Powered by Deep Web Technologies
Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


1

Fire alarm system improvement  

SciTech Connect

This document contains the Fire Alarm System Test Procedure for Building 234-5Z, 200-West Area on the Hanford Reservation, Richland, Washington. This Acceptance Test Procedure (ATP) has been prepared to demonstrate that the modifications to the Fire Protection systems function as required by project criteria. The ATP will test the Fire Alarm Control Panels, Flow Alarm Pressure Switch, Heat Detectors, Smoke Detectors, Flow Switches, Manual Pull Stations, and Gong/Door by Pass Switches.

Hodge, S.G.

1994-10-01T23:59:59.000Z

2

False fire alarms have a negative impact on UW operations False (or nuisance) alarms are very disruptive to UW operations. The alarms  

E-Print Network (OSTI)

protection devices and upgrading old fire protection equipment with current technology. How construction. · Temporary impairment/removal of fire alarm devices ­ Confer with the University Fire Protection Engineer Fire Alarm Shop. · Fire watch requirements - Confer with the University Fire Protection Engineer (206

Wilcock, William

3

Project 93L-EWL-097, fire alarm system improvements, 300 Area  

SciTech Connect

This document contains the Acceptance Test Procedure (ATP) which will demonstrate that the modifications to the Fire Protection systems in the 338 Building function as intended. The ATP will test the fire alarm control panel, flow alarm pressure switch, post indicator valve tamper switch, heat detectors, flow switches, and fire alarm signaling devices.

Scott, M.V.

1995-01-01T23:59:59.000Z

4

Activate the nearest fire alarm pull station Call 911 to report the fire  

E-Print Network (OSTI)

, records and hazardous materials. o Shut off non-essential electrical equipment. o Wait for instructions, fumes or vapors: Do not pull fire alarms. Do not touch light switches or electrical equipment. Call UH. Provide your location and the location of the odor to the dispatcher. Provide as many details as possible

Azevedo, Ricardo

5

Fire Alarm Testing and Inspection Planning and Vendor Check In/Check Out Process  

E-Print Network (OSTI)

Fire Alarm Testing and Inspection Planning and Vendor Check In/Check Out Process DOCUMENT PURPOSE This process is used for fire alarm testing and inspection pre-work planning and vendor check in and check out ____________________________________________________ CHECK IN PRIOR TO TESTING NOTES _____ Central Monitoring (BSAC) notified of daily testing start time

Webb, Peter

6

Setting fires, false alarms, or vandalizing fire protection equipment is illegal. Any person found to be participating in these activities will be prosecuted to the full extent of the law and/or disciplined through the University's disciplinary procedures  

E-Print Network (OSTI)

Setting fires, false alarms, or vandalizing fire protection equipment is illegal. Any person found University fire safety equipment should contact the Campus University Police or Security. FIRES What should I do if I discover a fire? ACTIVATE THE FIRE ALARM SYSTEM by pulling one of the pull stations that re

Fernandez, Eduardo

7

Setting fires, false alarms, or vandalizing fire protection equipment is illegal. Any person found to be participating in these activities will be prosecuted to the full extent of the law and/or disciplined through the University's disciplinary procedures  

E-Print Network (OSTI)

Setting fires, false alarms, or vandalizing fire protection equipment is illegal. Any person found University fire safety equipment should contact the Campus University Police or Security. FIRES What should I do if I discover a fire? · ACTIVATE THE FIRE ALARM SYSTEM by pulling one of the nearest pull stations

Fernandez, Eduardo

8

EA-289-B INTERCOM ENERGY INC | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

EA-289-B Intercom MX.pdf More Documents & Publications EA-318-C AEP Energy Partners, Inc. EA-386 IPR-GDF Suez Energy Marketing North America, Inc. (GSEMNA) EA-383 Pilot Power Group...

9

An evaluation of various types of fire detection alarm systems to awaken the elderly  

E-Print Network (OSTI)

to represent the hearing perception of an ei ghty year old male, were presented to ten college student participarits. These three alarm systems represented a smoke detector located in the hallway; in the bedroom and the liallway; and in the bedroom...-Sand Frequency Analyses (SPL re . 0002 microPascal) Taken 10 Feet from Source in UNass Anechoic Chaarber 18 IV An Average Eighty Year Old Nale's Hearing Perception of the Average Smoke Def~ctor Alarm Signals Neasured by Nober, Peirce and Well, at a Distance...

Townley, Timothy Edward

2012-06-07T23:59:59.000Z

10

Technical evaluation of equipment maintenance on fire alarm detection, suppression, and signaling  

SciTech Connect

This document delineates the application of WHC-CM-4-3, Program E-2 to Fire Systems on the Hanford Site.

Korslund, S.M.

1994-10-01T23:59:59.000Z

11

An analysis of firefighter personal safety alarm effectiveness on the fire ground  

Science Journals Connector (OSTI)

For firefighters in the line of duty the last line of defense and chance for rescue oftentimes relies on the effectiveness of their Personal Alert Safety System (PASS) devices. When activated a PASS device emits an alarm signal to notify others that a firefighter is in distress. However there have been notable instances where PASS devices have confused rescue personnel or created a more hazardous situation for instance when noise interference originating from other objects is involved. This research compiles data from various sources for example firefighter near miss reports and National Institute for Occupational Safety and Health (NIOSH) fatality reports regarding PASS device effectiveness. The research will investigate the causes of confusion and danger as well as take a look at the situations where the device achieved its goal and was able to save a life. The implications of discovering how interfering noises can render PASS devices ineffective could save several lives in the future and ultimately lead to increased firefighter safety.

Kyle Ford; Mudeer Habeeb; Joelle Suits; Mustafa Abbasi; Ofodike Ezekoye

2013-01-01T23:59:59.000Z

12

E-Print Network 3.0 - automatic alarm dosimeter Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

systems, and emergency lights. Firewatch... or to the fire alarm annunciatorcontrol panel for fire alarm systems. ... Source: Karsai, Istvan - Department of Biological...

13

Xcel Energy implements an alarm management strategy  

SciTech Connect

Not so long ago, Xcel Energy's Pawnee Station, a 505 MW coal-fired generating station in Brush, Colorado, USA was commonly generating 300 to 400 alarms per 8-hour shift. The article describes how the alarm system was revised and improved by tackling alarm dead-bands, and rationalising alarms for routine events. Operators are trained to understand the functions of alarm management components, their use and response, and obtain feedback. Today the power station reports about one alarm per hour. 3 photos.

Bass, J.; Abreu, G. [Xcel Energy (United States)

2007-11-15T23:59:59.000Z

14

STANFORD TOXIC GAS ALARM SYSTEMS 6 September 1999  

E-Print Network (OSTI)

to the Fire Alarm outputs if the TGO Alarm is activated. 11. If a bunker is separate from a building, during a bunker evacuation, only the bunker will be evacuated. G a s S h u t d o w n L a b G a s S h u t d o w n L

15

E-Print Network 3.0 - alarm systems Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

Location Fire Alarm Panel Location KnoxRetainer Box... Key Holder Office Phone Home Phone Cell ... Source: Texas A&M University, Institute for Applied Mathematics and...

16

SUBSURFACE VISUAL ALARM SYSTEM ANALYSIS  

SciTech Connect

The ''Subsurface Fire Hazard Analysis'' (CRWMS M&O 1998, page 61), and the document, ''Title III Evaluation Report for the Surface and Subsurface Communication System'', (CRWMS M&O 1999a, pages 21 and 23), both indicate the installed communication system is adequate to support Exploratory Studies Facility (ESF) activities with the exception of the mine phone system for emergency notification purposes. They recommend the installation of a visual alarm system to supplement the page/party phone system The purpose of this analysis is to identify data communication highway design approaches, and provide justification for the selected or recommended alternatives for the data communication of the subsurface visual alarm system. This analysis is being prepared to document a basis for the design selection of the data communication method. This analysis will briefly describe existing data or voice communication or monitoring systems within the ESF, and look at how these may be revised or adapted to support the needed data highway of the subsurface visual alarm. system. The existing PLC communication system installed in subsurface is providing data communication for alcove No.5 ventilation fans, south portal ventilation fans, bulkhead doors and generator monitoring system. It is given that the data communication of the subsurface visual alarm system will be a digital based system. It is also given that it is most feasible to take advantage of existing systems and equipment and not consider an entirely new data communication system design and installation. The scope and primary objectives of this analysis are to: (1) Briefly review and describe existing available data communication highways or systems within the ESF. (2) Examine technical characteristics of an existing system to disqualify a design alternative is paramount in minimizing the number of and depth of a system review. (3) Apply general engineering design practices or criteria such as relative cost, and degree of difficulty and complexity in determining requirements in adapting existing data communication highways to support the subsurface visual alarm system. These requirements would include such things as added or new communication cables, added Programmable Logic Controller (PLC), Inputs and Outputs (I/O), and communication hardware components, and human machine interfaces and their software operating system. (4) Select the best data communication highway system based on this review of adapting or integrating with existing data communication systems.

D.W. Markman

2001-08-06T23:59:59.000Z

17

Fire  

NLE Websites -- All DOE Office Websites (Extended Search)

Fire Fire Nature Bulletin No. 51 Febraury 1, 1946 Forest Preserve District of Cook County Clayton F. Smith, President Roberts Mann, Superintendent of Conservation FIRE Most people firmly believe the ancient notion that the prairies and vacant lots should be burnt off "to make better grass." Many are doing so now. Boys who have seen their parents and neighbors kindling fires on vacant property frequently do likewise on the prairies. Recently there have been four fires in the forest preserves which spread from adjoining land. Burning does more harm than good. True, it gets rid of the old weed stalks and dried grass of last year, so that new grass shows green more quickly. But repeated burnings kill the good, nutritious grasses such as bluegrass, timothy and clover. The wildflowers disappear. All food and nesting cover for birds, rabbits and other wildlife is destroyed, just when they need it most. Thistles thrive. Only tough grasses of little value for pasture or hay, such as crabgrass and quackgrass, and the weeds survive.

18

Fire Classifications Fires involving the ordinary  

E-Print Network (OSTI)

, plastics, etc. Fires involving combustible or flammable liquids such as gasoline, kerosene, oils, grease is protected by various devices such as smoke detectors, sprinkler systems, and manual fire alarm pull stations. Manual pull stations are strategically located throughout the University. Usually located by each exit

Jia, Songtao

19

HSL Fire Evacuation Plan HSL Appendix 1  

E-Print Network (OSTI)

to the assembly point ( in the car park opposite the side entrance of the library). All tag holders need to give should 7. Staff should remain at the Assembly point (by the wooden fence in the car park opposite/alarm, staff should report any shortcomings in the fire safety provision (e.g. defective fire alarm sounders

Anderson, Jim

20

Substation alarm multiplexing system (SAMS)  

SciTech Connect

This paper describes an on going R&D project to develop, design, install, and assess the field performance of an advanced substation alarm system. SAMS provides a highly fault-tolerant system for the reporting of equipment alarms. SAMS separates and identifies each of the multiple alarm contacts, transmits an alarm condition over existing substation two-wire system, and displays the alarm source, and its associated technical information, on a touch-screen monitor inside the substation control room, and a remote central location and on a hand held terminal which may be carried anywhere within the substation. SAMS is currently installed at the Sherman Creek substation in the Bronx for the purpose of a three month field evaluation.

ElBadaly, H.; Gaughan, J.; Ward, G.; Amengual, S.

1996-03-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


21

Annual Fire Report Page 1 of 4 Residence Hall/Historic Houses Fire Protection Equipment  

E-Print Network (OSTI)

Annual Fire Report Page 1 of 4 Residence Hall/Historic Houses Fire Protection Equipment 2012 Residence Hall/Historic Houses Fire Protection Equipment 2012 Calendar Year 24 Bull Street Annex-House X X X Calendar Year College of Charleston Residence Halls and Historic Housing Facilities Fire alarm monitoring

Kasman, Alex

22

Functional relationship-based alarm processing system  

DOE Patents (OSTI)

A functional relationship-based alarm processing system and method analyzes each alarm as it is activated and determines its relative importance with other currently activated alarms and signals in accordance with the functional relationships that the newly activated alarm has with other currently activated alarms. Once the initial level of importance of the alarm has been determined, that alarm is again evaluated if another related alarm is activated or deactivated. Thus, each alarm's importance is continuously updated as the state of the process changes during a scenario. Four hierarchical relationships are defined by this alarm filtering methodology: (1) level precursor (usually occurs when there are two alarm settings on the same parameter); (2) direct precursor (based on causal factors between two alarms); (3) required action (system response or action expected within a specified time following activation of an alarm or combination of alarms and process signals); and (4) blocking condition (alarms that are normally expected and are not considered important). The alarm processing system and method is sensitive to the dynamic nature of the process being monitored and is capable of changing the relative importance of each alarm as necessary. 12 figs.

Corsberg, D.R.

1988-04-22T23:59:59.000Z

23

The Best Ever Alarm System Toolkit  

SciTech Connect

Learning from our experience with the standard Experimental Physics and Industrial Control System (EPICS) alarm handler (ALH) as well as a similar intermediate approach based on script-generated operator screens, we developed the Best Ever Alarm System Toolkit (BEAST). It is based on Java and Eclipse on the Control System Studio (CSS) platform, using a relational database (RDB) to store the configuration and log actions. It employs a Java Message Service (JMS) for communication between the modular pieces of the toolkit, which include an Alarm Server to maintain the current alarm state, an arbitrary number of Alarm Client user interfaces (GUI), and tools to annunciate alarms or log alarm related actions. Web reports allow us to monitor the alarm system performance and spot deficiencies in the alarm configuration. The Alarm Client GUI not only gives the end users various ways to view alarms in tree and table, but also makes it easy to access the guidance information, the related operator displays and other CSS tools. It also allows online configuration to be simply modified from the GUI. Coupled with a good "alarm philosophy" on how to provide useful alarms, we can finally improve the configuration to achieve an effective alarm system.

Kasemir, Kay [ORNL; Chen, Xihui [ORNL; Danilova, Katia [ORNL

2009-01-01T23:59:59.000Z

24

Intelligent Economic Alarm Processor (IEAP)  

E-Print Network (OSTI)

): ?The 21st Substation Design?, and ??Verifying Interoperability and Application Performance of PMUs and PMU-enabled IEDs at the Device and System Level?. The fourth one is funded by Advanced Research Agency- Energy (ARPA-E) through Green Electricity... .......................................................................................................... 52? 4. USE OF SUBSTATION IED DATA TO IMPROVE ALARM PROCESSING ........ 53? 4.1? Introduction ...................................................................................................... 53? 4.2? Substation IED Data...

Guan, Yufan

2013-08-06T23:59:59.000Z

25

HOME INSECURITY: NO ALARMS, FALSE ALARMS, AND SIGINT  

SciTech Connect

The market share of home security systems has substantially increased as vendors incorporate more desirable features: intrusion detection, automation, wireless, and LCD touch panel controls. Wireless connectivity allows vendors to manufacture cheaper, more featureful products that require little to no home modification to install. Consumer win, since adding devices is easier. The result: an ostensibly more secure, convenient, and connected home for a larger number of citizens. Sadly, this hypothesis is flawed; the idea of covering a home with more security sensors does not translate into a more secure home. Additionally, the number of homes using these vulnerable systems is large, and the growth rate is increasing producing a even larger problem. In this talk, I will demonstrate a generalized approach for compromising three systems: ADT, the largest home security dealer in North America; Honeywell, one of the largest manufacturers of security devices; and Vivint, a top 5 security dealer. We will suppress alarms, create false alarms, and collect artifacts that facilitate tracking the movements of individuals in their homes.

Lamb, Logan M [ORNL

2014-01-01T23:59:59.000Z

26

H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2010.doc Annual Fire Safety Report  

E-Print Network (OSTI)

. Building Sprinkler System? % Sprinkler Monitored Fire Alarm? Smoke Detection Extinguisher Devices Placards of vehicle parts, fuel and oil is prohibited. l. Hallways must remain clear at all times for safety in case Safety Systems The following table describes each on-campus residential facility fire safety system

Sze, Lawrence

27

Analysis of Fire Calls to an Industrial Complex Over a 12-year Period  

SciTech Connect

This paper gives an analysis of fire calls from over a decade of operations at a process facility. These data include valid alarms, unwanted or false alarms, ambulance calls, and hazardous material cleanup calls. Of special interest are false alarms, which are not only a nuisance to facility productivity but are detrimental to public and facility safety. Of the fire calls listed here, over half were from false alarms. The results given are compared to National Fire Protection Association data. The data presented can serve as exemplar data for future facilities and can be compared to other operating facilities experiences.

L. C. Cadwallader

2009-03-01T23:59:59.000Z

28

Reduction of fire hazards on large mining equipment  

SciTech Connect

Although standards and regulations are in place to prevent large mining equipment fires, recent analyses of mine accident data show that mining equipment fires still occur with alarming frequency and grave consequences, particularly at all surface mines and in underground metal/nonmetal mines. Recently technological advances in fire protection, combined with the statistical data on equipment fires, led NIOSH to reinvestigate this and to improve operator safety. NIOSH demonstrated that newly developed technologies, such as dual cab fire inerting systems and engine compartment fire barriers, can greatly enhance operator safety and lessen the damage of property during large mobile equipment fires. 10 refs., 5 figs.

Maria I. De Rosa

2008-09-15T23:59:59.000Z

29

Alarm Response Training | Y-12 National Security Complex  

NLE Websites -- All DOE Office Websites (Extended Search)

On Time: 4:04 min. View an introduction to our Alarm Response Training, which prepares and trains personnel responding to civilian nuclear and radiological security alarms...

30

Dynamic alarm presentation in a nuclear plant control room  

DOE Patents (OSTI)

The alarm activation set point and priority for a given, spatially fixed alarm tile can vary depending in part on the mode of plant operation.

Kenneth, Scarola (Windsor, CT); Jamison, David S. (Windsor, CT); Manazir, Richard M. (North Canton, CT); Rescorl, Robert L. (Vernon, CT); Harmon, Daryl L. (Enfield, CT)

1994-01-01T23:59:59.000Z

31

Alarm acknowledgement in a nuclear plant control room  

DOE Patents (OSTI)

Alarm acknowledgment can be made not only at the alarm tile array of a given console but via other touch sensitive alarm indications in the screen displays of the monitoring system at the same or other consoles; also, touching one tile can acknowledge multiple alarm sources.

Scarola, Kenneth (Windsor, CT); Jamison, David S. (Windsor, CT); Manazir, Richard M. (North Canton, CT); Rescorl, Robert L. (Vernon, CT); Harmon, Daryl L. (Enfield, CT)

1994-01-01T23:59:59.000Z

32

Pressurized security barrier and alarm system  

DOE Patents (OSTI)

A security barrier for placement across a passageway is made up of interconnected pressurized tubing made up in a grid pattern with openings too small to allow passage. The tubing is connected to a pressure switch, located away from the barrier site, which activates an alarm upon occurrence of a pressure drop. A reinforcing bar is located inside and along the length of the tubing so as to cause the tubing to rupture and set off the alarm upon an intruder`s making an attempt to crimp and seal off a portion of the tubing by application of a hydraulic tool. Radial and rectangular grid patterns are disclosed. 7 figures.

Carver, D.W.

1995-04-11T23:59:59.000Z

33

Door Placard for No Automatic Fire Alarm with Automatic Fire Sprinkler Protection System  

E-Print Network (OSTI)

apartment with wet towels or sheets, and seal air ducts or other openings where smoke may enter Open address, floor, apartment number and the number of people in your apartment Seal the doors to your

Pawlowski, Wojtek

34

Door Placard for Full Fire Alarm and Sprinkler Fire Code Compliance  

E-Print Network (OSTI)

apartment with wet towels or sheets, and seal air ducts or other openings where smoke may enter Open address, floor, apartment number and the number of people in your apartment Seal the doors to your

Pawlowski, Wojtek

35

Door Placard for Fire Alarm and No Sprinkler System Fire Code Compliance  

E-Print Network (OSTI)

apartment with wet towels or sheets, and seal air ducts or other openings where smoke may enter Open address, floor, apartment number and the number of people in your apartment Seal the doors to your

Pawlowski, Wojtek

36

calgary.ca/fire | call 3-1-1 Student Fire  

E-Print Network (OSTI)

or accidentally burning toast) Batteries are replaced yearly (ask the landlord when it was last done) Alarms can mean nobody, smokes in bed baSement Furnace and hot water tank are clear of stuff that can burn in planters, on grass, in peat moss or mulch (almost empty "beverage" cans work well) Fire pits

Habib, Ayman

37

Alarm system for a nuclear control complex  

DOE Patents (OSTI)

An advanced control room complex for a nuclear power plant, including a discrete indicator and alarm system (72) which is nuclear qualified for rapid response to changes in plant parameters and a component control system (64) which together provide a discrete monitoring and control capability at a panel (14-22, 26, 28) in the control room (10). A separate data processing system (70), which need not be nuclear qualified, provides integrated and overview information to the control room and to each panel, through CRTs (84) and a large, overhead integrated process status overview board (24). The discrete indicator and alarm system (72) and the data processing system (70) receive inputs from common plant sensors and validate the sensor outputs to arrive at a representative value of the parameter for use by the operator during both normal and accident conditions, thereby avoiding the need for him to assimilate data from each sensor individually. The integrated process status board (24) is at the apex of an information hierarchy that extends through four levels and provides access at each panel to the full display hierarchy. The control room panels are preferably of a modular construction, permitting the definition of inputs and outputs, the man machine interface, and the plant specific algorithms, to proceed in parallel with the fabrication of the panels, the installation of the equipment and the generic testing thereof.

Scarola, Kenneth (Windsor, CT); Jamison, David S. (Windsor, CT); Manazir, Richard M. (North Canton, CT); Rescorl, Robert L. (Vernon, CT); Harmon, Daryl L. (Enfield, CT)

1994-01-01T23:59:59.000Z

38

Using active database techniques for an advanced alarm processing  

SciTech Connect

An Advanced Alarm System (AAS) is primarily a digital system employing advanced alarm process logics and a VDU (Visual Display Unit) based control and display for the alarms. Active Database Systems (ADSs) are able to monitor a special situation represented by an event and one or more conditions. When the event occurs and the conditions are evaluated as true, the corresponding actions are executed. Hence, ADSs can recognize specific situations and react to them without direct explicit user or application requests. ADSs are very useful for timely applications such as the advanced, alarm processing. This paper proposes a new approach to the advanced alarm processing by using Event-Condition- Action(ECA) rules that can be automatically triggered by an active database. And this paper describes the design considerations and solution plan for advanced alarm processing by using active database techniques. (authors)

Jang, G. S. [I and C HFE Dept., Korea Atomic Energy Research Inst., 150, Duckjin-dong, Yusung-ku, Daejeon 305-353 (Korea, Republic of); Seong, D. H. [Samchang Enterprise Co., LTD, 974-1, Goyean-ri, Ulju-gun, Ulsan, 689-871 (Korea, Republic of); Keum, J. Y.; Park, H. Y. [I and C HFE Dept., Korea Atomic Energy Research Inst., 150, Duckjin-dong, Yusung-ku, Daejeon 305-353 (Korea, Republic of); Kim, Y. K. [Dept. of Computer Science, Chungnam National Univ., Daejeon, 305-764 (Korea, Republic of)

2006-07-01T23:59:59.000Z

39

Technical basis for setting Hanford Fire Department electronic dosimetry for emergency response (TBD-HSO-RC-009)  

SciTech Connect

This document addresses the need to establish a reasonable methodology for establishing alarm points for electronic dosimetry used by the Hanford Fire Department (HFD) for emergency response in radiological facilities.

EVANS, C.L.

2003-04-01T23:59:59.000Z

40

Allegations Regarding the Consolidation of Central Alarm Stations...  

Energy Savers (EERE)

Allegations Regarding the Consolidation of Central Alarm Stations at the Oak Ridge Reservation DOEIG-0929 December 2014 U.S. Department of Energy Office of Inspector General...

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


41

FIRE WATCH FORM University Fire Marshal  

E-Print Network (OSTI)

the Fire Code of New York State that pertain to the impairment of a fire protection system to the impairment of a fire protection system Fire Code of New York State Chapter-9 "Fire Protection Systems" 901.7 Systems out of service. Where a required fire protection system is out of service, the fire department

Pawlowski, Wojtek

42

Cold Vacuum Drying facility fire protection system design description (SYS 24)  

SciTech Connect

This document describes the Cold Vacuum Drying Facility (CVDF) fire protection system (FPS). The FPS provides fire detection, suppression, and loss limitation for the CVDF structure, personnel, and in-process spent nuclear fuel. The system provides, along with supporting interfacing systems, detection, alarm, and activation instrumentation and controls, distributive piping system, isolation valves, and materials and controls to limit combustibles and the associated fire loadings.

PITKOFF, C.C.

1999-07-06T23:59:59.000Z

43

E-Print Network 3.0 - alarm system analysis Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

(SAS) to monitor scientific equipment that is critical to ongoing... Equipment System (AES): The notebook found at various alarm panels Scientific Alarm System (SAS... ): The...

44

Fire Protection  

Directives, Delegations, and Requirements

This Standard was developed to provide acceptable methods and approaches for meeting DOE fire protection program and design requirements and to address special or unique fire protection issues at DOE facilities that are not comprehensively or adequately addressed in national consensus standards or other design criteria.

2012-12-05T23:59:59.000Z

45

Fire Egress  

NLE Websites -- All DOE Office Websites (Extended Search)

OSHAX.org - OSHAX.org - The Unofficial Guide To the OSHA 1 Introduction  Fires and explosions kill more than 200 and injure more than 5,000 workers each year  There is a long and tragic history of workplace fires in this country caused by problems with fire exits and extinguishing systems  OSHA requires employers to provide proper exits, fire fighting equipment, and employee training to prevent fire deaths and injuries in the workplace OSHAX.org - The Unofficial Guide To the OSHA 2 Exit Route  A continuous and unobstructed path of exit travel from any point within a workplace to a place of safety (including refuge areas)  Consists of three parts:  Exit access  Exit  Exit discharge OSHAX.org - The Unofficial Guide To the OSHA 3 Exit Routes Basic Requirements

46

Painterly fire  

Science Journals Connector (OSTI)

This sketch describes how to construct a painterly 'wall' of fire, one which exhibits realistic motion while managing to maintain an artistic look. Keywords: effects animation, natural phenomena, rendering

Saty Raghavachary; Fernando Benitez

2002-07-01T23:59:59.000Z

47

Fires - 1946  

NLE Websites -- All DOE Office Websites (Extended Search)

Fires - 1946 Fires - 1946 Nature Bulletin No. 85 September 28, 1946 Forest Preserve District of Cook County Clayton F. Smith, President Roberts Mann, Superintendent of Conservation FIRES - 1946 It happens every fall. Thousands of acres of vacant land are being burned-off: some of them because of matches, cigarettes or pipe dottle carelessly tossed aside along the highways and along the trails; some of them set afire by thoughtless boys; most of them deliberately burned by people who believe they will improve the crop of grass next year. That is stupid. And if you start a fire which burns over another person's property you are liable to arrest and heavy penalty, under the Illinois law, unless you have given that person proper notice of your intention. Fires harm -- they never help. The tough seeds and roots of the worthless grasses and weeds survive a fire but the good nutritious grasses and most wildflowers are killed. Further, all the winter food and cover for birds and other wildlife are destroyed.

48

Cold Vacuum Dryer (CVD) Facility Fire Protection System Design Description (SYS 24)  

SciTech Connect

This system design description (SDD) addresses the Cold Vacuum Drying (CVD) Facility fire protection system (FPS). The primary features of the FPS for the CVD are a fire alarm and detection system, automatic sprinklers, and fire hydrants. The FPS also includes fire extinguishers located throughout the facility and fire hydrants to assist in manual firefighting efforts. In addition, a fire barrier separates the operations support (administrative) area from the process bays and process bay support areas. Administrative controls to limit combustible materials have been established and are a part of the overall fire protection program. The FPS is augmented by assistance from the Hanford Fire Department (HED) and by interface systems including service water, electrical power, drains, instrumentation and controls. This SDD, when used in conjunction with the other elements of the definitive design package, provides a complete picture of the FPS for the CVD Facility.

SINGH, G.

2000-10-17T23:59:59.000Z

49

Nuclear-power-plant perimeter-intrusion alarm systems  

SciTech Connect

Timely intercept of an intruder requires the examination of perimeter barriers and sensors in terms of reliable detection, immediate assessment and prompt response provisions. Perimeter security equipment and operations must at the same time meet the requirements of the Code of Federal Regulations, 10 CFR 73.55 with some attention to the performance and testing figures of Nuclear Regulatory Guide 5.44, Revision 2, May 1980. A baseline system is defined which recommends a general approach to implementing perimeter security elements: barriers, lighting, intrusion detection, alarm assessment. The baseline approach emphasizes cost/effectiveness achieved by detector layering and logic processing of alarm signals to produce reliable alarms and low nuisance alarm rates. A cost benefit of layering along with video assessment is reduction in operating expense. The concept of layering is also shown to minimize testing costs where detectability performance as suggested by Regulatory Guide 5.44 is to be performed. Synthesis of the perimeter intrusion alarm system and limited testing of CCTV and Video Motion Detectors (VMD), were performed at E-Systems, Greenville Division, Greenville, Texas during 1981.

Halsey, D.J.

1982-04-01T23:59:59.000Z

50

FIRE PROTECTION IMPAIRMENTS University Fire Marshal  

E-Print Network (OSTI)

FIRE PROTECTION IMPAIRMENTS University Fire Marshal Guidance Document Approved by: R. Flynn Last revised by: R. Flynn Revision date: 08/18/2012 Fire Protection Impairments Page 1 of 1 This document contains excerpts from the Fire Code of New York State that pertain to the impairment of a fire protection

Pawlowski, Wojtek

51

Fire Protection  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

NOT MEASUREMENT NOT MEASUREMENT SENSITIVE DOE-STD-1066-2012 December 2012 _______________ Supersedes DOE-STD-1066-99 DOE STANDARD FIRE PROTECTION U.S. Department of Energy AREA FIRP Washington, DC 20585 DISTRIBUTION STATEMENT. Approved for public release; distribution is unlimited. This document is available on the Department of Energy Technical Standards Program Web page at http://www.hss.doe.gov/nuclearsafety/ns/techstds/ DOE-STD-1066-2012 FOREWORD This Department of Energy (DOE) Standard (STD) supersedes DOE-STD-1066-99 1 and is approved for use by DOE and its contractors. The following fire protection standard is canceled with the issuance of this Standard and appropriate technical content was incorporated into this Standard:  DOE-STD-1088-95, Fire Protection for Relocatable Structures

52

2009 Berea College Residence Hall Fire Protection Systems, Notification Systems and Fire Drill Data Berea College Fire Alarm Partial 1 Full 2 Smoke Fire Evacuations Evacuation  

E-Print Network (OSTI)

Lights Doors Anna Smith Yes Yes Yes Yes Yes 3 Yes Yes Bingham** Yes Yes *Yes* Yes Yes 2 Yes Yes Blue Yes 2 Yes Yes Edwards Yes Yes Yes Yes Yes 4 Yes No Estill Street No No Yes Yes Yes 1 Yes No Elizabeth

Baltisberger, Jay H.

53

Rawls' Fairness, Income Distribution and Alarming Level of Gini Coefficient  

E-Print Network (OSTI)

The argument that the alarming level of Gini coefficient is 0.4 is very popular, especially in the media industry, all around the world for a long time. Although the 0.4 standard is widely accepted, the derivation of the value lacks rigid theoretical foundations. In fact, to the best of our knowledge, it is not based on any prevalent and convincing economic theories. In this paper, we incorporate Rawls' principle of fair equality of opportunity into Arrow-Debreu's framework of general equilibrium theory with heterogeneous agents, and derive the alarming level of Gini coefficient formally. Our theory reveals that the exponential distribution of income not only satisfies Pareto optimality, but also obeys social fairness in Rawls' sense. Therefore, we specify the maximal value of the Gini coefficient when income follows exponential distribution as a possible alarming level. Our computations show that the alarming level should be specified at least equal or larger than 0.5 rather than 0.4. We empirically investig...

Tao, Yong; Li, Changshuai

2014-01-01T23:59:59.000Z

54

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network (OSTI)

the Authoritarian Model: How Putin?s Crackdown Holds RussiaAuthoritarianism Under Putin, Demokratizatsiya: The Journal

Hart, Melanie M.

2010-01-01T23:59:59.000Z

55

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network (OSTI)

Wang?s factory was burning hazardous waste materials, China?waste materials, not the more stringent standards for factories burning (

Hart, Melanie M.

2010-01-01T23:59:59.000Z

56

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network (OSTI)

and standards for heavy metal pollution. The MEP passed aHandling of Heavy Metal Pollution on August 28, 2009.

Hart, Melanie M.

2010-01-01T23:59:59.000Z

57

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network (OSTI)

Hygiene] Law and cause food poisoning accidents or otherFood and Drug Administration (SFDA) traces the poisonouspoisonings were most likely a macro-level issue stemming from a wide variety of sources such as contaminated food,

Hart, Melanie M.

2010-01-01T23:59:59.000Z

58

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network (OSTI)

Ibid. Walker (2008). planned hydropower projects in Yunnanlands are expropriated for hydropower developments. In 2004to lose their lands for a hydropower project on the Nujiang

Hart, Melanie M.

2010-01-01T23:59:59.000Z

59

Door Placard for No Automatic Fire Alarm and No Sprinkler System  

E-Print Network (OSTI)

apartment with wet towels or sheets, and seal air ducts or other openings where smoke may enter Open address, floor, apartment number and the number of people in your apartment Seal the doors to your

Pawlowski, Wojtek

60

Trottier BuildingTrottier Building Fire SafetyFire Safety  

E-Print Network (OSTI)

building 1.1. Fire SafetyFire Safety 2.2. Fire Protection equipmentFire Protection equipment 3 OfficersFire Prevention Officers #12;Trottier BuildingTrottier Building Fire ProtectionFire Protection#12;Trottier BuildingTrottier Building Fire SafetyFire Safety in Trottier buildingin Trottier

Pientka, Brigitte

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


61

E-Print Network 3.0 - alarm processing system Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

the Management of Multi-Layered Networks Summary: on the definition of alarms that can enter the system. Therefore, three alarm categories are created based... with a single-layer...

62

E-Print Network 3.0 - alarm system commercial Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

the Management of Multi-Layered Networks Summary: on the definition of alarms that can enter the system. Therefore, three alarm categories are created based... with a single-layer...

63

E-Print Network 3.0 - advanced alarm systems Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

the Management of Multi-Layered Networks Summary: on the definition of alarms that can enter the system. Therefore, three alarm categories are created based... with a single-layer...

64

Annual Fire Safety Report  

E-Print Network (OSTI)

2010 Annual Fire Safety Report University of California, Irvine HIGHER EDUCATION OPPORTUNITY to the Fire Safety in Student Housing Buildings of current or perspective students and employees be reported publish an annual fire safety report, keep a fire log, and report fire statistics to the Secretary

Loudon, Catherine

65

Fire Safety January 2011  

E-Print Network (OSTI)

1 Fire Safety PROCEDURES January 2011 firesafety@uwo.ca Campus Phones ­ EMERGENCY ­ Dial 911 Fire Safety Service is the focal point for the coordinated administration of the University Fire Safety Prevention and Fire Safety to minimize the risk of injury or loss of life or property due to fire

Lennard, William N.

66

Preventing Laboratory FiresPreventing Laboratory Fires AgendaAgenda  

E-Print Network (OSTI)

.contents. #12;Laboratory Fire CodeLaboratory Fire Code RegulationsRegulations #12;National Fire ProtectionNational Fire Protection Association (NFPA)Association (NFPA) NFPA 1NFPA 1 ­­ General Protection against FireGeneral Protection against Fire NFPA 10NFPA 10 ­­ Fire ExtinguishersFire Extinguishers NFPA 30NFPA 30 ­­ Flammable

Farritor, Shane

67

Fire Safety Training: Fire Modeling- NUREG 1934  

Energy.gov (U.S. Department of Energy (DOE))

Presenter: Frederick W. Mowrer, Ph.D., P.E. Director Fire Protection Engineering Programs - Cal Poly SLO

68

Stone Fire  

NLE Websites -- All DOE Office Websites (Extended Search)

Effect of Change in Cookstove Types on Visibility - Case Study of the Berkeley-Darfur Stove and Three- Stone Fire Extended Abstract #1 Yungang Wang, Ashok J. Gadgil, Thomas W. Kirchstetter Environmental Energy Technologies Division Indoor Environment Group Lawrence Berkeley National Laboratory Berkeley, CA September 2012 This publication was made possible by grant number 500-99-013 from the California Energy Commission (CEC). This work was also supported by the Assistant Secretary for Energy Efficiency and Renewable Energy, Building Technologies Program of the U.S. Department of Energy under contract DE- AC02- 05CH11231. LBNL-6291E LBNL-6291E Disclaimer This document was prepared as an account of work sponsored by the United States

69

FIRE PROTECTION ENGINEERING  

E-Print Network (OSTI)

FIRE PROTECTION ENGINEERING FPE College of Engineering California Polytechnic State University San problems and develop fire safety design solutions in a variety of professional settings. Fire Protection Engineering Science � Apply concepts associated with the thermal sciences, to the analysis of fire protection

Sze, Lawrence

70

FIRE PROTECTION ENGINEERING  

E-Print Network (OSTI)

FIRE PROTECTION ENGINEERING FPE College of Engineering California Polytechnic State University San and develop fire safety design solutions in a variety of professional settings. Fire Protection Engineering Science · Apply concepts associated with the thermal sciences, to the analysis of fire protection

Sze, Lawrence

71

E-Print Network 3.0 - alarm processing techniques Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

TASA Summary: relationships of the alarms into account. 2.2. TASA methodology A KDD process, adapted from 11, consists of: 1... Interactive exploration of interesting...

72

E-Print Network 3.0 - alarm system verification Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

City Collection: Mathematics 11 Sensitivity Analysis of the JPALS Shipboard Relative GPS Measurement Summary: unnecessarily, increasing the false alarm rate and adversely...

73

Testing and Evaluation Protocol for Alarming Personal Radiation Detectors for Homeland Security  

E-Print Network (OSTI)

Testing and Evaluation Protocol for Alarming Personal Radiation Detectors for Homeland Security T................................................................................1 4. Test and evaluation steps .........................................................................................1 5. Recording test results

74

Fire Protection Program  

NLE Websites -- All DOE Office Websites (Extended Search)

Program Program Fire Protection Overview The Department of Energy (DOE) Fire Protection Program is multi-faceted. It includes published fire safety directives (Orders, standards, and guidance documents), a range of oversight activities, an annual fire protection program summary, and a directory of fire safety professionals. DOE also sponsors fire safety conferences, various training initiatives, and a spectrum of technical assistance activities. This Home Page is intended to bring together in one location as much of the Program's resources as possible to facilitate greater understanding, communication, and efficiency of operations. Guidelines -- NFPA Codes and standards, CFRs, and DOE Directives (policy statements, Orders, Standards, and Guidance Documents)

75

Stochastic Representation of Fire Behavior in a Wildland Fire Protection  

E-Print Network (OSTI)

Stochastic Representation of Fire Behavior in a Wildland Fire Protection Planning Model on wildland fire used by the California Department of Forestry and Fire Protection. Fire rate of spread (ROS. S IMULATIONMODELSOFINITIALATTACKonwildland fireare important tools for wildland fire protection planning, and several new models have been

Fried, Jeremy S.

76

A hybrid intelligent system for alarm processing in power distribution substations  

Science Journals Connector (OSTI)

This application paper presents an intelligent system for alarm processing and fault location in power substations. A hybrid model is constructed using rule-based systems and an artificial neural network. Incoming alarms are initially handled by an input ... Keywords: Expert systems, fault location, neural networks

J. C. Stacchini de Souza; M. B. Do Coutto Filho; R. S. Freund

2010-04-01T23:59:59.000Z

77

Fire Protection Related Sites  

Energy.gov (U.S. Department of Energy (DOE))

Fire Protection related sites for Department of Energy, Non-DOE Government and Non-Government information.

78

Substation fire protection features  

SciTech Connect

This paper describes Commonwealth Edison`s (ComEd) approach to substation fire protection. Substation fires can have a major operational, financial, as well as political impact on a utility. The overall Company philosophy encompasses both active and passive fire protection features to provide prompt detection, notification, and confinement of fire and its by-products. Conservatively designed smoke detection systems and floor and wall penetration seals form the backbone of this strategy. The Company has implemented a program to install these features in new and existing substations. Thus far these measures have been successful in mitigating the consequences of substation fires.

Hausheer, T.G. [Commonwealth Edison Co., Chicago, IL (United States)

1995-10-01T23:59:59.000Z

79

Wildland Fire Management Program  

NLE Websites -- All DOE Office Websites (Extended Search)

Significant Wildland Fire Potential Outlook Significant Wildland Fire Potential Outlook Predictive Services National Interagency Fire Center Issued: June 1, 2013 Next Issuance: July 1, 2013 Outlook Period - June, July and August through September Executive Summary The June, July and August through September 2013 significant wildland fire potential forecasts included in this outlook represent the cumulative forecasts of the eleven Geographic Area Predictive Services Units and the National Predictive Services Unit. June - Significant fire potential will be above normal for much of the interior mountains and foothills of California, the Sacramento Valley, and adjacent lower foothills as well as the coastal areas. - Significant fire potential will increase to above normal in Arizona, western New Mexico, and far

80

E-Print Network 3.0 - alarming oxygen depletion Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

protecting life on Earth (1). In 1985, scientists and the public became alarmed when Farman et al. (2... studies (5-8). These studies showed that ozone depletion has a large...

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


81

E-Print Network 3.0 - alarm border monitoring Sample Search Results  

NLE Websites -- All DOE Office Websites (Extended Search)

deployed at U.S. ports of entry. Due... to the occurrence of nuisance alarms based on naturally occurring radioactive material and the low base rate of nu Source: Parasuraman, Raja...

82

FIRE MANAGEMENT PLAN MONTAGUE PLAIN  

E-Print Network (OSTI)

FIRE MANAGEMENT PLAN FOR MONTAGUE PLAIN WILDLIFE MANAGEMENT AREA #12;Fire Management Plan for Montague Plain Wildlife Management Area prepared for Massachusetts Dept. of Fisheries, Wildlife. 2003. Fire Management Plan for Montague Plain Wildlife Management Area. Department of Natural Resources

Schweik, Charles M.

83

H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2013.doc Annual Fire Safety Report  

E-Print Network (OSTI)

and Fire Protection (Cal Fire) responds to the State Response Area of campus, including the outlyingH:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2013.doc Annual Fire Safety #12;H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2013.doc Fire and Life

Sze, Lawrence

84

H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2012.doc Annual Fire Safety Report  

E-Print Network (OSTI)

and Fire Protection (Cal Fire) responds to the State Response Area of campus, including the outlyingH:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2012.doc Annual Fire Safety #12;H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2012.doc Fire and Life

Sze, Lawrence

85

SILENE Benchmark Critical Experiments for Criticality Accident Alarm Systems  

SciTech Connect

In October 2010 a series of benchmark experiments was conducted at the Commissariat a Energie Atomique et aux Energies Alternatives (CEA) Valduc SILENE [1] facility. These experiments were a joint effort between the US Department of Energy (DOE) and the French CEA. The purpose of these experiments was to create three benchmarks for the verification and validation of radiation transport codes and evaluated nuclear data used in the analysis of criticality accident alarm systems (CAASs). This presentation will discuss the geometric configuration of these experiments and the quantities that were measured and will present some preliminary comparisons between the measured data and calculations. This series consisted of three single-pulsed experiments with the SILENE reactor. During the first experiment the reactor was bare (unshielded), but during the second and third experiments it was shielded by lead and polyethylene, respectively. During each experiment several neutron activation foils and thermoluminescent dosimeters (TLDs) were placed around the reactor, and some of these detectors were themselves shielded from the reactor by high-density magnetite and barite concrete, standard concrete, and/or BoroBond. All the concrete was provided by CEA Saclay, and the BoroBond was provided by Y-12 National Security Complex. Figure 1 is a picture of the SILENE reactor cell configured for pulse 1. Also included in these experiments were measurements of the neutron and photon spectra with two BICRON BC-501A liquid scintillators. These two detectors were provided and operated by CEA Valduc. They were set up just outside the SILENE reactor cell with additional lead shielding to prevent the detectors from being saturated. The final detectors involved in the experiments were two different types of CAAS detectors. The Babcock International Group provided three CIDAS CAAS detectors, which measured photon dose and dose rate with a Geiger-Mueller tube. CIDAS detectors are currently in use at Y-12 in the newly constructed Highly Enriched Uranium Materials Facility. The second CAAS detector used a {sup 6}LiF TLD to absorb neutrons and a silicon detector to count the charge particles released by these absorption events. Lawrence Livermore National Laboratory provided four of these detectors, which had formerly been used at the Rocky Flats facility in the United States.

Miller, Thomas Martin [ORNL] [ORNL; Reynolds, Kevin H. [Y-12 National Security Complex] [Y-12 National Security Complex

2011-01-01T23:59:59.000Z

86

856 IEEE TRANSACTIONS ON SYSTEMS, MAN, AND CYBERNETICS--PART C: APPLICATIONS AND REVIEWS, VOL. 38, NO. 6, NOVEMBER 2008 Designing Effective Alarms for Radiation Detection  

E-Print Network (OSTI)

to the occurrence of nuisance alarms based on naturally occurring radioactive material and the low base rate of nu Naturally occurring radioactive material. p(false alarm) Probability of a false alarm. p(hit) Probability, NO. 6, NOVEMBER 2008 Designing Effective Alarms for Radiation Detection in Homeland Security

Parasuraman, Raja

87

P\\procedure\\EH&S#2 Page 1 of 3 TITLE: BOCA RATON CAMPUS FIRE ALARM POLICY ACCESS AND RESPONSE  

E-Print Network (OSTI)

only authorized personnel have access to the systems. Provide training and guidelines about and repairs. UNIVERSITY POLICE Operate and maintain the Proprietary Monitoring Station. Assign trained of University operations. Objectives include: A well-designed service program with optimum productivity

Fernandez, Eduardo

88

Fire science at LLNL: A review  

SciTech Connect

This fire sciences report from LLNL includes topics on: fire spread in trailer complexes, properties of welding blankets, validation of sprinkler systems, fire and smoke detectors, fire modeling, and other fire engineering and safety issues. (JEF)

Hasegawa, H.K. (ed.)

1990-03-01T23:59:59.000Z

89

Subsurface Fire Hazards Technical Report  

SciTech Connect

The results from this report are preliminary and cannot be used as input into documents supporting procurement, fabrication, or construction. This technical report identifies fire hazards and proposes their mitigation for the subsurface repository fire protection system. The proposed mitigation establishes the minimum level of fire protection to meet NRC regulations, DOE fire protection orders, that ensure fire containment, adequate life safety provisions, and minimize property loss. Equipment requiring automatic fire suppression systems is identified. The subsurface fire hazards that are identified can be adequately mitigated.

Logan, R.C.

1999-09-27T23:59:59.000Z

90

Flooding and Fire Ants  

E-Print Network (OSTI)

Fire ants can be a serious problem during and after a flood. This publication explains how to protect yourself when you must return to flooded structures or deal with storm debris....

Nester, Paul

2008-08-05T23:59:59.000Z

91

Safety, Security & Fire Report  

E-Print Network (OSTI)

2013 Safety, Security & Fire Report Stanford University #12;Table of Contents Public Safety About the Stanford University Department of Public Safety Community Outreach & Education Programs Emergency Access Transportation Safety Bicycle Safety The Jeanne Clery and Higher Education Act Timely Warning

Straight, Aaron

92

Hanford Site Fire June 2000 AM  

SciTech Connect

The Hanford Site Fire on the morning of June 29, 2000. Fire crews working to contain a fire on the Hanford Site in June 2000.

2000-06-29T23:59:59.000Z

93

Ignition and spread of electrical wire fires  

E-Print Network (OSTI)

Airplane fires; (b) Nuclear power plant fires; (c) Chemicalignition sources in nuclear power plants: statistical,number of fire cases in nuclear power plants (NPP) [2]. Most

Huang, Xinyan

2012-01-01T23:59:59.000Z

94

Fire Simulation, Evacuation Analysis and Proposal of Fire Protection Systems Inside an Underground Cavern  

E-Print Network (OSTI)

Fire Simulation, Evacuation Analysis and Proposal of Fire Protection Systems Inside an Underground Cavern

Stella, Carlo

95

False Alarms and Close Calls: A Conceptual Model of Warning Accuracy LINDSEY R. BARNES*  

E-Print Network (OSTI)

of the key metrics for verifying National Weather Service (NWS) weather warnings. The national FAR, Health, & Hazards Center, Colorado Springs, Colorado Submitted to Weather and Forecasting Forecasters. In addition, we argue that the metrics used to evaluate false alarms do not accurately represent the numbers

Schultz, David

96

IE 361 Module 14 Patterns on Control Charts and "Special Checks"/Extra Alarm Rules  

E-Print Network (OSTI)

3.4 of Statistical Quality Assurance Methods for Engineers Prof. Steve Vardeman and Prof. Max MorrisIE 361 Module 14 Patterns on Control Charts and "Special Checks"/Extra Alarm Rules Reading: Section equipment or a clear change in the quality of a raw material

Vardeman, Stephen B.

97

Fire Test of Profile Plank for Transformer Pit Fire Protection  

Science Journals Connector (OSTI)

In general it is recommended to fill a transformer pit with rock ballast to extinguish the fire if there is a leakage of burning transformer oil. There is a lack of ... design of solutions for fire extinguishment...

Johan Lindstrm; Michael Frsth

2014-05-01T23:59:59.000Z

98

Emergency, Fire Information  

NLE Websites -- All DOE Office Websites (Extended Search)

Emergency, Fire Information Emergency, Fire Information Emergency, Fire Information Protecting our people, emergency personnel, national security information, facilities, lands, and neighboring communities. Contact Communications Office (505) 667-7000 Email LANL Update (505) 667-6622 or (877) 723-4101 toll-free Emergency Public Information In the event of an emergency, Los Alamos National Laboratory will provide you with needed information here as it becomes available. The Los Alamos Site Office/Los Alamos National Laboratory Emergency Public Information Plan provides a framework for coordinated, accurate, and timely release of information to Laboratory employees, the news media, potentially affected members of the public, and other stakeholders. Want emergency news emailed to you? Subscribe here.

99

E-Print Network 3.0 - accident experience alarm Sample Search...  

NLE Websites -- All DOE Office Websites (Extended Search)

, accident investigation, indoor air quality, bloodborne pathogens, chemical safety, lockout-tagout, hot work... Campus Fires 11 12 Accident Reporting 14 Employee Accidents 15...

100

EHSO TRAINING CLASSES Fire Safety Program Training  

E-Print Network (OSTI)

EHSO TRAINING CLASSES Fire Safety Program Training 1. Fire Safety (60 minutes) Instruction includes an actual fire eperience. 2. Fire Extinguisher Training (30 minutes) A practical demonstration on actual burnable liquid fires. This practical extinguisher training is a critical portion of the fire

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


101

ANNUAL FIRE SAFETY RESIDENCE HALLS  

E-Print Network (OSTI)

protection systems. Documents in the following websites are referenced in the report: · www.fau.edu/facilities/EH&S/safety/fire evacuation procedures. · Inspecting, testing and maintaining fire protection systems in accordance with National Fire Protection Association (NFPA) standards. · Performing plan reviews and code consultation

Fernandez, Eduardo

102

Fire-Immune Cable  

Science Journals Connector (OSTI)

... A FACTORY, opened by Lord Ridley on October 12, for making fire-resist ing cable called 'Pyrotenax', marks a new development which promises to be of far-reaching ... -plate elements, which are made of resistance wire embedded in the oxide. 'Pyrotenax' cable has a copper conductor, magnesia insulation, and copper sheath. The new technique enables ...

1937-11-20T23:59:59.000Z

103

Technical aspects of the sigma factor alarm method in alpha CAMs  

SciTech Connect

Some test must be applied to the low-level count data from alpha continuous air monitors (CAMs) to determine if the count is statistically significant (i.e., different from background). The test should also automatically account for different levels of background (i.e., ambient radon progeny concentrations). The method should, in other words, be as sensitive as possible, automatically desensitize when required, but in such a manner as to not exceed a previously-chosen acceptable false-alarm rate.

Justus, Alan Lawrence [Los Alamos National Laboratory

2009-01-01T23:59:59.000Z

104

The design of an intrusion security system using digital processing for alarm indication  

E-Print Network (OSTI)

has been noise spikes in the diode. These spikes can easily cause a false alarm which is difficult to trace since it results from a sporadic, elec- tronic malfunction. General Electric, Amperex, and other concerned companies have made a great... is the requirement of multiple triggering of this one threshold. AMF Inc. , Alexandria, Virginia, has recently introduced an intricate signal processor with diode transistor logic and transistor transistor logic integrated circuits to handle intru- sion signals...

Holyoak, Joel Nelson

2012-06-07T23:59:59.000Z

105

Fire Protection Program: Summary  

NLE Websites -- All DOE Office Websites (Extended Search)

Summary Summary Since May 1950, an Annual Fire Protection Program Summary has been submitted by DOE's fire protection community. Currently, this report is required by section 5a.(8) of DOE Order 231.1. "Environment, Safety and Health Reporting." In 1999, an automation initiative was undertaken to streamline data collection and provide a more through review of DOE Reporting Element activities. This action resulted in the delayed publications of the CY 1999 and 2000 reports until 2002. It is now possible however to view all Annual Summary Reporting Element responses since 1991 at the Site, Operations, Lead Program Secretarial Office and Headquarters levels. Additionally, a build-in reference to other DOE reporting activities (CAIRS and ORPS) is available that allows Reporting Elements and managers the opportunity to review all fire protection events along previously mentioned categories. Reports listed below were generated from this application. To obtain a copy of the Annual Summary Application please contact Jim Bisker in the Office of Nuclear and Facility Safety Policy (EH-53) at (301)903-6542 or Jim Bisker.

106

Abstract B31: Collaborative breast health education addressing an alarming public health concern in the District of Columbia  

Science Journals Connector (OSTI)

...meeting-abstract Behavioral and Social Science Poster Presentations - Proffered Abstracts...B31: Collaborative breast health education addressing an alarming public health...Early Awareness is a breast health education program of Howard University Cancer...

Kimberly Higginbotham; Deon Regis; Lucile Adams-Campbell; Carla WIlliams; Wayne Frederick; Karen Peterson; Jasmine Greenamyer; Erica Childs; and Carolyn Aldige

2008-11-01T23:59:59.000Z

107

Lab and field estimates of active time of chemical alarm cues of a cyprinid fish and an  

E-Print Network (OSTI)

Lab and field estimates of active time of chemical alarm cues of a cyprinid fish and an amphipod., 1999; Stankowich, 2008), seismic (Gregory et al., 1986) and vibratory mechanostimuli (Kirchner et al

Wisenden, Brian D.

108

Effect Of False Alarm Rate On Pilot Use And Trust Of Automation Under Conditions Of Simulated High Risk  

E-Print Network (OSTI)

An experimental study was conducted to investigate the relationships between automation false alarm rate, human trust in automation, and human use of automation, specifically under conditions of simulated high risk. The ...

Cafarelli, Deborah

2010-11-05T23:59:59.000Z

109

Report Wildland Fire Area Hazard  

NLE Websites -- All DOE Office Websites (Extended Search)

Report Wildland Fire Area Hazard Report Wildland Fire Area Hazard Report Wildland Fire Area Hazard Report wildland fire area hazards or incidents that are non-life threatening only. Call 911 for all emergencies that require immediate assistance. How to report wildland fire hazard Use the following form to report any wildland fire area hazards or incidents that are non-life threatening only. Call 911 for all emergencies that require immediate assistance. Fill out this form as completely as possible so we can better assess the hazard. All submissions will be assessed as promptly as possible. For assistance with a non-emergency situation, contact the Operations Support Center at 667-6211. Name (optional): Hazard Type (check one): Wildlife Sighting (check box if animal poses serious threat) Trails (access/egress)

110

Date ______________________ New York City Fire Department  

E-Print Network (OSTI)

familiar with the fire protection and fire suppression systems in the premises where heDate ______________________ New York City Fire Department Bureau of Fire Prevention 9 Metro received training in 3RCNY §10-01, Fire Code Sections 2701 - 2703 & 2706, the New C-14 study material

Jia, Songtao

111

ANNUAL SECURITY FIRE SAFETY REPORT  

E-Print Network (OSTI)

ANNUAL SECURITY AND FIRE SAFETY REPORT OCTOBER 1, 2013 DARTMOUTH COLLEGE http................................................................................................................................................................... 7 ANNUAL SECURITY REPORT........................................................................................................................9 PREPARATION OF THE REPORT AND DISCLOSURE OF CRIME STATISTICS

112

Fire and Ice Issue 9  

E-Print Network (OSTI)

s FIRE AND ICE # 9 IB FIRE ICE #9 A Blake/Avon slash fanzine r Available from: Kathleen Resch POBox 1766 Temple City, CA 91780 Kathleener@aol.com FIRE AND ICE # 9copyright May, 2005 by Kathleen Resch for the contributors. No reprints... or reproduction without the written permission ofthe author/artist This is an amateur publication and is not p intended to infringe upon the rights ofany holders of"Blake's 7" copyrights. FIRE AND ICE 9 TABLE OF CONTENTS LEAVING ROOM 101 by Nova 2 TOO MANY...

Multiple Contributors

2005-01-01T23:59:59.000Z

113

Design of the Wireless Temperature Measurement Alarming System in the High-Voltage Transformer Substation  

Science Journals Connector (OSTI)

Due to electric power overload and equipment aging, fire and explosion occur at transmission circuitry joints in high-voltage transformer substation caused by high temperatures accumulated at these...

Qiang Gao; Hongli Wang; Huaxiang Wang

2008-01-01T23:59:59.000Z

114

Fire Lane must Fire Lane must be kept clear  

E-Print Network (OSTI)

#12;#12; Fire Lane must Fire Lane must be kept clear at all timesa a es #12; Emergency Egress Keep Safety Data Sheets #12; Safety glasses Safety goggles Face shield #12; Eye protection Skin protection Spectators protection from the light energygy #12; Safety glasses are required when any machinery

Asaithambi, Asai

115

Fire Safety Committee Meeting Minutes- May 2014  

Energy.gov (U.S. Department of Energy (DOE))

DOE Fire Safety Committee Meeting Minutes, May, 2014 Topics included discussions on Fire modeling, revisions to DOE regulations and other important items relating to DOE and Fire Safety Community.

116

MARGINAL VALUATION OF FIRE EFFECTS  

E-Print Network (OSTI)

in the planning unit's land, resource and fire management plans. These goals and objectives can assist you with identifying the resources that are important to protect or improve through fire management activities. As you and cultural attributes of the landscape that have value. Defining the resource considered for value change 2

117

WHC fire hazards analysis policy  

SciTech Connect

The purpose of this document is to establish the fire protection policy for Westinghouse Hanford Company (WHC) relative to US Department of Energy (DOE) directives for Fire Hazards Analyses (FHAs) and their relationship to facility Safety Analysis Reports (SARs) as promulgated by the DOE Richland Operations Office.

Evans, C.B.

1994-04-01T23:59:59.000Z

118

ANNUAL SECURITY & FIRE SAFETY REPORT  

E-Print Network (OSTI)

ANNUAL SECURITY & FIRE SAFETY REPORT 2014 A guide to policies, procedures, practices, and programs implemented to keep students, faculty, and staff safe and facilities secure. www.montana.edu/reports/security.pdf #12;Inside this Report 2014 Annual Security and Fire Safety Report for Reporting Year 2013

Maxwell, Bruce D.

119

LNG facilities Engineered fire protection systems  

Science Journals Connector (OSTI)

Dry chemical fire extinguishers used in conjunction with high expansion foam have been used successfully in tests to extinguish LNG spill fires.

Kenneth Zuber

1976-02-01T23:59:59.000Z

120

BlueFire Ethanol | Department of Energy  

Office of Energy Efficiency and Renewable Energy (EERE) Indexed Site

BlueFire Ethanol BlueFire Ethanol Construct and operate a facility that converts green waste and lignocellulosic fractions diverted from landfills or Southern California Materials...

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


121

Fire hazards analysis of central waste complex  

SciTech Connect

This document analyzes the fire hazards associated with operational the Central Waste Complex. It provides the analysis and recommendations necessary to ensure compliance with applicable fire codes.

Irwin, R.M.

1996-05-30T23:59:59.000Z

122

New Buildings at the Fire Research Station  

Science Journals Connector (OSTI)

... THE new buildings of the Fire Research Station A of the Joint Fire Research Organization of the Department ... chemicals will be studied in the new chemical engineering laboratory.

D. I. LAWSON

1961-01-14T23:59:59.000Z

123

fire & fuels management Spruce Beetle-Induced Changes to Engelmann  

E-Print Network (OSTI)

. Keywords: crown fire, bark beetles, heat of combustion, fire behavior, time to ignition E ngelmann spruce

124

Remote keyless entry honking, convenience horn honking, and audible car alarms: redundancies and quieter options  

Science Journals Connector (OSTI)

Vehicle sound emissions car alarms and horn honking are the subject of many noise complaints. Auto manufacturers spent years engineering quieter vehicles and have created cars whose approach is so subtle that they pose a danger to blind pedestrians. But while engine noise has decreased and car alarms are less reactive horn honking that is linked with remote keyless entry (RKE) technology increasingly contributes to community noise. RKE horn noise has never been the subject of public health inquiry. In scientific literature discussion of road noise and health does not distinguish noise among separate sources and tends to measure aggregate ambient noise levels rather than impulsive noise. RKE horn noise violates state traffic laws and some local noise ordinances regarding horn use but there have been no legislative attempts to address the technology. This raises questions about whether political leaders and policy setters are not exposed to RKE noise or do not discern RKE sounds from traffic noise and are therefore unaware of it. Using available auto industry data and case studies this paper will introduce key facts about RKE horn use in the United States and Canada reviewing new technologies that render noisy counterparts still in use as redundant.

Jeanine Botta

2013-01-01T23:59:59.000Z

125

Remote keyless entry honking, convenience horn honking, and audible car alarms: Redundancies and quieter options  

Science Journals Connector (OSTI)

Vehicle sound emissions car alarms and horn honking are the subject of many noise complaints. Auto manufacturers spent years engineering quieter vehicles and have created cars whose approach is so subtle that they pose a danger to blind pedestrians. But while engine noise has decreased and car alarms are less reactive horn honking that is linked with remote keyless entry (RKE) technology increasingly contributes to community noise. RKE horn noise has never been the subject of public health inquiry. In scientific literature discussion of road noise and health does not distinguish noise among separate sources and tends to measure aggregate ambient noise levels rather than impulsive noise. RKE horn noise violates state traffic laws and some local noise ordinances regarding horn use but there have been no legislative attempts to address the technology. This raises questions about whether political leaders and policy setters are not exposed to RKE noise or do not discern RKE sounds from traffic noise and are therefore unaware of it. Using available auto industry data and case studies this paper will introduce key facts about RKE horn use in the United States and Canada reviewing new technologies that render noisy counterparts still in use as redundant.

2013-01-01T23:59:59.000Z

126

Fire Protection Account Request Form  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fire Protection System Account Request Form Fire Protection System Account Request Form To obtain a user id and password to access the Fire Protection system, please complete the form, save the file and email it to hssUserSupport@hq.doe.gov or print and fax it to 301-903-9823. We will provide a username and password to new account holders. Please allow several business days to process your account request. When your request is approved, you will be contacted with your

127

Fire and Ice Issue 7  

E-Print Network (OSTI)

       ' FIRE and ICE # 7 -p! jP) FIRE AND ICE VII Available from: Kathleen Resch PO Box 1766 Temple City, CA 91780 Kathleener@aol.com May 2002by Kathleen Reschfor the contributors. No reprints or reproduction without the written... permission of the author/artist. Thisis an amateur publication and is not in tended to infringe upon the rights ofTerryNation, BBC-TV or any others. i - J FIRE AND ICE VI Table of Contents HALF A LOAF by Linda Norman 1 GROUNDHOG LAY by Predatrlx 5 PLAYTIME...

Multiple Contributors

2002-01-01T23:59:59.000Z

128

Fire and Ice Issue 3  

E-Print Network (OSTI)

,fpl ^1 FIRE AND ICE Available from: Kathleen Resch PO Box 1766 Temple City,CA 91780 III May, 1995 by Kathleen Resch for the contributors. No reprints or reproduction without the written permission of the author/artist. This is an amateur... publication and is not intended to infringe upon the rightsof "Blake's 7" copyright holders.. FIRE AND ICE TABLE OF CONTENTS THE GIFT by Pat Terra 1 "innerspace" by Pat Terra 24 WILD, BEAUTIFUL AND DAMNED by Gemini 25 SET THE NIGHT ON FIRE by Riley Cannon 40...

Multiple Contributors

1995-01-01T23:59:59.000Z

129

Fire Behavior at the Landscape Scale  

E-Print Network (OSTI)

Fire Behavior at the Landscape Scale Scott Stephens, ESPMScott Stephens, ESPM DepartmentStrategies for Landscape Fuel TreatmentsLandscape Fuel Treatments Fire Containment · Fuelbreaks Fire Modification · Area (WUI) ·· Maintenance? Must maintain into futureMaintenance? Must maintain into future #12;Tyee Fire

Stephens, Scott L.

130

Wildland Fire Protection Program NEBRASKA FOREST SERVICE  

E-Print Network (OSTI)

Wildland Fire Protection Program NEBRASKA FOREST SERVICE HOW NEBRASKANS BENEFIT: · improved protection of life and property from wildland fires · improved firefighting capability in rural fire districts · increased firefighter knowledge of wildland fire suppression and prevention · reduced forest

Farritor, Shane

131

FIRE PREVENTION AND PROTECTION Table Of Contents  

E-Print Network (OSTI)

EM 385-1-1 XX Sep 13 i Section 9 FIRE PREVENTION AND PROTECTION Table Of Contents Section: Page 09 and Melting Kettles.............................9-25 09.F First response Fire Protection FIRE PREVENTION AND PROTECTION 09.A GENERAL 09.A.01 A fire prevention plan shall be written for all

US Army Corps of Engineers

132

Firing of pulverized solvent refined coal  

DOE Patents (OSTI)

An air-purged burner for the firing of pulverized solvent refined coal is constructed and operated such that the solvent refined coal can be fired without the coking thereof on the burner components. The air-purged burner is designed for the firing of pulverized solvent refined coal in a tangentially fired boiler.

Derbidge, T. Craig (Sunnyvale, CA); Mulholland, James A. (Chapel Hill, NC); Foster, Edward P. (Macungie, PA)

1986-01-01T23:59:59.000Z

133

No material is "fire proof;" however, proper use and assembly of fire-rated building materials  

E-Print Network (OSTI)

C has the least resistance. However, Class A materials generally need an underlayment of additional-Defensible Zones 6.303, Fire-Resistant Landscaping 6.304, Forest Home Fire Safety 6.305, FireWise Plant Materials 6General No material is "fire proof;" however, proper use and assembly of fire-rated building

134

fire Protection The Fire Protection Technology associate degree is awarded by UNL's College of  

E-Print Network (OSTI)

fire Protection DeGreeS offereD A.S. The Fire Protection Technology associate degree is awarded Protection courses are taught by UNL College of Engineering faculty, as well as fire service and industry fire protection specialists. These fire protection specialists teach students not only from textbooks

Farritor, Shane

135

Fire in a contaminated area  

SciTech Connect

This document supports the development and presentation of the following accident scenario in the TWRS Final Safety Analysis Report: Fire in Contaminated Area. The calculations needed to quantify the risk associated with this accident scenario are included within.

Ryan, G.W., Westinghouse Hanford

1996-08-02T23:59:59.000Z

136

New Canadian Fire Research Laboratory  

Science Journals Connector (OSTI)

... which follows the time - temperature curve designated in the current U.S. Standard (ASTM E119-57, Standard Methods of Fire Tests of Building Construction and Materials).

R. F. LEGGET

1959-03-07T23:59:59.000Z

137

Model Fire Protection Assessment Guide  

Energy.gov (U.S. Department of Energy (DOE))

This Assessment guide covers the implementation of the DOE's responsibility of assuring that DOE and the DOE Contractors have established Fire Protection Programs that are at the level required for the area being assessed.

138

The Importance of Technical Reachback in the Adjudication of Radiation Alarms  

SciTech Connect

The large-scale deployment of radiation sensors at borders, ports-of-entry and other locations carries two disparate priorities: the reliable detection and identification of threat materials and the rapid characterization of non-threat materials comprised of naturally occurring radioactive materials (NORM) and legitimate radioactive materials in streams of commerce. These priorities are partially achieved through the technologies contained in the detection systems and the procedures developed for their operation. However, questions and ambiguities will occur. Without established capabilities and procedures for the operators of these detector systems to 'reach back' to trained spectroscopists and appropriate subject matter experts, the system will likely experience an unacceptable number of response operations and delays resolving alarms. Technical reachback operations need to be able to address the priorities discussed above while causing minimal perturbations in the flow of legitimate streams of commerce. Yet when necessary, reachback needs to be able to rapidly mobilize the appropriate response assets.

Buckley, W M; Allen, R W

2009-03-18T23:59:59.000Z

139

Incipient fire detection system  

DOE Patents (OSTI)

A method and apparatus for an incipient fire detection system that receives gaseous samples and measures the light absorption spectrum of the mixture of gases evolving from heated combustibles includes a detector for receiving gaseous samples and subjecting the samples to spectroscopy and determining wavelengths of absorption of the gaseous samples. The wavelengths of absorption of the gaseous samples are compared to predetermined absorption wavelengths. A warning signal is generated whenever the wavelengths of absorption of the gaseous samples correspond to the predetermined absorption wavelengths. The method includes receiving gaseous samples, subjecting the samples to light spectroscopy, determining wavelengths of absorption of the gaseous samples, comparing the wavelengths of absorption of the gaseous samples to predetermined absorption wavelengths and generating a warning signal whenever the wavelengths of absorption of the gaseous samples correspond to the predetermined absorption wavelengths. In an alternate embodiment, the apparatus includes a series of channels fluidically connected to a plurality of remote locations. A pump is connected to the channels for drawing gaseous samples into the channels. A detector is connected to the channels for receiving the drawn gaseous samples and subjecting the samples to spectroscopy. The wavelengths of absorption are determined and compared to predetermined absorption wavelengths is provided. A warning signal is generated whenever the wavelengths correspond.

Brooks, Jr., William K. (Newport News, VA)

1999-01-01T23:59:59.000Z

140

FireWxNet: a multi-tiered portable wireless system for monitoring weather conditions in wildland fire environments  

Science Journals Connector (OSTI)

In this paper we present FireWxNet, a multi-tiered portable wireless system for monitoring weather conditions in rugged wildland fire environments. FireWxNet provides the fire fighting community the ability to safely and easily measure and view fire ... Keywords: applications, deployments, fire, forest fires, wireless sensor networks

Carl Hartung; Richard Han; Carl Seielstad; Saxon Holbrook

2006-06-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


141

Evaluation of coverage of enriched UF{sub 6} cylinder storage lots by existing criticality accident alarms  

SciTech Connect

The Portsmouth Gaseous Diffusion Plant (PORTS) is leased from the US Department of Energy (DOE) by the United States Enrichment Corporation (USEC), a government corporation formed in 1993. PORTS is in transition from regulation by DOE to regulation by the Nuclear Regulatory Commission (NRC). One regulation is 10 CFR Part 76.89, which requires that criticality alarm systems be provided for the site. PORTS originally installed criticality accident alarm systems in all building for which nuclear criticality accidents were credible. Currently, however, alarm systems are not installed in the enriched uranium hexafluoride (UF{sub 6}) cylinder storage lots. This report analyzes and documents the extent to which enriched UF{sub 6} cylinder storage lots at PORTS are covered by criticality detectors and alarms currently installed in adjacent buildings. Monte Carlo calculations are performed on simplified models of the cylinder storage lots and adjacent buildings. The storage lots modelled are X-745B, X-745C, X745D, X-745E, and X-745F. The criticality detectors modelled are located in building X-343, the building X-344A/X-342A complex, and portions of building X-330. These criticality detectors are those located closest to the cylinder storage lots. Results of this analysis indicate that the existing criticality detectors currently installed at PORTS are largely ineffective in detecting neutron radiation from criticality accidents in most of the cylinder storage lots at PORTS, except sometimes along portions of their peripheries.

Lee, B.L. Jr.; Dobelbower, M.C.; Woollard, J.E.; Sutherland, P.J.; Tayloe, R.W. Jr.

1995-03-01T23:59:59.000Z

142

CRAD, Fire Protection - October 12, 2012 | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fire Protection - October 12, 2012 Fire Protection - October 12, 2012 CRAD, Fire Protection - October 12, 2012 October 12, 2012 Fire Protection Inspection Criteria, Approach, and Lines of Inquiry HSS CRAD 45-34, Rev. 1) Review fire protection system design and defense in-depth strategies. Interviews shall be conducted of personnel including fire engineers, fire coordinators, fire system technicians, facility operations personnel, and fire department personnel. Review policies, procedures, fire hazards analyses, and safety basis documentation. Additionally, perform facility building walk downs and inspections, and observe selected work activities, such as hot work, fire system impairments, combustible storage practices, dispensing flammable liquids, maintenance and testing of fire protection

143

Untrained Forward Observer (UFO) translator for call for fire .  

E-Print Network (OSTI)

??Many observers need indirect fire but are not proficient in Call for Fire, the procedure used to request indirect fire. To alleviate this, we propose (more)

King, Regan R.

2013-01-01T23:59:59.000Z

144

EXHAUST GAS BOILER FIRE PERVENTION  

E-Print Network (OSTI)

Today's demands for better overall usability of fuel oil in large two-stroke low speed marine diesel engines greatly influenced their development, and the purity of their exhaust gases. With this paper we would like to indicate on to factors which directly influence on soot forming, deposition and cause of occurance of fire in exhaust gas boiler (EGB). Due the fact that a fire in the EGB can result in complete destruction of the boiler, and a longer interruption of the vessel commercial operations, crew must be familiar with the main reasons of soot deposition on the boiler tubes and elements and origination of fire, and to have taken proper and timely protection measures 1.

Branko Lali? Dipl. Ing; Mr. Ivan Komar; Dipl. Ing

145

ANNUAL FIRE SAFETY REPORT 2013 Ithaca, NY Campus  

E-Print Network (OSTI)

related services including programs in: · Fire Protection, Emergency Services, Emergency Management o Fire Protection Systems and Equipment o University Fire Marshal o Emergency Management o Events Management oANNUAL FIRE SAFETY REPORT 2013 Ithaca, NY Campus http

Chen, Tsuhan

146

ANNUAL FIRE SAFETY REPORT 2012 Ithaca, NY Campus  

E-Print Network (OSTI)

: · Fire Protection, Emergency Services, Emergency Management o Fire Protection Systems and Equipment oANNUAL FIRE SAFETY REPORT 2012 Ithaca, NY Campus http Annual Fire Safety Report 2012 Page 2 From the Department of Environmental Health and Safety (EH

Chen, Tsuhan

147

Initial Joint Review of Wildland Fire Safety at DOE Sites  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Wildland Fire" November 2000 2. U.S. Fish & Wildlife, "24 Command Fire, A National Level Review by the Interagency Fire Team," September 2000 INEEL Site (Tea Kettle Fire, etc.) In...

148

SOLVENT FIRE BY-PRODUCTS  

SciTech Connect

Southwest Research Institute (SwRI) conducted a burn test of the Caustic-Side Solvent Extraction (CSSX) solvent to determine the combustion products. The testing showed hydrogen fluoride gas is not a combustion product from a solvent fire when up to 70% of the solvent is consumed. The absence of HF in the combustion gases may reflect concentration of the modifier containing the fluoride groups in the unburned portion. SwRI reported results for other gases (CO, HCN, NOx, formaldehyde, and hydrocarbons). The results, with other supporting information, can be used for evaluating the consequences of a facility fire involving the CSSX solvent inventory.

Walker, D; Samuel Fink, S

2006-05-22T23:59:59.000Z

149

Fire suppression and detection equipment  

SciTech Connect

Inspection and testing guidelines go beyond the 'Code of Federal Regulation'. Title 30 of the US Code of Federal Regulations (30 CFR) contains requirements and references to national standards for inspection, testing and maintenance of fire suppression and detection equipment for mine operators. However, federal requirements have not kept pace with national standards and best practices. The article lists National Fire Protection (NFPA) standards that are referenced by the US Mine Safety and Health Administration (MSHA) in 30 CFR. It then discusses other NFPA Standards excluded from 30 CFR and explains the NFPA standard development process. 2 refs., 3 tabs., 5 photos.

E.E. Bates [HSB Professional Loss Control, Lexington, KY (United States)

2006-01-15T23:59:59.000Z

150

Fire and Ice Issue 6  

E-Print Network (OSTI)

9#HDIQNV3>IM ".: FIRE AND ICE VI Available from: Kathleen Resch PO Box 1766 Temple City, CA 91780 October, 2000 by Kathleen Resch for the contributors. No reprints or reproduction without the written permission of the author.../artist. This is an amateur publication and is not intended to infringe upon the rights ofTerry Nation, BBC-TV or any others. FIRE AND ICE VI 1 Table of Contents A DANGEROUS CONCEPT by Nova 1 A FRIEND IN NEED... by Julia Stamford 14 ...IS A FRIEND INDEED by Julia Stamford 19...

Multiple Contributors

2000-01-01T23:59:59.000Z

151

Fire and Ice Issue 2  

E-Print Network (OSTI)

. fipl cpn r FLASHPOINT A flame that can't be seen, cloaked in black and silver and disdain, born of anger and of love no longer dared. An ice-encrusted soul, dormant in the aftermath of accusations piled like snow against the heated passions of a man who...^ $$% i&l /P^ \\0 rffej FIRE AND ICE AVAILABLE FROM Kathleen Resch PO Box 1766 Temple City, CA 91780 FIRE AND ICE II TABLE OF CONTENTS COVER by Phoenix FRONTISPIECE by Gayle Feyrer "Flashpoint" by Rachel Duncan 1 PEDESTAL by Thomas 2 "A Damn Fine...

Multiple Contributors

1993-01-01T23:59:59.000Z

152

Fire Protection Engineering Qualification Standard Reference Guide  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fire Protection Fire Protection Engineering Qualification Standard Reference Guide SEPTEMBER 2009 This page is intentionally blank. Table of Contents i ACRONYMS ................................................................................................................................. ii PURPOSE.......................................................................................................................................1 SCOPE ............................................................................................................................................1 PREFACE.......................................................................................................................................1 TECHNICAL COMPETENCIES................................................................................................3

153

Fire performance of gable frame structures  

E-Print Network (OSTI)

Fire protection engineering and structural engineering are two relevant but separated fields of study. Many experiments conducted by fire protection engineers are under certain ideal boundary conditions, which may not be ...

Qian, Congyi

2013-01-01T23:59:59.000Z

154

Solid waste drum array fire performance  

SciTech Connect

Fire hazards associated with drum storage of radioactively contaminated waste are a major concern in DOE waste storage facilities. This report is the second of two reports on fire testing designed to provide data relative to the propagation of a fire among storage drum arrays. The first report covers testing of individual drums subjected to an initiating fire and the development of the analytical methodology to predict fire propagation among storage drum arrays. This report is the second report, which documents the results of drum array fire tests. The purpose of the array tests was to confirm the analytical methodology developed by Phase I fire testing. These tests provide conclusive evidence that fire will not propagate from drum to drum unless an continuous fuel source other than drum contents is provided.

Louie, R.L. [Westinghouse Hanford Co., Richland, WA (United States); Haecker, C.F. [Los Alamos Technical Associates, Inc., Kennewick, WA (United States); Beitel, J.J.; Gottuck, D.T.; Rhodes, B.T.; Bayier, C.L. [Hughes Associates, Inc., Baltimore, MD (United States)

1995-09-01T23:59:59.000Z

155

FireStream: Sensor Stream Processing for Monitoring Fire Spread Venkatesh Raghavan1  

E-Print Network (OSTI)

Institute, Worcester, MA 01609 2 Department of Fire Protection Engineering, Worcester Polytechnic Institute. In this demonstration, we present FireStream, a collabo- rative effort between Computer Science and Fire Protection experiments conducted at lab- oratories such as NIST/BFRL and the Department of Fire Protection Engineering

156

Wildland fire emissions, carbon, and climate: Wildland fire detection and burned area in the United States  

E-Print Network (OSTI)

Wildland fire emissions, carbon, and climate: Wildland fire detection and burned area in the United Wildland fires can be an important source of greenhouse gases as well as black carbon emissions that have of climate response to fire emissions compared to other emission sources of GHG, aerosols, and black carbon

157

Planning Rural Fire Protection for Texas.  

E-Print Network (OSTI)

IOC rA24S.7 73 ).1196 (Blank Pa.ge InOdgiuat Bulletinl ~ ; ''; . : .. . ~. " PLANNING RURAL FIRE PROTECTION FOR TEXAS JACK L. JONES, EXTENSION COMMUNITY DEVELOPMENT SPECIALIST TEXAS AGRICULTURAL EXTENSION SERVICE INTRODUCTION A home fire... is one of the most feared accidents a homeowner can? have, especially in rural areas where extended distances, inadequate water supplies or lack of any community fire fighting services limit fire fighting capability. Unless a rural resident makes prior...

Jones, Jack L.

1981-01-01T23:59:59.000Z

158

Nuclear incident monitor criticality alarm instrument for the Savannah River Site: Technical manual  

SciTech Connect

The Savannah River Site is a Department of Energy facility. The facility stores, processes, and works with fissionable material at a number of locations. Technical standards and US Department of Energy orders, require these locations to be monitored by criticality alarm systems under certain circumstances. The Savannah River Site calls such instruments Nuclear Incident Monitors or NIMs. The Sole purpose of the Nuclear Incident Monitor is to provide an immediate evacuation signal in the case of an accidental criticality in order to minimize personnel exposure to radiation. The new unit is the third generation Nuclear Incident Monitor at the Savannah River Site. The second generation unit was developed in 1979. It was designed to eliminate vacuum-tube circuits, and was the first solid state NIM at SRS. The major design objectives of the second generation NIM were to improve reliability and reduce maintenance costs. Ten prototype units have been built and tested. This report describes the design of the new NIM and the testing that took place to verify its acceptability.

Jenkins, J.B.

1996-05-21T23:59:59.000Z

159

CONSTITUTION AND BY-LAWS FIRE DEPARTMENT  

E-Print Network (OSTI)

of lives, and the protection of property endangered by fires and other disasters, and to promote the teaching and practice of fire prevention and protection. ARTICLE II Section 1. The OfficersSAMPLE CONSTITUTION AND BY-LAWS OF THE FIRE DEPARTMENT WHEREAS, Certain laws and regulations

160

Fire Protection Systems Program Program Manual  

E-Print Network (OSTI)

Fire Protection Systems Program Program Manual Approved by: (name) Last revised by: (name) Revision/FPS_Program_Manual_Template.docx 1. Introduction The Fire Protection Systems Program is designed to make sure the annual compliance ................................................................................................................. 3 7.1.1 Job Plan: Fire Pump Testing

Pawlowski, Wojtek

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


161

Research Overview Department of Fire Protection Engineering  

E-Print Network (OSTI)

Research Overview Department of Fire Protection Engineering University of Maryland College Park, MD, detection M.J. Gollner wildfires, flammability, structures A.W. Marshall fire flows, combustion, suppression J.A. Milke structures, detection, egress S.I. Stoliarov pyrolysis, flammability, fire growth P

Shapiro, Benjamin

162

Imperial College London FIRE SERVICES  

E-Print Network (OSTI)

to minimise the hazard the following precautions are recommended: Christmas tree lights, fibre optic trees hazards. Avoid leaving Christmas lights on unattended for long periods. Lighted candles are generally at Christmas During the lead up to Christmas the risk of fire can be increased with the introduction

163

HOURGLASS FIRE Pingree Park Vicinity  

E-Print Network (OSTI)

needles). Fuel moistures were extremely low throughout Colorado during spring/early summer of 1994 firefighters in a blowup near Glenwood Springs. Table 1 indicates dead fuel moistures in the Pingree Park). Spotting was occurring 1/2 mile in advance of the fire. By this time personnel/engines from Colorado State

164

Applications of Living Fire PRA models to Fire Protection Significance Determination Process in Taiwan  

SciTech Connect

The living fire probabilistic risk assessment (PRA) models for all three operating nuclear power plants (NPPs) in Taiwan had been established in December 2000. In that study, a scenario-based PRA approach was adopted to systematically evaluate the fire and smoke hazards and associated risks. Using these fire PRA models developed, a risk-informed application project had also been completed in December 2002 for the evaluation of cable-tray fire-barrier wrapping exemption. This paper presents a new application of the fire PRA models to fire protection issues using the fire protection significance determination process (FP SDP). The fire protection issues studied may involve the selection of appropriate compensatory measures during the period when an automatic fire detection or suppression system in a safety-related fire zone becomes inoperable. The compensatory measure can either be a 24-hour fire watch or an hourly fire patrol. The living fire PRA models were used to estimate the increase in risk associated with the fire protection issue in terms of changes in core damage frequency (CDF) and large early release frequency (LERF). In compliance with SDP at-power and the acceptance guidelines specified in RG 1.174, the fire protection issues in question can be grouped into four categories; red, yellow, white and green, in accordance with the guidelines developed for FD SDP. A 24-hour fire watch is suggested only required for the yellow condition, while an hourly fire patrol may be adopted for the white condition. More limiting requirement is suggested for the red condition, but no special consideration is needed for the green condition. For the calculation of risk measures, risk impacts from any additional fire scenarios that may have been introduced, as well as more severe initiating events and fire damages that may accompany the fire protection issue should be considered carefully. Examples are presented in this paper to illustrate the evaluation process. (authors)

De-Cheng, Chen; Chung-Kung, Lo; Tsu-Jen, Lin; Ching-Hui, Wu [Institute of Nuclear Energy Research, P. O. Box 3-3, Lung-Tan, Tao-Yuan Taiwan (China); Lin, James C. [ABSG Consulting Inc., 300 Commerce Drive, Suite 200, Irvine, CA 92602 (United States)

2004-07-01T23:59:59.000Z

165

Aging assessment for active fire protection systems  

SciTech Connect

This study assessed the impact of aging on the performance and reliability of active fire protection systems including both fixed fire suppression and fixed fire detection systems. The experience base shows that most nuclear power plants have an aggressive maintenance and testing program and are finding degraded fire protection system components before a failure occurs. Also, from the data reviewed it is clear that the risk impact of fire protection system aging is low. However, it is assumed that a more aggressive maintenance and testing program involving preventive diagnostics may reduce the risk impact even further.

Ross, S.B. [Science and Engineering Associates, Inc. (United States); Nowlen, S.P.; Tanaka, T. [Sandia National Labs., Albuquerque, NM (United States)

1995-06-01T23:59:59.000Z

166

Safety & Emergency Management  

NLE Websites -- All DOE Office Websites (Extended Search)

designed ESH 108 Building Orientation course. Fire Alarm System Testing Through Argonne Fire Protection Services, the fire alarm system is tested visually and audibly annually....

167

Tracking New Coal-Fired Power Plants  

NLE Websites -- All DOE Office Websites (Extended Search)

New Coal-Fired Power Plants New Coal-Fired Power Plants (data update 1/13/2012) January 13, 2012 National Energy Technology Laboratory Office of Strategic Energy Analysis & Planning Erik Shuster 2 Tracking New Coal-Fired Power Plants This report is intended to provide an overview of proposed new coal-fired power plants that are under development. This report may not represent all possible plants under consideration but is intended to illustrate the potential that exists for installation of new coal-fired power plants. Additional perspective has been added for non-coal-fired generation additions in the U.S. and coal-fired power plant activity in China. Experience has shown that public announcements of power plant developments do not provide an accurate representation of eventually

168

Pigments which reflect infrared radiation from fire  

DOE Patents (OSTI)

Conventional paints transmit or absorb most of the intense infrared (IR) radiation emitted by fire, causing them to contribute to the spread of fire. The present invention comprises a fire retardant paint additive that reflects the thermal IR radiation emitted by fire in the 1 to 20 micrometer (.mu.m) wavelength range. The important spectral ranges for fire control are typically about 1 to about 8 .mu.m or, for cool smoky fires, about 2 .mu.m to about 16 .mu.m. The improved inventive coatings reflect adverse electromagnetic energy and slow the spread of fire. Specific IR reflective pigments include titanium dioxide (rutile) and red iron oxide pigments with diameters of about 1 .mu.m to about 2 .mu.m and thin leafing aluminum flake pigments.

Berdahl, Paul H. (Oakland, CA)

1998-01-01T23:59:59.000Z

169

Pigments which reflect infrared radiation from fire  

DOE Patents (OSTI)

Conventional paints transmit or absorb most of the intense infrared (IR) radiation emitted by fire, causing them to contribute to the spread of fire. The present invention comprises a fire retardant paint additive that reflects the thermal IR radiation emitted by fire in the 1 to 20 micrometer ({micro}m) wavelength range. The important spectral ranges for fire control are typically about 1 to about 8 {micro}m or, for cool smoky fires, about 2 {micro}m to about 16 {micro}m. The improved inventive coatings reflect adverse electromagnetic energy and slow the spread of fire. Specific IR reflective pigments include titanium dioxide (rutile) and red iron oxide pigments with diameters of about 1 {micro}m to about 2 {micro}m and thin leafing aluminum flake pigments. 4 figs.

Berdahl, P.H.

1998-09-22T23:59:59.000Z

170

Fire protection program fiscal year 1997 site support program plan - Hanford fire department  

SciTech Connect

The mission of the Hanford Fires Department (HFD) is to support the safe and timely cleanup of the Hanford Site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating situations which could threaten the operations, employees, or interest of the US Department of Energy operated Hanford Site. this includes response to surrounding fire department districts under mutual aids agreements and contractual fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System) and various commercial entities operating on site. the fire department also provides site fire marshal overview authority, fire system testing, and maintenance, respiratory protection services, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention and education.

Good, D.E., Westinghouse Hanford

1996-07-01T23:59:59.000Z

171

Fire Protection Program fiscal year 1996, site support program plan Hanford Fire Department. Revision 2  

SciTech Connect

The mission of the Hanford Fire Department (HFD) is to support the safe and timely cleanup of the Hanford site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating emergency situations which could threaten the operations, employees, or interest of the US Department of Energy operated Hanford Site. This includes response to surrounding fire departments/districts under a mutual aid agreement and contractual fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System). The fire department also provides site fire marshal overview authority, fire system testing and maintenance, self-contained breathing apparatus maintenance, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention education. This report gives a program overview, technical program baselines, and cost and schedule baseline.

Good, D.E.

1995-09-01T23:59:59.000Z

172

Fire protection program fiscal year 1995 site support program plan, Hanford Fire Department  

SciTech Connect

The mission of the Hanford Fire Department (HFD) is to support the safe and timely cleanup of the Hanford site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating emergency situations which could threaten the operations, employees, or interest of the US Department of Energy operated Hanford Site. This includes response to surrounding fire departments/districts under a mutual aid agreement and contractual fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System). The fire department also provides site fire marshal overview authority, fire system testing and maintenance, self-contained breathing apparatus maintenance, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention education. This report describes the specific responsibilities and programs that the HFD must support and the estimated cost of this support for FY1995.

Good, D.E.

1994-09-01T23:59:59.000Z

173

Fire hazard analysis for the fuel supply shutdown storage buildings  

SciTech Connect

The purpose of a fire hazards analysis (FHA) is to comprehensively assess the risk from fire and other perils within individual fire areas in a DOE facility in relation to proposed fire protection so as to ascertain whether the objectives of DOE 5480.7A, Fire Protection, are met. This Fire Hazards Analysis was prepared as required by HNF-PRO-350, Fire Hazards Analysis Requirements, (Reference 7) for a portion of the 300 Area N Reactor Fuel Fabrication and Storage Facility.

REMAIZE, J.A.

2000-09-27T23:59:59.000Z

174

DOE Standard: Fire protection design criteria  

SciTech Connect

The development of this Standard reflects the fact that national consensus standards and other design criteria do not comprehensively or, in some cases, adequately address fire protection issues at DOE facilities. This Standard provides supplemental fire protection guidance applicable to the design and construction of DOE facilities and site features (such as water distribution systems) that are also provided for fire protection. It is intended to be used in conjunction with the applicable building code, National Fire Protection Association (NFPA) Codes and Standards, and any other applicable DOE construction criteria. This Standard replaces certain mandatory fire protection requirements that were formerly in DOE 5480.7A, ``Fire Protection``, and DOE 6430.1A, ``General Design Criteria``. It also contains the fire protection guidelines from two (now canceled) draft standards: ``Glove Box Fire Protection`` and ``Filter Plenum Fire Protection``. (Note: This Standard does not supersede the requirements of DOE 5480.7A and DOE 6430.1A where these DOE Orders are currently applicable under existing contracts.) This Standard, along with the criteria delineated in Section 3, constitutes the basic criteria for satisfying DOE fire and life safety objectives for the design and construction or renovation of DOE facilities.

Not Available

1999-07-01T23:59:59.000Z

175

How to Choose and Use Fire Extinguishers  

NLE Websites -- All DOE Office Websites (Extended Search)

How to Choose and Use Fire Extinguishers How to Choose and Use Fire Extinguishers By: John Kelsey, This Old House magazine A fire extinguisher can be a lifesaver. Placed near an exit, in an easy-to-grab spot, it can put out a small fire before the firefighters arrive, or at least suppress the flames while you escape. All household extinguishers are classified A, B, or C (or a combination of these) on the label to indicate which types of fires - ordinary combustibles, flammable liquids, or electrical-you can use them on. Many of the ones sold at home stores are classified A:B:C and fight all three types of fires. The main distinction among home extinguishers is size. In most cases bigger is better, but sometimes the biggest extinguishers are too heavy to maneuver. (The weight on an extinguisher refers to

176

FAQS Job Task Analyses - Fire Protection Engineering  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Job Task Analysis and Competency Review Job Task Analysis and Competency Review for All Level Competencies Fire Protection Engineering FAQS Initially conducted (expert competencies): August 2010 Updated (includes ALL Competencies): April 2011 Updated (includes ALL Competencies): October 2012 STEP 1: Job Task Analysis for Tasks Task (and Number) Source Importance Frequency Serve as the subject matter expert in the area of fire protection, life safety, and fire department emergency related services. FAQS Duties and Responsibilities Paragraph A 5 4 Review fire hazard analyses, assessments, and other fire safety documentation for compliance with applicable requirements. FAQS Duties and Responsibilities Paragraph B 5 3 Evaluate the adequacy of site emergency services. This includes all facets of the fire

177

Fire Hazard Analysis for the Cold Vacuum Drying (CVD) Facility  

SciTech Connect

This Fire Hazard Analysis assesses the risk from fire within individual fire areas in the Cold Vacuum Drying Facility at the Hanford Site in relation to existing or proposed fire protection features to ascertain whether the objectives of DOE Order 5480.7A Fire Protection are met.

JOHNSON, B.H.

1999-08-19T23:59:59.000Z

178

University of Vermont 2012 Student Housing Fire Safety Report  

E-Print Network (OSTI)

awards from FM Global (insurance) for fire protection programs. All on-campus residence halls by automatic cooking fire suppression systems. All fire protection systems are inspected regularly by UVM staff Marcus, Certified Fire Protection Specialist, University Fire Marshal 284 East Avenue, Burlington, VT

Hayden, Nancy J.

179

ENVIRONMENT, SAFETY & HEALTH DIVISION Chapter 12: Fire and Life Safety  

E-Print Network (OSTI)

ENVIRONMENT, SAFETY & HEALTH DIVISION Chapter 12: Fire and Life Safety Fire Protection Equipment The purpose of these requirements is to ensure the adequate provision and operability of fire protection Requirements Fire protection equipment includes Automatic fire suppression systems (such as sprinkler, clean

Wechsler, Risa H.

180

TU Vienna Fire Protection Regulations 1 General provisions  

E-Print Network (OSTI)

TU Vienna Fire Protection Regulations § 1 General provisions § 2 Scope § 3 Responsibility for preventive fire protection § 7 Conduct in the event of fire § 8 Assembly point § 9 Measures following a fire § 1 General provisions (1) Purpose and relationship to other legal regulations a) The fire protection

Szmolyan, Peter

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


181

Interagency Panel: Agency Fire Management Chair: Philip N. Omi  

E-Print Network (OSTI)

of Forestry and Fire Protection: Fire Management Summary1 Wayne Mitchell2 Abstract The California Department of Forestry and Fire Protection (CDF) is a full service wildland, rural, and urban fire department. CDF acres. About 55 percent of CDF's $452 million annual budget is used for wildland fire protection

Standiford, Richard B.

182

ENVIRONMENT, SAFETY & HEALTH DIVISION Chapter 12: Fire and Life Safety  

E-Print Network (OSTI)

ENVIRONMENT, SAFETY & HEALTH DIVISION Chapter 12: Fire and Life Safety Fire Protection SystemProcedImpair.pdf The purpose of these procedures is to minimize the downtime of active fire protection systems by closely controlling their impairment (any condition in which a fire protection system cannot perform its designed fire

Wechsler, Risa H.

183

Gas reburning in tangentially-fired, wall-fired and cyclone-fired boilers  

SciTech Connect

Gas Reburning has been successfully demonstrated for over 4,428 hours on three coal fired utility boilers as of March 31, 1994. Typically, NO{sub x} reductions have been above 60% in long-term, load-following operation. The thermal performance of the boilers has been virtually unaffected by Gas Reburning. At Illinois Power`s Hennepin Station, Gas Reburning in a 71 MWe tangentially-fired boiler achieved an average NO{sub x} reduction of 67% from the original baseline NO{sub x} level of 0.75 lb NO{sub x}/10{sup 6} Btu over a one year period. The nominal natural gas input was 18% of total heat input. Even at 10% gas heat input, NO{sub x} reduction of 55% was achieved. At Public Service Company of Colorado`s Cherokee Station, a Gas Reburning-Low NO{sub x} Burner system on a 172 MWe wall-fired boiler has achieved overall NO{sub x} reductions of 60--73% in parametric and long-term testing, based on the original baseline NO{sub x} level of 0.73 lb/10{sup 6} Btu. NO{sub x} reduction is as high as 60--65% even at relatively low natural gas usage (5--10% of total heat input). The NO{sub x} reduction by Low NO{sub x} Burners alone is typically 30--40%. NO{sub x} reduction has been found to be insensitive to changes in recirculated flue gas (2--7% of total flue gas) injected with natural gas. At City Water, Light and Power Company`s Lakeside Station in Springfield, Illinois, Gas Reburning in a 33 MWe cyclone-fired boiler has achieved an average NO{sub x} reduction of 66% (range 52--77%) at gas heat inputs of 20--26% in long-term testing, based on a baseline NO{sub x} level of 1.0 lb/10{sup 6} Btu (430 mg/MJ). This paper presents a summary of the operating experience at each site and discusses the long term impacts of applying this technology to units with tangential, cyclone and wall-fired (with Low NO{sub x} Burner) configurations.

May, T.J. [Illinois Power Co., Decatur, IL (United States); Rindahl, E.G. [Public Service Co. of Colorado, Denver, CO (United States); Booker, T. [City Water Light and Power, Springfield, IL (United States)] [and others

1994-12-31T23:59:59.000Z

184

Cryogenic slurry for extinguishing underground fires  

DOE Patents (OSTI)

A cryogenic slurry comprising a mixture of solid carbon dioxide particles suspended in liquid nitrogen is provided which is useful in extinguishing underground fires.

Chaiken, Robert F. (Pittsburgh, PA); Kim, Ann G. (Pittsburgh, PA); Kociban, Andrew M. (Wheeling, WV); Slivon, Jr., Joseph P. (Tarentum, PA)

1994-01-01T23:59:59.000Z

185

Sandia National Laboratories: National Fire Protection Association  

NLE Websites -- All DOE Office Websites (Extended Search)

Fire Protection Association More California Gas Stations Can Provide Hydrogen than Previously Thought, Sandia Study Says On July 29, 2014, in Center for Infrastructure Research and...

186

LNG fire and vapor control system technologies  

SciTech Connect

This report provides a review of fire and vapor control practices used in the liquefied natural gas (LNG) industry. Specific objectives of this effort were to summarize the state-of-the-art of LNG fire and vapor control; define representative LNG facilities and their associated fire and vapor control systems; and develop an approach for a quantitative effectiveness evaluation of LNG fire and vapor control systems. In this report a brief summary of LNG physical properties is given. This is followed by a discussion of basic fire and vapor control design philosophy and detailed reviews of fire and vapor control practices. The operating characteristics and typical applications and application limitations of leak detectors, fire detectors, dikes, coatings, closed circuit television, communication systems, dry chemicals, water, high expansion foam, carbon dioxide and halogenated hydrocarbons are described. Summary descriptions of a representative LNG peakshaving facility and import terminal are included in this report together with typical fire and vapor control systems and their locations in these types of facilities. This state-of-the-art review identifies large differences in the application of fire and vapor control systems throughout the LNG industry.

Konzek, G.J.; Yasutake, K.M.; Franklin, A.L.

1982-06-01T23:59:59.000Z

187

Tracking New Coal-Fired Power Plants  

NLE Websites -- All DOE Office Websites (Extended Search)

January 8, 2010 National Energy Technology Laboratory Office of Systems Analyses and Planning Erik Shuster 2 Tracking New Coal-Fired Power Plants This report is intended to...

188

Contained Firing Facility | National Nuclear Security Administration  

National Nuclear Security Administration (NNSA)

Contained Firing Facility | National Nuclear Security Administration Contained Firing Facility | National Nuclear Security Administration Our Mission Managing the Stockpile Preventing Proliferation Powering the Nuclear Navy Emergency Response Recapitalizing Our Infrastructure Continuing Management Reform Countering Nuclear Terrorism About Us Our Programs Our History Who We Are Our Leadership Our Locations Budget Our Operations Media Room Congressional Testimony Fact Sheets Newsletters Press Releases Speeches Events Social Media Video Gallery Photo Gallery NNSA Archive Federal Employment Apply for Our Jobs Our Jobs Working at NNSA Blog Contained Firing Facility Home > About Us > Our Programs > Defense Programs > Office of Research, Development, Test, and Evaluation > Office of Research and Development > Facilities > Contained Firing Facility

189

(BSET) FIRE SAFETY ENGINEERING TECHNOLOGY CURRICULUM FOUR YEAR FIRE SAFETY CONCENTRATION CURRICULUM  

E-Print Network (OSTI)

. ETFS 4323 3 Intro to Performance-based Fire Safety8 ETFS 32338 3 Ethical Issues and Cultural Critique3(BSET) FIRE SAFETY ENGINEERING TECHNOLOGY CURRICULUM FOUR YEAR FIRE SAFETY CONCENTRATION CURRICULUM 3 Technical Drawing I ETGR 1103 2 Western Culture and Hist. Awareness LBST 2101 3 Total Hours 16

Raja, Anita

190

What is prescribed fire? Prescribed fire is the controlled application of  

E-Print Network (OSTI)

What is prescribed fire? Prescribed fire is the controlled application of fire to the land an uncontrolled wildfire occur. What is a burn prescription? A burn prescription helps ensure that the objectives species to naturally regenerate. (Lodgepole pine is one such example.) What about the smoke? Controlling

191

Housing & Residence Education Disclosure of Fire Safety Standards and Measures 1 Campus Fire Safety Right-to-Know  

E-Print Network (OSTI)

Housing & Residence Education Disclosure of Fire Safety Standards and Measures 1 Campus Fire Safety and death resulting from each fire. #12;Housing & Residence Education Disclosure of Fire Safety Standards) -- HVAC fan motor burned up -- Alpha Chi Omega -- 3/13/10 $1,500 (Greek) -- Futon mattress caught fire

Fang, Yuguang "Michael"

192

Housing & Residence Education Disclosure of Fire Safety Standards and Measures 1 Campus Fire Safety Right-to-Know  

E-Print Network (OSTI)

Housing & Residence Education Disclosure of Fire Safety Standards and Measures 1 Campus Fire Safety and death resulting from each fire. #12;Housing & Residence Education Disclosure of Fire Safety Standards) -- Grease Fire -- Beaty Towers -- 9/10/10 $100 (Greek) -- HVAC fan motor burned up -- Alpha Chi Omega -- 3

Slatton, Clint

193

Sample Lesson Plan Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection 1 Sample Lesson Plan  

E-Print Network (OSTI)

, Emergency Action Plans, Fire Prevention Plans, and Fire Protection Overview of the OSHA Standard Subpart E problems finding and using it. Subpart L, Fire Protection, contains requirements for fire brigades, and all installed to meet the fire protection requirements of 29 CFR Part 1910. Step 1: Planning the Lesson

Homes, Christopher C.

194

Steam Plant Replaces Outdated Coal-Fired System | Department...  

Office of Environmental Management (EM)

Steam Plant Replaces Outdated Coal-Fired System September 1, 2012 - 12:00pm Addthis A new natural gas-fired steam plant will replace an older coal-fired steam plant shown here. The...

195

Fire Ecology Special Issue Vol. 5, No. 1, 2009  

E-Print Network (OSTI)

-fire rainfall events. Soil losses in the high end of that range definitely exceed soil loss tolerances, humankind transformed fire into one of its oldest tools. Human and lightning ignited fires altered

196

Old Dominion University Annual Security and Fire Safety Report  

E-Print Network (OSTI)

Protection Features in Residence Halls____________________ 21 Residential Facilities Fire Safety AmenitiesOld Dominion University 2012 Annual Security and Fire Safety Report All statements and policies _________________________________________ 17 Fire Safety ______________________________________________________________ 19 Residence Halls

197

FSEP-Rev.02 Fire Safety Evacuation Plan  

E-Print Network (OSTI)

.......................................................................................... 1 3.2 Fire Protection Authority ............................................................................................... 2 3.5 Fire Protection EquipmentFSEP-Rev.02 Fire Safety Evacuation Plan Henrietta Harvey Building Prepared By: Graham Mowbray Date

Oyet, Alwell

198

Fire Protection Engineering Four Year Academic Plan Name:_______________________________________________ UID:___________________________  

E-Print Network (OSTI)

Fire Protection Engineering Four Year Academic Plan Name;FIRE PROTECTION ENGINEERING NAME: _____________________________________ Major Requirements Requirements Dev Seminar 1 ENFP 405 - Structural Fire Protection 3 Requirements Course Credits Grade ENFP 410

Shapiro, Benjamin

199

FSEP-Rev.02 Fire Safety Evacuation Plan  

E-Print Network (OSTI)

.......................................................................................... 4 3.2 Fire Protection Authority ............................................................................................... 5 3.5 Fire Protection EquipmentFSEP-Rev.02 Fire Safety Evacuation Plan Ocean Sciences Centre Prepared By: Connie Short Date: April

Oyet, Alwell

200

ANNUAL FIRE SAFETY REPORT 2011 Ithaca, NY Campus  

E-Print Network (OSTI)

Plan ____________________________________________________ 14 Cornell University Fire Safety Plan including programs in: Fire Protection, Emergency Services, Emergency Management o Fire Protection Services o Research and Laboratory Safety o Chemical Safety o Radiation Safety o Biological Safe

Chen, Tsuhan

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


201

Underground Salt Haul Truck Fire at the Waste Isolation Pilot...  

Office of Environmental Management (EM)

Underground Salt Haul Truck Fire at the Waste Isolation Pilot Plant February 5, 2014 March 2014 Salt Haul Truck Fire at the Waste Isolation Pilot Plant Salt Haul Truck Fire at the...

202

Live Fire Range Environmental Assessment  

SciTech Connect

The Central Training Academy (CTA) is a DOE Headquarters Organization located in Albuquerque, New Mexico, with the mission to effectively and efficiently educate and train personnel involved in the protection of vital national security interests of DOE. The CTA Live Fire Range (LFR), where most of the firearms and tactical training occurs, is a complex separate from the main campus. The purpose of the proposed action is to expand the LFR to allow more options of implementing required training. The Department of Energy has prepared this Environmental Assessment (EA) for the proposed construction and operation of an expanded Live Fire Range Facility at the Central Training Academy in Albuquerque, New Mexico. Based on the analysis in the EA, DOE has determined that the proposed action is not a major Federal action significantly affecting the quality of the human environment, within the meaning of the National Environmental Policy Act (NEPA) of 1969. Therefore, the preparation of an environmental impact statement is not required and DOE is issuing this Finding of No Significant Impact (FONSI).

None

1993-08-01T23:59:59.000Z

203

Coal-fired diesel generator  

SciTech Connect

The objective of the proposed project is to test the technical, environmental, and economic viability of a coal-fired diesel generator for producing electric power in small power generating markets. Coal for the diesel generator would be provided from existing supplies transported for use in the University`s power plant. A cleanup system would be installed for limiting gaseous and particulate emissions. Electricity and steam produced by the diesel generator would be used to supply the needs of the University. The proposed diesel generator and supporting facilities would occupy approximately 2 acres of land adjacent to existing coal- and oil-fired power plant and research laboratory buildings at the University of Alaska, Fairbanks. The environmental analysis identified that the most notable changes to result from the proposed project would occur in the following areas: power plant configuration at the University of Alaska, Fairbanks; air emissions, water use and discharge, and the quantity of solid waste for disposal; noise levels at the power plant site; and transportation of coal to the power plant. No substantive adverse impacts or environmental concerns were identified in analyzing the effects of these changes.

NONE

1997-05-01T23:59:59.000Z

204

Fire and explosion hazards of oil shale  

SciTech Connect

The US Bureau of Mines publication presents the results of investigations into the fire and explosion hazards of oil shale rocks and dust. Three areas have been examined: the explosibility and ignitability of oil shale dust clouds, the fire hazards of oil shale dust layers on hot surfaces, and the ignitability and extinguishment of oil shale rubble piles. 10 refs., 54 figs., 29 tabs.

Not Available

1989-01-01T23:59:59.000Z

205

Managing Imported Fire Ants in Urban Areas  

E-Print Network (OSTI)

The imported fire ant is found in much of Texas and across the southeastern U.S. This publication describes options for managing the pest in specific locations such as home lawns, gardens and buildings. Other topics include fire ant treatment...

Drees, Bastiaan M.

2006-08-17T23:59:59.000Z

206

The Fire Walk Ceremony in Tahiti  

Science Journals Connector (OSTI)

... all essential particulars with those in the accounts already cited. According to these, a pit was dug in which large stones were heated red hot by a fire which had ... dug in which large stones were heated red hot by a fire which had been burning many hours. The upper stones were pushed away just before the ceremony, so as ...

S. P. LANGLEY

1901-08-22T23:59:59.000Z

207

Modeling long-term fire regimes of southern California shrublands1 (Suggested running head: "Modeling fire regimes with HFire")3  

E-Print Network (OSTI)

of three fire regime metrics (fire size24 distributions, fire return interval maps, cumulative total area pattern of ignitions, fuels, weather,38 and topography, and describes the size, spatial pattern

Carlson, Jean

208

CRAD, Fire Protection - Oak Ridge National Laboratory High Flux...  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fire Protection - Oak Ridge National Laboratory High Flux Isotope Reactor CRAD, Fire Protection - Oak Ridge National Laboratory High Flux Isotope Reactor February 2006 A section of...

209

The Simulation Analysis of Fire Feature on Underground Substation  

Science Journals Connector (OSTI)

Underground transformer substations constructed with non-dwelling buildings have a ... out simulation analysis of fire feature on underground substation. The corresponding fire protection strategy is also...

Xin Han; Xie He; Beihua Cong

2012-01-01T23:59:59.000Z

210

Suspension-fired biomass boilers. Three case studies  

SciTech Connect

A discussion of the conversion of oil-or gas-fired boilers to fire pulverized bark and wood wastes in suspension.

Robinson, L.

1986-01-01T23:59:59.000Z

211

Sandia National Laboratories: Sandia Study Shows Large LNG Fires...  

NLE Websites -- All DOE Office Websites (Extended Search)

ClimateECInfrastructure SecurityAnalysisSandia Study Shows Large LNG Fires Hotter but Smaller Than Expected Sandia Study Shows Large LNG Fires Hotter but Smaller Than Expected...

212

Version 2 Global Fire Emissions Database Available  

NLE Websites -- All DOE Office Websites (Extended Search)

Global Fire Emissions Database Available Global Fire Emissions Database Available The ORNL DAAC announces the release of the data set "Global Fire Emissions Database, Version 2 (GFEDv2)." This data set, which supersedes and replaces the Global Fire Emissions Database, Version 1 (GFEDv1), consists of 1 degree x 1 degree gridded monthly burned area, fuel loads, combustion completeness, and fire emissions of carbon (C), carbon dioxide (CO2), carbon monoxide (CO), methane (CH4), non-methane hydrocarbons (NMHC), molecular hydrogen (H2), nitrogen oxides (NOx), nitrous oxide (N2O), particulate matter (PM2.5), total particulate matter (TPM), total carbon (TC), organic carbon (OC), and black carbon (BC) for the time period January 1997 - December 2004. For more information or to access this data set, please see the Vegetation

213

Repository Subsurface Preliminary Fire Hazard Analysis  

SciTech Connect

This fire hazard analysis identifies preliminary design and operations features, fire, and explosion hazards, and provides a reasonable basis to establish the design requirements of fire protection systems during development and emplacement phases of the subsurface repository. This document follows the Technical Work Plan (TWP) (CRWMS M&O 2001c) which was prepared in accordance with AP-2.21Q, ''Quality Determinations and Planning for Scientific, Engineering, and Regulatory Compliance Activities''; Attachment 4 of AP-ESH-008, ''Hazards Analysis System''; and AP-3.11Q, ''Technical Reports''. The objective of this report is to establish the requirements that provide for facility nuclear safety and a proper level of personnel safety and property protection from the effects of fire and the adverse effects of fire-extinguishing agents.

Richard C. Logan

2001-07-30T23:59:59.000Z

214

t_fired.p65  

NLE Websites -- All DOE Office Websites (Extended Search)

-MWE DEMONSTRATION OF ADVANCED -MWE DEMONSTRATION OF ADVANCED TANGENTIALLY FIRED COMBUSTION TECHNIQUES FOR THE REDUCTION OF NO X EMISSIONS SOUTHERN COMPANY SERVICES, INC. PROJECT PERFORMANCE SUMMARY CLEAN COAL TECHNOLOGY DEMONSTRATION PROGRAM JUNE 1999 DOE/FE-0397 Disclaimer This report was prepared using publically available information, including the Final Technical Report and other reports prepared pursuant to a cooperative agreement partially funded by the U.S. Department of Energy. Neither the United States Government nor any agency, employee, contractor, or representative thereof, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe upon privately

215

Coal-Fired Power Plants  

NLE Websites -- All DOE Office Websites (Extended Search)

Impacts of TMDLs on Impacts of TMDLs on Coal-Fired Power Plants April 2010 DOE/NETL-2010/1408 Disclaimer This report was prepared as an account of work sponsored by an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference therein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof. The

216

Assessment of the Plutonium Finishing Plant Criticality Alarm System U.S. Department of Energy Richland Operations Office  

SciTech Connect

At the request of the Assistant Manager for Safety and Engineering, the U.S. Department of Energy Richland Operations Office (RL) Engineering Support Division, performed an oversight review of the Plutonium Finishing Plant (PFP) nuclear Criticality Alarm System (CAS). The review was conducted to satisfy requirements and agreements associated with Defense Nuclear Facility Safety Board (DNFSB) Recommendation 2000-2, ''Vital Safety Systems.'' The PFP is managed by Fluor Hanford, Inc. for RL. The field assessment and staff interviews were conducted August 12 through August 19,2002. This was a limited scope assessment that consisted of a review of the nuclear CAS operations, maintenance, and compliance with National Consensus Standards Requirements. The main purpose of the assessment was to determine the adequacy of the existing alarm system and its associated infrastructure to support the PFP facility mission through the remaining facility lifetime. The Review Plan was modeled upon Criteria and Review Approach Documents (CRAD) developed for DNFSB Recommendation 2000-2 reviews conducted across the Hanford Site. Concerns regarding component degradation and failure, increasing numbers of occurrence reports associated with the alarm system, and reliability issues were addressed. Additionally, RL performed a review of the engineering aspects of the CAS including the functions of design authorities and aspects of systems engineering. However, the focus of the assessment was on operations, maintenance, and reliability of the CAS, associated procurement practices, adequacy of safety and engineering policies and procedures, safety documentation, and fundamental engineering practices including training, qualification, and systems engineering. This assessment revealed that the PFP CAS and its associated infrastructure, administrative procedures, and conduct of operations are generally effective. There are no imminent criticality safety issues associated with the operation of the existing CAS. The Assessment Team believes that the CAS, as it presently exists at the PFP facility, is adequate to support the remaining mission lifetime of the facility while continuing to ensure personnel safety. This conclusion is dependent upon a continued level of funding adequate to support the required maintenance and occasional system upgrade. Two findings were identified during this assessment. Additionally, the report identified eight observations and two recommendations. The assessment revealed that recent changes to OSR compliance procedures and other documents do not contain the signature of the CSR as required by procedure. Lack of appropriate approval signatures is a noncompliance with site-level procedures.

NIRIDER, L.T.

2002-10-01T23:59:59.000Z

217

Kuwaiti oil fires: Composition of source smoke  

SciTech Connect

While the Kuwaiti oil-fire smoke plumes manifested a pronounced impact on solar radiation in the Gulf region (visibility, surface temperatures, etc.), smoke plume concentrations of combustion-generated pollutants suggest that the overall chemical impact on the atmosphere of the smoke from these fires was probably much less than anticipated. Combustion in the Kuwaiti oil fires was surprisingly efficient, releasing on average more than 93% of the combusted hydrocarbon fuels as carbon dioxide (CO{sub 2}). Correspondingly, combustion-produced quantities of carbon monoxide (CO) and carbonaceous particles were low, each {approximately} 2% by weight. The fraction of methane (CH{sub 4}) produced by the fires was also relatively low ({approximately} 0.2%), but source emissions of nonmethane hydrocarbons were high ({approximately} 2%). Processes other than combustion (e.g., volatilization) probably contributed significantly to the measured in-plume hydrocarbon concentrations. Substantially, different elemental to organic carbon ratios were obtained for aerosol particles from several different types of fires/smokes. Sulfur emissions (particulate and gaseous) measured at the source fires were lower ({approximately} 0.5%) than predicted based on average sulfur contents in the crude. Sulfur dioxide measurements (SO{sub 2}) reported herein, however, were both limited in actual number and in the number of well fires sampled. Nitrous oxide (N{sub 2}O) emissions from the Kuwaiti oil fires were very low and often could not be distinguished from background concentrations. About 25-30% of the fires produced white smoke plumes that were found to be highly enriched in sodium and calcium chlorides. 18 refs., 1 fig., 4 tabs.

Cofer, W.R. III; Cahoon, D.R. [Langley Research Center, Hampton, VA (United States); Stevens, R.K.; Pinto, J.P. [Environmental Protection Agency, Research Triangle Park, NC (United States); Winstead, E.L.; Sebacher, D.I. [Hughes STX Corp., Hampton, VA (United States); Abdulraheem, M.Y. [Kuwait Environmental Protection Dept., Kuwait City (Kuwait); Al-Sahafi, M. [Ministry of Defense and Aviation, Eastern Province (Saudi Arabia); Mazurek, M.A. [Brookhaven National Lab., Upton, NY (United States); Rasmussen, R.A. [Oregon Graduate Institute of Science and Technology, Beaverton, OR (United States)] [and others

1992-09-20T23:59:59.000Z

218

Material Analysis for a Fire Assessment.  

SciTech Connect

This report consolidates technical information on several materials and material classes for a fire assessment. The materials include three polymeric materials, wood, and hydraulic oil. The polymers are polystyrene, polyurethane, and melamine- formaldehyde foams. Samples of two of the specific materials were tested for their behavior in a fire - like environment. Test data and the methods used to test the materials are presented. Much of the remaining data are taken from a literature survey. This report serves as a reference source of properties necessary to predict the behavior of these materials in a fire.

Brown, Alexander; Nemer, Martin

2014-08-01T23:59:59.000Z

219

The Research about Fire Prevention of Vehicle Refuelling Stations  

Science Journals Connector (OSTI)

Abstract Fuel oil and gas offered by vehicle refuelling stations have combustion and explosion characteristics, serious casualties and economic losses often caused by fire. The research about oil and gas fire risk, refuelling process and facilities, proposing appropriate fire prevention measures possess great significance for reducing refuelling stations fire losses, and ensuring the safety of the station and surrounding environment.

Hong-yu Zhang

2014-01-01T23:59:59.000Z

220

Fire Hazards Analysis for the Inactive Equipment Storage Sprung Structure  

SciTech Connect

The purpose of the analysis is to comprehensively assess the risk from fire within individual fire areas in relation to proposed fire protection so as to ascertain whether the fire protection objective of DOE Order 5480.1A are met. The order acknowledges a graded approach commensurate with the hazards involved.

MYOTT, C.F.

2000-02-03T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


221

Justification to remove 333 Building fire suppression system  

SciTech Connect

Justification to remove the 333 Building fire suppression system is provided. The Maximum Possible Fire Loss (MPFL) is provided (approximately $800K), potential radiological and toxicological impacts from a postulated fire are discussed, Life Safety Code issues are addressed, and coordination with the Hanford Fire Department is assured.

Benecke, M.W.

1995-12-04T23:59:59.000Z

222

Page 1 of 3 Policy: Fire Protection Equipment Policy  

E-Print Network (OSTI)

Page 1 of 3 Policy: Fire Protection Equipment Policy Responsible Party: Director, Safety and Risk The Office of Safety and Risk Management (SRM) has developed, and implemented the Fire Protection Equipment of Fire Protection Equipment throughout MSU to maintain its working order. Fire Protection Equipment

Dyer, Bill

223

(BSET) -FIRE SAFETY ENGINEERING TECHNOLOGY CURRICULUM Effective Fall 2003  

E-Print Network (OSTI)

Disasters State and Local Government Active Fire Protection Fire Safety Engr. Prob. Analysis Sem. & Year.Apps Intro to Fire Protection* (3hrs) Hydraulics and Water Distribution* (3hrs) FSET Specific Life Education* (3hrs) Building Construction* (3hrs) (not offered at UNCC) ETFS 1252 -Fire Protection Law (not

Raja, Anita

224

WASTE HANDLING BUILDING FIRE PROTECTION SYSTEM DESCRIPTION DOCUMENT  

SciTech Connect

The Waste Handling Building Fire Protection System provides the capability to detect, control, and extinguish fires and/or mitigate explosions throughout the Waste Handling Building (WHB). Fire protection includes appropriate water-based and non-water-based suppression, as appropriate, and includes the distribution and delivery systems for the fire suppression agents. The Waste Handling Building Fire Protection System includes fire or explosion detection panel(s) controlling various detectors, system actuation, annunciators, equipment controls, and signal outputs. The system interfaces with the Waste Handling Building System for mounting of fire protection equipment and components, location of fire suppression equipment, suppression agent runoff, and locating fire rated barriers. The system interfaces with the Waste Handling Building System for adequate drainage and removal capabilities of liquid runoff resulting from fire protection discharges. The system interfaces with the Waste Handling Building Electrical Distribution System for power to operate, and with the Site Fire Protection System for fire protection water supply to automatic sprinklers, standpipes, and hose stations. The system interfaces with the Site Fire Protection System for fire signal transmission outside the WHB as needed to respond to a fire emergency, and with the Waste Handling Building Ventilation System to detect smoke and fire in specific areas, to protect building high-efficiency particulate air (HEPA) filters, and to control portions of the Waste Handling Building Ventilation System for smoke management and manual override capability. The system interfaces with the Monitored Geologic Repository (MGR) Operations Monitoring and Control System for annunciation, and condition status.

J. D. Bigbee

2000-06-21T23:59:59.000Z

225

FAQS Qualification Card - Fire Protection | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fire Protection Fire Protection FAQS Qualification Card - Fire Protection A key element for the Department's Technical Qualification Programs is a set of common Functional Area Qualification Standards (FAQS) and associated Job Task Analyses (JTA). These standards are developed for various functional areas of responsibility in the Department, including oversight of safety management programs identified as hazard controls in Documented Safety Analyses (DSA). For each functional area, the FAQS identify the minimum technical competencies and supporting knowledge and skills for a typical qualified individual working in the area. FAQC-FireProtection-2007.docx Description Fire Protection Qualification Card - 2007 FAQC-FireProtection-2000.docx Description Fire Protection Qualification Card - 2000

226

Fire Protection Database | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fire Protection Database Fire Protection Database Fire Protection Database DOE O 231.1, Environment, Safety, And Health Reporting, requires the submission of an Annual Fire Protection Summary. The previous process used to collect the required data utilizes a Microsoft Access database that was downloaded, completed by the field and then sent to Headquarters for summation and analysis by engineers in Office of Sustainability Support. Data collection for the CY2013 Summary will begin Jan. 1, 2014, and a commitment has been made to the Defense Nuclear Facilities Safety Board to collect this information and make it available utilizing a standard systematic approach. This approach will be accomplished via a web based system which will allow reporting organizations to enter or edit information.

227

Fire victim helped by area programs  

NLE Websites -- All DOE Office Websites (Extended Search)

Fire victim helped by area programs Fire victim helped by area programs Fire victim helped by local nonprofit organizations A perennial helper, didn't realize that she might someday need help herself. April 3, 2012 Beatrice Dubois is grateful for the help she received from Lab-supported Beatrice Dubois is grateful for the help she received from Lab-supported, local nonprofits during her time of need. Contact Kurt Steinhaus Community Programs Office (505) 665-7370 Email Beatrice Dubois, dedicated fundraiser, assisted after home fire Beatrice Dubois has always been a strong advocate for LANL employee giving programs. Every year, she organizes a bake sale in support of the annual employee giving campaign and musters support with her coworkers for the Lab's annual holiday drive. A perennial helper, she didn't realize

228

Forest fire near Los Alamos National Laboratory  

NLE Websites -- All DOE Office Websites (Extended Search)

Forest fire near Los Alamos National Laboratory Forest fire near Los Alamos National Laboratory Forest fire near Los Alamos National Laboratory The Las Conchas fire burning in the Jemez Mountains approximately 12 miles southwest of the boundary of LANL has not entered Lab property at this time. June 26, 2011 Los Alamos National Laboratory sits on top of a once-remote mesa in northern New Mexico with the Jemez mountains as a backdrop to research and innovation covering multi-disciplines from bioscience, sustainable energy sources, to plasma physics and new materials. Los Alamos National Laboratory sits on top of a once-remote mesa in northern New Mexico with the Jemez mountains as a backdrop to research and innovation covering multi-disciplines from bioscience, sustainable energy sources, to plasma physics and new materials.

229

Fire Island Wind Project | Open Energy Information  

Open Energy Info (EERE)

Island Wind Project Island Wind Project Jump to: navigation, search Name Fire Island Wind Project Facility Fire Island Wind Project Sector Wind energy Facility Type Commercial Scale Wind Facility Status In Service Owner CIRI Developer Fire Island Wind LLC Energy Purchaser Chugach Location Fire Island AK Coordinates 61.144146°, -150.217652° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":61.144146,"lon":-150.217652,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

230

MODELING VENTILATION SYSTEM RESPONSE TO FIRE  

SciTech Connect

Fires in facilities containing nuclear material have the potential to transport radioactive contamination throughout buildings and may lead to widespread downwind dispersal threatening both worker and public safety. Development and implementation of control strategies capable of providing adequate protection from fire requires realistic characterization of ventilation system response which, in turn, depends on an understanding of fire development timing and suppression system response. This paper discusses work in which published HEPA filter data was combined with CFAST fire modeling predictions to evaluate protective control strategies for a hypothetical DOE non-reactor nuclear facility. The purpose of this effort was to evaluate when safety significant active ventilation coupled with safety class passive ventilation might be a viable control strategy.

Coutts, D

2007-04-17T23:59:59.000Z

231

Fire Protection for Laboratories Using Chemicals  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Protection Engineer Fire Protection Engineering Pacific Northwest National Laboratory Phone 509-371-7902; Cell 509-308-7658 Fax 509-371-7890 andrew.minister@pnnl.gov Questions?...

232

Fire Protection Training | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Project. The goal of this contract was to provide needed information and a method to train fire departments and other emergency responders who may be called upon to respond to...

233

ANNUAL FIRE SAFETY REPORT For Student Housing  

E-Print Network (OSTI)

and in the public areas of each of these 15 halls. The smoke detectors located in Estill Street Complex are battery, emergency lights and fire egress systems. Twenty Eight of the 50 apartments in the Ecovillage, designed

Baltisberger, Jay H.

234

Fire Protection Program Guidelines | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

14, 1995 Guidelines for Developing Medical Standards for Fire Fighters December 1994 Primer on Spontaneous Heating and Pyrophoricity (DOE-HDBK-1081-94) Oct 1994 Guidance for the...

235

Annual Fire Protection Summary Information Reporting Guide  

Energy.gov (U.S. Department of Energy (DOE))

The Department of Energy (DOE) Annual Fire Protection Program Summary continues the series started in 1972. The report annually summarizes monetary loss information sent to Headquarters by reporting elements.

236

Physically-based realistic fire rendering  

Science Journals Connector (OSTI)

Accurately rendering fires is a challenging problem due to the various subtle ways in which the electromagnetic waves interact with this complex participating medium. We present a new method for physically-based rendering of flames from detailed simulations ...

Vincent Pegoraro; Steven G. Parker

2006-09-01T23:59:59.000Z

237

POST-FIRE REVEGETATION AT HANFORD  

SciTech Connect

Range fires on the Hanford Site can have a long lasting effect on native plant communities. Wind erosion following removal of protective vegetation from fragile soils compound the damaging effect of fires. Dust storms caused by erosion create health and safety hazards to personnel, and damage facilities and equipment. The Integrated Biological Control Program (IBC) revegetates burned areas to control erosion and consequent dust. Use of native, perennial vegetation in revegetation moves the resulting plant community away from fire-prone annual weeds, and toward the native shrub-steppe that is much less likely to burn in the future. Over the past 10 years, IBC has revegetated major fire areas with good success. IBC staff is monitoring the success of these efforts, and using lessons learned to improve future efforts.

ROOS RC; JOHNSON AR; CAUDILL JG; RODRIGUEZ JM; WILDE JW

2010-01-05T23:59:59.000Z

238

Fire spread in concealed foamed plastic insulation  

Science Journals Connector (OSTI)

A test program, jointly sponsored by the Society of the Plastics Industry of Canada and the National Research Council, examined the contribution of plastic foams to fire spread in buildings. The conditions und...

Dr. W. Taylor

1983-08-01T23:59:59.000Z

239

California State Fire Marshal Information Bulletin  

Alternative Fuels and Advanced Vehicles Data Center (EERE)

California State Fire Marshal California State Fire Marshal Information Bulletin April 27, 2009 INFORMATION REGARDING PLACEMENT OF E85 FUEL DISPENSING EQUIPMENT ON STATE OWNED OR STATE LEASED FACILITIES In an effort to assist interested parties with criteria addressing E85 dispensing equipment, the Office of the State Fire Marshal (OSFM) is providing this informational bulletin. E85 is the acronym for an alcohol-blended gasoline fuel that contains between 15 to 85 percent ethanol (alcohol). Presently, there are over 10,000 gas service stations in California selling petroleum fuels (gasoline and diesel); and the number of stations dispensing E85 fuel continues to increase. The California Fire Code (CFC) and Title 19 of the California Code of Regulations (CCR) require all fuel-dispensers to be listed and labeled by an approved testing

240

Final Manuscript submitted to the Fire Safety Journal Chen et. al., Fire detection using smoke and gas sensors  

E-Print Network (OSTI)

Santa Fe, NM 87505, USA 2 Department of Fire Protection Engineering University of Maryland, College Park Protection Engineering University of Maryland, College Park, MD 20742-3031, USA Abstract Fire detectionFinal Manuscript submitted to the Fire Safety Journal Chen et. al., Fire detection using smoke

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


241

Georgia Institute of Technology Fire Watch Procedures  

E-Print Network (OSTI)

-385-1000) Area II (404-385-2000) Area III (404-385-3000) Area IV (404-385-4000) Area V (404-385-5000) II. Fire Marshal 404-894-2990 2. Georgia Tech Police Department 404-894-2500 3. Facilities-Area 1 (404 the fire watch is in effect. 2. Patrol the entire area affected by the service outage every 30 minutes

242

Wild Fire Computer Model Helps Firefighters  

ScienceCinema (OSTI)

A high-tech computer model called HIGRAD/FIRETEC, the cornerstone of a collaborative effort between U.S. Forest Service Rocky Mountain Research Station and Los Alamos National Laboratory, provides insights that are essential for front-line fire fighters. The science team is looking into levels of bark beetle-induced conditions that lead to drastic changes in fire behavior and how variable or erratic the behavior is likely to be.

Canfield, Jesse

2014-06-02T23:59:59.000Z

243

Estimating Fire Risks at Industrial Nuclear Facilities  

SciTech Connect

The Savannah River Site (SRS) has a wide variety of nuclear production facilities that include chemical processing facilities, machine shops, production reactors, and laboratories. Current safety documentation must be maintained for the nuclear facilities at SRS. Fire Risk Analyses (FRAs) are used to support the safety documentation basis. These FRAs present the frequency that specified radiological and chemical consequences will be exceeded. The consequence values are based on mechanistic models assuming specific fire protection features fail to function as designed.

Coutts, D.A.

1999-07-12T23:59:59.000Z

244

Reducing NOx in Fired Heaters and Boilers  

E-Print Network (OSTI)

-6, 2000 Reducing NOx in Fired Heaters Air Pollution Control and Boilers Keeping the environment clean Presented by Ashutosh Garg Furnace Improvements Low cost solutions for fired heaters Trace compounds ? Nitric oxides ? Carbon monoxide ? Sulfur... it is essential to estimate accurately baseline NOx emissions. ? This will establish each units current compliance status. ? Emissions ? Current excess air level ? Carbon monoxide ? Combustibles ? NOx corrected to 3% 02 314 ESL-IE-00-04-46 Proceedings...

Garg, A.

245

if it is a gas leak, do not activate building alarms, use mobile phones, hand held radios, electronic equipment or light flammable material!  

E-Print Network (OSTI)

gas leak gas leak if it is a gas leak, do not activate building alarms, use mobile phones, hand held radios, electronic equipment or light flammable material! 1. If you discover a Gas Leak, shout and check that the nearest gas isolator switch is off. 4. Evacuate the building immediately, avoiding

Hickman, Mark

246

FY 2013 EL Program Description EL Program: Fire Risk Reduction in Buildings  

E-Print Network (OSTI)

product. Structure fires and fire protection account for $170 B. To reduce the U.S. fire burden, the Fire of installed fire protection through performance-based design ($63 B) and a reduction in residential fire of structures and their contents by enabling innovative, cost-effective fire protection technologies by 2016

Bentz, Dale P.

247

NETL F 451.1/1-1, Categorical Exclusion Designation Form  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

NA Facility Support Services, Inc. FE SOD 2012 102012 - 092013 Ben Smith Morgantown, WV Morgantown Parking Garage Fire Alarm System Install and tie in Siemens fire alarm system...

248

NETL F 451.1/1-1, Categorical Exclusion Designation Form  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

NA Eagle Design, Inc. FE SOD 2012 102012 - 092013 Ben Smith Morgantown, WV Morgantown Parking Garage Fire Alarm System Install and tie in Siemens fire alarm system components...

249

NIST Technical Note 1629 Fire Fighting Tactics Under Wind Driven Fire Conditions  

E-Print Network (OSTI)

(FEMA) Assistance to Firefighters Research and Development Grant Program and the United States Fire Administrator United States Fire Administration Glenn A. Gaines, Acting Assistant Administrator U.S. Department to differences in staffing, equipment, building stock, typical weather conditions, etc. There is uniformity

Bentz, Dale P.

250

Fuel Treatment, Prescribed Fire, and Fire Restoration: Are the Benefits Worth It?  

E-Print Network (OSTI)

Fuel Treatment, Prescribed Fire, and Fire Restoration: Are the Benefits Worth It? Chairs: Susan Husari and Melanie Miller #12;Applying Simulation and Optimization to Plan Fuel Treatments at Landscape Scales1 J. Greg Jones,2 Jimmie D. Chew,2 Hans R. Zuuring3 Abstract Fuel treatment activities are analyzed

Standiford, Richard B.

251

FIRE ECOLOGY Perhaps the image most often associated with wildland fire is  

E-Print Network (OSTI)

. While it is true that fire has a great potential for the destruction of homes, wildlife, and even human that influence intensity are available fuel, moisture and temperature, fuel composition, wind, and topography. Wind increases oxygen supply, convects heat and can produce "spot fires" from fragments that blow down-wind

Johnson, Matthew

252

Thanks to Our Neighbors in Fighting Fire on INL  

NLE Websites -- All DOE Office Websites (Extended Search)

Thanks to Our Neighbors in Fighting Fire on INL Thanks to Our Neighbors in Fighting Fire on INL Idaho Bureau of Homeland Security view of the Twin Buttes Wildland fire aftermath atop the East Twin Butte. As the Department of Energy's manager at the Idaho National Laboratory, I want to commend the outstanding efforts of More than 50 firefighters and equipment battled the fire that was contained at 9:10 p.m. Mountain Standard Time July 19, 2007 An aerial scan of the area indicated the fire burned more than 9,000 acres. INL employees, and firefighting and law enforcement staff from our regional neighbors for the outstanding team-work they exhibited in controlling the Twin Buttes Fire on the INL from July 18-20. The INL Firefighters and support workers joined together with the Blackfoot Fire Department, Idaho Falls Fire Department, Shelley Fire

253

Surveillance Guide - FPS 12.2 Fire Protection and Prevention  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

FIRE PROTECTION AND PREVENTION FIRE PROTECTION AND PREVENTION 1.0 Objective The objective of this surveillance is to ensure that the contractor is implementing an effective program to minimize the potential for fires that could threaten the health and safety of the public or DOE's workers, or produce significant losses. In addition, the surveillance examines the effectiveness of steps taken to mitigate any fires that might occur. Finally, the surveillance provides an opportunity to evaluate compliance with requirements and standards for fire prevention and mitigation established by DOE. 2.0 References DOE 5480.7A, Fire Protection (or DOE O 420.1, Facility Safety) RLID 5480.7, Fire Protection (or RLID 420.1, Fire Protection) 29 CFR 1910 29 CFR 1926 DOE-HDBK-1062-96, "DOE Fire Protection Handbook (See this as well as other

254

Fire hazard analysis of the radioactive mixed waste trenchs  

SciTech Connect

This Fire Hazards Analysis (FHA) is intended to assess comprehensively the risk from fire associated with the disposal of low level radioactive mixed waste in trenches within the lined landfills, provided by Project W-025, designated Trench 31 and 34 of the Burial Ground 218-W-5. Elements within the FHA make recommendations for minimizing risk to workers, the public, and the environment from fire during the course of the operation`s activity. Transient flammables and combustibles present that support the operation`s activity are considered and included in the analysis. The graded FHA contains the following elements: description of construction, protection of essential safety class equipment, fire protection features, description of fire hazards, life safety considerations, critical process equipment, high value property, damage potential--maximum credible fire loss (MCFL) and maximum possible fire loss (MPFL), fire department/brigade response, recovery potential, potential for a toxic, biological and/or radiation incident due to a fire, emergency planning, security considerations related to fire protection, natural hazards (earthquake, flood, wind) impact on fire safety, and exposure fire potential, including the potential for fire spread between fire areas. Recommendations for limiting risk are made in the text of this report and printed in bold type. All recommendations are repeated in a list in Section 18.0.

McDonald, K.M. [Westinghouse Hanford Co., Richland, WA (United States)

1995-04-27T23:59:59.000Z

255

Interest of the Theory of Uncertain in the Dynamic LCA- Fire Methodology to Assess Fire Effects  

Science Journals Connector (OSTI)

Abstract Life Cycle Impact Assessment (LCIA) is the third phase of Life Cycle Assessment (LCA) described in ISO 14042. The purpose of LCIA is to assess a product system's life cycle inventory analysis (LCI) in order to better understand its environmental significance. However, LCIA typically excludes spatial, temporal, threshold and dose-response information, and combines emissions or activities over space and/or time. This may diminish the environmental relevance of the indicator result. The methodology, Dynamic LCA -Fire proposed in this paper to complete the International Standard ISO 14042 in the fire field, combines the LCA - Fire method with the Dispersion Numerical Model. It is based on the use of the plume model used to assess pollutant concentrations and thermal effects from fire accident scenarios. In this study, The Dynamic LCA - Fire methodology is applied to a case study for petroleum production process management.

Samia Chettouh; Rachida Hamzi; Fares Innal; Djamel Haddad

2014-01-01T23:59:59.000Z

256

Mitsubishi FGD plants for lignite fired boilers  

SciTech Connect

In order to respond to the increasing electric energy demand for sustaining economic growth, construction of coal-fired thermal power plants worldwide is indispensable. As a countermeasure for environmental pollution which otherwise may reach a serious proportion from the operation of these plants, construction of flue gas desulfurization (FGD) plants is being promoted. Among these power stations where lignite fuel is burnt, the FGD plants concerned have to be designed to cope with high gas volume and SO{sub x} concentration as well as violent fluctuations in their values caused by such features of lignite as high sulfur content, low calorific volume, and unstable properties. Mitsubishi Heavy Industries (MHI) has received construction awards for a total of seven (7) FGD plants for lignite-fired boilers in succession starting from that for CEZ as, Czech Republic followed by those for EGAT, Thailand in 1993. All these plants are presently operating satisfactorily since successful completion of their performance tests in 1996. Further, a construction award of three (3) more FGD plants for lignite-fired boilers was received from ENDESA (Spain) in 1995 which are now being outfitted and scheduled to start commercial operation in 1998. In this paper, the authors discuss the outline design of FGD plants for lignite-fired boilers based on experience of FGD plants constructed since 1970 for heavy oil--as well as black coal-fired boilers, together with items confirmed from the operation and design guideline hereafter.

Kotake, Shinichiro; Okazoe, Kiyoshi; Iwashita, Koichiro; Yajima, Satoru

1998-07-01T23:59:59.000Z

257

Externally fired gas turbine technology: A review  

Science Journals Connector (OSTI)

Abstract Externally fired heat engines were used widely since helium the industrial revolution using dirty solid fuels for example coal, due to the lack of refined fuels. However, with the availability of clean fuels, external firing mode was abandoned, except for steam power plants. Lately, with the global trend moving towards green power production, the idea of the external fired system has captured the attention again especially externally fired gas turbine (EFGT) due to its wider range of power generation and the potential of using environment friendly renewable energy sources like biomass. In this paper, a wide range of thermal power sources utilizing EFGT such as concentrated solar power (CSP), fossil, nuclear and biomass fuels are reviewed. Gas turbine as the main component of EFGT is investigated from micro scale below 1MWe to the large scale central power generation. Moreover, the different high temperature heat exchanger (HTHE) materials and designs are reviewed. Finally, the methods of improving cycle efficiency such as the externally fired combined cycle (EFCC), humidified air turbine (HAT), EFGT with fuel cells and other cycles are reviewed thoroughly.

K.A. Al-attab; Z.A. Zainal

2015-01-01T23:59:59.000Z

258

Fire Energy S L | Open Energy Information  

Open Energy Info (EERE)

Fire Energy S L Fire Energy S L Jump to: navigation, search Name Fire Energy, S.L. Place Madrid, Spain Zip 28806 Sector Solar Product Solar power developer and distributor based in Spain. Coordinates 40.4203°, -3.705774° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":40.4203,"lon":-3.705774,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

259

BlueFire Ethanol | Open Energy Information  

Open Energy Info (EERE)

BlueFire Ethanol BlueFire Ethanol Jump to: navigation, search Name BlueFire Ethanol Place Irvine, California Zip 92618 Sector Hydro Product US biofuel producer that utilises a patented concentrated acid hydrolysis technology to process various cellulosic waste materials into ethanol. Coordinates 41.837752°, -79.268594° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":41.837752,"lon":-79.268594,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

260

co-firing | OpenEI  

Open Energy Info (EERE)

co-firing co-firing Dataset Summary Description The Planning Database Project provides the UK Department of Energy and Climate Change (DECC) with regular data to track progress towards achieving EU targets for electricity generation from renewable energy (RE) sources. Extracts from the database are available each month. Information collected in the database includes: name, location and installed capacity of RE projects over 0.1MW; environmental designations; planning status; and construction status. Included here is the October 2010 Progress Datasheet, and an extract from December, 15, 2010 (i.e. Source UK Department of Energy and Climate Change (DECC) Date Released December 15th, 2010 (4 years ago) Date Updated Unknown Keywords biomass co-firing installed capacity

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


261

Ready. Aim. Fire. | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Ready. Aim. Fire. Ready. Aim. Fire. Ready. Aim. Fire. March 28, 2011 - 4:27pm Addthis John Lippert I wrote in a previous blog posting about using digital electric meters to locate "leaking" electricity-often referred to as phantom loads and vampire loads-and high electrical power consumption. In another posting I described what I'm doing to reach out in my community to get my neighbors to use these meters to locate wasteful electricity usage in their homes. Now my community will have another tool in its arsenal to combat energy waste: a thermal leak detector. Whereas the digital electric meter helps locate electricity leaks, the thermal leak detector helps locate-well, you guessed it-thermal (heat) leaks. Heating and cooling your home account for close to half of the energy use

262

NETL: Coal-Fired Power Plants (CFPPs)  

NLE Websites -- All DOE Office Websites (Extended Search)

NOx Sources NOx Sources Coal-Fired Power Plants (CFPPs) Causes of greenhouse gases, Including NOx What is NOx? Environmental Impacts NOx Sources Reduction Efforts Several greenhouse gases, including NOx, are increasing due to human activities in the following areas: Burning of fossil fuel (for example, coal-fired power plants), Logging (mainly contributes to carbon monoxide), Agriculture processes, Use of chlorofluorocarbons (CFC) in holon fire suppression and refrigeration The chart below shows the three major gases contributing to greenhouse gas emissions along with their source by sector. Annual Greenhouse Gas Emissions by Sector Note: This figure was created and copyrighted by Robert A. Rohde from published data and is part of the Global Warming Art project. This image is an original work created for Global Warming Art Permission is granted to copy, distribute and/or modify this image under either:

263

Fire-resistant pits: Reducing the probability of accidental plutonium dispersal from fuel fires  

SciTech Connect

Reductions in risk of Pu dispersal from hydrocarbon fuel fires were estimated using pool and spill fire data. Improvements in FRP temperature capabilities, on a system-independent basis, lead to the following estimated reductions in risk, using three probabilistic temperature distributions normalized to a temperature capability of 640[degree]C (the melting point of plutonium): 1OOO[degree]C - factor of 3 to 5; 11OO[degree]C - factor of 10 to 13; and 1200[degree]C - factor of 120 to 300. The above values would, of course, vary for a different normalization temperature. These values were derived to be as system-independent as possible. Incorporation of fuel fire durations or of longer time-averaging (than the two minutes employed in this study) would tend to increase these FRP improvement factors. Incorporation of propellant fires, burning metal or of combined impact/fire accidents would tend to decrease them. Further studies of fuel fire durations, particularly of a fuel fire duration model, is recommended, as is an uncertainty analysis of the temperature distributions.

Stephens, D.R.

1992-03-01T23:59:59.000Z

264

The Influence of Canadian Forest Fires on Pollutant Concentrations in the United States  

Science Journals Connector (OSTI)

...forest fires (6), that fires, together with stratospheric...intrusions, contribute a major fraction of total oxidized nitrogen...1995, 18 UTC. Forest fire release locations are marked with...18-UTC. Forest fire release locations are marked with...

Gerhard Wotawa; Michael Trainer

2000-04-14T23:59:59.000Z

265

24 Command Fire Improvement Action Program Plan  

SciTech Connect

Fluor Hanford (FH) is responsible for providing support to the Department of Energy Richland Operations Office (RL) in the implementation of the Hanford Emergency Preparedness (EP) program. During fiscal year 2000, a number of program improvements were identified from various sources including a major range fire (24 Command Fire). Evaluations of the emergency preparedness program have confirmed that it currently meets all requirements and that performance of personnel involved is good, however the desire to effect continuous improvement resulted in the development of this improvement program plan. This program plan defines the activities that will be performed in order to achieve the desired performance improvements.

GRIFFIN, G.B.

2000-12-01T23:59:59.000Z

266

Inflatable partition for fighting mine fires  

DOE Patents (OSTI)

The seal is a lightweight, inflatable, bag which may be inflated by a portable air generator and is used to seal a burning mine passage. A collapsible tube-like aperture extends through the seal and allows passage of high expansion foam through the seal in a feed tube. The foam fills the passageway and extinguishes the fire. In other embodiments, the feed tubes incorporate means to prevent collapse of the aperture. In these embodiments a shroud connects the feed tube to a foam generator. This seal allows creation of a high expansion foam fire fighting barrier even in upward sloping passages.

Conti, Ronald S. (Pittsburgh, PA); Lazzara, Charles P. (Pittsburgh, PA)

1995-01-01T23:59:59.000Z

267

Firing of pulverized solvent refined coal  

DOE Patents (OSTI)

A burner for the firing of pulverized solvent refined coal is constructed and operated such that the solvent refined coal can be fired successfully without any performance limitations and without the coking of the solvent refined coal on the burner components. The burner is provided with a tangential inlet of primary air and pulverized fuel, a vaned diffusion swirler for the mixture of primary air and fuel, a center water-cooled conical diffuser shielding the incoming fuel from the heat radiation from the flame and deflecting the primary air and fuel steam into the secondary air, and a watercooled annulus located between the primary air and secondary air flows.

Lennon, Dennis R. (Allentown, PA); Snedden, Richard B. (McKeesport, PA); Foster, Edward P. (Macungie, PA); Bellas, George T. (Library, PA)

1990-05-15T23:59:59.000Z

268

Fire Department Gets New Trucks, Saves Money | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fire Department Gets New Trucks, Saves Money Fire Department Gets New Trucks, Saves Money Fire Department Gets New Trucks, Saves Money August 27, 2013 - 12:00pm Addthis Hanford firefighters stand next to the 31-year-old chemical truck. Pictured, left to right, are Hanford Fire Lt. Robert Smith, Firefighter/Paramedic Kyle Harbert, Firefighter Don Blackburn and Capt. Sean Barajas. Hanford firefighters stand next to the 31-year-old chemical truck. Pictured, left to right, are Hanford Fire Lt. Robert Smith, Firefighter/Paramedic Kyle Harbert, Firefighter Don Blackburn and Capt. Sean Barajas. One of two of the Hanford Fire Department’s new chemical trucks. One of two of the Hanford Fire Department's new chemical trucks. Hanford firefighters stand next to the 31-year-old chemical truck. Pictured, left to right, are Hanford Fire Lt. Robert Smith, Firefighter/Paramedic Kyle Harbert, Firefighter Don Blackburn and Capt. Sean Barajas.

269

Fire is the Enemy of Field and Forest  

NLE Websites -- All DOE Office Websites (Extended Search)

Fire is the Enemy of Field and Forest Fire is the Enemy of Field and Forest Nature Bulletin No. 10 April 14, 1945 Forest Preserve District of Cook County Clayton F. Smith, President Roberts Mann, Superintendent of Conservation FIRE IS THE ENEMY OF FIELD AND FOREST There have been 112 fires in the forest preserves since January 1, burning over 612 acres, including 150 acres of fine woodland and young forest plantings. There need not have been ONE if people only understood the damage done by forest and grass fires. Every spring and every fall, thousands of acres of prairie and vacant subdivisions are burnt off. Some of these fires jump over into forest preserves. Many fires start inside the preserves, or along their highway borders, from matches, cigarettes or pipe bottle thrown aside by careless people. Some start from picnic fires. A few are kindled by boys who have seen their parents or neighbors do the same thing at home.

270

The Role of Convective Outflow in the Waldo Canyon Fire  

Science Journals Connector (OSTI)

The meteorological conditions associated with the rapid intensification and spread of the catastrophic Waldo Canyon fire on 26 June 2012 are studied. The fire caused two fatalities, destroyed 347 homes in Colorado Springs, and resulted in ...

Richard H. Johnson; Russ S. Schumacher; James H. Ruppert Jr.; Daniel T. Lindsey; Julia E. Ruthford; Lisa Kriederman

2014-09-01T23:59:59.000Z

271

Multi-Function Fuel-Fired Heat Pump Research Project  

Energy.gov (U.S. Department of Energy (DOE))

The U.S. Department of Energy is currently conducting research into multi-function fuel-fired heat pumps. Multi-function fuel-fired heat pump technology has the potential for a significant impact...

272

Savanna and shrubland fire behavior modeling in South Texas  

E-Print Network (OSTI)

The vegetation of South Texas has changed from mesquite savanna to mixed mesquite/acacia (Prosopis/Acacia) shrubland over the last hundred years. Fire reduction due to lack of fine fuel and suppression of fires is cited as reasons...

Streeks, Tamara Jean

2012-06-07T23:59:59.000Z

273

Management of Imported Fire Ants in Cattle Production Systems  

E-Print Network (OSTI)

This publication can help ranch managers develop integrated pest management plans for managing fire ant problems in cattle operations. It covers the specifics of managing fire ants in hay pastures and rangelands, around farm ponds, and near...

Fuchs, Thomas W.; Drees, Bastiaan M.

2004-03-31T23:59:59.000Z

274

Initial Joint Review, Wildland Fire Safety at DOE Sites - December...  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fire Safety Enchancements - Jan 19, 2001 Audit Report: IG-0760 Type B Accident Investigation, Response to the 24 Command Wildland Fire on the Hanford Site, June 27-July 1, 200...

275

Fire Protection Program Assessment, Building 9116- Y12 Plant, Oak Ridge, Tennessee  

Energy.gov (U.S. Department of Energy (DOE))

This assessment is intended to evaluate the fire hazards, life safety and fire protection features inherent in Building 9116.

276

Initial Joint Review of Wildland Fire Safety at DOE Sites  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

December December 2000 A Report to the Secretary of Energy Initial Joint Review of Wildland Fire Safety at DOE Sites OVERSIGHT Table of Contents Executive Summary................................................................................... 1 1.0 Introduction ......................................................................................... 5 2.0 Summary of Review Results .............................................................. 8 2.1 Wildland Fire Management Policy ............................................. 8 2.2 Fire/Emergency Hazards Assessments ....................................... 9 2.3 Wildland Fire Prevention and Response .................................. 11 2.4 Offsite Interfaces and Agreements ........................................... 13 2.5 Feedback and Continuous Improvement

277

Understanding Corrosion Mechanisms in Oxy-Fired Systems  

NLE Websites -- All DOE Office Websites (Extended Search)

Understanding Corrosion Mechanisms Understanding Corrosion Mechanisms in Oxy-Fired Systems Background In Oxy-fired Systems, oxygen is used for combustion of coal rather than air. It produces flue (exhaust) gas with concentrated carbon dioxide (CO2), thus facilitating its capture and sequestration. An added benefit of oxy-firing is that it reduces or eliminates nitrogen oxide (NO X ) emissions. Additional energy is required with oxy-firing and subsequent carbon sequestration

278

Review of the Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System, October 2012  

NLE Websites -- All DOE Office Websites (Extended Search)

Department of Energy Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System August 2012 October 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy Table of Contents 1.0 Purpose................................................................................................................................................... 1 2.0 Assessment Background ........................................................................................................................ 1 3.0 Scope...................................................................................................................................................... 2

279

Review of the Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System, October 2012  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Department of Energy Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System August 2012 October 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy Table of Contents 1.0 Purpose................................................................................................................................................... 1 2.0 Assessment Background ........................................................................................................................ 1 3.0 Scope...................................................................................................................................................... 2

280

Colorado State Forest Service SB09-020 --Responsibility for Responding to Wildland Fires  

E-Print Network (OSTI)

SB09-020 clarifies the roles and responsibilities of fire protection districts, county sheriffs and responsibilities progressively from local jurisdiction to fire protection district jurisdiction to county: · The fire chief of the fire protection district is responsible for all fires, including wildland fires

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


281

Retrofitted coal-fired firetube boiler and method employed therewith  

DOE Patents (OSTI)

A coal-fired firetube boiler and a method for converting a gas-fired firetube boiler to a coal-fired firetube boiler, the converted boiler including a plurality of combustion zones within the firetube and controlled stoichiometry within the combustion zones.

Wagoner, Charles L. (Tullahoma, TN); Foote, John P. (Tullahoma, TN)

1995-01-01T23:59:59.000Z

282

Retrofitted coal-fired firetube boiler and method employed therewith  

DOE Patents (OSTI)

A coal-fired firetube boiler and a method for converting a gas-fired firetube boiler to a coal-fired firetube boiler are disclosed. The converted boiler includes a plurality of combustion zones within the firetube and controlled stoichiometry within the combustion zones. 19 figs.

Wagoner, C.L.; Foote, J.P.

1995-07-04T23:59:59.000Z

283

Synthesis and Summary: Land Use Decisions and Fire Risk1  

E-Print Network (OSTI)

was spent in fire suppres- sion. The bill for all costs and damages amounted to more than $1 billion. Given of fuel management and fire protection. The complexity of watershed manage- ment was defined growth on fuel management and fire protection, concerns stated or implied in all presentations. Jim Davis

Standiford, Richard B.

284

FireViz : a personal firewall visualizing tool  

E-Print Network (OSTI)

In this thesis, I present FireViz, a personal firewall visualizing tool. FireViz visually displays activities of a personal firewall in real time. The primary goal of FireViz is to educate typical computer users of the ...

Sharma, Nidhi

2005-01-01T23:59:59.000Z

285

Airborne Studies of the Smoke from the Kuwait Oil Fires  

Science Journals Connector (OSTI)

...smoke from the Kuwait fires produced a small-scale...Concluding Remarks The airborne studies of the smoke from the Kuwait fires provided a large...1. Uncontrolled releases of oil began in January...and the oil field fires began in late February...Zimmerman). 3. An airborne study of the smoke...

Peter V. Hobbs; Lawrence F. Radke

1992-05-15T23:59:59.000Z

286

A Spatial Planning and Analysis System for Wildland Fire Management  

E-Print Network (OSTI)

STARFIRE 11/29/2011 A Spatial Planning and Analysis System for Wildland Fire Management Welcome is an advanced and powerful spatial fire management planning and analysis system which is designed to provide visual and analytic support for fire management planning, decisions and communication. The system

287

Phase 2 fire hazard analysis for the canister storage building  

SciTech Connect

The fire hazard analysis assesses the risk from fire in a facility to ascertain whether the fire protection policies are met. This document provides a preliminary FHA for the CSB facility. Open items have been noted in the document. A final FHA will be required at the completion of definitive design, prior to operation of the facility.

Sadanaga, C.T., Westinghouse Hanford

1996-07-01T23:59:59.000Z

288

Coal-fired generation staging a comeback. 2nd ed.  

SciTech Connect

The report is an overview of the renewed U.S. market interest in coal-fired power generation. It provides a concise look at what is driving interest in coal-fired generation, the challenges faced in implementing coal-fired generation projects, and the current and future state of coal-fired generation. Topics covered in the report include: An overview of coal-fired generation including its history, the current market environment, and its future prospects; An analysis of the key business factors that are driving renewed interest in coal-fired generation; An analysis of the challenges that are hindering the implementation of coal-fired generation projects; A description of coal-fired generation technologies; A review of the economic drivers of coal-fired generation project success; An evaluation of coal-fired generation versus other generation technologies; A discussion of the key government initiatives supporting new coal-fired generation; and A listing of planned coal-fired generation projects. 13 figs., 12 tabs., 1 app.

NONE

2007-07-01T23:59:59.000Z

289

Procedure No 400.04 Subject: Fire Protection & Life Safety  

E-Print Network (OSTI)

Procedure No 400.04 Subject: Fire Protection & Life Safety Reference: OSHA CFR1910.157, Subpart L egress time and protection from fire exposure. DEFINITIONS Combustibles: A material, such as paper, wood protection to the opening when closed. Fire Watch: A person or persons assigned to an area for the purpose

Karsai, Istvan

290

Estimating Hydrologic Values for Planning Wildland Fire Protection1  

E-Print Network (OSTI)

Estimating Hydrologic Values for Planning Wildland Fire Protection1 Henry W. Anderson and Clinton B- quencies under various levels of protection in the area, and (c) the effects of those fires-26, 1981, San Diego, California. 2 Consulting Hydrologist, Lafayette, California, Assistant Chief of Fire

Standiford, Richard B.

291

Structural stability of polymer matrix composite panels in fire  

E-Print Network (OSTI)

of a quantitative methodology for fire protection design is discussed in the context of the analyses and the experiments. Design diagrams are constructed to design mechanical loads for given fire protection time, and on the opposite, to design fire protection time for given mechanical loads. ? 2009 Elsevier Ltd. All rights

Dao, Ming

292

Rules for fire Protection Ludwig-Maximilians-University  

E-Print Network (OSTI)

Rules for fire Protection of the Ludwig-Maximilians-University (except Gro?hadern and City Center in the university buildings the principles contained in the rules for fire protection must be observed without exception.Violations of these rules for fire protection may have legal consequences and may be prosecuted

Kersting, Roland

293

6 THE SINGAPORE ENGINEER Feb 2009 Fire Protection  

E-Print Network (OSTI)

6 · THE SINGAPORE ENGINEER Feb 2009 Fire Protection Smoke Control by Pressurisation in Stairwells during fires. In this regard, it is the `across door' portion of the stack effect pressure difference that is directly related to smoke migration and control. A fire located on a lower floor can cause substantial

Miller, Richard S.

294

Carbon dioxide emission during forest fires ignited by lightning  

E-Print Network (OSTI)

In this paper we developed the model for the carbon dioxide emission from forest fire. The master equation for the spreading of the carbon dioxide to atmosphere is the hyperbolic diffusion equation. In the paper we study forest fire ignited by lightning. In that case the fores fire has the well defined front which propagates with finite velocity.

Magdalena Pelc; Radoslaw Osuch

2009-03-31T23:59:59.000Z

295

Wildland fire emissions, carbon, and climate: Emission factors Shawn Urbanski  

E-Print Network (OSTI)

Wildland fire emissions, carbon, and climate: Emission factors Shawn Urbanski Missoula Fire burning Greenhouse gases Emission factors a b s t r a c t While the vast majority of carbon emitted wildland fire greenhouse gas and aerosol (organic aerosol (OA) and black carbon (BC)) emission inventories

296

Using Satellite Fire Detection to Calibrate Components of the Fire Weather Index System in Malaysia and Indonesia  

Science Journals Connector (OSTI)

Vegetation fires have become an increasing problem in tropical environments as a consequence of socioeconomic pressures and subsequent land-use change. In response, fire management systems are being developed. Th...

Caren C. Dymond; Robert D. Field; Orbita Roswintiarti; Guswanto

2005-04-01T23:59:59.000Z

297

Simulating Historic Landscape Patterns of Fire in the Southern Appalachian Mountains: Implications for Fire History and Management  

E-Print Network (OSTI)

Fire suppression policies implemented in the early 20th century led to a decrease in fire-associated species and ecosystems in the southern Appalachian Mountains. As managers work towards restoration, a greater understanding of the pre...

Gass, Ellen R

2014-05-21T23:59:59.000Z

298

Wildland Fire Management Plan for Brookhaven National Laboratory  

SciTech Connect

This Wildland Fire Management Plan (FMP) for Brookhaven National Lab (BNL) updates the 2003 plan incorporating changes necessary to comply with DOE Order 450.1 and DOE P 450.4, Federal Wildland Fire Management Policy and Program Review; Wildland and Prescribed Fire Management Policy and implementation Procedures Reference Guide. This current plan incorporates changes since the original draft of the FMP that result from new policies on the national level. This update also removes references and dependence on the U.S. Fish & Wildlife Service and Department of the Interior, fully transitioning Wildland Fire Management responsibilities to BNL. The Department of Energy policy for managing wildland fires requires that all areas, managed by the DOE and/or its various contractors, that can sustain fire must have a FMP that details fire management guidelines for operational procedures associated with wild fire, operational, and prescribed fires. Fire management plans provide guidance on fire preparedness, fire prevention, wildfire suppression, and the use of controlled, 'prescribed' fires and mechanical means to control the amount of available combustible material. Values reflected in the BNL Wildland FMP include protecting life and public safety; Lab properties, structures and improvements; cultural and historical sites; neighboring private and public properties; and endangered, threatened, and species of concern. Other values supported by the plan include the enhancement of fire-dependent ecosystems at BNL. This FMP will be reviewed periodically to ensure the fire program advances and evolves with the missions of the DOE and BNL. This Fire Management Plan is presented in a format that coverers all aspects specified by DOE guidance documents which are based on the national template for fire management plans adopted under the National Fire Plan. The DOE is one of the signatory agencies on the National Fire Plan. This FMP is to be used and implemented for the entire BNL site including the Upton Reserve and has been reviewed by, The Nature Conservancy, New York State Department of Environmental Conservation Forest Rangers, and DOE, as well as appropriate BNL emergency services personnel. The BNL Fire Department is the lead on wildfire suppression. However, the BNL Natural Resource Manager will be assigned to all wildland fires as technical resource advisor.

Green,T.

2009-10-23T23:59:59.000Z

299

Carbon Dioxide Capture from Coal-Fired  

E-Print Network (OSTI)

Carbon Dioxide Capture from Coal-Fired Power Plants: A Real Options Analysis May 2005 MIT LFEE 2005 are valued using the "real options" valuation methodology in an uncertain carbon dioxide (CO2) price (baseline IGCC), and IGCC with pre-investments that make future retrofit for CO2 capture less expensive (pre

300

Direct fired absorption machine flue gas recuperator  

DOE Patents (OSTI)

A recuperator which recovers heat from a gas, generally the combustion gas of a direct-fired generator of an absorption machine. The recuperator includes a housing with liquid flowing therethrough, the liquid being in direct contact with the combustion gas for increasing the effectiveness of the heat transfer between the gas and the liquid.

Reimann, Robert C. (Lafayette, NY); Root, Richard A. (Spokane, WA)

1985-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


301

UF{sub 6} cylinder fire test  

SciTech Connect

With the increasing number of nuclear reactors for power generation, there is a comparable increase in the amount of UF{sub 6} being transported. Likewise, the probability of having an accident involving UF{sub 6}-filled cylinders also increases. Accident scenarios which have been difficult to assess are those involving a filled UF{sub 6} cylinder subjected to fire. A study is underway at the Oak Ridge K-25 Site, as part of the US DOE Enrichment Program, to provide empirical data and a computer model that can be used to evaluate various cylinder-in-fire scenarios. It is expected that the results will provide information leading to better handling of possible fire accidents as well as show whether changes should be made to provide different physical protection during shipment. The computer model being developed will be capable of predicting the rupture of various cylinder sizes and designs as well as the amount of UF{sub 6}, its distribution in the cylinder, and the conditions of the fire.

Park, S.H. [Oak Ridge K-25 Site, Oak Ridge, TN (United States)

1991-12-31T23:59:59.000Z

302

William Brownrigg's papers on fire-damps  

Science Journals Connector (OSTI)

...they were found was connected to a second pit through which air was circulated to vent...it would be exhausted by the fires that burn everywhere. He suspected that the pabulum...An Account of the damp air in a coal-pit of Sir James Lowther, Bart. Sunk within...

2010-01-01T23:59:59.000Z

303

Blank fire configuration for automatic pistol  

DOE Patents (OSTI)

A pistol configured to fire blank cartridges includes a modified barrel with a breech portion connected to an aligned inner sleeve. Around the inner sleeve, there is disposed an outer sleeve having a vent therein through which the cartridge discharges. The breech portion is connected to a barrel anchor to move backward in a slight arc when the pistol is fired. A spring retention rod projects from the barrel anchor and receives a shortened recoil spring therearound which recoil spring has one end abutting a stop on the barrel anchor and the other end in abutment with the end of a spring retaining cup. The spring retaining cup is engaged by a flange projecting from a slide so that when the pistol is fired, the slide moves rearwardly against the compression of the spring to eject the spent cartridge and then moves forwardly under the urging of the spring to load a fresh cartridge into the breech portion. The spring then returns all of the slidable elements to their initial position so that the pistol may again be fired.

Teague, Tommy L. (Albuquerque, NM)

1990-01-01T23:59:59.000Z

304

Fire and fire surrogate treatment effects on leaf litter arthropods in a western Sierra Nevada mixed-conifer forest  

E-Print Network (OSTI)

mixed-conifer forest Kyle O. Apigian *, Donald L. Dahlsten ä , Scott L. Stephens Department to coexist. We conclude that the use of fire and fire surrogate treatments in Sierran mixed-conifer forests will be important in restoring ecosystem processes and reducing fire risk in our conifer forests (Stephens

Stephens, Scott L.

305

Is the situation and immediate threat to life and health? Spill/Leak/Release Medical Emergency Fire or Flammable Gas Spill/Leak/Release Medical Emergency Fire or Flammable Gas Chemical Odor? Possible Fire / Natural Gas  

E-Print Network (OSTI)

? Possible Fire / Natural Gas (including chemicals and bio agents") (not including chemicals or bio agents Fire or Flammable Gas Spill/Leak/Release Medical Emergency Fire or Flammable Gas Chemical Odor

306

Electrical Sitchgear Building No. 5010-ESF Fire Hazards Technical Report  

SciTech Connect

The purpose of this Fire Hazards Analysis Technical Report (hereinafter referred to as Technical Report) is to assess the risk from fire within individual fire areas to ascertain whether the U.S. Department of Energy (DOE) fire safety objectives are met. The objectives, identified in DOE Order 420.1, Change 2, Fire Safety, Section 4.2, establish requirements for a comprehensive fire and related hazards protection program for facilities sufficient to minimize the potential for: (1) The occurrence of a fire or related event; (2) A fire that causes an unacceptable on-site or off-site release of hazardous or radiological material that will threaten the health and safety of the employees, the public, and the environment; (3) Vital DOE programs suffering unacceptable interruptions as a result of fire and related hazards; (4) Property losses from a fire and related events exceeding defined limits established by DOE; and (5) Critical process controls and safety class systems being damaged as a result of a fire and related event.

N.M. Ruonavaara

2001-05-08T23:59:59.000Z

307

Approval Memorandum, Additional Qualification Courses of Fire - December  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Approval Memorandum, Additional Qualification Courses of Fire - Approval Memorandum, Additional Qualification Courses of Fire - December 13, 2011 Approval Memorandum, Additional Qualification Courses of Fire - December 13, 2011 December 13, 2011 Request approval of revised courses of fire. As indicated in the background section of the memorandum, subjects: Newly Developed SECURITY Policy Officer/Special Response Team Qualification Courses of Fire, dated October 12,2011, members of the Department of Energy (DOE) Firearms Policy Panel, DOE Training Managers Working Group, the National Nuclear Security Administration, and the DOE National Training Center have devloped , reviewed and revised the following courses of fire (attached) for inclusion in the Protective Force Firearms Qualification Courses Manual. The courses of fire pertain to the incubent Security Police

308

Fire Hazards Analysis for the 200 Area Interim Storage Area  

SciTech Connect

This documents the Fire Hazards Analysis (FHA) for the 200 Area Interim Storage Area. The Interim Storage Cask, Rad-Vault, and NAC-1 Cask are analyzed for fire hazards and the 200 Area Interim Storage Area is assessed according to HNF-PRO-350 and the objectives of DOE Order 5480 7A. This FHA addresses the potential fire hazards associated with the Interim Storage Area (ISA) facility in accordance with the requirements of DOE Order 5480 7A. It is intended to assess the risk from fire to ensure there are no undue fire hazards to site personnel and the public and to ensure property damage potential from fire is within acceptable limits. This FHA will be in the form of a graded approach commensurate with the complexity of the structure or area and the associated fire hazards.

JOHNSON, D.M.

2000-01-06T23:59:59.000Z

309

FIREPLUME model for plume dispersion from fires: Application to uranium hexafluoride cylinder fires  

SciTech Connect

This report provides basic documentation of the FIREPLUME model and discusses its application to the prediction of health impacts resulting from releases of uranium hexafluoride (UF{sub 6}) in fires. The model application outlined in this report was conducted for the Draft Programmatic Environmental Impact Statement for Alternative Strategies for the Long-Term Management and Use of Depleted UF{sub 6}. The FIREPLUME model is an advanced stochastic model for atmospheric plume dispersion that predicts the downwind consequences of a release of toxic materials from an explosion or a fire. The model is based on the nonbuoyant atmospheric dispersion model MCLDM (Monte Carlo Lagrangian Dispersion Model), which has been shown to be consistent with available laboratory and field data. The inclusion of buoyancy and the addition of a postprocessor to evaluate time-varying concentrations lead to the current model. The FIREPLUME model, as applied to fire-related UF{sub 6} cylinder releases, accounts for three phases of release and dispersion. The first phase of release involves the hydraulic rupture of the cylinder due to heating of the UF{sub 6} in the fire. The second phase involves the emission of material into the burning fire, and the third phase involves the emission of material after the fire has died during the cool-down period. The model predicts the downwind concentration of the material as a function of time at any point downwind at or above the ground. All together, five fire-related release scenarios are examined in this report. For each scenario, downwind concentrations of the UF{sub 6} reaction products, uranyl fluoride and hydrogen fluoride, are provided for two meteorological conditions: (1) D stability with a 4-m/s wind speed, and (2) F stability with a 1-m/s wind speed.

Brown, D.F.; Dunn, W.E. [Univ. of Illinois, Champaign-Urbana, IL (United States). Dept. of Mechanical Engineering; Policastro, A.J.; Maloney, D. [Argonne National Lab., IL (United States)

1997-06-01T23:59:59.000Z

310

Kuwait summons more fire fighting teams  

SciTech Connect

Kuwait is calling in more muscle to help kill its wild wells. This paper reports on the latest action in Kuwait, the leasing of well control contracts to Abel Engineering/Well Control Inc., Houston, and China Petroleum Engineering Construction Co. (CPEC). Abel is the sixth North American well control company called to the scene, while CPEC is the first summoned from the East. In addition, the service responsible for combating well fires and blowouts in the U.S.S.R.'s Azerbaijan oil fields signed an agreement with Kuwait's government, apparently involving a contract valued at more than $100 million, to extinguish fires at 150 Kuwaiti wells, reported Eastern Bloc Energy, a publication of Eastern Bloc Research Ltd., Newton Kyme, U.K. More help likely is on the way.

Not Available

1991-08-05T23:59:59.000Z

311

Chapter 3 - Coal-fired Power Plants  

Science Journals Connector (OSTI)

Abstract Coal provides around 40% of the worlds electricity, more than any other source. Most modern coal-fired power stations burn pulverized coal in a boiler to raise steam for a steam turbine. High efficiency is achieved by using supercritical boilers made of advanced alloys that produce high steam temperatures, and large, high-efficiency steam turbines. Alternative types of coal-fired power plants include fluidized bed boilers that can burn a variety of poor fuels, as well as coal gasifiers that allow coal to be turned into a combustible gas that can be burned in a gas turbine. Emissions from coal plants include sulfur dioxide, nitrogen oxide, and trace metals, all of which must be controlled. Capturing carbon dioxide from a coal plant is also under consideration. This can be achieved using post-combustion capture, a pre-combustion gasification process, or by burning coal in oxygen instead of air.

Paul Breeze

2014-01-01T23:59:59.000Z

312

Assessment of fire pump caisson integrity  

SciTech Connect

Fire pump and water lift caissons often suffer damage due to combinations of corrosion, fatigue and repeated impacts. These effects have been investigated in the context of integrity evaluations for a number of caissons and a number of contributory factors have been identified and investigated. The paper describes these investigations in some detail, as well as the mitigation measures identified and adopted to eliminate the problem.

Ellinas, C.P. [Advanced Mechanics and Engineering Ltd., Croydon (United Kingdom); Weir, T. [Total Oil Marine, Aberdeen (United Kingdom)

1995-12-31T23:59:59.000Z

313

Resistance after firing protected electric match  

DOE Patents (OSTI)

An electric match having electrical leads embedded in flame-producing compound is protected against an accidental resistance across the leads after firing by a length of heat-shrinkable tubing encircling the match body and having a skirt portion extending beyond the leads. The heat of the burning match and an adjacent thermal battery causes the tubing to fold over the end of the match body, covering the ends of the leads and protecting them from molten pieces of the battery.

Montoya, Arsenio P. (Albuquerque, NM)

1981-11-10T23:59:59.000Z

314

WILDLAND FIRE MANAGEMENT PLAN FOR BROOKHAVEN NATIONAL LABORATORY.  

SciTech Connect

This Wildland Fire Management Plan (FMP) for Brookhaven National Lab (BNL) and the Upton Ecological and Research Reserve (Upton Reserve) is based on the U.S. Fish & Wildlife Service (FWS) fire management planning procedures and was developed in cooperation with the Department of Energy (DOE) by Brookhaven Science Associates. As the Upton Reserve is contained within the BNL 5,265-acre site, it is logical that the plan applies to both the Upton Reserve and BNL. The Department of the Interior policy for managing wildland fires requires that all areas managed by FWS that can sustain fire must have an FMP that details fire management guidelines for operational procedures and specifies values to be protected or enhanced. Fire management plans provide guidance on fire preparedness, fire prevention, wildfire suppression, and the use of controlled, ''prescribed'' fires and mechanical means to control the amount of available combustible material. Values reflected in the BNL/Upton Reserve Wildland FMP include protecting life and public safety; Lab properties, structures and improvements; cultural and historical sites; neighboring private and public properties; and endangered and threatened species and species of concern. Other values supported by the plan include the enhancement of fire-dependent ecosystems at BNL and the Upton Reserve. This FMP will be reviewed periodically to ensure the fire program advances and evolves with the missions of FWS, BNL, and the Upton Reserve. This Fire Management Plan is a modified version of the Long Island National Wildlife Refuge Complex Fire plan (updated in 2000), which contains all FWS fire plan requirements and is presented in the format specified by the national template for fire management plans adopted under the National Fire Plan. The DOE is one of the signatory agencies on the National Fire Plan. FWS shall be, through an Interagency Agreement dated November 2000 (Appendix C), responsible for coordinating and implementing prescribed burns and fuel reduction projects in the Upton Reserve. Prescribed fire and fuel reduction in locations outside the Upton Reserve will be coordinated through the Natural Resource Management Program at BNL, and done in consultation with FWS. This FMP is to be used and implemented for the entire BNL site including the Upton Reserve and has been reviewed by FWS, The Nature Conservancy, New York State Department of Environmental Conservation Forest Rangers, and DOE, as well as appropriate BNL emergency services personnel.

ENVIRONMENTAL AND WASTE MANAGEMENT SERVICES DIVISION

2003-09-01T23:59:59.000Z

315

Fire exposure of empty 30B cylinders  

SciTech Connect

Cylinders for UF{sub 6} handling, transport, and storage are designed and built as unfired pressure vessels under ASME Boiler and Pressure Vessel Code criteria and standards. They are normally filled and emptied while UF{sub 6} is in its liquid phase. Transport cylinders such as the Model 30B are designed for service at 200 psi and 250{degrees}F, to sustain the process conditions which prevail during filling or emptying operations. While in transport, however, at ambient temperature the UF{sub 6} is solid, and the cylinder interior is well below atmospheric pressure. When the cylinders contain isotopically enriched product (above 1.0 percent U-235), they are transported in protective overpacks which function to guard the cylinders and their contents against thermal or mechanical damage in the event of possible transport accidents. Two bare Model 30B cylinders were accidentally exposed to a storage warehouse fire in which a considerable amount of damage was sustained by stored materials and the building structure, as well as by the cylinder valves and valve protectors. The cylinders were about six years old, and had been cleaned, inspected, hydrotested, and re-certified for service, but were still empty at the time of the fire. The privately-owned cylinders were transferred to DOE for testing and evaluation of the fire damage.

Ziehlke, K.T. [MJB Technical Associates, Inc., Knoxville, TN (United States)

1991-12-31T23:59:59.000Z

316

Surface Fire Hazards Analysis Technical Report-Constructor Facilities  

SciTech Connect

The purpose of this Fire Hazards Analysis Technical Report (hereinafter referred to as Technical Report) is to assess the risk from fire within individual fire areas to ascertain whether the U.S. Department of Energy (DOE) fire safety objectives are met. The objectives identified in DOE Order 420.1, Change 2, Facility Safety, Section 4.2, establish requirements for a comprehensive fire and related hazards protection program for facilities sufficient to minimize the potential for: The occurrence of a fire or related event; A fire that causes an unacceptable on-site or off-site release of hazardous or radiological material that will threaten the health and safety of employees, the public, or the environment; Vital DOE programs suffering unacceptable interruptions as a result of fire and related hazards; Property losses from a fire and related events exceeding defined limits established by DOE; and Critical process controls and safety class systems being damaged as a result of a fire and related events.

R.E. Flye

2000-10-24T23:59:59.000Z

317

Fire Protection System Account Request Form | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fire Protection System Account Request Form Fire Protection System Account Request Form Fire Protection System Account Request Form December 2, 2010 Account request form used to obtain user credentials for the Fire Protection Database To obtain a user id and password to access the Fire Protection system, please complete the form, save the file and email it to HSSUserSupport@hq.doe.gov or print and fax it to 301-903-9823. We will provide a username and password to new account holders. Please allow several business days to process your account request. When your request is approved, you will be contacted with your account information. Fire Protection System Account Request Form More Documents & Publications CAIRS Registration Form Microsoft Word - PARS II User Acct Access Guide.rtf PARS Domain User Maintenance Function Support Team Guide (v

318

Real time simulation of 2007 Santa Ana fires  

E-Print Network (OSTI)

There are many wildfire behaviors of increasing relevance that are outside the forecast capabilities of even the most sophisticated operational fire spread and fire behavior model. The limitations of the operational models are due primarily to their inability to represent coupled fire-atmosphere interactions. Coupled wildfire-atmosphere models are physics-based fluid-dynamical prognostic models of wildfire spread and behavior that attempt an almost complete representation of fire-atmosphere interactions. This level of fidelity however means that these models cannot be used operationally. The reason is that, despite ever increasing computational resources, the complexity and range of processes and scales (1 mm to 100 km) involved in this modeling approach make computational costs prohibitively expensive. In this study we propose an intermediate approach. A physics-based coupled atmosphere-fire model is used to resolve the large-scale and local weather as well as the atmosphere-fire interactions, while combusti...

Kochanski, A K; Krueger, S K; Mandel, J; Beezley, J D

2012-01-01T23:59:59.000Z

319

What is the problem? The cost of fire in the U.S. is growing. In  

E-Print Network (OSTI)

understanding of fire behavior, which hinders the develop- ment of innovative fire protection. Current Protection generation of standards, codes, and tech- nologies that address the U.S. fire problem. Measurement innovative fire protection M e a s u r e M e n t s c i e n c e f o r innovative fire protection challenging

Magee, Joseph W.

320

Wildland fire emissions, carbon, and climate: U.S. emissions inventories Narasimhan K. Larkin a,  

E-Print Network (OSTI)

Wildland fire emissions, carbon, and climate: U.S. emissions inventories Narasimhan K. Larkin a: Fire emissions Emissions inventories Greenhouse gases a b s t r a c t Emissions from wildland fire fire emissions change considerably due to fluctuations from year to year with overall fire season

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


321

10. Vorbeugender Brand-und Gefahrenschutz / Fire prevention  

E-Print Network (OSTI)

in den Gebäuden / Passiv Fire Protection 10.1.2.1. Löscheinrichtungen in den Gebäuden / Extinguishing / Structural fire protection10.2.1.1. ?berprüfung von Bauanträgen 10.2.1.2. ?berprüfung von Umwidmungen 10.2.2. Anlagentechnischer Brand- und Gefahrenschutz von Flächen / Passiv Fire Protection 10.2.2.1. Löscheinrichtungen auf

Berlin,Technische Universität

322

An assessment of fire vulnerability for aged electrical relays  

SciTech Connect

There has been some concern that, as nuclear power plants age, protective measures taken to control and minimize the impact of fire may become ineffective, or significantly less effective, and hence result in an increased fire risk. One objective of the Fire Vulnerability of Aged Electrical Components Program is to assess the effects of aging and service wear on the fire vulnerability of electrical equipment. An increased fire vulnerability of components may lead to an overall increase in fire risk to the plant. Because of their widespread use in various electrical safety systems, electromechanical relays were chosen to be the initial components for evaluation. This test program assessed the impact of operational and thermal aging on the vulnerability of these relays to fire-induced damage. Only thermal effects of a fire were examined in this test program. The impact of smoke, corrosive materials, or fire suppression effects on relay performance were not addressed in this test program. The purpose of this test program was to assess whether the fire vulnerability of electrical relays increased with aging. The sequence followed for the test program was to: identify specific relay types, develop three fire scenarios, artificially age several relays, test the unaged and aged relays in the fire exposure scenarios, and compare the results. The relays tested were Agastat GPI, General Electric (GE) HMA, HGA, and HFA. At least two relays of each type were artificially aged and at least two relays of each type were new. Relays were operationally aged by cycling the relay under rated load for 2,000 operations. These relays were then thermally aged for 60 days with their coil energized.

Vigil, R.A. [Sandia National Labs., Albuquerque, NM (United States)]|[Science and Engineering Associates, Inc., Albuquerque, NM (United States); Nowlen, S.P. [Sandia National Labs., Albuquerque, NM (United States)

1995-03-01T23:59:59.000Z

323

Independent Oversight Review of the Fire Protection Program and...  

Office of Environmental Management (EM)

Tanks NFPA National Fire Protection Association OFI Opportunity for Improvement OREM Oak Ridge Environmental Management ORNL Oak Ridge National Laboratory PB Process Building...

324

Pantex High Pressure Fire Loop Project Completed On Time, Under...  

National Nuclear Security Administration (NNSA)

the Baseline Change Proposal process. Two 400,000-gallon fire protection water supply tanks and associated pumping facilities were added. Later in the project, an additional...

325

Global estimation of burned area using MODIS active fire observations  

E-Print Network (OSTI)

the 1995 fire season in South America, J. Geophys. Res. -Central America Northern Hemisphere South America SouthernHemisphere South America Europe Middle East Northern

Giglio, L.; van der Werf, G. R; Randerson, J. T; Collatz, G. J; Kasibhatla, P.

2006-01-01T23:59:59.000Z

326

A Method for Evaluating Fire After Earthquake Scenarios for Single...  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Evaluating Fire After Earthquake Scenarios for Single Buildings Authors: Elizabeth J. Kelly and Raymond N. Tell Intended Use: Handout for DOE Natural Phenomena Hazards Workshop,...

327

A Method for Evaluating Fire after Earthquake Scenarios for Single...  

Office of Environmental Management (EM)

Method for Evaluating Fire After Earthquake Scenarios for Single Buildings Elizabeth J. Kelly and Raymond N. Tell, LANL U.S. Department of Energy Natural Phenomena Hazards Workshop...

328

A Method for Evaluating Fire After Earthquake Scenarios for Single...  

Office of Environmental Management (EM)

Method for Evaluating Fire After Earthquake Scenarios for Single Buildings Elizabeth J. Kelly and Raymond N. Tell, LANL U.S. Department of Energy Natural Phenomena Hazards Workshop...

329

NREL: Energy Analysis - Natural Gas-Fired Generation Results...  

NLE Websites -- All DOE Office Websites (Extended Search)

assessments have shown wide-ranging results. To better understand the greenhouse gas (GHG) emissions from utility-scale, natural gas-fired electricity generation systems (based...

330

NREL: Energy Analysis - Coal-Fired Electricity Generation Results...  

NLE Websites -- All DOE Office Websites (Extended Search)

assessments have shown wide-ranging results. To better understand the greenhouse gas (GHG) emissions from utility-scale, coal-fired electricity generation systems (based on...

331

Install Waste Heat Recovery Systems for Fuel-Fired Furnaces  

Energy.gov (U.S. Department of Energy (DOE))

This tip sheet recommends installing waste heat recovery systems for fuel-fired furnaces to increase the energy efficiency of process heating systems.

332

Multiple organizations build interagency fire center at LANL  

NLE Websites -- All DOE Office Websites (Extended Search)

facility will also include room for offices, training, and meetings, and storage for fire protection and suppression equipment. The new facility is designed to meet Leadership...

333

Assessment of Passive Fire Protection on Steel-Girder Bridges.  

E-Print Network (OSTI)

?? Bridges in the US are severely damaged or suffer collapse from fires at significant rates, even when compared to other hazards such as earthquakes. (more)

Davidson, Michael

2012-01-01T23:59:59.000Z

334

Project examples Install new HVAC, electrical, fire protection,  

E-Print Network (OSTI)

Project examples Install new HVAC, electrical, fire protection, and plumbing systems in Mechanical. · Totransformthisspaceandincreaseaccessibility, anelevatorisrequired.Currently,Blakelydoesnot haveone. Replace HVAC and electrical system

Blanchette, Robert A.

335

Slurry fired heater cold-flow modelling  

SciTech Connect

This report summarizes the experimental and theoretical work leading to the scale-up of the SRC-I Demonstration Plant slurry fired heater. The scale-up involved a theoretical model using empirical relations in the derivation, and employed variables such as flow conditions, liquid viscosity, and slug frequency. Such variables have been shown to affect the heat transfer characteristics ofthe system. The model assumes that, if all other variables remain constant, the heat transfer coefficient can be scaled up proportional to D/sup -2/3/ (D = inside diameter of the fired heater tube). All flow conditions, liquid viscosities, and pipe inclinations relevant to the demonstration plant have indicated a slug flow regime in the slurry fired heater. The annular and stratified flow regimes should be avoided to minimize the potential for excessive pipe erosion and to decrease temperature gradients along the pipe cross section leading to coking and thermal stresses, respectively. Cold-flow studies in 3- and 6.75-in.-inside-diameter (ID) pipes were conducted to determine the effect of scale-up on flow regime, slug frequency, and slug dimensions. The developed model assumes that conduction heat transfer occurs through the liquid film surrounding the gas slug and laminar convective heat transfer to the liquid slug. A weighted average of these two heat transfer mechanisms gives a value for the average pipe heat transfer coefficient. The cold-flow work showed a decrease in the observed slug frequency between the 3- and 6.75-ID pipes. Data on the ratio of gas to liquid slug length in the 6.75-in. pipe are not yet complete, but are expected to yield generally lower values than those obtained in the 3-in. pipe; this will probably affect the scale-up to demonstration plant conditions. 5 references, 15 figures, 7 tables.

Moujaes, S.F.

1983-07-01T23:59:59.000Z

336

New Fire Code adopted July 1, 2008 Fire Code requires all non-  

E-Print Network (OSTI)

2008 Fire Code. NWC, newly renovated labs. Labs established before July 2008 called "Pre storage rooms Offices and lavatories Page 6 #12; Lab Hazard Classification Pre-existing labs Type I, II V to Class I Roman #'s Higher # / Lower Hazard Page 13 #12; FDNY Permits > 1 gallon of flammable

Jia, Songtao

337

A Wood-Fired Gas Turbine Plant  

E-Print Network (OSTI)

-fired turbine, it probably seems that a wood gasification system must be involved. This is a proven and accepted method of producing gas to drive this type of power unit, but the fuel produced is a dirty fuel containing large amounts of me' ~ "'1 re, tars..., and other undesirable impurities that make it unsuitable for use as a fuel until a rather expensive cleanup process and residual waste disposal can take place. However, Aerospace Research felt that there must be a way to improve on the wood gasification...

Powell, S. H.; Hamrick, J. T.

338

Global fire emissions and the contribution of deforestation, savanna, forest, agricultural, and peat fires (1997-2009)  

E-Print Network (OSTI)

Estimating direct carbon emissions from Canadian wildlandfuel consumption and carbon emissions in Canadian borealY. : Fire-related carbon emissions from land use transitions

2010-01-01T23:59:59.000Z

339

EPRI/NRC-RES fire human reliability analysis guidelines.  

SciTech Connect

During the 1990s, the Electric Power Research Institute (EPRI) developed methods for fire risk analysis to support its utility members in the preparation of responses to Generic Letter 88-20, Supplement 4, 'Individual Plant Examination - External Events' (IPEEE). This effort produced a Fire Risk Assessment methodology for operations at power that was used by the majority of U.S. nuclear power plants (NPPs) in support of the IPEEE program and several NPPs overseas. Although these methods were acceptable for accomplishing the objectives of the IPEEE, EPRI and the U.S. Nuclear Regulatory Commission (NRC) recognized that they required upgrades to support current requirements for risk-informed, performance-based (RI/PB) applications. In 2001, EPRI and the USNRC's Office of Nuclear Regulatory Research (RES) embarked on a cooperative project to improve the state-of-the-art in fire risk assessment to support a new risk-informed environment in fire protection. This project produced a consensus document, NUREG/CR-6850 (EPRI 1011989), entitled 'Fire PRA Methodology for Nuclear Power Facilities' which addressed fire risk for at power operations. NUREG/CR-6850 developed high level guidance on the process for identification and inclusion of human failure events (HFEs) into the fire PRA (FPRA), and a methodology for assigning quantitative screening values to these HFEs. It outlined the initial considerations of performance shaping factors (PSFs) and related fire effects that may need to be addressed in developing best-estimate human error probabilities (HEPs). However, NUREG/CR-6850 did not describe a methodology to develop best-estimate HEPs given the PSFs and the fire-related effects. In 2007, EPRI and RES embarked on another cooperative project to develop explicit guidance for estimating HEPs for human failure events under fire generated conditions, building upon existing human reliability analysis (HRA) methods. This document provides a methodology and guidance for conducting a fire HRA. This process includes identification and definition of post-fire human failure events, qualitative analysis, quantification, recovery, dependency, and uncertainty. This document provides three approaches to quantification: screening, scoping, and detailed HRA. Screening is based on the guidance in NUREG/CR-6850, with some additional guidance for scenarios with long time windows. Scoping is a new approach to quantification developed specifically to support the iterative nature of fire PRA quantification. Scoping is intended to provide less conservative HEPs than screening, but requires fewer resources than a detailed HRA analysis. For detailed HRA quantification, guidance has been developed on how to apply existing methods to assess post-fire fire HEPs.

Lewis, Stuart R. (Electric Power Research Institute, Charlotte, NC); Cooper, Susan E. (U.S. Nuclear Regulatory Commission, Rockville, MD); Najafi, Bijan (SAIC, Campbell, CA); Collins, Erin (SAIC, Campbell, CA); Hannaman, Bill (SAIC, Campbell, CA); Kohlhepp, Kaydee (Scientech, Tukwila, WA); Grobbelaar, Jan (Scientech, Tukwila, WA); Hill, Kendra (U.S. Nuclear Regulatory Commission, Rockville, MD); Hendrickson, Stacey M. Langfitt; Forester, John Alan; Julius, Jeff (Scientech, Tukwila, WA)

2010-03-01T23:59:59.000Z

340

Turbulent closure and the modelling of fire by using computational fluid dynamics  

Science Journals Connector (OSTI)

...fire modelling. In Combustion fundamentals of fire (ed. G. Cox), pp...formation and combustion of soot in diesel engines. In Heat transfer in flames...diffusion flames. In Combustion fundamentals of fire (ed. G. Cox), pp...

1998-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


341

December 2006 Spatial Autocorrelation and Pseudoreplication 107 Practices and Applications in Fire Ecology  

E-Print Network (OSTI)

Ecology SPATIAL AUTOCORRELATION AND PSEUDOREPLICATION IN FIRE ECOLOGY Amanda L. Bataineh1 , Brian P the traditional statistical assumption of observational independence. What, if anything, can the fire ecology fire ecology researchers. Key Words: nearness, experimental design, ecology, landscape

Hung, I-Kuai

342

Modelling long-term fire regimes of southern California Seth H. PetersonA,F  

E-Print Network (OSTI)

the response of three fire regime metrics (fire size distributions, fire return interval maps, cumulative total the spatiotemporal pattern of ignitions, fuels, weather and topography, and describes the size, spatial pattern

Carlson, Jean

343

Effect of the shutdown of a large coal fired power plant on ambient mercury species  

E-Print Network (OSTI)

Effect of the shutdown of a coal-fired power plant on urbanof the shutdown of a large coal-fired power plant on ambientof the shutdown of a large coal-fired power plant on ambient

Wang, Yungang

2014-01-01T23:59:59.000Z

344

Enhanced Elemental Mercury Removal from Coal-fired Flue Gas by Sulfur-chlorine Compounds  

E-Print Network (OSTI)

removal from flue gas of coal-fired power plants. Environ.Speciation in a 100-MW Coal-Fired Boiler with Low-NOxControl Technologies for Coal-Fired Power Plants, DOE/NETL

Miller, Nai-Qiang Yan-Zan Qu Yao Chi Shao-Hua Qiao Ray Dod Shih-Ger Chang Charles

2008-01-01T23:59:59.000Z

345

The application of expansion foam on liquefied natural gas (LNG) to suppress LNG vapor and LNG pool fire thermal radiation  

E-Print Network (OSTI)

Liquefied Natural Gas (LNG) hazards include LNG flammable vapor dispersion and LNG pool fire thermal radiation. A large LNG pool fire emits high thermal radiation thus preventing fire fighters from approaching and extinguishing the fire. One...

Suardin, Jaffee Arizon

2009-05-15T23:59:59.000Z

346

Fire-Induced Response in Foam Encapsulants  

SciTech Connect

The paper provides a concise overview of a coordinated experimental/theoretical/numerical program at Sandia National Laboratories to develop an experimentally validated model of fire-induced response of foam-filled engineered systems for nuclear and transportation safety applications. Integral experiments are performed to investigate the thermal response of polyurethane foam-filled systems exposed to fire-like heat fluxes. A suite of laboratory experiments is performed to characterize the decomposition chemistry of polyurethane. Mass loss and energy associated with foam decomposition and chemical structures of the virgin and decomposed foam are determined. Decomposition chemistry is modeled as the degradation of macromolecular structures by bond breaking followed by vaporization of small fragments of the macromolecule with high vapor pressures. The chemical decomposition model is validated against the laboratory data. Data from integral experiments is used to assess and validate a FEM foam thermal response model with the chemistry model developed from the decomposition experiments. Good agreement was achieved both in the progression of the decomposition front and the in-depth thermal response.

Borek, T.T.; Chu, T.Y.; Erickson, K.L.; Gill, W.; Hobbs, M.L.; Humphries, L.L.; Renlund, A.M.; Ulibarri, T.A.

1999-04-02T23:59:59.000Z

347

Forest Fire Modeling and Early Detection using Wireless Sensor Networks  

E-Print Network (OSTI)

cases fires are part of the forest ecosys- tem and they are important to the life cycle of indigenous. The analysis of the FWI System could be of interest in its own right to researchers working in the sensor Columbia, Canada. The fire was spread by the strong wind and within a few days it turned into a firestorm

Zhang, Richard "Hao"

348

Improve the design of fire emergency relief systems  

SciTech Connect

In recognition of the potential severe consequences of a process vessel rupture under fire exposure, industry codes such as the National Fire Protection Association (NFPA) 30 and the American Petroleum Institute (API) Standard 2000 have been established for the specification of emergency relief systems (ERSs). The intent is to reduce the risk of human injury and asset losses associated with process plant fires. These codes are largely prescriptive in nature. That is, they provide specific details on how to achieve safe design. Prescriptive standards are easy to apply, because they are simplified approaches which generally apply to many (but not all) situations. But they also have limitations, including the tendency to result in, at best, suboptimal (overly conservative) designs, and in some instances potentially unsafe designs. As the fire community moves toward performance-based standards for building protection, perhaps it is time to consider a similar approach for vessel protection in a fire. The design issues addressed in this article include: Use of heat input based on actual fuel burning rate, heat of combustion, and flame emissive power, vs. NFPA 30 and API 2000 heat-input equations; Effect of drainage (from vessel to sump) on fire duration, rather than heat input; Use of risk assessment to determine the relative frequency of fire and process-induced incidents; and design for containment, rather than vessel protection when fire probability is low

Stickles, R.P.; Melhem, G.A.; Eckhardt, D.R.

1995-11-01T23:59:59.000Z

349

PRESSURIZATION OF FIXED ROOF STORAGE TANKS DUE TO EXTERNAL FIRES  

E-Print Network (OSTI)

PRESSURIZATION OF FIXED ROOF STORAGE TANKS DUE TO EXTERNAL FIRES Fabien FouiHen, INERIS, Parc. Reflections led on this accident have pushed to consider the phenomenon of tank pressurization as a potential initiating event of the fire ball observed. In concrete terms, when a fixed roof storage tank is surrounded

Paris-Sud XI, Université de

350

Levels and Sources of Forest Fire Prevention Knowledge  

E-Print Network (OSTI)

Levels and Sources of Forest Fire Prevention Knowledge of California Hunters William S. Folkman U-managerial occupations. Their level of knowl- edge about forest fire prevention is generally high, but their knowledge prevention is generally high, but their knowledge is weak in some pertinent areas. Most frequently reported

Standiford, Richard B.

351

WRF-Fire Applied in Bulgaria Nina Dobrinkova1  

E-Print Network (OSTI)

and Statistical Sciences University of Colorado Denver jan.mandel@ucdenver.edu Abstract. WRF-Fire consists in a wildfire. Bulgaria as part of this region also has huge problems with wildland fires. Statistics have been]. Even though the number of wildfires is increasing and the consequences are not only of environmental

Mustakerov, Ivan

352

Post-Election Prospects for Natural-Gas-Fired Generation  

Science Journals Connector (OSTI)

The extraordinary growth of gas-fired generation during President Obama's first term has upended power markets across the country. But how will gas-fired power fare during the next four years? And how much will the outcome be impacted by the federal energy and environmental policies that the Administration and Congress can shape? This essay provides some preliminary answers to these questions.

Gregory C. Staple; Patrick Bean

2013-01-01T23:59:59.000Z

353

Cycling firing method for bypass operation of bridge converters  

SciTech Connect

The bridge converter comprises a number of switching elements and an electronic logic system which regulated the electric power levels by controlling the firing, i.e., the initiation of the conduction period of the switching elements. Cyclic firing of said elements allows the direct current to bypass the alternating current system with high power factor and negligible losses.

Zabar, Zivan (99-72 66th Rd., Apt. 9N, Forest Hills, NY 11375)

1982-01-01T23:59:59.000Z

354

Modeling wildland fire propagation with level set methods  

Science Journals Connector (OSTI)

Level set methods are versatile and extensible techniques for general front tracking problems, including the practically important problem of predicting the advance of a fire front across expanses of surface vegetation. Given a rule, empirical or otherwise, ... Keywords: Front propagation, Hamilton-Jacobi equations, Level set methods, Multivac software, Wildland fire spread

V. Mallet; D. E. Keyes; F. E. Fendell

2009-04-01T23:59:59.000Z

355

High resolution weather modeling for improved fire management  

Science Journals Connector (OSTI)

A critical element to the accurate prediction of fire/weather behaviour is the knowledge of near-surface weather. Weather variables, such as wind, temperature, humidity and precipitation, make direct impacts on the practice of managing prescribed burns ... Keywords: fire behavior, numerical weather prediction, parallel computing

Kevin Roe; Duane Stevens; Carol McCord

2001-11-01T23:59:59.000Z

356

Coupled AtmosphereWildland Fire Modelling Jean Baptiste Filippi1  

E-Print Network (OSTI)

to the estimation of the rate of spread of the fire. Wildfire's convection (i.e., entire plume) can modify the local localized extreme events. These models have been selected because they can be run coupled and support model used in ForeFire provides a physical formulation to take into account the effect of wind and slope

Clements, Craig

357

Accounting for Fire Injection Height in Climate Charlie Zender  

E-Print Network (OSTI)

Radiative Power (FRP): FRP [W m-2 ] = dR dt (2) The MODIS FTA Giglio et al. (2003), e.g., inverts Science, University of California, Irvine Contributions from: New Student (UCI) Presented to: Somewhere Power Satellites retrievals use a Fire Thermal Anomaly (FTA) method to determine the (broadband) Fire

Zender, Charles

358

ANTHROPOGENIC FIRES, FOREST RESOURCES, AND LOCAL LIVELIHOODS AT CHYULU HILLS, KENYA.  

E-Print Network (OSTI)

??Anthropogenic fires are rife in rural Africa as people use fire to modify landscapes for their livelihoods. Although burning occurs as a very significant practice (more)

Kamau, Peter Ngugi

2013-01-01T23:59:59.000Z

359

Fire Protection Program Assessment, Building 9203 & 9203A Complex- Y12 Plant, Oak Ridge, Tennessee  

Energy.gov (U.S. Department of Energy (DOE))

This assessment is intended to evaluate the fire hazards, life safety and fire protection features inherent in the Building 9203 and 9203A complex.

360

Experimental determination of the shipboard fire environment for simulated radioactive material packages  

SciTech Connect

A series of eight fire tests with simulated radioactive material shipping containers aboard the test ship Mayo Lykes, a break-bulk freighter, is described. The tests simulate three basic types of fires: engine room fires, cargo fires and open pool fires. Detailed results from the tests include temperatures, heat fluxes and air flows measured during the fires. The first examination of the results indicates that shipboard fires are not significantly different from fires encountered in land transport. 13 refs., 15 figs., 11 tabs.

Koski, J.A.; Bobbe, J.G.; Arviso, M. [and others

1997-03-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


361

Fire-related carbon emissions from land use transitions in southern Amazonia  

E-Print Network (OSTI)

2008 Fire-related carbon emissions from land use transitionscontribute to atmospheric carbon emissions, including forest2008), Fire-related carbon emissions from land use

2008-01-01T23:59:59.000Z

362

Global Fire Emissions Database, Version 3.1 Published  

NLE Websites -- All DOE Office Websites (Extended Search)

Fire Emissions Database, Version 3.1 Published Fire Emissions Database, Version 3.1 Published The ORNL DAAC is pleased to announce the release of the Global Fire Emissions Database, Version 3.1: Global Fire Emissions Database, Version 3.1. Data set prepared by J.T. Randerson, G.R. van der Werf, L. Giglio, G.J. Collatz, and P.S. Kasibhatla. This data set provides monthly burned area, and monthly and annual fire emissions data from July 1996 to February 2012. Emissions data are available for carbon (C), dry matter (DM), carbon dioxide (CO2), carbon monoxide (CO), methane (CH4), hydrogen (H2), nitrous oxide (N2O), nitrogen oxides (NOx), non-methane hydrocarbons (NMHC), organic carbon (OC), black carbon (BC), particulate matter 2.5 micron (PM2p5), total particulate matter (TPM), and sulfur dioxide (SO2) among others. The C4 fraction of

363

Geothermal system saving money at fire station | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Geothermal system saving money at fire station Geothermal system saving money at fire station Geothermal system saving money at fire station April 9, 2010 - 3:45pm Addthis Joshua DeLung What will the project do? A geothermal heating and cooling system has enabled the substation to save taxpayers $15,000 annually when compared to a traditional system. The high temperature of the treatment building's water helps reduce the amount of energy needed to heat water in the substation. An environmentally friendly geothermal heating and cooling system in Pennsylvania will save taxpayers $15,000 a year as part of a new fire substation that will decrease emergency response times. The Alpha Fire Co. celebrated the opening of substation on the ground floor of the College Township municipal building earlier this year in State

364

CRAD, Fire Protection - Oak Ridge National Laboratory High Flux Isotope  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fire Protection - Oak Ridge National Laboratory High Flux Fire Protection - Oak Ridge National Laboratory High Flux Isotope Reactor CRAD, Fire Protection - Oak Ridge National Laboratory High Flux Isotope Reactor February 2006 A section of Appendix C to DOE G 226.1-2 "Federal Line Management Oversight of Department of Energy Nuclear Facilities." Consists of Criteria Review and Approach Documents (CRADs) used for a February 2006 Commencement of Operations assessment of the Fire Protection program at the Idaho National Laboratory, Idaho Accelerated Retrieval Project Phase II. CRADs provide a recommended approach and the types of information to gather to assess elements of a DOE contractor's programs. CRAD, Fire Protection - Oak Ridge National Laboratory High Flux Isotope Reactor More Documents & Publications

365

NETL: News Release - Jet Engine Successful in Fighting Mine Fire  

NLE Websites -- All DOE Office Websites (Extended Search)

2, 2003 2, 2003 Jet Engine Successful in Fighting Mine Fire Energy Department's Assistance Brings West Virginia Coal Miners Back To Work One Year Early - Australian Jet Engine Successfully Fights West Virginia Mine Fire - By blowing its exhaust into the underground mine, the modified jet engine was able to snuff out the mine fire much faster than traditional methods. FAIRVIEW, WV - A modified jet engine has been used to successfully fight a West Virginia mine fire that had been burning for nearly two months and was the cause of 300 employees being temporarily laid off when mine operations were idled. Positioned at the mouth of the one of the mineshafts, the jet engine was used to blow water vapor and inert gases into the mine to smother the fire by creating an inert environment underground. It was the

366

NNSA Celebrates Earth Week: Pantex 'greens' firing range | National Nuclear  

NLE Websites -- All DOE Office Websites (Extended Search)

'greens' firing range | National Nuclear 'greens' firing range | National Nuclear Security Administration Our Mission Managing the Stockpile Preventing Proliferation Powering the Nuclear Navy Emergency Response Recapitalizing Our Infrastructure Continuing Management Reform Countering Nuclear Terrorism About Us Our Programs Our History Who We Are Our Leadership Our Locations Budget Our Operations Media Room Congressional Testimony Fact Sheets Newsletters Press Releases Speeches Events Social Media Video Gallery Photo Gallery NNSA Archive Federal Employment Apply for Our Jobs Our Jobs Working at NNSA Blog Home > NNSA Blog > NNSA Celebrates Earth Week: Pantex 'greens' firing range NNSA Celebrates Earth Week: Pantex 'greens' firing range Posted By Greg Cunningham, Pantex The lead that flies at the Pantex Firing Range has to land somewhere, and

367

CRAD, Fire Protection - Los Alamos National Laboratory Waste  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fire Protection - Los Alamos National Laboratory Waste Fire Protection - Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility CRAD, Fire Protection - Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility A section of Appendix C to DOE G 226.1-2 "Federal Line Management Oversight of Department of Energy Nuclear Facilities." Consists of Criteria Review and Approach Documents (CRADs) used for an assessment of the Fire Protection Program portion of an Operational Readiness Review at the Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility. CRADs provide a recommended approach and the types of information to gather to assess elements of a DOE contractor's programs. CRAD, Fire Protection - Los Alamos National Laboratory Waste

368

CRAD, Fire Protection - Idaho Accelerated Retrieval Project Phase II |  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Fire Protection - Idaho Accelerated Retrieval Project Phase Fire Protection - Idaho Accelerated Retrieval Project Phase II CRAD, Fire Protection - Idaho Accelerated Retrieval Project Phase II February 2006 A section of Appendix C to DOE G 226.1-2 "Federal Line Management Oversight of Department of Energy Nuclear Facilities." Consists of Criteria Review and Approach Documents (CRADs) used for a February 2006 Commencement of Operations assessment of the Fire Protection program at the Idaho National Laboratory, Idaho Accelerated Retrieval Project Phase II. CRADs provide a recommended approach and the types of information to gather to assess elements of a DOE contractor's programs. CRAD, Fire Protection - Idaho Accelerated Retrieval Project Phase II More Documents & Publications CRAD, Engineering - Idaho Accelerated Retrieval Project Phase II

369

Los Alamos National Laboratory: Las Conchas Fire Update | Department of  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Alamos National Laboratory: Las Conchas Fire Update Alamos National Laboratory: Las Conchas Fire Update Los Alamos National Laboratory: Las Conchas Fire Update June 29, 2011 - 10:33am Addthis Liisa O'Neill Liisa O'Neill Former New Media Specialist, Office of Public Affairs Many of you have asked for more information about the potential impact of the fire in New Mexico on the Energy Department's Los Alamos National Laboratory. We'd like to share the latest update from the lab below. You can also monitor the Laboratory's news site for the latest information. LANL Announces Closure for Thursday, June 30 Los Alamos, New Mexico, June 28, 2011, 7:00pm--Los Alamos National Laboratory tonight announced it will remain closed through Thursday, June 30 because of risks presented by the Las Conchas Fire and the mandatory

370

Memorandum, Additional Approved Qualification Courses of Fire - September  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Memorandum, Additional Approved Qualification Courses of Fire - Memorandum, Additional Approved Qualification Courses of Fire - September 23, 2011 Memorandum, Additional Approved Qualification Courses of Fire - September 23, 2011 September 23, 2011 Newly developed Security Police Officer/Special Response Team Qualification Courses of Fire In accordance with DOE Order 473.2 Protection Program Operations , Section E , paragraph 2 and Section K, Paragraph 2, members of the Department of Energy (DOE) Firearms Policy Panel, DOE Protective Forces Safety Committee, DOE Trainin Managers Working Group, the National Nuclear Security Administration, and the DOE National Training Center have developed, reviewed and revised the following courses of fire (attached) for inclusion in the Protective Force Firearms Qualification Courses Manual. The courses

371

CONSTRUCTION ALERT Additional Notice to Ongoing Project  

E-Print Network (OSTI)

-541-510 CONTRACTOR: Circuit Builders Inc. SCOPE OF WORK: Testing of the new fire alarm system DURATION OF PROJECT Operations, Campus Security, and Fire Safety. SUBJECT: Bachman Hall Replace Fire Alarm System UHM 09

372

Independent Oversight Review of the Fire Protection Program and Fire Protection Systems at the Transuranic Waste Processing Center, December 2013  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

and Fire Protection Systems and Fire Protection Systems at the Transuranic Waste Processing Center December 2013 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U. S. Department of Energy Table of Contents 1.0 Purpose.................................................................................................................................................... 1 2.0 Background ............................................................................................................................................. 1 3.0 Scope....................................................................................................................................................... 2 4.0 Methodology .......................................................................................................................................... 2

373

Though no material is "fire proof," the proper use and assembly of fire-rated building materials  

E-Print Network (OSTI)

been done on the toxicity of fumes released by this melted material. Fire-resistive materials The same · Wood panels and boards Material Class is categorized by composition, or resistance to fire (combustible or noncombustible). Class A has the highest resistance; class C has the least resistance. However, Class A materials

374

Fire Prevention: Preventing fires is everyone's job. We all need to be alert to anything that could  

E-Print Network (OSTI)

- sparking tools, and control static electricity as required. 8. Help maintain building security to prevent emergency telephone numbers as well as the company address by the telephone in your station/desk for quick://www.uwinnipeg.ca/index/safety-hazard-alert Using a Portable Fire Extinguisher: #12;Portable Fire Extinguishers can be a useful tool to save lives

Martin, Jeff

375

Remote sensing data of biomass and fire history were used to characterise woodland degradation across the landscape (fig. 2). Fires  

E-Print Network (OSTI)

Remote sensing data of biomass and fire history were used to characterise woodland degradation. Results MODEL OUTPUT There is potential for considerable biomass variation as a result of fire (fig. 3 biomass woodlands are particularly vulnerable to degradation, though were also found to be capable

376

Fire in the Ice, Summer 2004  

NLE Websites -- All DOE Office Websites (Extended Search)

R R Vol. 4, Iss. 3 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ CONTENTS Gulf of Mexico Remote Observatory Update ............... 1 Hydrate Decomposition Studies at USGS .................... 5 NETL's HP View Cell Operational .......................... 10 Announcements .................. 13 * AAPG Hedberg Conference * JIP Drilling Delayed * TOUGH-Fx/HYDRATE v1.0 * Advisory Committee Meeting * Anaximander project Spotlight on Research ........ 16 Dr. Keith Kvenvolden CONTACT POINT Ray Boswell National Energy Technology Laboratory (304) 285-4541 (304) 285-4469 fax Ray.Boswell@netl.doe.gov The Fire in the Ice Newsletter is

377

Fire-driven flows in enclosures  

SciTech Connect

A two-dimensional Boussinesq model describing heat-driven, buoyant convection in a polygonal enclosure is presented. The hydrodynamic model is based on the time-dependent Navier-Stokes equations with constant viscosity and thermal conductivity; no turbulence model or other empirical parameters are introduced. The polygonal domain is mapped via a numerical Schwarz-Christoffel transformation onto a rectangle, where the equations of motion are written in terms of the vorticity and stream function. An alternating direction implicit (ADI) difference scheme, second-order in space and first-order in time, is used to solve the Poisson equation for the stream function. Computational results which are of interest to the fire research community are presented. 13 refs,. 5 figs.

McGrattan, K.B.; Rehm, R.G.; Baum, H.R. (National Institute of Standards and Technology, Gaithersburg, MD (United States))

1994-02-01T23:59:59.000Z

378

Error-eliminating rapid ultrasonic firing  

DOE Patents (OSTI)

A system for producing reliable navigation data for a mobile vehicle, such as a robot, combines multiple range samples to increase the confidence'' of the algorithm in the existence of an obstacle. At higher vehicle speed, it is crucial to sample each sensor quickly and repeatedly to gather multiple samples in time to avoid a collision. Erroneous data is rejected by delaying the issuance of an ultrasonic energy pulse by a predetermined wait-period, which may be different during alternate ultrasonic firing cycles. Consecutive readings are compared, and the corresponding data is rejected if the readings differ by more than a predetermined amount. The rejection rate for the data is monitored and the operating speed of the navigation system is reduced if the data rejection rate is increased. This is useful to distinguish and eliminate noise from the data which truly represents the existence of an article in the field of operation of the vehicle.

Borenstein, J.; Koren, Y.

1993-08-24T23:59:59.000Z

379

Error-eliminating rapid ultrasonic firing  

DOE Patents (OSTI)

A system for producing reliable navigation data for a mobile vehicle, such as a robot, combines multiple range samples to increase the "confidence" of the algorithm in the existence of an obstacle. At higher vehicle speed, it is crucial to sample each sensor quickly and repeatedly to gather multiple samples in time to avoid a collision. Erroneous data is rejected by delaying the issuance of an ultrasonic energy pulse by a predetermined wait-period, which may be different during alternate ultrasonic firing cycles. Consecutive readings are compared, and the corresponding data is rejected if the readings differ by more than a predetermined amount. The rejection rate for the data is monitored and the operating speed of the navigation system is reduced if the data rejection rate is increased. This is useful to distinguish and eliminate noise from the data which truly represents the existence of an article in the field of operation of the vehicle.

Borenstein, Johann (Ann Arbor, MI); Koren, Yoram (Ann Arbor, MI)

1993-08-24T23:59:59.000Z

380

327 Building fire hazards analysis implementation plan  

SciTech Connect

In March 1998, the 327 Building Fire Hazards Analysis (FHA) (Reference 1) was approved by the U.S. Department of Energy, Richland Operations Office (DOE-E) for implementation by B and W Hanford Company (BWC). The purpose of the FHA was to identify gaps in compliance with DOE Order 5480.7A (Reference 2) and Richland Operations Office Implementation Directive (RLID) 5480.7 (Reference 3), especially in regard to loss limitation. The FHA identified compliance gaps in five areas and provided nine recommendations (11 items) to bring the 327 Building into compliance. A status is provided for each recommendation in this document. BWHC will use this Implementation Plan to bring the 327 Building and its operation into compliance with DOE Order 5480.7A and IUD 5480.7.

BARILO, N.F.

1999-05-10T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


381

Fire in the Ice, Fall 2004  

NLE Websites -- All DOE Office Websites (Extended Search)

4 4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ CONTENTS AAPG Hedberg Research Conference ............................ 1 Oak Ridge Facilities .............. 4 Relic Gas Hydrates of Northwestern Siberia ............. 8 Announcements .................. 11 * JIP Tests in the Gulf of Mexico * Planning Workshop Slated for Early Next Year Spotlight on Research ........ 12 Ingo Pecher CONTACT POINT Ray Boswell National Energy Technology Laboratory (304) 285-4541 (304) 285-4216 fax Ray.Boswell@netl.doe.gov The Fire in the Ice Newsletter is also available online at our website (http://www.netl.doe.gov/ scngo/Natural%20Gas/hydrates/)

382

Model of ventilation flows during large tunnel fires  

Science Journals Connector (OSTI)

In order to describe the reduction in the longitudinal airflow velocity due to the fire and hot gases resistances in a large tunnel fire, a theoretical model, taking into consideration the pressure losses over the fire source and obstructions, the thermal stack effects, and the hydraulic resistance induced by the tunnel walls, fire protection boards and a HGV trailer mock-up, is developed and validated using the large-scale tests data from the fire tests performed in the Runehamar tunnel with longitudinal ventilation in Norway 2003. Two large mobile fan units were used to create a longitudinal flow within the tunnel and prevent smoke backlayering upstream of the fire. One fan was located outside the entrance of the tunnel and the other inside the tunnel. The fire load consisted of a mock-up simulating a heavy goods vehicle (HGV) trailer creating a maximum heat release rates in the range of 66202MW. Two methods of calculating the mean temperature related to the thermal expansion and stack effect are proposed and compared.

Haukur Ingason; Anders Lnnermark; Ying Zhen Li

2012-01-01T23:59:59.000Z

383

Investigation of UF/sub 6/ behavior in a fire  

SciTech Connect

Reactions between UF/sub 6/ and combustible gases and the potential for UF/sub 6/-filled cylinders to rupture when exposed to fire are addressed. Although the absence of kinetic data prevents specific identification and quantification of the chemical species formed, potential reaction products resulting from the release of UF/sub 6/ into a fire include UF/sub 4/, UO/sub 2/F/sub 2/, HF, C, CF/sub 4/,COF/sub 2/, and short chain, fluorinated or partially fluorinated hydrocarbons. Such a release adds energy to a fire relative to normal combustion reactions. Time intervals to an assumed point of rupture for UF/sub 6/-filled cylinders exposed to fire are estimated conservatively. Several related studies are also summarized, including a test series in which small UF/sub 6/-filled cylinders were immersed in fire resulting in valve failures and explosive ruptures. It is concluded that all sizes of UF/sub 6/ cylinders currently in use may rupture within 30 minutes when totally immersed in a fire. For cylinders adjacent to fires, rupture of the larger cylinders appears much less likely.

Williams, W.R.

1988-01-01T23:59:59.000Z

384

Fire hazard analysis for Plutonium Finishing Plant complex  

SciTech Connect

A fire hazards analysis (FHA) was performed for the Plutonium Finishing Plant (PFP) Complex at the Department of Energy (DOE) Hanford site. The scope of the FHA focuses on the nuclear facilities/structures in the Complex. The analysis was conducted in accordance with RLID 5480.7, [DOE Directive RLID 5480.7, 1/17/94] and DOE Order 5480.7A, ''Fire Protection'' [DOE Order 5480.7A, 2/17/93] and addresses each of the sixteen principle elements outlined in paragraph 9.a(3) of the Order. The elements are addressed in terms of the fire protection objectives stated in paragraph 4 of DOE 5480.7A. In addition, the FHA also complies with WHC-CM-4-41, Fire Protection Program Manual, Section 3.4 [1994] and WHC-SD-GN-FHA-30001, Rev. 0 [WHC, 1994]. Objectives of the FHA are to determine: (1) the fire hazards that expose the PFP facilities, or that are inherent in the building operations, (2) the adequacy of the fire safety features currently located in the PFP Complex, and (3) the degree of compliance of the facility with specific fire safety provisions in DOE orders, related engineering codes, and standards.

MCKINNIS, D.L.

1999-02-23T23:59:59.000Z

385

Microsoft Word - Appendix G - Wildland Fire Mgmt Plan.docx  

Office of Legacy Management (LM)

G G Wildland Fire Management Plan for the Rocky Flats, Colorado, Site This page intentionally left blank LMS/RFS/S04638-5.0 Wildland Fire Management Plan for the Rocky Flats, Colorado, Site July 2013 This page intentionally left blank U.S. Department of Energy Wildland Fire Management Plan for the Rocky Flats, Colorado, Site July 2013 Doc. No. S04638-5.0 Page i Contents Abbreviations .................................................................................................................................. ii 1.0 Introduction and Purpose ...................................................................................................... 1 1.1 Plan Purpose............................................................................................................... 1

386

Evaluation of Heat Losses in Fire Tube Boiler  

E-Print Network (OSTI)

Abstract The efficiency of oil fired fire tube boiler was calculated by evaluating the heat losses. Investigation on the performance of the boiler was conducted by examining the heat losses, identifying the reasons for losses, measuring the individual loss and developing a strategy for loss reduction. This study was carried out in Texmaco package horizontal fire tube boiler at Travancore Titanium Products Ltd (TTPL), Trivandrum, Kerala. The boiler efficiency was measured by indirect method. Heat losses in dry flue gas and due to unburned fuel were found to be the major problems. Since they were interrelated, installation of Zirconium oxygen sensor was recommended as a common remedy.

S. Krishnanunni; Josephkunju Paul C; Mathu Potti; Ernest Markose Mathew

387

Benchmark enclosure fire suppression experiments - phase 1 test report.  

SciTech Connect

A series of fire benchmark water suppression tests were performed that may provide guidance for dispersal systems for the protection of high value assets. The test results provide boundary and temporal data necessary for water spray suppression model development and validation. A review of fire suppression in presented for both gaseous suppression and water mist fire suppression. The experimental setup and procedure for gathering water suppression performance data are shown. Characteristics of the nozzles used in the testing are presented. Results of the experiments are discussed.

Figueroa, Victor G.; Nichols, Robert Thomas; Blanchat, Thomas K.

2007-06-01T23:59:59.000Z

388

Fire Impacts on the Mojave Desert Ecosystem: Literature Review  

SciTech Connect

The Nevada National Security Site (NNSS) is located within the Mojave Desert, which is the driest region in North America. Precipitation on the NNSS varies from an annual average of 130 millimeters (mm; 5.1 inches) with a minimum of 47 mm (1.9 inches) and maximum of 328 mm (12.9 inches) over the past 15 year period to an annual average of 205 mm (8.1 inches) with an annual minimum of 89 mm (3.5 inches) and maximum of 391 mm (15.4 inches) for the same time period; for a Frenchman Flat location at 970 meters (m; 3182 feet) and a Pahute Mesa location at 1986 m (6516 feet), respectively. The combination of aridity and temperature extremes has resulted in sparsely vegetated basins (desert shrub plant communities) to moderately vegetated mountains (mixed coniferous forest plant communities); both plant density and precipitation increase with increasing elevation. Whereas some plant communities have evolved under fire regimes and are dependent upon fire for seed germination, plant communities within the Mojave Desert are not dependent on a fire regime and therefore are highly impacted by fire (Brown and Minnich, 1986; Brooks, 1999). As noted by Johansen (2003) natural range fires are not prevalent in the Mojave and Sonoran Deserts because there is not enough vegetation present (too many shrub interspaces) to sustain a fire. Fire research and hence publications addressing fires in the Southwestern United States (U.S.) have therefore focused on forest, shrub-steppe and grassland fires caused by both natural and anthropogenic ignition sources. In the last few decades, however, invasion of mid-elevation shrublands by non-native Bromus madritensis ssp. rubens and Bromus tectorum (Hunter, 1991) have been highly correlated with increased fire frequency (Brooks and Berry, 2006; Brooks and Matchett, 2006). Coupled with the impact of climate change, which has already been shown to be playing a role in increased forest fires (Westerling et al., 2006), it is likely that the fire frequency will further increase in the Mojave Desert (Knapp 1998; Smith et al., 1987; Smith et al., 2000).

Fenstermaker Lynn

2012-01-01T23:59:59.000Z

389

Wireless Short Range Communication Technologies for Home Automation.  

E-Print Network (OSTI)

?? A modern home contains varieties of electronic equipment and systems like: TV, Hi-fi equipment, central heating systems, fire alarm systems, security alarm systems, lighting (more)

Oyekunle, Abiola Taiwo

2008-01-01T23:59:59.000Z

390

Dendrochronology-based fire history of mixed-conifer forests in the San Jacinto Mountains, California  

E-Print Network (OSTI)

Dendrochronology-based fire history of mixed-conifer forests in the San Jacinto Mountains. Introduction Characterizing fire regimes and fire seasonality in Californian mixed-conifer forests is difficult, 2003). Fire regimes in mixed-conifer forests in southern California have yet to be characterised using

Stephens, Scott L.

391

Self-sustained firing of human motor units Monica A. Gorassinib,  

E-Print Network (OSTI)

Self-sustained firing of human motor units Monica A. Gorassinib, *, David J. Bennetta,c, Jaynie F synaptic input (self-sustained firing). This firing behavior is due to the activation of intrinsic, voltage if such self-sustained firing occurs in motoneurons of the intact human. In this paper, we present evidence

Gorassini, Monica

392

Protecting Oregon Old-Growth Forests from Fires: How Much Is It Worth?1  

E-Print Network (OSTI)

Protecting Oregon Old-Growth Forests from Fires: How Much Is It Worth?1 Armando González-Cabán John and will be protected from fire for current and future generations. The methodology was applied to old-growth forests into fire management decision making is a growing concern of Federal agencies with wildland fire protection

Standiford, Richard B.

393

Conventional Facilities Chapter 8: Fire Protection 8-1 NSLS-II Preliminary Design Report  

E-Print Network (OSTI)

Conventional Facilities Chapter 8: Fire Protection 8-1 NSLS-II Preliminary Design Report 8 FIRE of New York State National Institute of Standards and Technology National Fire Protection Association, corresponding to the ring pentants. 8.2.2 Fire Protection System #12;8-2 Part 3: Conventional Facilities Scope

Ohta, Shigemi

394

Wildland fire management and air quality in the southern Sierra Nevada: Using the Lion Fire as a case study with a multi-year perspective on PM2.5 impacts and fire policy  

Science Journals Connector (OSTI)

Abstract Management of fire is an important and controversial policy issue. Active fire suppression has led to a backlog of fuels, limited the ecological benefits of fire, and reduced short-term smoke impacts likely delaying these emissions to future generations over a larger spatial extent. Smoke impacts can be expected to increase as fire size and intensity increase and the fuel backlog is consumed; whether through reintroduction of fire under desirable conditions or through stand replacing fire. Land Management Agencies would like to increase the use of naturally ignited fires to burn during favorable conditions as a way to reduce catastrophic fires. This study provides information about the levels of air quality impacts expected from these types of fires and discusses some of the policy controversies of managed fire that propagate inconsistencies between agencies and enter the public discourse. The Lion Fire, a primarily low intensity 8,370ha fire that was extensively monitored for Particulate Matter less than 2.5 microns (PM2.5), is used to quantify impacts to air quality. PM2.5 monitoring sites are used to assess exposure, public health impacts, and subsequently quantify annual air quality during a year with a fire that is within the historic normal fire size and intensity for this area. Ground level PM2.5 impacts were found to be localized with 99% of the hourly Air Quality Index readings in the moderate or good category for the sites impacted by the fire. PM2.5 concentrations at sites nearest the fire were below annual federal air quality standards for PM2.5 with annual 98th percentile at the most impacted sites (Johnsondale, Kernville, and Camp Nelson) of 35.0, 34.0, and 28.0?gm3 respectively. Smoke impacts to PM2.5 concentrations were not found to reach the populated Central Valley. The findings suggest that this type of fire can be implemented with minimal public health impacts thus allowing an opportunity for air and fire managers to alter policy to allow additional burning in an area with severe anthropogenic air pollution and where frequent widespread fire is both beneficial and inevitable. The more extensive air quality impacts documented with large high intensity fire may be averted by embracing the use of fire to prevent unwanted high intensity burns. A widespread increase in the use of fire for ecological benefit may provide the resiliency needed in Sierra Nevada forests as well as be the most beneficial to public health through the reduction of single dose exposure to smoke and limiting impacts spatially.

Don Schweizer; Ricardo Cisneros

2014-01-01T23:59:59.000Z

395

Y-12 Fire Protection Operations has new chief | Y-12 National Security  

NLE Websites -- All DOE Office Websites (Extended Search)

Fire Protection ... Fire Protection ... Y-12 Fire Protection Operations has new chief Posted: July 25, 2012 - 3:45pm J. Scott Vowell was recently appointed chief of Fire Protection Operations at the Y-12 National Security Complex. Vowell joined the Y-12 staff in 1993. Prior to being appointed fire chief, he served as assistant fire chief and fire captain. Previously he served as fire inspector at Oak Ridge National Laboratory. The Clinton native served on the Clinton City Emergency 911 Board from 1997 to 2001 and was a firefighter with the City of Clinton Fire Department for seven years. A division of Y-12's Safeguards, Security and Emergency Services, Fire Protection Operations has a roster of approximately 90, including firefighters, battalion chiefs and support staff. It provides emergency

396

Overview of the ARM/FIRE Water Vapor Experiment (AFWEX)  

NLE Websites -- All DOE Office Websites (Extended Search)

Overview of the ARM/FIRE Water Vapor Overview of the ARM/FIRE Water Vapor Experiment (AFWEX) D. C. Tobin, H. E. Revercomb, and D. D. Turner University of Wisconsin-Madison Madison, Wisconsin Introduction An overview of the ARM/FIRE Water Vapor Experiment (AFWEX) is given. This field experiment was conducted during November-December 2000 near the central ground-based Atmospheric Radiation Measurement (ARM) site in north central Oklahoma, and was sponsored jointly by the ARM, the National Aeronautics and Space Administration (NASA) First ISCCP Regional Experiment (FIRE), and the National Polar-orbiting Operational Environmental Satellite System (NPOESS) programs. Its primary goal was to collect accurate measurements of upper-level (~8 to 12 km) water vapor near the ground-based ARM site. These data are being used to determine the accuracy of measurements that are

397

Summary of Fire Protection Programs for Calendar Year 2007  

NLE Websites -- All DOE Office Websites (Extended Search)

SUMMARY of SUMMARY of FIRE PROTECTION PROGRAMS for CALENDAR YEAR 2007 UNITED STATES DEPARTMENT OF ENERGY Office of Corporate Safety Analysis Office of Nuclear Safety Policy and Assistance February 2009 Fire Protection Summary for Calendar Year 2007 i ii i FOREWORD A key safety objective of the U. S. Department of Energy (DOE) is to minimize the potential for and consequences of fires at DOE facilities. Since May 1950, an annual Fire Protection Program Summary (Annual Summary) has been developed by DOE and its predecessor agencies, the Atomic Energy Commission and the Energy Research Development Administration, to provide a means for measuring how well DOE is meeting this objective and where improvements can be made. In 1999, the Annual Summary reporting process was automated to streamline data collection and

398

Selectively fired, tubing-conveyed perforating guns save rig time  

SciTech Connect

Selective firing of tubing-conveyed perforating (TCP) guns during drill stem tests (DSTs) added flexibility and saved costs for Marathon Oil Co. As an example, in the Garland field in Wyoming, the guns allowed perforating multiple zones in one trip. This saved 1 1/2--2 days/well in rig time and $25,000--30,000/well in electric wire line and DST tool charges. For international offshore operations, savings of $200,000/well appear possible. Savings result not only from perforating multiple zones, but also from arbitrarily setting firing patterns with or without zone isolation. The paper describes the testing of equipment, the design of the guns, firing heads, crossover assembly, pressure isolation sub, control line, and select-fire sub, and applications for the guns.

Snider, P.M. (Marathon Oil Co., Houston, TX (United States)); Bond, P.L. (Halliburton Energy Services, Dallas, TX (United States))

1993-07-19T23:59:59.000Z

399

The 2010 OSU Clery Act Report Fire Safety Report  

E-Print Network (OSTI)

The 2010 OSU Clery Act Report And Fire Safety Report The Jeanne Clery Disclosure of Campus Security Policy and Campus Crime Statistics Act #12;#12;Page | i Table of Contents The Annual Clery Act Report..........................................................................................................................................1 Reportable Areas

Escher, Christine

400

Cable Hot Shorts and Circuit Analysis in Fire Risk Assessment  

SciTech Connect

Under existing methods of probabilistic risk assessment (PRA), the analysis of fire-induced circuit faults has typically been conducted on a simplistic basis. In particular, those hot-short methodologies that have been applied remain controversial in regards to the scope of the assessments, the underlying methods, and the assumptions employed. To address weaknesses in fire PRA methodologies, the USNRC has initiated a fire risk analysis research program that includes a task for improving the tools for performing circuit analysis. The objective of this task is to obtain a better understanding of the mechanisms linking fire-induced cable damage to potentially risk-significant failure modes of power, control, and instrumentation cables. This paper discusses the current status of the circuit analysis task.

LaChance, Jeffrey; Nowlen, Steven P.; Wyant, Frank

1999-05-19T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


401

Investigating dynamic underground coal fires by means of numerical simulation  

Science Journals Connector (OSTI)

......available within the combustion centre. Combustion will only proceed whenever...controls the overall combustion rate. For numerical...transport-only and a chemistry-only part. Common...rate of underground coal fires by oxygen transport......

S. Wessling; W. Kessels; M. Schmidt; U. Krause

2008-01-01T23:59:59.000Z

402

Thermal Effects by Firing Oil Shale Fuel in CFB Boilers  

Science Journals Connector (OSTI)

It is well known that during firing of oil shale fuel the amount of heat released during its combustion per kg of fuel is significantly affected by the endothermic and exothermic processes taking place in mine...

D. Neshumayev; A. Ots; T. Parve; T Pihu

2010-01-01T23:59:59.000Z

403

WILDLAND FIRE SERVICES CENTER FOR ENVIRONMENTAL MANAGEMENT OF MILITARY LANDS  

E-Print Network (OSTI)

of the Warner College of Natural Resources within Colorado State University, we also have access to world class greater than on most public lands. CEMML is a leader in munitions ignition mitigation. #12;WILDLAND FIRE

404

Heat Transfer to the Structure during the Fire  

E-Print Network (OSTI)

The post-flashover Fire Test One of a furnished room in Dalmarnock provides a wealth of information including measurements in both the gas phase and on compartment boundaries (Chapter 3). Total heat fluxes at a number ...

Jowsey, Allan; Torero, Jose L; Lane, Barbara

2007-11-14T23:59:59.000Z

405

Resuspension of radionuclides into the atmosphere due to forest fires  

Science Journals Connector (OSTI)

Two major wild fire episodes occurred in north-western Russia in April/May and August 2008. The burning biomass and heating of the surface soil released several hazardous components into the atmosphere. During...

Jussi Paatero; K. Vesterbacka; U. Makkonen

2009-11-01T23:59:59.000Z

406

Six Sigma process improvements and sourcing strategies following factory fire  

E-Print Network (OSTI)

This thesis addresses Six Sigma process improvements and the supplier management issues resulting from the shift to external suppliers in the aftermath of a fire. Originally, this thesis was to address a lean implementation ...

Egan, Sarah (Sarah J.)

2005-01-01T23:59:59.000Z

407

Move to test nuclear waste site draws fire  

Science Journals Connector (OSTI)

Move to test nuclear waste site draws fire ... The Department of Energy has stirred up a storm of opposition by taking administrative action, bypassing Congress, that would enable it to start testing an underground nuclear waste repository in New Mexico. ...

RICHARD SELTZER

1991-10-14T23:59:59.000Z

408

Emission factor of mercury from coal-fired power stations  

Science Journals Connector (OSTI)

Mercury emission from coal-fired power stations, situated in Poland in the Silesian region ... mercury in the consumed coal and in combustion gas, used in this research, are described. ... the air from coal combu...

Wojciech Mniszek

1994-11-01T23:59:59.000Z

409

Cold Vacuum Drying (CVD) Facility Diesel Generator Fire Protection  

SciTech Connect

This Acceptance Test Procedure (ATP) has been prepared to demonstrate that the Fire Protection and Detection System installed by Project W-441 (Cold Vacuum Drying Facility and Diesel Generator Building) functions as required by project specifications.

SINGH, G.

2000-04-25T23:59:59.000Z

410

Annual Security and Fire Safety Report | 2010 public safety  

E-Print Network (OSTI)

Annual Security and Fire Safety Report | 2010 col u m bia univer sity public safety #12;Contents A Message from the Vice President for Public Safety.............................................1 The Clery .............................................................................................................2 The Department of Public Safety

Kim, Philip

411

Relating violence to MODIS fire detections in Darfur, Sudan  

Science Journals Connector (OSTI)

The Moderate Resolution Imaging Spectroradiometer (MODIS) Thermal Anomalies and Fire Detection data product can provide an input into early warning and rapid response efforts of interest to human rights, humanitarian and security communities. A review ...

Lars Bromley

2010-03-01T23:59:59.000Z

412

Relating violence to MODIS fire detections in Darfur, Sudan  

Science Journals Connector (OSTI)

The Moderate Resolution Imaging Spectroradiometer MODIS Thermal Anomalies and Fire Detection data product can provide an input into early warning and rapid response efforts of interest to human rights, humanitarian and security communities. A review ...

Lars Bromley

2010-05-01T23:59:59.000Z

413

A Natural-Gas-Fired Thermoelectric Power Generation System  

Science Journals Connector (OSTI)

This paper presents a combustion-driven thermoelectric power generation system that uses PbSnTe-based thermoelectric modules. The modules were integrated into a gas-fired furnace with a special burner design. The...

K. Qiu; A.C.S. Hayden

2009-07-01T23:59:59.000Z

414

Low Light Imaging for Power Outage and Fire Detection  

E-Print Network (OSTI)

boats. Fires in Africa Gas flares ­ Persian Gulf Fishing boats & city lights - Japan #12;Sorting The Recovery of Lighting? Gulf Coast USA Radiance Calibrated Lights 2006=red 2003=green 2000=blue #12;New

415

Education, Awareness & Prevention 2012 Annual Security Report and Fire Report  

E-Print Network (OSTI)

1 Education, Awareness & Prevention 2012 Annual Security Report and Fire Report Issue for 2013 criminal activity is being reported, i.e., 2012 TABLE OF CONTENTS Item Page Message from the President Action .................................................................. 14 Crimes Reported to FSUPD

416

CRAD, Fire Protection - October 12, 2012 | Department of Energy  

Office of Energy Efficiency and Renewable Energy (EERE) Indexed Site

- October 12, 2012 October 12, 2012 Fire Protection Inspection Criteria, Approach, and Lines of Inquiry (HSS CRAD 45-34, Rev. 1) This Criteria Review and Approach Document (HSS...

417

Clark County Fire Department 575 E. Flamingo Road Las Vegas,...  

National Nuclear Security Administration (NNSA)

County entities. We look forward to 2009 and the new opportuni- ties ahead Steven M. Smith Fire Chief * Phone Pick-up to First Unit At-Scene and Excludes Non-Emergencies...

418

Light My Fire...Or Yours | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Light My Fire...Or Yours Light My Fire...Or Yours Light My Fire...Or Yours February 6, 2012 - 12:15pm Addthis Ernie Tucker Editor, National Renewable Energy Laboratory It comes as no surprise that 9-out-of-10 American homes burned wood for heat a little more than a century ago. Likewise, it's also probably not news that the number dwindled to less than 1% by the 1970s. After all, who wants to chop and stack cordwood when you can set the thermostat to be comfortable? Perhaps that's why Paul Bunyan is so rarely spotted around town these days. Still, there is something irresistible about the warmth of a crackling fire. That appeal probably explains why fireplaces and wood-burning heating stoves haven't disappeared in many communities, and that upgrades such as energy efficient inserts and stoves are common.

419

Impact of the red imported fire ant upon cotton arthropods  

E-Print Network (OSTI)

IMPACT OF THE RED IMPORTED FIRE ANT UPON COTTON ARTHROPODS A Thesis by RODRIGO ROGELIO DIAZ GALARRAGA Submitted to the Office of Graduate Studies of Texas A&M University in partial fulfillment of the requirements... for the degree of MASTER OF SCIENCE May 2003 Major Subject: Entomology IMPACT OF THE RED IMPORTED FIRE ANT UPON COTTON ARTHROPODS A Thesis By RODRIGO ROGELIO DIAZ GALARRAGA Submitted to Texas A&M University in partial...

Diaz Galarraga, Rodrigo Rogelio

2004-09-30T23:59:59.000Z

420

Dump fire leaves toxic air, sludge A fire which burned for four days at a landfill site in Thessaloniki, sending thick black  

E-Print Network (OSTI)

Dump fire leaves toxic air, sludge A fire which burned for four days at a landfill site to break. This led to sludge flowing into some nearby houses. Authorities are due to begin the cleanup

Columbia University

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


421

Exergetic analysis and evaluation of coal-fired supercritical thermal power plant and natural gas-fired combined cycle power plant  

Science Journals Connector (OSTI)

The present work has been undertaken for energetic and exergetic analysis of coal-fired supercritical thermal power plant and natural gas-fired combined cycle power plant. Comparative analysis has been conducted ...

V. Siva Reddy; S. C. Kaushik; S. K. Tyagi

2014-03-01T23:59:59.000Z

422

A Remote Sensing and GIS Based Investigation of a Boreal Forest Coal Fire  

Science Journals Connector (OSTI)

A coal seam fire in interior Alaska was suspected to have started the Rex Creek forest fire in the summer of 2009. With prevailing winds, the forest fire spread rapidly to the north and within eleven days it burned about 410km2 of boreal forest. Coal seam fires can go unnoticed and unreported when present in remote and inaccessible areas. However, they still pose a serious threat to the surroundings. We used summer-time thermal infrared images from 1999 through 2009 acquired by the Landsat satellite and, through the process of image stacking, identified a region where the surface persistently showed temperatures 5C to 14C higher than the background areas. Field validation confirmed that this thermal anomaly area corresponds to a previously undocumented shallow coal seam fire. Superimposing the boundary of the Rex Creek forest fire revealed that the coal seam fire was at the southern end of the burn area where the forest fire originated. Plotting the location of all lightning strikes during this period helped to rule out lightning as the cause of the forest fire. Coal fires and forest fires can have a complex and dynamic relationship, one being the possible cause of the other. A thorough inventory of all past and present known coal seam fire locations can help to update forest fire hazard maps. A detailed map of shallow coal seam areas can help to prioritize fire fighting operations in order to avoid the chance of starting a new coal seam fire.

Anupma Prakash; Kate Schaefer; William K. Witte; Kim Collins; Rudiger Gens; Michael P. Goyette

2011-01-01T23:59:59.000Z

423

Fire in the Ice, Winter 2005  

NLE Websites -- All DOE Office Websites (Extended Search)

Understanding Methane Understanding Methane Hydrate Behavior .................... 1 Quantitative Assessment of Marine Gas Hydrates ............. 5 New Method for Gas Hydrate Production .............................. 8 Announcements .................. 12 * International Workshop * Chiba, Hedberg Abstracts * Chemists Highlight Hydrates * NETL Solicits Proposals * IODP Planning Two Cruises * Gulf of Mexico Expedition * TOUGH-Fx Training Offered Spotlight on Research ........ 16 Dr. Frank R. Rack CONTACT POINT Ray Boswell National Energy Technology Laboratory (304) 285-4541 (304) 285-4216 fax Ray.Boswell@netl.doe.gov The Fire in the Ice Newsletter is also available online at our website www.netl.doe.gov/scngo/ Natural%20Gas/hydrates T H E N A T I O N A L E N E R G Y T E C H N O L O G Y L A B O R A T O R Y M E T H A N E H Y D R A T E N E W S L E T T E R Vol. 5, Iss. 1

424

Fire in the Ice, Spring 2005  

NLE Websites -- All DOE Office Websites (Extended Search)

Marine Multi-Component Marine Multi-Component Seismology ............................ 1 Discovery of Possible Gas Hydrate Features ................... 5 Monitoring Station Update ..... 8 Announcements .................. 10 * Research Cruise Completed * Advisory Committee Meeting * Hot Ice Project Reports * Norway ICGH Meeting * Simulator Publicly Released * TOUGH-Fx/HYDRATE V 2.4 * AAPG Committee to Meet Spotlight on Research ........ 12 Scott Dallimore CONTACT POINT Ray Boswell National Energy Technology Laboratory (304) 285-4541 (304) 285-4216 fax Ray.Boswell@netl.doe.gov The Fire in the Ice Newsletter is also available online at our website www.netl.doe.gov/scngo/ NaturalGas/hydrates/index.html T H E N A T I O N A L E N E R G Y T E C H N O L O G Y L A B O R A T O R Y M E T H A N E H Y D R A T E N E W S L E T T E R Vol. 5, Iss. 2 ○ ○ ○ ○ ○

425

Fire testing of bare uranium hexafluoride cylinders  

SciTech Connect

In 1965, the Oak Ridge Gaseous Diffusion Plant (ORGDP), now the K-25 Site, conducted a series of tests in which bare cylinders of uranium hexafluoride (UF{sub 6}) were exposed to engulfing oil fires for the US Atomic Energy Commission (AEC), now the US Department of Energy (DOE). The tests are described and the results, conclusions, and observations are presented. Two each of the following types of cylinders were tested: 3.5-in.-diam {times} 7.5-in.-long cylinders of Monel (Harshaw), 5.0-in.-diam {times} 30-in.-long cylinders of Monel, and 8-in.-diam {times} 48-in.-long cylinders of nickel. The cylinders were filled approximately to the standard UF{sub 6} fill limits of 5, 55, and 250 lb, respectively, with a U-235 content of 0.22%. The 5-in.- and 8-in.-diam cylinders were tested individually with and without their metal valve covers. For the 3.5-in.-diam Harshaw cylinders and the 5.0-in.-diam cylinder without a valve cover the valves failed and UF{sub 6} was released. The remaining cylinders ruptured explosively in time intervals ranging from about 8.5 to 11 min.

Pryor, W.A. [PAI Corp., Oak Rige, TN (United States)

1991-12-31T23:59:59.000Z

426

Fire testing of bare uranium hexafluoride cylinders  

SciTech Connect

In 1965, the Oak Ridge Gaseous Diffusion Plant (ORGDP), now the K-25 Site, conducted a series of tests in which bare cylinders of uranium hexafluoride (UF{sub 6}) were exposed to engulfing oil fires for the US Atomic Energy Commission (AEC), now the US Department of Energy (DOE). The tests are described and the results, conclusions, and observations are presented. Two each of the following types of cylinders were tested: 3.5-in.-diam {times} 7.5-in.-long cylinders of Monel (Harshaw), 5.0-in.-diam {times} x 30-in.-long cylinders of Monel, and 8-in.-diam {times} 48-in.-long cylinders of nickel. The cylinders were filled approximately to the standard UF{sub 6} fill limits of 5, 55, and 250 lb, respectively, with a U-235 content of 0.22%. The 5-in.- and 8-in.-diam cylinders were tested individually with and without their metal valve covers. For the 3.5-in.-diam Harshaw cylinders and the 5.0-in.-diam cylinder without a valve cover, the valves failed and UF{sub 6} was released. The remaining 6 cylinders ruptured explosively in time intervals ranging from about 8.5 to 11 min.

Pryor, W.A. [PAI Corp., Oak Ridge, TN (United States)

1991-12-31T23:59:59.000Z

427

The Impact of a Wildland Fire on Air Pollution Concentrations Using WRF/Chem/Fire: An Application over Murcia (Spain)  

Science Journals Connector (OSTI)

In this contribution we will show the impact on air pollution concentration of a Fire developed in the ... of Murcia (Spain). The impact on air pollution concentrations has been done using the WRF/ ... modifying ...

Roberto San Jos; Juan Luis Prez

2014-01-01T23:59:59.000Z

428

Global fire emissions and the contribution of deforestation, savanna, forest, agricultural, and peat fires (1997-2009)  

E-Print Network (OSTI)

15%), agricultural waste burning (3%), and tropi- cal peat3.5), with agricultural waste burning estimated to be theforest 1 Agricultural waste burning 1 Peat fires 3 1 Based

2010-01-01T23:59:59.000Z

429

Audit Report, "Fire Protection Deficiencies at Los Alamos National Laboratory"  

SciTech Connect

The Department of Energy's Los Alamos National Laboratory (Los Alamos) maintains some of the Nation's most important national security assets, including nuclear materials. Many of Los Alamos' facilities are located in close proximity to one another, are occupied by large numbers of contract and Federal employees, and support activities ranging from nuclear weapons design to science-related activities. Safeguarding against fires, regardless of origin, is essential to protecting employees, surrounding communities, and national security assets. On June 1, 2006, Los Alamos National Security, LLC (LANS), became the managing and operating contractor for Los Alamos, under contract with the Department's National Nuclear Security Administration (NNSA). In preparation for assuming its management responsibilities at Los Alamos, LANS conducted walk-downs of the Laboratory's facilities to identify pre-existing deficiencies that could give rise to liability, obligation, loss or damage. The walk-downs, which identified 812 pre-existing fire protection deficiencies, were conducted by subject matter professionals, including fire protection experts. While the Los Alamos Site Office has overall responsibility for the effectiveness of the fire protection program, LANS, as the Laboratory's operating contractor, has a major, day-to-day role in minimizing fire-related risks. The issue of fire protection at Los Alamos is more than theoretical. In May 2000, the 'Cerro Grande' fire burned about 43,000 acres, including 7,700 acres of Laboratory property. Due to the risk posed by fire to the Laboratory's facilities, workforce, and surrounding communities, we initiated this audit to determine whether pre-existing fire protection deficiencies had been addressed. Our review disclosed that LANS had not resolved many of the fire protection deficiencies that had been identified in early 2006: (1) Of the 296 pre-existing deficiencies we selected for audit, 174 (59 percent) had not been corrected; and, (2) A substantial portion of the uncorrected deficiencies, 86 (49 percent) were considered by the walk-down teams to be significant enough to warrant compensatory actions until the deficiency was corrected or was tracked to closure through implementation of corrective actions. Further, we found that 32 of the significant deficiencies had been closed by the previous Los Alamos contractor, prior to LANS assuming responsibility for operation of the Laboratory, even though the deficiencies had not been corrected. A fire protection expert provided technical support during the audit. As an example of uncorrected problems, LANS had not resolved, by performing periodic tests, a deficiency identified in 2006 regarding a kitchen hood fire suppression system in a facility located within the Los Alamos Neutron Science Center. Such systems are required to be tested twice a year by the National Fire Protection Association standard, a standard that had been adopted by Department of Energy under DOE Order 420.1B. Yet, in 2006, the LANS walk-down team recognized that this system had not been inspected since May 2004 and noted that deficient suppression systems could result in significantly high levels of property damage and loss. After we brought this issue to management's attention on February 6, 2009, LANS officials stated that the Laboratory would correct this deficiency. As with the problems involving the fire suppression system, we observed that LANS had not always corrected life safety deficiencies involving building exits at one of its primary facilities. This included providing a secondary emergency exit for a building with occupants on multiple floor levels. LANS had removed personnel from the third floor and improved the sprinkler system of the facility, but it had still not provided a secondary exit for personnel on the second floor by the time we completed our review. NNSA has since stated that this fire protection issue will be completely addressed by relocating personnel from the second floor. Perhaps most serious, our testing revealed that a number of deficien

None

2009-06-01T23:59:59.000Z

430

Proceedings of the Second International Symposium on Fire Economics, Planning, and Policy: A Global View Fire Management Plan at Regional Scale in  

E-Print Network (OSTI)

protection (L.353/2000) is presented. In particular the main features of the recent regional fire management of the fire management plan are reported, together with the criteria followed to define the protection at regional scale are based on the wildland fire protection national law L. 353/2000. This regulation

Standiford, Richard B.

431

Current Fire Extinguisher Colour Codes (UK) Fire extinguishers meeting BS EN3 are manufactured with a red body and have a band of a second colour  

E-Print Network (OSTI)

, Straw, Textiles, Coal etc. Class B Fires Flammable Liquids i.e.: Petrol, Diesel, Oils, Paraffin etc identification easier for the user. DO NOT HOLD THE HORN WHEN OPERATING Use on: wood, paper, textiles, liquid and electrical fires. Powder Use on: wood, paper, textiles and liquid fires. Foam Use on: liquid and electrical

Guo, Zaoyang

432

Page 1 | B.S.E.T. in Fire Safety Engineering Technology | Academic Plan of Study Updated March 2014 B.S.E.T. in Fire Safety Engineering Technology  

E-Print Network (OSTI)

· Credit Hours: 125 hours · Concentrations: Fire Safety, Fire Protection · Declaring the Major: Minimum GPAD, Coordinator-Fire Protection Concentration, 704-687-3727, aixi.zhou@uncc.edu Ms. Madelyn S. Wilson, Student Concentration) as well as those preparing for work in fire protection (Fire Protection Concentration) related

Raja, Anita

433

High opacity white plumes from coal-fired and oil-fired sources  

SciTech Connect

In recent years, with the installation of high efficiency particulate emission control devices on utility and industrial boilers, high-opacity white plumes have become more of a problem because formerly the emissions of primary particulate matter obscured and/or served as a condensing surface for the condensable material. The problem common to some of these installations is the violation of opacity standards due to the presence of a high-opacity persistent plume that emits from the stack. Oil fired boilers violating opacity standards typically comply with mass emission standards while coal fired boilers typically violate visual emission standards when simultaneously violating mass emission standards. The investigation reported here focuses on the atypical case when in-situ transmissometer measurements show compliance but plume opacity as measured by Reference Method 9 or LIDAR exceeds opacity standards. This case comes about due to gas phase reactions that produce fine aerosols, vapor phase condensation and physical agglomeration of sub-micron sized clusters and particles. The plume opacity control technology applicable to these aerosols which are created and/or grown in white plume is discussed in this paper.

Lee, K.T. (National Cheng Kung Univ. (TW))

1988-01-01T23:59:59.000Z

434

242T FACP replacement  

SciTech Connect

This Acceptance Test Procedure (ATP) has been prepared to demonstrate that the Fire Protection system functions as required by project criteria. This ATP will test the Pyrotronic CP-400 fire alarm control panel (FACP), and interfaces with the radio fire alarm reporting box, alarm/supervisory initiating devices, and alarm indicating appliances. This document is to certify the installation and testing of the fire alarm control panel and all attached devices to insure the Hanford Fire Dept. receives the proper signals. This fire alarm control panel is located in Bldg. 242T in the 200 W Area of Hanford.

Ferry, M.F.

1994-11-17T23:59:59.000Z

435

2707SX FACP replacement  

SciTech Connect

This Acceptance Test Procedure (ATP) has been prepared to demonstrate that the Fire Protection system functions as required by project criteria. This ATP will test the Pyrotronic CP-400 fire alarm control panel (FACP), and interfaces with the radio fire alarm reporting box, alarm/supervisory initiating devices, and alarm indicating appliances. This document is to certify the installation of the fire alarm control panel and all attached devices to insure the Hanford Fire Dept. receives the proper signals. This particular fire alarm control panel services Bldg. 2707SX in the 200W Area of Hanford.

Ferry, M.F.

1994-11-17T23:59:59.000Z

436

Suitability of the Weather Research and Forecasting (WRF) Model to Predict the June 2005 Fire Weather for Interior Alaska  

E-Print Network (OSTI)

temperature, and daily accumulated shortwave radiation well. Daily minimum (maximum) temperature and relative to local fire management authorities on the potential for wild- fires to plan prescribed burns, alert of fire control into fire indices that reflect protection require- ments. The National Fire Danger Rating

Moelders, Nicole

437

DynCorp Tricities Services, Inc. Hanford fire department FY 1998 annual work plan  

SciTech Connect

The mission of the Hanford Fire Department (HFD) is to support the safe and timely cleanup of the Hanford site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating emergency situations which could threaten the operations, employees, or interest of the U.S. Department of Energy operated Hanford site. This includes response to surrounding fire departments/districts under mutual aid and state mobilization agreements and fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System) and various commercial entities operating on site through Requests for Service from DOE-RL. This fire department also provides site fire marshal overview authority, fire system testing and maintenance, respiratory protection services, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention education. This plan provides a program overview, program baselines, and schedule baseline.

Good, D.E.

1997-08-19T23:59:59.000Z

438

Fire hazards analysis for the uranium oxide (UO{sub 3}) facility  

SciTech Connect

The Fire Hazards Analysis (FHA) documents the deactivation end-point status of the UO{sub 3} complex fire hazards, fire protection and life safety systems. This FHA has been prepared for the Uranium Oxide Facility by Westinghouse Hanford Company in accordance with the criteria established in DOE 5480.7A, Fire Protection and RLID 5480.7, Fire Protection. The purpose of the Fire Hazards Analysis is to comprehensively and quantitatively assess the risk from a fire within individual fire areas in a Department of Energy facility so as to ascertain whether the objectives stated in DOE Order 5480.7, paragraph 4 are met. Particular attention has been paid to RLID 5480.7, Section 8.3, which specifies the criteria for deactivating fire protection in decommission and demolition facilities.

Wyatt, D.M.

1994-12-06T23:59:59.000Z

439

Alternative Fuels Data Center: Rio Rico Fire District Turns Grease Into  

Alternative Fuels and Advanced Vehicles Data Center (EERE)

Rio Rico Fire District Rio Rico Fire District Turns Grease Into Biodiesel to someone by E-mail Share Alternative Fuels Data Center: Rio Rico Fire District Turns Grease Into Biodiesel on Facebook Tweet about Alternative Fuels Data Center: Rio Rico Fire District Turns Grease Into Biodiesel on Twitter Bookmark Alternative Fuels Data Center: Rio Rico Fire District Turns Grease Into Biodiesel on Google Bookmark Alternative Fuels Data Center: Rio Rico Fire District Turns Grease Into Biodiesel on Delicious Rank Alternative Fuels Data Center: Rio Rico Fire District Turns Grease Into Biodiesel on Digg Find More places to share Alternative Fuels Data Center: Rio Rico Fire District Turns Grease Into Biodiesel on AddThis.com... March 3, 2013 Rio Rico Fire District Turns Grease Into Biodiesel

440

Prescriptive vs. performance based cook-off fire testing.  

SciTech Connect

In the fire safety community, the trend is toward implementing performance-based standards in place of existing prescriptive ones. Prescriptive standards can be difficult to adapt to changing design methods, materials, and application situations of systems that ultimately must perform well in unwanted fire situations. In general, this trend has produced positive results and is embraced by the fire protection community. The question arises as to whether this approach could be used to advantage in cook-off testing. Prescribed fuel fire cook-off tests have been instigated because of historical incidents that led to extensive damage to structures and loss of life. They are designed to evaluate the propensity for a violent response. The prescribed protocol has several advantages: it can be defined in terms of controllable parameters (wind speed, fuel type, pool size, etc.); and it may be conservative for a particular scenario. However, fires are inherently variable and prescribed tests are not necessarily representative of a particular accident scenario. Moreover, prescribed protocols are not necessarily adaptable and may not be conservative. We also consider performance-based testing. This requires more knowledge and thought regarding not only the fire environment, but the behavior of the munitions themselves. Sandia uses a performance based approach in assuring the safe behavior of systems of interest that contain energetic materials. Sandia also conducts prescriptive fire testing for the IAEA, NRC and the DOT. Here we comment on the strengths and weakness of both approaches and suggest a path forward should it be desirable to pursue a performance based cook-off standard.

Nakos, James Thomas; Tieszen, Sheldon Robert; Erikson, William Wilding; Gill, Walter; Blanchat, Thomas K.

2010-07-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


441

Tribology in coal-fired power plants  

Science Journals Connector (OSTI)

Material wear and degradation is of great importance to the economy of South Africa especially within the mining, agriculture, manufacturing and power generation fields. It has been found that unexpected and high rates of fly-ash erosion occur at certain sections of power plants, this is particularly evident at the Majuba power station. The loss of small amounts of material due to erosion can be enough to cause serious damage and significantly reduce the working lifetime of, for, e.g. hopper liners. This study investigated the long-term solid particle erosion of a range of oxide and nitride-fired SiC-based ceramics and alumina with the aim of reducing erosive wear damage in power plants. This entailed carrying out experimental tests on an in-house built erosion testing machine that simulate the problems encountered in the industry. The target materials were eroded with 125180?m silica sand at shallow and high impact angles. The surface wear characteristics were studied using both light and scanning electron microscopy (SEM). The results obtained indicate that the erosion rates of the materials remain fairly constant from the onset. It was found that prolonged exposure to erosion results in the progressive removal of the matrix and subsequent loss of unsupported SiC particulates. The fact that the particles were relatively small did not have a significant effect on the erosion rate. This would explain the observed constant rates of erosion for longer periods. These behaviours can be further explained in terms of the composition and mechanical properties of the erodents and target ceramics.

D.O. Moumakwa; K. Marcus

2005-01-01T23:59:59.000Z

442

Campus Holiday Fire Safety According to the U.S. Fire Administration, each year, 230 home fires start with Christmas trees. These  

E-Print Network (OSTI)

start with Christmas trees. These fires cause an average of 4 deaths, 21 injuries and $17.3 million of Approval on packages of decorative materials. · Only UL approved, low wattage, fused lights may be used to decorate trees. No screw-in type bulbs are permitted. · Lights must be unplugged at the end of each

Burke, Peter

443

Optical extinction of smoke from the Kuwait oil fires  

SciTech Connect

Aircraft-based measurements of optical extinction, optical scattering, and particle mass concentrations were obtained in the smoke from the Kuwait oil fires during May and June 1991. These measurements were used to derive optical absorption, single-scattering albedo ({anti {omega}}), specific absorption and the amount of soot in the smoke. Measurements were made in smoke from individual oil wells, pool fires and in composite smoke plumes. The value of {anti {omega}} for smoke from the individual fires was either 0.35-0.4 (for the black smoke) or 0.85-0.95 (for the white smoke). For the aged composite plume from all of the fires, {anti {omega}} ranged from 0.52 to 0.6. The specific absorption of the composite smoke varied from about 2 m{sup 2} g{sup {minus}1} near the fires to about 1.5 m{sup 2} g{sup {minus}1} well downwind. 8 refs., 2 figs., 1 tab.

Weiss, R.E. [Radiance Research, Inc., Seattle, WA (United States); Hobbs, P.V. [Univ. of Washington, Seattle, WA (United States)

1992-09-20T23:59:59.000Z

444

Fire protection review, Westinghouse Idaho Nuclear Company, Idaho Falls, Idaho  

SciTech Connect

A fire protection survey was conducted for the Department of Energy at the Westinghouse Idaho Nuclear Company, INC., Idaho Falls, Idaho, on April 24--27, April 30--May 4, June 4--8, and June 11--15, 1990. The purpose of the survey was to review the facility's fire protection program and to make recommendations according to the following criteria established by the Department of Energy: (1) Recommendations which would be made as the result of an improved risk or Highly Protected Risk (HPR) fire inspection of an industrial insured facility. (2) Identification of areas which are presently not protected or are inadequately protected where provision of automatic protection would reduce a fire or explosion loss to less than $1 million. (3) Identification of areas where loss potentials exceed $50 million assuming a failure of automatic protection systems and subsequent reliance only on separation and fire walls. (4) Evaluation of adequacy of compliance with recommendations made in prior surveys. Findings and recommendations in this report reflect to some degree the relative importance of the operation and the time to restore it to useful condition in the event that a loss were to occur.

Dobson, P.H.

1990-10-01T23:59:59.000Z

445

Proceedings of the Second International Symposium on Fire Economics, Planning, and Policy: A Global View Proceedings of the Second International Symposium on Fire Economics, Planning, and Policy: A Global View  

E-Print Network (OSTI)

: A Global View Optimal Maneuvering of Forest Fire Protection Resources1 Joseph Romanovsky,2 Vladimir. t is taken in consideration, that now there are no one dispatcher bases that monitor both air fire protection and land fire protection

Standiford, Richard B.

446

Vegetation dynamics and exotic plant invasion following high severity crown fire in a southern California conifer forest  

Science Journals Connector (OSTI)

Early post-fire vegetation dynamics following large, severe forest fires are largely unknown for the southern ... to historic fire suppression. Vegetation in 38 forest stands was surveyed (2004, 2005, and...2 qua...

Janet Franklin

2010-04-01T23:59:59.000Z

447

A Web-Oriented Geoinformation System Application for Forest Fire Danger Prediction in Typical Forests of the Ukraine  

Science Journals Connector (OSTI)

A web-oriented geoinformation system for forest fire danger prediction based on a probabilistic fire danger criteria is described in this chapter. A new method for determining the probabilistic fire danger cri...

Nikolay Baranovskiy; Marina Zharikova

2014-01-01T23:59:59.000Z

448

Gas-Fired Boilers and Furnaces | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Gas-Fired Boilers and Furnaces Gas-Fired Boilers and Furnaces Gas-Fired Boilers and Furnaces May 16, 2013 - 4:36pm Addthis A residential natural gas meter. A residential natural gas meter. What does this mean for me? Your gas boiler or furnace may be oversized, particularly if you've upgraded the energy efficiency of your home. Your gas boiler or furnace can be retrofitted to improve its energy efficiency. Gas boilers and furnaces can be fueled by either natural gas or propane with simple modifications accounting for the different characteristics of the fuels. Propane is usually more expensive as a fuel, but is available throughout the United States. Natural gas supplies depend on having a natural gas distribution system in your area, and areas at the end of the pipeline (such as the Northeast) tend to pay higher prices for natural gas.

449

Oil-Fired Boilers and Furnaces | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Oil-Fired Boilers and Furnaces Oil-Fired Boilers and Furnaces Oil-Fired Boilers and Furnaces May 16, 2013 - 3:15pm Addthis Diagram of an oil boiler. New tanks are generally double-wall or have a spill container built underneath to reduce the chances of an oil spill. Typically, the tank drip pan shown here is required only for single-wall tanks and would extend the full width of the tank. | Photo courtesy State of Massachusetts. Diagram of an oil boiler. New tanks are generally double-wall or have a spill container built underneath to reduce the chances of an oil spill. Typically, the tank drip pan shown here is required only for single-wall tanks and would extend the full width of the tank. | Photo courtesy State of Massachusetts. What does this mean for me? If you have an oil furnace or boiler, you can now burn oil blended

450

Oil-Fired Boilers and Furnaces | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Oil-Fired Boilers and Furnaces Oil-Fired Boilers and Furnaces Oil-Fired Boilers and Furnaces May 16, 2013 - 3:15pm Addthis Diagram of an oil boiler. New tanks are generally double-wall or have a spill container built underneath to reduce the chances of an oil spill. Typically, the tank drip pan shown here is required only for single-wall tanks and would extend the full width of the tank. | Photo courtesy State of Massachusetts. Diagram of an oil boiler. New tanks are generally double-wall or have a spill container built underneath to reduce the chances of an oil spill. Typically, the tank drip pan shown here is required only for single-wall tanks and would extend the full width of the tank. | Photo courtesy State of Massachusetts. What does this mean for me? If you have an oil furnace or boiler, you can now burn oil blended

451

Gas-Fired Boilers and Furnaces | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Gas-Fired Boilers and Furnaces Gas-Fired Boilers and Furnaces Gas-Fired Boilers and Furnaces May 16, 2013 - 4:36pm Addthis A residential natural gas meter. A residential natural gas meter. What does this mean for me? Your gas boiler or furnace may be oversized, particularly if you've upgraded the energy efficiency of your home. Your gas boiler or furnace can be retrofitted to improve its energy efficiency. Gas boilers and furnaces can be fueled by either natural gas or propane with simple modifications accounting for the different characteristics of the fuels. Propane is usually more expensive as a fuel, but is available throughout the United States. Natural gas supplies depend on having a natural gas distribution system in your area, and areas at the end of the pipeline (such as the Northeast) tend to pay higher prices for natural gas.

452

Avestar® - Syngas-Fired Combined Cycle Dynamic Simulator  

NLE Websites -- All DOE Office Websites (Extended Search)

Syngas-Fired Combined Cycle Dynamic Simulator Syngas-Fired Combined Cycle Dynamic Simulator The AVESTAR® center offers courses using the Combined Cycle Simulator, focusing on the power generation process after gasification. This simulator is well-suited for concentrated training on operation and control of the gas and steam turbines; condensate, feed water, and circulating water systems; heat recovery steam generator; and selective catalytic reduction (SCR) unit. Combined cycle simulator startup operations include bringing up the gas turbine to rated speed on natural gas and then switching over to the firing of synthesis gas. Key capabilities of the Combined Cycle Simulator include: Combined Cycle Simulator Operator training station HMI display for overview of Gas Turbine - Train A Normal base load operation

453

PrairieFire BioFuels Cooperative | Open Energy Information  

Open Energy Info (EERE)

PrairieFire BioFuels Cooperative PrairieFire BioFuels Cooperative Jump to: navigation, search Name PrairieFire BioFuels Cooperative Place Madison, Wisconsin Zip 53704 Product A member-owned cooperative which produces and distributes vegetable oil-based biodiesel. Coordinates 43.07295°, -89.386694° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":43.07295,"lon":-89.386694,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

454

An economic analysis of coal-fired magnetohydrodynamics  

SciTech Connect

This paper is an economic comparison of the coal-fired magnetohydrodynamics (MHD) technology with conventional coal-fired steam power plants; the comparisons made are based on a levelized Cost of Electricity for similarly sized plants. A revenue requirement analysis was used for the economic evaluation of engineering alternatives in the electric utility industry. The basis for the MHD technology used in the comparison is a recently completed conceptual design done by the MHD Development Corporation for retrofitting the coal-fired J.E. Corette plant with a 250-MW MHD unit. A 500-MW MHD consideration is based on the Advanced Power Train predictions of the Department of Energy (DOE), and the conventional plant considerations are based on the Technical Assessment Guide of the Electric Power Research Institute (EPRI). The economic comparisons indicate that MHD is considerably more attractive than a conventional unit.

Lohrasbi, J.; Ashby, G. (MSE, Inc., Butte, MT (United States)); Walter, F.E. (Montana Power Co., Butte, MT (United States))

1991-01-01T23:59:59.000Z

455

Analysis of coal-firing modes shows pulverized least costly  

SciTech Connect

A plant owner opting to build a new coal-fired facility has several processes from which to choose. Among the most common are the spreader-stoker- and the pulverized-coal-fired boiler. Since pollution control is now an integral part of any coal-fired operation, fluidized-bed combustion (FBC) is becoming increasingly popular. Reason: This process does not require auxiliary equipment to control SO/sub 2/. Comparing the operation and economics of four coal-burning processes can help make this selection a somewhat easier one. This analysis examines four types of combustion: spreader stoker, pulverized coal, bubbling fluidized bed, and circulating fluidized bed. The descriptions are for a 200,000-lb/hr unit operating under like conditions.

Lutwen, R.C.; Fitzpatrick, T.J.

1986-04-01T23:59:59.000Z

456

Integration of a MEMS based safe arm and fire device  

Science Journals Connector (OSTI)

The paper describes a new architecture of a Safe Arm and Fire device (SAF) that could constitute a real breakthrough for safe miniature fuzing device. On the one hand, it takes all the functions embodied in a conventional mechanical arm and fire system and integrates them in a single 1cm3 package made of assembly of different parts. On the other hand, for the first time, it combines a mechanical arming unit with electrical safety functionalities on the same silicon initiator's chip. It respects the STANAG 4187 norm (1A/W during 5min of not fire) and requires only 635mW for ignition. The paper presents the design, fabrication and test of one miniature SAF device integrating a micropyrotechnical actuation.

Hlne Pezous; Carole Rossi; Marjorie Sanchez; Fabrice Mathieu; Xavier Dollat; Samuel Charlot; Ludovic Salvagnac; Vronique Condra

2010-01-01T23:59:59.000Z

457

Fire protection guide for solid waste metal drum storage  

SciTech Connect

This guide provides a method to assess potential fire development in drum storage facilities. The mechanism of fire propagation/spread through stored drum arrays is a complex process. It involves flame heat transfer, transient conduction,convection, and radiation between drums (stored in an array configuration). There are several phenomena which may occur when drums are exposed to fire. The most dramatic is violent lid failure which results in total lid removal. When a drum loses its lid due to fire exposure, some or all of the contents may be ejected from the drum, and both the ejected combustible material and the combustible contents remaining within the container will burn. The scope of this guide is limited to storage arrays of steel drums containing combustible (primarily Class A) and noncombustible contents. Class B combustibles may be included in small amounts as free liquid within the solid waste contents.Storage arrays, which are anticipated in this guide, include single or multi-tier palletized (steel or wood pallets) drums,high rack storage of drums, and stacked arrays of drums where plywood sheets are used between tiers. The purpose of this guide is to describe a simple methodology that estimates the consequences of a fire in drum storage arrays. The extent of fire development and the resulting heat release rates can be estimated. Release fractions applicable to this type of storage are not addressed, and the transport of contaminants away from the source is not addressed. However, such assessments require the amount of combustible material consumed and the surface area of this burning material. The methods included in this guide do provide this information.

Bucci, H.M.

1996-09-16T23:59:59.000Z

458

Fire tests on defective tank-car thermal protection systems  

Science Journals Connector (OSTI)

Many railway tank-cars carrying hazardous materials are thermally protected from fire impingement by thermal insulation and a steel jacket applied to the outside of the tank-car shell. Over time, it is possible that the thermal insulation will sag, rip, degrade, or be crushed under the steel jacket. A thermographic technique to determine whether or not a tank has insulation deficiencies has been developed, but it is necessary to determine which thermal deficiencies do not affect a tanks survivability in a fire and which thermal deficiencies must be repaired. In order to develop a guideline in assessing thermal defects, a thermal model and experimental data would be beneficial. A series of fire tests were performed on a quarter-section tank-car mock-up to assist in developing a guideline and to provide validation data for a thermal model. Twelve fire tests, with constant, credible, simulated pool fire conditions, were performed on the tank-car mock-up with various insulation deficiencies. An infrared thermal imaging camera was used to measure the tank wall temperature. The thermal images were useful in determining the temperature profiles across the defects at different times and the transient temperature behaviour at different locations. It was seen that the properly installed thermal protection system significantly reduced the heat transfer from the fire to the tank wall. It was also seen that the steel jacket alone (i.e. 100% defect) acted as a radiation shield and provided a significant level of protection. With small defects, it was observed that the surrounding protected material provided a cooling effect by thermal conduction. A square defect greater than about 40 cm on each side should be considered significant, because unlike smaller defects, there is little benefit from the surrounding material as far as the peak defect temperature is concerned.

J.D.J VanderSteen; A.M Birk

2003-01-01T23:59:59.000Z

459

Multi-Function Fuel-Fired Heat Pump  

NLE Websites -- All DOE Office Websites (Extended Search)

Multi-Function Fuel-Fired Heat Pump Multi-Function Fuel-Fired Heat Pump CRADA Ed Vineyard Oak Ridge National Laboratory, Building Equipment Research vineyardea@ornl.gov, 865-576-0576 April 2, 2013 2 | Building Technologies Office eere.energy.gov Purpose & Objectives Problem Statement: 55% residential building energy use for space conditioning & water heating; highly efficient systems needed to facilitate DOE/BTO goal for 50% reduction in building energy use by 2030 Impact of Project: Cumulative energy savings potential of 0.25 Quads

460

Forecasting the probability of forest fires in Northeast Texas  

E-Print Network (OSTI)

class interval 39 15. Calculated daily fires from the best linear relationship. 52 16. Calculated daily fires from the best linear relationship and the best transformations. . . . 52 1. INTRODUCTION A~A' i The aim of this study is to determine... spontaneous combustion are raze and the influence of human behavior can not be predicted or measured The citations on the following pages follow the style of the J i f A~li d M~f* i reliably. The only important variable from a meteorological view- point...

Wadleigh, Stuart Allen

1972-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


461

Case studies on recent fossil-fired plants  

SciTech Connect

The article summarises the findings of case studies on fossil-fired power plants carried out by the IEA Clean Coal Centre for the IEA at the request of world leaders at the Gleneagles G8 Summit in July 2005. The studies compared the cost, efficiency and emissions of eight recently constructed coal-fired plants using pulverized coal combustion with subcritical, supercritical or ultra-supercritical steam turbine cycles. Also included was a review of IGCC developments. A case study of a natural gas combined-cycle plant was included for comparison. The full report has been published by the IEA. 1 tab.

Henderson, C. [IEA Clean Coal Centre, London (United Kingdom)

2007-12-31T23:59:59.000Z

462

Energy from waste via coal/waste co-firing  

SciTech Connect

The paper reviews the feasibility of waste-to-energy plants using the cocombustion of coal with refuse-derived fuels. The paper discusses the types of wastes available: municipal solid wastes, plastics, tires, biomass, and specialized industrial wastes, such as waste oils, post-consumer carpet, auto shredder residues, and petroleum coke. The five most common combustion systems used in co-firing are briefly described. They are the stoker boiler, suspension-fired boilers, cyclone furnaces, fluidized bed boilers, and cement kilns. The paper also discusses the economic incentives for generating electricity from waste.

Winslow, J.; Ekmann, J.; Smouse, S. [Dept. of Energy, Pittsburgh, PA (United States). Pittsburgh Energy Technology Center; Ramezan, M. [Burns and Roe Services Corp., Pittsburgh, PA (United States); Harding, S.

1996-12-31T23:59:59.000Z

463

Chip-Firing And A Devils Staircase  

E-Print Network (OSTI)

The devils staircase a continuous function on the unit interval [0,1] which is not constant, yet is locally constant on an open dense set is the sort of exotic creature a combinatorialist might never expect to encounter in real life. We show how a devils staircase arises from the combinatorial problem of parallel chip-firing on the complete graph. This staircase helps explain a previously observed mode locking phenomenon, as well as the surprising tendency of parallel chip-firing to find periodic states of small period.

Lionel Levine

464

Building Technologies Office: Gas-Fired Absorption Heat Pump Water Heater  

NLE Websites -- All DOE Office Websites (Extended Search)

Gas-Fired Absorption Gas-Fired Absorption Heat Pump Water Heater Research Project to someone by E-mail Share Building Technologies Office: Gas-Fired Absorption Heat Pump Water Heater Research Project on Facebook Tweet about Building Technologies Office: Gas-Fired Absorption Heat Pump Water Heater Research Project on Twitter Bookmark Building Technologies Office: Gas-Fired Absorption Heat Pump Water Heater Research Project on Google Bookmark Building Technologies Office: Gas-Fired Absorption Heat Pump Water Heater Research Project on Delicious Rank Building Technologies Office: Gas-Fired Absorption Heat Pump Water Heater Research Project on Digg Find More places to share Building Technologies Office: Gas-Fired Absorption Heat Pump Water Heater Research Project on AddThis.com...

465

Saving Energy and Money at 24/7 Fire Stations | Department of Energy  

Energy.gov (U.S. Department of Energy (DOE)) Indexed Site

Saving Energy and Money at 24/7 Fire Stations Saving Energy and Money at 24/7 Fire Stations Saving Energy and Money at 24/7 Fire Stations June 28, 2010 - 11:11am Addthis Coal Creek Fire and Rescue's fire station in New Richmond, Ind. where a new furnace and air conditioner will save energy and money. | Photo courtesy of New Richmond Coal Creek Fire and Rescue's fire station in New Richmond, Ind. where a new furnace and air conditioner will save energy and money. | Photo courtesy of New Richmond What are the key facts? The Indiana Office of Energy Development received $14.1 million in EECBG grants from the American Recovery and Reinvestment Act "The fire station is a building that is in use 24 hours a day, 7 days a week, so naturally it consumes a significant amount of energy," says Molly Whitehead, grants specialist for the Indiana Office of Energy Development.

466

UrbanSolutionsCenter Landscape Maintenance Practices Influence Fire Ant Establishment  

E-Print Network (OSTI)

UrbanSolutionsCenter Landscape Maintenance Practices Influence Fire Ant Establishment Background one of our most economically important pests in urban landscapes. Fire Ants cause extensive mounding are often necessary in urban landscapes around residential and commercial buildings, in parks

467

Thermal buckling of metal oil tanks subject to an adjacent fire  

E-Print Network (OSTI)

Fire is one of the main hazards associated with storage tanks containing flammable liquids. These tanks are usually closely spaced and in large groups, so where a petroleum fire occurs, adjacent tanks are susceptible to ...

Liu, Ying

2011-01-01T23:59:59.000Z

468

Thermal buckling of metal oil tanks subject to an adjacent fire  

E-Print Network (OSTI)

Fire is one of the main hazards associated with storage tanks containing flammable liquids. These tanks are usually closely spaced and in large groups, so where a petroleum fire occurs, adjacent tanks are susceptible to ...

Liu, Ying

2011-11-22T23:59:59.000Z

469

Proceedings of 4th Fire Behavior and Fuels Conference, July 1 4, 2013, St. Petersburg, Russia  

E-Print Network (OSTI)

Proceedings of 4th Fire Behavior and Fuels Conference, July 1 ­ 4, 2013, St. Petersburg, Russia Fire Behavior and Fuels Conference, July 1 ­ 4, 2013, St. Petersburg, Russia Published

470

Fire dynamics during the 20th century simulated by the Community Land Model  

E-Print Network (OSTI)

Fire is an integral Earth System process that interacts with climate in multiple ways. Here we assessed the parametrization of fires in the Community Land Model (CLM-CN) and improved the ability of the model to reproduce ...

Kloster, S.; Mahowald, N. M.; Randerson, J. T.; Thornton, P. E.; Hoffman, F. M.; Levis, Samuel; Lawrence, P. J.; Feddema, Johannes J.; Oleson, Keith W.; Lawrence, D. M.

2010-01-01T23:59:59.000Z

471

309 Building fire protection analysis and justification for deactivation of sprinkler system. Revision 1  

SciTech Connect

Provide a `graded approach` fire evaluation in preparation for turnover to Environmental Restoration Contractor for D&D. Scope includes revising 309 Building book value and evaluating fire hazards, radiological and toxicological releases, and life safety issues.

Conner, R.P.

1997-06-25T23:59:59.000Z

472

Fire Ant Control: The Two-Step Method and Other Approaches  

E-Print Network (OSTI)

There may not be one "best way to control fire ants, but this publication can help you find the most cost-effective and environmentally sound method for each situation. It includes information on fire ant identification, control products...

Drees, Bastiaan M.; Schofield, Kimberly; Brown, Elizabeth; Nester, Paul; Keck, Molly; Flanders, K.

2008-03-27T23:59:59.000Z

473

Preliminary fire hazards analysis for W-211, Initial Tank Retrieval Systems  

SciTech Connect

A fire hazards analysis (FHA) was performed for Project W-211, Initial Tank Retrieval System (ITRS), at the Department of Energy (DOE) Hanford site. The objectives of this FHA was to determine (1) the fire hazards that expose the Initial Tank Retrieval System or are inherent in the process, (2) the adequacy of the fire-safety features planned, and (3) the degree of compliance of the project with specific fire safety provisions in DOE orders and related engineering codes and standards. The scope included the construction, the process hazards, building fire protection, and site wide fire protection. The results are presented in terms of the fire hazards present, the potential extent of fire damage, and the impact on employees and public safety. This study evaluated the ITRS with respect to its use at Tank 241-SY-101 only.

Huckfeldt, R.A.

1995-03-16T23:59:59.000Z

474

Possible Locations for Gas-Fired Power Generation in Southern Germany  

Science Journals Connector (OSTI)

Gas-fired power generation has not only grown continuously in Europe, ... . Significant transport capacities in a high pressure gas grid are required to guarantee stable generation of gas-fired electricity. The p...

Joachim Mller-Kirchenbauer

2013-01-01T23:59:59.000Z

475

Lessons Learned from Internal Fire PSAs on Candu Reactors and PWRs in Korea  

SciTech Connect

Internal fire risk has been one of the major concerns for nuclear power plants. To reduce the risk from internal fire, installing the suppression system, establishment of fire protection program, changing to qualified cables, and sealing the opening can be considered. The approaches to fire protection design are different for each plant design, and they are highly dependent on the plant type. The fire PSA revealed that the potential plant risk due to a fire event is highly dependent on the design. The approaches to fire protection design are different for each plant type, especially between Wolsong Unit 1 (Candu) and Korea Standard Nuclear Plants (KSNP). In this paper, plant design and fire PSA of Wolsong Unit 1 (Candu) were compared with those of the KSNP (PWR) to identify plant-specific and risk-significant items. (authors)

Kim, Sung-Hyun; Jeong, Beom-Hee; Kang, Sun-Koo [Integrated Safety Assessment Department Korea Power Engineering Co., 360-9, Mabuk-Ri, Kusung-Eup, Yongin-Shi, Kyunggi-Do, 449-713 (Korea, Republic of); Jeong, Young-Ki; Kim, Poong-Shick; Cho, Byung-Ok [Nuclear Safety and Technology Department, Korea Hydro and Nuclear Power Co., 167, Samseong-Dong, Gangnam-Gu, Seoul 135-791 (Korea, Republic of)

2004-07-01T23:59:59.000Z

476

Advanced Development Of The Coal Fired Oxyfuel Process With CO2...  

Open Energy Info (EERE)

Development Of The Coal Fired Oxyfuel Process With CO2 Separation ADECOS Jump to: navigation, search Name: Advanced Development Of The Coal-Fired Oxyfuel Process With CO2...

477

The application of expansion foam on liquefied natural gas (LNG) to suppress LNG vapor and LNG pool fire thermal radiation.  

E-Print Network (OSTI)

??Liquefied Natural Gas (LNG) hazards include LNG flammable vapor dispersion and LNG pool fire thermal radiation. A large LNG pool fire emits high thermal radiation (more)

Suardin, Jaffee Arizon

2009-01-01T23:59:59.000Z

478

Air Pollution Control Regulations: No. 13- Particulate Emissions from Fossil Fuel Fired Steam or Hot Water Generating Units (Rhode Island)  

Energy.gov (U.S. Department of Energy (DOE))

The purpose of this regulation is to limit emissions of particulate matter from fossil fuel fired and wood-fired steam or hot water generating units.

479

On the Potential Use of Small Scale Fire Tests for Screening Steiner Tunnel Results for Spray Foam Insulation.  

E-Print Network (OSTI)

??The goal of this study is to assess the potential of using bench-scale fire testing to screen materials for the Steiner tunnel fire test. It (more)

Didomizio, Matthew

2013-01-01T23:59:59.000Z

480

Fire spread probabilities for experimental beds composed of mixedwood boreal forest fuels  

E-Print Network (OSTI)

that fire spread was largely determined by the heat sink, heat of combustion, and fuel bed depth. We found

Johnson, Edward A.

Note: This page contains sample records for the topic "fire alarms intercoms" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


481

A Method for Evaluating Fire After Earthquake Scenarios for Single Buildings  

Energy.gov (U.S. Department of Energy (DOE))

A Method for Evaluating Fire After Earthquake Scenarios for Single Buildings Authors: Elizabeth J. Kelly and Raymond N. Tell

482

Emergency Action Plan For incidents involving hazardous materials, fires, explosions, or natural gas  

E-Print Network (OSTI)

-492-6025. For Non-Emergency Fire and Natural Gas Questions call the CU Fire Marshall @ 303-492-4042. AdditionalEmergency Action Plan For incidents involving hazardous materials, fires, explosions, or natural gas leaks, the following actions should be taken: 1) Life Safety First 2) Evacuate Immediate Area 3

Mojzsis, Stephen J.

483

Fire History in the Cherokee Nation of Oklahoma Michael C. Stambaugh & Richard P. Guyette &  

E-Print Network (OSTI)

Fire History in the Cherokee Nation of Oklahoma Michael C. Stambaugh & Richard P. Guyette & Joseph history in northeastern Oklahoma on lands once occupied by the Cherokee Nation. A fire event chronology American groups includ- ing Cherokee was significantly correlated (r=0.84) with the number of fires per

Stambaugh, Michael C

484

3D building reconstruction and thermal mapping in fire brigade operations  

Science Journals Connector (OSTI)

Fire fighting remains a dangerous profession despite many recent technological and organizational measures. Sensors and technical systems can augment the performance of fire fighters to increase safety and efficiency during operation. An important aspect ... Keywords: augmented reality, fire fighter safety, real-time dense reconstruction, thermal camera

Christian Schnauer; Emanuel Vonach; Georg Gerstweiler; Hannes Kaufmann

2013-03-01T23:59:59.000Z

485

Presented at the International Conference on Building Fire Safety 20-21 November 2003  

E-Print Network (OSTI)

for fire engineering services to suit regulatory and particular client objectives on a wide range professionals in related disciplines such as structural engineering, building services engineering and building Campus QUT Brisbane Fire Safety Engineering ­ the Graduates' Perspective Chris Gildersleeve ­ Arup Fire

Hickman, Mark

486

The effect of monsoonal atmospheric moisture on lightning fire ignitions in southwestern North America  

E-Print Network (OSTI)

atmospheric moisture and precipitation. Using 16 years of lightning flash, relative humidity), on observed lightning fire data. The probability that a lightning flash would ignite an observed fireThe effect of monsoonal atmospheric moisture on lightning fire ignitions in southwestern North

Stephens, Scott L.

487

Dating of coal fires in Xinjiang, north-west China Xiangmin Zhang,1  

E-Print Network (OSTI)

of coal resources and mining safety, coal fires cause considerable environmental problems, such as air pollution and land degradation. Coal fires have a global impact as well; the emission of CO2 might). Active coal fires in China are usu- ally related to mining activity; how- ever, the direct cause

Utrecht, Universiteit

488

Physically-based modeling, simulation and rendering of fire for computer animation  

Science Journals Connector (OSTI)

We give an up-to-date survey on techniques and methods for fire simulation in computer graphics. Physically-based method prevails over traditional non-physical methods for realistic visual effect. In this paper, we explore visual simulation of fire-related ... Keywords: Blackbody radiation, Chemical reaction, Fire, Navier---Stokes equations, Physically-based simulation, Visual adaption

Zhanpeng Huang, Guanghong Gong, Liang Han

2014-08-01T23:59:59.000Z

489

Particle and Gas Emissions from a Simulated Coal-Burning Household Fire Pit  

Science Journals Connector (OSTI)

Particle and Gas Emissions from a Simulated Coal-Burning Household Fire Pit ... Chinese anthracite and bituminous coals produce different amounts of emissions when burned in a fire pit that simulates common rural household use of these fuels. ... Here we present emissions from burning 15 different fuels in a laboratory system designed to mimic the fire pits used in Xuan Wei County, China. ...

Linwei Tian; Donald Lucas; Susan L. Fischer; S. C. Lee; S. Katharine Hammond; Catherine P. Koshland

2008-02-21T23:59:59.000Z

490

Reducing the Wildland Fire Threat to Homes: Where and How Much?1  

E-Print Network (OSTI)

Reducing the Wildland Fire Threat to Homes: Where and How Much?1 Jack D. Cohen2 Abstract Understanding how ignitions occur is critical for effectively mitigating home fire losses during wildland fires, and local agencies that have responsibilities involving homes within and adjacent to wildlands. Agencies

Standiford, Richard B.

491

Department of Fire Protection Engineering A. JAMES CLARK SCHOOL OF ENGINEERING  

E-Print Network (OSTI)

1 Department of Fire Protection Engineering A. JAMES CLARK SCHOOL OF ENGINEERING 3000 J to Graduate Study Policies and Procedures January, 2013 1. INTRODUCTION The Department of Fire Protection organization of the graduate program. Additional information about fire protection engineering graduate program

Shapiro, Benjamin

492

Department of Fire Protection Engineering A. JAMES CLARK SCHOOL OF ENGINEERING  

E-Print Network (OSTI)

1 Department of Fire Protection Engineering A. JAMES CLARK SCHOOL OF ENGINEERING 3000 J about fire protection engineering graduate program and requirements for M.S. degrees are available on fire protection engineering by enrolling in the Ph.D. programs of other UMD departments

Shapiro, Benjamin

493

Department of Fire Protection Engineering A. JAMES CLARK SCHOOL OF ENGINEERING  

E-Print Network (OSTI)

1 Department of Fire Protection Engineering A. JAMES CLARK SCHOOL OF ENGINEERING 3000 J to Graduate Study Policies and Procedures August, 2013 1. INTRODUCTION The Department of Fire Protection organization of the graduate program. Additional information about fire protection engineering graduate program

Shapiro, Benjamin

494

Two years in the planning, the symposium on Wildland Fire 2000 was held  

E-Print Network (OSTI)

Sciences Research of the Forest Service, at the Conference on Fire Management--Challenge of Protection of the Interior; California Department of Forestry and Fire Protection; International Union of Forestry developed by Delmer L. Albright of the California Department of Forestry and Fire Protection (see his

Standiford, Richard B.

495

Productivity change of coal-fired thermal power plants in India: a Malmquist index approach  

Science Journals Connector (OSTI)

......productivity. Keywords: coal-fired power plants...infrastructure for the socio- economic development of a...Manufacturing industry, Economic and Political Weekly...Performance analysis of coal fired power plants...PRODUCTIVITY CHANGE OF COAL-FIRED THERMAL POWER...Asia Pacific Annual Economic Association (APEA......

S. K. Behera; J. A. Farooquie; A. P. Dash

2011-10-01T23:59:59.000Z

496

18 Use of Satellite Remote Sensing Data for Modeling Carbon Emissions from Fires: A Perspective in  

E-Print Network (OSTI)

18 Use of Satellite Remote Sensing Data for Modeling Carbon Emissions from Fires: A Perspective of the accurate estimation of carbon emissions from fires. So far, the continental-scale estimates of carbon conventional and satellite data to maximize their utility for fire emission estimation. 18.2 Carbon Emission

Li, Zhanqing

497

Wildland fire emissions, carbon, and climate: Science overview and knowledge needs  

E-Print Network (OSTI)

Wildland fire emissions, carbon, and climate: Science overview and knowledge needs William T: Available online 6 January 2014 Keywords: Wildland fire Climate Forests Carbon cycle Emissions a b s t r a c climate change and the principal emissions component of wildland fires, while black carbon and other

498

Refrigeration monitor and alarm system  

SciTech Connect

A monitor is described for a refrigeration system including a heat reclaiming system coupled therewith, comprising: a sensor positioned to detect the level of liquid state refrigerant in the system and provide an electrical output signal therefrom; a digital display for displaying the refrigerant level; first circuit means coupling the digital display to the sensor for actuating the digital display; and lockout means coupled with the sensor for deactivating the heat reclaiming system when a preselected refrigerant level is reached.

Branz, M.A.; Renaud, P.F.

1986-09-23T23:59:59.000Z

499

General Items o Alarm clock  

E-Print Network (OSTI)

. standardsforliving.com o Refrigerators (3.5 cubic feet or smaller) o Stereo w/Headphones o Television, VCR o Explosives/Fireworks o Extension Cords (any type) o Fog/Smoke Machines o Freezers o Furniture

Saidak, Filip

500

Rotary Firing in Ring-Shaped Protein Explains Unidirectionality  

NLE Websites -- All DOE Office Websites (Extended Search)

Rotary Firing in Ring-Shaped Rotary Firing in Ring-Shaped Protein Explains Unidirectionality Rotary Firing in Ring-Shaped Protein Explains Unidirectionality Print Wednesday, 28 April 2010 00:00 Hexameric motor proteins represent a complex class of molecular machines that variously push and pull on biological molecules using adenosine triphosphate (ATP) as chemical fuel. A specialized class of ring-shaped motor proteins, hexameric helicases, can unwind DNA strands and perform large-scale manipulations of single-stranded nucleic acids in processes such as DNA replication, DNA repair, and gene expression. To understand how certain hexameric helicases walk with directional polarity along single-stranded nucleic acids, Berkeley researchers used x-ray crystallography at the ALS to solve the structure of a hexameric helicase, the Rho transcription termination factor (from E. coli), bound to both ATP mimics and an RNA substrate. The results showed that Rho functions like a rotary engine: as the motor spins, it pulls RNA strands through its interior. Interestingly, the rotary firing order of the motor is biased so that the Rho protein can walk in only one direction along the RNA chain.