratory's facilities, workforce, and surrounding communities, we initiated this audit to determine whether pre-existing fire protection deficiencies had been addressed. Our review disclosed that LANS had not resolved many of the fire protection deficiencies that had been identified in early 2006: (1) Of the 296 pre-existing deficiencies we selected for audit, 174 (59 percent) had not been corrected; and, (2) A substantial portion of the uncorrected deficiencies, 86 (49 percent) were considered by the walk-down teams to be significant enough to warrant compensatory actions until the deficiency was corrected or was tracked to closure through implementation of corrective actions. Further, we found that 32 of the significant deficiencies had been closed by the previous Los Alamos contractor, prior to LANS assuming responsibility for operation of the Laboratory, even though the deficiencies had not been corrected. A fire protection expert provided technical support during the audit. As an example of uncorrected problems, LANS had not resolved, by performing periodic tests, a deficiency identified in 2006 regarding a kitchen hood fire suppression system in a facility located within the Los Alamos Neutron Science Center. Such systems are required to be tested twice a year by the National Fire Protection Association standard, a standard that had been adopted by Department of Energy under DOE Order 420.1B. Yet, in 2006, the LANS walk-down team recognized that this system had not been inspected since May 2004 and noted that deficient suppression systems could result in significantly high levels of property damage and loss. After we brought this issue to management's attention on February 6, 2009, LANS officials stated that the Laboratory would correct this deficiency. As with the problems involving the fire suppression system, we observed that LANS had not always corrected life safety deficiencies involving building exits at one of its primary facilities. This included providing a secondary emergency exit for a building with occupants on multiple floor levels. LANS had removed personnel from the third floor and improved the sprinkler system of the facility, but it had still not provided a secondary exit for personnel on the second floor by the time we completed our review. NNSA has since stated that this fire protection issue will be completely addressed by relocating personnel from the second floor. Perhaps most serious, our testing revealed that a number of deficien

None

2009-06-01T23:59:59.000Z

25

Analysis of Fire Calls to an Industrial Complex Over a 12-year Period  

SciTech Connect (OSTI)

This paper gives an analysis of fire calls from over a decade of operations at a process facility. These data include valid alarms, unwanted or false alarms, ambulance calls, and hazardous material cleanup calls. Of special interest are false alarms, which are not only a nuisance to facility productivity but are detrimental to public and facility safety. Of the fire calls listed here, over half were from false alarms. The results given are compared to National Fire Protection Association data. The data presented can serve as exemplar data for future facilities and can be compared to other operating facilities experiences.

L. C. Cadwallader

2009-03-01T23:59:59.000Z

26

Fire History in the Cherokee Nation of Oklahoma Michael C. Stambaugh & Richard P. Guyette &  

E-Print Network [OSTI]

Fire History in the Cherokee Nation of Oklahoma Michael C. Stambaugh & Richard P. Guyette & Joseph history in northeastern Oklahoma on lands once occupied by the Cherokee Nation. A fire event chronology American groups includ- ing Cherokee was significantly correlated (r=0.84) with the number of fires per

Stambaugh, Michael C

27

Review of the Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System, October 2012  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Department of Energy Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System August 2012 October 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy Table of Contents 1.0 Purpose................................................................................................................................................... 1 2.0 Assessment Background ........................................................................................................................ 1 3.0 Scope...................................................................................................................................................... 2

28

Review of the Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System, October 2012  

Broader source: Energy.gov (indexed) [DOE]

Department of Energy Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System August 2012 October 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy Table of Contents 1.0 Purpose................................................................................................................................................... 1 2.0 Assessment Background ........................................................................................................................ 1 3.0 Scope...................................................................................................................................................... 2

29

Y-12 Fire Protection Operations has new chief | Y-12 National Security  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Fire Protection ... Fire Protection ... Y-12 Fire Protection Operations has new chief Posted: July 25, 2012 - 3:45pm J. Scott Vowell was recently appointed chief of Fire Protection Operations at the Y-12 National Security Complex. Vowell joined the Y-12 staff in 1993. Prior to being appointed fire chief, he served as assistant fire chief and fire captain. Previously he served as fire inspector at Oak Ridge National Laboratory. The Clinton native served on the Clinton City Emergency 911 Board from 1997 to 2001 and was a firefighter with the City of Clinton Fire Department for seven years. A division of Y-12's Safeguards, Security and Emergency Services, Fire Protection Operations has a roster of approximately 90, including firefighters, battalion chiefs and support staff. It provides emergency

30

Sandia National Laboratories: Sandia Study Shows Large LNG Fires...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

ClimateECInfrastructure SecurityAnalysisSandia Study Shows Large LNG Fires Hotter but Smaller Than Expected Sandia Study Shows Large LNG Fires Hotter but Smaller Than Expected...

31

Independent Oversight Review of the Fire Protection Program at Lawrence Livermore National Laboratory, September 2013  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection Program at Fire Protection Program at Lawrence Livermore National Laboratory May 2011 February 2013 September 2013 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U. S. Department of Energy Table of Contents 1.0 Purpose .................................................................................................................................................... 1 2.0 Background ............................................................................................................................................. 1 3.0 Scope ....................................................................................................................................................... 2

32

Independent Oversight Review of the Fire Protection Program at Lawrence Livermore National Laboratory, September 2013  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Fire Protection Program at Fire Protection Program at Lawrence Livermore National Laboratory May 2011 February 2013 September 2013 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U. S. Department of Energy Table of Contents 1.0 Purpose .................................................................................................................................................... 1 2.0 Background ............................................................................................................................................. 1 3.0 Scope ....................................................................................................................................................... 2

33

Idaho National Engineering and Environmental Laboratory Wildland Fire Management Environmental Assessment  

Broader source: Energy.gov (indexed) [DOE]

72 72 April 2003 IDAHO NATIONAL ENGINEERING AND ENVIRONMENTAL LABORATORY WILDLAND FIRE MANAGEMENT ENVIRONMENTAL ASSESSMENT iii CONTENTS ACRONYMS.................................................................................................................................. v 1. INTRODUCTION ................................................................................................................... 1 1.1. Purpose and Need ......................................................................................................................... 1 1.2. Background................................................................................................................................... 1 1.3. Related Actions ............................................................................................................................

34

STANFORD TOXIC GAS ALARM SYSTEMS 6 September 1999  

E-Print Network [OSTI]

to the Fire Alarm outputs if the TGO Alarm is activated. 11. If a bunker is separate from a building, during a bunker evacuation, only the bunker will be evacuated. G a s S h u t d o w n L a b G a s S h u t d o w n L

35

E-Print Network 3.0 - alarm systems Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Location Fire Alarm Panel Location KnoxRetainer Box... Key Holder Office Phone Home Phone Cell ... Source: Texas A&M University, Institute for Applied Mathematics and...

36

SUBSURFACE VISUAL ALARM SYSTEM ANALYSIS  

SciTech Connect (OSTI)

The ''Subsurface Fire Hazard Analysis'' (CRWMS M&O 1998, page 61), and the document, ''Title III Evaluation Report for the Surface and Subsurface Communication System'', (CRWMS M&O 1999a, pages 21 and 23), both indicate the installed communication system is adequate to support Exploratory Studies Facility (ESF) activities with the exception of the mine phone system for emergency notification purposes. They recommend the installation of a visual alarm system to supplement the page/party phone system The purpose of this analysis is to identify data communication highway design approaches, and provide justification for the selected or recommended alternatives for the data communication of the subsurface visual alarm system. This analysis is being prepared to document a basis for the design selection of the data communication method. This analysis will briefly describe existing data or voice communication or monitoring systems within the ESF, and look at how these may be revised or adapted to support the needed data highway of the subsurface visual alarm. system. The existing PLC communication system installed in subsurface is providing data communication for alcove No.5 ventilation fans, south portal ventilation fans, bulkhead doors and generator monitoring system. It is given that the data communication of the subsurface visual alarm system will be a digital based system. It is also given that it is most feasible to take advantage of existing systems and equipment and not consider an entirely new data communication system design and installation. The scope and primary objectives of this analysis are to: (1) Briefly review and describe existing available data communication highways or systems within the ESF. (2) Examine technical characteristics of an existing system to disqualify a design alternative is paramount in minimizing the number of and depth of a system review. (3) Apply general engineering design practices or criteria such as relative cost, and degree of difficulty and complexity in determining requirements in adapting existing data communication highways to support the subsurface visual alarm system. These requirements would include such things as added or new communication cables, added Programmable Logic Controller (PLC), Inputs and Outputs (I/O), and communication hardware components, and human machine interfaces and their software operating system. (4) Select the best data communication highway system based on this review of adapting or integrating with existing data communication systems.

D.W. Markman

2001-08-06T23:59:59.000Z

37

Fire  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Fire Fire Nature Bulletin No. 51 Febraury 1, 1946 Forest Preserve District of Cook County Clayton F. Smith, President Roberts Mann, Superintendent of Conservation FIRE Most people firmly believe the ancient notion that the prairies and vacant lots should be burnt off "to make better grass." Many are doing so now. Boys who have seen their parents and neighbors kindling fires on vacant property frequently do likewise on the prairies. Recently there have been four fires in the forest preserves which spread from adjoining land. Burning does more harm than good. True, it gets rid of the old weed stalks and dried grass of last year, so that new grass shows green more quickly. But repeated burnings kill the good, nutritious grasses such as bluegrass, timothy and clover. The wildflowers disappear. All food and nesting cover for birds, rabbits and other wildlife is destroyed, just when they need it most. Thistles thrive. Only tough grasses of little value for pasture or hay, such as crabgrass and quackgrass, and the weeds survive.

38

Fire regimes and forest structure in a sky island mixed conifer forest, Guadalupe Mountains National Park, Texas, USA  

Science Journals Connector (OSTI)

Fire is a key disturbance agent in the fire-prone mixed conifer and ponderosa pine forests of the southwestern United States. Human activities (i.e., livestock grazing, logging, and fire suppression) have resulted in the exclusion of fire from these forests for the past century and fire exclusion has caused changes in forest structure and composition. This study quantifies spatial and temporal variability in fire regimes and forest change in a 1000-ha area of mixed conifer forest in Guadalupe Mountains National Park (GMNP), an area with an uncommon history of grazing and fire suppression. Dendroecological methods were used to quantify fire frequency, season, severity, and extent, as well as forest structural and compositional change. The mean composite fire return interval (CFI) for the study area was 4 years. Widespread fires were less frequent. The mean CFI for fires recorded in at least 10% of the samples collected was 9.2 years, and mean CFI for fires scarring at least 25% of samples was 16.3 years. Many of these widespread fires occurred in the 19th century. The mean point fire return interval (PFI) was longer at 24 years. Fire scars were primarily formed in the earliest portion of earlywood in annual rings, indicating that fires burned mainly in the spring, at the beginning of the growing season. The onset of grazing in the 1920s dramatically reduced fire frequency. An increase in tree density and a compositional shift from southwestern white pine (Pinus strobiformis Engelm.) to Douglas-fir (Pseudotsuga menziesii [Mirb.] Franco) coincides with the grazing era. In addition, the pre-ranching era was characterized by low-severity fires, while structural changes have resulted in a contemporary forest that is prone to high severity fire, as evidenced by two stand-replacing wildfires in GMNP in the 1990s.

John Sakulich; Alan H. Taylor

2007-01-01T23:59:59.000Z

39

Oversight Reports - Pacific Northwest National Laboratory | Department of  

Broader source: Energy.gov (indexed) [DOE]

Oversight Reports - Pacific Northwest National Laboratory Oversight Reports - Pacific Northwest National Laboratory Oversight Reports - Pacific Northwest National Laboratory September 9, 2013 Independent Oversight Review, Pacific Northwest National Laboratory - September 2013 Review of the Fire Protection Program at Pacific Northwest National Laboratory and the Fire Suppression System at the Radiochemical Processing Laboratory October 31, 2012 Independent Oversight Review, Pacific Northwest National Laboratory - October 2012 Review of the Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System January 30, 2012 Independent Activity Report, Pacific Northwest National Laboratory - January 2012 Pacific Northwest National Laboratory Orientation Visit

40

CRAD, Fire Protection- Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility  

Broader source: Energy.gov [DOE]

A section of Appendix C to DOE G 226.1-2 "Federal Line Management Oversight of Department of Energy Nuclear Facilities." Consists of Criteria Review and Approach Documents (CRADs) used for an assessment of the Fire Protection Program portion of an Operational Readiness Review at the Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility.

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


41

Measurements of air contaminants during the Cerro Grande fire at Los Alamos National Laboratory  

SciTech Connect (OSTI)

Ambient air sampling for radioactive air contaminants was continued throughout the Cerro Grande fire that burned part of Los Alamos National Laboratory. During the fire, samples were collected more frequently than normal because buildup of smoke particles on the filters was decreasing the air flow. Overall, actual sampling time was 96% of the total possible sampling time for the May 2000 samples. To evaluate potential human exposure to air contaminants, the samples were analyzed as soon as possible and for additional specific radionuclides. Analyses showed that the smoke from the fire included resuspended radon decay products that had been accumulating for many years on the vegetation and the forest floor that burned. Concentrations of plutonium, americium, and depleted uranium were also measurable, but at locations and concentrations comparable to non-fire periods. A continuous particulate matter sampler measured concentrations that exceeded the National Ambient Air Quality Standard for PM-10 (particles less than 10 micrometers in diameter). These high concentrations were caused by smoke from the fire when it was close to the sampler.

Eberhart, Craig

2010-08-01T23:59:59.000Z

42

Fire tests to evaluate the potential fire threat and its effects on HEPA filter integrity in cell ventilation at the Oak Ridge National Laboratory, Building 7920  

SciTech Connect (OSTI)

As a result of a DOE (Tiger Team) Technical Safety Appraisal (November 1990) of the Radiochemical Engineering Development Center (REDC), ORNL Building 7920, a number of fire protection concerns were identified. The primary concern was the perceived loss of ventilation system containment due to the thermal destruction and/or breaching of the prefilters and/or high-efficiency particulate air filters (HEPA `s) and the resultant radioactive release to the external environment. The following report describes the results of an extensive fire test program performed by the Fire Research Discipline (FRD) of the Special Projects Division of Lawrence Livermore National Lab (LLNL) and funded by ORNL to address these concerns. Full scale mock-ups of a REDC hot cell tank pit, adjacent cubicle pit, and associated ventilation system were constructed at LLNL and 13 fire experiments were conducted to specifically answer the questions raised by the Tiger Team. Our primary test plan was to characterize the burning of a catastrophic solvent spill (kerosene) of 40 liters and its effect on the containment ventilation system prefilters and HEPA filters. In conjunction with ORNL and Lockwood Greene we developed a test matrix that assessed the fire performance of the prefilters and HEPA filters; evaluated the fire response of the fiber reinforced plastic (FRP) epoxy ventilation duct work; the response and effectiveness of the fire protection system, the effect of fire in a cubicle on the vessel off-gas (VOG) elbow, and other fire safety questions.

Hasegawa, H.K.; Staggs, K.J.; Doughty, S.M. [Oak Ridge National Lab., TN (United States)

1992-12-01T23:59:59.000Z

43

Independent Oversight Review of the Fire Protection Program at the Pacific Northwest National Laboratory and the Fire Suppression System at the Radiochemical Processing Laboratory, September 2013  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Independent Oversight Review of the Independent Oversight Review of the Fire Protection Program at Pacific Northwest National Laboratory and the Fire Suppression System at the Radiochemical Processing Laboratory May 2011 February 2013 September 2013 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy Table of Contents 1.0 Purpose.................................................................................................................................................... 1 2.0 Background ............................................................................................................................................. 1 3.0 Scope....................................................................................................................................................... 2

44

Independent Oversight Review of the Fire Protection Program at the Pacific Northwest National Laboratory and the Fire Suppression System at the Radiochemical Processing Laboratory, September 2013  

Broader source: Energy.gov (indexed) [DOE]

Independent Oversight Review of the Independent Oversight Review of the Fire Protection Program at Pacific Northwest National Laboratory and the Fire Suppression System at the Radiochemical Processing Laboratory May 2011 February 2013 September 2013 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy Table of Contents 1.0 Purpose.................................................................................................................................................... 1 2.0 Background ............................................................................................................................................. 1 3.0 Scope....................................................................................................................................................... 2

45

Preventing Laboratory FiresPreventing Laboratory Fires AgendaAgenda  

E-Print Network [OSTI]

.contents. #12;Laboratory Fire CodeLaboratory Fire Code RegulationsRegulations #12;National Fire ProtectionNational Fire Protection Association (NFPA)Association (NFPA) NFPA 1NFPA 1 ­­ General Protection against FireGeneral Protection against Fire NFPA 10NFPA 10 ­­ Fire ExtinguishersFire Extinguishers NFPA 30NFPA 30 ­­ Flammable

Farritor, Shane

46

Fire Classifications Fires involving the ordinary  

E-Print Network [OSTI]

, plastics, etc. Fires involving combustible or flammable liquids such as gasoline, kerosene, oils, grease is protected by various devices such as smoke detectors, sprinkler systems, and manual fire alarm pull stations. Manual pull stations are strategically located throughout the University. Usually located by each exit

Jia, Songtao

47

Needs assessment for fire department services and resources for the Los Alamos National Laboratory, Los Alamos, New Mexico. Final report  

SciTech Connect (OSTI)

This report has been developed in response to a request from the Los Alamos National Laboratory (LANL) to evaluate the need for fire department services so as to enable the Laboratory to plan effective fire protection and thereby: meet LANL`s regulatory and contractual obligations; interface with the Department of Energy (DOE) and other agencies on matters relating to fire and emergency services; and ensure appropriate protection of the community and environment. This study is an outgrowth of the 1993 Fire Department Needs Assessment (prepared for DOE) but is developed from the LANL perspective. Input has been received from cognizant and responsible representatives at LANL, DOE, Los Alamos County (LAC) and the Los Alamos Fire Department (LAFD).

NONE

1995-11-15T23:59:59.000Z

48

HSL Fire Evacuation Plan HSL Appendix 1  

E-Print Network [OSTI]

to the assembly point ( in the car park opposite the side entrance of the library). All tag holders need to give should 7. Staff should remain at the Assembly point (by the wooden fence in the car park opposite/alarm, staff should report any shortcomings in the fire safety provision (e.g. defective fire alarm sounders

Anderson, Jim

49

Report on the Scope of the Accident Investigation of the Tristan Fire at the DOE Brookhaven National Laboratory, IG-0386  

Broader source: Energy.gov (indexed) [DOE]

4/93) 4/93) United States Government Department of Energy memorandum DATE: MARCH 15, 1996 REPLY TO ATTN OF: IG-1 SUBJECT: INFORMATION: Report on lSummary Results of the Inspection of Issues Regarding the Scope of the Accident Investigation of the TRISTAN Fire at the Brookhaven National Laboratoryn TO: The Secretary BACKGROUND: The subject final report is provided to inform you of our findings and recommendations concerning our review of issues regarding the scope of the accident investigation of a March 31, 1994, fire at the Terrific Reactor Isotope Separator To Analyze Nuclides (TRISTAN) experiment at the Department of Energy (DOE) Brookhaven National Laboratory

50

Substation alarm multiplexing system (SAMS)  

SciTech Connect (OSTI)

This paper describes an on going R&D project to develop, design, install, and assess the field performance of an advanced substation alarm system. SAMS provides a highly fault-tolerant system for the reporting of equipment alarms. SAMS separates and identifies each of the multiple alarm contacts, transmits an alarm condition over existing substation two-wire system, and displays the alarm source, and its associated technical information, on a touch-screen monitor inside the substation control room, and a remote central location and on a hand held terminal which may be carried anywhere within the substation. SAMS is currently installed at the Sherman Creek substation in the Bronx for the purpose of a three month field evaluation.

ElBadaly, H.; Gaughan, J.; Ward, G.; Amengual, S.

1996-03-01T23:59:59.000Z

51

Review of the Los Alamos National Laboratory Chemistry and Metallurgy Research Facility Fire Suppression Vital Safety System, January 2012  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

the the Los Alamos National Laboratory Chemistry and Metallurgy Research Facility Fire Suppression Vital Safety System January 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy i Table of Contents 1.0 Purpose ................................................................................................................................................... 1 2.0 Background ............................................................................................................................................ 1 3.0 Scope ...................................................................................................................................................... 1

52

Review of the Los Alamos National Laboratory Chemistry and Metallurgy Research Facility Fire Suppression Vital Safety System, January 2012  

Broader source: Energy.gov (indexed) [DOE]

the the Los Alamos National Laboratory Chemistry and Metallurgy Research Facility Fire Suppression Vital Safety System January 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy i Table of Contents 1.0 Purpose ................................................................................................................................................... 1 2.0 Background ............................................................................................................................................ 1 3.0 Scope ...................................................................................................................................................... 1

53

Type B Accident Investigation of the January 10, 2006, Flash Fire and Injury at the Savannah River National Laboratory  

Broader source: Energy.gov [DOE]

On January 10, 2006, at approximately 7:47 a.m., a first-line manager (FLM) at the Savannah River National Laboratory (SRNL) received first- and second-degree burns to his head, face, neck, and left hand that required hospitalization after a flash fire occurred during equipment cleaning operations in SRNL Laboratory D-1169.

54

Independent Oversight Review of the Technical Area 55 Safety Class Fire Suppression System at Los Alamos National Laboratory, December 2013  

Broader source: Energy.gov (indexed) [DOE]

Technical Area 55 Technical Area 55 Safety Class Fire Suppression System at Los Alamos National Laboratory December 2013 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy Table of Contents 1.0 Purpose .................................................................................................................................................... 1 2.0 Background ............................................................................................................................................. 1 3.0 Scope ....................................................................................................................................................... 2

55

Annual Fire Report Page 1 of 4 Residence Hall/Historic Houses Fire Protection Equipment  

E-Print Network [OSTI]

Annual Fire Report Page 1 of 4 Residence Hall/Historic Houses Fire Protection Equipment 2012 Residence Hall/Historic Houses Fire Protection Equipment 2012 Calendar Year 24 Bull Street Annex-House X X X Calendar Year College of Charleston Residence Halls and Historic Housing Facilities Fire alarm monitoring

Kasman, Alex

56

Functional relationship-based alarm processing system  

DOE Patents [OSTI]

A functional relationship-based alarm processing system and method analyzes each alarm as it is activated and determines its relative importance with other currently activated alarms and signals in accordance with the functional relationships that the newly activated alarm has with other currently activated alarms. Once the initial level of importance of the alarm has been determined, that alarm is again evaluated if another related alarm is activated or deactivated. Thus, each alarm's importance is continuously updated as the state of the process changes during a scenario. Four hierarchical relationships are defined by this alarm filtering methodology: (1) level precursor (usually occurs when there are two alarm settings on the same parameter); (2) direct precursor (based on causal factors between two alarms); (3) required action (system response or action expected within a specified time following activation of an alarm or combination of alarms and process signals); and (4) blocking condition (alarms that are normally expected and are not considered important). The alarm processing system and method is sensitive to the dynamic nature of the process being monitored and is capable of changing the relative importance of each alarm as necessary. 12 figs.

Corsberg, D.R.

1988-04-22T23:59:59.000Z

57

Fire Protection  

Broader source: Directives, Delegations, and Requirements [Office of Management (MA)]

This Standard was developed to provide acceptable methods and approaches for meeting DOE fire protection program and design requirements and to address special or unique fire protection issues at DOE facilities that are not comprehensively or adequately addressed in national consensus standards or other design criteria.

2012-12-05T23:59:59.000Z

58

The Best Ever Alarm System Toolkit  

SciTech Connect (OSTI)

Learning from our experience with the standard Experimental Physics and Industrial Control System (EPICS) alarm handler (ALH) as well as a similar intermediate approach based on script-generated operator screens, we developed the Best Ever Alarm System Toolkit (BEAST). It is based on Java and Eclipse on the Control System Studio (CSS) platform, using a relational database (RDB) to store the configuration and log actions. It employs a Java Message Service (JMS) for communication between the modular pieces of the toolkit, which include an Alarm Server to maintain the current alarm state, an arbitrary number of Alarm Client user interfaces (GUI), and tools to annunciate alarms or log alarm related actions. Web reports allow us to monitor the alarm system performance and spot deficiencies in the alarm configuration. The Alarm Client GUI not only gives the end users various ways to view alarms in tree and table, but also makes it easy to access the guidance information, the related operator displays and other CSS tools. It also allows online configuration to be simply modified from the GUI. Coupled with a good "alarm philosophy" on how to provide useful alarms, we can finally improve the configuration to achieve an effective alarm system.

Kasemir, Kay [ORNL; Chen, Xihui [ORNL; Danilova, Katia [ORNL

2009-01-01T23:59:59.000Z

59

Intelligent Economic Alarm Processor (IEAP)  

E-Print Network [OSTI]

): ?The 21st Substation Design?, and ??Verifying Interoperability and Application Performance of PMUs and PMU-enabled IEDs at the Device and System Level?. The fourth one is funded by Advanced Research Agency- Energy (ARPA-E) through Green Electricity... .......................................................................................................... 52? 4. USE OF SUBSTATION IED DATA TO IMPROVE ALARM PROCESSING ........ 53? 4.1? Introduction ...................................................................................................... 53? 4.2? Substation IED Data...

Guan, Yufan

2013-08-06T23:59:59.000Z

60

Quantification of uranium transport away from firing sites at Los Alamos National Laboratory: A mass balance approach  

SciTech Connect (OSTI)

Investigations were conducted at Los Alamos National Laboratory to quantify the extent of migration of depleted uranium away from firing sites. Extensive sampling of air particles, soil, sediment, and water was conducted to establish the magnitude of uranium contamination throughout one watershed. The uranium source term was estimated, and mass balance calculations were performed to compare the percentage of migrated uranium with original expenditures. Mass balance calculations can be powerful in identification of the extent of waste migration and used as an aid in planning future waste investigations.

Becker, N.M.

1992-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


61

Quantification of uranium transport away from firing sites at Los Alamos National Laboratory: A mass balance approach  

SciTech Connect (OSTI)

Investigations were conducted at Los Alamos National Laboratory to quantify the extent of migration of depleted uranium away from firing sites. Extensive sampling of air particles, soil, sediment, and water was conducted to establish the magnitude of uranium contamination throughout one watershed. The uranium source term was estimated, and mass balance calculations were performed to compare the percentage of migrated uranium with original expenditures. Mass balance calculations can be powerful in identification of the extent of waste migration and used as an aid in planning future waste investigations.

Becker, N.M.

1992-02-01T23:59:59.000Z

62

Material control and accountability (MC&A) recovery from the Cerro Grande fire at Los Alamos National Laboratory  

SciTech Connect (OSTI)

During the week of May 10-14, 2000, the Cerro Grande Fire scorched over 40,000 acres of prime forestland and destroyed over 400 homes in the Los Alamos community and several structures at the Los Alamos National Laboratory (LANL). Of the land affected by the fire, nearly one quarter of it was Laboratory property. All of LANL's 64 material balance areas (MBAs) were affected to some degree, but one Category I technical area and several Category I11 and IV areas sustained heavy damage. When the MC&A personnel were allowed to return to work on May 23, they addressed the following problems: How do we assure both ourselves and the Department of Energy (DOE) that no nuclear materials had been compromised? How do we assist the nuclear material (NM) custodians and their operating groups so that they can resume normal MC&A operations? Immediately after the return to work, the Laboratory issued emergency MC&A assurance actions for Category I through Category IV facilities. We conducted special inventories, area walkthroughs, and other forms of evaluation so that within a month after the fire, we were able to release the last MBA to resume work and assure that all nuclear material had been accounted for. This paper discusses the measures LANL adopted to ensure that none of its nuclear material had been compromised.

Haag, William Earl

2001-01-01T23:59:59.000Z

63

CRAD, Fire Protection- Oak Ridge National Laboratory High Flux Isotope Reactor  

Broader source: Energy.gov [DOE]

A section of Appendix C to DOE G 226.1-2 "Federal Line Management Oversight of Department of Energy Nuclear Facilities." Consists of Criteria Review and Approach Documents (CRADs) used for a February 2006 Commencement of Operations assessment of the Fire Protection program at the Idaho Accelerated Retrieval Project Phase II.

64

Implementation of National Fire Plan treatments near the wildlandurban interface in the western  

E-Print Network [OSTI]

, and Teresa B. Chapmana aDepartment of Geography, 260 UCB, University of Colorado, Boulder, CO 80309; b of Natural Resources and Natural Resource Ecology Laboratory, Colorado State University, Fort Collins, CO to restore historical fire behavior and mitigate wildfire risk. During the last 5 years (2004­ 2008), 44

Nelson, Cara

65

HOME INSECURITY: NO ALARMS, FALSE ALARMS, AND SIGINT  

SciTech Connect (OSTI)

The market share of home security systems has substantially increased as vendors incorporate more desirable features: intrusion detection, automation, wireless, and LCD touch panel controls. Wireless connectivity allows vendors to manufacture cheaper, more featureful products that require little to no home modification to install. Consumer win, since adding devices is easier. The result: an ostensibly more secure, convenient, and connected home for a larger number of citizens. Sadly, this hypothesis is flawed; the idea of covering a home with more security sensors does not translate into a more secure home. Additionally, the number of homes using these vulnerable systems is large, and the growth rate is increasing producing a even larger problem. In this talk, I will demonstrate a generalized approach for compromising three systems: ADT, the largest home security dealer in North America; Honeywell, one of the largest manufacturers of security devices; and Vivint, a top 5 security dealer. We will suppress alarms, create false alarms, and collect artifacts that facilitate tracking the movements of individuals in their homes.

Lamb, Logan M [ORNL

2014-01-01T23:59:59.000Z

66

H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2010.doc Annual Fire Safety Report  

E-Print Network [OSTI]

. Building Sprinkler System? % Sprinkler Monitored Fire Alarm? Smoke Detection Extinguisher Devices Placards of vehicle parts, fuel and oil is prohibited. l. Hallways must remain clear at all times for safety in case Safety Systems The following table describes each on-campus residential facility fire safety system

Sze, Lawrence

67

DOE/SEA-03; Special Environmental Analysis for the Department of Energy, National Nuclear Security Administration, Actions Taken in Response to the Cerro Grande Fire at Los Alamos National Laboratory, Los Alamos, New Mexico (September 2000)  

Broader source: Energy.gov (indexed) [DOE]

Analysis for Actions Taken in Response to the Cerro Grande Fire at LANL Analysis for Actions Taken in Response to the Cerro Grande Fire at LANL DOE/LAAO September 2000 S-1 SUMMARY The U.S. Department of Energy (DOE), National Nuclear Security Administration, is issuing this special environmental analysis (SEA) to document its assessment of impacts associated with emergency activities conducted at Los Alamos National Laboratory (LANL), Los Alamos County, New Mexico, in response to major disaster conditions caused by the recent wildfire known as the Cerro Grande Fire. This wildfire burned about 7,650 1 acres (ac) (3,061 hectares [ha]) within the boundaries of LANL and about an additional 35,500 ac (14,200 ha) in neighboring areas. DOE's emergency response to the threat of this fire began with certain preventative actions undertaken immediately before

68

DOE/SEA-03; Special Environmental Analysis for the Department of Energy, National Nuclear Security Administration, Actions Taken in Response to the Cerro Grande Fire at Los Alamos National Laboratory, Los Alamos, New Mexico (September 2000)  

Broader source: Energy.gov (indexed) [DOE]

Analysis Analysis Actions taken in Response to the Cerro Grande Fire at Los Alamos National Laboratory, Los Alamos, New Mexico September 2000 U.S. Department of Energy Los Alamos Area Office Los Alamos, New Mexico for the Department of Energy, National Nuclear Security Administration DOE/SEA-03 COVER SHEET Responsible Agency: U.S. Department of Energy (DOE), National Nuclear Security Administration Title: Special Environmental Analysis for the Department of Energy, National Nuclear Security Administration, Actions Taken in Response to the Cerro Grande Fire at Los Alamos National Laboratory, Los Alamos, New Mexico Contacts: For further information on this Special Environmental Analysis (SEA) or to provide comments contact: Ms. Elizabeth Withers SEA Document Manager Los Alamos Area Office,

69

Reduction of fire hazards on large mining equipment  

SciTech Connect (OSTI)

Although standards and regulations are in place to prevent large mining equipment fires, recent analyses of mine accident data show that mining equipment fires still occur with alarming frequency and grave consequences, particularly at all surface mines and in underground metal/nonmetal mines. Recently technological advances in fire protection, combined with the statistical data on equipment fires, led NIOSH to reinvestigate this and to improve operator safety. NIOSH demonstrated that newly developed technologies, such as dual cab fire inerting systems and engine compartment fire barriers, can greatly enhance operator safety and lessen the damage of property during large mobile equipment fires. 10 refs., 5 figs.

Maria I. De Rosa

2008-09-15T23:59:59.000Z

70

Dynamic alarm presentation in a nuclear plant control room  

DOE Patents [OSTI]

The alarm activation set point and priority for a given, spatially fixed alarm tile can vary depending in part on the mode of plant operation.

Kenneth, Scarola (Windsor, CT); Jamison, David S. (Windsor, CT); Manazir, Richard M. (North Canton, CT); Rescorl, Robert L. (Vernon, CT); Harmon, Daryl L. (Enfield, CT)

1994-01-01T23:59:59.000Z

71

False Alarms and Close Calls: A Conceptual Model of Warning Accuracy LINDSEY R. BARNES*  

E-Print Network [OSTI]

of the key metrics for verifying National Weather Service (NWS) weather warnings. The national FAR, Health, & Hazards Center, Colorado Springs, Colorado Submitted to Weather and Forecasting Forecasters. In addition, we argue that the metrics used to evaluate false alarms do not accurately represent the numbers

Schultz, David

72

Cerro Grande Fire Impact to Water Quality and Stream Flow near Los Alamos National Laboratory: Results of Four Years of Monitoring  

SciTech Connect (OSTI)

In May 2000, the Cerro Grande fire burned about 7400 acres of mixed conifer forest on the Los Alamos National Laboratory (LANL), and much of the 10,000 acres of mountainside draining onto LANL was severely burned. The resulting burned landscapes raised concerns of increased storm runoff and transport of contaminants by runoff in the canyons traversing LANL. The first storms after the fire produced runoff peaks that were more than 200 times greater than prefire levels. Total runoff volume for the year 2000 increased 50% over prefire years, despite a decline in total precipitation of 13% below normal and a general decrease in the number of monsoonal thunderstorms. The majority of runoff in 2000 occurred in the canyons at LANL south of Pueblo Canyon (70%), where the highest runoff volume occurred in Water Canyon and the peak discharge occurred in Pajarito Canyon. This report describes the observed effects of the Cerro Grande fire and related environmental impacts to watersheds at and near Los Alamos National Laboratory (LANL) for the first four runoff seasons after the fire, from 2000 through 2003. Spatial and temporal trends in radiological and chemical constituents that were identified as being associated with the Cerro Grande fire and those that were identified as being associated with historic LANL discharges are evaluated with regard to impacts to the Rio Grande and area reservoirs downstream of LANL. The results of environmental sampling performed by LANL, the New Mexico Environment Department (NMED), and U.S. Geological Survey (USGS) after the Cerro Grande fire are included in the evaluation. Effects are described for storm runoff, baseflow, stream sediments, and area regional reservoir sediment.

B.M. Gallaher; R.J. Koch

2004-09-15T23:59:59.000Z

73

Initial Joint Review of Wildland Fire Safety at DOE Sites  

Broader source: Energy.gov (indexed) [DOE]

Wildland Fire" November 2000 2. U.S. Fish & Wildlife, "24 Command Fire, A National Level Review by the Interagency Fire Team," September 2000 INEEL Site (Tea Kettle Fire, etc.) In...

74

Understanding Mixed Conifer Forests in Yosemite National Park: An Historical Analysis of Fire Regimes and Vegetation Dynamics.  

E-Print Network [OSTI]

??This dissertation presents the results of an historical ecological analysis that quantifies the temporal and spatial variation in forest structure and fire regimes in the (more)

Scholl, Andrew

2008-01-01T23:59:59.000Z

75

Alarm acknowledgement in a nuclear plant control room  

DOE Patents [OSTI]

Alarm acknowledgment can be made not only at the alarm tile array of a given console but via other touch sensitive alarm indications in the screen displays of the monitoring system at the same or other consoles; also, touching one tile can acknowledge multiple alarm sources.

Scarola, Kenneth (Windsor, CT); Jamison, David S. (Windsor, CT); Manazir, Richard M. (North Canton, CT); Rescorl, Robert L. (Vernon, CT); Harmon, Daryl L. (Enfield, CT)

1994-01-01T23:59:59.000Z

76

Wildland Fire Management Program  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Significant Wildland Fire Potential Outlook Significant Wildland Fire Potential Outlook Predictive Services National Interagency Fire Center Issued: June 1, 2013 Next Issuance: July 1, 2013 Outlook Period - June, July and August through September Executive Summary The June, July and August through September 2013 significant wildland fire potential forecasts included in this outlook represent the cumulative forecasts of the eleven Geographic Area Predictive Services Units and the National Predictive Services Unit. June - Significant fire potential will be above normal for much of the interior mountains and foothills of California, the Sacramento Valley, and adjacent lower foothills as well as the coastal areas. - Significant fire potential will increase to above normal in Arizona, western New Mexico, and far

77

Identification of Process Hazards and Accident Scenarios for Site 300 B-Division Firing Areas, Lawrence Livermore National Laboratory  

SciTech Connect (OSTI)

This report describes a hazard and accident analysis conducted for Site 300 operations to support update of the ''Site 300 B-Division Firing Areas Safety Analysis Report'' (SAR) [LLNL 1997]. A significant change since the previous SAR is the construction and the new Contained Firing Facility (CFF). Therefore, this hazard and accident analysis focused on the hazards associated with bunker operations to ensure that the hazards at CFF are properly characterized in the updated SAR. Hazard tables were created to cover both the CFF and the existing bunkers with ''open air'' firing tables.

Lambert, H; Johnson, G

2001-05-04T23:59:59.000Z

78

Pressurized security barrier and alarm system  

DOE Patents [OSTI]

A security barrier for placement across a passageway is made up of interconnected pressurized tubing made up in a grid pattern with openings too small to allow passage. The tubing is connected to a pressure switch, located away from the barrier site, which activates an alarm upon occurrence of a pressure drop. A reinforcing bar is located inside and along the length of the tubing so as to cause the tubing to rupture and set off the alarm upon an intruder`s making an attempt to crimp and seal off a portion of the tubing by application of a hydraulic tool. Radial and rectangular grid patterns are disclosed. 7 figures.

Carver, D.W.

1995-04-11T23:59:59.000Z

79

ANNUAL FIRE SAFETY RESIDENCE HALLS  

E-Print Network [OSTI]

protection systems. Documents in the following websites are referenced in the report: · www.fau.edu/facilities/EH&S/safety/fire evacuation procedures. · Inspecting, testing and maintaining fire protection systems in accordance with National Fire Protection Association (NFPA) standards. · Performing plan reviews and code consultation

Fernandez, Eduardo

80

Report on summary results of the inspection of issues regarding the scope of the accident investigation of the TRISTAN Fire at the Brookhaven National Laboratory  

SciTech Connect (OSTI)

The subject final report is provided to inform you of our findings and recommendations concerning our review of issues regarding the scope of the accident investigation of a March 31, 1994, fire at the Terrific Reactor Isotope Separator To Analyze Nuclides (TRISTAN) experiment at the Department of Energy (DOE) Brookhaven National Laboratory (BNL), Upton, New York. The Chicago Operations Office (CH) Manager appointed a Type B Accident Investigation Board (Board) to investigate the fire. In a June 16, 1994, letter to the Inspector General, DOE, the CH Manager requested the Inspector General to look into an allegation by a former Board member that senior Chicago management consciously violated the requirements of DOE Order 5484.1, {open_quotes}Environmental Protection, Safety, And Health Protection Information Reporting Requirements,{close_quotes} in attempting to control the investigation. The former Board member alleged that there was not a clear verbal agreement among the Board members regarding the focus of the scope of the investigation. He said that the Board Chairman wanted to focus on the physical causes of the fire, while he (the former Board member) believed that the Board should focus on the apparent management deficiencies that allowed TRISTAN to operate without a proper safety analysis and in violation of DOE orders for so many years.

NONE

1996-03-01T23:59:59.000Z

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


81

Door Placard for No Automatic Fire Alarm with Automatic Fire Sprinkler Protection System  

E-Print Network [OSTI]

apartment with wet towels or sheets, and seal air ducts or other openings where smoke may enter Open address, floor, apartment number and the number of people in your apartment Seal the doors to your

Pawlowski, Wojtek

82

Door Placard for Full Fire Alarm and Sprinkler Fire Code Compliance  

E-Print Network [OSTI]

apartment with wet towels or sheets, and seal air ducts or other openings where smoke may enter Open address, floor, apartment number and the number of people in your apartment Seal the doors to your

Pawlowski, Wojtek

83

Door Placard for Fire Alarm and No Sprinkler System Fire Code Compliance  

E-Print Network [OSTI]

apartment with wet towels or sheets, and seal air ducts or other openings where smoke may enter Open address, floor, apartment number and the number of people in your apartment Seal the doors to your

Pawlowski, Wojtek

84

Review of the Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility Fire Suppression System, January 2012  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Waste Waste Characterization, Reduction, and Repackaging Facility Fire Suppression System January 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy i Table of Contents 1.0 Purpose ................................................................................................................................................... 1 2.0 Background ............................................................................................................................................ 1 3.0 Scope ...................................................................................................................................................... 1

85

Review of the Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility Fire Suppression System, January 2012  

Broader source: Energy.gov (indexed) [DOE]

Waste Waste Characterization, Reduction, and Repackaging Facility Fire Suppression System January 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy i Table of Contents 1.0 Purpose ................................................................................................................................................... 1 2.0 Background ............................................................................................................................................ 1 3.0 Scope ...................................................................................................................................................... 1

86

calgary.ca/fire | call 3-1-1 Student Fire  

E-Print Network [OSTI]

or accidentally burning toast) Batteries are replaced yearly (ask the landlord when it was last done) Alarms can mean nobody, smokes in bed baSement Furnace and hot water tank are clear of stuff that can burn in planters, on grass, in peat moss or mulch (almost empty "beverage" cans work well) Fire pits

Habib, Ayman

87

Statement by Secretary Moniz on National Climate Assessment ...  

Office of Environmental Management (EM)

National Climate Assessment: "The scientific community has been sounding the alarm over climate change for decades, and the 3rd U.S. National Climate Assessment released today...

88

Oversight Reports - Pacific Northwest National Laboratory | Department...  

Broader source: Energy.gov (indexed) [DOE]

Oversight Review, Pacific Northwest National Laboratory - September 2013 Review of the Fire Protection Program at Pacific Northwest National Laboratory and the Fire Suppression...

89

Stone Fire  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Effect of Change in Cookstove Types on Visibility - Case Study of the Berkeley-Darfur Stove and Three- Stone Fire Extended Abstract #1 Yungang Wang, Ashok J. Gadgil, Thomas W. Kirchstetter Environmental Energy Technologies Division Indoor Environment Group Lawrence Berkeley National Laboratory Berkeley, CA September 2012 This publication was made possible by grant number 500-99-013 from the California Energy Commission (CEC). This work was also supported by the Assistant Secretary for Energy Efficiency and Renewable Energy, Building Technologies Program of the U.S. Department of Energy under contract DE- AC02- 05CH11231. LBNL-6291E LBNL-6291E Disclaimer This document was prepared as an account of work sponsored by the United States

90

Chemical Concentrations in Field Mice from Open-Detonation Firing Sites TA-36 Minie and TA-39 Point 6 at Los Alamos National Laboratory  

SciTech Connect (OSTI)

Field mice (mostly Peromyscus spp.) were collected at two open-detonation (high explosive) firing sites - Minie at Technical Area (TA) 36 and Point 6 at TA-39 - at Los Alamos National Laboratory in August of 2010 and in February of 2011 for chemical analysis. Samples of whole body field mice from both sites were analyzed for target analyte list elements (mostly metals), dioxin/furans, polychlorinated biphenyl congeners, high explosives, and perchlorate. In addition, uranium isotopes were analyzed in a composite sample collected from TA-36 Minie. In general, all constituents, with the exception of lead at TA-39 Point 6, in whole body field mice samples collected from these two open-detonation firing sites were either not detected or they were detected below regional statistical reference levels (99% confidence level), biota dose screening levels, and/or soil ecological chemical screening levels. The amount of lead in field mice tissue collected from TA-39 Point 6 was higher than regional background, and some lead levels in the soil were higher than the ecological screening level for the field mouse; however, these levels are not expected to affect the viability of the populations over the site as a whole.

Fresquez, Philip R. [Los Alamos National Laboratory

2011-01-01T23:59:59.000Z

91

Reaching an agreement to build a new coal-fired power plant near a national park by mitigating potential environmental impacts  

SciTech Connect (OSTI)

This paper presents an interesting example of compromise through comprehensive environmental analysis and intensive negotiation to build a coal-fired power plant near an environmentally sensitive area. In December 1993, the US Department of Energy (DOE) completed the final environmental impact statement (EIS) for the Healy Clean Coal Project (HCCP), a proposed demonstration project that would be cost-shared by DOE and the Alaska Industrial Development and Export Authority (AIDEA). The HCCP would be built adjacent to the existing coal-fired Golden Valley Electric Association, Inc. (GVEA) Unit No. 1 in Healy, Alaska, about 4 miles north of Denali National Park and Preserve (DNPP). In response to US Department of the Interior (DOI) concerns about potential air quality related impacts on DNPP, DOE facilitated negotiations among DOI, AIDEA, and GVEA which overcame a ``stalemate`` situation. A Memorandum of Agreement was signed by all four parties, enabling DOI to withdraw its objections. The cornerstone of the Agreement is the planned retrofit of Unit No. 1 to reduce emissions of sulfur dioxide and oxides of nitrogen. if the demonstration technologies operate as expected, combined emissions from the Healy site would increase by only about 8% but electrical generation would triple. The Agreement is a ``win/win`` outcome: DOE can demonstrate the new technologies, AIDEA can build a new power plant for GVEA to operate, and DOI can safeguard the pristine environment of DNPP.

Miller, R.L. [Oak Ridge National Lab., TN (United States); Ruppel, T.C.; Evans, E.W.; Heintz, S.J. [USDOE Pittsburgh Energy Technology Center, PA (United States)

1994-12-31T23:59:59.000Z

92

Alarm system for a nuclear control complex  

DOE Patents [OSTI]

An advanced control room complex for a nuclear power plant, including a discrete indicator and alarm system (72) which is nuclear qualified for rapid response to changes in plant parameters and a component control system (64) which together provide a discrete monitoring and control capability at a panel (14-22, 26, 28) in the control room (10). A separate data processing system (70), which need not be nuclear qualified, provides integrated and overview information to the control room and to each panel, through CRTs (84) and a large, overhead integrated process status overview board (24). The discrete indicator and alarm system (72) and the data processing system (70) receive inputs from common plant sensors and validate the sensor outputs to arrive at a representative value of the parameter for use by the operator during both normal and accident conditions, thereby avoiding the need for him to assimilate data from each sensor individually. The integrated process status board (24) is at the apex of an information hierarchy that extends through four levels and provides access at each panel to the full display hierarchy. The control room panels are preferably of a modular construction, permitting the definition of inputs and outputs, the man machine interface, and the plant specific algorithms, to proceed in parallel with the fabrication of the panels, the installation of the equipment and the generic testing thereof.

Scarola, Kenneth (Windsor, CT); Jamison, David S. (Windsor, CT); Manazir, Richard M. (North Canton, CT); Rescorl, Robert L. (Vernon, CT); Harmon, Daryl L. (Enfield, CT)

1994-01-01T23:59:59.000Z

93

Using active database techniques for an advanced alarm processing  

SciTech Connect (OSTI)

An Advanced Alarm System (AAS) is primarily a digital system employing advanced alarm process logics and a VDU (Visual Display Unit) based control and display for the alarms. Active Database Systems (ADSs) are able to monitor a special situation represented by an event and one or more conditions. When the event occurs and the conditions are evaluated as true, the corresponding actions are executed. Hence, ADSs can recognize specific situations and react to them without direct explicit user or application requests. ADSs are very useful for timely applications such as the advanced, alarm processing. This paper proposes a new approach to the advanced alarm processing by using Event-Condition- Action(ECA) rules that can be automatically triggered by an active database. And this paper describes the design considerations and solution plan for advanced alarm processing by using active database techniques. (authors)

Jang, G. S. [I and C HFE Dept., Korea Atomic Energy Research Inst., 150, Duckjin-dong, Yusung-ku, Daejeon 305-353 (Korea, Republic of); Seong, D. H. [Samchang Enterprise Co., LTD, 974-1, Goyean-ri, Ulju-gun, Ulsan, 689-871 (Korea, Republic of); Keum, J. Y.; Park, H. Y. [I and C HFE Dept., Korea Atomic Energy Research Inst., 150, Duckjin-dong, Yusung-ku, Daejeon 305-353 (Korea, Republic of); Kim, Y. K. [Dept. of Computer Science, Chungnam National Univ., Daejeon, 305-764 (Korea, Republic of)

2006-07-01T23:59:59.000Z

94

Technical basis for setting Hanford Fire Department electronic dosimetry for emergency response (TBD-HSO-RC-009)  

SciTech Connect (OSTI)

This document addresses the need to establish a reasonable methodology for establishing alarm points for electronic dosimetry used by the Hanford Fire Department (HFD) for emergency response in radiological facilities.

EVANS, C.L.

2003-04-01T23:59:59.000Z

95

Emergency, Fire Information  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Emergency, Fire Information Emergency, Fire Information Emergency, Fire Information Protecting our people, emergency personnel, national security information, facilities, lands, and neighboring communities. Contact Communications Office (505) 667-7000 Email LANL Update (505) 667-6622 or (877) 723-4101 toll-free Emergency Public Information In the event of an emergency, Los Alamos National Laboratory will provide you with needed information here as it becomes available. The Los Alamos Site Office/Los Alamos National Laboratory Emergency Public Information Plan provides a framework for coordinated, accurate, and timely release of information to Laboratory employees, the news media, potentially affected members of the public, and other stakeholders. Want emergency news emailed to you? Subscribe here.

96

Allegations Regarding the Consolidation of Central Alarm Stations...  

Energy Savers [EERE]

Allegations Regarding the Consolidation of Central Alarm Stations at the Oak Ridge Reservation DOEIG-0929 December 2014 U.S. Department of Energy Office of Inspector General...

97

Y-12 Opens New NNSA Alarm Response Training Academy | National...  

National Nuclear Security Administration (NNSA)

Response Training Program has been in operation for more than five years and has helped train some 3,400 on-site radiation safety and security personnel, local law enforcement...

98

Y-12 Opens New NNSA Alarm Response Training Academy | National...  

National Nuclear Security Administration (NNSA)

Z machine helps scientists understand the sun's heart NNSA Blog Livermore researchers create new technology for first responders NNSA Blog Annular Core Research Reactor - Critical...

99

Alarm Response Training Academy opens at Y-12 | National Nuclear...  

National Nuclear Security Administration (NNSA)

Harrington, NNSA Deputy Administrator, Defense Nuclear Nonproliferation; and Morgan Smith, Chief Operating Officer, Consolidated Nuclear Security. The free course taught at...

100

Tracking New Coal-Fired Power Plants  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

January 8, 2010 National Energy Technology Laboratory Office of Systems Analyses and Planning Erik Shuster 2 Tracking New Coal-Fired Power Plants This report is intended to...

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


101

CRAD, Environmental Protection - Los Alamos National Laboratory...  

Broader source: Energy.gov (indexed) [DOE]

National Laboratory Waste Characterization, Reduction, and Repackaging Facility CRAD, Fire Protection - Los Alamos National Laboratory Waste Characterization, Reduction, and...

102

CRAD, Radiological Controls - Los Alamos National Laboratory...  

Broader source: Energy.gov (indexed) [DOE]

National Laboratory Waste Characterization, Reduction, and Repackaging Facility CRAD, Fire Protection - Los Alamos National Laboratory Waste Characterization, Reduction, and...

103

FIRE WATCH FORM University Fire Marshal  

E-Print Network [OSTI]

the Fire Code of New York State that pertain to the impairment of a fire protection system to the impairment of a fire protection system Fire Code of New York State Chapter-9 "Fire Protection Systems" 901.7 Systems out of service. Where a required fire protection system is out of service, the fire department

Pawlowski, Wojtek

104

Independent Oversight Review of the Fire Protection Program and...  

Office of Environmental Management (EM)

Tanks NFPA National Fire Protection Association OFI Opportunity for Improvement OREM Oak Ridge Environmental Management ORNL Oak Ridge National Laboratory PB Process Building...

105

Cold Vacuum Drying facility fire protection system design description (SYS 24)  

SciTech Connect (OSTI)

This document describes the Cold Vacuum Drying Facility (CVDF) fire protection system (FPS). The FPS provides fire detection, suppression, and loss limitation for the CVDF structure, personnel, and in-process spent nuclear fuel. The system provides, along with supporting interfacing systems, detection, alarm, and activation instrumentation and controls, distributive piping system, isolation valves, and materials and controls to limit combustibles and the associated fire loadings.

PITKOFF, C.C.

1999-07-06T23:59:59.000Z

106

E-Print Network 3.0 - alarm system analysis Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

(SAS) to monitor scientific equipment that is critical to ongoing... Equipment System (AES): The notebook found at various alarm panels Scientific Alarm System (SAS... ): The...

107

Independent Oversight Review, Pacific Northwest National Laboratory- October 2012  

Broader source: Energy.gov [DOE]

Review of the Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System

108

Fire Egress  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

OSHAX.org - OSHAX.org - The Unofficial Guide To the OSHA 1 Introduction  Fires and explosions kill more than 200 and injure more than 5,000 workers each year  There is a long and tragic history of workplace fires in this country caused by problems with fire exits and extinguishing systems  OSHA requires employers to provide proper exits, fire fighting equipment, and employee training to prevent fire deaths and injuries in the workplace OSHAX.org - The Unofficial Guide To the OSHA 2 Exit Route  A continuous and unobstructed path of exit travel from any point within a workplace to a place of safety (including refuge areas)  Consists of three parts:  Exit access  Exit  Exit discharge OSHAX.org - The Unofficial Guide To the OSHA 3 Exit Routes Basic Requirements

109

Independent Activity Report, Lawrence Livermore National Laboratory...  

Office of Environmental Management (EM)

and the Alameda County Fire Department to a fire in a fume hood containing a depleted uranium part. Independent Activity Report, Lawrence Livermore National Laboratory -...

110

Fire suppression and detection equipment  

SciTech Connect (OSTI)

Inspection and testing guidelines go beyond the 'Code of Federal Regulation'. Title 30 of the US Code of Federal Regulations (30 CFR) contains requirements and references to national standards for inspection, testing and maintenance of fire suppression and detection equipment for mine operators. However, federal requirements have not kept pace with national standards and best practices. The article lists National Fire Protection (NFPA) standards that are referenced by the US Mine Safety and Health Administration (MSHA) in 30 CFR. It then discusses other NFPA Standards excluded from 30 CFR and explains the NFPA standard development process. 2 refs., 3 tabs., 5 photos.

E.E. Bates [HSB Professional Loss Control, Lexington, KY (United States)

2006-01-15T23:59:59.000Z

111

Painterly fire  

Science Journals Connector (OSTI)

This sketch describes how to construct a painterly 'wall' of fire, one which exhibits realistic motion while managing to maintain an artistic look. Keywords: effects animation, natural phenomena, rendering

Saty Raghavachary; Fernando Benitez

2002-07-01T23:59:59.000Z

112

Fires - 1946  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Fires - 1946 Fires - 1946 Nature Bulletin No. 85 September 28, 1946 Forest Preserve District of Cook County Clayton F. Smith, President Roberts Mann, Superintendent of Conservation FIRES - 1946 It happens every fall. Thousands of acres of vacant land are being burned-off: some of them because of matches, cigarettes or pipe dottle carelessly tossed aside along the highways and along the trails; some of them set afire by thoughtless boys; most of them deliberately burned by people who believe they will improve the crop of grass next year. That is stupid. And if you start a fire which burns over another person's property you are liable to arrest and heavy penalty, under the Illinois law, unless you have given that person proper notice of your intention. Fires harm -- they never help. The tough seeds and roots of the worthless grasses and weeds survive a fire but the good nutritious grasses and most wildflowers are killed. Further, all the winter food and cover for birds and other wildlife are destroyed.

113

Cold Vacuum Dryer (CVD) Facility Fire Protection System Design Description (SYS 24)  

SciTech Connect (OSTI)

This system design description (SDD) addresses the Cold Vacuum Drying (CVD) Facility fire protection system (FPS). The primary features of the FPS for the CVD are a fire alarm and detection system, automatic sprinklers, and fire hydrants. The FPS also includes fire extinguishers located throughout the facility and fire hydrants to assist in manual firefighting efforts. In addition, a fire barrier separates the operations support (administrative) area from the process bays and process bay support areas. Administrative controls to limit combustible materials have been established and are a part of the overall fire protection program. The FPS is augmented by assistance from the Hanford Fire Department (HED) and by interface systems including service water, electrical power, drains, instrumentation and controls. This SDD, when used in conjunction with the other elements of the definitive design package, provides a complete picture of the FPS for the CVD Facility.

SINGH, G.

2000-10-17T23:59:59.000Z

114

Fire and Ice Issue 7  

E-Print Network [OSTI]

       ' FIRE and ICE # 7 -p! jP) FIRE AND ICE VII Available from: Kathleen Resch PO Box 1766 Temple City, CA 91780 Kathleener@aol.com May 2002by Kathleen Reschfor the contributors. No reprints or reproduction without the written... permission of the author/artist. Thisis an amateur publication and is not in tended to infringe upon the rights ofTerryNation, BBC-TV or any others. i - J FIRE AND ICE VI Table of Contents HALF A LOAF by Linda Norman 1 GROUNDHOG LAY by Predatrlx 5 PLAYTIME...

Multiple Contributors

2002-01-01T23:59:59.000Z

115

Nuclear-power-plant perimeter-intrusion alarm systems  

SciTech Connect (OSTI)

Timely intercept of an intruder requires the examination of perimeter barriers and sensors in terms of reliable detection, immediate assessment and prompt response provisions. Perimeter security equipment and operations must at the same time meet the requirements of the Code of Federal Regulations, 10 CFR 73.55 with some attention to the performance and testing figures of Nuclear Regulatory Guide 5.44, Revision 2, May 1980. A baseline system is defined which recommends a general approach to implementing perimeter security elements: barriers, lighting, intrusion detection, alarm assessment. The baseline approach emphasizes cost/effectiveness achieved by detector layering and logic processing of alarm signals to produce reliable alarms and low nuisance alarm rates. A cost benefit of layering along with video assessment is reduction in operating expense. The concept of layering is also shown to minimize testing costs where detectability performance as suggested by Regulatory Guide 5.44 is to be performed. Synthesis of the perimeter intrusion alarm system and limited testing of CCTV and Video Motion Detectors (VMD), were performed at E-Systems, Greenville Division, Greenville, Texas during 1981.

Halsey, D.J.

1982-04-01T23:59:59.000Z

116

Independent Oversight Review, Los Alamos National Laboratory December 2013  

Broader source: Energy.gov [DOE]

Review of the Technical Area 55 Safety Class Fire Suppression System at Los Alamos National Laboratory

117

Enterprise Assessments Review, Los Alamos National Laboratory- November 2014  

Broader source: Energy.gov [DOE]

Review of the Los Alamos National Laboratory Weapons Engineering Tritium Facility Fire Suppression System

118

FIRE PROTECTION IMPAIRMENTS University Fire Marshal  

E-Print Network [OSTI]

FIRE PROTECTION IMPAIRMENTS University Fire Marshal Guidance Document Approved by: R. Flynn Last revised by: R. Flynn Revision date: 08/18/2012 Fire Protection Impairments Page 1 of 1 This document contains excerpts from the Fire Code of New York State that pertain to the impairment of a fire protection

Pawlowski, Wojtek

119

SILENE Benchmark Critical Experiments for Criticality Accident Alarm Systems  

SciTech Connect (OSTI)

In October 2010 a series of benchmark experiments was conducted at the Commissariat a Energie Atomique et aux Energies Alternatives (CEA) Valduc SILENE [1] facility. These experiments were a joint effort between the US Department of Energy (DOE) and the French CEA. The purpose of these experiments was to create three benchmarks for the verification and validation of radiation transport codes and evaluated nuclear data used in the analysis of criticality accident alarm systems (CAASs). This presentation will discuss the geometric configuration of these experiments and the quantities that were measured and will present some preliminary comparisons between the measured data and calculations. This series consisted of three single-pulsed experiments with the SILENE reactor. During the first experiment the reactor was bare (unshielded), but during the second and third experiments it was shielded by lead and polyethylene, respectively. During each experiment several neutron activation foils and thermoluminescent dosimeters (TLDs) were placed around the reactor, and some of these detectors were themselves shielded from the reactor by high-density magnetite and barite concrete, standard concrete, and/or BoroBond. All the concrete was provided by CEA Saclay, and the BoroBond was provided by Y-12 National Security Complex. Figure 1 is a picture of the SILENE reactor cell configured for pulse 1. Also included in these experiments were measurements of the neutron and photon spectra with two BICRON BC-501A liquid scintillators. These two detectors were provided and operated by CEA Valduc. They were set up just outside the SILENE reactor cell with additional lead shielding to prevent the detectors from being saturated. The final detectors involved in the experiments were two different types of CAAS detectors. The Babcock International Group provided three CIDAS CAAS detectors, which measured photon dose and dose rate with a Geiger-Mueller tube. CIDAS detectors are currently in use at Y-12 in the newly constructed Highly Enriched Uranium Materials Facility. The second CAAS detector used a {sup 6}LiF TLD to absorb neutrons and a silicon detector to count the charge particles released by these absorption events. Lawrence Livermore National Laboratory provided four of these detectors, which had formerly been used at the Rocky Flats facility in the United States.

Miller, Thomas Martin [ORNL] [ORNL; Reynolds, Kevin H. [Y-12 National Security Complex] [Y-12 National Security Complex

2011-01-01T23:59:59.000Z

120

Conventional Facilities Chapter 8: Fire Protection 8-1 NSLS-II Preliminary Design Report  

E-Print Network [OSTI]

Conventional Facilities Chapter 8: Fire Protection 8-1 NSLS-II Preliminary Design Report 8 FIRE of New York State National Institute of Standards and Technology National Fire Protection Association, corresponding to the ring pentants. 8.2.2 Fire Protection System #12;8-2 Part 3: Conventional Facilities Scope

Ohta, Shigemi

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


121

Fire Protection  

Broader source: Energy.gov (indexed) [DOE]

NOT MEASUREMENT NOT MEASUREMENT SENSITIVE DOE-STD-1066-2012 December 2012 _______________ Supersedes DOE-STD-1066-99 DOE STANDARD FIRE PROTECTION U.S. Department of Energy AREA FIRP Washington, DC 20585 DISTRIBUTION STATEMENT. Approved for public release; distribution is unlimited. This document is available on the Department of Energy Technical Standards Program Web page at http://www.hss.doe.gov/nuclearsafety/ns/techstds/ DOE-STD-1066-2012 FOREWORD This Department of Energy (DOE) Standard (STD) supersedes DOE-STD-1066-99 1 and is approved for use by DOE and its contractors. The following fire protection standard is canceled with the issuance of this Standard and appropriate technical content was incorporated into this Standard:  DOE-STD-1088-95, Fire Protection for Relocatable Structures

122

2009 Berea College Residence Hall Fire Protection Systems, Notification Systems and Fire Drill Data Berea College Fire Alarm Partial 1 Full 2 Smoke Fire Evacuations Evacuation  

E-Print Network [OSTI]

Lights Doors Anna Smith Yes Yes Yes Yes Yes 3 Yes Yes Bingham** Yes Yes *Yes* Yes Yes 2 Yes Yes Blue Yes 2 Yes Yes Edwards Yes Yes Yes Yes Yes 4 Yes No Estill Street No No Yes Yes Yes 1 Yes No Elizabeth

Baltisberger, Jay H.

123

Tracking New Coal-Fired Power Plants  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

New Coal-Fired Power Plants New Coal-Fired Power Plants (data update 1/13/2012) January 13, 2012 National Energy Technology Laboratory Office of Strategic Energy Analysis & Planning Erik Shuster 2 Tracking New Coal-Fired Power Plants This report is intended to provide an overview of proposed new coal-fired power plants that are under development. This report may not represent all possible plants under consideration but is intended to illustrate the potential that exists for installation of new coal-fired power plants. Additional perspective has been added for non-coal-fired generation additions in the U.S. and coal-fired power plant activity in China. Experience has shown that public announcements of power plant developments do not provide an accurate representation of eventually

124

DOE Standard: Fire protection design criteria  

SciTech Connect (OSTI)

The development of this Standard reflects the fact that national consensus standards and other design criteria do not comprehensively or, in some cases, adequately address fire protection issues at DOE facilities. This Standard provides supplemental fire protection guidance applicable to the design and construction of DOE facilities and site features (such as water distribution systems) that are also provided for fire protection. It is intended to be used in conjunction with the applicable building code, National Fire Protection Association (NFPA) Codes and Standards, and any other applicable DOE construction criteria. This Standard replaces certain mandatory fire protection requirements that were formerly in DOE 5480.7A, ``Fire Protection``, and DOE 6430.1A, ``General Design Criteria``. It also contains the fire protection guidelines from two (now canceled) draft standards: ``Glove Box Fire Protection`` and ``Filter Plenum Fire Protection``. (Note: This Standard does not supersede the requirements of DOE 5480.7A and DOE 6430.1A where these DOE Orders are currently applicable under existing contracts.) This Standard, along with the criteria delineated in Section 3, constitutes the basic criteria for satisfying DOE fire and life safety objectives for the design and construction or renovation of DOE facilities.

Not Available

1999-07-01T23:59:59.000Z

125

Rawls' Fairness, Income Distribution and Alarming Level of Gini Coefficient  

E-Print Network [OSTI]

The argument that the alarming level of Gini coefficient is 0.4 is very popular, especially in the media industry, all around the world for a long time. Although the 0.4 standard is widely accepted, the derivation of the value lacks rigid theoretical foundations. In fact, to the best of our knowledge, it is not based on any prevalent and convincing economic theories. In this paper, we incorporate Rawls' principle of fair equality of opportunity into Arrow-Debreu's framework of general equilibrium theory with heterogeneous agents, and derive the alarming level of Gini coefficient formally. Our theory reveals that the exponential distribution of income not only satisfies Pareto optimality, but also obeys social fairness in Rawls' sense. Therefore, we specify the maximal value of the Gini coefficient when income follows exponential distribution as a possible alarming level. Our computations show that the alarming level should be specified at least equal or larger than 0.5 rather than 0.4. We empirically investig...

Tao, Yong; Li, Changshuai

2014-01-01T23:59:59.000Z

126

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network [OSTI]

the Authoritarian Model: How Putin?s Crackdown Holds RussiaAuthoritarianism Under Putin, Demokratizatsiya: The Journal

Hart, Melanie M.

2010-01-01T23:59:59.000Z

127

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network [OSTI]

Wang?s factory was burning hazardous waste materials, China?waste materials, not the more stringent standards for factories burning (

Hart, Melanie M.

2010-01-01T23:59:59.000Z

128

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network [OSTI]

and standards for heavy metal pollution. The MEP passed aHandling of Heavy Metal Pollution on August 28, 2009.

Hart, Melanie M.

2010-01-01T23:59:59.000Z

129

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network [OSTI]

Hygiene] Law and cause food poisoning accidents or otherFood and Drug Administration (SFDA) traces the poisonouspoisonings were most likely a macro-level issue stemming from a wide variety of sources such as contaminated food,

Hart, Melanie M.

2010-01-01T23:59:59.000Z

130

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network [OSTI]

Ibid. Walker (2008). planned hydropower projects in Yunnanlands are expropriated for hydropower developments. In 2004to lose their lands for a hydropower project on the Nujiang

Hart, Melanie M.

2010-01-01T23:59:59.000Z

131

Door Placard for No Automatic Fire Alarm and No Sprinkler System  

E-Print Network [OSTI]

apartment with wet towels or sheets, and seal air ducts or other openings where smoke may enter Open address, floor, apartment number and the number of people in your apartment Seal the doors to your

Pawlowski, Wojtek

132

Brookhaven National Laboratory  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Building 725 Fire Hazard Analysis/Fire Hazard Assessment Number: LS-ESH-0068 Revision: 1 Effective: 7/15/2009 Page 1 of 18 Prepared By: Robert Chmiel Approved By: Andrew Ackerman Approved By: Joe Levesque *Approval signatures on file with master copy. Revision Log Purpose/Scope The purpose of this Assessment is to comprehensively and qualitatively assess the risk from fire within the National Synchrotron Light Source (NSLS) to ensure DOE fire safety objectives are met. DOE fire protection criteria are outlined in DOE Order 420.1. The Fire Protection Assessment includes identifying the risks from fire and related hazards (direct flame impingement, hot gases, smoke migration, fire-fighting water damage, etc.). A Fire Hazard

133

Independent Oversight Review, Pacific Northwest National Laboratory- September 2013  

Broader source: Energy.gov [DOE]

Review of the Fire Protection Program at Pacific Northwest National Laboratory and the Fire Suppression System at the Radiochemical Processing Laboratory

134

Trottier BuildingTrottier Building Fire SafetyFire Safety  

E-Print Network [OSTI]

building 1.1. Fire SafetyFire Safety 2.2. Fire Protection equipmentFire Protection equipment 3 OfficersFire Prevention Officers #12;Trottier BuildingTrottier Building Fire ProtectionFire Protection#12;Trottier BuildingTrottier Building Fire SafetyFire Safety in Trottier buildingin Trottier

Pientka, Brigitte

135

E-Print Network 3.0 - alarm processing system Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

the Management of Multi-Layered Networks Summary: on the definition of alarms that can enter the system. Therefore, three alarm categories are created based... with a single-layer...

136

E-Print Network 3.0 - alarm system commercial Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

the Management of Multi-Layered Networks Summary: on the definition of alarms that can enter the system. Therefore, three alarm categories are created based... with a single-layer...

137

E-Print Network 3.0 - advanced alarm systems Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

the Management of Multi-Layered Networks Summary: on the definition of alarms that can enter the system. Therefore, three alarm categories are created based... with a single-layer...

138

Fire Protection for Laboratories Using Chemicals  

Broader source: Energy.gov (indexed) [DOE]

Protection Engineer Fire Protection Engineering Pacific Northwest National Laboratory Phone 509-371-7902; Cell 509-308-7658 Fax 509-371-7890 andrew.minister@pnnl.gov Questions?...

139

Fire spread in concealed foamed plastic insulation  

Science Journals Connector (OSTI)

A test program, jointly sponsored by the Society of the Plastics Industry of Canada and the National Research Council, examined the contribution of plastic foams to fire spread in buildings. The conditions und...

Dr. W. Taylor

1983-08-01T23:59:59.000Z

140

Suitability of the Weather Research and Forecasting (WRF) Model to Predict the June 2005 Fire Weather for Interior Alaska  

E-Print Network [OSTI]

temperature, and daily accumulated shortwave radiation well. Daily minimum (maximum) temperature and relative to local fire management authorities on the potential for wild- fires to plan prescribed burns, alert of fire control into fire indices that reflect protection require- ments. The National Fire Danger Rating

Moelders, Nicole

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


141

Annual Fire Safety Report  

E-Print Network [OSTI]

2010 Annual Fire Safety Report University of California, Irvine HIGHER EDUCATION OPPORTUNITY to the Fire Safety in Student Housing Buildings of current or perspective students and employees be reported publish an annual fire safety report, keep a fire log, and report fire statistics to the Secretary

Loudon, Catherine

142

Fire Safety January 2011  

E-Print Network [OSTI]

1 Fire Safety PROCEDURES January 2011 firesafety@uwo.ca Campus Phones ­ EMERGENCY ­ Dial 911 Fire Safety Service is the focal point for the coordinated administration of the University Fire Safety Prevention and Fire Safety to minimize the risk of injury or loss of life or property due to fire

Lennard, William N.

143

Thanks to Our Neighbors in Fighting Fire on INL  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Thanks to Our Neighbors in Fighting Fire on INL Thanks to Our Neighbors in Fighting Fire on INL Idaho Bureau of Homeland Security view of the Twin Buttes Wildland fire aftermath atop the East Twin Butte. As the Department of Energy's manager at the Idaho National Laboratory, I want to commend the outstanding efforts of More than 50 firefighters and equipment battled the fire that was contained at 9:10 p.m. Mountain Standard Time July 19, 2007 An aerial scan of the area indicated the fire burned more than 9,000 acres. INL employees, and firefighting and law enforcement staff from our regional neighbors for the outstanding team-work they exhibited in controlling the Twin Buttes Fire on the INL from July 18-20. The INL Firefighters and support workers joined together with the Blackfoot Fire Department, Idaho Falls Fire Department, Shelley Fire

144

Independent Activity Report, Los Alamos National Laboratory ...  

Broader source: Energy.gov (indexed) [DOE]

Alamos National Laboratory - April 2010 April 2010 Los Alamos Site Office Assessment of Fire Protection Activities at the Los Alamos National Laboratory The U.S. Department of...

145

Oversight Reports - Lawrence Livermore National Laboratory |...  

Broader source: Energy.gov (indexed) [DOE]

Oversight Review, Lawrence Livermore National Laboratory - September 2013 Review of the Fire Protection Program at Lawrence Livermore National Laboratory July 19, 2013...

146

Fire and Ice Issue 6  

E-Print Network [OSTI]

9#HDIQNV3>IM ".: FIRE AND ICE VI Available from: Kathleen Resch PO Box 1766 Temple City, CA 91780 October, 2000 by Kathleen Resch for the contributors. No reprints or reproduction without the written permission of the author.../artist. This is an amateur publication and is not intended to infringe upon the rights ofTerry Nation, BBC-TV or any others. FIRE AND ICE VI 1 Table of Contents A DANGEROUS CONCEPT by Nova 1 A FRIEND IN NEED... by Julia Stamford 14 ...IS A FRIEND INDEED by Julia Stamford 19...

Multiple Contributors

2000-01-01T23:59:59.000Z

147

Fire Safety Training: Fire Modeling- NUREG 1934  

Broader source: Energy.gov [DOE]

Presenter: Frederick W. Mowrer, Ph.D., P.E. Director Fire Protection Engineering Programs - Cal Poly SLO

148

Approval Memorandum, Additional Qualification Courses of Fire - December  

Broader source: Energy.gov (indexed) [DOE]

Approval Memorandum, Additional Qualification Courses of Fire - Approval Memorandum, Additional Qualification Courses of Fire - December 13, 2011 Approval Memorandum, Additional Qualification Courses of Fire - December 13, 2011 December 13, 2011 Request approval of revised courses of fire. As indicated in the background section of the memorandum, subjects: Newly Developed SECURITY Policy Officer/Special Response Team Qualification Courses of Fire, dated October 12,2011, members of the Department of Energy (DOE) Firearms Policy Panel, DOE Training Managers Working Group, the National Nuclear Security Administration, and the DOE National Training Center have devloped , reviewed and revised the following courses of fire (attached) for inclusion in the Protective Force Firearms Qualification Courses Manual. The courses of fire pertain to the incubent Security Police

149

Los Alamos National Laboratory to  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

instrument that helps ensure the integrity of the nation's nuclear stockpile without nuclear testing. Scientists and engineers at DARHT can now begin test firings of the...

150

FIRE PROTECTION ENGINEERING  

E-Print Network [OSTI]

FIRE PROTECTION ENGINEERING FPE College of Engineering California Polytechnic State University San problems and develop fire safety design solutions in a variety of professional settings. Fire Protection Engineering Science � Apply concepts associated with the thermal sciences, to the analysis of fire protection

Sze, Lawrence

151

FIRE PROTECTION ENGINEERING  

E-Print Network [OSTI]

FIRE PROTECTION ENGINEERING FPE College of Engineering California Polytechnic State University San and develop fire safety design solutions in a variety of professional settings. Fire Protection Engineering Science · Apply concepts associated with the thermal sciences, to the analysis of fire protection

Sze, Lawrence

152

Wild Fire Computer Model Helps Firefighters  

ScienceCinema (OSTI)

A high-tech computer model called HIGRAD/FIRETEC, the cornerstone of a collaborative effort between U.S. Forest Service Rocky Mountain Research Station and Los Alamos National Laboratory, provides insights that are essential for front-line fire fighters. The science team is looking into levels of bark beetle-induced conditions that lead to drastic changes in fire behavior and how variable or erratic the behavior is likely to be.

Canfield, Jesse

2014-06-02T23:59:59.000Z

153

E-Print Network 3.0 - alarm processing techniques Sample Search...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

TASA Summary: relationships of the alarms into account. 2.2. TASA methodology A KDD process, adapted from 11, consists of: 1... Interactive exploration of interesting...

154

E-Print Network 3.0 - alarm system verification Sample Search...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

City Collection: Mathematics 11 Sensitivity Analysis of the JPALS Shipboard Relative GPS Measurement Summary: unnecessarily, increasing the false alarm rate and adversely...

155

Testing and Evaluation Protocol for Alarming Personal Radiation Detectors for Homeland Security  

E-Print Network [OSTI]

Testing and Evaluation Protocol for Alarming Personal Radiation Detectors for Homeland Security T................................................................................1 4. Test and evaluation steps .........................................................................................1 5. Recording test results

156

Enterprise Assessments Targeted Review, Idaho National Laboratory December 2014  

Broader source: Energy.gov [DOE]

Review of the Idaho National Laboratory Fire Protection Program as Implemented at the Irradiated Materials Characterization Laboratory

157

Fire Protection Program  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Program Program Fire Protection Overview The Department of Energy (DOE) Fire Protection Program is multi-faceted. It includes published fire safety directives (Orders, standards, and guidance documents), a range of oversight activities, an annual fire protection program summary, and a directory of fire safety professionals. DOE also sponsors fire safety conferences, various training initiatives, and a spectrum of technical assistance activities. This Home Page is intended to bring together in one location as much of the Program's resources as possible to facilitate greater understanding, communication, and efficiency of operations. Guidelines -- NFPA Codes and standards, CFRs, and DOE Directives (policy statements, Orders, Standards, and Guidance Documents)

158

Stochastic Representation of Fire Behavior in a Wildland Fire Protection  

E-Print Network [OSTI]

Stochastic Representation of Fire Behavior in a Wildland Fire Protection Planning Model on wildland fire used by the California Department of Forestry and Fire Protection. Fire rate of spread (ROS. S IMULATIONMODELSOFINITIALATTACKonwildland fireare important tools for wildland fire protection planning, and several new models have been

Fried, Jeremy S.

159

Fire and Emergency Management Group SLAC-I-730-0A12A-001-R000  

E-Print Network [OSTI]

Fire and Emergency Management Group SLAC-I-730-0A12A-001-R000 Fire Protection System Impairment NFPA National Fire Protection Association SLAC Stanford Linear Accelerator Center SSO DOE Stanford Site000 iii #12;#12;1 Introduction This document describes the fire protection system impairment program

Wechsler, Risa H.

160

Proceedings of the Second International Symposium on Fire Economics, Planning, and Policy: A Global View Fire Management Plan at Regional Scale in  

E-Print Network [OSTI]

protection (L.353/2000) is presented. In particular the main features of the recent regional fire management of the fire management plan are reported, together with the criteria followed to define the protection at regional scale are based on the wildland fire protection national law L. 353/2000. This regulation

Standiford, Richard B.

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


161

A hybrid intelligent system for alarm processing in power distribution substations  

Science Journals Connector (OSTI)

This application paper presents an intelligent system for alarm processing and fault location in power substations. A hybrid model is constructed using rule-based systems and an artificial neural network. Incoming alarms are initially handled by an input ... Keywords: Expert systems, fault location, neural networks

J. C. Stacchini de Souza; M. B. Do Coutto Filho; R. S. Freund

2010-04-01T23:59:59.000Z

162

Fire Protection Related Sites  

Broader source: Energy.gov [DOE]

Fire Protection related sites for Department of Energy, Non-DOE Government and Non-Government information.

163

Site Visit Report, Lawrence Livermore National Laboratory - May...  

Broader source: Energy.gov (indexed) [DOE]

National Laboratory - May 2010 May 2010 Review of Lawrence Livermore National Laboratory Fire Protection Design Review Process This site visit report documents the results of the...

164

Substation fire protection features  

SciTech Connect (OSTI)

This paper describes Commonwealth Edison`s (ComEd) approach to substation fire protection. Substation fires can have a major operational, financial, as well as political impact on a utility. The overall Company philosophy encompasses both active and passive fire protection features to provide prompt detection, notification, and confinement of fire and its by-products. Conservatively designed smoke detection systems and floor and wall penetration seals form the backbone of this strategy. The Company has implemented a program to install these features in new and existing substations. Thus far these measures have been successful in mitigating the consequences of substation fires.

Hausheer, T.G. [Commonwealth Edison Co., Chicago, IL (United States)

1995-10-01T23:59:59.000Z

165

Oversight Reports - Los Alamos National Laboratory | Department...  

Broader source: Energy.gov (indexed) [DOE]

December 13, 2013 Independent Oversight Review, Los Alamos National Laboratory - December 2013 Review of the Technical Area 55 Safety Class Fire Suppression System at Los...

166

Enterprise Assessments Review, Los Alamos National Laboratory...  

Office of Energy Efficiency and Renewable Energy (EERE) Indexed Site

Laboratory - November 2014 November 2014 Review of the Los Alamos National Laboratory Weapons Engineering Tritium Facility Fire Suppression System The Department of Energy Office...

167

Independent Oversight Review, Los Alamos National Laboratory...  

Broader source: Energy.gov (indexed) [DOE]

consensus standards, U.S. Department of Energy orders and standards, and National Fire Protection Association standards and requirements. Independent Oversight Review, Los...

168

Memorandum, Additional Approved Qualification Courses of Fire - September  

Broader source: Energy.gov (indexed) [DOE]

Memorandum, Additional Approved Qualification Courses of Fire - Memorandum, Additional Approved Qualification Courses of Fire - September 23, 2011 Memorandum, Additional Approved Qualification Courses of Fire - September 23, 2011 September 23, 2011 Newly developed Security Police Officer/Special Response Team Qualification Courses of Fire In accordance with DOE Order 473.2 Protection Program Operations , Section E , paragraph 2 and Section K, Paragraph 2, members of the Department of Energy (DOE) Firearms Policy Panel, DOE Protective Forces Safety Committee, DOE Trainin Managers Working Group, the National Nuclear Security Administration, and the DOE National Training Center have developed, reviewed and revised the following courses of fire (attached) for inclusion in the Protective Force Firearms Qualification Courses Manual. The courses

169

E-Print Network 3.0 - alarming oxygen depletion Sample Search...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

protecting life on Earth (1). In 1985, scientists and the public became alarmed when Farman et al. (2... studies (5-8). These studies showed that ozone depletion has a large...

170

E-Print Network 3.0 - alarm border monitoring Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

deployed at U.S. ports of entry. Due... to the occurrence of nuisance alarms based on naturally occurring radioactive material and the low base rate of nu Source: Parasuraman, Raja...

171

Fifth Anniversary of Radiological Alarm Response Training for...  

National Nuclear Security Administration (NNSA)

Training The three-day course is held at NNSA's Y-12 National Security Complex in Oak Ridge, Tenn. While at Y-12, participants develop and discuss their own tactics,...

172

FIRE MANAGEMENT PLAN MONTAGUE PLAIN  

E-Print Network [OSTI]

FIRE MANAGEMENT PLAN FOR MONTAGUE PLAIN WILDLIFE MANAGEMENT AREA #12;Fire Management Plan for Montague Plain Wildlife Management Area prepared for Massachusetts Dept. of Fisheries, Wildlife. 2003. Fire Management Plan for Montague Plain Wildlife Management Area. Department of Natural Resources

Schweik, Charles M.

173

H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2013.doc Annual Fire Safety Report  

E-Print Network [OSTI]

and Fire Protection (Cal Fire) responds to the State Response Area of campus, including the outlyingH:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2013.doc Annual Fire Safety #12;H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2013.doc Fire and Life

Sze, Lawrence

174

H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2012.doc Annual Fire Safety Report  

E-Print Network [OSTI]

and Fire Protection (Cal Fire) responds to the State Response Area of campus, including the outlyingH:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2012.doc Annual Fire Safety #12;H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2012.doc Fire and Life

Sze, Lawrence

175

Live Fire Range Environmental Assessment  

SciTech Connect (OSTI)

The Central Training Academy (CTA) is a DOE Headquarters Organization located in Albuquerque, New Mexico, with the mission to effectively and efficiently educate and train personnel involved in the protection of vital national security interests of DOE. The CTA Live Fire Range (LFR), where most of the firearms and tactical training occurs, is a complex separate from the main campus. The purpose of the proposed action is to expand the LFR to allow more options of implementing required training. The Department of Energy has prepared this Environmental Assessment (EA) for the proposed construction and operation of an expanded Live Fire Range Facility at the Central Training Academy in Albuquerque, New Mexico. Based on the analysis in the EA, DOE has determined that the proposed action is not a major Federal action significantly affecting the quality of the human environment, within the meaning of the National Environmental Policy Act (NEPA) of 1969. Therefore, the preparation of an environmental impact statement is not required and DOE is issuing this Finding of No Significant Impact (FONSI).

None

1993-08-01T23:59:59.000Z

176

856 IEEE TRANSACTIONS ON SYSTEMS, MAN, AND CYBERNETICS--PART C: APPLICATIONS AND REVIEWS, VOL. 38, NO. 6, NOVEMBER 2008 Designing Effective Alarms for Radiation Detection  

E-Print Network [OSTI]

to the occurrence of nuisance alarms based on naturally occurring radioactive material and the low base rate of nu Naturally occurring radioactive material. p(false alarm) Probability of a false alarm. p(hit) Probability, NO. 6, NOVEMBER 2008 Designing Effective Alarms for Radiation Detection in Homeland Security

Parasuraman, Raja

177

Independent Oversight Review, Los Alamos National Laboratory Chemistry and Metallurgy Research Facility- January 2012  

Broader source: Energy.gov [DOE]

Review of the Los Alamos National Laboratory Chemistry and Metallurgy Research Facility Fire Suppression Vital Safety System

178

P\\procedure\\EH&S#2 Page 1 of 3 TITLE: BOCA RATON CAMPUS FIRE ALARM POLICY ACCESS AND RESPONSE  

E-Print Network [OSTI]

only authorized personnel have access to the systems. Provide training and guidelines about and repairs. UNIVERSITY POLICE Operate and maintain the Proprietary Monitoring Station. Assign trained of University operations. Objectives include: A well-designed service program with optimum productivity

Fernandez, Eduardo

179

Fire science at LLNL: A review  

SciTech Connect (OSTI)

This fire sciences report from LLNL includes topics on: fire spread in trailer complexes, properties of welding blankets, validation of sprinkler systems, fire and smoke detectors, fire modeling, and other fire engineering and safety issues. (JEF)

Hasegawa, H.K. (ed.)

1990-03-01T23:59:59.000Z

180

Contained Firing Facility | National Nuclear Security Administration  

National Nuclear Security Administration (NNSA)

Related Topics Maintaining the Stockpile stockpile stewardship R&D llnl Related News SOLAR POWER PURCHASE FOR DOE LABORATORIES NNSA's Stockpile Stewardship Program Quarterly...

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


181

Source: http://tiny.cc/test-fear OnlineAlarm  

E-Print Network [OSTI]

chest pain during a heart attack? Learn more at the National Library of Medicine's heart attacks, help- ing to prevent them, subtle signs and symptoms, and not confusing heart attacks with other-healthy education training module - http://tiny.cc/love-your-heart. The sound/animation tutorial discusses heart

Oliver, Douglas L.

182

Assessment of the Plutonium Finishing Plant Criticality Alarm System U.S. Department of Energy Richland Operations Office  

SciTech Connect (OSTI)

At the request of the Assistant Manager for Safety and Engineering, the U.S. Department of Energy Richland Operations Office (RL) Engineering Support Division, performed an oversight review of the Plutonium Finishing Plant (PFP) nuclear Criticality Alarm System (CAS). The review was conducted to satisfy requirements and agreements associated with Defense Nuclear Facility Safety Board (DNFSB) Recommendation 2000-2, ''Vital Safety Systems.'' The PFP is managed by Fluor Hanford, Inc. for RL. The field assessment and staff interviews were conducted August 12 through August 19,2002. This was a limited scope assessment that consisted of a review of the nuclear CAS operations, maintenance, and compliance with National Consensus Standards Requirements. The main purpose of the assessment was to determine the adequacy of the existing alarm system and its associated infrastructure to support the PFP facility mission through the remaining facility lifetime. The Review Plan was modeled upon Criteria and Review Approach Documents (CRAD) developed for DNFSB Recommendation 2000-2 reviews conducted across the Hanford Site. Concerns regarding component degradation and failure, increasing numbers of occurrence reports associated with the alarm system, and reliability issues were addressed. Additionally, RL performed a review of the engineering aspects of the CAS including the functions of design authorities and aspects of systems engineering. However, the focus of the assessment was on operations, maintenance, and reliability of the CAS, associated procurement practices, adequacy of safety and engineering policies and procedures, safety documentation, and fundamental engineering practices including training, qualification, and systems engineering. This assessment revealed that the PFP CAS and its associated infrastructure, administrative procedures, and conduct of operations are generally effective. There are no imminent criticality safety issues associated with the operation of the existing CAS. The Assessment Team believes that the CAS, as it presently exists at the PFP facility, is adequate to support the remaining mission lifetime of the facility while continuing to ensure personnel safety. This conclusion is dependent upon a continued level of funding adequate to support the required maintenance and occasional system upgrade. Two findings were identified during this assessment. Additionally, the report identified eight observations and two recommendations. The assessment revealed that recent changes to OSR compliance procedures and other documents do not contain the signature of the CSR as required by procedure. Lack of appropriate approval signatures is a noncompliance with site-level procedures.

NIRIDER, L.T.

2002-10-01T23:59:59.000Z

183

CRAD, Fire Protection - Idaho Accelerated Retrieval Project Phase II |  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection - Idaho Accelerated Retrieval Project Phase Fire Protection - Idaho Accelerated Retrieval Project Phase II CRAD, Fire Protection - Idaho Accelerated Retrieval Project Phase II February 2006 A section of Appendix C to DOE G 226.1-2 "Federal Line Management Oversight of Department of Energy Nuclear Facilities." Consists of Criteria Review and Approach Documents (CRADs) used for a February 2006 Commencement of Operations assessment of the Fire Protection program at the Idaho National Laboratory, Idaho Accelerated Retrieval Project Phase II. CRADs provide a recommended approach and the types of information to gather to assess elements of a DOE contractor's programs. CRAD, Fire Protection - Idaho Accelerated Retrieval Project Phase II More Documents & Publications CRAD, Engineering - Idaho Accelerated Retrieval Project Phase II

184

Subsurface Fire Hazards Technical Report  

SciTech Connect (OSTI)

The results from this report are preliminary and cannot be used as input into documents supporting procurement, fabrication, or construction. This technical report identifies fire hazards and proposes their mitigation for the subsurface repository fire protection system. The proposed mitigation establishes the minimum level of fire protection to meet NRC regulations, DOE fire protection orders, that ensure fire containment, adequate life safety provisions, and minimize property loss. Equipment requiring automatic fire suppression systems is identified. The subsurface fire hazards that are identified can be adequately mitigated.

Logan, R.C.

1999-09-27T23:59:59.000Z

185

Independent Oversight Review, Pacific Northwest National Laboratory -  

Broader source: Energy.gov (indexed) [DOE]

Pacific Northwest National Laboratory Pacific Northwest National Laboratory - October 2012 Independent Oversight Review, Pacific Northwest National Laboratory - October 2012 October 2012 Review of the Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System The Office of Enforcement and Oversight (Independent Oversight), within the U.S. Department of Energy (DOE) Office of Health, Safety and Security (HSS), conducted a shadow assessment of the Office of Science (SC) review of the Pacific Northwest National Laboratory (PNNL) Radiochemical Processing Laboratory (RPL) Criticality Alarm System (CAS). SC's Pacific Northwest Site Office (PNSO) coordinated the SC review. The SC assessment focused on the operability of the CAS at the PNNL RPL

186

Preliminary Notice of Violation, National Security Technologies, LLC- NEA-2011-03  

Broader source: Energy.gov [DOE]

Issued to National Security Technologies, LLC related to Deficiencies in Inspection and Installation of Penetration Fire Seals and Other Components at the Nevada National Security Site

187

Flooding and Fire Ants  

E-Print Network [OSTI]

Fire ants can be a serious problem during and after a flood. This publication explains how to protect yourself when you must return to flooded structures or deal with storm debris....

Nester, Paul

2008-08-05T23:59:59.000Z

188

Safety, Security & Fire Report  

E-Print Network [OSTI]

2013 Safety, Security & Fire Report Stanford University #12;Table of Contents Public Safety About the Stanford University Department of Public Safety Community Outreach & Education Programs Emergency Access Transportation Safety Bicycle Safety The Jeanne Clery and Higher Education Act Timely Warning

Straight, Aaron

189

Overview of the ARM/FIRE Water Vapor Experiment (AFWEX)  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Overview of the ARM/FIRE Water Vapor Overview of the ARM/FIRE Water Vapor Experiment (AFWEX) D. C. Tobin, H. E. Revercomb, and D. D. Turner University of Wisconsin-Madison Madison, Wisconsin Introduction An overview of the ARM/FIRE Water Vapor Experiment (AFWEX) is given. This field experiment was conducted during November-December 2000 near the central ground-based Atmospheric Radiation Measurement (ARM) site in north central Oklahoma, and was sponsored jointly by the ARM, the National Aeronautics and Space Administration (NASA) First ISCCP Regional Experiment (FIRE), and the National Polar-orbiting Operational Environmental Satellite System (NPOESS) programs. Its primary goal was to collect accurate measurements of upper-level (~8 to 12 km) water vapor near the ground-based ARM site. These data are being used to determine the accuracy of measurements that are

190

Improve the design of fire emergency relief systems  

SciTech Connect (OSTI)

In recognition of the potential severe consequences of a process vessel rupture under fire exposure, industry codes such as the National Fire Protection Association (NFPA) 30 and the American Petroleum Institute (API) Standard 2000 have been established for the specification of emergency relief systems (ERSs). The intent is to reduce the risk of human injury and asset losses associated with process plant fires. These codes are largely prescriptive in nature. That is, they provide specific details on how to achieve safe design. Prescriptive standards are easy to apply, because they are simplified approaches which generally apply to many (but not all) situations. But they also have limitations, including the tendency to result in, at best, suboptimal (overly conservative) designs, and in some instances potentially unsafe designs. As the fire community moves toward performance-based standards for building protection, perhaps it is time to consider a similar approach for vessel protection in a fire. The design issues addressed in this article include: Use of heat input based on actual fuel burning rate, heat of combustion, and flame emissive power, vs. NFPA 30 and API 2000 heat-input equations; Effect of drainage (from vessel to sump) on fire duration, rather than heat input; Use of risk assessment to determine the relative frequency of fire and process-induced incidents; and design for containment, rather than vessel protection when fire probability is low

Stickles, R.P.; Melhem, G.A.; Eckhardt, D.R.

1995-11-01T23:59:59.000Z

191

Hanford Site Fire June 2000 AM  

SciTech Connect (OSTI)

The Hanford Site Fire on the morning of June 29, 2000. Fire crews working to contain a fire on the Hanford Site in June 2000.

2000-06-29T23:59:59.000Z

192

Ignition and spread of electrical wire fires  

E-Print Network [OSTI]

Airplane fires; (b) Nuclear power plant fires; (c) Chemicalignition sources in nuclear power plants: statistical,number of fire cases in nuclear power plants (NPP) [2]. Most

Huang, Xinyan

2012-01-01T23:59:59.000Z

193

Fire Simulation, Evacuation Analysis and Proposal of Fire Protection Systems Inside an Underground Cavern  

E-Print Network [OSTI]

Fire Simulation, Evacuation Analysis and Proposal of Fire Protection Systems Inside an Underground Cavern

Stella, Carlo

194

IE 361 Module 14 Patterns on Control Charts and "Special Checks"/Extra Alarm Rules  

E-Print Network [OSTI]

3.4 of Statistical Quality Assurance Methods for Engineers Prof. Steve Vardeman and Prof. Max MorrisIE 361 Module 14 Patterns on Control Charts and "Special Checks"/Extra Alarm Rules Reading: Section equipment or a clear change in the quality of a raw material

Vardeman, Stephen B.

195

Fire Test of Profile Plank for Transformer Pit Fire Protection  

Science Journals Connector (OSTI)

In general it is recommended to fill a transformer pit with rock ballast to extinguish the fire if there is a leakage of burning transformer oil. There is a lack of ... design of solutions for fire extinguishment...

Johan Lindstrm; Michael Frsth

2014-05-01T23:59:59.000Z

196

Enforcement Letter, Los Alamos National Laboratory - July 7,...  

Broader source: Energy.gov (indexed) [DOE]

1997 July 7, 1997 Issued to the University of California related to Potential Quality Assurance Rule Violations associated with an Explosion and Fire at the Los Alamos National...

197

E-Print Network 3.0 - accident experience alarm Sample Search...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

, accident investigation, indoor air quality, bloodborne pathogens, chemical safety, lockout-tagout, hot work... Campus Fires 11 12 Accident Reporting 14 Employee Accidents 15...

198

EHSO TRAINING CLASSES Fire Safety Program Training  

E-Print Network [OSTI]

EHSO TRAINING CLASSES Fire Safety Program Training 1. Fire Safety (60 minutes) Instruction includes an actual fire eperience. 2. Fire Extinguisher Training (30 minutes) A practical demonstration on actual burnable liquid fires. This practical extinguisher training is a critical portion of the fire

199

Lawrence Livermore National Laboratory - Reports  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Lawrence Livermore National Laboratory Lawrence Livermore National Laboratory Review Reports 2013 Independent Oversight Review of the Fire Protection Program at Lawrence Livermore National Laboratory, September 2013 Independent Oversight Review of Preparedness for Severe Natural Phenomena Events at the Lawrence Livermore National Laboratory, July 2013 Activity Reports 2013 Lawrence Livermore National Laboratory Operational Drill at the B332 Plutonium Facility, February 2013 Activity Reports 2012 Lawrence Livermore National Laboratory Site Lead Planning Activities, October 2012 Review Reports 2011 Review of Integrated Safety Management System Effectiveness at the Livermore Site Office, October 2011 Review of Integrated Safety Management System Effectiveness at Lawrence Livermore National Laboratory, September 2011

200

Fire-Immune Cable  

Science Journals Connector (OSTI)

... A FACTORY, opened by Lord Ridley on October 12, for making fire-resist ing cable called 'Pyrotenax', marks a new development which promises to be of far-reaching ... -plate elements, which are made of resistance wire embedded in the oxide. 'Pyrotenax' cable has a copper conductor, magnesia insulation, and copper sheath. The new technique enables ...

1937-11-20T23:59:59.000Z

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


201

Light My Fire...Or Yours | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Light My Fire...Or Yours Light My Fire...Or Yours Light My Fire...Or Yours February 6, 2012 - 12:15pm Addthis Ernie Tucker Editor, National Renewable Energy Laboratory It comes as no surprise that 9-out-of-10 American homes burned wood for heat a little more than a century ago. Likewise, it's also probably not news that the number dwindled to less than 1% by the 1970s. After all, who wants to chop and stack cordwood when you can set the thermostat to be comfortable? Perhaps that's why Paul Bunyan is so rarely spotted around town these days. Still, there is something irresistible about the warmth of a crackling fire. That appeal probably explains why fireplaces and wood-burning heating stoves haven't disappeared in many communities, and that upgrades such as energy efficient inserts and stoves are common.

202

Independent Oversight Review, Pacific Northwest National Laboratory -  

Broader source: Energy.gov (indexed) [DOE]

Pacific Northwest National Laboratory Pacific Northwest National Laboratory - September 2013 Independent Oversight Review, Pacific Northwest National Laboratory - September 2013 September 2013 Review of the Fire Protection Program at Pacific Northwest National Laboratory and the Fire Suppression System at the Radiochemical Processing Laboratory. This report documents the results of an independent oversight review of the fire protection program at the Pacific Northwest National Laboratory (PNNL) and the fire suppression system at the Radiochemical Processing Laboratory. The review was performed March 18-29, 2013, by the U.S. Department of Energy's (DOE) Office of Safety and Emergency Management Evaluations, which is within the DOE Office of Health, Safety and Security. The review was performed as one part of an ongoing targeted

203

Technical aspects of the sigma factor alarm method in alpha CAMs  

SciTech Connect (OSTI)

Some test must be applied to the low-level count data from alpha continuous air monitors (CAMs) to determine if the count is statistically significant (i.e., different from background). The test should also automatically account for different levels of background (i.e., ambient radon progeny concentrations). The method should, in other words, be as sensitive as possible, automatically desensitize when required, but in such a manner as to not exceed a previously-chosen acceptable false-alarm rate.

Justus, Alan Lawrence [Los Alamos National Laboratory

2009-01-01T23:59:59.000Z

204

The design of an intrusion security system using digital processing for alarm indication  

E-Print Network [OSTI]

has been noise spikes in the diode. These spikes can easily cause a false alarm which is difficult to trace since it results from a sporadic, elec- tronic malfunction. General Electric, Amperex, and other concerned companies have made a great... is the requirement of multiple triggering of this one threshold. AMF Inc. , Alexandria, Virginia, has recently introduced an intricate signal processor with diode transistor logic and transistor transistor logic integrated circuits to handle intru- sion signals...

Holyoak, Joel Nelson

2012-06-07T23:59:59.000Z

205

Emergency Services, Brookhaven National Laboratory, BNL  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Emergency Services Emergency Services at Brookhaven National Laboratory :: Fire Danger Index LOW ▪ Index Description (pdf) ▪ NWS Fire Weather Forecast ▪ What is the Fire Danger Index ? The Fire Danger Index level takes into account current and antecedent weather, fuel types, and both live and dead fuel moisture. Hide :: Important Links EMERGENCY Numbers Lab Phone: 911 or 2222 Cell Phone/Offsite: 631-344-2222 OHSAS 18001 :: Contact Links ▪ Email LP Division Manager ▪ Email Fire Chief ▪ Email Fire Captains ▪ Email Fire Protection Engineer The mission of the Emergency Services Division is to provide preparedness, assessment, engineering and response services for all types of non-security related emergencies. The Division develops policies and programs for fire safety and fire risk management; provides emergency services for fire suppression, emergency medical services, hazardous material incidents, rescue, salvage, and property protection. As well as maintains the mechanical components of certain fire safety systems.

206

Fire Protection Program: Summary  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Summary Summary Since May 1950, an Annual Fire Protection Program Summary has been submitted by DOE's fire protection community. Currently, this report is required by section 5a.(8) of DOE Order 231.1. "Environment, Safety and Health Reporting." In 1999, an automation initiative was undertaken to streamline data collection and provide a more through review of DOE Reporting Element activities. This action resulted in the delayed publications of the CY 1999 and 2000 reports until 2002. It is now possible however to view all Annual Summary Reporting Element responses since 1991 at the Site, Operations, Lead Program Secretarial Office and Headquarters levels. Additionally, a build-in reference to other DOE reporting activities (CAIRS and ORPS) is available that allows Reporting Elements and managers the opportunity to review all fire protection events along previously mentioned categories. Reports listed below were generated from this application. To obtain a copy of the Annual Summary Application please contact Jim Bisker in the Office of Nuclear and Facility Safety Policy (EH-53) at (301)903-6542 or Jim Bisker.

207

Abstract B31: Collaborative breast health education addressing an alarming public health concern in the District of Columbia  

Science Journals Connector (OSTI)

...meeting-abstract Behavioral and Social Science Poster Presentations - Proffered Abstracts...B31: Collaborative breast health education addressing an alarming public health...Early Awareness is a breast health education program of Howard University Cancer...

Kimberly Higginbotham; Deon Regis; Lucile Adams-Campbell; Carla WIlliams; Wayne Frederick; Karen Peterson; Jasmine Greenamyer; Erica Childs; and Carolyn Aldige

2008-11-01T23:59:59.000Z

208

Lab and field estimates of active time of chemical alarm cues of a cyprinid fish and an  

E-Print Network [OSTI]

Lab and field estimates of active time of chemical alarm cues of a cyprinid fish and an amphipod., 1999; Stankowich, 2008), seismic (Gregory et al., 1986) and vibratory mechanostimuli (Kirchner et al

Wisenden, Brian D.

209

Effect Of False Alarm Rate On Pilot Use And Trust Of Automation Under Conditions Of Simulated High Risk  

E-Print Network [OSTI]

An experimental study was conducted to investigate the relationships between automation false alarm rate, human trust in automation, and human use of automation, specifically under conditions of simulated high risk. The ...

Cafarelli, Deborah

2010-11-05T23:59:59.000Z

210

Fire Impacts on the Mojave Desert Ecosystem: Literature Review  

SciTech Connect (OSTI)

The Nevada National Security Site (NNSS) is located within the Mojave Desert, which is the driest region in North America. Precipitation on the NNSS varies from an annual average of 130 millimeters (mm; 5.1 inches) with a minimum of 47 mm (1.9 inches) and maximum of 328 mm (12.9 inches) over the past 15 year period to an annual average of 205 mm (8.1 inches) with an annual minimum of 89 mm (3.5 inches) and maximum of 391 mm (15.4 inches) for the same time period; for a Frenchman Flat location at 970 meters (m; 3182 feet) and a Pahute Mesa location at 1986 m (6516 feet), respectively. The combination of aridity and temperature extremes has resulted in sparsely vegetated basins (desert shrub plant communities) to moderately vegetated mountains (mixed coniferous forest plant communities); both plant density and precipitation increase with increasing elevation. Whereas some plant communities have evolved under fire regimes and are dependent upon fire for seed germination, plant communities within the Mojave Desert are not dependent on a fire regime and therefore are highly impacted by fire (Brown and Minnich, 1986; Brooks, 1999). As noted by Johansen (2003) natural range fires are not prevalent in the Mojave and Sonoran Deserts because there is not enough vegetation present (too many shrub interspaces) to sustain a fire. Fire research and hence publications addressing fires in the Southwestern United States (U.S.) have therefore focused on forest, shrub-steppe and grassland fires caused by both natural and anthropogenic ignition sources. In the last few decades, however, invasion of mid-elevation shrublands by non-native Bromus madritensis ssp. rubens and Bromus tectorum (Hunter, 1991) have been highly correlated with increased fire frequency (Brooks and Berry, 2006; Brooks and Matchett, 2006). Coupled with the impact of climate change, which has already been shown to be playing a role in increased forest fires (Westerling et al., 2006), it is likely that the fire frequency will further increase in the Mojave Desert (Knapp 1998; Smith et al., 1987; Smith et al., 2000).

Fenstermaker Lynn

2012-01-01T23:59:59.000Z

211

Report Wildland Fire Area Hazard  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Report Wildland Fire Area Hazard Report Wildland Fire Area Hazard Report Wildland Fire Area Hazard Report wildland fire area hazards or incidents that are non-life threatening only. Call 911 for all emergencies that require immediate assistance. How to report wildland fire hazard Use the following form to report any wildland fire area hazards or incidents that are non-life threatening only. Call 911 for all emergencies that require immediate assistance. Fill out this form as completely as possible so we can better assess the hazard. All submissions will be assessed as promptly as possible. For assistance with a non-emergency situation, contact the Operations Support Center at 667-6211. Name (optional): Hazard Type (check one): Wildlife Sighting (check box if animal poses serious threat) Trails (access/egress)

212

NEON: a hierarchically designed national ecological network  

E-Print Network [OSTI]

NEON: a hierarchically designed national ecological network 59 David Schimel, NEON Inc, Boulder, CO (such as fire or flooding), and recovery develop within the domains, constrained by the biophysical

Hargrove, William W.

213

Date ______________________ New York City Fire Department  

E-Print Network [OSTI]

familiar with the fire protection and fire suppression systems in the premises where heDate ______________________ New York City Fire Department Bureau of Fire Prevention 9 Metro received training in 3RCNY §10-01, Fire Code Sections 2701 - 2703 & 2706, the New C-14 study material

Jia, Songtao

214

Texas A&M AgriLife Extension Service Procedures 24.01.01.X0.10 Fire Safety for StateOwned Residences  

E-Print Network [OSTI]

Protection Association (NFPA) 101®, Life Safety Code© has been adopted by the Texas State Fire MarshalTexas A&M AgriLife Extension Service Procedures 24.01.01.X0.10 Fire Safety for State.01.01.X0.10 Fire Safety for State­Owned Residences Page 1 of 2 PROCEDURE STATEMENT The National Fire

215

ANNUAL SECURITY FIRE SAFETY REPORT  

E-Print Network [OSTI]

ANNUAL SECURITY AND FIRE SAFETY REPORT OCTOBER 1, 2013 DARTMOUTH COLLEGE http................................................................................................................................................................... 7 ANNUAL SECURITY REPORT........................................................................................................................9 PREPARATION OF THE REPORT AND DISCLOSURE OF CRIME STATISTICS

216

Fire and Ice Issue 9  

E-Print Network [OSTI]

s FIRE AND ICE # 9 IB FIRE ICE #9 A Blake/Avon slash fanzine r Available from: Kathleen Resch POBox 1766 Temple City, CA 91780 Kathleener@aol.com FIRE AND ICE # 9copyright May, 2005 by Kathleen Resch for the contributors. No reprints... or reproduction without the written permission ofthe author/artist This is an amateur publication and is not p intended to infringe upon the rights ofany holders of"Blake's 7" copyrights. FIRE AND ICE 9 TABLE OF CONTENTS LEAVING ROOM 101 by Nova 2 TOO MANY...

Multiple Contributors

2005-01-01T23:59:59.000Z

217

Design of the Wireless Temperature Measurement Alarming System in the High-Voltage Transformer Substation  

Science Journals Connector (OSTI)

Due to electric power overload and equipment aging, fire and explosion occur at transmission circuitry joints in high-voltage transformer substation caused by high temperatures accumulated at these...

Qiang Gao; Hongli Wang; Huaxiang Wang

2008-01-01T23:59:59.000Z

218

Independent Oversight Review, Lawrence Livermore National Laboratory -  

Broader source: Energy.gov (indexed) [DOE]

Lawrence Livermore National Lawrence Livermore National Laboratory - September 2013 Independent Oversight Review, Lawrence Livermore National Laboratory - September 2013 September 2013 Review of the Fire Protection Program at Lawrence Livermore National Laboratory This report documents the results of an independent oversight review of the fire protection program at the Lawrence Livermore National Laboratory. The review was performed June 10-21, 2013, by the U.S. Department of Energy's (DOE) Office of Safety and Emergency Management Evaluations, which is within the DOE Office of Health, Safety and Security. The review was one part of a targeted assessment of fire protection at nuclear facilities across the DOE complex, including National Nuclear Security Administration sites. The purpose of the Independent Oversight targeted assessment was to

219

Independent Oversight Review, Lawrence Livermore National Laboratory -  

Broader source: Energy.gov (indexed) [DOE]

Lawrence Livermore National Lawrence Livermore National Laboratory - September 2013 Independent Oversight Review, Lawrence Livermore National Laboratory - September 2013 September 2013 Review of the Fire Protection Program at Lawrence Livermore National Laboratory This report documents the results of an independent oversight review of the fire protection program at the Lawrence Livermore National Laboratory. The review was performed June 10-21, 2013, by the U.S. Department of Energy's (DOE) Office of Safety and Emergency Management Evaluations, which is within the DOE Office of Health, Safety and Security. The review was one part of a targeted assessment of fire protection at nuclear facilities across the DOE complex, including National Nuclear Security Administration sites. The purpose of the Independent Oversight targeted assessment was to

220

Fire Lane must Fire Lane must be kept clear  

E-Print Network [OSTI]

#12;#12; Fire Lane must Fire Lane must be kept clear at all timesa a es #12; Emergency Egress Keep Safety Data Sheets #12; Safety glasses Safety goggles Face shield #12; Eye protection Skin protection Spectators protection from the light energygy #12; Safety glasses are required when any machinery

Asaithambi, Asai

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


221

Fire Safety Committee Meeting Minutes- May 2014  

Broader source: Energy.gov [DOE]

DOE Fire Safety Committee Meeting Minutes, May, 2014 Topics included discussions on Fire modeling, revisions to DOE regulations and other important items relating to DOE and Fire Safety Community.

222

Multi-Function Fuel-Fired Heat Pump  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Multi-Function Fuel-Fired Heat Pump Multi-Function Fuel-Fired Heat Pump CRADA Ed Vineyard Oak Ridge National Laboratory, Building Equipment Research vineyardea@ornl.gov, 865-576-0576 April 2, 2013 2 | Building Technologies Office eere.energy.gov Purpose & Objectives Problem Statement: 55% residential building energy use for space conditioning & water heating; highly efficient systems needed to facilitate DOE/BTO goal for 50% reduction in building energy use by 2030 Impact of Project: Cumulative energy savings potential of 0.25 Quads

223

Enforcement Documents - Pacific Northwest National Laboratory | Department  

Broader source: Energy.gov (indexed) [DOE]

Pacific Northwest National Laboratory Pacific Northwest National Laboratory Enforcement Documents - Pacific Northwest National Laboratory January 8, 2008 Preliminary Notice of Violation,Battelle Memorial Institute - EA-2007-07 Preliminary Notice of Violation issued to Battelle Memorial Institute related to Radiological Events and the Independent Assessment Program at the Pacific Northwest National Laboratory May 5, 2004 Enforcement Letter, Battelle Memorial Institute - May 5, 2004 Enforcement Letter issued to Battelle Memorial Institute related to Radiological Work Practices at the Pacific Northwest National Laboratory April 3, 1996 Preliminary Notice of Violation, Pacific Northwest National Laboratory - EA-96-01 Preliminary Notice of Violation issued to Battelle related to the Delayed Response to a Criticality Safety Alarm at the Pacific Northwest National

224

MARGINAL VALUATION OF FIRE EFFECTS  

E-Print Network [OSTI]

in the planning unit's land, resource and fire management plans. These goals and objectives can assist you with identifying the resources that are important to protect or improve through fire management activities. As you and cultural attributes of the landscape that have value. Defining the resource considered for value change 2

225

WHC fire hazards analysis policy  

SciTech Connect (OSTI)

The purpose of this document is to establish the fire protection policy for Westinghouse Hanford Company (WHC) relative to US Department of Energy (DOE) directives for Fire Hazards Analyses (FHAs) and their relationship to facility Safety Analysis Reports (SARs) as promulgated by the DOE Richland Operations Office.

Evans, C.B.

1994-04-01T23:59:59.000Z

226

ANNUAL SECURITY & FIRE SAFETY REPORT  

E-Print Network [OSTI]

ANNUAL SECURITY & FIRE SAFETY REPORT 2014 A guide to policies, procedures, practices, and programs implemented to keep students, faculty, and staff safe and facilities secure. www.montana.edu/reports/security.pdf #12;Inside this Report 2014 Annual Security and Fire Safety Report for Reporting Year 2013

Maxwell, Bruce D.

227

LNG facilities Engineered fire protection systems  

Science Journals Connector (OSTI)

Dry chemical fire extinguishers used in conjunction with high expansion foam have been used successfully in tests to extinguish LNG spill fires.

Kenneth Zuber

1976-02-01T23:59:59.000Z

228

BlueFire Ethanol | Department of Energy  

Office of Energy Efficiency and Renewable Energy (EERE) Indexed Site

BlueFire Ethanol BlueFire Ethanol Construct and operate a facility that converts green waste and lignocellulosic fractions diverted from landfills or Southern California Materials...

229

Fire hazards analysis of central waste complex  

SciTech Connect (OSTI)

This document analyzes the fire hazards associated with operational the Central Waste Complex. It provides the analysis and recommendations necessary to ensure compliance with applicable fire codes.

Irwin, R.M.

1996-05-30T23:59:59.000Z

230

New Buildings at the Fire Research Station  

Science Journals Connector (OSTI)

... THE new buildings of the Fire Research Station A of the Joint Fire Research Organization of the Department ... chemicals will be studied in the new chemical engineering laboratory.

D. I. LAWSON

1961-01-14T23:59:59.000Z

231

fire & fuels management Spruce Beetle-Induced Changes to Engelmann  

E-Print Network [OSTI]

. Keywords: crown fire, bark beetles, heat of combustion, fire behavior, time to ignition E ngelmann spruce

232

Preliminary Notice of Violation, Pacific Northwest National Laboratory -  

Broader source: Energy.gov (indexed) [DOE]

Pacific Northwest National Pacific Northwest National Laboratory - EA-96-01 Preliminary Notice of Violation, Pacific Northwest National Laboratory - EA-96-01 April 3, 1996 Preliminary Notice of Violation issued to Battelle related to the Delayed Response to a Criticality Safety Alarm at the Pacific Northwest National Laboratory This refers to the Department of Energy's (DOE) investigation of the circumstances surrounding a seven month delay in responding to a high level alarm for a criticality safe slab tank in the [specified building's] laboratory vacuum system. The DOE Office of Enforcement and Investigation initiated its investigation on November 27, 1995, after an Occurrence Report issued on October 11, 1995 identified collectively significant related occurrences in the [building's] laboratory vacuum system. These

233

Remote keyless entry honking, convenience horn honking, and audible car alarms: redundancies and quieter options  

Science Journals Connector (OSTI)

Vehicle sound emissions car alarms and horn honking are the subject of many noise complaints. Auto manufacturers spent years engineering quieter vehicles and have created cars whose approach is so subtle that they pose a danger to blind pedestrians. But while engine noise has decreased and car alarms are less reactive horn honking that is linked with remote keyless entry (RKE) technology increasingly contributes to community noise. RKE horn noise has never been the subject of public health inquiry. In scientific literature discussion of road noise and health does not distinguish noise among separate sources and tends to measure aggregate ambient noise levels rather than impulsive noise. RKE horn noise violates state traffic laws and some local noise ordinances regarding horn use but there have been no legislative attempts to address the technology. This raises questions about whether political leaders and policy setters are not exposed to RKE noise or do not discern RKE sounds from traffic noise and are therefore unaware of it. Using available auto industry data and case studies this paper will introduce key facts about RKE horn use in the United States and Canada reviewing new technologies that render noisy counterparts still in use as redundant.

Jeanine Botta

2013-01-01T23:59:59.000Z

234

Remote keyless entry honking, convenience horn honking, and audible car alarms: Redundancies and quieter options  

Science Journals Connector (OSTI)

Vehicle sound emissions car alarms and horn honking are the subject of many noise complaints. Auto manufacturers spent years engineering quieter vehicles and have created cars whose approach is so subtle that they pose a danger to blind pedestrians. But while engine noise has decreased and car alarms are less reactive horn honking that is linked with remote keyless entry (RKE) technology increasingly contributes to community noise. RKE horn noise has never been the subject of public health inquiry. In scientific literature discussion of road noise and health does not distinguish noise among separate sources and tends to measure aggregate ambient noise levels rather than impulsive noise. RKE horn noise violates state traffic laws and some local noise ordinances regarding horn use but there have been no legislative attempts to address the technology. This raises questions about whether political leaders and policy setters are not exposed to RKE noise or do not discern RKE sounds from traffic noise and are therefore unaware of it. Using available auto industry data and case studies this paper will introduce key facts about RKE horn use in the United States and Canada reviewing new technologies that render noisy counterparts still in use as redundant.

2013-01-01T23:59:59.000Z

235

The effects of early season and late season prescribed fires on small mammals in a Sierra Nevada mixed conifer forest  

Science Journals Connector (OSTI)

Prescribed fire is an important management tool used in the restoration of Sierra Nevada mixed conifer forests where fire has been suppressed over the last century. It is not well known, however, how the timing of prescribed fire affects wildlife populations. We used model selection and multi-model inference methods to compare the effects of early (spring and early summer) and late (late summer and fall) season prescribed fires on small mammal populations, based on 4 years of mark-recapture data collected in Sequoia National Park, California. The effects of prescribed fires on four small mammal metrics were evaluated: deer mouse (Peromyscus maniculatus) densities, deer mouse age ratios, lodgepole chipmunk (Neotamias speciosus) densities, and total small mammal biomass. For each of these four metrics, the top ranked model in the evaluation of prescribed fire treatment effects contained no prescribed fire effects, but did contain effects of strong year-to-year variation in populations. Models which predicted that fire effects differed depending on the season of fire received only limited support for each of the four metrics. Our results suggest that initial prescribed fires set during the early season will have similar impacts as late season fires on deer mouse populations, lodgepole chipmunk populations, and total small mammal biomass in Sierra Nevada mixed conifer forests.

Michelle E. Monroe; Sarah J. Converse

2006-01-01T23:59:59.000Z

236

Development of custom fire behavior fuel models from FCCS fuelbeds for the Savannah River fuel assessment project.  

SciTech Connect (OSTI)

The purpose of this project is to create fire behavior fuel models that replicate the fire behavior characteristics (spread rate and fireline intensity) produced by 23 candidate FCCS fuelbeds developed for the Savannah River National Wildlife Refuge. These 23 fuelbeds were created by FERA staff in consultation with local fuel managers. The FCCS produces simulations of surface fire spread rate and flame length (and therefore fireline intensity) for each of these fuelbeds, but it does not produce maps of those fire behavior characteristics or simulate fire growththose tasks currently require the use of the FARSITE and/or FlamMap software systems. FARSITE and FlamMap do not directly use FCCS fuelbeds, but instead use standard or custom fire behavior fuel models to describe surface fuel characteristics for fire modeling. Therefore, replicating fire growth and fire behavior potential calculations using FCCS?simulated fire characteristics requires the development of custom fuel models that mimic, as closely as possible, the fire behavior characteristics produced by the FCCS for each fuelbed, over a range of fuel moisture and wind speeds.

Scott, Joe, H.

2009-07-23T23:59:59.000Z

237

Fire Protection Account Request Form  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection System Account Request Form Fire Protection System Account Request Form To obtain a user id and password to access the Fire Protection system, please complete the form, save the file and email it to hssUserSupport@hq.doe.gov or print and fax it to 301-903-9823. We will provide a username and password to new account holders. Please allow several business days to process your account request. When your request is approved, you will be contacted with your

238

Fire and Ice Issue 3  

E-Print Network [OSTI]

,fpl ^1 FIRE AND ICE Available from: Kathleen Resch PO Box 1766 Temple City,CA 91780 III May, 1995 by Kathleen Resch for the contributors. No reprints or reproduction without the written permission of the author/artist. This is an amateur... publication and is not intended to infringe upon the rightsof "Blake's 7" copyright holders.. FIRE AND ICE TABLE OF CONTENTS THE GIFT by Pat Terra 1 "innerspace" by Pat Terra 24 WILD, BEAUTIFUL AND DAMNED by Gemini 25 SET THE NIGHT ON FIRE by Riley Cannon 40...

Multiple Contributors

1995-01-01T23:59:59.000Z

239

Fire Behavior at the Landscape Scale  

E-Print Network [OSTI]

Fire Behavior at the Landscape Scale Scott Stephens, ESPMScott Stephens, ESPM DepartmentStrategies for Landscape Fuel TreatmentsLandscape Fuel Treatments Fire Containment · Fuelbreaks Fire Modification · Area (WUI) ·· Maintenance? Must maintain into futureMaintenance? Must maintain into future #12;Tyee Fire

Stephens, Scott L.

240

Wildland Fire Protection Program NEBRASKA FOREST SERVICE  

E-Print Network [OSTI]

Wildland Fire Protection Program NEBRASKA FOREST SERVICE HOW NEBRASKANS BENEFIT: · improved protection of life and property from wildland fires · improved firefighting capability in rural fire districts · increased firefighter knowledge of wildland fire suppression and prevention · reduced forest

Farritor, Shane

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


241

FIRE PREVENTION AND PROTECTION Table Of Contents  

E-Print Network [OSTI]

EM 385-1-1 XX Sep 13 i Section 9 FIRE PREVENTION AND PROTECTION Table Of Contents Section: Page 09 and Melting Kettles.............................9-25 09.F First response Fire Protection FIRE PREVENTION AND PROTECTION 09.A GENERAL 09.A.01 A fire prevention plan shall be written for all

US Army Corps of Engineers

242

Firing of pulverized solvent refined coal  

DOE Patents [OSTI]

An air-purged burner for the firing of pulverized solvent refined coal is constructed and operated such that the solvent refined coal can be fired without the coking thereof on the burner components. The air-purged burner is designed for the firing of pulverized solvent refined coal in a tangentially fired boiler.

Derbidge, T. Craig (Sunnyvale, CA); Mulholland, James A. (Chapel Hill, NC); Foster, Edward P. (Macungie, PA)

1986-01-01T23:59:59.000Z

243

No material is "fire proof;" however, proper use and assembly of fire-rated building materials  

E-Print Network [OSTI]

C has the least resistance. However, Class A materials generally need an underlayment of additional-Defensible Zones 6.303, Fire-Resistant Landscaping 6.304, Forest Home Fire Safety 6.305, FireWise Plant Materials 6General No material is "fire proof;" however, proper use and assembly of fire-rated building

244

fire Protection The Fire Protection Technology associate degree is awarded by UNL's College of  

E-Print Network [OSTI]

fire Protection DeGreeS offereD A.S. The Fire Protection Technology associate degree is awarded Protection courses are taught by UNL College of Engineering faculty, as well as fire service and industry fire protection specialists. These fire protection specialists teach students not only from textbooks

Farritor, Shane

245

Fire Effects in Blue Oak Woodland1 Patricia K. Haggerty2  

E-Print Network [OSTI]

relationship between fire dates and new establishment on two Yuba County sites. Mensing (1988) reported Sierra Nevada, Tulare County, California. Land ownership included Bureau of Land Management, National Forestry Technician, Sequoia and Kings Canyon National Parks, Three Rivers, California, and Graduate

Standiford, Richard B.

246

Los Alamos National Laboratory - Reports  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

DOE Nuclear Safety Home Nuclear Sites Map Nuclear Sites List › Argonne National Laboratory › East Tennessee Technology Park › Hanford › Idaho Site › Los Alamos National Laboratory › Lawrence Livermore National Laboratory › Nevada National Security Site › New Brunswick Laboratory › Oak Ridge National Laboratory › Paducah › Pantex › Pacific Northwest National Laboratory › Portsmouth Gaseous Diffusion Plant › Sandia National Laboratories › Savannah River Site › Waste Isolation Pilot Plant › West Valley Demonstration Project › Y-12 National Security Complex HSS Reports - Enforcement - Corporate Safety Analysis Fire Protection DOELAP - Safety and Emergency Management Evaluations Safety Basis Information System Office of Corporate Safety Analysis

247

RCM and application at Sandia National Labs.  

SciTech Connect (OSTI)

Reliability-Centered Maintenance (RCM) is a process used to determine what must be done to ensure that any physical asset continues to do whatever its users want it to do in its present operating context. There are 7 basic questions of RCM: (1) what are the functions of the asset; (2) in hwat ways does it fail to fulfill its functions; (3) what causes each functional failure; (4) what happens when each failure occurs; (5) in what way does each failure matter; (6) what can be done to predict or prevent each failure; and (7) what should be done if a suitable proactive task cannot be found. SNL's RCM experiences: (1) acid exhaust system - (a) reduced risk of system failure (safety and operational consequences), (b) reduced annual correctiv maintenance hours from 138 in FY06 to zero in FY07, FY08, FY09, FY10 and FY11 so far, (c) identified single point of failure, mitigated risk, and recommended a permanent solution; (2) fire alarm system - (a) reduced false alarms, which cause costly evacuations, (b) precented 1- to 2-day evacuation by identifying and obtaining a critical spare for a network card; (3) heating water system - (a) reduced PM hours on fire-tube boilers by 60%, (b) developed operator tasks and PM plan for modular boilers, which can be applied to many installations; and (4) GIF source elevator system - (a) reduced frequency of PM tasks from 6 months to 1 year, (b) established predictive maintenance task that identified overheating cabinet and prevented potential electrical failure or fire.

Williams, Edward J., Jr.

2010-09-01T23:59:59.000Z

248

Fire in a contaminated area  

SciTech Connect (OSTI)

This document supports the development and presentation of the following accident scenario in the TWRS Final Safety Analysis Report: Fire in Contaminated Area. The calculations needed to quantify the risk associated with this accident scenario are included within.

Ryan, G.W., Westinghouse Hanford

1996-08-02T23:59:59.000Z

249

New Canadian Fire Research Laboratory  

Science Journals Connector (OSTI)

... which follows the time - temperature curve designated in the current U.S. Standard (ASTM E119-57, Standard Methods of Fire Tests of Building Construction and Materials).

R. F. LEGGET

1959-03-07T23:59:59.000Z

250

Model Fire Protection Assessment Guide  

Broader source: Energy.gov [DOE]

This Assessment guide covers the implementation of the DOE's responsibility of assuring that DOE and the DOE Contractors have established Fire Protection Programs that are at the level required for the area being assessed.

251

The Importance of Technical Reachback in the Adjudication of Radiation Alarms  

SciTech Connect (OSTI)

The large-scale deployment of radiation sensors at borders, ports-of-entry and other locations carries two disparate priorities: the reliable detection and identification of threat materials and the rapid characterization of non-threat materials comprised of naturally occurring radioactive materials (NORM) and legitimate radioactive materials in streams of commerce. These priorities are partially achieved through the technologies contained in the detection systems and the procedures developed for their operation. However, questions and ambiguities will occur. Without established capabilities and procedures for the operators of these detector systems to 'reach back' to trained spectroscopists and appropriate subject matter experts, the system will likely experience an unacceptable number of response operations and delays resolving alarms. Technical reachback operations need to be able to address the priorities discussed above while causing minimal perturbations in the flow of legitimate streams of commerce. Yet when necessary, reachback needs to be able to rapidly mobilize the appropriate response assets.

Buckley, W M; Allen, R W

2009-03-18T23:59:59.000Z

252

Incipient fire detection system  

DOE Patents [OSTI]

A method and apparatus for an incipient fire detection system that receives gaseous samples and measures the light absorption spectrum of the mixture of gases evolving from heated combustibles includes a detector for receiving gaseous samples and subjecting the samples to spectroscopy and determining wavelengths of absorption of the gaseous samples. The wavelengths of absorption of the gaseous samples are compared to predetermined absorption wavelengths. A warning signal is generated whenever the wavelengths of absorption of the gaseous samples correspond to the predetermined absorption wavelengths. The method includes receiving gaseous samples, subjecting the samples to light spectroscopy, determining wavelengths of absorption of the gaseous samples, comparing the wavelengths of absorption of the gaseous samples to predetermined absorption wavelengths and generating a warning signal whenever the wavelengths of absorption of the gaseous samples correspond to the predetermined absorption wavelengths. In an alternate embodiment, the apparatus includes a series of channels fluidically connected to a plurality of remote locations. A pump is connected to the channels for drawing gaseous samples into the channels. A detector is connected to the channels for receiving the drawn gaseous samples and subjecting the samples to spectroscopy. The wavelengths of absorption are determined and compared to predetermined absorption wavelengths is provided. A warning signal is generated whenever the wavelengths correspond.

Brooks, Jr., William K. (Newport News, VA)

1999-01-01T23:59:59.000Z

253

AMERICA'S NATIONAL LABS  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

AMERICA'S AMERICA'S NATIONAL LABS by 50 50 M A D E IN U S A B r e a k t h r o u g h s America's National Laboratory system has been changing and improving the lives of millions for more than 80 years. Born at a time of great societal need, this network of Department of Energy Laboratories has now grown into 17 facilities, working together as engines of prosperity and invention. As this list of 50 Break- throughs attests, National Laboratory discoveries have spawned industries, saved lives, generated new products, fired the imagination, and helped to reveal the secrets of the universe. Rooted in the need to be the best and bring the best, America's National Laboratories have put an American stamp on the past century of science. With equal ingenuity and tenacity, they are now engaged in

254

Fire-Induced Response in Foam Encapsulants  

SciTech Connect (OSTI)

The paper provides a concise overview of a coordinated experimental/theoretical/numerical program at Sandia National Laboratories to develop an experimentally validated model of fire-induced response of foam-filled engineered systems for nuclear and transportation safety applications. Integral experiments are performed to investigate the thermal response of polyurethane foam-filled systems exposed to fire-like heat fluxes. A suite of laboratory experiments is performed to characterize the decomposition chemistry of polyurethane. Mass loss and energy associated with foam decomposition and chemical structures of the virgin and decomposed foam are determined. Decomposition chemistry is modeled as the degradation of macromolecular structures by bond breaking followed by vaporization of small fragments of the macromolecule with high vapor pressures. The chemical decomposition model is validated against the laboratory data. Data from integral experiments is used to assess and validate a FEM foam thermal response model with the chemistry model developed from the decomposition experiments. Good agreement was achieved both in the progression of the decomposition front and the in-depth thermal response.

Borek, T.T.; Chu, T.Y.; Erickson, K.L.; Gill, W.; Hobbs, M.L.; Humphries, L.L.; Renlund, A.M.; Ulibarri, T.A.

1999-04-02T23:59:59.000Z

255

Oversight Reports - Lawrence Livermore National Laboratory | Department of  

Broader source: Energy.gov (indexed) [DOE]

Lawrence Livermore National Laboratory Lawrence Livermore National Laboratory Oversight Reports - Lawrence Livermore National Laboratory October 2, 2013 Independent Oversight Review, Lawrence Livermore National Laboratory - September 2013 Review of the Fire Protection Program at Lawrence Livermore National Laboratory July 19, 2013 Independent Oversight Review, Lawrence Livermore National Laboratory - July 2013 Review of Preparedness for Severe Natural Phenomena Events at the Lawrence Livermore National Laboratory April 12, 2013 Independent Activity Report, Lawrence Livermore National Laboratory - February 2013 Lawrence Livermore National Laboratory Operational Drill at the B332 Plutonium Facility [HIAR LLNL-2013-02-27] December 18, 2012 Independent Activity Report, Lawrence Livermore National Laboratory -

256

FireWxNet: a multi-tiered portable wireless system for monitoring weather conditions in wildland fire environments  

Science Journals Connector (OSTI)

In this paper we present FireWxNet, a multi-tiered portable wireless system for monitoring weather conditions in rugged wildland fire environments. FireWxNet provides the fire fighting community the ability to safely and easily measure and view fire ... Keywords: applications, deployments, fire, forest fires, wireless sensor networks

Carl Hartung; Richard Han; Carl Seielstad; Saxon Holbrook

2006-06-01T23:59:59.000Z

257

Evaluation of coverage of enriched UF{sub 6} cylinder storage lots by existing criticality accident alarms  

SciTech Connect (OSTI)

The Portsmouth Gaseous Diffusion Plant (PORTS) is leased from the US Department of Energy (DOE) by the United States Enrichment Corporation (USEC), a government corporation formed in 1993. PORTS is in transition from regulation by DOE to regulation by the Nuclear Regulatory Commission (NRC). One regulation is 10 CFR Part 76.89, which requires that criticality alarm systems be provided for the site. PORTS originally installed criticality accident alarm systems in all building for which nuclear criticality accidents were credible. Currently, however, alarm systems are not installed in the enriched uranium hexafluoride (UF{sub 6}) cylinder storage lots. This report analyzes and documents the extent to which enriched UF{sub 6} cylinder storage lots at PORTS are covered by criticality detectors and alarms currently installed in adjacent buildings. Monte Carlo calculations are performed on simplified models of the cylinder storage lots and adjacent buildings. The storage lots modelled are X-745B, X-745C, X745D, X-745E, and X-745F. The criticality detectors modelled are located in building X-343, the building X-344A/X-342A complex, and portions of building X-330. These criticality detectors are those located closest to the cylinder storage lots. Results of this analysis indicate that the existing criticality detectors currently installed at PORTS are largely ineffective in detecting neutron radiation from criticality accidents in most of the cylinder storage lots at PORTS, except sometimes along portions of their peripheries.

Lee, B.L. Jr.; Dobelbower, M.C.; Woollard, J.E.; Sutherland, P.J.; Tayloe, R.W. Jr.

1995-03-01T23:59:59.000Z

258

CRAD, Fire Protection - October 12, 2012 | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection - October 12, 2012 Fire Protection - October 12, 2012 CRAD, Fire Protection - October 12, 2012 October 12, 2012 Fire Protection Inspection Criteria, Approach, and Lines of Inquiry HSS CRAD 45-34, Rev. 1) Review fire protection system design and defense in-depth strategies. Interviews shall be conducted of personnel including fire engineers, fire coordinators, fire system technicians, facility operations personnel, and fire department personnel. Review policies, procedures, fire hazards analyses, and safety basis documentation. Additionally, perform facility building walk downs and inspections, and observe selected work activities, such as hot work, fire system impairments, combustible storage practices, dispensing flammable liquids, maintenance and testing of fire protection

259

Untrained Forward Observer (UFO) translator for call for fire .  

E-Print Network [OSTI]

??Many observers need indirect fire but are not proficient in Call for Fire, the procedure used to request indirect fire. To alleviate this, we propose (more)

King, Regan R.

2013-01-01T23:59:59.000Z

260

Fire in the Ice, Summer 2004  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

R R Vol. 4, Iss. 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ CONTENTS Gulf of Mexico Remote Observatory Update ............... 1 Hydrate Decomposition Studies at USGS .................... 5 NETL's HP View Cell Operational .......................... 10 Announcements .................. 13 * AAPG Hedberg Conference * JIP Drilling Delayed * TOUGH-Fx/HYDRATE v1.0 * Advisory Committee Meeting * Anaximander project Spotlight on Research ........ 16 Dr. Keith Kvenvolden CONTACT POINT Ray Boswell National Energy Technology Laboratory (304) 285-4541 (304) 285-4469 fax Ray.Boswell@netl.doe.gov The Fire in the Ice Newsletter is

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


261

Fire in the Ice, Fall 2004  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

4 4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ CONTENTS AAPG Hedberg Research Conference ............................ 1 Oak Ridge Facilities .............. 4 Relic Gas Hydrates of Northwestern Siberia ............. 8 Announcements .................. 11 * JIP Tests in the Gulf of Mexico * Planning Workshop Slated for Early Next Year Spotlight on Research ........ 12 Ingo Pecher CONTACT POINT Ray Boswell National Energy Technology Laboratory (304) 285-4541 (304) 285-4216 fax Ray.Boswell@netl.doe.gov The Fire in the Ice Newsletter is also available online at our website (http://www.netl.doe.gov/ scngo/Natural%20Gas/hydrates/)

262

Independent Oversight Review, Los Alamos National Laboratory - January 2012  

Broader source: Energy.gov (indexed) [DOE]

Los Alamos National Laboratory - Los Alamos National Laboratory - January 2012 Independent Oversight Review, Los Alamos National Laboratory - January 2012 January 2012 Review of the Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility Fire Suppression System The Office of Enforcement and Oversight (Independent Oversight), within the Office of Health, Safety and Security (HSS), conducted an independent review of the Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility (WCRRF) safety significant fire suppression system (FSS) vital safety system in conjunction with a scheduled Los Alamos Site Office (LASO) assessment. Overall, the LASO assessment was competently performed by knowledgeable LASO personnel using appropriate criteria as defined in LASO Procedure MP

263

EXHAUST GAS BOILER FIRE PERVENTION  

E-Print Network [OSTI]

Today's demands for better overall usability of fuel oil in large two-stroke low speed marine diesel engines greatly influenced their development, and the purity of their exhaust gases. With this paper we would like to indicate on to factors which directly influence on soot forming, deposition and cause of occurance of fire in exhaust gas boiler (EGB). Due the fact that a fire in the EGB can result in complete destruction of the boiler, and a longer interruption of the vessel commercial operations, crew must be familiar with the main reasons of soot deposition on the boiler tubes and elements and origination of fire, and to have taken proper and timely protection measures 1.

Branko Lali? Dipl. Ing; Mr. Ivan Komar; Dipl. Ing

264

ANNUAL FIRE SAFETY REPORT 2013 Ithaca, NY Campus  

E-Print Network [OSTI]

related services including programs in: · Fire Protection, Emergency Services, Emergency Management o Fire Protection Systems and Equipment o University Fire Marshal o Emergency Management o Events Management oANNUAL FIRE SAFETY REPORT 2013 Ithaca, NY Campus http

Chen, Tsuhan

265

ANNUAL FIRE SAFETY REPORT 2012 Ithaca, NY Campus  

E-Print Network [OSTI]

: · Fire Protection, Emergency Services, Emergency Management o Fire Protection Systems and Equipment oANNUAL FIRE SAFETY REPORT 2012 Ithaca, NY Campus http Annual Fire Safety Report 2012 Page 2 From the Department of Environmental Health and Safety (EH

Chen, Tsuhan

266

SOLVENT FIRE BY-PRODUCTS  

SciTech Connect (OSTI)

Southwest Research Institute (SwRI) conducted a burn test of the Caustic-Side Solvent Extraction (CSSX) solvent to determine the combustion products. The testing showed hydrogen fluoride gas is not a combustion product from a solvent fire when up to 70% of the solvent is consumed. The absence of HF in the combustion gases may reflect concentration of the modifier containing the fluoride groups in the unburned portion. SwRI reported results for other gases (CO, HCN, NOx, formaldehyde, and hydrocarbons). The results, with other supporting information, can be used for evaluating the consequences of a facility fire involving the CSSX solvent inventory.

Walker, D; Samuel Fink, S

2006-05-22T23:59:59.000Z

267

Fire and Ice Issue 2  

E-Print Network [OSTI]

. fipl cpn r FLASHPOINT A flame that can't be seen, cloaked in black and silver and disdain, born of anger and of love no longer dared. An ice-encrusted soul, dormant in the aftermath of accusations piled like snow against the heated passions of a man who...^ $$% i&l /P^ \\0 rffej FIRE AND ICE AVAILABLE FROM Kathleen Resch PO Box 1766 Temple City, CA 91780 FIRE AND ICE II TABLE OF CONTENTS COVER by Phoenix FRONTISPIECE by Gayle Feyrer "Flashpoint" by Rachel Duncan 1 PEDESTAL by Thomas 2 "A Damn Fine...

Multiple Contributors

1993-01-01T23:59:59.000Z

268

Fire Protection Engineering Qualification Standard Reference Guide  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection Fire Protection Engineering Qualification Standard Reference Guide SEPTEMBER 2009 This page is intentionally blank. Table of Contents i ACRONYMS ................................................................................................................................. ii PURPOSE.......................................................................................................................................1 SCOPE ............................................................................................................................................1 PREFACE.......................................................................................................................................1 TECHNICAL COMPETENCIES................................................................................................3

269

Fire performance of gable frame structures  

E-Print Network [OSTI]

Fire protection engineering and structural engineering are two relevant but separated fields of study. Many experiments conducted by fire protection engineers are under certain ideal boundary conditions, which may not be ...

Qian, Congyi

2013-01-01T23:59:59.000Z

270

Solid waste drum array fire performance  

SciTech Connect (OSTI)

Fire hazards associated with drum storage of radioactively contaminated waste are a major concern in DOE waste storage facilities. This report is the second of two reports on fire testing designed to provide data relative to the propagation of a fire among storage drum arrays. The first report covers testing of individual drums subjected to an initiating fire and the development of the analytical methodology to predict fire propagation among storage drum arrays. This report is the second report, which documents the results of drum array fire tests. The purpose of the array tests was to confirm the analytical methodology developed by Phase I fire testing. These tests provide conclusive evidence that fire will not propagate from drum to drum unless an continuous fuel source other than drum contents is provided.

Louie, R.L. [Westinghouse Hanford Co., Richland, WA (United States); Haecker, C.F. [Los Alamos Technical Associates, Inc., Kennewick, WA (United States); Beitel, J.J.; Gottuck, D.T.; Rhodes, B.T.; Bayier, C.L. [Hughes Associates, Inc., Baltimore, MD (United States)

1995-09-01T23:59:59.000Z

271

FireStream: Sensor Stream Processing for Monitoring Fire Spread Venkatesh Raghavan1  

E-Print Network [OSTI]

Institute, Worcester, MA 01609 2 Department of Fire Protection Engineering, Worcester Polytechnic Institute. In this demonstration, we present FireStream, a collabo- rative effort between Computer Science and Fire Protection experiments conducted at lab- oratories such as NIST/BFRL and the Department of Fire Protection Engineering

272

Wildland fire emissions, carbon, and climate: Wildland fire detection and burned area in the United States  

E-Print Network [OSTI]

Wildland fire emissions, carbon, and climate: Wildland fire detection and burned area in the United Wildland fires can be an important source of greenhouse gases as well as black carbon emissions that have of climate response to fire emissions compared to other emission sources of GHG, aerosols, and black carbon

273

Prescribed Fire As a Means of Reducing Forest Carbon Emissions in the Western United States  

Science Journals Connector (OSTI)

Prescribed Fire As a Means of Reducing Forest Carbon Emissions in the Western United States ... National Center for Atmospheric Research, 1850 Table Mesa Drive, Boulder, Colorado 80301 and Western Regional Center of the National Institute for Climatic Change Research, Northern Arizona University, PO Box 6077, Flagstaff, Arizona 86011 ... Daily estimates of fire emissions of CO2 were calculated for 2001?2008 for eleven states in the western U.S. (Arizona, California, Colorado, Idaho, Montana, New Mexico, Nevada, Oregon, Utah, Washington, and Wyoming). ...

Christine Wiedinmyer; Matthew D. Hurteau

2010-02-11T23:59:59.000Z

274

Planning Rural Fire Protection for Texas.  

E-Print Network [OSTI]

IOC rA24S.7 73 ).1196 (Blank Pa.ge InOdgiuat Bulletinl ~ ; ''; . : .. . ~. " PLANNING RURAL FIRE PROTECTION FOR TEXAS JACK L. JONES, EXTENSION COMMUNITY DEVELOPMENT SPECIALIST TEXAS AGRICULTURAL EXTENSION SERVICE INTRODUCTION A home fire... is one of the most feared accidents a homeowner can? have, especially in rural areas where extended distances, inadequate water supplies or lack of any community fire fighting services limit fire fighting capability. Unless a rural resident makes prior...

Jones, Jack L.

1981-01-01T23:59:59.000Z

275

Nuclear incident monitor criticality alarm instrument for the Savannah River Site: Technical manual  

SciTech Connect (OSTI)

The Savannah River Site is a Department of Energy facility. The facility stores, processes, and works with fissionable material at a number of locations. Technical standards and US Department of Energy orders, require these locations to be monitored by criticality alarm systems under certain circumstances. The Savannah River Site calls such instruments Nuclear Incident Monitors or NIMs. The Sole purpose of the Nuclear Incident Monitor is to provide an immediate evacuation signal in the case of an accidental criticality in order to minimize personnel exposure to radiation. The new unit is the third generation Nuclear Incident Monitor at the Savannah River Site. The second generation unit was developed in 1979. It was designed to eliminate vacuum-tube circuits, and was the first solid state NIM at SRS. The major design objectives of the second generation NIM were to improve reliability and reduce maintenance costs. Ten prototype units have been built and tested. This report describes the design of the new NIM and the testing that took place to verify its acceptability.

Jenkins, J.B.

1996-05-21T23:59:59.000Z

276

Emergency Management Program, Brookhaven National Laboratory, BNL  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Management Management Homepage Emergency Management Mike Venegoni, Manager Brookhaven National Laboratory Bldg. 860 - P.O. Box 5000 Upton, NY 11973-5000 (631) 344-7280 E-mail: mvenegoni@bnl.gov Emergency Management Program Brookhaven National Laboratory :: Fire Danger Index - LOW The Fire Danger Index level takes into account current and antecedent weather, fuel types, and both live and dead fuel moisture. ▪ Index Description (pdf) ▪ NWS Fire Weather Forecast :: Important Information EMERGENCY Numbers Offsite: 631-344-2222 ▪ Emergency Services ▪ Hurricane Awareness :: Be Alert, Be Aware! Watch out for unattended bags/packages and report any unusual or suspicious incidents immediately to Police Headquarters by calling: 631-344-2222 The mission of the Emergency Management Program at Brookhaven National Laboratory is provide the framework for development, coordination, control, and direction of all emergency planning, preparedness, readiness assurance, response, and recovery actions.

277

CONSTITUTION AND BY-LAWS FIRE DEPARTMENT  

E-Print Network [OSTI]

of lives, and the protection of property endangered by fires and other disasters, and to promote the teaching and practice of fire prevention and protection. ARTICLE II Section 1. The OfficersSAMPLE CONSTITUTION AND BY-LAWS OF THE FIRE DEPARTMENT WHEREAS, Certain laws and regulations

278

Fire Protection Systems Program Program Manual  

E-Print Network [OSTI]

Fire Protection Systems Program Program Manual Approved by: (name) Last revised by: (name) Revision/FPS_Program_Manual_Template.docx 1. Introduction The Fire Protection Systems Program is designed to make sure the annual compliance ................................................................................................................. 3 7.1.1 Job Plan: Fire Pump Testing

Pawlowski, Wojtek

279

Research Overview Department of Fire Protection Engineering  

E-Print Network [OSTI]

Research Overview Department of Fire Protection Engineering University of Maryland College Park, MD, detection M.J. Gollner wildfires, flammability, structures A.W. Marshall fire flows, combustion, suppression J.A. Milke structures, detection, egress S.I. Stoliarov pyrolysis, flammability, fire growth P

Shapiro, Benjamin

280

Independent Activity Report, Los Alamos National Laboratory - April 2010 |  

Broader source: Energy.gov (indexed) [DOE]

Activity Report, Los Alamos National Laboratory - April Activity Report, Los Alamos National Laboratory - April 2010 Independent Activity Report, Los Alamos National Laboratory - April 2010 April 2010 Los Alamos Site Office Assessment of Fire Protection Activities at the Los Alamos National Laboratory The U.S. Department of Energy Office of Independent Oversight, within the Office of Health, Safety and Security, in coordination with the Los Alamos Site Office (LASO), provided a technical expert to conduct several fire protection oversight activities, including validation of Los Alamos County's Fire Hydrant Flow Test Methodology and a review of Los Alamos National Laboratory Equivalency Request Review Process in support of LASO oversight of the contractor. Independent Activity Report, Los Alamos National Laboratory - April 2010

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


281

Imperial College London FIRE SERVICES  

E-Print Network [OSTI]

to minimise the hazard the following precautions are recommended: Christmas tree lights, fibre optic trees hazards. Avoid leaving Christmas lights on unattended for long periods. Lighted candles are generally at Christmas During the lead up to Christmas the risk of fire can be increased with the introduction

282

HOURGLASS FIRE Pingree Park Vicinity  

E-Print Network [OSTI]

needles). Fuel moistures were extremely low throughout Colorado during spring/early summer of 1994 firefighters in a blowup near Glenwood Springs. Table 1 indicates dead fuel moistures in the Pingree Park). Spotting was occurring 1/2 mile in advance of the fire. By this time personnel/engines from Colorado State

283

Applications of Living Fire PRA models to Fire Protection Significance Determination Process in Taiwan  

SciTech Connect (OSTI)

The living fire probabilistic risk assessment (PRA) models for all three operating nuclear power plants (NPPs) in Taiwan had been established in December 2000. In that study, a scenario-based PRA approach was adopted to systematically evaluate the fire and smoke hazards and associated risks. Using these fire PRA models developed, a risk-informed application project had also been completed in December 2002 for the evaluation of cable-tray fire-barrier wrapping exemption. This paper presents a new application of the fire PRA models to fire protection issues using the fire protection significance determination process (FP SDP). The fire protection issues studied may involve the selection of appropriate compensatory measures during the period when an automatic fire detection or suppression system in a safety-related fire zone becomes inoperable. The compensatory measure can either be a 24-hour fire watch or an hourly fire patrol. The living fire PRA models were used to estimate the increase in risk associated with the fire protection issue in terms of changes in core damage frequency (CDF) and large early release frequency (LERF). In compliance with SDP at-power and the acceptance guidelines specified in RG 1.174, the fire protection issues in question can be grouped into four categories; red, yellow, white and green, in accordance with the guidelines developed for FD SDP. A 24-hour fire watch is suggested only required for the yellow condition, while an hourly fire patrol may be adopted for the white condition. More limiting requirement is suggested for the red condition, but no special consideration is needed for the green condition. For the calculation of risk measures, risk impacts from any additional fire scenarios that may have been introduced, as well as more severe initiating events and fire damages that may accompany the fire protection issue should be considered carefully. Examples are presented in this paper to illustrate the evaluation process. (authors)

De-Cheng, Chen; Chung-Kung, Lo; Tsu-Jen, Lin; Ching-Hui, Wu [Institute of Nuclear Energy Research, P. O. Box 3-3, Lung-Tan, Tao-Yuan Taiwan (China); Lin, James C. [ABSG Consulting Inc., 300 Commerce Drive, Suite 200, Irvine, CA 92602 (United States)

2004-07-01T23:59:59.000Z

284

Pantex High Pressure Fire Loop Project Completed On Time, Under Budget |  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

High Pressure Fire Loop Project Completed On Time, Under Budget | High Pressure Fire Loop Project Completed On Time, Under Budget | National Nuclear Security Administration Our Mission Managing the Stockpile Preventing Proliferation Powering the Nuclear Navy Emergency Response Recapitalizing Our Infrastructure Continuing Management Reform Countering Nuclear Terrorism About Us Our Programs Our History Who We Are Our Leadership Our Locations Budget Our Operations Media Room Congressional Testimony Fact Sheets Newsletters Press Releases Speeches Events Social Media Video Gallery Photo Gallery NNSA Archive Federal Employment Apply for Our Jobs Our Jobs Working at NNSA Blog Home > Media Room > Press Releases > Pantex High Pressure Fire Loop Project Completed ... Press Release Pantex High Pressure Fire Loop Project Completed On Time, Under Budget

285

Prestigious Coal-Fired Project of the Year Award Goes to Plant  

Broader source: Energy.gov (indexed) [DOE]

Prestigious Coal-Fired Project of the Year Award Goes to Plant Prestigious Coal-Fired Project of the Year Award Goes to Plant Demonstrating Innovative DOE-Funded Technology Prestigious Coal-Fired Project of the Year Award Goes to Plant Demonstrating Innovative DOE-Funded Technology December 16, 2010 - 12:00pm Addthis Washington, DC - An innovative project demonstrating DryFining™ technology, a more cost-effective way to control coal-based power plant emissions while improving fuel quality, has been named the 2010 Coal-Fired Project of the Year by the editors of Power Engineering magazine. The project, managed by the Office of Fossil Energy's National Energy Technology Laboratory, was developed with funding from the Department of Energy's Clean Coal Power Initiative and was originally implemented at Great River Energy's Coal Creek Station in Underwood, ND, in 2009. The

286

Numerical prediction of heat-flux to massive calorimeters engulfed in regulatory fires with the cask analysis fire environment (CAFE) model  

SciTech Connect (OSTI)

Recent observations show that the thermal boundary conditions within large-scale fires are significantly affected by the presence of thermally massive objects. These objects cool the soot and gas near their surfaces, and these effects reduce the incoming radiant heat-flux to values lower than the levels expected from simple {sigma}T{sub fire}{sup 4} models. They also affect the flow and temperature fields in the fire far from their surfaces. The Cask Analysis Fire Environment (CAFE) code has been developed at Sandia National Laboratories to provide an enhanced fire boundary condition for the design of radioactive material packages. CAFE is a set of computer subroutines that use computational fluid mechanics methods to predict convective heat transfer and mixing. It also includes models for fuel and oxygen transport, chemical reaction, and participating-media radiation heat transfer. This code uses two-dimensional computational models so that it has reasonably short turnaround times on standard workstations and is well suited for design and risk studies. In this paper, CAFE is coupled with a commercial finite-element program to model a large cylindrical calorimeter fully engulfed in a pool fire. The time-dependent heat-flux to the calorimeter and the calorimeter surface temperature are determined for several locations around the calorimeter circumference. The variation of heat-flux with location is determined for calorimeters with different diameters and wall thickness, and the observed effects discussed.

KOSKI,JORMAN A.; SUO-ANTITLA,AHTI; KRAMER,M. ALEX; GREINER,MILES

2000-05-11T23:59:59.000Z

287

GLOVEBOX WINDOWS, FIRE PROTECTION AND VOICES FROM THE PAST  

SciTech Connect (OSTI)

'Study the past--what is past is prologue'. These words appear as the motto on a pair of statues at the National Archives Building in Washington DC. They are also the opening sentence in the preface of a document written in August of 1956 entitled 'A Summary of Accidents and Incidents Involving Radiation in Atomic Energy Activities--June 1945 thru December 1955'. This document, one of several written by D.F. Hayes of the Safety and Fire Protection Branch, Division of Organization and Personnel, U.S. Atomic Energy Commission in Washington DC, and many others are often forgotten even though they contain valuable glovebox fire protection lessons for us today.

Till, W

2009-04-15T23:59:59.000Z

288

Stirling engines for gas fired micro-cogen and cooling  

SciTech Connect (OSTI)

This paper describes the design and performance of free-piston Stirling engine-alternators particularly suited for use as natural gas fired micro-cogen and cooling devices. Stirling based cogen systems offer significant potential advantages over internal combustion engines in efficiency, to maintain higher efficiencies at lower power levels than than combustion engines significantly expands the potential for micro-cogen. System cost reduction and electric prices higher than the U.S. national average will have a far greater effect on commercial success than any further increase in Stirling engine efficiency. There exist niche markets where Stirling engine efficiency. There exist niche markets where Stirling based cogen systems are competitive. Machines of this design are being considered for production in the near future as gas-fired units for combined heat and power in sufficiently large quantities to assure competitive prices for the final unit.

Lane, N.W.; Beale, W.T. [Sunpower, Inc., Athens, OH (United States)

1996-12-31T23:59:59.000Z

289

Aging assessment for active fire protection systems  

SciTech Connect (OSTI)

This study assessed the impact of aging on the performance and reliability of active fire protection systems including both fixed fire suppression and fixed fire detection systems. The experience base shows that most nuclear power plants have an aggressive maintenance and testing program and are finding degraded fire protection system components before a failure occurs. Also, from the data reviewed it is clear that the risk impact of fire protection system aging is low. However, it is assumed that a more aggressive maintenance and testing program involving preventive diagnostics may reduce the risk impact even further.

Ross, S.B. [Science and Engineering Associates, Inc. (United States); Nowlen, S.P.; Tanaka, T. [Sandia National Labs., Albuquerque, NM (United States)

1995-06-01T23:59:59.000Z

290

Safety & Emergency Management  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

designed ESH 108 Building Orientation course. Fire Alarm System Testing Through Argonne Fire Protection Services, the fire alarm system is tested visually and audibly annually....

291

Pigments which reflect infrared radiation from fire  

DOE Patents [OSTI]

Conventional paints transmit or absorb most of the intense infrared (IR) radiation emitted by fire, causing them to contribute to the spread of fire. The present invention comprises a fire retardant paint additive that reflects the thermal IR radiation emitted by fire in the 1 to 20 micrometer (.mu.m) wavelength range. The important spectral ranges for fire control are typically about 1 to about 8 .mu.m or, for cool smoky fires, about 2 .mu.m to about 16 .mu.m. The improved inventive coatings reflect adverse electromagnetic energy and slow the spread of fire. Specific IR reflective pigments include titanium dioxide (rutile) and red iron oxide pigments with diameters of about 1 .mu.m to about 2 .mu.m and thin leafing aluminum flake pigments.

Berdahl, Paul H. (Oakland, CA)

1998-01-01T23:59:59.000Z

292

Pigments which reflect infrared radiation from fire  

DOE Patents [OSTI]

Conventional paints transmit or absorb most of the intense infrared (IR) radiation emitted by fire, causing them to contribute to the spread of fire. The present invention comprises a fire retardant paint additive that reflects the thermal IR radiation emitted by fire in the 1 to 20 micrometer ({micro}m) wavelength range. The important spectral ranges for fire control are typically about 1 to about 8 {micro}m or, for cool smoky fires, about 2 {micro}m to about 16 {micro}m. The improved inventive coatings reflect adverse electromagnetic energy and slow the spread of fire. Specific IR reflective pigments include titanium dioxide (rutile) and red iron oxide pigments with diameters of about 1 {micro}m to about 2 {micro}m and thin leafing aluminum flake pigments. 4 figs.

Berdahl, P.H.

1998-09-22T23:59:59.000Z

293

Fire protection program fiscal year 1997 site support program plan - Hanford fire department  

SciTech Connect (OSTI)

The mission of the Hanford Fires Department (HFD) is to support the safe and timely cleanup of the Hanford Site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating situations which could threaten the operations, employees, or interest of the US Department of Energy operated Hanford Site. this includes response to surrounding fire department districts under mutual aids agreements and contractual fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System) and various commercial entities operating on site. the fire department also provides site fire marshal overview authority, fire system testing, and maintenance, respiratory protection services, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention and education.

Good, D.E., Westinghouse Hanford

1996-07-01T23:59:59.000Z

294

Fire Protection Program fiscal year 1996, site support program plan Hanford Fire Department. Revision 2  

SciTech Connect (OSTI)

The mission of the Hanford Fire Department (HFD) is to support the safe and timely cleanup of the Hanford site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating emergency situations which could threaten the operations, employees, or interest of the US Department of Energy operated Hanford Site. This includes response to surrounding fire departments/districts under a mutual aid agreement and contractual fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System). The fire department also provides site fire marshal overview authority, fire system testing and maintenance, self-contained breathing apparatus maintenance, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention education. This report gives a program overview, technical program baselines, and cost and schedule baseline.

Good, D.E.

1995-09-01T23:59:59.000Z

295

Fire protection program fiscal year 1995 site support program plan, Hanford Fire Department  

SciTech Connect (OSTI)

The mission of the Hanford Fire Department (HFD) is to support the safe and timely cleanup of the Hanford site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating emergency situations which could threaten the operations, employees, or interest of the US Department of Energy operated Hanford Site. This includes response to surrounding fire departments/districts under a mutual aid agreement and contractual fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System). The fire department also provides site fire marshal overview authority, fire system testing and maintenance, self-contained breathing apparatus maintenance, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention education. This report describes the specific responsibilities and programs that the HFD must support and the estimated cost of this support for FY1995.

Good, D.E.

1994-09-01T23:59:59.000Z

296

Response to Comment on Prescribed Fire As a Means of Reducing Forest Carbon Emissions in the Western United States  

Science Journals Connector (OSTI)

Response to Comment on Prescribed Fire As a Means of Reducing Forest Carbon Emissions in the Western United States ... Western Regional Center of the National Institute for Climatic Change Research, Northern Arizona University, Flagstaff, Arizona, and National Center for Atmospheric Research, Boulder, Colorado ...

Matthew D. Hurteau; Christine Wiedinmyer

2010-07-23T23:59:59.000Z

297

NETL: News Release - Updated Report Consolidates Information about Nation's  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

16, 2007 16, 2007 Updated Report Consolidates Information about Nation's Existing Fleet of Coal-Fired Power Plants MORE INFO Link to NETL's 2007 Coal Power Plant Database Washington, DC - The Office of Fossil Energy's National Energy Technology Laboratory (NETL) has released its 2007 Coal Power Plant Database, a new, updated version which contains the most current and comprehensive collection of coal-fired power plant data in the United States. The database consolidates large quantities of information on the nation's existing coal-fired power plants in a single location. It covers 191 fields and provides information on more than 1,700 boilers and associated units. Emissions, generation, location, and firing data for all U.S. coal-power plants are located in the database, which supports DOE's Office of Fossil

298

Fire hazard analysis for the fuel supply shutdown storage buildings  

SciTech Connect (OSTI)

The purpose of a fire hazards analysis (FHA) is to comprehensively assess the risk from fire and other perils within individual fire areas in a DOE facility in relation to proposed fire protection so as to ascertain whether the objectives of DOE 5480.7A, Fire Protection, are met. This Fire Hazards Analysis was prepared as required by HNF-PRO-350, Fire Hazards Analysis Requirements, (Reference 7) for a portion of the 300 Area N Reactor Fuel Fabrication and Storage Facility.

REMAIZE, J.A.

2000-09-27T23:59:59.000Z

299

BIOFUELS FOR TRANSPORT IN THE 21st WHY FIRE SAFETY IS A REAL ISSUE  

E-Print Network [OSTI]

BIOFUELS FOR TRANSPORT IN THE 21st CENTURY: WHY FIRE SAFETY IS A REAL ISSUE Guy Marlair1 , Patricia's), with thé new century venue we are assisting of a booming industry regarding biofuels of biofuels for transport. This contribution is a fîrst output from a National research program named

Paris-Sud XI, Université de

300

Aerosols from Fires: An Examination of the Effects on Ozone Photochemistry in the Western United States  

Science Journals Connector (OSTI)

National Center for Atmospheric Research, Boulder, Colorado, United States ... Sensitivity simulations of a wildfire event that occurred in Idaho and Montana in August 2007 were carried out to understand these impacts. ... Wildfires burned more than 1.1 million ha in Montana and Idaho in 2007 (http://www.nifc.gov/nicc/predictive/intelligence/2007_statssumm/fires_acres.pdf ...

Xiaoyan Jiang; Christine Wiedinmyer; Annmarie G. Carlton

2012-09-26T23:59:59.000Z

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


301

Slipstream Testing of a Membrane CO2 Capture Process for Existing Coal-Fired Power Plants  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Testing of a Membrane CO Testing of a Membrane CO 2 Capture Process for Existing Coal-Fired Power Plants Background The mission of the U.S. Department of Energy/National Energy Technology Laboratory (DOE/NETL) Existing Plants, Emissions & Capture (EPEC) Research & Development (R&D) Program is to develop innovative environmental control technologies to enable full use of the nation's vast coal reserves, while at the same time allowing the current fleet of

302

Jupiter Oxy-combustion and Integrated Pollutant Removal for the Existing Coal Fired Power Generation Fleet  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Jupiter Oxy-combustion and Integrated Jupiter Oxy-combustion and Integrated Pollutant Removal for the Existing Coal Fired Power Generation Fleet Background The mission of the U.S. Department of Energy/National Energy Technology Laboratory (DOE/NETL) Existing Plants, Emissions & Capture (EPEC) Research & Development (R&D) Program is to develop innovative environmental control technologies to enable full use of the nation's vast coal reserves, while at the same time allowing the current fleet of

303

How to Choose and Use Fire Extinguishers  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

How to Choose and Use Fire Extinguishers How to Choose and Use Fire Extinguishers By: John Kelsey, This Old House magazine A fire extinguisher can be a lifesaver. Placed near an exit, in an easy-to-grab spot, it can put out a small fire before the firefighters arrive, or at least suppress the flames while you escape. All household extinguishers are classified A, B, or C (or a combination of these) on the label to indicate which types of fires - ordinary combustibles, flammable liquids, or electrical-you can use them on. Many of the ones sold at home stores are classified A:B:C and fight all three types of fires. The main distinction among home extinguishers is size. In most cases bigger is better, but sometimes the biggest extinguishers are too heavy to maneuver. (The weight on an extinguisher refers to

304

FAQS Job Task Analyses - Fire Protection Engineering  

Broader source: Energy.gov (indexed) [DOE]

Job Task Analysis and Competency Review Job Task Analysis and Competency Review for All Level Competencies Fire Protection Engineering FAQS Initially conducted (expert competencies): August 2010 Updated (includes ALL Competencies): April 2011 Updated (includes ALL Competencies): October 2012 STEP 1: Job Task Analysis for Tasks Task (and Number) Source Importance Frequency Serve as the subject matter expert in the area of fire protection, life safety, and fire department emergency related services. FAQS Duties and Responsibilities Paragraph A 5 4 Review fire hazard analyses, assessments, and other fire safety documentation for compliance with applicable requirements. FAQS Duties and Responsibilities Paragraph B 5 3 Evaluate the adequacy of site emergency services. This includes all facets of the fire

305

Fire Hazard Analysis for the Cold Vacuum Drying (CVD) Facility  

SciTech Connect (OSTI)

This Fire Hazard Analysis assesses the risk from fire within individual fire areas in the Cold Vacuum Drying Facility at the Hanford Site in relation to existing or proposed fire protection features to ascertain whether the objectives of DOE Order 5480.7A Fire Protection are met.

JOHNSON, B.H.

1999-08-19T23:59:59.000Z

306

University of Vermont 2012 Student Housing Fire Safety Report  

E-Print Network [OSTI]

awards from FM Global (insurance) for fire protection programs. All on-campus residence halls by automatic cooking fire suppression systems. All fire protection systems are inspected regularly by UVM staff Marcus, Certified Fire Protection Specialist, University Fire Marshal 284 East Avenue, Burlington, VT

Hayden, Nancy J.

307

ENVIRONMENT, SAFETY & HEALTH DIVISION Chapter 12: Fire and Life Safety  

E-Print Network [OSTI]

ENVIRONMENT, SAFETY & HEALTH DIVISION Chapter 12: Fire and Life Safety Fire Protection Equipment The purpose of these requirements is to ensure the adequate provision and operability of fire protection Requirements Fire protection equipment includes Automatic fire suppression systems (such as sprinkler, clean

Wechsler, Risa H.

308

TU Vienna Fire Protection Regulations 1 General provisions  

E-Print Network [OSTI]

TU Vienna Fire Protection Regulations § 1 General provisions § 2 Scope § 3 Responsibility for preventive fire protection § 7 Conduct in the event of fire § 8 Assembly point § 9 Measures following a fire § 1 General provisions (1) Purpose and relationship to other legal regulations a) The fire protection

Szmolyan, Peter

309

Interagency Panel: Agency Fire Management Chair: Philip N. Omi  

E-Print Network [OSTI]

of Forestry and Fire Protection: Fire Management Summary1 Wayne Mitchell2 Abstract The California Department of Forestry and Fire Protection (CDF) is a full service wildland, rural, and urban fire department. CDF acres. About 55 percent of CDF's $452 million annual budget is used for wildland fire protection

Standiford, Richard B.

310

ENVIRONMENT, SAFETY & HEALTH DIVISION Chapter 12: Fire and Life Safety  

E-Print Network [OSTI]

ENVIRONMENT, SAFETY & HEALTH DIVISION Chapter 12: Fire and Life Safety Fire Protection SystemProcedImpair.pdf The purpose of these procedures is to minimize the downtime of active fire protection systems by closely controlling their impairment (any condition in which a fire protection system cannot perform its designed fire

Wechsler, Risa H.

311

Sandia National Laboratories: Sandia National Laboratories: Missions:  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

results. Our areas of accomplishment for results. Our areas of accomplishment for 2010 include: Nuclear Weapons Engineering People photo 90-day Feasibility Study: Sandia researchers conducted a 90-day feasibility study for the Office of the Secretary of Defense in a common arming, fuzing, and firing (AF&F) system for the W78/Mk12A and W88/Mk5 warheads, with excursions of the AF&F for high-surety warheads and the W87/Mk21 systems. The study found that significant levels of AF&F commonality are possible with existing system architectures that support use in the Mk5, Mk12A, and Mk21 re-entry systems and enable modernization goals for the future stockpile. People photo Arming & Fuzing Subsystem Inspection: On July 23, 2010, the 500th Arming & Fuzing Subsystem (AFS) was accepted by the National Nuclear

312

Gas reburning in tangentially-fired, wall-fired and cyclone-fired boilers  

SciTech Connect (OSTI)

Gas Reburning has been successfully demonstrated for over 4,428 hours on three coal fired utility boilers as of March 31, 1994. Typically, NO{sub x} reductions have been above 60% in long-term, load-following operation. The thermal performance of the boilers has been virtually unaffected by Gas Reburning. At Illinois Power`s Hennepin Station, Gas Reburning in a 71 MWe tangentially-fired boiler achieved an average NO{sub x} reduction of 67% from the original baseline NO{sub x} level of 0.75 lb NO{sub x}/10{sup 6} Btu over a one year period. The nominal natural gas input was 18% of total heat input. Even at 10% gas heat input, NO{sub x} reduction of 55% was achieved. At Public Service Company of Colorado`s Cherokee Station, a Gas Reburning-Low NO{sub x} Burner system on a 172 MWe wall-fired boiler has achieved overall NO{sub x} reductions of 60--73% in parametric and long-term testing, based on the original baseline NO{sub x} level of 0.73 lb/10{sup 6} Btu. NO{sub x} reduction is as high as 60--65% even at relatively low natural gas usage (5--10% of total heat input). The NO{sub x} reduction by Low NO{sub x} Burners alone is typically 30--40%. NO{sub x} reduction has been found to be insensitive to changes in recirculated flue gas (2--7% of total flue gas) injected with natural gas. At City Water, Light and Power Company`s Lakeside Station in Springfield, Illinois, Gas Reburning in a 33 MWe cyclone-fired boiler has achieved an average NO{sub x} reduction of 66% (range 52--77%) at gas heat inputs of 20--26% in long-term testing, based on a baseline NO{sub x} level of 1.0 lb/10{sup 6} Btu (430 mg/MJ). This paper presents a summary of the operating experience at each site and discusses the long term impacts of applying this technology to units with tangential, cyclone and wall-fired (with Low NO{sub x} Burner) configurations.

May, T.J. [Illinois Power Co., Decatur, IL (United States); Rindahl, E.G. [Public Service Co. of Colorado, Denver, CO (United States); Booker, T. [City Water Light and Power, Springfield, IL (United States)] [and others

1994-12-31T23:59:59.000Z

313

Fire in the Ice, Winter 2005  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Understanding Methane Understanding Methane Hydrate Behavior .................... 1 Quantitative Assessment of Marine Gas Hydrates ............. 5 New Method for Gas Hydrate Production .............................. 8 Announcements .................. 12 * International Workshop * Chiba, Hedberg Abstracts * Chemists Highlight Hydrates * NETL Solicits Proposals * IODP Planning Two Cruises * Gulf of Mexico Expedition * TOUGH-Fx Training Offered Spotlight on Research ........ 16 Dr. Frank R. Rack CONTACT POINT Ray Boswell National Energy Technology Laboratory (304) 285-4541 (304) 285-4216 fax Ray.Boswell@netl.doe.gov The Fire in the Ice Newsletter is also available online at our website www.netl.doe.gov/scngo/ Natural%20Gas/hydrates T H E N A T I O N A L E N E R G Y T E C H N O L O G Y L A B O R A T O R Y M E T H A N E H Y D R A T E N E W S L E T T E R Vol. 5, Iss. 1

314

Fire in the Ice, Spring 2005  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Marine Multi-Component Marine Multi-Component Seismology ............................ 1 Discovery of Possible Gas Hydrate Features ................... 5 Monitoring Station Update ..... 8 Announcements .................. 10 * Research Cruise Completed * Advisory Committee Meeting * Hot Ice Project Reports * Norway ICGH Meeting * Simulator Publicly Released * TOUGH-Fx/HYDRATE V 2.4 * AAPG Committee to Meet Spotlight on Research ........ 12 Scott Dallimore CONTACT POINT Ray Boswell National Energy Technology Laboratory (304) 285-4541 (304) 285-4216 fax Ray.Boswell@netl.doe.gov The Fire in the Ice Newsletter is also available online at our website www.netl.doe.gov/scngo/ NaturalGas/hydrates/index.html T H E N A T I O N A L E N E R G Y T E C H N O L O G Y L A B O R A T O R Y M E T H A N E H Y D R A T E N E W S L E T T E R Vol. 5, Iss. 2 ○ ○ ○ ○ ○

315

Cryogenic slurry for extinguishing underground fires  

DOE Patents [OSTI]

A cryogenic slurry comprising a mixture of solid carbon dioxide particles suspended in liquid nitrogen is provided which is useful in extinguishing underground fires.

Chaiken, Robert F. (Pittsburgh, PA); Kim, Ann G. (Pittsburgh, PA); Kociban, Andrew M. (Wheeling, WV); Slivon, Jr., Joseph P. (Tarentum, PA)

1994-01-01T23:59:59.000Z

316

LNG fire and vapor control system technologies  

SciTech Connect (OSTI)

This report provides a review of fire and vapor control practices used in the liquefied natural gas (LNG) industry. Specific objectives of this effort were to summarize the state-of-the-art of LNG fire and vapor control; define representative LNG facilities and their associated fire and vapor control systems; and develop an approach for a quantitative effectiveness evaluation of LNG fire and vapor control systems. In this report a brief summary of LNG physical properties is given. This is followed by a discussion of basic fire and vapor control design philosophy and detailed reviews of fire and vapor control practices. The operating characteristics and typical applications and application limitations of leak detectors, fire detectors, dikes, coatings, closed circuit television, communication systems, dry chemicals, water, high expansion foam, carbon dioxide and halogenated hydrocarbons are described. Summary descriptions of a representative LNG peakshaving facility and import terminal are included in this report together with typical fire and vapor control systems and their locations in these types of facilities. This state-of-the-art review identifies large differences in the application of fire and vapor control systems throughout the LNG industry.

Konzek, G.J.; Yasutake, K.M.; Franklin, A.L.

1982-06-01T23:59:59.000Z

317

(BSET) FIRE SAFETY ENGINEERING TECHNOLOGY CURRICULUM FOUR YEAR FIRE SAFETY CONCENTRATION CURRICULUM  

E-Print Network [OSTI]

. ETFS 4323 3 Intro to Performance-based Fire Safety8 ETFS 32338 3 Ethical Issues and Cultural Critique3(BSET) FIRE SAFETY ENGINEERING TECHNOLOGY CURRICULUM FOUR YEAR FIRE SAFETY CONCENTRATION CURRICULUM 3 Technical Drawing I ETGR 1103 2 Western Culture and Hist. Awareness LBST 2101 3 Total Hours 16

Raja, Anita

318

What is prescribed fire? Prescribed fire is the controlled application of  

E-Print Network [OSTI]

What is prescribed fire? Prescribed fire is the controlled application of fire to the land an uncontrolled wildfire occur. What is a burn prescription? A burn prescription helps ensure that the objectives species to naturally regenerate. (Lodgepole pine is one such example.) What about the smoke? Controlling

319

Housing & Residence Education Disclosure of Fire Safety Standards and Measures 1 Campus Fire Safety Right-to-Know  

E-Print Network [OSTI]

Housing & Residence Education Disclosure of Fire Safety Standards and Measures 1 Campus Fire Safety and death resulting from each fire. #12;Housing & Residence Education Disclosure of Fire Safety Standards) -- HVAC fan motor burned up -- Alpha Chi Omega -- 3/13/10 $1,500 (Greek) -- Futon mattress caught fire

Fang, Yuguang "Michael"

320

Housing & Residence Education Disclosure of Fire Safety Standards and Measures 1 Campus Fire Safety Right-to-Know  

E-Print Network [OSTI]

Housing & Residence Education Disclosure of Fire Safety Standards and Measures 1 Campus Fire Safety and death resulting from each fire. #12;Housing & Residence Education Disclosure of Fire Safety Standards) -- Grease Fire -- Beaty Towers -- 9/10/10 $100 (Greek) -- HVAC fan motor burned up -- Alpha Chi Omega -- 3

Slatton, Clint

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


321

Sample Lesson Plan Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection 1 Sample Lesson Plan  

E-Print Network [OSTI]

, Emergency Action Plans, Fire Prevention Plans, and Fire Protection Overview of the OSHA Standard Subpart E problems finding and using it. Subpart L, Fire Protection, contains requirements for fire brigades, and all installed to meet the fire protection requirements of 29 CFR Part 1910. Step 1: Planning the Lesson

Homes, Christopher C.

322

Commercialization Development of Oxygen Fired CFB for Greenhouse Gas Control  

SciTech Connect (OSTI)

Given that fossil fuel fired power plants are among the largest and most concentrated producers of CO{sub 2} emissions, recovery and sequestration of CO{sub 2} from the flue gas of such plants has been identified as one of the primary means for reducing anthropogenic (i.e., man-made) CO{sub 2} emissions. In 2001, ALSTOM Power Inc. (ALSTOM) began a two-phase program to investigate the feasibility of various carbon capture technologies. This program was sponsored under a Cooperative Agreement from the US Department of Energy's National Energy Technology Laboratory (DOE). The first phase entailed a comprehensive study evaluating the technical feasibility and economics of alternate CO{sub 2} capture technologies applied to Greenfield US coal-fired electric generation power plants. Thirteen cases, representing various levels of technology development, were evaluated. Seven cases represented coal combustion in CFB type equipment. Four cases represented Integrated Gasification Combined Cycle (IGCC) systems. Two cases represented advanced Chemical Looping Combined Cycle systems. Marion, et al. reported the details of this work in 2003. One of the thirteen cases studied utilized an oxygen-fired circulating fluidized bed (CFB) boiler. In this concept, the fuel is fired with a mixture of oxygen and recirculated flue gas (mainly CO{sub 2}). This combustion process yields a flue gas containing over 80 percent (by volume) CO{sub 2}. This flue gas can be processed relatively easily to enrich the CO{sub 2} content to over 96 percent for use in enhanced oil or gas recovery (EOR or EGR) or simply dried for sequestration. The Phase I study identified the O{sub 2}-fired CFB as having a near term development potential, because it uses conventional commercial CFB technology and commercially available CO{sub 2} capture enabling technologies such as cryogenic air separation and simple rectification or distillation gas processing systems. In the long term, air separation technology advancements offer significant reductions in power requirements, which would improve plant efficiency and economics for the oxygen-fired technology. The second phase consisted of pilot-scale testing followed by a refined performance and economic evaluation of the O{sub 2} fired CFB concept. As a part of this workscope, ALSTOM modified its 3 MW{sub th} (9.9 MMBtu/hr) Multiuse Test Facility (MTF) pilot plant to operate with O{sub 2}/CO{sub 2} mixtures of up to 70 percent O{sub 2} by volume. Tests were conducted with coal and petroleum coke. The test objectives were to determine the impacts of oxygen firing on heat transfer, bed dynamics, potential agglomeration, and gaseous and particulate emissions. The test data results were used to refine the design, performance, costs, and economic models developed in Phase-I for the O{sub 2}-fired CFB with CO{sub 2} capture. Nsakala, Liljedahl, and Turek reported results from this study in 2004. ALSTOM identified several items needing further investigation in preparation for large scale demonstration of the oxygen-fired CFB concept, namely: (1) Operation and performance of the moving bed heat exchanger (MBHE) to avoid recarbonation and also for cost savings compared to the standard bubbling fluid bed heat exchanger (FBHE); (2) Performance of the back-end flash dryer absorber (FDA) for sulfur capture under high CO{sub 2}/high moisture flue gas environment using calcined limestone in the fly ash and using fresh commercial lime directly in the FDA; (3) Determination of the effect of recarbonation on fouling in the convective pass; (4) Assessment of the impact of oxygen firing on the mercury, other trace elements, and volatile organic compound (VOC) emissions; and (5) Develop a proposal-level oxygen-fired retrofit design for a relatively small existing CFB steam power plant in preparation for a large-scale demonstration of the O{sub 2} fired CFB concept. Hence, ALSTOM responded to a DOE Solicitation to address all these issues with further O{sub 2} fired MTF pilot testing and a subsequent retrofit design study of oxygen firing and CO{s

Nsakala ya Nsakala; Gregory N. Liljedahl; David G. Turek

2007-03-31T23:59:59.000Z

323

Steam Plant Replaces Outdated Coal-Fired System | Department...  

Office of Environmental Management (EM)

Steam Plant Replaces Outdated Coal-Fired System September 1, 2012 - 12:00pm Addthis A new natural gas-fired steam plant will replace an older coal-fired steam plant shown here. The...

324

Fire Ecology Special Issue Vol. 5, No. 1, 2009  

E-Print Network [OSTI]

-fire rainfall events. Soil losses in the high end of that range definitely exceed soil loss tolerances, humankind transformed fire into one of its oldest tools. Human and lightning ignited fires altered

325

Old Dominion University Annual Security and Fire Safety Report  

E-Print Network [OSTI]

Protection Features in Residence Halls____________________ 21 Residential Facilities Fire Safety AmenitiesOld Dominion University 2012 Annual Security and Fire Safety Report All statements and policies _________________________________________ 17 Fire Safety ______________________________________________________________ 19 Residence Halls

326

FSEP-Rev.02 Fire Safety Evacuation Plan  

E-Print Network [OSTI]

.......................................................................................... 1 3.2 Fire Protection Authority ............................................................................................... 2 3.5 Fire Protection EquipmentFSEP-Rev.02 Fire Safety Evacuation Plan Henrietta Harvey Building Prepared By: Graham Mowbray Date

Oyet, Alwell

327

Fire Protection Engineering Four Year Academic Plan Name:_______________________________________________ UID:___________________________  

E-Print Network [OSTI]

Fire Protection Engineering Four Year Academic Plan Name;FIRE PROTECTION ENGINEERING NAME: _____________________________________ Major Requirements Requirements Dev Seminar 1 ENFP 405 - Structural Fire Protection 3 Requirements Course Credits Grade ENFP 410

Shapiro, Benjamin

328

FSEP-Rev.02 Fire Safety Evacuation Plan  

E-Print Network [OSTI]

.......................................................................................... 4 3.2 Fire Protection Authority ............................................................................................... 5 3.5 Fire Protection EquipmentFSEP-Rev.02 Fire Safety Evacuation Plan Ocean Sciences Centre Prepared By: Connie Short Date: April

Oyet, Alwell

329

ANNUAL FIRE SAFETY REPORT 2011 Ithaca, NY Campus  

E-Print Network [OSTI]

Plan ____________________________________________________ 14 Cornell University Fire Safety Plan including programs in: Fire Protection, Emergency Services, Emergency Management o Fire Protection Services o Research and Laboratory Safety o Chemical Safety o Radiation Safety o Biological Safe

Chen, Tsuhan

330

Underground Salt Haul Truck Fire at the Waste Isolation Pilot...  

Office of Environmental Management (EM)

Underground Salt Haul Truck Fire at the Waste Isolation Pilot Plant February 5, 2014 March 2014 Salt Haul Truck Fire at the Waste Isolation Pilot Plant Salt Haul Truck Fire at the...

331

Independent Oversight Review, Los Alamos National Laboratory Chemistry and  

Broader source: Energy.gov (indexed) [DOE]

Laboratory Laboratory Chemistry and Metallurgy Research Facility - January 2012 Independent Oversight Review, Los Alamos National Laboratory Chemistry and Metallurgy Research Facility - January 2012 January 2012 Review of the Los Alamos National Laboratory Chemistry and Metallurgy Research Facility Fire Suppression Vital Safety System The Office of Enforcement and Oversight (Independent Oversight), within the Office of Health, Safety and Security (HSS), conducted an independent review of the Los Alamos National Laboratory Chemistry and Metallurgy Research (CMR) Facility safety significant fire suppression system (FSS) vital safety system in conjunction with a scheduled Los Alamos Site Office (LASO) assessment. The purpose of the LASO assessment was to evaluate the

332

Independent Oversight Review, Los Alamos National Laboratory - January 2012  

Broader source: Energy.gov (indexed) [DOE]

2 2 Independent Oversight Review, Los Alamos National Laboratory - January 2012 January 2012 Review of the Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility Fire Suppression System The Office of Enforcement and Oversight (Independent Oversight), within the Office of Health, Safety and Security (HSS), conducted an independent review of the Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility (WCRRF) safety significant fire suppression system (FSS) vital safety system in conjunction with a scheduled Los Alamos Site Office (LASO) assessment. Overall, the LASO assessment was competently performed by knowledgeable LASO personnel using appropriate criteria as defined in LASO Procedure MP

333

Coal-fired diesel generator  

SciTech Connect (OSTI)

The objective of the proposed project is to test the technical, environmental, and economic viability of a coal-fired diesel generator for producing electric power in small power generating markets. Coal for the diesel generator would be provided from existing supplies transported for use in the University`s power plant. A cleanup system would be installed for limiting gaseous and particulate emissions. Electricity and steam produced by the diesel generator would be used to supply the needs of the University. The proposed diesel generator and supporting facilities would occupy approximately 2 acres of land adjacent to existing coal- and oil-fired power plant and research laboratory buildings at the University of Alaska, Fairbanks. The environmental analysis identified that the most notable changes to result from the proposed project would occur in the following areas: power plant configuration at the University of Alaska, Fairbanks; air emissions, water use and discharge, and the quantity of solid waste for disposal; noise levels at the power plant site; and transportation of coal to the power plant. No substantive adverse impacts or environmental concerns were identified in analyzing the effects of these changes.

NONE

1997-05-01T23:59:59.000Z

334

Fire and explosion hazards of oil shale  

SciTech Connect (OSTI)

The US Bureau of Mines publication presents the results of investigations into the fire and explosion hazards of oil shale rocks and dust. Three areas have been examined: the explosibility and ignitability of oil shale dust clouds, the fire hazards of oil shale dust layers on hot surfaces, and the ignitability and extinguishment of oil shale rubble piles. 10 refs., 54 figs., 29 tabs.

Not Available

1989-01-01T23:59:59.000Z

335

Managing Imported Fire Ants in Urban Areas  

E-Print Network [OSTI]

The imported fire ant is found in much of Texas and across the southeastern U.S. This publication describes options for managing the pest in specific locations such as home lawns, gardens and buildings. Other topics include fire ant treatment...

Drees, Bastiaan M.

2006-08-17T23:59:59.000Z

336

The Fire Walk Ceremony in Tahiti  

Science Journals Connector (OSTI)

... all essential particulars with those in the accounts already cited. According to these, a pit was dug in which large stones were heated red hot by a fire which had ... dug in which large stones were heated red hot by a fire which had been burning many hours. The upper stones were pushed away just before the ceremony, so as ...

S. P. LANGLEY

1901-08-22T23:59:59.000Z

337

Modeling long-term fire regimes of southern California shrublands1 (Suggested running head: "Modeling fire regimes with HFire")3  

E-Print Network [OSTI]

of three fire regime metrics (fire size24 distributions, fire return interval maps, cumulative total area pattern of ignitions, fuels, weather,38 and topography, and describes the size, spatial pattern

Carlson, Jean

338

The Simulation Analysis of Fire Feature on Underground Substation  

Science Journals Connector (OSTI)

Underground transformer substations constructed with non-dwelling buildings have a ... out simulation analysis of fire feature on underground substation. The corresponding fire protection strategy is also...

Xin Han; Xie He; Beihua Cong

2012-01-01T23:59:59.000Z

339

Suspension-fired biomass boilers. Three case studies  

SciTech Connect (OSTI)

A discussion of the conversion of oil-or gas-fired boilers to fire pulverized bark and wood wastes in suspension.

Robinson, L.

1986-01-01T23:59:59.000Z

340

Version 2 Global Fire Emissions Database Available  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Global Fire Emissions Database Available Global Fire Emissions Database Available The ORNL DAAC announces the release of the data set "Global Fire Emissions Database, Version 2 (GFEDv2)." This data set, which supersedes and replaces the Global Fire Emissions Database, Version 1 (GFEDv1), consists of 1 degree x 1 degree gridded monthly burned area, fuel loads, combustion completeness, and fire emissions of carbon (C), carbon dioxide (CO2), carbon monoxide (CO), methane (CH4), non-methane hydrocarbons (NMHC), molecular hydrogen (H2), nitrogen oxides (NOx), nitrous oxide (N2O), particulate matter (PM2.5), total particulate matter (TPM), total carbon (TC), organic carbon (OC), and black carbon (BC) for the time period January 1997 - December 2004. For more information or to access this data set, please see the Vegetation

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


341

Repository Subsurface Preliminary Fire Hazard Analysis  

SciTech Connect (OSTI)

This fire hazard analysis identifies preliminary design and operations features, fire, and explosion hazards, and provides a reasonable basis to establish the design requirements of fire protection systems during development and emplacement phases of the subsurface repository. This document follows the Technical Work Plan (TWP) (CRWMS M&O 2001c) which was prepared in accordance with AP-2.21Q, ''Quality Determinations and Planning for Scientific, Engineering, and Regulatory Compliance Activities''; Attachment 4 of AP-ESH-008, ''Hazards Analysis System''; and AP-3.11Q, ''Technical Reports''. The objective of this report is to establish the requirements that provide for facility nuclear safety and a proper level of personnel safety and property protection from the effects of fire and the adverse effects of fire-extinguishing agents.

Richard C. Logan

2001-07-30T23:59:59.000Z

342

NNSA joins other federal agencies to build Interagency Fire Center in New  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

joins other federal agencies to build Interagency Fire Center in New joins other federal agencies to build Interagency Fire Center in New Mexico | National Nuclear Security Administration Our Mission Managing the Stockpile Preventing Proliferation Powering the Nuclear Navy Emergency Response Recapitalizing Our Infrastructure Continuing Management Reform Countering Nuclear Terrorism About Us Our Programs Our History Who We Are Our Leadership Our Locations Budget Our Operations Media Room Congressional Testimony Fact Sheets Newsletters Press Releases Speeches Events Social Media Video Gallery Photo Gallery NNSA Archive Federal Employment Apply for Our Jobs Our Jobs Working at NNSA Blog Home > NNSA Blog > NNSA joins other federal agencies to build ... NNSA joins other federal agencies to build Interagency Fire Center in New Mexico Posted By Office of Public Affairs

343

NNSA joins other federal agencies to build Interagency Fire Center in New  

National Nuclear Security Administration (NNSA)

joins other federal agencies to build Interagency Fire Center in New joins other federal agencies to build Interagency Fire Center in New Mexico | National Nuclear Security Administration Our Mission Managing the Stockpile Preventing Proliferation Powering the Nuclear Navy Emergency Response Recapitalizing Our Infrastructure Continuing Management Reform Countering Nuclear Terrorism About Us Our Programs Our History Who We Are Our Leadership Our Locations Budget Our Operations Media Room Congressional Testimony Fact Sheets Newsletters Press Releases Speeches Events Social Media Video Gallery Photo Gallery NNSA Archive Federal Employment Apply for Our Jobs Our Jobs Working at NNSA Blog Home > NNSA Blog > NNSA joins other federal agencies to build ... NNSA joins other federal agencies to build Interagency Fire Center in New Mexico Posted By Office of Public Affairs

344

t_fired.p65  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

-MWE DEMONSTRATION OF ADVANCED -MWE DEMONSTRATION OF ADVANCED TANGENTIALLY FIRED COMBUSTION TECHNIQUES FOR THE REDUCTION OF NO X EMISSIONS SOUTHERN COMPANY SERVICES, INC. PROJECT PERFORMANCE SUMMARY CLEAN COAL TECHNOLOGY DEMONSTRATION PROGRAM JUNE 1999 DOE/FE-0397 Disclaimer This report was prepared using publically available information, including the Final Technical Report and other reports prepared pursuant to a cooperative agreement partially funded by the U.S. Department of Energy. Neither the United States Government nor any agency, employee, contractor, or representative thereof, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe upon privately

345

Coal-Fired Power Plants  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Impacts of TMDLs on Impacts of TMDLs on Coal-Fired Power Plants April 2010 DOE/NETL-2010/1408 Disclaimer This report was prepared as an account of work sponsored by an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference therein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof. The

346

Preliminary Notice of Violation, National Security Technologies, LLC -  

Broader source: Energy.gov (indexed) [DOE]

National Security Technologies, National Security Technologies, LLC - NEA-2011-03 Preliminary Notice of Violation, National Security Technologies, LLC - NEA-2011-03 August 11, 2011 Preliminary Notice of Violation issued to National Security Technologies, LLC related to Deficiencies in Inspection and Installation of Penetration Fire Seals and Other Components at the Nevada National Security Site The Office of Health, Safety and Security's Office of Enforcement and Oversight has completed its investigation into the facts and circumstances associated with quality assurance (QA) related deficiencies in the inspection and installation of penetration fire seals and other components at the Criticality Experiments Facility (CEF) and the Device Assembly Facility (OAF) at the Nevada National Security Site. The results of

347

Kuwaiti oil fires: Composition of source smoke  

SciTech Connect (OSTI)

While the Kuwaiti oil-fire smoke plumes manifested a pronounced impact on solar radiation in the Gulf region (visibility, surface temperatures, etc.), smoke plume concentrations of combustion-generated pollutants suggest that the overall chemical impact on the atmosphere of the smoke from these fires was probably much less than anticipated. Combustion in the Kuwaiti oil fires was surprisingly efficient, releasing on average more than 93% of the combusted hydrocarbon fuels as carbon dioxide (CO{sub 2}). Correspondingly, combustion-produced quantities of carbon monoxide (CO) and carbonaceous particles were low, each {approximately} 2% by weight. The fraction of methane (CH{sub 4}) produced by the fires was also relatively low ({approximately} 0.2%), but source emissions of nonmethane hydrocarbons were high ({approximately} 2%). Processes other than combustion (e.g., volatilization) probably contributed significantly to the measured in-plume hydrocarbon concentrations. Substantially, different elemental to organic carbon ratios were obtained for aerosol particles from several different types of fires/smokes. Sulfur emissions (particulate and gaseous) measured at the source fires were lower ({approximately} 0.5%) than predicted based on average sulfur contents in the crude. Sulfur dioxide measurements (SO{sub 2}) reported herein, however, were both limited in actual number and in the number of well fires sampled. Nitrous oxide (N{sub 2}O) emissions from the Kuwaiti oil fires were very low and often could not be distinguished from background concentrations. About 25-30% of the fires produced white smoke plumes that were found to be highly enriched in sodium and calcium chlorides. 18 refs., 1 fig., 4 tabs.

Cofer, W.R. III; Cahoon, D.R. [Langley Research Center, Hampton, VA (United States); Stevens, R.K.; Pinto, J.P. [Environmental Protection Agency, Research Triangle Park, NC (United States); Winstead, E.L.; Sebacher, D.I. [Hughes STX Corp., Hampton, VA (United States); Abdulraheem, M.Y. [Kuwait Environmental Protection Dept., Kuwait City (Kuwait); Al-Sahafi, M. [Ministry of Defense and Aviation, Eastern Province (Saudi Arabia); Mazurek, M.A. [Brookhaven National Lab., Upton, NY (United States); Rasmussen, R.A. [Oregon Graduate Institute of Science and Technology, Beaverton, OR (United States)] [and others

1992-09-20T23:59:59.000Z

348

PACIFIC ISLANDS DIGITAL ELEVATION MODELS Coastal Models Supporting our Nation's Needs through Science and Technology  

E-Print Network [OSTI]

. Seismic activity at plate boundaries along the Pacific Ring of Fire, along with other tectonic stresses as a protected national monument with the other northwestern Hawaiian Islands, and is managed by the U.S. Fish

349

Fire Safety Tests for Cesium-Loaded Spherical Resorcinol Formaldehyde Resin: Data Summary Report  

SciTech Connect (OSTI)

A draft safety evaluation of the scenario for spherical resorcinol formaldehyde (SRF) resin fire inside the ion exchange column was performed by the Hanford Tank Waste Treatment and Immobilization Plant (WTP) Fire Safety organization. The result of this draft evaluation suggested a potential change of the fire safety classification for the Cesium Ion Exchange Process System (CXP) emergency elution vessels, equipment, and piping. To resolve this question, the fire properties of the SRF resin were measured by Southwest Research Institute (SwRI) through a subcontract managed by Pacific Northwest National Laboratory (PNNL). The results of initial fire safety tests on the SRF resin were documented in a previous report (WTP-RPT-218). The present report summarizes the results of additional tests performed by SwRI on the cesium-loaded SRF resin. The efforts by PNNL were limited to summarizing the test results provided by SwRI into one consolidated data report. The as-received SwRI report is attached to this report in the Appendix A. Where applicable, the precision and bias of each test method, as given by each American Society for Testing and Materials (ASTM) standard procedure, are included and compared with the SwRI test results of the cesium-loaded SRF resin.

Kim, Dong-Sang; Schweiger, Michael J.; Peterson, Reid A.

2012-09-01T23:59:59.000Z

350

Material Analysis for a Fire Assessment.  

SciTech Connect (OSTI)

This report consolidates technical information on several materials and material classes for a fire assessment. The materials include three polymeric materials, wood, and hydraulic oil. The polymers are polystyrene, polyurethane, and melamine- formaldehyde foams. Samples of two of the specific materials were tested for their behavior in a fire - like environment. Test data and the methods used to test the materials are presented. Much of the remaining data are taken from a literature survey. This report serves as a reference source of properties necessary to predict the behavior of these materials in a fire.

Brown, Alexander; Nemer, Martin

2014-08-01T23:59:59.000Z

351

The Research about Fire Prevention of Vehicle Refuelling Stations  

Science Journals Connector (OSTI)

Abstract Fuel oil and gas offered by vehicle refuelling stations have combustion and explosion characteristics, serious casualties and economic losses often caused by fire. The research about oil and gas fire risk, refuelling process and facilities, proposing appropriate fire prevention measures possess great significance for reducing refuelling stations fire losses, and ensuring the safety of the station and surrounding environment.

Hong-yu Zhang

2014-01-01T23:59:59.000Z

352

Fire Hazards Analysis for the Inactive Equipment Storage Sprung Structure  

SciTech Connect (OSTI)

The purpose of the analysis is to comprehensively assess the risk from fire within individual fire areas in relation to proposed fire protection so as to ascertain whether the fire protection objective of DOE Order 5480.1A are met. The order acknowledges a graded approach commensurate with the hazards involved.

MYOTT, C.F.

2000-02-03T23:59:59.000Z

353

Justification to remove 333 Building fire suppression system  

SciTech Connect (OSTI)

Justification to remove the 333 Building fire suppression system is provided. The Maximum Possible Fire Loss (MPFL) is provided (approximately $800K), potential radiological and toxicological impacts from a postulated fire are discussed, Life Safety Code issues are addressed, and coordination with the Hanford Fire Department is assured.

Benecke, M.W.

1995-12-04T23:59:59.000Z

354

Page 1 of 3 Policy: Fire Protection Equipment Policy  

E-Print Network [OSTI]

Page 1 of 3 Policy: Fire Protection Equipment Policy Responsible Party: Director, Safety and Risk The Office of Safety and Risk Management (SRM) has developed, and implemented the Fire Protection Equipment of Fire Protection Equipment throughout MSU to maintain its working order. Fire Protection Equipment

Dyer, Bill

355

(BSET) -FIRE SAFETY ENGINEERING TECHNOLOGY CURRICULUM Effective Fall 2003  

E-Print Network [OSTI]

Disasters State and Local Government Active Fire Protection Fire Safety Engr. Prob. Analysis Sem. & Year.Apps Intro to Fire Protection* (3hrs) Hydraulics and Water Distribution* (3hrs) FSET Specific Life Education* (3hrs) Building Construction* (3hrs) (not offered at UNCC) ETFS 1252 -Fire Protection Law (not

Raja, Anita

356

WASTE HANDLING BUILDING FIRE PROTECTION SYSTEM DESCRIPTION DOCUMENT  

SciTech Connect (OSTI)

The Waste Handling Building Fire Protection System provides the capability to detect, control, and extinguish fires and/or mitigate explosions throughout the Waste Handling Building (WHB). Fire protection includes appropriate water-based and non-water-based suppression, as appropriate, and includes the distribution and delivery systems for the fire suppression agents. The Waste Handling Building Fire Protection System includes fire or explosion detection panel(s) controlling various detectors, system actuation, annunciators, equipment controls, and signal outputs. The system interfaces with the Waste Handling Building System for mounting of fire protection equipment and components, location of fire suppression equipment, suppression agent runoff, and locating fire rated barriers. The system interfaces with the Waste Handling Building System for adequate drainage and removal capabilities of liquid runoff resulting from fire protection discharges. The system interfaces with the Waste Handling Building Electrical Distribution System for power to operate, and with the Site Fire Protection System for fire protection water supply to automatic sprinklers, standpipes, and hose stations. The system interfaces with the Site Fire Protection System for fire signal transmission outside the WHB as needed to respond to a fire emergency, and with the Waste Handling Building Ventilation System to detect smoke and fire in specific areas, to protect building high-efficiency particulate air (HEPA) filters, and to control portions of the Waste Handling Building Ventilation System for smoke management and manual override capability. The system interfaces with the Monitored Geologic Repository (MGR) Operations Monitoring and Control System for annunciation, and condition status.

J. D. Bigbee

2000-06-21T23:59:59.000Z

357

FAQS Qualification Card - Fire Protection | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection Fire Protection FAQS Qualification Card - Fire Protection A key element for the Department's Technical Qualification Programs is a set of common Functional Area Qualification Standards (FAQS) and associated Job Task Analyses (JTA). These standards are developed for various functional areas of responsibility in the Department, including oversight of safety management programs identified as hazard controls in Documented Safety Analyses (DSA). For each functional area, the FAQS identify the minimum technical competencies and supporting knowledge and skills for a typical qualified individual working in the area. FAQC-FireProtection-2007.docx Description Fire Protection Qualification Card - 2007 FAQC-FireProtection-2000.docx Description Fire Protection Qualification Card - 2000

358

Fire Protection Database | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection Database Fire Protection Database Fire Protection Database DOE O 231.1, Environment, Safety, And Health Reporting, requires the submission of an Annual Fire Protection Summary. The previous process used to collect the required data utilizes a Microsoft Access database that was downloaded, completed by the field and then sent to Headquarters for summation and analysis by engineers in Office of Sustainability Support. Data collection for the CY2013 Summary will begin Jan. 1, 2014, and a commitment has been made to the Defense Nuclear Facilities Safety Board to collect this information and make it available utilizing a standard systematic approach. This approach will be accomplished via a web based system which will allow reporting organizations to enter or edit information.

359

Fire victim helped by area programs  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Fire victim helped by area programs Fire victim helped by area programs Fire victim helped by local nonprofit organizations A perennial helper, didn't realize that she might someday need help herself. April 3, 2012 Beatrice Dubois is grateful for the help she received from Lab-supported Beatrice Dubois is grateful for the help she received from Lab-supported, local nonprofits during her time of need. Contact Kurt Steinhaus Community Programs Office (505) 665-7370 Email Beatrice Dubois, dedicated fundraiser, assisted after home fire Beatrice Dubois has always been a strong advocate for LANL employee giving programs. Every year, she organizes a bake sale in support of the annual employee giving campaign and musters support with her coworkers for the Lab's annual holiday drive. A perennial helper, she didn't realize

360

Fire Island Wind Project | Open Energy Information  

Open Energy Info (EERE)

Island Wind Project Island Wind Project Jump to: navigation, search Name Fire Island Wind Project Facility Fire Island Wind Project Sector Wind energy Facility Type Commercial Scale Wind Facility Status In Service Owner CIRI Developer Fire Island Wind LLC Energy Purchaser Chugach Location Fire Island AK Coordinates 61.144146°, -150.217652° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":61.144146,"lon":-150.217652,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


361

MODELING VENTILATION SYSTEM RESPONSE TO FIRE  

SciTech Connect (OSTI)

Fires in facilities containing nuclear material have the potential to transport radioactive contamination throughout buildings and may lead to widespread downwind dispersal threatening both worker and public safety. Development and implementation of control strategies capable of providing adequate protection from fire requires realistic characterization of ventilation system response which, in turn, depends on an understanding of fire development timing and suppression system response. This paper discusses work in which published HEPA filter data was combined with CFAST fire modeling predictions to evaluate protective control strategies for a hypothetical DOE non-reactor nuclear facility. The purpose of this effort was to evaluate when safety significant active ventilation coupled with safety class passive ventilation might be a viable control strategy.

Coutts, D

2007-04-17T23:59:59.000Z

362

Fire Protection Training | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Project. The goal of this contract was to provide needed information and a method to train fire departments and other emergency responders who may be called upon to respond to...

363

ANNUAL FIRE SAFETY REPORT For Student Housing  

E-Print Network [OSTI]

and in the public areas of each of these 15 halls. The smoke detectors located in Estill Street Complex are battery, emergency lights and fire egress systems. Twenty Eight of the 50 apartments in the Ecovillage, designed

Baltisberger, Jay H.

364

Fire Protection Program Guidelines | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

14, 1995 Guidelines for Developing Medical Standards for Fire Fighters December 1994 Primer on Spontaneous Heating and Pyrophoricity (DOE-HDBK-1081-94) Oct 1994 Guidance for the...

365

Annual Fire Protection Summary Information Reporting Guide  

Broader source: Energy.gov [DOE]

The Department of Energy (DOE) Annual Fire Protection Program Summary continues the series started in 1972. The report annually summarizes monetary loss information sent to Headquarters by reporting elements.

366

Physically-based realistic fire rendering  

Science Journals Connector (OSTI)

Accurately rendering fires is a challenging problem due to the various subtle ways in which the electromagnetic waves interact with this complex participating medium. We present a new method for physically-based rendering of flames from detailed simulations ...

Vincent Pegoraro; Steven G. Parker

2006-09-01T23:59:59.000Z

367

POST-FIRE REVEGETATION AT HANFORD  

SciTech Connect (OSTI)

Range fires on the Hanford Site can have a long lasting effect on native plant communities. Wind erosion following removal of protective vegetation from fragile soils compound the damaging effect of fires. Dust storms caused by erosion create health and safety hazards to personnel, and damage facilities and equipment. The Integrated Biological Control Program (IBC) revegetates burned areas to control erosion and consequent dust. Use of native, perennial vegetation in revegetation moves the resulting plant community away from fire-prone annual weeds, and toward the native shrub-steppe that is much less likely to burn in the future. Over the past 10 years, IBC has revegetated major fire areas with good success. IBC staff is monitoring the success of these efforts, and using lessons learned to improve future efforts.

ROOS RC; JOHNSON AR; CAUDILL JG; RODRIGUEZ JM; WILDE JW

2010-01-05T23:59:59.000Z

368

California State Fire Marshal Information Bulletin  

Alternative Fuels and Advanced Vehicles Data Center [Office of Energy Efficiency and Renewable Energy (EERE)]

California State Fire Marshal California State Fire Marshal Information Bulletin April 27, 2009 INFORMATION REGARDING PLACEMENT OF E85 FUEL DISPENSING EQUIPMENT ON STATE OWNED OR STATE LEASED FACILITIES In an effort to assist interested parties with criteria addressing E85 dispensing equipment, the Office of the State Fire Marshal (OSFM) is providing this informational bulletin. E85 is the acronym for an alcohol-blended gasoline fuel that contains between 15 to 85 percent ethanol (alcohol). Presently, there are over 10,000 gas service stations in California selling petroleum fuels (gasoline and diesel); and the number of stations dispensing E85 fuel continues to increase. The California Fire Code (CFC) and Title 19 of the California Code of Regulations (CCR) require all fuel-dispensers to be listed and labeled by an approved testing

369

Final Manuscript submitted to the Fire Safety Journal Chen et. al., Fire detection using smoke and gas sensors  

E-Print Network [OSTI]

Santa Fe, NM 87505, USA 2 Department of Fire Protection Engineering University of Maryland, College Park Protection Engineering University of Maryland, College Park, MD 20742-3031, USA Abstract Fire detectionFinal Manuscript submitted to the Fire Safety Journal Chen et. al., Fire detection using smoke

370

Trace gas measurements in the Kuwait oil fire smoke plume  

SciTech Connect (OSTI)

The authors report trace gas measurements made both inside and outside the Kuwait oil-fire smoke plume during a flight of an instrumented research aircraft on May 30, 1991. Concentrations of SO{sub 2}, CO, and NO{sub x} averaged vertically and horizontally throughout the plume 80 km downwind of Kuwait City were 106, 127, and 9.1 parts per billion by volume (ppbv), respectively, above background concentrations. With the exception of SO{sub 2}, trace gas concentrations were far below typical US urban levels and primary national ambient air quality standards. Ambient ozone was titrated by NO in the dark, dense core of the smoke plume close to the fires, and photochemical ozone production was limited to the diffuse edge of the plume. Photochemical O{sub 3} production was noted throughout the plume at a distance of 160 km downwind of Kuwait City, and averaged 2.3 ppbv per hour during the first 3 hours of transport. Little additional photochemical production was noted at a downwind range of 340 km. The fluxes of sulfur dioxide, carbon monoxide, and reactive nitrogen from the roughly 520 fires still burning on May 30, 1991 are estimated at 1.4 x 10{sup 7} kg SO{sub 2}/d, 6.9 x 10{sup 6} kg CO/d, and 2.7 x 10{sup 5} kg N/d, respectively. Generally low concentrations of CO and NO{sub x} indicate that the combustion was efficient and occurred at low temperatures. Low total nonmethane hydrocarbon concentrations suggest that the volatile components of the petroleum were burned efficiently. 37 refs., 4 figs., 4 tabs.

Luke, W.T.; Kok, G.L.; Schillawski, R.D.; Zimmerman, P.R.; Greenberg, J.P.; Kadavanich, M. [National Center for Atmospheric Research, Boulder, CO (United States)

1992-09-20T23:59:59.000Z

371

Georgia Institute of Technology Fire Watch Procedures  

E-Print Network [OSTI]

-385-1000) Area II (404-385-2000) Area III (404-385-3000) Area IV (404-385-4000) Area V (404-385-5000) II. Fire Marshal 404-894-2990 2. Georgia Tech Police Department 404-894-2500 3. Facilities-Area 1 (404 the fire watch is in effect. 2. Patrol the entire area affected by the service outage every 30 minutes

372

Estimating Fire Risks at Industrial Nuclear Facilities  

SciTech Connect (OSTI)

The Savannah River Site (SRS) has a wide variety of nuclear production facilities that include chemical processing facilities, machine shops, production reactors, and laboratories. Current safety documentation must be maintained for the nuclear facilities at SRS. Fire Risk Analyses (FRAs) are used to support the safety documentation basis. These FRAs present the frequency that specified radiological and chemical consequences will be exceeded. The consequence values are based on mechanistic models assuming specific fire protection features fail to function as designed.

Coutts, D.A.

1999-07-12T23:59:59.000Z

373

Reducing NOx in Fired Heaters and Boilers  

E-Print Network [OSTI]

-6, 2000 Reducing NOx in Fired Heaters Air Pollution Control and Boilers Keeping the environment clean Presented by Ashutosh Garg Furnace Improvements Low cost solutions for fired heaters Trace compounds ? Nitric oxides ? Carbon monoxide ? Sulfur... it is essential to estimate accurately baseline NOx emissions. ? This will establish each units current compliance status. ? Emissions ? Current excess air level ? Carbon monoxide ? Combustibles ? NOx corrected to 3% 02 314 ESL-IE-00-04-46 Proceedings...

Garg, A.

374

if it is a gas leak, do not activate building alarms, use mobile phones, hand held radios, electronic equipment or light flammable material!  

E-Print Network [OSTI]

gas leak gas leak if it is a gas leak, do not activate building alarms, use mobile phones, hand held radios, electronic equipment or light flammable material! 1. If you discover a Gas Leak, shout and check that the nearest gas isolator switch is off. 4. Evacuate the building immediately, avoiding

Hickman, Mark

375

Mercury Reduction in Coal-Fired Power Plants: DOE's R&D Program  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Reduction in Coal-Fired Power Reduction in Coal-Fired Power Plants: DOE's R&D Program ARIPPA Technical Symposium August 21, 2002 State College, PA Thomas J. Feeley, III, Product Manager Innovations for Existing Plants ARIPPA_TJF082102 Presentation Outline * About NETL * IEP Program * Hg Background * Hg Control R&D * Q&As ARIPPA_TJF082102 About NETL ARIPPA_TJF082102 * One of DOE's 17 national labs * Government owned / operated * Sites in: - Pennsylvania - West Virginia - Oklahoma - Alaska * More than 1,100 federal and support contractor employees National Energy Technology Laboratory ARIPPA_TJF082102 Electric Power Using Coal Clean Liquid Fuels Natural Gas Coal Production Environmental Control V21 Next Generation Carbon Sequestration Exploration & Production Refining & Delivery Alternative Fuels Exploration &

376

FY 2013 EL Program Description EL Program: Fire Risk Reduction in Buildings  

E-Print Network [OSTI]

product. Structure fires and fire protection account for $170 B. To reduce the U.S. fire burden, the Fire of installed fire protection through performance-based design ($63 B) and a reduction in residential fire of structures and their contents by enabling innovative, cost-effective fire protection technologies by 2016

Bentz, Dale P.

377

Eos,Vol. 85, No. 31, 3 August 2004 attack tactics were ineffective.Fire whirls were  

E-Print Network [OSTI]

the U.S. National Oceanographic and Atmospheric Administration's Office of Global Programs. We thank E.Bainto for assistance with the graphics and C.Allen and M.Moritz for their comments. References Mensing.,Mission-Centered Solutions,Inc.,Parker,Colo.; http://wildfirelessons. net/. Predictive Services (2003),Monthly Fire Weather

Eustice, Ryan

378

Ambient air monitoring during the 2011 Las Conchas wildland fire near Los Alamos, U.S.A.  

SciTech Connect (OSTI)

Air monitoring data collected during the Las Conchas fire near the Los Alamos National Laboratory during 2011 are presented. Data included are for selected radionuclides and selected metals found in particulate matter. None of these analytes were seen at levels which exceeded any state or federal standards.

Green, Andrew A. [Los Alamos National Laboratory; Schlemann, Shea A. [Los Alamos Technical Associates; Young, Daniel L. [Los Alamos National Laboratory

2012-08-31T23:59:59.000Z

379

NETL F 451.1/1-1, Categorical Exclusion Designation Form  

Broader source: Energy.gov (indexed) [DOE]

NA Facility Support Services, Inc. FE SOD 2012 102012 - 092013 Ben Smith Morgantown, WV Morgantown Parking Garage Fire Alarm System Install and tie in Siemens fire alarm system...

380

NETL F 451.1/1-1, Categorical Exclusion Designation Form  

Broader source: Energy.gov (indexed) [DOE]

NA Eagle Design, Inc. FE SOD 2012 102012 - 092013 Ben Smith Morgantown, WV Morgantown Parking Garage Fire Alarm System Install and tie in Siemens fire alarm system components...

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


381

Spent Fuel Transportation Cask Response to the Caldecott Tunnel Fire Scenario  

SciTech Connect (OSTI)

On April 7, 1982, a tank truck and trailer carrying 8,800 gallons of gasoline was involved in an accident in the Caldecott tunnel on State Route 24 near Oakland, California. The tank trailer overturned and subsequently caught fire. The United States Nuclear Regulatory Commission (USNRC), one of the agencies responsible for ensuring the safe transportation of radioactive materials in the United States, undertook analyses to determine the possible regulatory implications of this particular event for the transportation of spent nuclear fuel by truck. The Fire Dynamics Simulator (FDS) code developed by National Institute of Standards and Technology (NIST) was used to determine the thermal environment in the Caldecott tunnel during the fire. The FDS results were used to define boundary conditions for a thermal transient model of a truck transport cask containing spent nuclear fuel. The Nuclear Assurance Corporation (NAC) Legal Weight Truck (LWT) transportation cask was selected for this evaluation, as it represents a typical truck (over-the-road) cask, and can be used to transport a wide variety of spent nuclear fuels. Detailed analysis of the cask response to the fire was performed using the ANSYS computer code to evaluate the thermal performance of the cask design in this fire scenario. This report describes the methods and approach used to assess the thermal response of the selected cask design to the conditions predicted in the Caldecott tunnel fire. The results of the analysis are presented in detail, with an evaluation of the cask response to the fire. The staff concluded that some components of smaller transportation casks resembling the NAC LWT, despite placement within an ISO container, could degrade significantly. Small transportation casks similar to the NAC LWT would probably experience failure of seals in this severe accident scenario. USNRC staff evaluated the radiological consequences of the cask response to the Caldecott tunnel fire. Although some components heated up beyond their service temperatures, the staff determined that there would be no significant release as a result of the fire for the NAC LWT and similar casks.

Adkins, Harold E.; Koeppel, Brian J.; Cuta, Judith M.

2007-01-01T23:59:59.000Z

382

Site Visit Report, Lawrence Livermore National Laboratory - May 2010 |  

Broader source: Energy.gov (indexed) [DOE]

Site Visit Report, Lawrence Livermore National Laboratory - May Site Visit Report, Lawrence Livermore National Laboratory - May 2010 Site Visit Report, Lawrence Livermore National Laboratory - May 2010 May 2010 Review of Lawrence Livermore National Laboratory Fire Protection Design Review Process This review of the Lawrence Livermore National Laboratory (LLNL) Fire Protection Design Review Process, conducted on March 24 through April 2, 2010, was sponsored by the U.S. Department of Energy (DOE) Livermore Site Office (LSO) and conducted jointly with LSO staff. Overall, the design review process was observed to be effective and the LLNL programs for performing these reviews were being implemented. Many aspects of the process are effective, and the personnel who implement it are knowledgeable and experienced. This review identified only one

383

Independent Oversight Review, Los Alamos National Laboratory - December  

Broader source: Energy.gov (indexed) [DOE]

Independent Oversight Review, Los Alamos National Laboratory - Independent Oversight Review, Los Alamos National Laboratory - December 2013 Independent Oversight Review, Los Alamos National Laboratory - December 2013 December 2013 Review of the Technical Area 55 Safety Class Fire Suppression System at Los Alamos National Laboratory This report documents the results of an independent oversight review of the Los Alamos National Laboratory (LANL) Technical Area 55 Plutonium Facility safety class fire suppression system (FSS), concurrent with a scheduled Los Alamos Field Office vital safety system assessment. The review was performed April 29 through May 20, 2013, by the U.S. Department of Energy's (DOE) Office of Safety and Emergency Management Evaluations, which is within the DOE Office of Health, Safety and Security. The

384

NIST Technical Note 1629 Fire Fighting Tactics Under Wind Driven Fire Conditions  

E-Print Network [OSTI]

(FEMA) Assistance to Firefighters Research and Development Grant Program and the United States Fire Administrator United States Fire Administration Glenn A. Gaines, Acting Assistant Administrator U.S. Department to differences in staffing, equipment, building stock, typical weather conditions, etc. There is uniformity

Bentz, Dale P.

385

Fuel Treatment, Prescribed Fire, and Fire Restoration: Are the Benefits Worth It?  

E-Print Network [OSTI]

Fuel Treatment, Prescribed Fire, and Fire Restoration: Are the Benefits Worth It? Chairs: Susan Husari and Melanie Miller #12;Applying Simulation and Optimization to Plan Fuel Treatments at Landscape Scales1 J. Greg Jones,2 Jimmie D. Chew,2 Hans R. Zuuring3 Abstract Fuel treatment activities are analyzed

Standiford, Richard B.

386

FIRE ECOLOGY Perhaps the image most often associated with wildland fire is  

E-Print Network [OSTI]

. While it is true that fire has a great potential for the destruction of homes, wildlife, and even human that influence intensity are available fuel, moisture and temperature, fuel composition, wind, and topography. Wind increases oxygen supply, convects heat and can produce "spot fires" from fragments that blow down-wind

Johnson, Matthew

387

Fire Protection Engineering Functional Area Qualification Standard, 2000  

Broader source: Energy.gov (indexed) [DOE]

NOT MEASUREMENT SENSITIVE DOE-STD-1137-2000 July 2000 DOE STANDARD FIRE PROTECTION ENGINEERING FUNCTIONAL AREA QUALIFICATION STANDARD DOE Defense Nuclear Facilities Technical Personnel U.S. Department of Energy AREA TRNG Washington, D.C. 20585 DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited. This document has been reproduced directly from the best available copy. Available to DOE and DOE contractors from ES&H Technical Information Services, U.S. Department of Energy, (800) 473-4375, fax: (301) 903-9823. Available to the public from the U.S. Department of Commerce, Technology Administration, National Technical Information Service, Springfield, VA 22161; (703) 605-6000. DOE-STD-1137-2000 iii APPROVAL DOE-STD-1137-2000 iv INTENTIONALLY BLANK

388

Gas-Fired Distributed Energy Resource Technology Characterizations  

SciTech Connect (OSTI)

The U. S. Department of Energy (DOE) Office of Energy Efficiency and Renewable Energy (EERE) is directing substantial programs in the development and encouragement of new energy technologies. Among them are renewable energy and distributed energy resource technologies. As part of its ongoing effort to document the status and potential of these technologies, DOE EERE directed the National Renewable Energy Laboratory to lead an effort to develop and publish Distributed Energy Technology Characterizations (TCs) that would provide both the department and energy community with a consistent and objective set of cost and performance data in prospective electric-power generation applications in the United States. Toward that goal, DOE/EERE - joined by the Electric Power Research Institute (EPRI) - published the Renewable Energy Technology Characterizations in December 1997.As a follow-up, DOE EERE - joined by the Gas Research Institute - is now publishing this document, Gas-Fired Distributed Energy Resource Technology Characterizations.

Goldstein, L.; Hedman, B.; Knowles, D.; Freedman, S. I.; Woods, R.; Schweizer, T.

2003-11-01T23:59:59.000Z

389

DOE-STD-1066-99; Fire Protection Design Criteria  

Broader source: Energy.gov (indexed) [DOE]

6-99 6-99 July 1999 Superseding DOE-STD-1066-97 DOE STANDARD FIRE PROTECTION DESIGN CRITERIA U.S. Department of Energy AREA FIRP Washington, D.C. 20585 DISTRIBUTION STATEMENT. Approved for public release; distribution is unlimited. This document has been reproduced from the best available copy. Available to DOE and DOE contractors from ES&H Technical Information Services, U.S. Department of Energy, (800) 473-4375, fax: (301) 903-9823. Available to the public from the U.S. Department of Commerce, Technology Administration, National Technical Information Service, Springfield, VA 22161; (703) 605-6000. DOE-STD-1066-99 iii FOREWORD This Department of Energy (DOE) Standard is approved for use by all DOE elements and their contractors. DOE Standards are part of the DOE Directives System and are issued to provide supplemental

390

Surveillance Guide - FPS 12.2 Fire Protection and Prevention  

Broader source: Energy.gov (indexed) [DOE]

FIRE PROTECTION AND PREVENTION FIRE PROTECTION AND PREVENTION 1.0 Objective The objective of this surveillance is to ensure that the contractor is implementing an effective program to minimize the potential for fires that could threaten the health and safety of the public or DOE's workers, or produce significant losses. In addition, the surveillance examines the effectiveness of steps taken to mitigate any fires that might occur. Finally, the surveillance provides an opportunity to evaluate compliance with requirements and standards for fire prevention and mitigation established by DOE. 2.0 References DOE 5480.7A, Fire Protection (or DOE O 420.1, Facility Safety) RLID 5480.7, Fire Protection (or RLID 420.1, Fire Protection) 29 CFR 1910 29 CFR 1926 DOE-HDBK-1062-96, "DOE Fire Protection Handbook (See this as well as other

391

Fire hazard analysis of the radioactive mixed waste trenchs  

SciTech Connect (OSTI)

This Fire Hazards Analysis (FHA) is intended to assess comprehensively the risk from fire associated with the disposal of low level radioactive mixed waste in trenches within the lined landfills, provided by Project W-025, designated Trench 31 and 34 of the Burial Ground 218-W-5. Elements within the FHA make recommendations for minimizing risk to workers, the public, and the environment from fire during the course of the operation`s activity. Transient flammables and combustibles present that support the operation`s activity are considered and included in the analysis. The graded FHA contains the following elements: description of construction, protection of essential safety class equipment, fire protection features, description of fire hazards, life safety considerations, critical process equipment, high value property, damage potential--maximum credible fire loss (MCFL) and maximum possible fire loss (MPFL), fire department/brigade response, recovery potential, potential for a toxic, biological and/or radiation incident due to a fire, emergency planning, security considerations related to fire protection, natural hazards (earthquake, flood, wind) impact on fire safety, and exposure fire potential, including the potential for fire spread between fire areas. Recommendations for limiting risk are made in the text of this report and printed in bold type. All recommendations are repeated in a list in Section 18.0.

McDonald, K.M. [Westinghouse Hanford Co., Richland, WA (United States)

1995-04-27T23:59:59.000Z

392

Interest of the Theory of Uncertain in the Dynamic LCA- Fire Methodology to Assess Fire Effects  

Science Journals Connector (OSTI)

Abstract Life Cycle Impact Assessment (LCIA) is the third phase of Life Cycle Assessment (LCA) described in ISO 14042. The purpose of LCIA is to assess a product system's life cycle inventory analysis (LCI) in order to better understand its environmental significance. However, LCIA typically excludes spatial, temporal, threshold and dose-response information, and combines emissions or activities over space and/or time. This may diminish the environmental relevance of the indicator result. The methodology, Dynamic LCA -Fire proposed in this paper to complete the International Standard ISO 14042 in the fire field, combines the LCA - Fire method with the Dispersion Numerical Model. It is based on the use of the plume model used to assess pollutant concentrations and thermal effects from fire accident scenarios. In this study, The Dynamic LCA - Fire methodology is applied to a case study for petroleum production process management.

Samia Chettouh; Rachida Hamzi; Fares Innal; Djamel Haddad

2014-01-01T23:59:59.000Z

393

Sandia National Laboratories: Sandia National Laboratories: Locations...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Regional Park District Joshua Tree National Park Lassen Volcanic National Park Sequoia & Kings Canyon National Parks Yosemite National Park Cave exploring Diablo Grotto Moaning...

394

The Advanced Tangentially Fired Combustion Techniques for the Reduction of Nitrogen Oxides (NOx) Emissions From Coal-Fired Boilers Demonstration Project: A DOE Assessment  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

2 2 The Advanced Tangentially Fired Combustion Techniques for the Reduction of Nitrogen Oxides (NO ) Emissions From Coal-Fired Boilers X Demonstration Project: A DOE Assessment March 2000 U.S. Department of Energy National Energy Technology Laboratory P.O. Box 880, 3610 Collins Ferry Road Morgantown, WV 26507-0880 and P.O. Box 10940, 626 Cochrans Mill Road Pittsburgh, PA 15236-0940 2 Disclaimer This report was prepared as an account of work sponsored by an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or

395

GREENHOUSE GAS EMISSIONS CONTROL BY OXYGEN FIRING IN CIRCULATING FLUIDIZED BED BOILERS  

SciTech Connect (OSTI)

Given that fossil fuel fired power plants are among the largest and most concentrated producers of CO{sub 2} emissions, recovery and sequestration of CO{sub 2} from the flue gas of such plants has been identified as one of the primary means for reducing anthropogenic CO{sub 2} emissions. In this study, ALSTOM Power Inc. (ALSTOM) has investigated several coal fired power plant configurations designed to capture CO{sub 2} from effluent gas streams for use or sequestration. Burning fossil fuels in mixtures of oxygen and recirculated flue gas (made principally of CO{sub 2}) essentially eliminates the presence of atmospheric nitrogen in the flue gas. The resulting flue gas is comprised primarily of CO{sub 2}. Oxygen firing in utility scale Pulverized Coal (PC) fired boilers has been shown to be a more economical method for CO{sub 2} capture than amine scrubbing (Bozzuto, et al., 2001). Additionally, oxygen firing in Circulating Fluid Bed Boilers (CFB's) can be more economical than in PC or Stoker firing, because recirculated gas flow can be reduced significantly. Oxygen-fired PC and Stoker units require large quantities of recirculated flue gas to maintain acceptable furnace temperatures. Oxygen-fired CFB units, on the other hand, can accomplish this by additional cooling of recirculated solids. The reduced recirculated gas flow with CFB units results in significant Boiler Island cost savings. Additionally, ALSTOM has identified several advanced/novel plant configurations, which improve the efficiency and cost of the CO{sub 2} product cleanup and compression process. These advanced/novel concepts require long development efforts. An economic analysis indicates that the proposed oxygen-firing technology in circulating fluidized boilers could be developed and deployed economically in the near future in enhanced oil recovery (EOR) applications or enhanced gas recovery (EGR), such as coal bed methane recovery. ALSTOM received a Cooperative Agreement from the US Department of Energy National Energy Technology Laboratory (DOE) in 2001 to carry out a project entitled ''Greenhouse Gas Emissions Control by Oxygen Firing in Circulating Fluidized Bed Boilers.'' This two-phased project is in effect from September 28, 2001, to October 27, 2004. (U.S. DOE NETL Cooperative Agreement No. DE-FC26-01NT41146). Phase I consisted of an evaluation of the technical feasibility and economics of alternate CO{sub 2} capture technologies applied to Greenfield US coal-fired electric generation power plants, and supporting bench-scale testing. And Phase II consists of pilot-scale testing, supporting a refined performance and economic evaluation of the oxygen-fired AFC concept. Phase I, detailed in this report, entails a comprehensive study evaluating the technical feasibility and economics of alternate CO{sub 2} capture technologies applied to Greenfield US coal-fired electric generation power plants. Thirteen separate but related cases (listed below), representing various levels of technology development, were evaluated as described herein. The first seven cases represent coal combustion cases in CFB type equipment. The next four cases represent Integrated Gasification Combined Cycle (IGCC) systems. The last two cases represent advanced Chemical Looping systems, which were completely paid for by ALSTOM and included herein for completeness.

Nsakala ya Nsakala; Gregory N. Liljedahl

2003-05-15T23:59:59.000Z

396

Sandia National Laboratories: Sandia National Laboratories: Tonopah Test  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Tonopah Test Range Tonopah Test Range Tonopah Tonopah Test Range (TTR) is the testing range of choice for all national security missions. Sandia conducts operations at TTR in support of the Department of Energy/National Nuclear Security Administration's weapons programs. Principal DOE activities at TTR include stockpile reliability testing; arming, fusing, and firing systems testing; and the testing of nuclear weapon delivery systems. The range also offers a unique test environment for use by other U.S. government agencies and their contractors. Located about 160 miles northwest of Las Vegas, TTR is an immense area of flat terrain ideal for rockets and low-altitude, high-speed aircraft operations. Situated between two mountain ranges, TTR's remote location and restricted airspace ensure that tests can be conducted with a high degree

397

Mitsubishi FGD plants for lignite fired boilers  

SciTech Connect (OSTI)

In order to respond to the increasing electric energy demand for sustaining economic growth, construction of coal-fired thermal power plants worldwide is indispensable. As a countermeasure for environmental pollution which otherwise may reach a serious proportion from the operation of these plants, construction of flue gas desulfurization (FGD) plants is being promoted. Among these power stations where lignite fuel is burnt, the FGD plants concerned have to be designed to cope with high gas volume and SO{sub x} concentration as well as violent fluctuations in their values caused by such features of lignite as high sulfur content, low calorific volume, and unstable properties. Mitsubishi Heavy Industries (MHI) has received construction awards for a total of seven (7) FGD plants for lignite-fired boilers in succession starting from that for CEZ as, Czech Republic followed by those for EGAT, Thailand in 1993. All these plants are presently operating satisfactorily since successful completion of their performance tests in 1996. Further, a construction award of three (3) more FGD plants for lignite-fired boilers was received from ENDESA (Spain) in 1995 which are now being outfitted and scheduled to start commercial operation in 1998. In this paper, the authors discuss the outline design of FGD plants for lignite-fired boilers based on experience of FGD plants constructed since 1970 for heavy oil--as well as black coal-fired boilers, together with items confirmed from the operation and design guideline hereafter.

Kotake, Shinichiro; Okazoe, Kiyoshi; Iwashita, Koichiro; Yajima, Satoru

1998-07-01T23:59:59.000Z

398

Externally fired gas turbine technology: A review  

Science Journals Connector (OSTI)

Abstract Externally fired heat engines were used widely since helium the industrial revolution using dirty solid fuels for example coal, due to the lack of refined fuels. However, with the availability of clean fuels, external firing mode was abandoned, except for steam power plants. Lately, with the global trend moving towards green power production, the idea of the external fired system has captured the attention again especially externally fired gas turbine (EFGT) due to its wider range of power generation and the potential of using environment friendly renewable energy sources like biomass. In this paper, a wide range of thermal power sources utilizing EFGT such as concentrated solar power (CSP), fossil, nuclear and biomass fuels are reviewed. Gas turbine as the main component of EFGT is investigated from micro scale below 1MWe to the large scale central power generation. Moreover, the different high temperature heat exchanger (HTHE) materials and designs are reviewed. Finally, the methods of improving cycle efficiency such as the externally fired combined cycle (EFCC), humidified air turbine (HAT), EFGT with fuel cells and other cycles are reviewed thoroughly.

K.A. Al-attab; Z.A. Zainal

2015-01-01T23:59:59.000Z

399

National Security  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

because NIF provides the only process for scientists to gain access to and examine thermonuclear burn. These experiments will also help the nation maintain the skills of nuclear...

400

Fire Energy S L | Open Energy Information  

Open Energy Info (EERE)

Fire Energy S L Fire Energy S L Jump to: navigation, search Name Fire Energy, S.L. Place Madrid, Spain Zip 28806 Sector Solar Product Solar power developer and distributor based in Spain. Coordinates 40.4203°, -3.705774° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":40.4203,"lon":-3.705774,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


401

BlueFire Ethanol | Open Energy Information  

Open Energy Info (EERE)

BlueFire Ethanol BlueFire Ethanol Jump to: navigation, search Name BlueFire Ethanol Place Irvine, California Zip 92618 Sector Hydro Product US biofuel producer that utilises a patented concentrated acid hydrolysis technology to process various cellulosic waste materials into ethanol. Coordinates 41.837752°, -79.268594° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":41.837752,"lon":-79.268594,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

402

co-firing | OpenEI  

Open Energy Info (EERE)

co-firing co-firing Dataset Summary Description The Planning Database Project provides the UK Department of Energy and Climate Change (DECC) with regular data to track progress towards achieving EU targets for electricity generation from renewable energy (RE) sources. Extracts from the database are available each month. Information collected in the database includes: name, location and installed capacity of RE projects over 0.1MW; environmental designations; planning status; and construction status. Included here is the October 2010 Progress Datasheet, and an extract from December, 15, 2010 (i.e. Source UK Department of Energy and Climate Change (DECC) Date Released December 15th, 2010 (4 years ago) Date Updated Unknown Keywords biomass co-firing installed capacity

403

Ready. Aim. Fire. | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Ready. Aim. Fire. Ready. Aim. Fire. Ready. Aim. Fire. March 28, 2011 - 4:27pm Addthis John Lippert I wrote in a previous blog posting about using digital electric meters to locate "leaking" electricity-often referred to as phantom loads and vampire loads-and high electrical power consumption. In another posting I described what I'm doing to reach out in my community to get my neighbors to use these meters to locate wasteful electricity usage in their homes. Now my community will have another tool in its arsenal to combat energy waste: a thermal leak detector. Whereas the digital electric meter helps locate electricity leaks, the thermal leak detector helps locate-well, you guessed it-thermal (heat) leaks. Heating and cooling your home account for close to half of the energy use

404

NETL: Coal-Fired Power Plants (CFPPs)  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

NOx Sources NOx Sources Coal-Fired Power Plants (CFPPs) Causes of greenhouse gases, Including NOx What is NOx? Environmental Impacts NOx Sources Reduction Efforts Several greenhouse gases, including NOx, are increasing due to human activities in the following areas: Burning of fossil fuel (for example, coal-fired power plants), Logging (mainly contributes to carbon monoxide), Agriculture processes, Use of chlorofluorocarbons (CFC) in holon fire suppression and refrigeration The chart below shows the three major gases contributing to greenhouse gas emissions along with their source by sector. Annual Greenhouse Gas Emissions by Sector Note: This figure was created and copyrighted by Robert A. Rohde from published data and is part of the Global Warming Art project. This image is an original work created for Global Warming Art Permission is granted to copy, distribute and/or modify this image under either:

405

Fire-resistant pits: Reducing the probability of accidental plutonium dispersal from fuel fires  

SciTech Connect (OSTI)

Reductions in risk of Pu dispersal from hydrocarbon fuel fires were estimated using pool and spill fire data. Improvements in FRP temperature capabilities, on a system-independent basis, lead to the following estimated reductions in risk, using three probabilistic temperature distributions normalized to a temperature capability of 640[degree]C (the melting point of plutonium): 1OOO[degree]C - factor of 3 to 5; 11OO[degree]C - factor of 10 to 13; and 1200[degree]C - factor of 120 to 300. The above values would, of course, vary for a different normalization temperature. These values were derived to be as system-independent as possible. Incorporation of fuel fire durations or of longer time-averaging (than the two minutes employed in this study) would tend to increase these FRP improvement factors. Incorporation of propellant fires, burning metal or of combined impact/fire accidents would tend to decrease them. Further studies of fuel fire durations, particularly of a fuel fire duration model, is recommended, as is an uncertainty analysis of the temperature distributions.

Stephens, D.R.

1992-03-01T23:59:59.000Z

406

Empirical validation of the conceptual design of the LLNL 60-kg contained-firing facility  

SciTech Connect (OSTI)

In anticipation of increasingly stringent environmental regulations, Lawrence Livermore National Laboratory (LLNL) is proposing to modify an existing facility to add a 60-kg firing chamber and related support areas. This modification will provide blast-effects containment for most of its open-air, high-explosive, firing operations. Even though these operations are within current environmental limits, containment of the blast effects and hazardous debris will further drastically reduce emissions to the environment and minimize the hazardous waste generated. The major design consideration of such a chamber is its overall structural dynamic response in terms of its long-term ability to contain all blast effects from repeated internal detonations of high explosives. Another concern is how much other portions of the facility outside the firing chamber must be hardened to ensure personnel protection in the event of an accidental detonation while the chamber door is open. To assess these concerns, a 1/4-scale replica model of the planned contained firing chamber was engineered, constructed, and tested with scaled explosive charges ranging from 25 to 125% of the operational explosives limit of 60 kg. From 16 detonations of high explosives, 880 resulting strains, blast pressures, and temperatures within the model were measured to provide information for the final design.

Pastrnak, J.W.; Baker, C.F.; Simmons, L.F.

1995-02-24T23:59:59.000Z

407

The Influence of Canadian Forest Fires on Pollutant Concentrations in the United States  

Science Journals Connector (OSTI)

...forest fires (6), that fires, together with stratospheric...intrusions, contribute a major fraction of total oxidized nitrogen...1995, 18 UTC. Forest fire release locations are marked with...18-UTC. Forest fire release locations are marked with...

Gerhard Wotawa; Michael Trainer

2000-04-14T23:59:59.000Z

408

24 Command Fire Improvement Action Program Plan  

SciTech Connect (OSTI)

Fluor Hanford (FH) is responsible for providing support to the Department of Energy Richland Operations Office (RL) in the implementation of the Hanford Emergency Preparedness (EP) program. During fiscal year 2000, a number of program improvements were identified from various sources including a major range fire (24 Command Fire). Evaluations of the emergency preparedness program have confirmed that it currently meets all requirements and that performance of personnel involved is good, however the desire to effect continuous improvement resulted in the development of this improvement program plan. This program plan defines the activities that will be performed in order to achieve the desired performance improvements.

GRIFFIN, G.B.

2000-12-01T23:59:59.000Z

409

Inflatable partition for fighting mine fires  

DOE Patents [OSTI]

The seal is a lightweight, inflatable, bag which may be inflated by a portable air generator and is used to seal a burning mine passage. A collapsible tube-like aperture extends through the seal and allows passage of high expansion foam through the seal in a feed tube. The foam fills the passageway and extinguishes the fire. In other embodiments, the feed tubes incorporate means to prevent collapse of the aperture. In these embodiments a shroud connects the feed tube to a foam generator. This seal allows creation of a high expansion foam fire fighting barrier even in upward sloping passages.

Conti, Ronald S. (Pittsburgh, PA); Lazzara, Charles P. (Pittsburgh, PA)

1995-01-01T23:59:59.000Z

410

Firing of pulverized solvent refined coal  

DOE Patents [OSTI]

A burner for the firing of pulverized solvent refined coal is constructed and operated such that the solvent refined coal can be fired successfully without any performance limitations and without the coking of the solvent refined coal on the burner components. The burner is provided with a tangential inlet of primary air and pulverized fuel, a vaned diffusion swirler for the mixture of primary air and fuel, a center water-cooled conical diffuser shielding the incoming fuel from the heat radiation from the flame and deflecting the primary air and fuel steam into the secondary air, and a watercooled annulus located between the primary air and secondary air flows.

Lennon, Dennis R. (Allentown, PA); Snedden, Richard B. (McKeesport, PA); Foster, Edward P. (Macungie, PA); Bellas, George T. (Library, PA)

1990-05-15T23:59:59.000Z

411

Fire Department Gets New Trucks, Saves Money | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Fire Department Gets New Trucks, Saves Money Fire Department Gets New Trucks, Saves Money Fire Department Gets New Trucks, Saves Money August 27, 2013 - 12:00pm Addthis Hanford firefighters stand next to the 31-year-old chemical truck. Pictured, left to right, are Hanford Fire Lt. Robert Smith, Firefighter/Paramedic Kyle Harbert, Firefighter Don Blackburn and Capt. Sean Barajas. Hanford firefighters stand next to the 31-year-old chemical truck. Pictured, left to right, are Hanford Fire Lt. Robert Smith, Firefighter/Paramedic Kyle Harbert, Firefighter Don Blackburn and Capt. Sean Barajas. One of two of the Hanford Fire Department’s new chemical trucks. One of two of the Hanford Fire Department's new chemical trucks. Hanford firefighters stand next to the 31-year-old chemical truck. Pictured, left to right, are Hanford Fire Lt. Robert Smith, Firefighter/Paramedic Kyle Harbert, Firefighter Don Blackburn and Capt. Sean Barajas.

412

Fire is the Enemy of Field and Forest  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Fire is the Enemy of Field and Forest Fire is the Enemy of Field and Forest Nature Bulletin No. 10 April 14, 1945 Forest Preserve District of Cook County Clayton F. Smith, President Roberts Mann, Superintendent of Conservation FIRE IS THE ENEMY OF FIELD AND FOREST There have been 112 fires in the forest preserves since January 1, burning over 612 acres, including 150 acres of fine woodland and young forest plantings. There need not have been ONE if people only understood the damage done by forest and grass fires. Every spring and every fall, thousands of acres of prairie and vacant subdivisions are burnt off. Some of these fires jump over into forest preserves. Many fires start inside the preserves, or along their highway borders, from matches, cigarettes or pipe bottle thrown aside by careless people. Some start from picnic fires. A few are kindled by boys who have seen their parents or neighbors do the same thing at home.

413

The Role of Convective Outflow in the Waldo Canyon Fire  

Science Journals Connector (OSTI)

The meteorological conditions associated with the rapid intensification and spread of the catastrophic Waldo Canyon fire on 26 June 2012 are studied. The fire caused two fatalities, destroyed 347 homes in Colorado Springs, and resulted in ...

Richard H. Johnson; Russ S. Schumacher; James H. Ruppert Jr.; Daniel T. Lindsey; Julia E. Ruthford; Lisa Kriederman

2014-09-01T23:59:59.000Z

414

Multi-Function Fuel-Fired Heat Pump Research Project  

Broader source: Energy.gov [DOE]

The U.S. Department of Energy is currently conducting research into multi-function fuel-fired heat pumps. Multi-function fuel-fired heat pump technology has the potential for a significant impact...

415

Savanna and shrubland fire behavior modeling in South Texas  

E-Print Network [OSTI]

The vegetation of South Texas has changed from mesquite savanna to mixed mesquite/acacia (Prosopis/Acacia) shrubland over the last hundred years. Fire reduction due to lack of fine fuel and suppression of fires is cited as reasons...

Streeks, Tamara Jean

2012-06-07T23:59:59.000Z

416

Management of Imported Fire Ants in Cattle Production Systems  

E-Print Network [OSTI]

This publication can help ranch managers develop integrated pest management plans for managing fire ant problems in cattle operations. It covers the specifics of managing fire ants in hay pastures and rangelands, around farm ponds, and near...

Fuchs, Thomas W.; Drees, Bastiaan M.

2004-03-31T23:59:59.000Z

417

Initial Joint Review, Wildland Fire Safety at DOE Sites - December...  

Broader source: Energy.gov (indexed) [DOE]

Fire Safety Enchancements - Jan 19, 2001 Audit Report: IG-0760 Type B Accident Investigation, Response to the 24 Command Wildland Fire on the Hanford Site, June 27-July 1, 200...

418

Enforcement Letter - Los Alamos National Laboratory  

Broader source: Energy.gov (indexed) [DOE]

7, 1997 7, 1997 Dr. Sigfried S. Hecker [ ] Los Alamos National Laboratory P.O. Box 1663 Los Alamos, NM 87545 Subject: Noncompliance Report NTS-ALO-LA-LANL-LANL-1996-0004 Dear Dr. Hecker: This letter refers to the Department of Energy's (DOE's) evaluation of potential noncompliances with the requirements of 10 CFR 830.120 (Quality Assurance Rule). The noncompliances involved the failure of Los Alamos National Laboratory (LANL) to adequately implement the requirements contained in the governing quality assurance standard for stockpile evaluations in the areas of work controls and procedural compliance. As a result of these failures, an explosion and fire occurred at the [ ] on November 14, 1996.

419

Fire Protection Program Assessment, Building 9116- Y12 Plant, Oak Ridge, Tennessee  

Broader source: Energy.gov [DOE]

This assessment is intended to evaluate the fire hazards, life safety and fire protection features inherent in Building 9116.

420

Initial Joint Review of Wildland Fire Safety at DOE Sites  

Broader source: Energy.gov (indexed) [DOE]

December December 2000 A Report to the Secretary of Energy Initial Joint Review of Wildland Fire Safety at DOE Sites OVERSIGHT Table of Contents Executive Summary................................................................................... 1 1.0 Introduction ......................................................................................... 5 2.0 Summary of Review Results .............................................................. 8 2.1 Wildland Fire Management Policy ............................................. 8 2.2 Fire/Emergency Hazards Assessments ....................................... 9 2.3 Wildland Fire Prevention and Response .................................. 11 2.4 Offsite Interfaces and Agreements ........................................... 13 2.5 Feedback and Continuous Improvement

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


421

Understanding Corrosion Mechanisms in Oxy-Fired Systems  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Understanding Corrosion Mechanisms Understanding Corrosion Mechanisms in Oxy-Fired Systems Background In Oxy-fired Systems, oxygen is used for combustion of coal rather than air. It produces flue (exhaust) gas with concentrated carbon dioxide (CO2), thus facilitating its capture and sequestration. An added benefit of oxy-firing is that it reduces or eliminates nitrogen oxide (NO X ) emissions. Additional energy is required with oxy-firing and subsequent carbon sequestration

422

Colorado State Forest Service SB09-020 --Responsibility for Responding to Wildland Fires  

E-Print Network [OSTI]

SB09-020 clarifies the roles and responsibilities of fire protection districts, county sheriffs and responsibilities progressively from local jurisdiction to fire protection district jurisdiction to county: · The fire chief of the fire protection district is responsible for all fires, including wildland fires

423

Retrofitted coal-fired firetube boiler and method employed therewith  

DOE Patents [OSTI]

A coal-fired firetube boiler and a method for converting a gas-fired firetube boiler to a coal-fired firetube boiler, the converted boiler including a plurality of combustion zones within the firetube and controlled stoichiometry within the combustion zones.

Wagoner, Charles L. (Tullahoma, TN); Foote, John P. (Tullahoma, TN)

1995-01-01T23:59:59.000Z

424

Retrofitted coal-fired firetube boiler and method employed therewith  

DOE Patents [OSTI]

A coal-fired firetube boiler and a method for converting a gas-fired firetube boiler to a coal-fired firetube boiler are disclosed. The converted boiler includes a plurality of combustion zones within the firetube and controlled stoichiometry within the combustion zones. 19 figs.

Wagoner, C.L.; Foote, J.P.

1995-07-04T23:59:59.000Z

425

Synthesis and Summary: Land Use Decisions and Fire Risk1  

E-Print Network [OSTI]

was spent in fire suppres- sion. The bill for all costs and damages amounted to more than $1 billion. Given of fuel management and fire protection. The complexity of watershed manage- ment was defined growth on fuel management and fire protection, concerns stated or implied in all presentations. Jim Davis

Standiford, Richard B.

426

FireViz : a personal firewall visualizing tool  

E-Print Network [OSTI]

In this thesis, I present FireViz, a personal firewall visualizing tool. FireViz visually displays activities of a personal firewall in real time. The primary goal of FireViz is to educate typical computer users of the ...

Sharma, Nidhi

2005-01-01T23:59:59.000Z

427

Airborne Studies of the Smoke from the Kuwait Oil Fires  

Science Journals Connector (OSTI)

...smoke from the Kuwait fires produced a small-scale...Concluding Remarks The airborne studies of the smoke from the Kuwait fires provided a large...1. Uncontrolled releases of oil began in January...and the oil field fires began in late February...Zimmerman). 3. An airborne study of the smoke...

Peter V. Hobbs; Lawrence F. Radke

1992-05-15T23:59:59.000Z

428

A Spatial Planning and Analysis System for Wildland Fire Management  

E-Print Network [OSTI]

STARFIRE 11/29/2011 A Spatial Planning and Analysis System for Wildland Fire Management Welcome is an advanced and powerful spatial fire management planning and analysis system which is designed to provide visual and analytic support for fire management planning, decisions and communication. The system

429

Phase 2 fire hazard analysis for the canister storage building  

SciTech Connect (OSTI)

The fire hazard analysis assesses the risk from fire in a facility to ascertain whether the fire protection policies are met. This document provides a preliminary FHA for the CSB facility. Open items have been noted in the document. A final FHA will be required at the completion of definitive design, prior to operation of the facility.

Sadanaga, C.T., Westinghouse Hanford

1996-07-01T23:59:59.000Z

430

Coal-fired generation staging a comeback. 2nd ed.  

SciTech Connect (OSTI)

The report is an overview of the renewed U.S. market interest in coal-fired power generation. It provides a concise look at what is driving interest in coal-fired generation, the challenges faced in implementing coal-fired generation projects, and the current and future state of coal-fired generation. Topics covered in the report include: An overview of coal-fired generation including its history, the current market environment, and its future prospects; An analysis of the key business factors that are driving renewed interest in coal-fired generation; An analysis of the challenges that are hindering the implementation of coal-fired generation projects; A description of coal-fired generation technologies; A review of the economic drivers of coal-fired generation project success; An evaluation of coal-fired generation versus other generation technologies; A discussion of the key government initiatives supporting new coal-fired generation; and A listing of planned coal-fired generation projects. 13 figs., 12 tabs., 1 app.

NONE

2007-07-01T23:59:59.000Z

431

Procedure No 400.04 Subject: Fire Protection & Life Safety  

E-Print Network [OSTI]

Procedure No 400.04 Subject: Fire Protection & Life Safety Reference: OSHA CFR1910.157, Subpart L egress time and protection from fire exposure. DEFINITIONS Combustibles: A material, such as paper, wood protection to the opening when closed. Fire Watch: A person or persons assigned to an area for the purpose

Karsai, Istvan

432

Estimating Hydrologic Values for Planning Wildland Fire Protection1  

E-Print Network [OSTI]

Estimating Hydrologic Values for Planning Wildland Fire Protection1 Henry W. Anderson and Clinton B- quencies under various levels of protection in the area, and (c) the effects of those fires-26, 1981, San Diego, California. 2 Consulting Hydrologist, Lafayette, California, Assistant Chief of Fire

Standiford, Richard B.

433

Structural stability of polymer matrix composite panels in fire  

E-Print Network [OSTI]

of a quantitative methodology for fire protection design is discussed in the context of the analyses and the experiments. Design diagrams are constructed to design mechanical loads for given fire protection time, and on the opposite, to design fire protection time for given mechanical loads. ? 2009 Elsevier Ltd. All rights

Dao, Ming

434

Rules for fire Protection Ludwig-Maximilians-University  

E-Print Network [OSTI]

Rules for fire Protection of the Ludwig-Maximilians-University (except Gro?hadern and City Center in the university buildings the principles contained in the rules for fire protection must be observed without exception.Violations of these rules for fire protection may have legal consequences and may be prosecuted

Kersting, Roland

435

6 THE SINGAPORE ENGINEER Feb 2009 Fire Protection  

E-Print Network [OSTI]

6 · THE SINGAPORE ENGINEER Feb 2009 Fire Protection Smoke Control by Pressurisation in Stairwells during fires. In this regard, it is the `across door' portion of the stack effect pressure difference that is directly related to smoke migration and control. A fire located on a lower floor can cause substantial

Miller, Richard S.

436

Carbon dioxide emission during forest fires ignited by lightning  

E-Print Network [OSTI]

In this paper we developed the model for the carbon dioxide emission from forest fire. The master equation for the spreading of the carbon dioxide to atmosphere is the hyperbolic diffusion equation. In the paper we study forest fire ignited by lightning. In that case the fores fire has the well defined front which propagates with finite velocity.

Magdalena Pelc; Radoslaw Osuch

2009-03-31T23:59:59.000Z

437

Wildland fire emissions, carbon, and climate: Emission factors Shawn Urbanski  

E-Print Network [OSTI]

Wildland fire emissions, carbon, and climate: Emission factors Shawn Urbanski Missoula Fire burning Greenhouse gases Emission factors a b s t r a c t While the vast majority of carbon emitted wildland fire greenhouse gas and aerosol (organic aerosol (OA) and black carbon (BC)) emission inventories

438

Using Satellite Fire Detection to Calibrate Components of the Fire Weather Index System in Malaysia and Indonesia  

Science Journals Connector (OSTI)

Vegetation fires have become an increasing problem in tropical environments as a consequence of socioeconomic pressures and subsequent land-use change. In response, fire management systems are being developed. Th...

Caren C. Dymond; Robert D. Field; Orbita Roswintiarti; Guswanto

2005-04-01T23:59:59.000Z

439

Simulating Historic Landscape Patterns of Fire in the Southern Appalachian Mountains: Implications for Fire History and Management  

E-Print Network [OSTI]

Fire suppression policies implemented in the early 20th century led to a decrease in fire-associated species and ecosystems in the southern Appalachian Mountains. As managers work towards restoration, a greater understanding of the pre...

Gass, Ellen R

2014-05-21T23:59:59.000Z

440

Carbon Dioxide Capture from Coal-Fired  

E-Print Network [OSTI]

Carbon Dioxide Capture from Coal-Fired Power Plants: A Real Options Analysis May 2005 MIT LFEE 2005 are valued using the "real options" valuation methodology in an uncertain carbon dioxide (CO2) price (baseline IGCC), and IGCC with pre-investments that make future retrofit for CO2 capture less expensive (pre

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


441

Direct fired absorption machine flue gas recuperator  

DOE Patents [OSTI]

A recuperator which recovers heat from a gas, generally the combustion gas of a direct-fired generator of an absorption machine. The recuperator includes a housing with liquid flowing therethrough, the liquid being in direct contact with the combustion gas for increasing the effectiveness of the heat transfer between the gas and the liquid.

Reimann, Robert C. (Lafayette, NY); Root, Richard A. (Spokane, WA)

1985-01-01T23:59:59.000Z

442

UF{sub 6} cylinder fire test  

SciTech Connect (OSTI)

With the increasing number of nuclear reactors for power generation, there is a comparable increase in the amount of UF{sub 6} being transported. Likewise, the probability of having an accident involving UF{sub 6}-filled cylinders also increases. Accident scenarios which have been difficult to assess are those involving a filled UF{sub 6} cylinder subjected to fire. A study is underway at the Oak Ridge K-25 Site, as part of the US DOE Enrichment Program, to provide empirical data and a computer model that can be used to evaluate various cylinder-in-fire scenarios. It is expected that the results will provide information leading to better handling of possible fire accidents as well as show whether changes should be made to provide different physical protection during shipment. The computer model being developed will be capable of predicting the rupture of various cylinder sizes and designs as well as the amount of UF{sub 6}, its distribution in the cylinder, and the conditions of the fire.

Park, S.H. [Oak Ridge K-25 Site, Oak Ridge, TN (United States)

1991-12-31T23:59:59.000Z

443

William Brownrigg's papers on fire-damps  

Science Journals Connector (OSTI)

...they were found was connected to a second pit through which air was circulated to vent...it would be exhausted by the fires that burn everywhere. He suspected that the pabulum...An Account of the damp air in a coal-pit of Sir James Lowther, Bart. Sunk within...

2010-01-01T23:59:59.000Z

444

Blank fire configuration for automatic pistol  

DOE Patents [OSTI]

A pistol configured to fire blank cartridges includes a modified barrel with a breech portion connected to an aligned inner sleeve. Around the inner sleeve, there is disposed an outer sleeve having a vent therein through which the cartridge discharges. The breech portion is connected to a barrel anchor to move backward in a slight arc when the pistol is fired. A spring retention rod projects from the barrel anchor and receives a shortened recoil spring therearound which recoil spring has one end abutting a stop on the barrel anchor and the other end in abutment with the end of a spring retaining cup. The spring retaining cup is engaged by a flange projecting from a slide so that when the pistol is fired, the slide moves rearwardly against the compression of the spring to eject the spent cartridge and then moves forwardly under the urging of the spring to load a fresh cartridge into the breech portion. The spring then returns all of the slidable elements to their initial position so that the pistol may again be fired.

Teague, Tommy L. (Albuquerque, NM)

1990-01-01T23:59:59.000Z

445

Characterization of Oxy-combustion Impacts in Existing Coal-fired Boilers  

SciTech Connect (OSTI)

Reaction Engineering International (REI) managed a team of experts from University of Utah, Siemens Energy, Praxair, Vattenfall AB, Sandia National Laboratories, Brigham Young University (BYU) and Corrosion Management Ltd. to perform multi-scale experiments, coupled with mechanism development, process modeling and CFD modeling, for both applied and fundamental investigations. The primary objective of this program was to acquire data and develop tools to characterize and predict impacts of CO{sub 2} flue gas recycle and burner feed design on flame characteristics (burnout, NO{sub x}, SO{sub x}, mercury and fine particle emissions, heat transfer) and operational concerns (fouling, slagging and corrosion) inherent in the retrofit of existing coal-fired boilers for oxy-coal combustion. Experimental work was conducted at Sandia National Laboratories Entrained Flow Reactor, the University of Utah Industrial Combustion Research Facility, and Brigham Young University. Process modeling and computational fluid dynamics (CFD) modeling was performed at REI. Successful completion of the project objectives resulted in the following key deliverables: 1) Multi-scale test data from 0.1 kW bench-scale, 100 kW and 200 kW laboratory-scale, and 1 MW semi-industrial scale combustors that describe differences in flame characteristics, fouling, slagging and corrosion for coal combustion under air-firing and oxygen-firing conditions, including sensitivity to oxy-burner design and flue gas recycle composition. 2) Validated mechanisms developed from test data that describe fouling, slagging, waterwall corrosion, heat transfer, char burnout and sooting under coal oxy-combustion conditions. The mechanisms were presented in a form suitable for inclusion in CFD models or process models. 3) Principles to guide design of pilot-scale and full-scale coal oxy-firing systems and flue gas recycle configurations, such that boiler operational impacts from oxy-combustion retrofits are minimized. 4) Assessment of oxy-combustion impacts in two full-scale coal-fired utility boiler retrofits based on computational fluid dynamics (CFD) modeling of air-fired and oxygen-fired operation. This research determined that it is technically feasible to retrofit the combustion system in an air-fired boiler for oxy-fired operation. The impacts of CO{sub 2} flue gas recycle and burner design on flame characteristics (burnout, NO{sub x}, SO{sub x}, mercury and fine particle emissions, heat transfer) and operational concerns (fouling, slagging and corrosion) were minimal, with the exception of high sulfur levels resulting from untreated flue gas recycle with medium and high-sulfur coals. This work focused on combustion in the radiant and convective sections of the boiler and did not address boiler system integration issues, plant efficiencies, impacts on downstream air pollution control devices, or CO{sub 2} capture and compression. The experimental data, oxy-firing system principles and oxy-combustion process mechanisms provided by this work can be used by electric utilities, boiler OEMs, equipment suppliers, design firms, software vendors, consultants and government agencies to assess retrofit applications of oxy-combustion technologies to existing boilers and to guide development of new designs.

Adams, Bradley; Davis, Kevin; Senior, Constance; Shim, Hong Shim; Otten, Brydger; Fry, Andrew; Wendt, Jost; Eddings, Eric; Paschedag, Alan; Shaddix, Christopher; Cox, William; Tree, Dale

2013-09-30T23:59:59.000Z

446

Fire and fire surrogate treatment effects on leaf litter arthropods in a western Sierra Nevada mixed-conifer forest  

E-Print Network [OSTI]

mixed-conifer forest Kyle O. Apigian *, Donald L. Dahlsten ä , Scott L. Stephens Department to coexist. We conclude that the use of fire and fire surrogate treatments in Sierran mixed-conifer forests will be important in restoring ecosystem processes and reducing fire risk in our conifer forests (Stephens

Stephens, Scott L.

447

Is the situation and immediate threat to life and health? Spill/Leak/Release Medical Emergency Fire or Flammable Gas Spill/Leak/Release Medical Emergency Fire or Flammable Gas Chemical Odor? Possible Fire / Natural Gas  

E-Print Network [OSTI]

? Possible Fire / Natural Gas (including chemicals and bio agents") (not including chemicals or bio agents Fire or Flammable Gas Spill/Leak/Release Medical Emergency Fire or Flammable Gas Chemical Odor

448

Preventing Laptop Fires and Thermal Runaway | U.S. DOE Office of Science  

Office of Science (SC) Website

Stories of Discovery & Innovation: Preventing Laptop Stories of Discovery & Innovation: Preventing Laptop Fires and Thermal Runaway Energy Frontier Research Centers (EFRCs) EFRCs Home Centers Research Science Highlights News & Events EFRC News Observing the Sparks of Life EFRC Events DOE Announcements Publications Contact BES Home 12.05.12 Stories of Discovery & Innovation: Preventing Laptop Fires and Thermal Runaway Print Text Size: A A A Subscribe FeedbackShare Page Researchers point to "self-healing" materials as a potential means of improving lithium ion battery safety. This work, featured in the Office of Science's Stories of Discovery & Innovation, was supported in part by the Center for Electrical Energy Storage (CEES), an EFRC led by Michael Thackeray at Argonne National Laboratory. Last modified: 3/27/2013 12:28:00

449

NETL: News Release - Novel Coal-Fired Heating System Proves Successful at  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

December 20, 2005 December 20, 2005 Novel Coal-Fired Heating System Proves Successful at Ohio Greenhouse Cost Savings and State EPA Standards Achieved in First Commercial Demonstration WASHINGTON, DC - Using a Department of Energy - funded coal-fired technology, a greenhouse in northeast Ohio is saving more than $1,000 a day in heating costs. The efficient fluidized-bed combustion unit provides an alternative to natural gas systems and, using locally available coal and limestone, surpasses state EPA standards for sulfur capture and stack emissions. "The promise of the unit lies in its novel design," said Donald Bonk, a senior technical advisor for the National Energy Technology Laboratory (NETL), which manages the project for the Energy Department. "The fluidized-bed combustion system features flue-gas recirculation, replacing conventional, more expensive boiler tubes. By recycling the flue gas, the system better controls internal temperatures to burn fuel, reducing the formation of pollutants."

450

Review on optical fiber sensing technologies for industrial applications at the NEL-FOST  

E-Print Network [OSTI]

% of large oil tanks in China Petrochemical Company, fire and structural safety monitoring of the first optic hydrophones and gas sensors. However there still exist gaps to meet customer demand of the world's highest concrete face dam, fire alarm system of four national strategic oil storages and 90

Boyer, Edmond

451

Enhancing fire safety at Hydro plants with dry transformers  

SciTech Connect (OSTI)

Hydroelectric plant owners and engineers can use dry-type transformers to reduce fire hazards in auxiliary power systems. The decision to replace a liquid-immersed transformer with a dry-type product has a price: higher unit cost and a need to be more vigilant in detailing transformer specifications. But, whether the change affects only one failed transformer or is part of a plant rehabilitation project, the benefits in safety can be worth it. Voltages on hydroelectric plant auxiliary power systems can range from a 20 kV medium-voltage system to the normal 480-208/120 V low-voltage system. Dry transformers typically are used in such systems to reduce the fire hazard present with liquid-filled transformers. For a hydro plant owner or engineer seeking alternatives to liquid-filled transformers, there are two main kinds of dry-type transformers to consider: vacuum pressure impregnated (VPI) and cast coil epoxy resin. VPI transformers normally are manufactured in sizes up to 6,000 kVA with primary voltage ratings up to 20 kV. Cast coil transformers can be made in sizes from 75 to 10,000 kVA, with primary voltage ratings up to 34,500 V. Although the same transformer theory applies to dry transformers as to liquid-filled units, the cooling medium, air, required different temperature rise ratings, dielectric tests, and construction techniques to ensure reliability. Consequently, the factory and field tests for dry units are established by a separate set of American National Standards Institute (ANSI)/Institute of Electrical and Electronics Engineers (IEEE) standards. Cast coil transformers have several important advantages over VPI units.

Clemen, D.M. (Harza Engineering Company, Chicago, IL (United States))

1993-06-01T23:59:59.000Z

452

Electrical Sitchgear Building No. 5010-ESF Fire Hazards Technical Report  

SciTech Connect (OSTI)

The purpose of this Fire Hazards Analysis Technical Report (hereinafter referred to as Technical Report) is to assess the risk from fire within individual fire areas to ascertain whether the U.S. Department of Energy (DOE) fire safety objectives are met. The objectives, identified in DOE Order 420.1, Change 2, Fire Safety, Section 4.2, establish requirements for a comprehensive fire and related hazards protection program for facilities sufficient to minimize the potential for: (1) The occurrence of a fire or related event; (2) A fire that causes an unacceptable on-site or off-site release of hazardous or radiological material that will threaten the health and safety of the employees, the public, and the environment; (3) Vital DOE programs suffering unacceptable interruptions as a result of fire and related hazards; (4) Property losses from a fire and related events exceeding defined limits established by DOE; and (5) Critical process controls and safety class systems being damaged as a result of a fire and related event.

N.M. Ruonavaara

2001-05-08T23:59:59.000Z

453

Fire Hazards Analysis for the 200 Area Interim Storage Area  

SciTech Connect (OSTI)

This documents the Fire Hazards Analysis (FHA) for the 200 Area Interim Storage Area. The Interim Storage Cask, Rad-Vault, and NAC-1 Cask are analyzed for fire hazards and the 200 Area Interim Storage Area is assessed according to HNF-PRO-350 and the objectives of DOE Order 5480 7A. This FHA addresses the potential fire hazards associated with the Interim Storage Area (ISA) facility in accordance with the requirements of DOE Order 5480 7A. It is intended to assess the risk from fire to ensure there are no undue fire hazards to site personnel and the public and to ensure property damage potential from fire is within acceptable limits. This FHA will be in the form of a graded approach commensurate with the complexity of the structure or area and the associated fire hazards.

JOHNSON, D.M.

2000-01-06T23:59:59.000Z

454

Y-12 National Security Complex | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Y-12 National Security Complex Y-12 National Security Complex Y-12 National Security Complex Y-12 National Security Complex Aerial View Y-12 National Security Complex Aerial View Y-12 National Security Complex's primary mission is to support of the DOE nuclear weapons stockpile maintenance program. Activities include assembly and disassembly of nuclear weapons components, secure storage of special nuclear material (SNM), and various other nuclear weapons-related activities. Other activities include various aspects of testing and development, nonproliferation, and technology transfer. Enforcement June 13, 2008 Preliminary Notice of Violation, Babcock & Wilcox Teclmical Services Y -12, LLC - NEA-2008-01 Preliminary Notice of Violation issued to Babcock & Wilcox Technical Services Y-12, LLC, related to a Uranium Chip Fire at the Y-12 National

455

FIREPLUME model for plume dispersion from fires: Application to uranium hexafluoride cylinder fires  

SciTech Connect (OSTI)

This report provides basic documentation of the FIREPLUME model and discusses its application to the prediction of health impacts resulting from releases of uranium hexafluoride (UF{sub 6}) in fires. The model application outlined in this report was conducted for the Draft Programmatic Environmental Impact Statement for Alternative Strategies for the Long-Term Management and Use of Depleted UF{sub 6}. The FIREPLUME model is an advanced stochastic model for atmospheric plume dispersion that predicts the downwind consequences of a release of toxic materials from an explosion or a fire. The model is based on the nonbuoyant atmospheric dispersion model MCLDM (Monte Carlo Lagrangian Dispersion Model), which has been shown to be consistent with available laboratory and field data. The inclusion of buoyancy and the addition of a postprocessor to evaluate time-varying concentrations lead to the current model. The FIREPLUME model, as applied to fire-related UF{sub 6} cylinder releases, accounts for three phases of release and dispersion. The first phase of release involves the hydraulic rupture of the cylinder due to heating of the UF{sub 6} in the fire. The second phase involves the emission of material into the burning fire, and the third phase involves the emission of material after the fire has died during the cool-down period. The model predicts the downwind concentration of the material as a function of time at any point downwind at or above the ground. All together, five fire-related release scenarios are examined in this report. For each scenario, downwind concentrations of the UF{sub 6} reaction products, uranyl fluoride and hydrogen fluoride, are provided for two meteorological conditions: (1) D stability with a 4-m/s wind speed, and (2) F stability with a 1-m/s wind speed.

Brown, D.F.; Dunn, W.E. [Univ. of Illinois, Champaign-Urbana, IL (United States). Dept. of Mechanical Engineering; Policastro, A.J.; Maloney, D. [Argonne National Lab., IL (United States)

1997-06-01T23:59:59.000Z

456

Kuwait summons more fire fighting teams  

SciTech Connect (OSTI)

Kuwait is calling in more muscle to help kill its wild wells. This paper reports on the latest action in Kuwait, the leasing of well control contracts to Abel Engineering/Well Control Inc., Houston, and China Petroleum Engineering Construction Co. (CPEC). Abel is the sixth North American well control company called to the scene, while CPEC is the first summoned from the East. In addition, the service responsible for combating well fires and blowouts in the U.S.S.R.'s Azerbaijan oil fields signed an agreement with Kuwait's government, apparently involving a contract valued at more than $100 million, to extinguish fires at 150 Kuwaiti wells, reported Eastern Bloc Energy, a publication of Eastern Bloc Research Ltd., Newton Kyme, U.K. More help likely is on the way.

Not Available

1991-08-05T23:59:59.000Z

457

Chapter 3 - Coal-fired Power Plants  

Science Journals Connector (OSTI)

Abstract Coal provides around 40% of the worlds electricity, more than any other source. Most modern coal-fired power stations burn pulverized coal in a boiler to raise steam for a steam turbine. High efficiency is achieved by using supercritical boilers made of advanced alloys that produce high steam temperatures, and large, high-efficiency steam turbines. Alternative types of coal-fired power plants include fluidized bed boilers that can burn a variety of poor fuels, as well as coal gasifiers that allow coal to be turned into a combustible gas that can be burned in a gas turbine. Emissions from coal plants include sulfur dioxide, nitrogen oxide, and trace metals, all of which must be controlled. Capturing carbon dioxide from a coal plant is also under consideration. This can be achieved using post-combustion capture, a pre-combustion gasification process, or by burning coal in oxygen instead of air.

Paul Breeze

2014-01-01T23:59:59.000Z

458

Assessment of fire pump caisson integrity  

SciTech Connect (OSTI)

Fire pump and water lift caissons often suffer damage due to combinations of corrosion, fatigue and repeated impacts. These effects have been investigated in the context of integrity evaluations for a number of caissons and a number of contributory factors have been identified and investigated. The paper describes these investigations in some detail, as well as the mitigation measures identified and adopted to eliminate the problem.

Ellinas, C.P. [Advanced Mechanics and Engineering Ltd., Croydon (United Kingdom); Weir, T. [Total Oil Marine, Aberdeen (United Kingdom)

1995-12-31T23:59:59.000Z

459

Resistance after firing protected electric match  

DOE Patents [OSTI]

An electric match having electrical leads embedded in flame-producing compound is protected against an accidental resistance across the leads after firing by a length of heat-shrinkable tubing encircling the match body and having a skirt portion extending beyond the leads. The heat of the burning match and an adjacent thermal battery causes the tubing to fold over the end of the match body, covering the ends of the leads and protecting them from molten pieces of the battery.

Montoya, Arsenio P. (Albuquerque, NM)

1981-11-10T23:59:59.000Z

460

Enforcement Letter, Los Alamos National Laboratory - July 7, 1997 |  

Broader source: Energy.gov (indexed) [DOE]

July 7, 1997 July 7, 1997 Enforcement Letter, Los Alamos National Laboratory - July 7, 1997 July 7, 1997 Issued to the University of California related to Potential Quality Assurance Rule Violations associated with an Explosion and Fire at the Los Alamos National Laboratory This letter refers to the Department of Energy's (DOE's) evaluation of potential noncompliances with the requirements of 10 CFR 830.120 (Quality Assurance Rule). The noncompliances involved the failure of Los Alamos National Laboratory (LANL) to adequately implement the requirements contained in the governing quality assurance standard for stockpile evaluations in the areas of work controls and procedural compliance. As a result of these failures, an explosion and fire occurred at the [ ] on November 14, 1996.

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


461

Enforcement Letter, Los Alamos National Laboratory - July 7, 1997 |  

Broader source: Energy.gov (indexed) [DOE]

July 7, 1997 July 7, 1997 Enforcement Letter, Los Alamos National Laboratory - July 7, 1997 July 7, 1997 Issued to the University of California related to Potential Quality Assurance Rule Violations associated with an Explosion and Fire at the Los Alamos National Laboratory This letter refers to the Department of Energy's (DOE's) evaluation of potential noncompliances with the requirements of 10 CFR 830.120 (Quality Assurance Rule). The noncompliances involved the failure of Los Alamos National Laboratory (LANL) to adequately implement the requirements contained in the governing quality assurance standard for stockpile evaluations in the areas of work controls and procedural compliance. As a result of these failures, an explosion and fire occurred at the [ ] on November 14, 1996.

462

Oak Ridge National Laboratory National Security Programs  

E-Print Network [OSTI]

Oak Ridge National Laboratory National Security Programs Dr. Michael A. Kuliasha, Chief Scientist National Security Technologies Oak Ridge National Laboratory #12;2 OAK RIDGE NATIONAL LABORATORY U. S Security Challenges #12;3 OAK RIDGE NATIONAL LABORATORY U. S. DEPARTMENT OF ENERGY How Will Our Enemies

463

Fire exposure of empty 30B cylinders  

SciTech Connect (OSTI)

Cylinders for UF{sub 6} handling, transport, and storage are designed and built as unfired pressure vessels under ASME Boiler and Pressure Vessel Code criteria and standards. They are normally filled and emptied while UF{sub 6} is in its liquid phase. Transport cylinders such as the Model 30B are designed for service at 200 psi and 250{degrees}F, to sustain the process conditions which prevail during filling or emptying operations. While in transport, however, at ambient temperature the UF{sub 6} is solid, and the cylinder interior is well below atmospheric pressure. When the cylinders contain isotopically enriched product (above 1.0 percent U-235), they are transported in protective overpacks which function to guard the cylinders and their contents against thermal or mechanical damage in the event of possible transport accidents. Two bare Model 30B cylinders were accidentally exposed to a storage warehouse fire in which a considerable amount of damage was sustained by stored materials and the building structure, as well as by the cylinder valves and valve protectors. The cylinders were about six years old, and had been cleaned, inspected, hydrotested, and re-certified for service, but were still empty at the time of the fire. The privately-owned cylinders were transferred to DOE for testing and evaluation of the fire damage.

Ziehlke, K.T. [MJB Technical Associates, Inc., Knoxville, TN (United States)

1991-12-31T23:59:59.000Z

464

Surface Fire Hazards Analysis Technical Report-Constructor Facilities  

SciTech Connect (OSTI)

The purpose of this Fire Hazards Analysis Technical Report (hereinafter referred to as Technical Report) is to assess the risk from fire within individual fire areas to ascertain whether the U.S. Department of Energy (DOE) fire safety objectives are met. The objectives identified in DOE Order 420.1, Change 2, Facility Safety, Section 4.2, establish requirements for a comprehensive fire and related hazards protection program for facilities sufficient to minimize the potential for: The occurrence of a fire or related event; A fire that causes an unacceptable on-site or off-site release of hazardous or radiological material that will threaten the health and safety of employees, the public, or the environment; Vital DOE programs suffering unacceptable interruptions as a result of fire and related hazards; Property losses from a fire and related events exceeding defined limits established by DOE; and Critical process controls and safety class systems being damaged as a result of a fire and related events.

R.E. Flye

2000-10-24T23:59:59.000Z

465

Development and Demonstration of Waste Heat Integration with Solvent Process for More Efficient CO2 Removal from Coal-Fired Flue Gas  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

and Demonstration of and Demonstration of Waste Heat Integration with Solvent Process for More Efficient CO 2 Removal from Coal-Fired Flue Gas Background The mission of the U.S. Department of Energy/National Energy Technology Laboratory (DOE/NETL) Existing Plants, Emissions, & Capture (EPEC) Research & Development (R&D) Program is to develop innovative environmental control technologies to enable full use of the nation's vast coal reserves, while at the same time allowing the current fleet of coal-

466

Bench-scale Development of an Advanced Solid sorbent-based CO2 Capture Process for Coal-fired Power Plalnts  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

scale Development of an scale Development of an Advanced Solid Sorbent-based CO 2 Capture Process for Coal-fired Power Plants Background The mission of the U.S. Department of Energy/National Energy Technology Laboratory (DOE/NETL) Existing Plants, Emissions, & Capture (EPEC) Research & Development (R&D) Program is to develop innovative environmental control technologies to enable full use of the nation's vast coal reserves, while at the same time allowing the current

467

Near-Term Implications of a Ban on New Coal-Fired Power Plants in the United States  

Science Journals Connector (OSTI)

A national ban on new coal-fired power plants does not lead to CO2 reductions of the scale required under proposed federal legislation such as Lieberman-Warner but would greatly increase the fraction of time when natural gas sets the price of electricity, even with aggressive wind and demand response policies. ... In the demand response scenario, per capital demand growth is zero. ...

Adam Newcomer; Jay Apt

2009-04-27T23:59:59.000Z

468

National System Templates: Building Sustainable National Inventory  

Open Energy Info (EERE)

National System Templates: Building Sustainable National Inventory National System Templates: Building Sustainable National Inventory Management Systems Jump to: navigation, search Tool Summary LAUNCH TOOL Name: National System Templates: Building Sustainable National Inventory Management Systems Agency/Company /Organization: United States Environmental Protection Agency, United States Agency for International Development Sector: Energy, Land Focus Area: Non-renewable Energy, Forestry, Agriculture Topics: GHG inventory Resource Type: Guide/manual, Training materials Website: www.epa.gov/climatechange/emissions/ghginventorycapacitybuilding/templ National System Templates: Building Sustainable National Inventory Management Systems Screenshot References: National System Templates: Building Sustainable National Inventory Management Systems[1]

469

Categorical Exclusion Determinations: National Energy Technology Laboratory  

Broader source: Energy.gov (indexed) [DOE]

August 14, 2013 August 14, 2013 CX-010787: Categorical Exclusion Determination Fire Loop Soil Excavation CX(s) Applied: B3.1, B6.1 Date: 08/14/2013 Location(s): Oregon Offices(s): National Energy Technology Laboratory August 14, 2013 CX-010786: Categorical Exclusion Determination North Central Texas Alternative Fuel and Advanced Technology Investments CX(s) Applied: B5.23 Date: 08/14/2013 Location(s): Texas Offices(s): National Energy Technology Laboratory August 14, 2013 CX-010791: Categorical Exclusion Determination Gulf of Mexico Miocene Carbon Dioxide (CO2) Site Characterization Mega Transect CX(s) Applied: A9, A11 Date: 08/14/2013 Location(s): Texas Offices(s): National Energy Technology Laboratory August 14, 2013 CX-010792: Categorical Exclusion Determination Gulf of Mexico Miocene Carbon Dioxide (CO2) Site Characterization Mega

470

Categorical Exclusion Determinations: National Energy Technology Laboratory  

Broader source: Energy.gov (indexed) [DOE]

19, 2010 19, 2010 CX-004491: Categorical Exclusion Determination Site Characterization for Carbon Dioxide Storage from Coal-fired Power Facilities in the Black Warrior Basin of Alabama CX(s) Applied: A9, B3.1 Date: 11/19/2010 Location(s): Alabama Office(s): Fossil Energy, National Energy Technology Laboratory November 19, 2010 CX-004490: Categorical Exclusion Determination Utah Expansion Compressed Natural Gas Refueling Sites CX(s) Applied: B5.1 Date: 11/19/2010 Location(s): Salt Lake City, Utah Office(s): Energy Efficiency and Renewable Energy, National Energy Technology Laboratory November 19, 2010 CX-004489: Categorical Exclusion Determination Thai Process for Heavy Oil CX(s) Applied: B3.6 Date: 11/19/2010 Location(s): Laramie, Wyoming Office(s): Fossil Energy, National Energy Technology Laboratory

471

Categorical Exclusion Determinations: National Energy Technology Laboratory  

Broader source: Energy.gov (indexed) [DOE]

January 27, 2010 January 27, 2010 CX-000997: Categorical Exclusion Determination Biodiesel Infrastructure Project (PrairieFire) CX(s) Applied: A1, A9, B5.1 Date: 01/27/2010 Location(s): Monona, Wisconsin Office(s): Energy Efficiency and Renewable Energy, National Energy Technology Laboratory January 27, 2010 CX-000998: Categorical Exclusion Determination Biodiesel Infrastructure Project (Coulee) CX(s) Applied: A1, A9, B5.1 Date: 01/27/2010 Location(s): Blair, Wisconsin Office(s): Energy Efficiency and Renewable Energy, National Energy Technology Laboratory January 27, 2010 CX-000999: Categorical Exclusion Determination Biodiesel In-line Blending Project (Innovation) CX(s) Applied: A1, A9, B5.1 Date: 01/27/2010 Location(s): Milwaukee, Wisconsin Office(s): Energy Efficiency and Renewable Energy, National Energy

472

Categorical Exclusion Determinations: National Energy Technology Laboratory  

Broader source: Energy.gov (indexed) [DOE]

April 27, 2012 April 27, 2012 CX-008292: Categorical Exclusion Determination Waste Heat Integration with Solvent Process for More Efficient Carbon Dioxide Removal from Coal-Fired Flue Gas CX(s) Applied: A11 Date: 04/27/2012 Location(s): Texas Offices(s): National Energy Technology Laboratory April 25, 2012 CX-008309: Categorical Exclusion Determination Evaluation of Solid Sorbents as a Retrofit Technology for Carbon Dioxide Capture CX(s) Applied: B3.6 Date: 04/25/2012 Location(s): Colorado Offices(s): National Energy Technology Laboratory April 25, 2012 CX-008307: Categorical Exclusion Determination Deepwater Reverse-Circulation Primary Cementing CX(s) Applied: A9 Date: 04/25/2012 Location(s): Texas Offices(s): National Energy Technology Laboratory April 25, 2012 CX-008306: Categorical Exclusion Determination

473

Characterization of Oxy-combustion Impacts in Existing Coal-fired Boilers  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Characterization of Oxy-combustion Characterization of Oxy-combustion Impacts in Existing Coal-fired Boilers Background Technology and policy options are being investigated for mitigating CO 2 emissions. Electric power generation represents one of the largest CO 2 contributors in the United States and is expected to grow with fossil fuels continuing to be the dominant fuel source. Oxy-combustion is a developing technology that could become part of a national carbon capture effort to mitigate climate change. At a pulverized coal

474

Fire Protection System Account Request Form | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection System Account Request Form Fire Protection System Account Request Form Fire Protection System Account Request Form December 2, 2010 Account request form used to obtain user credentials for the Fire Protection Database To obtain a user id and password to access the Fire Protection system, please complete the form, save the file and email it to HSSUserSupport@hq.doe.gov or print and fax it to 301-903-9823. We will provide a username and password to new account holders. Please allow several business days to process your account request. When your request is approved, you will be contacted with your account information. Fire Protection System Account Request Form More Documents & Publications CAIRS Registration Form Microsoft Word - PARS II User Acct Access Guide.rtf PARS Domain User Maintenance Function Support Team Guide (v

475

Real time simulation of 2007 Santa Ana fires  

E-Print Network [OSTI]

There are many wildfire behaviors of increasing relevance that are outside the forecast capabilities of even the most sophisticated operational fire spread and fire behavior model. The limitations of the operational models are due primarily to their inability to represent coupled fire-atmosphere interactions. Coupled wildfire-atmosphere models are physics-based fluid-dynamical prognostic models of wildfire spread and behavior that attempt an almost complete representation of fire-atmosphere interactions. This level of fidelity however means that these models cannot be used operationally. The reason is that, despite ever increasing computational resources, the complexity and range of processes and scales (1 mm to 100 km) involved in this modeling approach make computational costs prohibitively expensive. In this study we propose an intermediate approach. A physics-based coupled atmosphere-fire model is used to resolve the large-scale and local weather as well as the atmosphere-fire interactions, while combusti...

Kochanski, A K; Krueger, S K; Mandel, J; Beezley, J D

2012-01-01T23:59:59.000Z

476

Enforcement Documents - Y-12 National Security Complex | Department of  

Broader source: Energy.gov (indexed) [DOE]

Y-12 National Security Complex Y-12 National Security Complex Enforcement Documents - Y-12 National Security Complex June 13, 2008 Preliminary Notice of Violation, Babcock & Wilcox Teclmical Services Y-12, LLC - NEA-2008-01 Preliminary Notice of Violation issued to Babcock & Wilcox Technical Services Y-12, LLC, related to a Uranium Chip Fire at the Y-12 National Security Complex September 18, 2007 Preliminary Notice of Violation, BWXT Y-12 LLC - EA-2007-04 Preliminary Notice of Violation issued to BWXT Y-12, LLC, related to Criticality Safety Controls at the Y-12 National Security Complex June 15, 2006 Enforcement Letter, BWXT Y-12 - June 15, 2006 Enforcement Letter issued to BWXT Y-12 related to Quality Assurance Deficiencies in construction activities at the Y-12 National Security

477

What is the problem? The cost of fire in the U.S. is growing. In  

E-Print Network [OSTI]

understanding of fire behavior, which hinders the develop- ment of innovative fire protection. Current Protection generation of standards, codes, and tech- nologies that address the U.S. fire problem. Measurement innovative fire protection M e a s u r e M e n t s c i e n c e f o r innovative fire protection challenging

Magee, Joseph W.

478

Wildland fire emissions, carbon, and climate: U.S. emissions inventories Narasimhan K. Larkin a,  

E-Print Network [OSTI]

Wildland fire emissions, carbon, and climate: U.S. emissions inventories Narasimhan K. Larkin a: Fire emissions Emissions inventories Greenhouse gases a b s t r a c t Emissions from wildland fire fire emissions change considerably due to fluctuations from year to year with overall fire season

479

A policy study examining the use of imported LNG for gas-fired power generation on the southeast coast of China  

Science Journals Connector (OSTI)

Since China's energy demand is growing quickly, speeding up the development of natural gas is an important substitute and supplement for coal and oil. The development of the natural gas market in many developing countries has demonstrated that the success of the whole project hinges upon the success of gas-fired power generation. However, under the current energy pricing system in China, the advantages of gas-fired power plants, such as low investment costs and high efficiency, have not been able to offset the low price of coal. The gas-fired power plants, both at downstream of the Liquefied Natural Gas (LNG) industry and upstream of the power sector, are faced with a dilemma. In order to solve the problems facing gas-fired power projects while providing policy guidance for the future development of gas-fired power projects, the policy of gas-fired power generation using imported LNG on the southeastern coast of China was examined. This study aims to identify the position of the national energy strategy that China should import some LNG from the other countries, to guide the development of energy policy in this region, and to formulate some clear policy measures.

Yajun Li; Fangfang Bai

2010-01-01T23:59:59.000Z

480

NACOM code for analysis of postulated sodium spray fires in LMFBRs  

SciTech Connect (OSTI)

An analysis of potential sodium spills and fires in liquid metal fast breeder reactors has been made to assess the maximum equipment cell loading conditions. A computer code called NACOM (sodium combustion) has been developed at Brookhaven National Laobratory (BNL) to analyze sodium spray fires. This report contains a detailed description of physical models used in this code as well as programming aspects. The single droplet combustion model and the model describing the droplets' motion are verified. Comparisons between NACOM predictions and SPRAY-3A predictions of the Atomics International (AI) LTV Jet Tests are made. Good agreement is found between the NACOM predictions and the experimental data. NACOM predictions of the pressure rise are more accurate than SPRAY-3A predictions for most of the cases studied. The code has been verified for oxygen concentrations ranging from 0 to 21%. NACOM utilizes more realistic single droplet and spray combustion models than SPRAY-3A. Moreover, NACOM does not utilize adjustable parameters for the burning rate equations, contrary to the approach taken with SPRAY-3A. Thus, the NACOM code is a more reliable code for use in the analysis of large-scale sodium spray fires in LMFBR containment cells. 24 refs., 32 figs.

Tsai, S.S.

1980-03-01T23:59:59.000Z

Note: This page contains sample records for the topic "national fire alarm" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


481

Environmental studies in support of the live fire training facilities project  

SciTech Connect (OSTI)

The Engineering Division of the Oak Ridge National Laboratory of Martin Marietta Energy System, Inc., provided services, under an Interagency Agreement, to the US Air Force to design, construct, and test environmentally acceptable fire training facilities at several Air Force bases for the purpose of providing live fire training capabilities without harming the environment. The purpose of this effort was to evaluate the wastewater treatment systems of the training facilities. The study focused on taking a set of background samples at a facility and then allowing the Air Force to conduct a series of training exercises. A set of samples was taken immediately following the training exercises to determine the effect the exercises had on the wastewater in the fuel/water separator and the holding pond. The separator and pond were also allowed to set undisturbed, except for sampling and environmental influences, for /approximately/60 d to determine if any stripping or biodegradation was occurring. Samples of the separator and pond were taken at 2, 4, 6, 8, 10, 11, 32, and 59 d following the training exercises. In addition, the burn pit was sampled immediately following the extinguishment of a fire and then again after the burn pit was flushed with water to determine if the materials remaining could be classified as hazardous under the Resource Conservation and Recovery Act (RCRA). 16 figs., 11 tabs.

Hylton, T.D.; Walker, J.F.

1989-08-01T23:59:59.000Z

482

10. Vorbeugender Brand-und Gefahrenschutz / Fire prevention  

E-Print Network [OSTI]

in den Gebäuden / Passiv Fire Protection 10.1.2.1. Löscheinrichtungen in den Gebäuden / Extinguishing / Structural fire protection10.2.1.1. ?berprüfung von Bauanträgen 10.2.1.2. ?berprüfung von Umwidmungen 10.2.2. Anlagentechnischer Brand- und Gefahrenschutz von Flächen / Passiv Fire Protection 10.2.2.1. Löscheinrichtungen auf

Berlin,Technische Universität

483

An assessment of fire vulnerability for aged electrical relays  

SciTech Connect (OSTI)

There has been some concern that, as nuclear power plants age, protective measures taken to control and minimize the impact of fire may become ineffective, or significantly less effective, and hence result in an increased fire risk. One objective of the Fire Vulnerability of Aged Electrical Components Program is to assess the effects of aging and service wear on the fire vulnerability of electrical equipment. An increased fire vulnerability of components may lead to an overall increase in fire risk to the plant. Because of their widespread use in various electrical safety systems, electromechanical relays were chosen to be the initial components for evaluation. This test program assessed the impact of operational and thermal aging on the vulnerability of these relays to fire-induced damage. Only thermal effects of a fire were examined in this test program. The impact of smoke, corrosive materials, or fire suppression effects on relay performance were not addressed in this test program. The purpose of this test program was to assess whether the fire vulnerability of electrical relays increased with aging. The sequence followed for the test program was to: identify specific relay types, develop three fire scenarios, artificially age several relays, test the unaged and aged relays in the fire exposure scenarios, and compare the results. The relays tested were Agastat GPI, General Electric (GE) HMA, HGA, and HFA. At least two relays of each type were artificially aged and at least two relays of each type were new. Relays were operationally aged by cycling the relay under rated load for 2,000 operations. These relays were then thermally aged for 60 days with their coil energized.

Vigil, R.A. [Sandia National Labs., Albuquerque, NM (United States)]|[Science and Engineering Associates, Inc., Albuquerque, NM (United States); Nowlen, S.P. [Sandia National Labs., Albuquerque, NM (United States)

1995-03-01T23:59:59.000Z

484

INNOVATIVE FOSSIL FUEL FIRED VITRIFICATION TECHNOLOGY FOR SOIL REMEDIATION  

SciTech Connect (OSTI)

This Summary Report summarizes the progress of Phases 3, 3A and 4 of a waste technology Demonstration Project sponsored under a DOE Environmental Management Research and Development Program and administered by the U.S. Department of Energy National Energy Technology Laboratory-Morgantown (DOE-NETL) for an ''Innovative Fossil Fuel Fired Vitrification Technology for Soil Remediation''. The Summary Reports for Phases 1 and 2 of the Program were previously submitted to DOE. The total scope of Phase 3 was to have included the design, construction and demonstration of Vortec's integrated waste pretreatment and vitrification process for the treatment of low level waste (LLW), TSCA/LLW and mixed low-level waste (MLLW). Due to funding limitations and delays in the project resulting from a law suit filed by an environmental activist and the extended time for DOE to complete an Environmental Assessment for the project, the scope of the project was reduced to completing the design, construction and testing of the front end of the process which consists of the Material Handling and Waste Conditioning (MH/C) Subsystem of the vitrification plant. Activities completed under Phases 3A and 4 addressed completion of the engineering, design and documentation of the Material Handling and Conditioning System such that final procurement of the remaining process assemblies can be completed and construction of a Limited Demonstration Project be initiated in the event DOE elects to proceed with the construction and demonstration testing of the MH/C Subsystem.

J. Hnat; L.M. Bartone; M. Pineda

2001-07-13T23:59:59.000Z

485

National Laboratory  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Homesteading on the Pajarito Plateau Homesteading on the Pajarito Plateau topic of inaugural lecture at Los Alamos National Laboratory January 4, 2013 Lecture series begins yearlong commemoration of 70th anniversary LOS ALAMOS, NEW MEXICO, Jan. 3, 2013-In commemoration of its 70th anniversary, Los Alamos National Laboratory kicks off a yearlong lecture series on Wednesday, Jan. 9, at 5:30 p.m. with a presentation about homesteading on the Pajarito Plateau at the Bradbury Science Museum, 1350 Central Avenue, Los Alamos. - 2 - The inaugural lecture is based on a book by local writers Dorothy Hoard, Judy Machen and Ellen McGehee about the area's settlement between 1887 and 1942. On hikes across the Pajarito Plateau, Hoard envisioned the Los Alamos area before modern roads and bridges made transportation much easier. The trails she walked

486

Pantex High Pressure Fire Loop Project Completed On Time, Under...  

National Nuclear Security Administration (NNSA)

the Baseline Change Proposal process. Two 400,000-gallon fire protection water supply tanks and associated pumping facilities were added. Later in the project, an additional...

487

Global estimation of burned area using MODIS active fire observations  

E-Print Network [OSTI]

the 1995 fire season in South America, J. Geophys. Res. -Central America Northern Hemisphere South America SouthernHemisphere South America Europe Middle East Northern

Giglio, L.; van der Werf, G. R; Randerson, J. T; Collatz, G. J; Kasibhatla, P.

2006-01-01T23:59:59.000Z

488

A Method for Evaluating Fire After Earthquake Scenarios for Single...  

Broader source: Energy.gov (indexed) [DOE]

Evaluating Fire After Earthquake Scenarios for Single Buildings Authors: Elizabeth J. Kelly and Raymond N. Tell Intended Use: Handout for DOE Natural Phenomena Hazards Workshop,...

489

A Method for Evaluating Fire after Earthquake Scenarios for Single...  

Office of Environmental Management (EM)

Method for Evaluating Fire After Earthquake Scenarios for Single Buildings Elizabeth J. Kelly and Raymond N. Tell, LANL U.S. Department of Energy Natural Phenomena Hazards Workshop...

490

A Method for Evaluating Fire After Earthquake Scenarios for Single...  

Office of Environmental Management (EM)

Method for Evaluating Fire After Earthquake Scenarios for Single Buildings Elizabeth J. Kelly and Raymond N. Tell, LANL U.S. Department of Energy Natural Phenomena Hazards Workshop...

491

NREL: Energy Analysis - Natural Gas-Fired Generation Results...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

assessments have shown wide-ranging results. To better understand the greenhouse gas (GHG) emissions from utility-scale, natural gas-fired electricity generation systems (based...

492

NREL: Energy Analysis - Coal-Fired Electricity Generation Results...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

assessments have shown wide-ranging results. To better understand the greenhouse gas (GHG) emissions from utility-scale, coal-fired electricity generation systems (based on...

493

Install Waste Heat Recovery Systems for Fuel-Fired Furnaces  

Broader source: Energy.gov [DOE]

This tip sheet recommends installing waste heat recovery systems for fuel-fired furnaces to increase the energy efficiency of process heating systems.

494

Multiple organizations build interagency fire center at LANL  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

facility will also include room for offices, training, and meetings, and storage for fire protection and suppression equipment. The new facility is designed to meet Leadership...

495

Assessment of Passive Fire Protection on Steel-Girder Bridges.  

E-Print Network [OSTI]

?? Bridges in the US are severely damaged or suffer collapse from fires at significant rates, even when compared to other hazards such as earthquakes. (more)

Davidson, Michael

2012-01-01T23:59:59.000Z

496

Project examples Install new HVAC, electrical, fire protection,  

E-Print Network [OSTI]

Project examples Install new HVAC, electrical, fire protection, and plumbing systems in Mechanical. · Totransformthisspaceandincreaseaccessibility, anelevatorisrequired.Currently,Blakelydoesnot haveone. Replace HVAC and electrical system

Blanchette, Robert A.

497

NATIONAL NEWS  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

March 5, 2010 National News......................................................................3 Schumer Proposal to Halt ARRA Funds for Renewable Projects Would Cause Immediate Job Loss in U.S., DOE Officials Tell Congress .................................................................................................................................. 3 Geothermal Energy Holds Strong Presence at Renewable Energy World Conference; Applications with Oil and Gas Coproduction Gain Attention .......................................................................................................................... 4 House Subcommittee on Energy and Mineral Resources Hold Legislative Hearing on the Geothermal Production and Expansion Act, HR 3709 ..............................................................................................................

498

Biopower Report Presents Methodology for Assessing the Value of Co-Firing Biomass in Pulverized Coal Plants  

Broader source: Energy.gov [DOE]

A joint Idaho National Laboratory (INL) and Pacific Northwest National Laboratory (PNNL) report presents the results of an evaluation funded by the Bioenergy Technologies Office that examines the effects of substituting up to 20% renewable biomass for coal in electricity production. This report is the first publically available assessment of its kind to investigate the impacts of co-firing biomass with coal at concentrations greater than 10% biomass without modification to the pulverized coal plant or its feed system. Findings have expanded the methodology that communities and energy providers can use to evaluate the potential economic and environmental benefits of using biomass in their coal plants.

499

Fly ash and concrete: a study determines whether biomass, or coal co-firing fly ash, can be used in concrete  

SciTech Connect (OSTI)

Current US national standards for using fly ash in concrete (ASTM C618) state that fly ash must come from coal combustion, thus precluding biomass-coal co-firing fly ash. The co-fired ash comes from a large and increasing fraction of US power plants due to rapid increases in co-firing opportunity fuels with coal. The fly ashes include coal fly ash, wood fly ash from pure wood combustion, biomass and coal co-fired fly ash SW1 and SW2. Also wood fly ash is blended with Class C or Class F to produce Wood C and Wood E. Concrete samples were prepared with fly ash replacing cement by 25%. All fly ash mixes except wood have a lower water demand than the pure cement mix. Fly ashes, either from coal or non coal combustion, increase the required air entraining agent (AEA) to meet the design specification of the mixes. If AEA is added arbitrarily without considering the amount or existence of fly ash results could lead to air content in concrete that is either too low or too high. Biomass fly ash does not impact concrete setting behaviour disproportionately. Switch grass-coal co-fired fly ash and blended wood fly ash generally lie within the range of pure coal fly ash strength. The 56 day flexure strength of all the fly ash mixes is comparable to that of the pure cement mix. The flexure strength from the coal-biomass co-fired fly ash does not differ much from pure coal fly ash. All fly ash concrete mixes exhibit lower chloride permeability than the pure cement mixes. In conclusion biomass coal co-fired fly ash perform similarly to coal fly ash in fresh and hardened concrete. As a result, there is no reason to exclude biomass-coal co-fired fly ash in concrete.

Wang, Shuangzhen; Baxter, Larry

2006-08-01T23:59:59.000Z

500

Slurry fired heater cold-flow modelling  

SciTech Connect (OSTI)

This report summarizes the experimental and theoretical work leading to the scale-up of the SRC-I Demonstration Plant slurry fired heater. The scale-up involved a theoretical model using empirical relations in the derivation, and employed variables such as flow conditions, liquid viscosity, and slug frequency. Such variables have been shown to affect the heat transfer characteristics ofthe system. The model assumes that, if all other variables remain constant, the heat transfer coefficient can be scaled up proportional to D/sup -2/3/ (D = inside diameter of the fired heater tube). All flow conditions, liquid viscosities, and pipe inclinations relevant to the demonstration plant have indicated a slug flow regime in the slurry fired heater. The annular and stratified flow regimes should be avoided to minimize the potential for excessive pipe erosion and to decrease temperature gradients along the pipe cross section leading to coking and thermal stresses, respectively. Cold-flow studies in 3- and 6.75-in.-inside-diameter (ID) pipes were conducted to determine the effect of scale-up on flow regime, slug frequency, and slug dimensions. The developed model assumes that conduction heat transfer occurs through the liquid film surrounding the gas slug and laminar convective heat transfer to the liquid slug. A weighted average of these two heat transfer mechanisms gives a value for the average pipe heat transfer coefficient. The cold-flow work showed a decrease in the observed slug frequency between the 3- and 6.75-ID pipes. Data on the ratio of gas to liquid slug length in the 6.75-in. pipe are not yet complete, but are expected to yield generally lower values than those obtained in the 3-in. pipe; this will probably affect the scale-up to demonstration plant conditions. 5 references, 15 figures, 7 tables.

Moujaes, S.F.

1983-07-01T23:59:59.000Z