Powered by Deep Web Technologies
Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


1

Fire alarm system improvement  

SciTech Connect (OSTI)

This document contains the Fire Alarm System Test Procedure for Building 234-5Z, 200-West Area on the Hanford Reservation, Richland, Washington. This Acceptance Test Procedure (ATP) has been prepared to demonstrate that the modifications to the Fire Protection systems function as required by project criteria. The ATP will test the Fire Alarm Control Panels, Flow Alarm Pressure Switch, Heat Detectors, Smoke Detectors, Flow Switches, Manual Pull Stations, and Gong/Door by Pass Switches.

Hodge, S.G.

1994-10-01T23:59:59.000Z

2

Project 93L-EWL-097, fire alarm system improvements, 300 Area  

SciTech Connect (OSTI)

This document contains the Acceptance Test Procedure (ATP) which will demonstrate that the modifications to the Fire Protection systems in the 338 Building function as intended. The ATP will test the fire alarm control panel, flow alarm pressure switch, post indicator valve tamper switch, heat detectors, flow switches, and fire alarm signaling devices.

Scott, M.V.

1995-01-01T23:59:59.000Z

3

An evaluation of various types of fire detection alarm systems to awaken the elderly  

E-Print Network [OSTI]

to represent the hearing perception of an ei ghty year old male, were presented to ten college student participarits. These three alarm systems represented a smoke detector located in the hallway; in the bedroom and the liallway; and in the bedroom...-Sand Frequency Analyses (SPL re . 0002 microPascal) Taken 10 Feet from Source in UNass Anechoic Chaarber 18 IV An Average Eighty Year Old Nale's Hearing Perception of the Average Smoke Def~ctor Alarm Signals Neasured by Nober, Peirce and Well, at a Distance...

Townley, Timothy Edward

2012-06-07T23:59:59.000Z

4

SUBSURFACE VISUAL ALARM SYSTEM ANALYSIS  

SciTech Connect (OSTI)

The ''Subsurface Fire Hazard Analysis'' (CRWMS M&O 1998, page 61), and the document, ''Title III Evaluation Report for the Surface and Subsurface Communication System'', (CRWMS M&O 1999a, pages 21 and 23), both indicate the installed communication system is adequate to support Exploratory Studies Facility (ESF) activities with the exception of the mine phone system for emergency notification purposes. They recommend the installation of a visual alarm system to supplement the page/party phone system The purpose of this analysis is to identify data communication highway design approaches, and provide justification for the selected or recommended alternatives for the data communication of the subsurface visual alarm system. This analysis is being prepared to document a basis for the design selection of the data communication method. This analysis will briefly describe existing data or voice communication or monitoring systems within the ESF, and look at how these may be revised or adapted to support the needed data highway of the subsurface visual alarm. system. The existing PLC communication system installed in subsurface is providing data communication for alcove No.5 ventilation fans, south portal ventilation fans, bulkhead doors and generator monitoring system. It is given that the data communication of the subsurface visual alarm system will be a digital based system. It is also given that it is most feasible to take advantage of existing systems and equipment and not consider an entirely new data communication system design and installation. The scope and primary objectives of this analysis are to: (1) Briefly review and describe existing available data communication highways or systems within the ESF. (2) Examine technical characteristics of an existing system to disqualify a design alternative is paramount in minimizing the number of and depth of a system review. (3) Apply general engineering design practices or criteria such as relative cost, and degree of difficulty and complexity in determining requirements in adapting existing data communication highways to support the subsurface visual alarm system. These requirements would include such things as added or new communication cables, added Programmable Logic Controller (PLC), Inputs and Outputs (I/O), and communication hardware components, and human machine interfaces and their software operating system. (4) Select the best data communication highway system based on this review of adapting or integrating with existing data communication systems.

D.W. Markman

2001-08-06T23:59:59.000Z

5

False fire alarms have a negative impact on UW operations False (or nuisance) alarms are very disruptive to UW operations. The alarms  

E-Print Network [OSTI]

protection devices and upgrading old fire protection equipment with current technology. How construction. · Temporary impairment/removal of fire alarm devices ­ Confer with the University Fire Protection Engineer Fire Alarm Shop. · Fire watch requirements - Confer with the University Fire Protection Engineer (206

Wilcock, William

6

Substation alarm multiplexing system (SAMS)  

SciTech Connect (OSTI)

This paper describes an on going R&D project to develop, design, install, and assess the field performance of an advanced substation alarm system. SAMS provides a highly fault-tolerant system for the reporting of equipment alarms. SAMS separates and identifies each of the multiple alarm contacts, transmits an alarm condition over existing substation two-wire system, and displays the alarm source, and its associated technical information, on a touch-screen monitor inside the substation control room, and a remote central location and on a hand held terminal which may be carried anywhere within the substation. SAMS is currently installed at the Sherman Creek substation in the Bronx for the purpose of a three month field evaluation.

ElBadaly, H.; Gaughan, J.; Ward, G.; Amengual, S.

1996-03-01T23:59:59.000Z

7

Setting fires, false alarms, or vandalizing fire protection equipment is illegal. Any person found to be participating in these activities will be prosecuted to the full extent of the law and/or disciplined through the University's disciplinary procedures  

E-Print Network [OSTI]

Setting fires, false alarms, or vandalizing fire protection equipment is illegal. Any person found University fire safety equipment should contact the Campus University Police or Security. FIRES What should I do if I discover a fire? ACTIVATE THE FIRE ALARM SYSTEM by pulling one of the pull stations that re

Fernandez, Eduardo

8

Setting fires, false alarms, or vandalizing fire protection equipment is illegal. Any person found to be participating in these activities will be prosecuted to the full extent of the law and/or disciplined through the University's disciplinary procedures  

E-Print Network [OSTI]

Setting fires, false alarms, or vandalizing fire protection equipment is illegal. Any person found University fire safety equipment should contact the Campus University Police or Security. FIRES What should I do if I discover a fire? · ACTIVATE THE FIRE ALARM SYSTEM by pulling one of the nearest pull stations

Fernandez, Eduardo

9

Functional relationship-based alarm processing system  

DOE Patents [OSTI]

A functional relationship-based alarm processing system and method analyzes each alarm as it is activated and determines its relative importance with other currently activated alarms and signals in accordance with the functional relationships that the newly activated alarm has with other currently activated alarms. Once the initial level of importance of the alarm has been determined, that alarm is again evaluated if another related alarm is activated or deactivated. Thus, each alarm's importance is continuously updated as the state of the process changes during a scenario. Four hierarchical relationships are defined by this alarm filtering methodology: (1) level precursor (usually occurs when there are two alarm settings on the same parameter); (2) direct precursor (based on causal factors between two alarms); (3) required action (system response or action expected within a specified time following activation of an alarm or combination of alarms and process signals); and (4) blocking condition (alarms that are normally expected and are not considered important). The alarm processing system and method is sensitive to the dynamic nature of the process being monitored and is capable of changing the relative importance of each alarm as necessary. 12 figs.

Corsberg, D.R.

1988-04-22T23:59:59.000Z

10

The Best Ever Alarm System Toolkit  

SciTech Connect (OSTI)

Learning from our experience with the standard Experimental Physics and Industrial Control System (EPICS) alarm handler (ALH) as well as a similar intermediate approach based on script-generated operator screens, we developed the Best Ever Alarm System Toolkit (BEAST). It is based on Java and Eclipse on the Control System Studio (CSS) platform, using a relational database (RDB) to store the configuration and log actions. It employs a Java Message Service (JMS) for communication between the modular pieces of the toolkit, which include an Alarm Server to maintain the current alarm state, an arbitrary number of Alarm Client user interfaces (GUI), and tools to annunciate alarms or log alarm related actions. Web reports allow us to monitor the alarm system performance and spot deficiencies in the alarm configuration. The Alarm Client GUI not only gives the end users various ways to view alarms in tree and table, but also makes it easy to access the guidance information, the related operator displays and other CSS tools. It also allows online configuration to be simply modified from the GUI. Coupled with a good "alarm philosophy" on how to provide useful alarms, we can finally improve the configuration to achieve an effective alarm system.

Kasemir, Kay [ORNL; Chen, Xihui [ORNL; Danilova, Katia [ORNL

2009-01-01T23:59:59.000Z

11

Activate the nearest fire alarm pull station Call 911 to report the fire  

E-Print Network [OSTI]

, records and hazardous materials. o Shut off non-essential electrical equipment. o Wait for instructions, fumes or vapors: Do not pull fire alarms. Do not touch light switches or electrical equipment. Call UH. Provide your location and the location of the odor to the dispatcher. Provide as many details as possible

Azevedo, Ricardo

12

Fire Alarm Testing and Inspection Planning and Vendor Check In/Check Out Process  

E-Print Network [OSTI]

Fire Alarm Testing and Inspection Planning and Vendor Check In/Check Out Process DOCUMENT PURPOSE This process is used for fire alarm testing and inspection pre-work planning and vendor check in and check out ____________________________________________________ CHECK IN PRIOR TO TESTING NOTES _____ Central Monitoring (BSAC) notified of daily testing start time

Webb, Peter

13

E-Print Network 3.0 - automatic alarm dosimeter Sample Search...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

systems, and emergency lights. Firewatch... or to the fire alarm annunciatorcontrol panel for fire alarm systems. ... Source: Karsai, Istvan - Department of Biological...

14

Refrigeration monitor and alarm system  

SciTech Connect (OSTI)

A monitor is described for a refrigeration system including a heat reclaiming system coupled therewith, comprising: a sensor positioned to detect the level of liquid state refrigerant in the system and provide an electrical output signal therefrom; a digital display for displaying the refrigerant level; first circuit means coupling the digital display to the sensor for actuating the digital display; and lockout means coupled with the sensor for deactivating the heat reclaiming system when a preselected refrigerant level is reached.

Branz, M.A.; Renaud, P.F.

1986-09-23T23:59:59.000Z

15

STANFORD TOXIC GAS ALARM SYSTEMS 6 September 1999  

E-Print Network [OSTI]

to the Fire Alarm outputs if the TGO Alarm is activated. 11. If a bunker is separate from a building, during a bunker evacuation, only the bunker will be evacuated. G a s S h u t d o w n L a b G a s S h u t d o w n L

16

Alarm system for a nuclear control complex  

DOE Patents [OSTI]

An advanced control room complex for a nuclear power plant, including a discrete indicator and alarm system (72) which is nuclear qualified for rapid response to changes in plant parameters and a component control system (64) which together provide a discrete monitoring and control capability at a panel (14-22, 26, 28) in the control room (10). A separate data processing system (70), which need not be nuclear qualified, provides integrated and overview information to the control room and to each panel, through CRTs (84) and a large, overhead integrated process status overview board (24). The discrete indicator and alarm system (72) and the data processing system (70) receive inputs from common plant sensors and validate the sensor outputs to arrive at a representative value of the parameter for use by the operator during both normal and accident conditions, thereby avoiding the need for him to assimilate data from each sensor individually. The integrated process status board (24) is at the apex of an information hierarchy that extends through four levels and provides access at each panel to the full display hierarchy. The control room panels are preferably of a modular construction, permitting the definition of inputs and outputs, the man machine interface, and the plant specific algorithms, to proceed in parallel with the fabrication of the panels, the installation of the equipment and the generic testing thereof.

Scarola, Kenneth (Windsor, CT); Jamison, David S. (Windsor, CT); Manazir, Richard M. (North Canton, CT); Rescorl, Robert L. (Vernon, CT); Harmon, Daryl L. (Enfield, CT)

1994-01-01T23:59:59.000Z

17

Pressurized security barrier and alarm system  

DOE Patents [OSTI]

A security barrier for placement across a passageway is made up of interconnected pressurized tubing made up in a grid pattern with openings too small to allow passage. The tubing is connected to a pressure switch, located away from the barrier site, which activates an alarm upon occurrence of a pressure drop. A reinforcing bar is located inside and along the length of the tubing so as to cause the tubing to rupture and set off the alarm upon an intruder`s making an attempt to crimp and seal off a portion of the tubing by application of a hydraulic tool. Radial and rectangular grid patterns are disclosed. 7 figures.

Carver, D.W.

1995-04-11T23:59:59.000Z

18

E-Print Network 3.0 - alarm systems Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Location Fire Alarm Panel Location KnoxRetainer Box... Key Holder Office Phone Home Phone Cell ... Source: Texas A&M University, Institute for Applied Mathematics and...

19

E-Print Network 3.0 - alarm system analysis Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

(SAS) to monitor scientific equipment that is critical to ongoing... Equipment System (AES): The notebook found at various alarm panels Scientific Alarm System (SAS... ): The...

20

Technical evaluation of equipment maintenance on fire alarm detection, suppression, and signaling  

SciTech Connect (OSTI)

This document delineates the application of WHC-CM-4-3, Program E-2 to Fire Systems on the Hanford Site.

Korslund, S.M.

1994-10-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


21

Nuclear-power-plant perimeter-intrusion alarm systems  

SciTech Connect (OSTI)

Timely intercept of an intruder requires the examination of perimeter barriers and sensors in terms of reliable detection, immediate assessment and prompt response provisions. Perimeter security equipment and operations must at the same time meet the requirements of the Code of Federal Regulations, 10 CFR 73.55 with some attention to the performance and testing figures of Nuclear Regulatory Guide 5.44, Revision 2, May 1980. A baseline system is defined which recommends a general approach to implementing perimeter security elements: barriers, lighting, intrusion detection, alarm assessment. The baseline approach emphasizes cost/effectiveness achieved by detector layering and logic processing of alarm signals to produce reliable alarms and low nuisance alarm rates. A cost benefit of layering along with video assessment is reduction in operating expense. The concept of layering is also shown to minimize testing costs where detectability performance as suggested by Regulatory Guide 5.44 is to be performed. Synthesis of the perimeter intrusion alarm system and limited testing of CCTV and Video Motion Detectors (VMD), were performed at E-Systems, Greenville Division, Greenville, Texas during 1981.

Halsey, D.J.

1982-04-01T23:59:59.000Z

22

Xcel Energy implements an alarm management strategy  

SciTech Connect (OSTI)

Not so long ago, Xcel Energy's Pawnee Station, a 505 MW coal-fired generating station in Brush, Colorado, USA was commonly generating 300 to 400 alarms per 8-hour shift. The article describes how the alarm system was revised and improved by tackling alarm dead-bands, and rationalising alarms for routine events. Operators are trained to understand the functions of alarm management components, their use and response, and obtain feedback. Today the power station reports about one alarm per hour. 3 photos.

Bass, J.; Abreu, G. [Xcel Energy (United States)

2007-11-15T23:59:59.000Z

23

E-Print Network 3.0 - alarm processing system Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

the Management of Multi-Layered Networks Summary: on the definition of alarms that can enter the system. Therefore, three alarm categories are created based... with a single-layer...

24

E-Print Network 3.0 - alarm system commercial Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

the Management of Multi-Layered Networks Summary: on the definition of alarms that can enter the system. Therefore, three alarm categories are created based... with a single-layer...

25

E-Print Network 3.0 - advanced alarm systems Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

the Management of Multi-Layered Networks Summary: on the definition of alarms that can enter the system. Therefore, three alarm categories are created based... with a single-layer...

26

An analysis of firefighter personal safety alarm effectiveness on the fire ground  

Science Journals Connector (OSTI)

For firefighters in the line of duty the last line of defense and chance for rescue oftentimes relies on the effectiveness of their Personal Alert Safety System (PASS) devices. When activated a PASS device emits an alarm signal to notify others that a firefighter is in distress. However there have been notable instances where PASS devices have confused rescue personnel or created a more hazardous situation for instance when noise interference originating from other objects is involved. This research compiles data from various sources for example firefighter near miss reports and National Institute for Occupational Safety and Health (NIOSH) fatality reports regarding PASS device effectiveness. The research will investigate the causes of confusion and danger as well as take a look at the situations where the device achieved its goal and was able to save a life. The implications of discovering how interfering noises can render PASS devices ineffective could save several lives in the future and ultimately lead to increased firefighter safety.

Kyle Ford; Mudeer Habeeb; Joelle Suits; Mustafa Abbasi; Ofodike Ezekoye

2013-01-01T23:59:59.000Z

27

A hybrid intelligent system for alarm processing in power distribution substations  

Science Journals Connector (OSTI)

This application paper presents an intelligent system for alarm processing and fault location in power substations. A hybrid model is constructed using rule-based systems and an artificial neural network. Incoming alarms are initially handled by an input ... Keywords: Expert systems, fault location, neural networks

J. C. Stacchini de Souza; M. B. Do Coutto Filho; R. S. Freund

2010-04-01T23:59:59.000Z

28

Cold Vacuum Drying facility fire protection system design description (SYS 24)  

SciTech Connect (OSTI)

This document describes the Cold Vacuum Drying Facility (CVDF) fire protection system (FPS). The FPS provides fire detection, suppression, and loss limitation for the CVDF structure, personnel, and in-process spent nuclear fuel. The system provides, along with supporting interfacing systems, detection, alarm, and activation instrumentation and controls, distributive piping system, isolation valves, and materials and controls to limit combustibles and the associated fire loadings.

PITKOFF, C.C.

1999-07-06T23:59:59.000Z

29

SILENE Benchmark Critical Experiments for Criticality Accident Alarm Systems  

SciTech Connect (OSTI)

In October 2010 a series of benchmark experiments was conducted at the Commissariat a Energie Atomique et aux Energies Alternatives (CEA) Valduc SILENE [1] facility. These experiments were a joint effort between the US Department of Energy (DOE) and the French CEA. The purpose of these experiments was to create three benchmarks for the verification and validation of radiation transport codes and evaluated nuclear data used in the analysis of criticality accident alarm systems (CAASs). This presentation will discuss the geometric configuration of these experiments and the quantities that were measured and will present some preliminary comparisons between the measured data and calculations. This series consisted of three single-pulsed experiments with the SILENE reactor. During the first experiment the reactor was bare (unshielded), but during the second and third experiments it was shielded by lead and polyethylene, respectively. During each experiment several neutron activation foils and thermoluminescent dosimeters (TLDs) were placed around the reactor, and some of these detectors were themselves shielded from the reactor by high-density magnetite and barite concrete, standard concrete, and/or BoroBond. All the concrete was provided by CEA Saclay, and the BoroBond was provided by Y-12 National Security Complex. Figure 1 is a picture of the SILENE reactor cell configured for pulse 1. Also included in these experiments were measurements of the neutron and photon spectra with two BICRON BC-501A liquid scintillators. These two detectors were provided and operated by CEA Valduc. They were set up just outside the SILENE reactor cell with additional lead shielding to prevent the detectors from being saturated. The final detectors involved in the experiments were two different types of CAAS detectors. The Babcock International Group provided three CIDAS CAAS detectors, which measured photon dose and dose rate with a Geiger-Mueller tube. CIDAS detectors are currently in use at Y-12 in the newly constructed Highly Enriched Uranium Materials Facility. The second CAAS detector used a {sup 6}LiF TLD to absorb neutrons and a silicon detector to count the charge particles released by these absorption events. Lawrence Livermore National Laboratory provided four of these detectors, which had formerly been used at the Rocky Flats facility in the United States.

Miller, Thomas Martin [ORNL] [ORNL; Reynolds, Kevin H. [Y-12 National Security Complex] [Y-12 National Security Complex

2011-01-01T23:59:59.000Z

30

Cold Vacuum Dryer (CVD) Facility Fire Protection System Design Description (SYS 24)  

SciTech Connect (OSTI)

This system design description (SDD) addresses the Cold Vacuum Drying (CVD) Facility fire protection system (FPS). The primary features of the FPS for the CVD are a fire alarm and detection system, automatic sprinklers, and fire hydrants. The FPS also includes fire extinguishers located throughout the facility and fire hydrants to assist in manual firefighting efforts. In addition, a fire barrier separates the operations support (administrative) area from the process bays and process bay support areas. Administrative controls to limit combustible materials have been established and are a part of the overall fire protection program. The FPS is augmented by assistance from the Hanford Fire Department (HED) and by interface systems including service water, electrical power, drains, instrumentation and controls. This SDD, when used in conjunction with the other elements of the definitive design package, provides a complete picture of the FPS for the CVD Facility.

SINGH, G.

2000-10-17T23:59:59.000Z

31

Fire Simulation, Evacuation Analysis and Proposal of Fire Protection Systems Inside an Underground Cavern  

E-Print Network [OSTI]

Fire Simulation, Evacuation Analysis and Proposal of Fire Protection Systems Inside an Underground Cavern

Stella, Carlo

32

Incipient fire detection system  

DOE Patents [OSTI]

A method and apparatus for an incipient fire detection system that receives gaseous samples and measures the light absorption spectrum of the mixture of gases evolving from heated combustibles includes a detector for receiving gaseous samples and subjecting the samples to spectroscopy and determining wavelengths of absorption of the gaseous samples. The wavelengths of absorption of the gaseous samples are compared to predetermined absorption wavelengths. A warning signal is generated whenever the wavelengths of absorption of the gaseous samples correspond to the predetermined absorption wavelengths. The method includes receiving gaseous samples, subjecting the samples to light spectroscopy, determining wavelengths of absorption of the gaseous samples, comparing the wavelengths of absorption of the gaseous samples to predetermined absorption wavelengths and generating a warning signal whenever the wavelengths of absorption of the gaseous samples correspond to the predetermined absorption wavelengths. In an alternate embodiment, the apparatus includes a series of channels fluidically connected to a plurality of remote locations. A pump is connected to the channels for drawing gaseous samples into the channels. A detector is connected to the channels for receiving the drawn gaseous samples and subjecting the samples to spectroscopy. The wavelengths of absorption are determined and compared to predetermined absorption wavelengths is provided. A warning signal is generated whenever the wavelengths correspond.

Brooks, Jr., William K. (Newport News, VA)

1999-01-01T23:59:59.000Z

33

Fire Classifications Fires involving the ordinary  

E-Print Network [OSTI]

, plastics, etc. Fires involving combustible or flammable liquids such as gasoline, kerosene, oils, grease is protected by various devices such as smoke detectors, sprinkler systems, and manual fire alarm pull stations. Manual pull stations are strategically located throughout the University. Usually located by each exit

Jia, Songtao

34

Fire Protection Systems Program Program Manual  

E-Print Network [OSTI]

Fire Protection Systems Program Program Manual Approved by: (name) Last revised by: (name) Revision/FPS_Program_Manual_Template.docx 1. Introduction The Fire Protection Systems Program is designed to make sure the annual compliance ................................................................................................................. 3 7.1.1 Job Plan: Fire Pump Testing

Pawlowski, Wojtek

35

Aging assessment for active fire protection systems  

SciTech Connect (OSTI)

This study assessed the impact of aging on the performance and reliability of active fire protection systems including both fixed fire suppression and fixed fire detection systems. The experience base shows that most nuclear power plants have an aggressive maintenance and testing program and are finding degraded fire protection system components before a failure occurs. Also, from the data reviewed it is clear that the risk impact of fire protection system aging is low. However, it is assumed that a more aggressive maintenance and testing program involving preventive diagnostics may reduce the risk impact even further.

Ross, S.B. [Science and Engineering Associates, Inc. (United States); Nowlen, S.P.; Tanaka, T. [Sandia National Labs., Albuquerque, NM (United States)

1995-06-01T23:59:59.000Z

36

Door Placard for No Automatic Fire Alarm with Automatic Fire Sprinkler Protection System  

E-Print Network [OSTI]

apartment with wet towels or sheets, and seal air ducts or other openings where smoke may enter Open address, floor, apartment number and the number of people in your apartment Seal the doors to your

Pawlowski, Wojtek

37

Door Placard for Fire Alarm and No Sprinkler System Fire Code Compliance  

E-Print Network [OSTI]

apartment with wet towels or sheets, and seal air ducts or other openings where smoke may enter Open address, floor, apartment number and the number of people in your apartment Seal the doors to your

Pawlowski, Wojtek

38

LNG fire and vapor control system technologies  

SciTech Connect (OSTI)

This report provides a review of fire and vapor control practices used in the liquefied natural gas (LNG) industry. Specific objectives of this effort were to summarize the state-of-the-art of LNG fire and vapor control; define representative LNG facilities and their associated fire and vapor control systems; and develop an approach for a quantitative effectiveness evaluation of LNG fire and vapor control systems. In this report a brief summary of LNG physical properties is given. This is followed by a discussion of basic fire and vapor control design philosophy and detailed reviews of fire and vapor control practices. The operating characteristics and typical applications and application limitations of leak detectors, fire detectors, dikes, coatings, closed circuit television, communication systems, dry chemicals, water, high expansion foam, carbon dioxide and halogenated hydrocarbons are described. Summary descriptions of a representative LNG peakshaving facility and import terminal are included in this report together with typical fire and vapor control systems and their locations in these types of facilities. This state-of-the-art review identifies large differences in the application of fire and vapor control systems throughout the LNG industry.

Konzek, G.J.; Yasutake, K.M.; Franklin, A.L.

1982-06-01T23:59:59.000Z

39

E-Print Network 3.0 - alarm system verification Sample Search...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

City Collection: Mathematics 11 Sensitivity Analysis of the JPALS Shipboard Relative GPS Measurement Summary: unnecessarily, increasing the false alarm rate and adversely...

40

FireWxNet: a multi-tiered portable wireless system for monitoring weather conditions in wildland fire environments  

Science Journals Connector (OSTI)

In this paper we present FireWxNet, a multi-tiered portable wireless system for monitoring weather conditions in rugged wildland fire environments. FireWxNet provides the fire fighting community the ability to safely and easily measure and view fire ... Keywords: applications, deployments, fire, forest fires, wireless sensor networks

Carl Hartung; Richard Han; Carl Seielstad; Saxon Holbrook

2006-06-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


41

H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2010.doc Annual Fire Safety Report  

E-Print Network [OSTI]

. Building Sprinkler System? % Sprinkler Monitored Fire Alarm? Smoke Detection Extinguisher Devices Placards of vehicle parts, fuel and oil is prohibited. l. Hallways must remain clear at all times for safety in case Safety Systems The following table describes each on-campus residential facility fire safety system

Sze, Lawrence

42

WASTE HANDLING BUILDING FIRE PROTECTION SYSTEM DESCRIPTION DOCUMENT  

SciTech Connect (OSTI)

The Waste Handling Building Fire Protection System provides the capability to detect, control, and extinguish fires and/or mitigate explosions throughout the Waste Handling Building (WHB). Fire protection includes appropriate water-based and non-water-based suppression, as appropriate, and includes the distribution and delivery systems for the fire suppression agents. The Waste Handling Building Fire Protection System includes fire or explosion detection panel(s) controlling various detectors, system actuation, annunciators, equipment controls, and signal outputs. The system interfaces with the Waste Handling Building System for mounting of fire protection equipment and components, location of fire suppression equipment, suppression agent runoff, and locating fire rated barriers. The system interfaces with the Waste Handling Building System for adequate drainage and removal capabilities of liquid runoff resulting from fire protection discharges. The system interfaces with the Waste Handling Building Electrical Distribution System for power to operate, and with the Site Fire Protection System for fire protection water supply to automatic sprinklers, standpipes, and hose stations. The system interfaces with the Site Fire Protection System for fire signal transmission outside the WHB as needed to respond to a fire emergency, and with the Waste Handling Building Ventilation System to detect smoke and fire in specific areas, to protect building high-efficiency particulate air (HEPA) filters, and to control portions of the Waste Handling Building Ventilation System for smoke management and manual override capability. The system interfaces with the Monitored Geologic Repository (MGR) Operations Monitoring and Control System for annunciation, and condition status.

J. D. Bigbee

2000-06-21T23:59:59.000Z

43

P\\procedure\\EH&S#2 Page 1 of 3 TITLE: BOCA RATON CAMPUS FIRE ALARM POLICY ACCESS AND RESPONSE  

E-Print Network [OSTI]

only authorized personnel have access to the systems. Provide training and guidelines about and repairs. UNIVERSITY POLICE Operate and maintain the Proprietary Monitoring Station. Assign trained of University operations. Objectives include: A well-designed service program with optimum productivity

Fernandez, Eduardo

44

Steam Plant Replaces Outdated Coal-Fired System | Department...  

Office of Environmental Management (EM)

Steam Plant Replaces Outdated Coal-Fired System September 1, 2012 - 12:00pm Addthis A new natural gas-fired steam plant will replace an older coal-fired steam plant shown here. The...

45

MODELING VENTILATION SYSTEM RESPONSE TO FIRE  

SciTech Connect (OSTI)

Fires in facilities containing nuclear material have the potential to transport radioactive contamination throughout buildings and may lead to widespread downwind dispersal threatening both worker and public safety. Development and implementation of control strategies capable of providing adequate protection from fire requires realistic characterization of ventilation system response which, in turn, depends on an understanding of fire development timing and suppression system response. This paper discusses work in which published HEPA filter data was combined with CFAST fire modeling predictions to evaluate protective control strategies for a hypothetical DOE non-reactor nuclear facility. The purpose of this effort was to evaluate when safety significant active ventilation coupled with safety class passive ventilation might be a viable control strategy.

Coutts, D

2007-04-17T23:59:59.000Z

46

Justification to remove 333 Building fire suppression system  

SciTech Connect (OSTI)

Justification to remove the 333 Building fire suppression system is provided. The Maximum Possible Fire Loss (MPFL) is provided (approximately $800K), potential radiological and toxicological impacts from a postulated fire are discussed, Life Safety Code issues are addressed, and coordination with the Hanford Fire Department is assured.

Benecke, M.W.

1995-12-04T23:59:59.000Z

47

2009 Berea College Residence Hall Fire Protection Systems, Notification Systems and Fire Drill Data Berea College Fire Alarm Partial 1 Full 2 Smoke Fire Evacuations Evacuation  

E-Print Network [OSTI]

Lights Doors Anna Smith Yes Yes Yes Yes Yes 3 Yes Yes Bingham** Yes Yes *Yes* Yes Yes 2 Yes Yes Blue Yes 2 Yes Yes Edwards Yes Yes Yes Yes Yes 4 Yes No Estill Street No No Yes Yes Yes 1 Yes No Elizabeth

Baltisberger, Jay H.

48

The design of an intrusion security system using digital processing for alarm indication  

E-Print Network [OSTI]

has been noise spikes in the diode. These spikes can easily cause a false alarm which is difficult to trace since it results from a sporadic, elec- tronic malfunction. General Electric, Amperex, and other concerned companies have made a great... is the requirement of multiple triggering of this one threshold. AMF Inc. , Alexandria, Virginia, has recently introduced an intricate signal processor with diode transistor logic and transistor transistor logic integrated circuits to handle intru- sion signals...

Holyoak, Joel Nelson

2012-06-07T23:59:59.000Z

49

A Spatial Planning and Analysis System for Wildland Fire Management  

E-Print Network [OSTI]

STARFIRE 11/29/2011 A Spatial Planning and Analysis System for Wildland Fire Management Welcome is an advanced and powerful spatial fire management planning and analysis system which is designed to provide visual and analytic support for fire management planning, decisions and communication. The system

50

Design of the Wireless Temperature Measurement Alarming System in the High-Voltage Transformer Substation  

Science Journals Connector (OSTI)

Due to electric power overload and equipment aging, fire and explosion occur at transmission circuitry joints in high-voltage transformer substation caused by high temperatures accumulated at these...

Qiang Gao; Hongli Wang; Huaxiang Wang

2008-01-01T23:59:59.000Z

51

Understanding Corrosion Mechanisms in Oxy-Fired Systems  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Understanding Corrosion Mechanisms Understanding Corrosion Mechanisms in Oxy-Fired Systems Background In Oxy-fired Systems, oxygen is used for combustion of coal rather than air. It produces flue (exhaust) gas with concentrated carbon dioxide (CO2), thus facilitating its capture and sequestration. An added benefit of oxy-firing is that it reduces or eliminates nitrogen oxide (NO X ) emissions. Additional energy is required with oxy-firing and subsequent carbon sequestration

52

Door Placard for No Automatic Fire Alarm and No Sprinkler System  

E-Print Network [OSTI]

apartment with wet towels or sheets, and seal air ducts or other openings where smoke may enter Open address, floor, apartment number and the number of people in your apartment Seal the doors to your

Pawlowski, Wojtek

53

Reduction of fire hazards on large mining equipment  

SciTech Connect (OSTI)

Although standards and regulations are in place to prevent large mining equipment fires, recent analyses of mine accident data show that mining equipment fires still occur with alarming frequency and grave consequences, particularly at all surface mines and in underground metal/nonmetal mines. Recently technological advances in fire protection, combined with the statistical data on equipment fires, led NIOSH to reinvestigate this and to improve operator safety. NIOSH demonstrated that newly developed technologies, such as dual cab fire inerting systems and engine compartment fire barriers, can greatly enhance operator safety and lessen the damage of property during large mobile equipment fires. 10 refs., 5 figs.

Maria I. De Rosa

2008-09-15T23:59:59.000Z

54

LNG facilities Engineered fire protection systems  

Science Journals Connector (OSTI)

Dry chemical fire extinguishers used in conjunction with high expansion foam have been used successfully in tests to extinguish LNG spill fires.

Kenneth Zuber

1976-02-01T23:59:59.000Z

55

Gas fired Advanced Turbine System  

SciTech Connect (OSTI)

The primary objective of the first phase of the Advanced Gas Turbine System (ATS) program was the concept definition of an advanced engine system that meets efficiency and emission goals far exceeding those that can be provided with today`s equipment. The thermal efficiency goal for such an advanced industrial engine was set at 50% some 15 percentage points higher than current equipment levels. Exhaust emissions goals for oxides of nitrogen (NO{sub x}), carbon monoxide (CO), and unburned hydrocarbons (UH) were fixed at 8 parts per million by volume (ppmv), 20 ppmv, and 20 ppmv respectively, corrected to 15% oxygen (O{sub 2}) levels. Other goals had to be addressed; these involved reducing the cost of power produced by 10 percent and improving or maintaining the reliability, availability, and maintainability (RAM) at current levels. This advanced gas turbine was to be fueled with natural gas, and it had to embody features that would allow it bum coal or coal derived fuels.

LeCren, R.T.; White, D.J.

1993-01-01T23:59:59.000Z

56

Install Waste Heat Recovery Systems for Fuel-Fired Furnaces  

Broader source: Energy.gov [DOE]

This tip sheet recommends installing waste heat recovery systems for fuel-fired furnaces to increase the energy efficiency of process heating systems.

57

Assessment of the Plutonium Finishing Plant Criticality Alarm System U.S. Department of Energy Richland Operations Office  

SciTech Connect (OSTI)

At the request of the Assistant Manager for Safety and Engineering, the U.S. Department of Energy Richland Operations Office (RL) Engineering Support Division, performed an oversight review of the Plutonium Finishing Plant (PFP) nuclear Criticality Alarm System (CAS). The review was conducted to satisfy requirements and agreements associated with Defense Nuclear Facility Safety Board (DNFSB) Recommendation 2000-2, ''Vital Safety Systems.'' The PFP is managed by Fluor Hanford, Inc. for RL. The field assessment and staff interviews were conducted August 12 through August 19,2002. This was a limited scope assessment that consisted of a review of the nuclear CAS operations, maintenance, and compliance with National Consensus Standards Requirements. The main purpose of the assessment was to determine the adequacy of the existing alarm system and its associated infrastructure to support the PFP facility mission through the remaining facility lifetime. The Review Plan was modeled upon Criteria and Review Approach Documents (CRAD) developed for DNFSB Recommendation 2000-2 reviews conducted across the Hanford Site. Concerns regarding component degradation and failure, increasing numbers of occurrence reports associated with the alarm system, and reliability issues were addressed. Additionally, RL performed a review of the engineering aspects of the CAS including the functions of design authorities and aspects of systems engineering. However, the focus of the assessment was on operations, maintenance, and reliability of the CAS, associated procurement practices, adequacy of safety and engineering policies and procedures, safety documentation, and fundamental engineering practices including training, qualification, and systems engineering. This assessment revealed that the PFP CAS and its associated infrastructure, administrative procedures, and conduct of operations are generally effective. There are no imminent criticality safety issues associated with the operation of the existing CAS. The Assessment Team believes that the CAS, as it presently exists at the PFP facility, is adequate to support the remaining mission lifetime of the facility while continuing to ensure personnel safety. This conclusion is dependent upon a continued level of funding adequate to support the required maintenance and occasional system upgrade. Two findings were identified during this assessment. Additionally, the report identified eight observations and two recommendations. The assessment revealed that recent changes to OSR compliance procedures and other documents do not contain the signature of the CSR as required by procedure. Lack of appropriate approval signatures is a noncompliance with site-level procedures.

NIRIDER, L.T.

2002-10-01T23:59:59.000Z

58

Alarm acknowledgement in a nuclear plant control room  

DOE Patents [OSTI]

Alarm acknowledgment can be made not only at the alarm tile array of a given console but via other touch sensitive alarm indications in the screen displays of the monitoring system at the same or other consoles; also, touching one tile can acknowledge multiple alarm sources.

Scarola, Kenneth (Windsor, CT); Jamison, David S. (Windsor, CT); Manazir, Richard M. (North Canton, CT); Rescorl, Robert L. (Vernon, CT); Harmon, Daryl L. (Enfield, CT)

1994-01-01T23:59:59.000Z

59

Fire Protection System Account Request Form | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection System Account Request Form Fire Protection System Account Request Form Fire Protection System Account Request Form December 2, 2010 Account request form used to obtain user credentials for the Fire Protection Database To obtain a user id and password to access the Fire Protection system, please complete the form, save the file and email it to HSSUserSupport@hq.doe.gov or print and fax it to 301-903-9823. We will provide a username and password to new account holders. Please allow several business days to process your account request. When your request is approved, you will be contacted with your account information. Fire Protection System Account Request Form More Documents & Publications CAIRS Registration Form Microsoft Word - PARS II User Acct Access Guide.rtf PARS Domain User Maintenance Function Support Team Guide (v

60

Geothermal system saving money at fire station | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Geothermal system saving money at fire station Geothermal system saving money at fire station Geothermal system saving money at fire station April 9, 2010 - 3:45pm Addthis Joshua DeLung What will the project do? A geothermal heating and cooling system has enabled the substation to save taxpayers $15,000 annually when compared to a traditional system. The high temperature of the treatment building's water helps reduce the amount of energy needed to heat water in the substation. An environmentally friendly geothermal heating and cooling system in Pennsylvania will save taxpayers $15,000 a year as part of a new fire substation that will decrease emergency response times. The Alpha Fire Co. celebrated the opening of substation on the ground floor of the College Township municipal building earlier this year in State

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


61

Using Satellite Fire Detection to Calibrate Components of the Fire Weather Index System in Malaysia and Indonesia  

Science Journals Connector (OSTI)

Vegetation fires have become an increasing problem in tropical environments as a consequence of socioeconomic pressures and subsequent land-use change. In response, fire management systems are being developed. Th...

Caren C. Dymond; Robert D. Field; Orbita Roswintiarti; Guswanto

2005-04-01T23:59:59.000Z

62

Intelligent Economic Alarm Processor (IEAP)  

E-Print Network [OSTI]

): ?The 21st Substation Design?, and ??Verifying Interoperability and Application Performance of PMUs and PMU-enabled IEDs at the Device and System Level?. The fourth one is funded by Advanced Research Agency- Energy (ARPA-E) through Green Electricity... .......................................................................................................... 52? 4. USE OF SUBSTATION IED DATA TO IMPROVE ALARM PROCESSING ........ 53? 4.1? Introduction ...................................................................................................... 53? 4.2? Substation IED Data...

Guan, Yufan

2013-08-06T23:59:59.000Z

63

A Natural-Gas-Fired Thermoelectric Power Generation System  

Science Journals Connector (OSTI)

This paper presents a combustion-driven thermoelectric power generation system that uses PbSnTe-based thermoelectric modules. The modules were integrated into a gas-fired furnace with a special burner design. The...

K. Qiu; A.C.S. Hayden

2009-07-01T23:59:59.000Z

64

Improve the design of fire emergency relief systems  

SciTech Connect (OSTI)

In recognition of the potential severe consequences of a process vessel rupture under fire exposure, industry codes such as the National Fire Protection Association (NFPA) 30 and the American Petroleum Institute (API) Standard 2000 have been established for the specification of emergency relief systems (ERSs). The intent is to reduce the risk of human injury and asset losses associated with process plant fires. These codes are largely prescriptive in nature. That is, they provide specific details on how to achieve safe design. Prescriptive standards are easy to apply, because they are simplified approaches which generally apply to many (but not all) situations. But they also have limitations, including the tendency to result in, at best, suboptimal (overly conservative) designs, and in some instances potentially unsafe designs. As the fire community moves toward performance-based standards for building protection, perhaps it is time to consider a similar approach for vessel protection in a fire. The design issues addressed in this article include: Use of heat input based on actual fuel burning rate, heat of combustion, and flame emissive power, vs. NFPA 30 and API 2000 heat-input equations; Effect of drainage (from vessel to sump) on fire duration, rather than heat input; Use of risk assessment to determine the relative frequency of fire and process-induced incidents; and design for containment, rather than vessel protection when fire probability is low

Stickles, R.P.; Melhem, G.A.; Eckhardt, D.R.

1995-11-01T23:59:59.000Z

65

Fire  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Fire Fire Nature Bulletin No. 51 Febraury 1, 1946 Forest Preserve District of Cook County Clayton F. Smith, President Roberts Mann, Superintendent of Conservation FIRE Most people firmly believe the ancient notion that the prairies and vacant lots should be burnt off "to make better grass." Many are doing so now. Boys who have seen their parents and neighbors kindling fires on vacant property frequently do likewise on the prairies. Recently there have been four fires in the forest preserves which spread from adjoining land. Burning does more harm than good. True, it gets rid of the old weed stalks and dried grass of last year, so that new grass shows green more quickly. But repeated burnings kill the good, nutritious grasses such as bluegrass, timothy and clover. The wildflowers disappear. All food and nesting cover for birds, rabbits and other wildlife is destroyed, just when they need it most. Thistles thrive. Only tough grasses of little value for pasture or hay, such as crabgrass and quackgrass, and the weeds survive.

66

856 IEEE TRANSACTIONS ON SYSTEMS, MAN, AND CYBERNETICS--PART C: APPLICATIONS AND REVIEWS, VOL. 38, NO. 6, NOVEMBER 2008 Designing Effective Alarms for Radiation Detection  

E-Print Network [OSTI]

to the occurrence of nuisance alarms based on naturally occurring radioactive material and the low base rate of nu Naturally occurring radioactive material. p(false alarm) Probability of a false alarm. p(hit) Probability, NO. 6, NOVEMBER 2008 Designing Effective Alarms for Radiation Detection in Homeland Security

Parasuraman, Raja

67

Review of the Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System, October 2012  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Department of Energy Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System August 2012 October 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy Table of Contents 1.0 Purpose................................................................................................................................................... 1 2.0 Assessment Background ........................................................................................................................ 1 3.0 Scope...................................................................................................................................................... 2

68

Review of the Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System, October 2012  

Broader source: Energy.gov (indexed) [DOE]

Department of Energy Department of Energy Office of Science Assessment of the Pacific Northwest National Laboratory Radiochemical Processing Laboratory Criticality Alarm System August 2012 October 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy Table of Contents 1.0 Purpose................................................................................................................................................... 1 2.0 Assessment Background ........................................................................................................................ 1 3.0 Scope...................................................................................................................................................... 2

69

FIRE WATCH FORM University Fire Marshal  

E-Print Network [OSTI]

the Fire Code of New York State that pertain to the impairment of a fire protection system to the impairment of a fire protection system Fire Code of New York State Chapter-9 "Fire Protection Systems" 901.7 Systems out of service. Where a required fire protection system is out of service, the fire department

Pawlowski, Wojtek

70

Independent Oversight Review of the Fire Protection Program and Fire Protection Systems at the Transuranic Waste Processing Center, December 2013  

Broader source: Energy.gov (indexed) [DOE]

and Fire Protection Systems and Fire Protection Systems at the Transuranic Waste Processing Center December 2013 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U. S. Department of Energy Table of Contents 1.0 Purpose.................................................................................................................................................... 1 2.0 Background ............................................................................................................................................. 1 3.0 Scope....................................................................................................................................................... 2 4.0 Methodology .......................................................................................................................................... 2

71

HOME INSECURITY: NO ALARMS, FALSE ALARMS, AND SIGINT  

SciTech Connect (OSTI)

The market share of home security systems has substantially increased as vendors incorporate more desirable features: intrusion detection, automation, wireless, and LCD touch panel controls. Wireless connectivity allows vendors to manufacture cheaper, more featureful products that require little to no home modification to install. Consumer win, since adding devices is easier. The result: an ostensibly more secure, convenient, and connected home for a larger number of citizens. Sadly, this hypothesis is flawed; the idea of covering a home with more security sensors does not translate into a more secure home. Additionally, the number of homes using these vulnerable systems is large, and the growth rate is increasing producing a even larger problem. In this talk, I will demonstrate a generalized approach for compromising three systems: ADT, the largest home security dealer in North America; Honeywell, one of the largest manufacturers of security devices; and Vivint, a top 5 security dealer. We will suppress alarms, create false alarms, and collect artifacts that facilitate tracking the movements of individuals in their homes.

Lamb, Logan M [ORNL

2014-01-01T23:59:59.000Z

72

Using active database techniques for an advanced alarm processing  

SciTech Connect (OSTI)

An Advanced Alarm System (AAS) is primarily a digital system employing advanced alarm process logics and a VDU (Visual Display Unit) based control and display for the alarms. Active Database Systems (ADSs) are able to monitor a special situation represented by an event and one or more conditions. When the event occurs and the conditions are evaluated as true, the corresponding actions are executed. Hence, ADSs can recognize specific situations and react to them without direct explicit user or application requests. ADSs are very useful for timely applications such as the advanced, alarm processing. This paper proposes a new approach to the advanced alarm processing by using Event-Condition- Action(ECA) rules that can be automatically triggered by an active database. And this paper describes the design considerations and solution plan for advanced alarm processing by using active database techniques. (authors)

Jang, G. S. [I and C HFE Dept., Korea Atomic Energy Research Inst., 150, Duckjin-dong, Yusung-ku, Daejeon 305-353 (Korea, Republic of); Seong, D. H. [Samchang Enterprise Co., LTD, 974-1, Goyean-ri, Ulju-gun, Ulsan, 689-871 (Korea, Republic of); Keum, J. Y.; Park, H. Y. [I and C HFE Dept., Korea Atomic Energy Research Inst., 150, Duckjin-dong, Yusung-ku, Daejeon 305-353 (Korea, Republic of); Kim, Y. K. [Dept. of Computer Science, Chungnam National Univ., Daejeon, 305-764 (Korea, Republic of)

2006-07-01T23:59:59.000Z

73

Fire tests on defective tank-car thermal protection systems  

Science Journals Connector (OSTI)

Many railway tank-cars carrying hazardous materials are thermally protected from fire impingement by thermal insulation and a steel jacket applied to the outside of the tank-car shell. Over time, it is possible that the thermal insulation will sag, rip, degrade, or be crushed under the steel jacket. A thermographic technique to determine whether or not a tank has insulation deficiencies has been developed, but it is necessary to determine which thermal deficiencies do not affect a tanks survivability in a fire and which thermal deficiencies must be repaired. In order to develop a guideline in assessing thermal defects, a thermal model and experimental data would be beneficial. A series of fire tests were performed on a quarter-section tank-car mock-up to assist in developing a guideline and to provide validation data for a thermal model. Twelve fire tests, with constant, credible, simulated pool fire conditions, were performed on the tank-car mock-up with various insulation deficiencies. An infrared thermal imaging camera was used to measure the tank wall temperature. The thermal images were useful in determining the temperature profiles across the defects at different times and the transient temperature behaviour at different locations. It was seen that the properly installed thermal protection system significantly reduced the heat transfer from the fire to the tank wall. It was also seen that the steel jacket alone (i.e. 100% defect) acted as a radiation shield and provided a significant level of protection. With small defects, it was observed that the surrounding protected material provided a cooling effect by thermal conduction. A square defect greater than about 40 cm on each side should be considered significant, because unlike smaller defects, there is little benefit from the surrounding material as far as the peak defect temperature is concerned.

J.D.J VanderSteen; A.M Birk

2003-01-01T23:59:59.000Z

74

Slag processing system for direct coal-fired gas turbines  

DOE Patents [OSTI]

Direct coal-fired gas turbine systems and methods for their operation are provided by this invention. The systems include a primary combustion compartment coupled to an impact separator for removing molten slag from hot combustion gases. Quenching means are provided for solidifying the molten slag removed by the impact separator, and processing means are provided forming a slurry from the solidified slag for facilitating removal of the solidified slag from the system. The released hot combustion gases, substantially free of molten slag, are then ducted to a lean combustion compartment and then to an expander section of a gas turbine.

Pillsbury, Paul W. (Winter Springs, FL)

1990-01-01T23:59:59.000Z

75

HSL Fire Evacuation Plan HSL Appendix 1  

E-Print Network [OSTI]

to the assembly point ( in the car park opposite the side entrance of the library). All tag holders need to give should 7. Staff should remain at the Assembly point (by the wooden fence in the car park opposite/alarm, staff should report any shortcomings in the fire safety provision (e.g. defective fire alarm sounders

Anderson, Jim

76

Preliminary fire hazards analysis for W-211, Initial Tank Retrieval Systems  

SciTech Connect (OSTI)

A fire hazards analysis (FHA) was performed for Project W-211, Initial Tank Retrieval System (ITRS), at the Department of Energy (DOE) Hanford site. The objectives of this FHA was to determine (1) the fire hazards that expose the Initial Tank Retrieval System or are inherent in the process, (2) the adequacy of the fire-safety features planned, and (3) the degree of compliance of the project with specific fire safety provisions in DOE orders and related engineering codes and standards. The scope included the construction, the process hazards, building fire protection, and site wide fire protection. The results are presented in terms of the fire hazards present, the potential extent of fire damage, and the impact on employees and public safety. This study evaluated the ITRS with respect to its use at Tank 241-SY-101 only.

Huckfeldt, R.A.

1995-03-16T23:59:59.000Z

77

A Web-Oriented Geoinformation System Application for Forest Fire Danger Prediction in Typical Forests of the Ukraine  

Science Journals Connector (OSTI)

A web-oriented geoinformation system for forest fire danger prediction based on a probabilistic fire danger criteria is described in this chapter. A new method for determining the probabilistic fire danger cri...

Nikolay Baranovskiy; Marina Zharikova

2014-01-01T23:59:59.000Z

78

Technical assessment of an oil-fired residential cogeneration system  

SciTech Connect (OSTI)

The definition of cogeneration, within the context of this project, is the simultaneous production of electricity and heat energy from a single machine. This report will present the results of an engineering analysis of the efficiency and energy-conservation potential associated with a unique residential oil-fired cogeneration system that provides both heat and electric power. The system operates whenever a thermostat signals a call for heat in the home, just as a conventional heating system. However, this system has the added benefit of cogenerating electricity whenever it is running to provide space heating comfort. The system is designed to burn No. 2 heating oil, which is consumed in an 11-horsepower, two cylinder, 56.75-cubic-inch, 1850-RPM diesel engine. This unit is the only pre-production prototype residential No. 2 oil-fired cogeneration system known to exist in the world. As such, it is considered a landmark development in the field of oil-heat technology.

McDonald, R.J.

1993-01-01T23:59:59.000Z

79

Coal-fired high performance power generating system. Final report  

SciTech Connect (OSTI)

As a result of the investigations carried out during Phase 1 of the Engineering Development of Coal-Fired High-Performance Power Generation Systems (Combustion 2000), the UTRC-led Combustion 2000 Team is recommending the development of an advanced high performance power generation system (HIPPS) whose high efficiency and minimal pollutant emissions will enable the US to use its abundant coal resources to satisfy current and future demand for electric power. The high efficiency of the power plant, which is the key to minimizing the environmental impact of coal, can only be achieved using a modern gas turbine system. Minimization of emissions can be achieved by combustor design, and advanced air pollution control devices. The commercial plant design described herein is a combined cycle using either a frame-type gas turbine or an intercooled aeroderivative with clean air as the working fluid. The air is heated by a coal-fired high temperature advanced furnace (HITAF). The best performance from the cycle is achieved by using a modern aeroderivative gas turbine, such as the intercooled FT4000. A simplified schematic is shown. In the UTRC HIPPS, the conversion efficiency for the heavy frame gas turbine version will be 47.4% (HHV) compared to the approximately 35% that is achieved in conventional coal-fired plants. This cycle is based on a gas turbine operating at turbine inlet temperatures approaching 2,500 F. Using an aeroderivative type gas turbine, efficiencies of over 49% could be realized in advanced cycle configuration (Humid Air Turbine, or HAT). Performance of these power plants is given in a table.

NONE

1995-08-31T23:59:59.000Z

80

Slag processing system for direct coal-fired gas turbines  

DOE Patents [OSTI]

Direct coal-fired gas turbine systems and methods for their operation are provided by this invention. The gas turbine system includes a primary zone for burning coal in the presence of compressed air to produce hot combustion gases and debris, such as molten slag. The turbine system further includes a secondary combustion zone for the lean combustion of the hot combustion gases. The operation of the system is improved by the addition of a cyclone separator for removing debris from the hot combustion gases. The cyclone separator is disposed between the primary and secondary combustion zones and is in pressurized communication with these zones. In a novel aspect of the invention, the cyclone separator includes an integrally disposed impact separator for at least separating a portion of the molten slag from the hot combustion gases.

Pillsbury, Paul W. (Winter Springs, FL)

1990-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


81

Management of Imported Fire Ants in Cattle Production Systems  

E-Print Network [OSTI]

This publication can help ranch managers develop integrated pest management plans for managing fire ant problems in cattle operations. It covers the specifics of managing fire ants in hay pastures and rangelands, around farm ponds, and near...

Fuchs, Thomas W.; Drees, Bastiaan M.

2004-03-31T23:59:59.000Z

82

Annual Fire Report Page 1 of 4 Residence Hall/Historic Houses Fire Protection Equipment  

E-Print Network [OSTI]

Annual Fire Report Page 1 of 4 Residence Hall/Historic Houses Fire Protection Equipment 2012 Residence Hall/Historic Houses Fire Protection Equipment 2012 Calendar Year 24 Bull Street Annex-House X X X Calendar Year College of Charleston Residence Halls and Historic Housing Facilities Fire alarm monitoring

Kasman, Alex

83

A Comparison of Two Prototype Laser-Optical Firing Systems  

SciTech Connect (OSTI)

The design and characterization of small, ruggedized laser-optical subsystems is required for the continued development of robust laser-optical firing systems. Typically, these subsystems must be capable of generating the needed laser optical energy, delivering that energy via fiber-optical cables while taking up occupying a volume as small as possible. A novel beam splitting and fiber injection scheme has been proposed which utilizes two diffractive optical components. These components were utilized to reduce the volume of a previously designed system. A laser-optical prototype system was assembled and tested which utilized this beam splitting and fiber injection scheme along other modifications to the laser module and the power supply. This prototype was based on earlier designs that utilized environmentally proven opto-mechanical sub-assemblies. The system was tested to characterize the laser performance, the splitter-coupler transmission efficiency, channel-to-channel energy balance and fiber interchangeability. The results obtained for this design will be compared to the performance of a prototype system based on a more traditional beam splitting and fiber injection scheme. The traditional design utilized partially reflecting mirrors for beam splitting and plano-convex lenses for fiber injection. These results will be discussed as will their ultimate impact on future designs and packaging strategies.

Gregg L. Morelli; Michelle R. Bright

2008-08-11T23:59:59.000Z

84

Design criteria document, Fire Protection Task, K Basin Essential Systems Recovery, Project W-405  

SciTech Connect (OSTI)

The K Basin were constructed in the early 1950`s with a 20 year design life. The K Basins are currently in their third design life and are serving as a near term storage facility for irradiated N Reactor fuel until an interim fuel storage solution can be implemented. In April 1994, Project W-405, K Basin Essential Systems Recovery, was established to address (among other things) the immediate fire protection needs of the 100K Area. A Fire Barrier Evaluation was performed for the wall between the active and inactive areas of the 105KE and 105KW buildings. This evaluation concludes that the wall is capable of being upgraded to provide an equivalent level of fire resistance as a qualified barrier having a fire resistance rating of 2 hours. The Fire Protection Task is one of four separate Tasks included within the scope of Project W405, K Basin Essential systems Recovery. The other three Tasks are the Water Distribution System Task, the Electrical System Task, and the Maintenance Shop/Support Facility Task. The purpose of Project W-405`s Fire Protection Task is to correct Life Safety Code (NFPA 101) non-compliances and to provide fire protection features in Buildings 105KE, 105KW and 190KE that are essential for assuring the safe operation and storage of spent nuclear fuel at the 100K Area Facilities` Irradiated Fuel Storage Basins (K Basins).

Johnson, B.H.

1994-12-14T23:59:59.000Z

85

Posted CX Q14 Sprinkler System Upgrade.pdf  

Broader source: Energy.gov (indexed) [DOE]

(NEPA) Categorical Exclusion (eX) (NEPA) Categorical Exclusion (eX) Determination Summary Form Q14 Sprinkler System Upgrade Project REFERENCE J 10 CFR Part 1021 , Department of Energy National Environmental Policy Act Implementation Procedures, Subpart 0 , Typical Classes of Actions PROJECT SCOPE DISCUSSION The project scope will upgrade the Q14 sprinkler system to meet exposed plastic design basis requirements by installing a fire pump and performing modifications to the Q14 sprinkler piping. The fire pump will be a pre-assembled skid system with enclosure diesel powered pump and associated diesel storage tank. The fire pump assembly wi ll be located on a foundation pad in the grassy area ,;!orthwest of 014. Electrical work will include providing general power to the fire pump building and fire pump control/alarm wiring to a fire alarm panel in the 014

86

Fire science at LLNL: A review  

SciTech Connect (OSTI)

This fire sciences report from LLNL includes topics on: fire spread in trailer complexes, properties of welding blankets, validation of sprinkler systems, fire and smoke detectors, fire modeling, and other fire engineering and safety issues. (JEF)

Hasegawa, H.K. (ed.)

1990-03-01T23:59:59.000Z

87

Flame quality monitor system for fixed firing rate oil burners  

DOE Patents [OSTI]

A method and apparatus for determining and indicating the flame quality, or efficiency of the air-fuel ratio, in a fixed firing rate heating unit, such as an oil burning furnace, is provided. When the flame brightness falls outside a preset range, the flame quality, or excess air, has changed to the point that the unit should be serviced. The flame quality indicator output is in the form of lights mounted on the front of the unit. A green light indicates that the flame is about in the same condition as when the burner was last serviced. A red light indicates a flame which is either too rich or too lean, and that servicing of the burner is required. At the end of each firing cycle, the flame quality indicator goes into a hold mode which is in effect during the period that the burner remains off. A yellow or amber light indicates that the burner is in the hold mode. In this mode, the flame quality lights indicate the flame condition immediately before the burner turned off. Thus the unit can be viewed when it is off, and the flame condition at the end of the previous firing cycle can be observed.

Butcher, Thomas A. (Pt. Jefferson, NY); Cerniglia, Philip (Moriches, NY)

1992-01-01T23:59:59.000Z

88

The qualification of advanced composite pipe for use in fire water deluge systems on open type offshore oil platforms  

SciTech Connect (OSTI)

Different types of FIBERBOND{reg_sign} pipe in the dry condition and with a butt and strap joint were subjected to a controlled fire for fire endurance evaluation. Testing adheres to a modification of the ASTM 1173-95 guideline, which simulates the development of an actual hydrocarbon fire. For a fire water deluge system, the pipe is in the dry condition approximately one to three minutes during an actual hydrocarbon fire. Preliminary testing shows that composite pipe is able to withstand this exposure to fire for the five minute duration of the test. This is achieved with modifying the chemical composition of the composite pipe and in some cases, adding an additional structural component to the overall pipe. Therefore, composite pipe could be used for the deluge fire system of an offshore oil platform.

Lea, R.H. [Specialty Plastics, Inc., Baton Rouge, LA (United States); Stubblefield, M.A.; Pang, S.S. [Louisiana State Univ., Baton Rouge, LA (United States). Dept. of Mechanical Engineering

1996-12-01T23:59:59.000Z

89

Independent Oversight Review of the Fire Protection Program at the Pacific Northwest National Laboratory and the Fire Suppression System at the Radiochemical Processing Laboratory, September 2013  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Independent Oversight Review of the Independent Oversight Review of the Fire Protection Program at Pacific Northwest National Laboratory and the Fire Suppression System at the Radiochemical Processing Laboratory May 2011 February 2013 September 2013 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy Table of Contents 1.0 Purpose.................................................................................................................................................... 1 2.0 Background ............................................................................................................................................. 1 3.0 Scope....................................................................................................................................................... 2

90

Independent Oversight Review of the Fire Protection Program at the Pacific Northwest National Laboratory and the Fire Suppression System at the Radiochemical Processing Laboratory, September 2013  

Broader source: Energy.gov (indexed) [DOE]

Independent Oversight Review of the Independent Oversight Review of the Fire Protection Program at Pacific Northwest National Laboratory and the Fire Suppression System at the Radiochemical Processing Laboratory May 2011 February 2013 September 2013 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy Table of Contents 1.0 Purpose.................................................................................................................................................... 1 2.0 Background ............................................................................................................................................. 1 3.0 Scope....................................................................................................................................................... 2

91

Development of a high-performance coal-fired power generating system with pyrolysis gas and char-fired high temperature furnace (HITAF)  

SciTech Connect (OSTI)

A concept for an advanced coal-fired combined-cycle power generating system is currently being developed. The first phase of this three-phase program consists of conducting the necessary research and development to define the system, evaluating the economic and technical feasibility of the concept, and preparing an R D plan to develop the concept further. The power generating system being developed in this project will be an improvement over current coal-fired systems. Goals have been specified that relate to the efficiency, emissions, costs, and general operation of the system. The system proposed to meet these goals is a combined-cycle system where air for a gas turbine is indirectly heated to approximately 1800[degrees]F in furnaces fired with coal-derived fuels and then directly heated in a natural-gas-fired combustor to about 2400[degrees]F. The system is based on a pyrolyzing process that converts the coal into a low-Btu fuel gas and char. The fuel gas is relatively clean, and it is fired to heat tube surfaces that are susceptible to corrosion and problems from ash deposition. In particular, the high-temperature air heater tubes, which will need to be a ceramic material, will be located in a separate furnace or region of a furnace that is exposed to combustion products from the low-Btu fuel gas only.

Not Available

1993-02-01T23:59:59.000Z

92

Low emission boiler system: Coal-fired power for the 21st century  

SciTech Connect (OSTI)

The U.S. Department of Energy, Pittsburgh Energy Technology Center, is working with private industry to develop the Low Emission Boiler System (LEBS), an advanced coal-fired power generation system for the 21st century. LEBS provides significantly higher thermal efficiency, superior environmental performance and a lower cost of electricity than conventional coal-fired systems. To meet the anticipated increase in electricity demand throughout the world, cleaner and more efficient power plants will be needed. This paper reviews performance of the LEBS, considers further improvements, and discusses its economics.

Ramezan, M. [Burns and Roe Services Corp., Pittsburgh, PA (United States); Van Bibber, L.; White, J. [Parsons Power Group Inc., Pittsburgh, PA (United States); Kim, S.S. [Dept. of Energy, Pittsburgh, PA (United States)

1996-12-31T23:59:59.000Z

93

Fire Egress  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

OSHAX.org - OSHAX.org - The Unofficial Guide To the OSHA 1 Introduction  Fires and explosions kill more than 200 and injure more than 5,000 workers each year  There is a long and tragic history of workplace fires in this country caused by problems with fire exits and extinguishing systems  OSHA requires employers to provide proper exits, fire fighting equipment, and employee training to prevent fire deaths and injuries in the workplace OSHAX.org - The Unofficial Guide To the OSHA 2 Exit Route  A continuous and unobstructed path of exit travel from any point within a workplace to a place of safety (including refuge areas)  Consists of three parts:  Exit access  Exit  Exit discharge OSHAX.org - The Unofficial Guide To the OSHA 3 Exit Routes Basic Requirements

94

Analysis of Fire Calls to an Industrial Complex Over a 12-year Period  

SciTech Connect (OSTI)

This paper gives an analysis of fire calls from over a decade of operations at a process facility. These data include valid alarms, unwanted or false alarms, ambulance calls, and hazardous material cleanup calls. Of special interest are false alarms, which are not only a nuisance to facility productivity but are detrimental to public and facility safety. Of the fire calls listed here, over half were from false alarms. The results given are compared to National Fire Protection Association data. The data presented can serve as exemplar data for future facilities and can be compared to other operating facilities experiences.

L. C. Cadwallader

2009-03-01T23:59:59.000Z

95

Radio frequency security system, method for a building facility or the like, and apparatus and methods for remotely monitoring the status of fire extinguishers  

DOE Patents [OSTI]

A system for remotely monitoring the status of one or more fire extinguishers includes means for sensing at least one parameter of each of the fire extinguishers; means for selectively transmitting the sensed parameters along with information identifying the fire extinguishers from which the parameters were sensed; and means for receiving the sensed parameters and identifying information for the fire extinguisher or extinguishers at a common location. Other systems and methods for remotely monitoring the status of multiple fire extinguishers are also provided.

Runyon, Larry (Richland, WA); Gunter, Wayne M. (Richland, WA); Gilbert, Ronald W. (Gilroy, CA)

2006-07-25T23:59:59.000Z

96

Vulnerability assessment of water supply systems for insufficient fire flows  

E-Print Network [OSTI]

and Data Acquisition (SCADA) systems. Generally speaking, SCADA systems are the monitoring and control systems in the utility industries which help in operating the water system components with proper timing and sequence, measuring water quality... parameters, etc., without physically accessing the network. Thus, SCADA systems can reduce operating cost for a water utility and thereby increase a water system?s efficiency. The proposed hardening methodology of the water supply system was based...

Kanta, Lufthansa Rahman

2009-05-15T23:59:59.000Z

97

Duct System Flammability and Air Sealing Fire Separation Assemblies in the International Residential Code  

SciTech Connect (OSTI)

IBACOS identified two barriers that limit the ability of builders to cost-effectively achieve higher energy efficiency levels in housing. These are (1) the use of duct system materials that inherently achieve airtightness and are appropriately sized for low-load houses and (2) the ability to air seal fire separation assemblies. The issues identified fall into a gray area of the codes.

Rudd, A.; Prahl, D.

2014-12-01T23:59:59.000Z

98

Development of a high-performance coal-fired power generating system with pyrolysis gas and char-fired high temperature furnace (HITAF)  

SciTech Connect (OSTI)

A concept for an advanced coal-fired combined-cycle power generating system is currently being developed. The first phase of this three-phase program consists of conducting the necessary research and development to define the system, evaluate the economic and technical feasibility of the concept, and prepare an R D plan to develop the concept further. Foster Wheeler Development Corporation is leading a team ofcompanies involved in this effort. The system proposed to meet these goals is a combined-cycle system where air for a gas turbine is indirectly heated to approximately 1800[degrees]F in furnaces fired with cool-derived fuels and then directly heated in a natural-gas-fired combustor up to about 2400[degrees]F. The system is based on a pyrolyzing process that converts the coal into a low-Btu fuel gas and char. The fuelgas is a relatively clean fuel, and it is fired to heat tube surfaces that are susceptible to corrosion and problems from ash deposition. In particular, the high-temperature air heater tubes, which will need tobe a ceramic material, will be located in a separate furnace or region of a furnace that is exposed to combustion products from the low-Btu fuel gas only. A simplified process flow diagram is shown.

Not Available

1992-11-01T23:59:59.000Z

99

Interdependent infrastructures and multi-mode attacks and failures: improving the security of urban water systems and fire response  

E-Print Network [OSTI]

This dissertation examines the interdependence between urban water distribution systems and urban fire response. The focus on interdependent critical infrastructures is driven by concern for security of water systems and the effects on related...

Bristow, Elizabeth Catherine

2009-05-15T23:59:59.000Z

100

Integration and operation of post-combustion capture system on coal-fired power generation: load following and peak power  

E-Print Network [OSTI]

Coal-fired power plants with post combustion capture and sequestration (CCS) systems have a variety of challenges to integrate the steam generation, air quality control, cooling water systems and steam turbine with the ...

Brasington, Robert David, S.M. Massachusetts Institute of Technology

2012-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


101

NETL: News Release - Novel Coal-Fired Heating System Proves Successful at  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

December 20, 2005 December 20, 2005 Novel Coal-Fired Heating System Proves Successful at Ohio Greenhouse Cost Savings and State EPA Standards Achieved in First Commercial Demonstration WASHINGTON, DC - Using a Department of Energy - funded coal-fired technology, a greenhouse in northeast Ohio is saving more than $1,000 a day in heating costs. The efficient fluidized-bed combustion unit provides an alternative to natural gas systems and, using locally available coal and limestone, surpasses state EPA standards for sulfur capture and stack emissions. "The promise of the unit lies in its novel design," said Donald Bonk, a senior technical advisor for the National Energy Technology Laboratory (NETL), which manages the project for the Energy Department. "The fluidized-bed combustion system features flue-gas recirculation, replacing conventional, more expensive boiler tubes. By recycling the flue gas, the system better controls internal temperatures to burn fuel, reducing the formation of pollutants."

102

2012 Facility Representative/Safety System Oversight/Fire Safety Workshop Agenda  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Facility Representative  Safety System Oversight  Fire Safety Facility Representative  Safety System Oversight  Fire Safety Overall Workshop Agenda May 14-18, 2012  Alexis Park Hotel  Las Vegas, Nevada Monday, May 14, 2012 8:00 a.m. - 5:00 p.m. SAF-271, SSO Assessments (Day 1) Zeus B Quality Assurance Overview for FR/SSO Personnel Zeus A 5:00 p.m. - 7:00 p.m. Workshop Registration Zeus Foyer Tuesday, May 15, 2012 8:00 a.m. - 5:00 p.m. Fire Safety Workshop Track Begins (see track agenda) Parthenon 4 SAF-271, SSO Assessments (Day 2) Zeus B . Safety Culture Workshop Zeus A Federal Technical Capability Panel Parthenon 2 5:00 p.m. - 7:00 p.m. Workshop Registration Zeus Foyer Wednesday, May 16, 2012 6:30 a.m. - 7:45 a.m. Workshop Registration Zeus Foyer 8:00 a.m. - 11:30 a.m. FR/SSO Tracks Begin; Plenary session with Fire Safety Track Parthenon 2 & 4

103

Alarm Response Training | Y-12 National Security Complex  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

On Time: 4:04 min. View an introduction to our Alarm Response Training, which prepares and trains personnel responding to civilian nuclear and radiological security alarms...

104

Dynamic alarm presentation in a nuclear plant control room  

DOE Patents [OSTI]

The alarm activation set point and priority for a given, spatially fixed alarm tile can vary depending in part on the mode of plant operation.

Kenneth, Scarola (Windsor, CT); Jamison, David S. (Windsor, CT); Manazir, Richard M. (North Canton, CT); Rescorl, Robert L. (Vernon, CT); Harmon, Daryl L. (Enfield, CT)

1994-01-01T23:59:59.000Z

105

Engineering development of coal-fired high-performance power systems  

SciTech Connect (OSTI)

A High Performance Power System (HIPPS) is being developed. This system is a coal-fired, combined cycle plant with indirect heating of gas turbine air. Foster Wheeler Development Corporation and a team consisting of Foster Wheeler Energy Corporation, Bechtel Corporation, University of Tennessee Space Institute and Westinghouse Electric Corporation are developing this system. In Phase 1 of the project, a conceptual design of a commercial plant was developed. Technical and economic analyses indicated that the plant would meet the goals of the project which include a 47 percent efficiency (HHV) and a 10 percent lower cost of electricity than an equivalent size PC plant. The concept uses a pyrolysis process to convert coal into fuel gas and char. The char is fired in a High Temperature Advanced Furnace (HITAF). The HITAF is a pulverized fuel-fired boiler/air heater where steam is generated and gas turbine air is indirectly heated. The fuel gas generated in the pyrolyzer is then used to heat the gas turbine air further before it enters the gas turbine. The project is currently in Phase 2 which includes engineering analysis, laboratory testing and pilot plant testing. Research and development is being done on the HIPPS systems that are not commercial or being developed on other projects. Pilot plant testing of the pyrolyzer subsystem and the char combustion subsystem are being done separately, and after each experimental program has been completed, a larger scale pyrolyzer will be tested at the Power Systems Development Facility (PSDF) in Wilsonville, AL. The facility is equipped with a gas turbine and a topping combustor, and as such, will provide an opportunity to evaluate integrated pyrolyzer and turbine operation. This report addresses the areas of technical progress for this quarter. The char combustion tests in the arch-fired arrangement were completed this quarter. A total of twenty-one setpoints were successfully completed, firing both synthetically-made char, and char generated from the pyrolyzer tests performed at FWDC's pilot plant in Livingston, New Jersey. Construction is to begin next quarter to retrofit the CETF for additional HIPPS char combustion studies in a wall-fired configuration. Design of the char transfer system for the PSDF also progressed during this quarter. A number of arrangements have been developed to modify the existing N-Valve configuration. As an experimental test facility, the PSDF needs to maintain operating flexibility in order to test under a wide range of conditions. Although a new char transfer design is needed to support the HIPPS testing at the facility, the Second Generation PFB program will also utilize this system.

NONE

1999-05-01T23:59:59.000Z

106

Aspects of the electrical system design of the colmi 660 mw coal-fired power plant  

SciTech Connect (OSTI)

The conceptual design of the electrical systems for Mexico's Commission Federal de Electricidad (CFE) COLMI 660-MW coal-fired power plant builds on Bechtel's experience with nuclear, gas and coal-fired generating plants. The COLMI conceptual design incorporates a combination of new equipment applications and design considerations that make it more economical when compared to traditional alternatives. Also it provides a reliable state-of-the-art distribution system that is flexible enough for any unit in the 400-900 MW range. Alternative approaches were studied for the system design and equipment arrangement. This paper reviews the approach taken to arrive at the conceptual design and describes the equipment selected and the advantages they provide. Exact sizing and determination of characteristics of the equipment are not given because these were not determined during the conceptual design. These will be determined during the detailed design phase of the project.

Aguilar, J. (Bechtel Corp., Norwalk, CA (US)); Fernandez, J.H. (Comision Federal de Electricidad, Mexico, D.F. (MX))

1992-01-01T23:59:59.000Z

107

Dilution-based emissions sampling from stationary sources: part 2 - gas-fired combustors compared with other fuel-fired systems  

SciTech Connect (OSTI)

With the recent focus on fine particle matter (PM2.5), new, self- consistent data are needed to characterize emissions from combustion sources. Emissions data for gas-fired combustors are presented, using dilution sampling as the reference. The sampling and analysis of the collected particles in the presence of precursor gases, SO{sub 2}, nitrogen oxide, volatile organic compound, and NH{sub 3} is discussed; the results include data from eight gas fired units, including a dual- fuel institutional boiler and a diesel engine powered electricity generator. These data are compared with results in the literature for heavy-duty diesel vehicles and stationary sources using coal or wood as fuels. The results show that the gas-fired combustors have very low PM2.5 mass emission rates in the range of {approximately}10{sup -4} lb/million Btu (MMBTU) compared with the diesel backup generator with particle filter, with {approximately} 5 x 10{sup -3} lb/MMBTU. Even higher mass emission rates are found in coal-fired systems, with rates of {approximately} 0.07 lb/MMBTU for a bag-filter-controlled pilot unit burning eastern bituminous coal. The characterization of PM2.5 chemical composition from the gas-fired units indicates that much of the measured primary particle mass in PM2.5 samples is organic or elemental carbon and, to a much less extent, sulfate. Metal emissions are low compared with the diesel engines and the coal- or wood-fueled combustors. The metals found in the gas- fired combustor particles are low in concentration. The interpretation of the particulate carbon emissions is complicated by the fact that an approximately equal amount of particulate carbon is found on the particle collector and a backup filter. It is likely that measurement artifacts are positively biasing 'true' particulate carbon emissions results. 49 refs., 1 fig., 12 tabs.

England, G.C.; Watson, J.G.; Chow, J.C.; Zielinska, B.; Chang, M.C.O.; Loos, K.R.; Hidy. G.M. [GE Energy, Santa Ana, CA (United States)

2007-01-15T23:59:59.000Z

108

2012 Facility Representative/Safety System Oversight/Fire Safety Workshop - Registrants  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Facility Representative / Safety System Oversight Workshop Facility Representative / Safety System Oversight Workshop DOE Fire Safety Workshop Federal Technical Capability Panel (FTCP) Meeting May 14 - 18, 2012, at the Alexis park Resort Hotel, Las Vegas, NV Registrants As of 5/15/2012 Total Number: 218 First Name Last Name Government /Contractor Agency Secretarial Office Site Position Training Course FTCP FS 5/15 FS 5/16 FR/SSO Plenary FR Track SSO Track Fire Safety Training Tour Ron Alderson Government Employee DOE NNSA Nevada SSO SAF-271 No No No Yes No Yes No No Josh Allen Government Employee DOE EM Richland FR No No No No Yes Yes No No No Mark Alsdorf Government Employee DOE HSS Headquarters NTC Safety Training Manager SAF-271 Yes No No Yes No No No No Xavier Aponte Government Employee

109

Engineering development of coal-fired high-performance power systems. Technical report, July - September 1996  

SciTech Connect (OSTI)

A High Performance Power System (HIPPS) is being developed. This system is a coal-fired, combined cycle plant with indirect heating of gas turbine air. Foster Wheeler Development Corporation and a team consisting of Foster Wheeler Energy Corporation, AlliedSignal Aerospace Equipment Systems, Bechtel Corporation, University of Tennessee Space Institute and Westinghouse Electric Corporation are developing this system. In Phase I of the project, a conceptual design of a commercial plant was developed. Technical and economic analyses indicated that the plant would meet the goals of the project which include a 47 percent efficiency (HHV) and a 10 percent lower cost of electricity than an equivalent size PC plant. The concept uses a pyrolyzation process to convert coal into fuel gas and char. The char is fired in a High Temperature Advanced Furnace (HITAF). It is a pulverized fuel-fired boiler/airheater where steam and gas turbine air are indirectly heated. The fuel gas generated in the pyrolyzer is then used to heat the gas turbine air further before it enters the gas turbine. The project is currently in Phase 2 which includes engineering analysis, laboratory testing and pilot plant testing. Research and development is being done on the HIPPS systems that are not commercial or being developed on other projects. Pilot plant testing of the pyrolyzer subsystem and the char combustion subsystem are being done separately, and then a pilot plant with integrated pyrolyzer and char combustion systems will be tested. In this report, progress in the pyrolyzer pilot plant preparation is reported. The results of extensive laboratory and bench scale testing of representative char are also reported. Preliminary results of combustion modeling of the char combustion system are included. There are also discussions of the auxiliary systems that are planned for the char combustion system pilot plant and the status of the integrated system pilot plant.

NONE

1996-11-01T23:59:59.000Z

110

Study of the Heating Load of a Manufactured Space with a Gas-fired Radiant Heating System  

E-Print Network [OSTI]

A thermal balance mathematics model of a manufactured space with a gas-fired radiant heating system is established to calculate the heating load. Computer programs are used to solve the model. Envelope internal surface temperatures under different...

Zheng, X.; Dong, Z.

2006-01-01T23:59:59.000Z

111

Life cycle considerations of the flue gas desulphurization system at a lignite-fired power plant in Thailand  

Science Journals Connector (OSTI)

The Flue Gas Desulphurization (FGD) system has been installed at the biggest lignite-fired power generation plant in Thailand to reduce the large...2...emission. In order to understand the costs and benefits, bot...

Sate Sampattagul; Seizo Kato

2004-11-01T23:59:59.000Z

112

Techno-Economic Assessment of Polymer Membrane Systems for Postcombustion Carbon Capture at Coal-Fired Power Plants  

Science Journals Connector (OSTI)

Techno-Economic Assessment of Polymer Membrane Systems for Postcombustion Carbon Capture at Coal-Fired Power Plants ... The HHVs for three coals are 30?840, 19?400, and 14?000 kJ/kg, respectively. ...

Haibo Zhai; Edward S. Rubin

2013-02-13T23:59:59.000Z

113

ENGINEERING DEVELOPMENT OF COAL-FIRED HIGH PERFORMANCE POWER SYSTEMS PHASE II AND III  

SciTech Connect (OSTI)

This report presents work carried out under contract DE-AC22-95PC95144 "Engineering Development of Coal-Fired High Performance Systems Phase II and III." The goals of the program are to develop a coal-fired high performance power generation system (HIPPS) that is capable of: thermal efficiency (HHV) >47%; NOx, SOx, and particulates <10% NSPS (New Source Performance Standard); coal providing >65% of heat input; all solid wastes benign; cost of electricity <90% of present plants. Phase I, which began in 1992, focused on the analysis of various configurations of indirectly fired cycles and on technical assessments of alternative plant subsystems and components, including performance requirements, developmental status, design options, complexity and reliability, and capital and operating costs. Phase I also included preliminary R&D and the preparation of designs for HIPPS commercial plants approximately 300 MWe in size. This phase, Phase II, involves the development and testing of plant subsystems, refinement and updating of the HIPPS commercial plant design, and the site selection and engineering design of a HIPPS prototype plant. Work reported herein is from: Task 2.2 HITAF Air Heaters; Task 6 HIPPS Commercial Plant Design Update.

NONE

1998-09-30T23:59:59.000Z

114

Safety & Emergency Management  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

designed ESH 108 Building Orientation course. Fire Alarm System Testing Through Argonne Fire Protection Services, the fire alarm system is tested visually and audibly annually....

115

Engineering development of coal-fired high-performance power systems  

SciTech Connect (OSTI)

In Phase I of the project, a conceptual design of a coal-fired high performance power system was developed, and small scale R&D was done in critical areas of the design. The current Phase Of the project includes development through the pilot plant stage, and design of a prototype plant that would be built in Phase 3. Foster Wheeler Development Corporation is leading a team of companies in this effort: AlliedSignal Aerospace Equipment Systems, Bechtel Corporation, University of Tennessee Space Institute (UTSI), and Westinghouse Electric Corporation. The power generating system being developed in this project will be an improvement over current coal-fired systems. The following goals have been identified that relate to the efficiency,emissions, costs and general operation of the system: total station efficiency of at least 4 percent on a higher heating value basis; emissions--NOx {lt} 0.06 lb/MMBtu, SOx {lt} 0.06 lb/MMBtu, particulates {lt} 0.003 lb/MMBtu; all solid wastes must be benign with regard to disposal; over 95 percent of the total heat input is ultimately from coal, with initial systems capable of using coal for at least 65 percent of the heat input; 10 percent lower cost of electricity relative to a modern coal-fired plant conforming to NSPS. The base case arrangement of the HIPPS cycle is a combined cycle plant, and is referred to as the All Coal HIPPS because it does not require any other fuels for normal operation. An alternative HIPPS cycle uses a ceramic air heater to heat the air to temperatures above what can be achieved with alloy tubes. This arrangement is referred to as the 35 percent natural gas HIPPS. 2 refs., 11 figs. 3 tabs.

NONE

1996-06-01T23:59:59.000Z

116

Install Waste Heat Recovery Systems for Fuel-Fired Furnaces (English/Chinese) (Fact Sheet)  

SciTech Connect (OSTI)

Chinese translation of ITP fact sheet about installing Waste Heat Recovery Systems for Fuel-Fired Furnaces. For most fuel-fired heating equipment, a large amount of the heat supplied is wasted as exhaust or flue gases. In furnaces, air and fuel are mixed and burned to generate heat, some of which is transferred to the heating device and its load. When the heat transfer reaches its practical limit, the spent combustion gases are removed from the furnace via a flue or stack. At this point, these gases still hold considerable thermal energy. In many systems, this is the greatest single heat loss. The energy efficiency can often be increased by using waste heat gas recovery systems to capture and use some of the energy in the flue gas. For natural gas-based systems, the amount of heat contained in the flue gases as a percentage of the heat input in a heating system can be estimated by using Figure 1. Exhaust gas loss or waste heat depends on flue gas temperature and its mass flow, or in practical terms, excess air resulting from combustion air supply and air leakage into the furnace. The excess air can be estimated by measuring oxygen percentage in the flue gases.

Not Available

2011-10-01T23:59:59.000Z

117

Thermophotovoltaic power generation systems using natural gas-fired radiant burners  

Science Journals Connector (OSTI)

Thermophotovoltaic (TPV) power generation in gas-fired furnaces is attracting technical attention. Considerable work has been done in the area of low bandgap GaSb cell-based TPV systems as well as silicon solar cell-based TPV systems. Previous investigations have shown that a radiant burner with a high conversion level of fuel to radiation energy must be developed to realize an efficient TPV system. In our work, we investigated different natural gas-fired radiant burners in order to raise the conversion of fuel energy to thermal radiation. These burners were used as radiation sources to establish and test two TPV prototype systems. It was found that for a non-surface combustion radiant burner, the radiation output can be enhanced using a thermal radiator with a porous structure. Also, we developed a cascaded radiant burner that generates two streams of radiation output. One stream illuminates silicon concentrator solar cells while the other drives low bandgap GaSb cells. In this way, useful radiation output and thus TPV system efficiency are significantly increased due to the cascaded utilization of combustion heat and optimized thermal management.

K. Qiu; A.C.S. Hayden

2007-01-01T23:59:59.000Z

118

Engineering Development of Coal-Fired High-Performance Power Systems  

SciTech Connect (OSTI)

A High Performance Power System (HIPPS) is being developed. This system is a coal-fired, combined cycle plant with indirect heating of gas turbine air. Foster Wheeler Development Corporation and a team consisting of Foster Wheeler Energy Corporation, Bechtel Corporation, University of Tennessee Space Institute and Westinghouse Electric Corporation are developing this system. In Phase 1 of the project, a conceptual design of a commercial plant was developed. Technical and economic analyses indicated that the plant would meet the goals of the project which include a 47 percent efficiency (HHV) and a 10 percent lower cost of electricity than an equivalent size PC plant. The concept uses a pyrolysis process to convert coal into fuel gas and char. The char is fired in a High Temperature Advanced Furnace (HITAF). The HITAF is a pulverized fuel-fired boiler/air heater where steam is generated and gas turbine air is indirectly heated. The fuel gas generated in the pyrolyzer is then used to heat the gas turbine air further before it enters the gas turbine. The project is currently in Phase 2 which includes engineering analysis, laboratory testing and pilot plant testing. Research and development is being done on the HIPPS systems that are not commercial or being developed on other projects. Pilot plant testing of the pyrolyzer subsystem and the char combustion subsystem are being done separately. This report addresses the areas of technical progress for this quarter. The detail of syngas cooler design is given in this report. The final construction work of the CFB pyrolyzer pilot plant has started during this quarter. No experimental testing was performed during this quarter. The proposed test matrix for the future CFB pyrolyzer tests is given in this report. Besides testing various fuels, bed temperature will be the primary test parameter.

York Tsuo

2000-12-31T23:59:59.000Z

119

ENGINEERING DEVELOPMENT OF COAL-FIRED HIGH-PERFORMANCE POWER SYSTEMS  

SciTech Connect (OSTI)

A High Performance Power System (HIPPS) is being developed. This system is a coal-fired, combined cycle plant with indirect heating of gas turbine air. Foster Wheeler Development Corporation and a team consisting of Foster Wheeler Energy Corporation, Bechtel Corporation, University of Tennessee Space Institute and Westinghouse Electric Corporation are developing this system. In Phase 1 of the project, a conceptual design of a commercial plant was developed. Technical and economic analyses indicated that the plant would meet the goals of the project which include a 47 percent efficiency (HHV) and a 10 percent lower cost of electricity than an equivalent size PC plant. The concept uses a pyrolyzation process to convert coal into fuel gas and char. The char is fired in a High Temperature Advanced Furnace (HITAF). The HITAF is a pulverized fuel-fired boiler/air heater where steam is generated and gas turbine air is indirectly heated. The fuel gas generated in the pyrolyzer is then used to heat the gas turbine air further before it enters the gas turbine. The project is currently in Phase 2, which includes engineering analysis, laboratory testing and pilot plant testing. Research and development is being done on the HIPPS systems that are not commercial or being developed on other projects. Pilot plant testing of the pyrolyzer subsystem and the char combustion subsystem are being done separately, and after each experimental program has been completed, a larger scale pyrolyzer will be tested at the Power Systems Development Facility (PSDF) in Wilsonville, Al. The facility is equipped with a gas turbine and a topping combustor, and as such, will provide an opportunity to evaluate integrated pyrolyzer and turbine operation. The design of the char burner was completed during this quarter. The burner is designed for arch-firing and has a maximum capacity of 30 MMBtu/hr. This size represents a half scale version of a typical commercial burner. The burner is outfitted with nozzles for separate injection of char, coal, and limestone. Burner performance will be rated according to three criteria, carbon conversion efficiency, NOx generation, and flame stability. If initial testing in the arch configuration proves successful, further tests will be performed in the wall-fired arrangement. A complete set of process and instrumentation drawings (P/ID's) were completed for the Combustion and Environmental Test Facility (CETF) this quarter. These drawings established an ISA approved instrument tagging structure, and provided a coherent database for the development of a data acquisition system. The data acquisition system polls tag information (value, range, engineering units, etc.) from the distributed control system (DCS) highway, and provides a platform for data reduction. The quadrupole mass spectrometer, used during the pyrolyzer tests performed at the pilot plant in Livingston, N.J., has been redesigned for use at the CETF. The mass spectrometer is designed to provide on-line gas analysis by identifying all of the chemical components within the secondary air line, the flue gas recycle line, and the furnace exit ducting. The construction effort at the CETF continued this quarter with the completion of the char storage system, reheat burner, flue gas recycle piping, and the pulverized coal feed system.

NONE

1998-11-01T23:59:59.000Z

120

Development status of coal-fired gas heaters for Brayton-cycle cogeneration systems  

SciTech Connect (OSTI)

Under contract from the Department of Energy, Rocketdyne is developing the technology of coal-fired gas heaters for utilization in Brayton-cycle cogeneration systems. The program encompasses both atmospheric fluidized bed and pulverized coal combustion systems; and it is directed toward the development of gas heater systems capable of delivering high pressure air or helium at 1550 F, when employing metallic heat exchangers, and 1750 F, when employing ceramic heat exchangers. This paper reports on the development status of the program, with discussions of the completed ''screening'' corrosion/erosion tests of candidate heat exchanger materials, a description and summary of the operating experience with the 6- by 6-foot AFB test facility and a projection of the potential for relatively near term commercialization of such heater systems.

Gunn, S.V.; McCarthy, J.R.

1983-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


121

Assembly and Characterization of a Prototype Laser-Optical Firing System  

SciTech Connect (OSTI)

The design, assembly and characterization of the latest generation of a small, ruggedized laser-optical firing system will be discussed. This work builds upon earlier results in an effort to continue the development of robust fiber-coupled laseroptical firing systems.[1][2] This newest prototype strives to improve on earlier designs, while continuing to utilize many of the environmentally proven opto-mechanical sub-assemblies.[2][3] One area of improvement involves the implementation of a second optical safing and arming component. Several additional design improvements were also incorporated to address shortcomings uncovered during environmental testing.[4][5] These tests and the subsequent failure analysis were performed at the laser sub-system level. Four identical prototypes were assembled and characterized. The performance of the units were evaluated by comparing a number of parameters including laser output energy, slope efficiency, beam divergence, spatial intensity profile, fiber injection and splitter-coupler transmission efficiency. Other factors evaluated were the ease of alignment, repeatability of the alignment process and the fabrication of the fiberoptical cables. The experimentally obtained results will be compared and contrasted to the performance of earlier prototypes.

Morelli, Gregg L

2009-08-03T23:59:59.000Z

122

Coal-fired high performance power generating system. Quarterly progress report, April 1--June 30, 1993  

SciTech Connect (OSTI)

This report covers work carried out under Task 2, Concept Definition and Analysis, Task 3, Preliminary R&D and Task 4, Commercial Generating Plant Design, under Contract AC22-92PC91155, ``Engineering Development of a Coal Fired High Performance Power Generation System`` between DOE Pittsburgh Energy Technology Center and United Technologies Research Center. The goals of the program are to develop a coal-fired high performance power generation system (HIPPS) by the year 2000 that is capable of: >47% thermal efficiency; NO{sub x}, SO{sub x} and Particulates {le}25% NSPS; cost {ge}65% of heat input; all solid wastes benign. In order to achieve these goals our team has outlined a research plan based on an optimized analysis of a 250 MW{sub e} combined cycle system applicable to both frame type and aeroderivative gas turbines. Under the constraints of the cycle analysis we have designed a high temperature advanced furnace (HITAF) which integrates several combustor and air heater designs with appropriate ash management procedures. A survey of currently available high temperature alloys has been completed and some of their high temperature properties are shown for comparison. Several of the most promising candidates will be selected for testing to determine corrosion resistance and high temperature strength. The corrosion resistance testing of candidate refractory coatings is continuing and some of the recent results are presented. This effort will provide important design information that will ultimately establish the operating ranges of the HITAF.

Not Available

1993-11-01T23:59:59.000Z

123

Subsurface Fire Hazards Technical Report  

SciTech Connect (OSTI)

The results from this report are preliminary and cannot be used as input into documents supporting procurement, fabrication, or construction. This technical report identifies fire hazards and proposes their mitigation for the subsurface repository fire protection system. The proposed mitigation establishes the minimum level of fire protection to meet NRC regulations, DOE fire protection orders, that ensure fire containment, adequate life safety provisions, and minimize property loss. Equipment requiring automatic fire suppression systems is identified. The subsurface fire hazards that are identified can be adequately mitigated.

Logan, R.C.

1999-09-27T23:59:59.000Z

124

DOE`s high performance power systems program: Development of advanced coal-fired combined-cycle systems  

SciTech Connect (OSTI)

Coal currently provides more than one third of the world`s electricity and more than one half of the US`s electricity. However, for coal to be the fuel of choice in the future, highly efficient, environmentally acceptable, and economically competitive, coal-fired power plants are needed. The US Department of Energy, Federal Energy Technology Center, under its High Performance Power Systems (HIPPS) Program, has two contracts in place, one with Foster Wheeler Development Corporation and one with United Technologies Research Center, to develop advanced power generation systems. Based on an indirectly fired cycle, HIPPS uses a combined cycle for power generation at efficiencies of 47--50% (HHV) with superior environmental performance (1/10 of New Source Performance Standards) and a lower cost-of-electricity (10% reduction relative to current coal-fired plants). HIPPS, scheduled to be ready for commercialization by the year 2005, could provide a solution to the anticipated worldwide demand for clean, efficient electricity generation. In this paper, the two HIPPS designs are reviewed and on-going research is discussed.

Ruth, L.; Plasynski, S.; Shaffer, F. [Dept. of Energy, Pittsburgh, PA (United States). Federal Energy Technology Center; Ramezan, M. [Burns and Roe Services Corp., Pittsburgh, PA (United States)

1997-09-01T23:59:59.000Z

125

A coal-fired combustion system for industrial process heating applications  

SciTech Connect (OSTI)

PETC has implemented a number of advanced combustion research projects that will lead to the establishment of a broad, commercially acceptable engineering data base for the advancement of coal as the fuel of choice for boilers, furnaces, and process heaters. Vortec Corporation's Phase III development contract DE-AC22-91PC91161 for a Coal-Fired Combustion System for Industrial Process Heating Applications'' is project funded under the DOE/PETC advanced combustion program. This advanced combustion system research program is for the development of innovative coal-fired process heaters which can be used for high temperature melting, smelling and waste vitrification processes. The process heater concepts to be developed are based on advanced glass melting and ore smelting furnaces developed and patented by Vortec Corporation. The process heater systems to be developed have multiple use applications; however, the Phase III research effort is being focused on the development of a process heater system to be used for producing value added vitrified glass products from boiler/incinerator ashes and industrial wastes. The primary objective of the Phase III project is to develop and integrate all the system components, from fuel through total system controls, and then test the complete system in order to evaluate its potential marketability. During the current reporting period, approval of Vortec's Environmental Assessment (EA) required under the National Environmental Policy Act (NEPA) was approved. The EA approval cycle took approximately 9 months. The preliminary test program which was being held in abeyance pending approval of the EA was initiated. Six preliminary test runs were successfully competed during the period. Engineering and design activities in support of the Phase III proof of concept are continuing, and modifications to the existing test system configuration to allow performance of the preliminary tests were completed.

Not Available

1992-09-03T23:59:59.000Z

126

Vent sizing of cumene hydroperoxide (CHP) system under fire scenario considering emergency flooding measure  

Science Journals Connector (OSTI)

Abstract Cumene hydroperoxide (CHP) can release large amounts of thermal energy and result in high temperature and pressure during runaway reactions. Calorimeters and related methodologies have been made for preventing runaway reactions of CHP. However, protective measures such as flooding and emergency relief system have not been studied intensively to protect CHP systems from runaway reactions of CHP. In this paper, vent sizing package 2 (VSP2) was used to study the runaway reactions of CHP in 12wt%, 28wt% and 48wt% concentration and CHP solution mixing with water under adiabatic and heat input conditions. Chemical systems according to runaway reaction of CHP in cumene have been identified as non tempered systems. However, tempering occurs at about 180C with pad pressure of 9bar in open cell tests after water addition. The Design Institute for Emergency Relief Systems (DIERS) methods were used to size the relief system of 120m3 reactor with 60t CHP solution content considering flooding. The required relief rate decreases significantly and the mass flow rate per unit flow area decreases slightly with the addition of water. So the vent diameter of reactors can be reduced when water has been added. The results show that the flooding and emergency relief system can be effective to protect 120m3 reactors from runaway reactions of CHP under fire scenario in the concentration around 28wt% or less. It is suggested that the relief system of CHP reactors should be sized properly considering fire scenario. If emergency flooding measure is involved for relief sizing, the measure must be credible. The volume of reactor and maximum concentration of CHP should be defined properly.

Feng Sun; Fan Zhang; Man-Ping Jin; Ning Shi; Wei Xu

2014-01-01T23:59:59.000Z

127

309 Building fire protection analysis and justification for deactivation of sprinkler system. Revision 1  

SciTech Connect (OSTI)

Provide a `graded approach` fire evaluation in preparation for turnover to Environmental Restoration Contractor for D&D. Scope includes revising 309 Building book value and evaluating fire hazards, radiological and toxicological releases, and life safety issues.

Conner, R.P.

1997-06-25T23:59:59.000Z

128

Substation fire protection features  

SciTech Connect (OSTI)

This paper describes Commonwealth Edison`s (ComEd) approach to substation fire protection. Substation fires can have a major operational, financial, as well as political impact on a utility. The overall Company philosophy encompasses both active and passive fire protection features to provide prompt detection, notification, and confinement of fire and its by-products. Conservatively designed smoke detection systems and floor and wall penetration seals form the backbone of this strategy. The Company has implemented a program to install these features in new and existing substations. Thus far these measures have been successful in mitigating the consequences of substation fires.

Hausheer, T.G. [Commonwealth Edison Co., Chicago, IL (United States)

1995-10-01T23:59:59.000Z

129

ENGINEERING DEVELOPMENT OF COAL-FIRED HIGH-PERFORMANCE POWER SYSTEMS  

SciTech Connect (OSTI)

A High Performance Power System (HIPPS) is being developed. This system is a coal-fired, combined cycle plant with indirect heating of gas turbine air. Foster Wheeler Development Corporation and a team consisting of Foster Wheeler Energy Corporation, Bechtel Corporation, University of Tennessee Space Institute and Westinghouse Electric Corporation are developing this system. In Phase 1 of the project, a conceptual design of a commercial plant was developed. Technical and economic analyses indicated that the plant would meet the goals of the project which include a 47 percent efficiency (HHV) and a 10 percent lower cost of electricity than an equivalent size PC plant. The concept uses a pyrolysis process to convert coal into fuel gas and char. The char is fired in a High Temperature Advanced Furnace (HITAF). The HITAF is a pulverized fuel-fired boiler/air heater where steam is generated and gas turbine air is indirectly heated. The fuel gas generated in the pyrolyzer is then used to heat the gas turbine air further before it enters the gas turbine. The project is currently in Phase 2 which includes engineering analysis, laboratory testing and pilot plant testing. Research and development is being done on the HIPPS systems that are not commercial or being developed on other projects. Pilot plant testing of the pyrolyzer subsystem and the char combustion subsystem are being done separately, and after each experimental program has been completed, a larger scale pyrolyzer will be tested at the Power Systems Development Facility (PSDF) in Wilsonville, AL. The facility is equipped with a gas turbine and a topping combustor, and as such, will provide an opportunity to evaluate integrated pyrolyzer and turbine operation. This report addresses the areas of technical progress for this quarter. A general arrangement drawing of the char transfer system was forwarded to SCS for their review. Structural steel drawings were used to generate a three-dimensional model of the char transfer system including all pressure vessels and major piping components. Experimental testing at the Combustion and Environmental Test Facility continued during this quarter. Performance of the char burner, as benchmarked by flame stability and low NOx, has been exceptional. The burner was operated successfully both without natural gas and supplemental pulverized coal.

Unknown

1999-02-01T23:59:59.000Z

130

Modeling of integrated environmental control systems for coal-fired power plants  

SciTech Connect (OSTI)

The general goal of this research project is to enhance, and transfer to DOE, a new computer simulation model for analyzing the performance and cost of environmental control systems for coal-fired power plants. Systems utilizing pre-combustion, combustion, or post-combustion control methods, individually or in combination, may be considered. A unique capability of this model is the probabilistic representation of uncertainty in model input parameters. This stochastic simulation capability allows the performance and cost of environmental control systems to be quantified probabilistically, accounting for the interactions among all uncertain process and economic parameters. This method facilitates more rigorous comparisons between conventional and advanced clean coal technologies promising improved cost and/or effectiveness for SO{sub 2} and NO{sub x} removal. Detailed modeling of several pre-combustion and post-combustion processes of interest to DOE/PETC have been selected for analysis as part of this project.

Rubin, E.S.

1989-10-01T23:59:59.000Z

131

Engineering Development of Coal-Fired High-Performance Power Systems  

SciTech Connect (OSTI)

A High Performance Power System (HIPPS) is being developed. This system is a coal-fired, combined cycle plant with indirect heating of gas turbine air. Foster Wheeler Development Corporation and a team consisting of Foster Wheeler Energy Corporation, Bechtel Corporation, University of Tennessee Space Institute and Westinghouse Electric Corporation are developing this system. In Phase 1 of the project, a conceptual design of a commercial plant was developed. Technical and economic analyses indicated that the plant would meet the goals of the project which include a 47 percent efficiency (HHV) and a 10 percent lower cost of electricity than an equivalent size PC plant. The concept uses a pyrolysis process to convert coal into fuel gas and char. The char is fired in a High Temperature Advanced Furnace (HITAF). The HITAF is a pulverized fuel-fired boiler/air heater where steam is generated and gas turbine air is indirectly heated. The fuel gas generated in the pyrolyzer is then used to heat the gas turbine air further before it enters the gas turbine. The project is currently in Phase 2 which includes engineering analysis, laboratory testing and pilot plant testing. Research and development is being done on the HIPPS systems that are not commercial or being developed on other projects. Pilot plant testing of the pyrolyzer subsystem and the char combustion subsystem are being done separately, and after each experimental program has been completed, a larger scale pyrolyzer will be tested at the Power Systems Development Facility (PSDF) in Wilsonville, AL. The facility is equipped with a gas turbine and a topping combustor, and as such, will provide an opportunity to evaluate integrated pyrolyzer and turbine operation. This report addresses the areas of technical progress for this quarter. Detailed design of the components to be used to for the circulating bed gasification tests is underway. The circulating fluidized bed will allow for easy scale-up to larger size plants. The existing pyrolyzer will be outfitted with a cyclone and a j-valve to capture and reinject char into the lower combustion zone. Additional development work has been performed to evaluate advanced cycles utilizing the HIPPS system concept.

York Tsuo

1999-12-31T23:59:59.000Z

132

CRAD, Fire Protection - October 12, 2012 | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection - October 12, 2012 Fire Protection - October 12, 2012 CRAD, Fire Protection - October 12, 2012 October 12, 2012 Fire Protection Inspection Criteria, Approach, and Lines of Inquiry HSS CRAD 45-34, Rev. 1) Review fire protection system design and defense in-depth strategies. Interviews shall be conducted of personnel including fire engineers, fire coordinators, fire system technicians, facility operations personnel, and fire department personnel. Review policies, procedures, fire hazards analyses, and safety basis documentation. Additionally, perform facility building walk downs and inspections, and observe selected work activities, such as hot work, fire system impairments, combustible storage practices, dispensing flammable liquids, maintenance and testing of fire protection

133

Fire hazard analysis of Rocky Flats Building 776/777 duct systems  

SciTech Connect (OSTI)

The objective of this analysis is to determine if ventilation ductwork in Building 776/777 will maintain their structural integrity during expected fire conditions as well as standard design fires typically used to ascertain fire resistance ratings. If the analysis shows that ductwork will not maintain structural integrity, the impact of this failure will be determined and analyzed, and alternative solutions recommended. Associated with this analysis is the development of a computer fire model which can be used as an engineering tool in analyzing the effect of fires on ductwork in other areas and buildings.

DiNenno, P.J.; Scheffey, J.L.; Gewain, R.G.; Shanley, J.H. Jr. [Hughes Associates, Inc., Wheaton, MD (United States)

1988-12-01T23:59:59.000Z

134

Door Placard for Full Fire Alarm and Sprinkler Fire Code Compliance  

E-Print Network [OSTI]

apartment with wet towels or sheets, and seal air ducts or other openings where smoke may enter Open address, floor, apartment number and the number of people in your apartment Seal the doors to your

Pawlowski, Wojtek

135

Engineering development of coal-fired high performance power systems phase 2 and 3  

SciTech Connect (OSTI)

The goals of the program are to develop a coal-fired high performance power generation system (HIPPS) that is capable of: thermal efficiency (HHV) {ge} 47%; NOx, SOx, and particulates {le}10% NSPS (New Source Performance Standard); coal providing {ge} 65% of heat input; all solid wastes benign; and cost of electricity {le} 90% of present plants. Phase 1, which began in 1992, focused on the analysis of various configurations of indirectly fired cycles and on technical assessments of alternative plant subsystems and components, including performance requirements, developmental status, design options, complexity and reliability, and capital and operating costs. Phase 1 also included preliminary R and D and the preparation of designs for HIPPS commercial plants approximately 300 MWe in size. This phase, Phase 2, involves the development and testing of plant subsystems, refinement and updating of the HIPPS commercial plant design, and the site selection and engineering design of a HIPPS prototype plant. Work reported herein is from: Task 2.2 HITAF Air Heaters; and Task 2.4 Duct Heater and Gas Turbine Integration.

Unknown

1999-08-01T23:59:59.000Z

136

Advanced furnace air staging and burner modifications for ultra-low NOx firing systems  

SciTech Connect (OSTI)

Overfire air is an effective means to reduce NOx emissions from coal fired furnaces. The current range of overfire air usage on wall-fired boilers in the US is in the range of 10 to 20%. In most cases this is enough to achieve current Title IV NOx reduction requirements. Future applications are likely to go beyond 20% Overfire Air to reduce NOx further for lower investment and operating costs of SCR retrofits. Summer ozone reduction requires NOx emissions of 0.15 lb/MBtu. Currently, industry is exploring the conditions under which this goal is attainable. The paper discussed the approach to achieve ultra-low NOx emissions by using advanced furnace air staging. It describes the unique approach of redesigning the burner to maintain low NOx burner performance when the overfire air system is added or increased in capacity. The impact on furnace corrosion and unburned carbon losses are presented. A case study is used to show the effects of overfire air both on emissions and unburned carbon.

McCarthy, K.; Laux, S.; Grusha, J.

1999-07-01T23:59:59.000Z

137

calgary.ca/fire | call 3-1-1 Student Fire  

E-Print Network [OSTI]

or accidentally burning toast) Batteries are replaced yearly (ask the landlord when it was last done) Alarms can mean nobody, smokes in bed baSement Furnace and hot water tank are clear of stuff that can burn in planters, on grass, in peat moss or mulch (almost empty "beverage" cans work well) Fire pits

Habib, Ayman

138

Date ______________________ New York City Fire Department  

E-Print Network [OSTI]

familiar with the fire protection and fire suppression systems in the premises where heDate ______________________ New York City Fire Department Bureau of Fire Prevention 9 Metro received training in 3RCNY §10-01, Fire Code Sections 2701 - 2703 & 2706, the New C-14 study material

Jia, Songtao

139

Modeling of integrated environmental control systems for coal-fired power plants  

SciTech Connect (OSTI)

The Integrated Environmental Control Model (IECM) was designed to permit the systematic evaluation of environmental control options for pulverized coal-fired (PC) power plants. Of special interest was the ability to compare the performance and cost of advanced pollution control systems to conventional'' technologies for the control of particulate, SO{sub 2} and NO{sub x}. Of importance also was the ability to consider pre-combustion, combustion and post-combustion control methods employed alone or in combination to meet tough air pollution emission standards. Finally, the ability to conduct probabilistic analyses is a unique capability of the IECM. Key results are characterized as distribution functions rather than as single deterministic values. (VC)

Rubin, E.S.; Salmento, J.S.; Frey, H.C.; Abu-Baker, A.; Berkenpas, M.

1991-05-01T23:59:59.000Z

140

Modeling of integrated environmental control systems for coal-fired power plants. Final report  

SciTech Connect (OSTI)

The Integrated Environmental Control Model (IECM) was designed to permit the systematic evaluation of environmental control options for pulverized coal-fired (PC) power plants. Of special interest was the ability to compare the performance and cost of advanced pollution control systems to ``conventional`` technologies for the control of particulate, SO{sub 2} and NO{sub x}. Of importance also was the ability to consider pre-combustion, combustion and post-combustion control methods employed alone or in combination to meet tough air pollution emission standards. Finally, the ability to conduct probabilistic analyses is a unique capability of the IECM. Key results are characterized as distribution functions rather than as single deterministic values. (VC)

Rubin, E.S.; Salmento, J.S.; Frey, H.C.; Abu-Baker, A.; Berkenpas, M.

1991-05-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


141

E-Print Network 3.0 - advanced coal-fired systems Sample Search...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Program Collection: Fossil Fuels 13 Nuclear Engineering Graduate Program Summary: pollutants, a coal-fired power plant, in contrast, annually releases 10 billion kg of carbon...

142

Review of the Los Alamos National Laboratory Chemistry and Metallurgy Research Facility Fire Suppression Vital Safety System, January 2012  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

the the Los Alamos National Laboratory Chemistry and Metallurgy Research Facility Fire Suppression Vital Safety System January 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy i Table of Contents 1.0 Purpose ................................................................................................................................................... 1 2.0 Background ............................................................................................................................................ 1 3.0 Scope ...................................................................................................................................................... 1

143

Review of the Los Alamos National Laboratory Chemistry and Metallurgy Research Facility Fire Suppression Vital Safety System, January 2012  

Broader source: Energy.gov (indexed) [DOE]

the the Los Alamos National Laboratory Chemistry and Metallurgy Research Facility Fire Suppression Vital Safety System January 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy i Table of Contents 1.0 Purpose ................................................................................................................................................... 1 2.0 Background ............................................................................................................................................ 1 3.0 Scope ...................................................................................................................................................... 1

144

Review of the Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility Fire Suppression System, January 2012  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Waste Waste Characterization, Reduction, and Repackaging Facility Fire Suppression System January 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy i Table of Contents 1.0 Purpose ................................................................................................................................................... 1 2.0 Background ............................................................................................................................................ 1 3.0 Scope ...................................................................................................................................................... 1

145

Review of the Los Alamos National Laboratory Waste Characterization, Reduction, and Repackaging Facility Fire Suppression System, January 2012  

Broader source: Energy.gov (indexed) [DOE]

Waste Waste Characterization, Reduction, and Repackaging Facility Fire Suppression System January 2012 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy i Table of Contents 1.0 Purpose ................................................................................................................................................... 1 2.0 Background ............................................................................................................................................ 1 3.0 Scope ...................................................................................................................................................... 1

146

Independent Oversight Review of the Technical Area 55 Safety Class Fire Suppression System at Los Alamos National Laboratory, December 2013  

Broader source: Energy.gov (indexed) [DOE]

Technical Area 55 Technical Area 55 Safety Class Fire Suppression System at Los Alamos National Laboratory December 2013 Office of Safety and Emergency Management Evaluations Office of Enforcement and Oversight Office of Health, Safety and Security U.S. Department of Energy Table of Contents 1.0 Purpose .................................................................................................................................................... 1 2.0 Background ............................................................................................................................................. 1 3.0 Scope ....................................................................................................................................................... 2

147

ANNUAL FIRE SAFETY REPORT 2013 Ithaca, NY Campus  

E-Print Network [OSTI]

related services including programs in: · Fire Protection, Emergency Services, Emergency Management o Fire Protection Systems and Equipment o University Fire Marshal o Emergency Management o Events Management oANNUAL FIRE SAFETY REPORT 2013 Ithaca, NY Campus http

Chen, Tsuhan

148

ANNUAL FIRE SAFETY REPORT 2012 Ithaca, NY Campus  

E-Print Network [OSTI]

: · Fire Protection, Emergency Services, Emergency Management o Fire Protection Systems and Equipment oANNUAL FIRE SAFETY REPORT 2012 Ithaca, NY Campus http Annual Fire Safety Report 2012 Page 2 From the Department of Environmental Health and Safety (EH

Chen, Tsuhan

149

Development of a high-performance coal-fired power generating system with pyrolysis gas and char-fired high temperature furnace (HITAF). Quarterly progress report No. 4, October--December 1992  

SciTech Connect (OSTI)

A concept for an advanced coal-fired combined-cycle power generating system is currently being developed. The first phase of this three-phase program consists of conducting the necessary research and development to define the system, evaluating the economic and technical feasibility of the concept, and preparing an R&D plan to develop the concept further. The power generating system being developed in this project will be an improvement over current coal-fired systems. Goals have been specified that relate to the efficiency, emissions, costs, and general operation of the system. The system proposed to meet these goals is a combined-cycle system where air for a gas turbine is indirectly heated to approximately 1800{degrees}F in furnaces fired with coal-derived fuels and then directly heated in a natural-gas-fired combustor to about 2400{degrees}F. The system is based on a pyrolyzing process that converts the coal into a low-Btu fuel gas and char. The fuel gas is relatively clean, and it is fired to heat tube surfaces that are susceptible to corrosion and problems from ash deposition. In particular, the high-temperature air heater tubes, which will need to be a ceramic material, will be located in a separate furnace or region of a furnace that is exposed to combustion products from the low-Btu fuel gas only.

Not Available

1993-02-01T23:59:59.000Z

150

ANNUAL FIRE SAFETY RESIDENCE HALLS  

E-Print Network [OSTI]

protection systems. Documents in the following websites are referenced in the report: · www.fau.edu/facilities/EH&S/safety/fire evacuation procedures. · Inspecting, testing and maintaining fire protection systems in accordance with National Fire Protection Association (NFPA) standards. · Performing plan reviews and code consultation

Fernandez, Eduardo

151

System Modeling of ORNL s 20 MW(t) Wood-fired Gasifying Boiler  

SciTech Connect (OSTI)

We present an overview of the new 20 MW(t) wood-fired steam plant currently under construction by Johnson Controls, Inc. at the Oak Ridge National Laboratory in Tennessee. The new plant will utilize a low-temperature air-blown gasifier system developed by the Nexterra Systems Corporation to generate low-heating value syngas (producer gas), which will then be burned in a staged combustion chamber to produce heat for the boiler. This is considered a showcase project for demonstrating the benefits of clean, bio-based energy, and thus there is considerable interest in monitoring and modeling the energy efficiency and environmental footprint of this technology relative to conventional steam generation with petroleum-based fuels. In preparation for system startup in 2012, we are developing steady-state and dynamic models of the major process components, including the gasifiers and combustor. These tools are intended to assist in tracking and optimizing system performance and for carrying out future conceptual studies of process changes that might improve the overall energy efficiency and sustainability. In this paper we describe the status of our steady-state gasifier and combustor models and illustrate preliminary results from limited parametric studies.

Daw, C Stuart [ORNL; FINNEY, Charles E A [ORNL; Wiggins, Gavin [ORNL; Hao, Ye [ORNL

2010-01-01T23:59:59.000Z

152

Proceedings of the coal-fired power systems 94: Advances in IGCC and PFBC review meeting. Volume 1  

SciTech Connect (OSTI)

The Coal-Fired Power Systems 94 -- Advances in IGCC and PFBC Review Meeting was held June 21--23, 1994, at the Morgantown Energy Center (METC) in Morgantown, West Virginia. This Meeting was sponsored and hosted by METC, the Office of Fossil Energy, and the US Department of Energy (DOE). METC annually sponsors this conference for energy executives, engineers, scientists, and other interested parties to review the results of research and development projects; to discuss the status of advanced coal-fired power systems and future plans with the industrial contractors; and to discuss cooperative industrial-government research opportunities with METC`s in-house engineers and scientists. Presentations included industrial contractor and METC in-house technology developments related to the production of power via coal-fired Integrated Gasification Combined Cycle (IGCC) and Pressurized Fluidized Bed Combustion (PFBC) systems, the summary status of clean coal technologies, and developments and advancements in advanced technology subsystems, such as hot gas cleanup. A keynote speaker and other representatives from the electric power industry also gave their assessment of advanced power systems. This meeting contained 11 formal sessions and one poster session, and included 52 presentations and 24 poster presentations. Volume I contains papers presented at the following sessions: opening commentaries; changes in the market and technology drivers; advanced IGCC systems; advanced PFBC systems; advanced filter systems; desulfurization system; turbine systems; and poster session. Selected papers have been processed separately for inclusion in the Energy Science and Technology Database.

McDaniel, H.M.; Staubly, R.K.; Venkataraman, V.K. [eds.

1994-06-01T23:59:59.000Z

153

EVALUATION OF MERCURY EMISSIONS FROM COAL-FIRED FACILITIES WITH SCR AND FGD SYSTEMS  

SciTech Connect (OSTI)

CONSOL Energy Inc., Research & Development (CONSOL), with support from the U.S. Department of Energy, National Energy Technology Laboratory (DOE) is evaluating the effects of selective catalytic reduction (SCR) on mercury (Hg) capture in coal-fired plants equipped with an electrostatic precipitator (ESP) - wet flue gas desulfurization (FGD) combination or a spray dyer absorber--fabric filter (SDA-FF) combination. In this program CONSOL is determining mercury speciation and removal at 10 coal-fired facilities. The objectives are (1) to evaluate the effect of SCR on mercury capture in the ESP-FGD and SDA-FF combinations at coal-fired power plants, (2) evaluate the effect of catalyst degradation on mercury capture; (3) evaluate the effect of low load operation on mercury capture in an SCR-FGD system, and (4) collect data that could provide the basis for fundamental scientific insights into the nature of mercury chemistry in flue gas, the catalytic effect of SCR systems on Hg speciation and the efficacy of different FGD technologies for Hg capture. This document, the second in a series of topical reports, describes the results and analysis of mercury sampling performed on a 330 MW unit burning a bituminous coal containing 1.0% sulfur. The unit is equipped with a SCR system for NOx control and a spray dryer absorber for SO{sub 2} control followed by a baghouse unit for particulate emissions control. Four sampling tests were performed in March 2003. Flue gas mercury speciation and concentrations were determined at the SCR inlet, air heater outlet (ESP inlet), and at the stack (FGD outlet) using the Ontario Hydro method. Process stream samples for a mercury balance were collected to coincide with the flue gas measurements. Due to mechanical problems with the boiler feed water pumps, the actual gross output was between 195 and 221 MW during the tests. The results showed that the SCR/air heater combination oxidized nearly 95% of the elemental mercury. Mercury removal, on a coal-to-stack basis, was 87%. The mercury material balance closures for the four tests conducted at the plant ranged from 89% to 114%, with an average of 100%. These results appear to show that the SCR had a positive effect on mercury removal. In earlier programs, CONSOL sampled mercury at six plants with wet FGDs for SO{sub 2} control without SCR catalysts. At those plants, an average of 61 {+-} 15% of the mercury was in the oxidized form at the air heater outlet. The principal purpose of this work is to develop a better understanding of the potential Hg removal ''co-benefits'' achieved by NOx, and SO{sub 2} control technologies. It is expected that this data will provide the basis for fundamental scientific insights into the nature of Hg chemistry in flue gas, the catalytic effect of SCR systems on Hg speciation and the efficacy of different FGD technologies for Hg capture. Ultimately, this insight could help to design and operate SCR and FGD systems to maximize Hg removal.

J. A. Withum; S.C. Tseng; J. E. Locke

2004-10-31T23:59:59.000Z

154

EVALUATION OF MERCURY EMISSIONS FROM COAL-FIRED FACILITIES WITH SCR AND FGD SYSTEMS  

SciTech Connect (OSTI)

CONSOL Energy Inc., Research & Development (CONSOL), with support from the U.S. Department of Energy, National Energy Technology Laboratory (DOE) and the Electric Power Research Institute (EPRI), is evaluating the effects of selective catalytic reduction (SCR) on mercury (Hg) capture in coal-fired plants equipped with an electrostatic precipitator (ESP)--wet flue gas desulfurization (FGD) combination or a spray dryer absorber--fabric filter (SDA-FF) combination. In this program CONSOL is determining mercury speciation and removal at 10 coal-fired facilities. The objectives are (1) to evaluate the effect of SCR on mercury capture in the ESP-FGD and SDA-FF combinations at coal-fired power plants, (2) evaluate the effect of catalyst degradation on mercury capture; (3) evaluate the effect of low load operation on mercury capture in an SCR-FGD system, and (4) collect data that could provide the basis for fundamental scientific insights into the nature of mercury chemistry in flue gas, the catalytic effect of SCR systems on mercury speciation and the efficacy of different FGD technologies for mercury capture. This document, the seventh in a series of topical reports, describes the results and analysis of mercury sampling performed on a 1,300 MW unit burning a bituminous coal containing three percent sulfur. The unit was equipped with an ESP and a limestone-based wet FGD to control particulate and SO2 emissions, respectively. At the time of sampling an SCR was not installed on this unit. Four sampling tests were performed in September 2003. Flue gas mercury speciation and concentrations were determined at the ESP outlet (FGD inlet), and at the stack (FGD outlet) using the Ontario Hydro method. Process stream samples for a mercury balance were collected to coincide with the flue gas measurements. The results show that the FGD inlet flue gas oxidized:elemental mercury ratio was roughly 2:1, with 66% oxidized mercury and 34% elemental mercury. Mercury removal, on a coal-to-stack basis, was 53%. The average Hg concentration in the stack flue gas was 4.09 {micro}g/m{sup 3}. The average stack mercury emission was 3.47 Ib/TBtu. The mercury material balance closures ranged from 87% to 108%, with an average of 97%. A sampling program similar to this one was performed on a similar unit (at the same plant) that was equipped with an SCR for NOx control. Comparison of the results from the two units show that the SCR increases the percentage of mercury that is in the oxidized form, which, in turn, lends to more of the total mercury being removed in the wet scrubber. The principal purpose of this work is to develop a better understanding of the potential mercury removal ''co-benefits'' achieved by NOx, and SO{sub 2} control technologies. It is expected that this data will provide the basis for fundamental scientific insights into the nature of mercury chemistry in flue gas, the catalytic effect of SCR systems on mercury speciation and the efficacy of different FGD technologies for mercury capture. Ultimately, this insight could help to design and operate SCR and FGD systems to maximize mercury removal.

J.A. Withum; S.C. Tseng; J.E. Locke

2005-11-01T23:59:59.000Z

155

Evaluation of Mercury Emissions from Coal-Fired Facilities with SCR and FGD Systems  

SciTech Connect (OSTI)

CONSOL Energy Inc., Research & Development (CONSOL), with support from the U.S. Department of Energy, National Energy Technology Laboratory (DOE) and the Electric Power Research Institute (EPRI), is evaluating the effects of selective catalytic reduction (SCR) on mercury (Hg) capture in coal-fired plants equipped with an electrostatic precipitator (ESP)--wet flue gas desulfurization (FGD) combination or a spray dyer absorber--fabric filter (SDA-FF) combination. In this program CONSOL is determining mercury speciation and removal at 10 coal-fired facilities. The principal purpose of this work is to develop a better understanding of the potential mercury removal ''co-benefits'' achieved by NO{sub x}, and SO{sub 2} control technologies. It is expected that these data will provide the basis for fundamental scientific insights into the nature of mercury chemistry in flue gas, the catalytic effect of SCR systems on mercury speciation and the efficacy of different FGD technologies for mercury capture. Ultimately, this insight could help to design and operate SCR and FGD systems to maximize mercury removal. The objectives are (1) to evaluate the effect of SCR on mercury capture in the ESP-FGD and SDA-FF combinations at coal-fired power plants, (2) evaluate the effect of SCR catalyst degradation on mercury capture; (3) evaluate the effect of low load operation on mercury capture in an SCR-FGD system, and (4) collect data that could provide the basis for fundamental scientific insights into the nature of mercury chemistry in flue gas, the catalytic effect of SCR systems on mercury speciation and the efficacy of different FGD technologies for mercury capture. This document, the ninth in a series of topical reports, describes the results and analysis of mercury sampling performed on Unit 1 at Plant 7, a 566 MW unit burning a bituminous coal containing 3.6% sulfur. The unit is equipped with a SCR, ESP, and wet FGD to control NO{sub x}, particulate, and SO{sub 2} emissions, respectively. Four sampling tests were performed in August 2004 during ozone season with the SCR operating; flue gas mercury speciation and concentrations were determined at the SCR inlet, SCR outlet, air heater outlet (ESP inlet), ESP outlet (FGD inlet), and at the stack (FGD outlet) using the Ontario Hydro method. Three sampling tests were also performed in November 2004 during non-ozone season with the SCR bypassed; flue gas mercury speciation and concentrations were determined at the ESP outlet (FGD inlet), and at the stack (FGD outlet). Process samples for material balances were collected during the flue gas measurements. The results show that, at the point where the flue gas enters the FGD, a greater percentage of the mercury was in the oxidized form when the SCR was operating compared to when the SCR was bypassed (97% vs 91%). This higher level of oxidation resulted in higher mercury removals in the FGD because the FGD removed 90-94% of the oxidized mercury in both cases. Total coal-to-stack mercury removal was 86% with the SCR operating, and 73% with the SCR bypassed. The average mercury mass balance closure was 81% during the ozone season tests and 87% during the non-ozone season tests.

J. A. Withum; S. C. Tseng; J. E. Locke

2006-01-31T23:59:59.000Z

156

Evaluation of Mercury Emissions from Coal-Fired Facilities with SCR and FGD Systems  

SciTech Connect (OSTI)

CONSOL Energy Inc., Research & Development (CONSOL), with support from the U.S. Department of Energy, National Energy Technology Laboratory (DOE) and the Electric Power Research Institute (EPRI), is evaluating the effects of selective catalytic reduction (SCR) on mercury (Hg) capture in coal-fired plants equipped with an electrostatic precipitator (ESP)--wet flue gas desulfurization (FGD) combination or a spray dyer absorber--fabric filter (SDA-FF) combination. In this program CONSOL is determining mercury speciation and removal at 10 coal-fired facilities. The principal purpose of this work is to develop a better understanding of the potential mercury removal ''co-benefits'' achieved by NO{sub x}, and SO{sub 2} control technologies. It is expected that this data will provide the basis for fundamental scientific insights into the nature of mercury chemistry in flue gas, the catalytic effect of SCR systems on mercury speciation and the efficacy of different FGD technologies for mercury capture. Ultimately, this insight could help to design and operate SCR and FGD systems to maximize mercury removal. The objectives are (1) to evaluate the effect of SCR on mercury capture in the ESP-FGD and SDA-FF combinations at coal-fired power plants, (2) evaluate the effect of SCR catalyst degradation on mercury capture; (3) evaluate the effect of low load operation on mercury capture in an SCR-FGD system, and (4) collect data that could provide the basis for fundamental scientific insights into the nature of mercury chemistry in flue gas, the catalytic effect of SCR systems on mercury speciation and the efficacy of different FGD technologies for mercury capture. This document, the tenth in a series of topical reports, describes the results and analysis of mercury sampling performed on two 468 MW units burning bituminous coal containing 1.3-1.7% sulfur. Unit 2 is equipped with an SCR, ESP, and wet FGD to control NO{sub x}, particulate, and SO{sub 2} emissions, respectively. Unit 1 is similar to Unit 2, except that Unit 1 has no SCR for NOx control. Four sampling tests were performed on both units in January 2005; flue gas mercury speciation and concentrations were determined at the economizer outlet, air heater outlet (ESP inlet), ESP outlet (FGD inlet), and at the stack (FGD outlet) using the Ontario Hydro method. Process samples for material balances were collected with the flue gas measurements. The results show that the SCR increased the oxidation of the mercury at the air heater outlet. At the exit of the air heater, a greater percentage of the mercury was in the oxidized and particulate forms on the unit equipped with an SCR compared to the unit without an SCR (97.4% vs 91%). This higher level of oxidation resulted in higher mercury removals in the scrubber. Total mercury removal averaged 97% on the unit with the SCR, and 87% on the unit without the SCR. The average mercury mass balance closure was 84% on Unit 1 and 103% on Unit 2.

J. A. Withum; J. E. Locke

2006-02-01T23:59:59.000Z

157

Technical basis for setting Hanford Fire Department electronic dosimetry for emergency response (TBD-HSO-RC-009)  

SciTech Connect (OSTI)

This document addresses the need to establish a reasonable methodology for establishing alarm points for electronic dosimetry used by the Hanford Fire Department (HFD) for emergency response in radiological facilities.

EVANS, C.L.

2003-04-01T23:59:59.000Z

158

Techno-economic analysis of a coal-fired CHP based combined heating system with gas-fired boilers for peak load compensation  

Science Journals Connector (OSTI)

Combined heat and power (CHP) plants dominate the heating market in China. With the ongoing energy structure reformation and increasing environmental concerns, we propose gas-fired boilers to be deployed in underperforming heating substations of heating networks for peak load compensation, in order to improve both energy efficiency and environmental sustainability. However, due to the relatively high price of gas, techno-economic analysis is required for evaluating different combined heating scenarios, characterized by basic heat load ratio (?). Therefore, we employ the dynamic economics and annual cost method to develop a techno-economic model for computing the net heating cost of the system, considering the current state of the art of cogeneration systems in China. The net heating cost is defined as the investment costs and operations costs of the system subtracted by revenues from power generation. We demonstrate the model in a real-life combined heating system of Daqing, China. The results show that the minimum net heating cost can be realized at ?=0.75 with a cost reduction of 16.8% compared to coal heating alone. Since fuel cost is the dominating factor, sensitivity analyses on coal and gas prices are discussed subsequently.

Hai-Chao Wang; Wen-Ling Jiao; Risto Lahdelma; Ping-Hua Zou

2011-01-01T23:59:59.000Z

159

Allegations Regarding the Consolidation of Central Alarm Stations...  

Energy Savers [EERE]

Allegations Regarding the Consolidation of Central Alarm Stations at the Oak Ridge Reservation DOEIG-0929 December 2014 U.S. Department of Energy Office of Inspector General...

160

NETL F 451.1/1-1, Categorical Exclusion Designation Form  

Broader source: Energy.gov (indexed) [DOE]

NA Facility Support Services, Inc. FE SOD 2012 102012 - 092013 Ben Smith Morgantown, WV Morgantown Parking Garage Fire Alarm System Install and tie in Siemens fire alarm system...

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


161

NETL F 451.1/1-1, Categorical Exclusion Designation Form  

Broader source: Energy.gov (indexed) [DOE]

NA Eagle Design, Inc. FE SOD 2012 102012 - 092013 Ben Smith Morgantown, WV Morgantown Parking Garage Fire Alarm System Install and tie in Siemens fire alarm system components...

162

Coal-fired high performance power generating system. Quarterly progress report, July 1, 1993--September 30, 1993  

SciTech Connect (OSTI)

This report covers work carried out under Task 3, Preliminary Research and Development, and Task 4, Commercial Generating Plant Design, under contract DE-AC22-92PC91155, {open_quotes}Engineering Development of a Coal Fired High Performance Power Generation System{close_quotes} between DOE Pittsburgh Energy Technology Center and United Technologies Research Center. The goals of the program are to develop a coal-fired high performance power generation system (HIPPS) by the year 2000 that is capable of >47% thermal efficiency; NO{sub x}, SO{sub x}, and particulates {le} 25% NSPS; cost {ge} 65% of heat input; and all solid wastes benign. The report discusses progress in cycle analysis, chemical reactor modeling, ash deposition rate calculations for HITAF (high temperature advanced furnace) convective air heater, air heater materials, and deposit initiation and growth on ceramic substrates.

Not Available

1993-12-31T23:59:59.000Z

163

Development, Application and Performance of Venturi Register L. E. A. Burner System for Firing Oil and Gas Fuels  

E-Print Network [OSTI]

DEVELOPMENT, APPLICATION AND PERFORMANCE OF VENTURI REGISTER L. E. A. BURNER SYSTEM FOR FIRING OIL AND GAS FUELS A. D. Cawte CEA Combustion, Inc. Stamford, Connecticut INTRODUCTION The effect of reducing excess air as a means of curtailing..., extensive investigation work was undertaken us ing the water analog model techniques developed by Associated British Combustion for burner design. The development work resulted in the burner design known today as the Venturi Register, LEA (low excess air...

Cawte, A. D.

1979-01-01T23:59:59.000Z

164

ENVIRONMENT, SAFETY & HEALTH DIVISION Chapter 12: Fire and Life Safety  

E-Print Network [OSTI]

ENVIRONMENT, SAFETY & HEALTH DIVISION Chapter 12: Fire and Life Safety Fire Protection SystemProcedImpair.pdf The purpose of these procedures is to minimize the downtime of active fire protection systems by closely controlling their impairment (any condition in which a fire protection system cannot perform its designed fire

Wechsler, Risa H.

165

Engineering development of coal-fired high-performance power systems. Progress report, April 1--June 30, 1996  

SciTech Connect (OSTI)

In Phase 1 of the project, a conceptual design of a coal-fired, high-performance power system (HIPPS) was developed, and small-scale R and D was done in critical areas of the design. The current phase of the project includes development through the pilot plant stage and design of a prototype plant that would be built in Phase 3. The power-generating system being developed in this project will be an improvement over current coal-fired systems. It is a combined-cycle plant. This arrangement is referred to as the All Coal HIPPS because it does not require any other fuels for normal operation. A fluidized bed, air-blown pyrolyzer converts coal into fuel gas and char. The char is fired in a high-temperature advanced furnace (HITAF) which heats both air for a gas turbine and steam for a steam turbine. The fuel gas from the pyrolyzer goes to a topping combustor where it is used to raise the air entering the gas turbine to 1288 C. In addition to the HITAF, steam duty is achieved with a heat-recovery steam generator (HRSG) in the gas turbine exhaust stream and economizers in the HITAF flue gas exhaust stream. Progress during the quarter is described.

NONE

1996-12-31T23:59:59.000Z

166

System definition and analysis gas-fired industrial advanced turbine systems  

SciTech Connect (OSTI)

The objective is to define and analyze an engine system based on the gas fuel Advanced Turbine from Task 3. Using the cycle results of Task 3, a technical effort was started for Task 6 which would establish the definition of the engine flowpath and the key engine component systems. The key engine systems are: gas turbine engine overall flowpath; booster (low pressure compressor); intercooler; high pressure compressor; combustor; high pressure turbine; low pressure turbine and materials; engine system packaging; and power plant configurations. The design objective is to use the GE90 engine as the platform for the GE Industrial Advanced Turbine System. This objective sets the bounds for the engine flowpath and component systems.

Holloway, G.M.

1997-05-01T23:59:59.000Z

167

Design of an expert system to aid in the selection of a wood fired boiler system.  

E-Print Network [OSTI]

??Currently most industrial and institutional facilities rely on fossil fuels to power their boiler systems. As the quantity of these non-renewable resources is depleted, and (more)

Morris, Melissa L.

2008-01-01T23:59:59.000Z

168

Development of a high-performance coal-fired power generating system with pyrolysis gas and char-fired high temperature furnace (HITAF). Quarterly progress report No. 7, July--September 1993  

SciTech Connect (OSTI)

A concept for an advanced coal-fired combined-cycle power generating system is currently being developed. The first phase of this three-phase program consists of conducting the necessary research and development to define the system, evaluating the economic and technical feasibility of the concept, and preparing an R&D plan to develop the concept further. Foster Wheeler Development Corporation (FWDC) is leading a team of companies involved in this effort. The power generating system being developed in this project will be an improvement over current coal-fired systems. Goals have been specified that relate to the efficiency, emissions, costs, and general operation of the system. The system proposed to meet these goals is a combined-cycle system where air for a gas turbine is indirectly heated to approximately 1800{degrees}F in furnaces fired with coal-derived fuels and then directly heated in a natural-gas-fired combustor to about 2400{degrees}F. The system is based on a pyrolyzing process that converts the coal into a low-Btu fuel gas and char. The fuel gas is relatively clean, and it is fired to heat tube surfaces that are susceptible to corrosion and problems from ash deposition. In particular, the high-temperature air heater tubes, which will need to be a ceramic material, will be located in a separate furnace or region of a furnace that is exposed to combustion products from the low-Btu fuel gas only. A simplified process flow diagram is shown in Figure 1.

Not Available

1993-11-01T23:59:59.000Z

169

Development of a high-performance coal-fired power generating system with pyrolysis gas and char-fired high temperature furnace (HITAF). Quarterly progress report No. 3, July--September 1992  

SciTech Connect (OSTI)

A concept for an advanced coal-fired combined-cycle power generating system is currently being developed. The first phase of this three-phase program consists of conducting the necessary research and development to define the system, evaluate the economic and technical feasibility of the concept, and prepare an R & D plan to develop the concept further. Foster Wheeler Development Corporation is leading a team ofcompanies involved in this effort. The system proposed to meet these goals is a combined-cycle system where air for a gas turbine is indirectly heated to approximately 1800{degrees}F in furnaces fired with cool-derived fuels and then directly heated in a natural-gas-fired combustor up to about 2400{degrees}F. The system is based on a pyrolyzing process that converts the coal into a low-Btu fuel gas and char. The fuelgas is a relatively clean fuel, and it is fired to heat tube surfaces that are susceptible to corrosion and problems from ash deposition. In particular, the high-temperature air heater tubes, which will need tobe a ceramic material, will be located in a separate furnace or region of a furnace that is exposed to combustion products from the low-Btu fuel gas only. A simplified process flow diagram is shown.

Not Available

1992-11-01T23:59:59.000Z

170

University of Vermont 2012 Student Housing Fire Safety Report  

E-Print Network [OSTI]

awards from FM Global (insurance) for fire protection programs. All on-campus residence halls by automatic cooking fire suppression systems. All fire protection systems are inspected regularly by UVM staff Marcus, Certified Fire Protection Specialist, University Fire Marshal 284 East Avenue, Burlington, VT

Hayden, Nancy J.

171

EVALUATION OF MERCURY EMISSIONS FROM COAL-FIRED FACILITIES WITH SCR AND FGD SYSTEMS  

SciTech Connect (OSTI)

CONSOL Energy Inc., Research & Development (CONSOL), with support from the U.S. Department of Energy, National Energy Technology Laboratory (DOE) and the Electric Power Research Institute (EPRI), evaluated the effects of selective catalytic reduction (SCR) on mercury (Hg) capture in coal-fired plants equipped with an electrostatic precipitator (ESP)-wet flue gas desulfurization (FGD) combination or a spray dyer absorber-fabric filter (SDA-FF) combination. In this program CONSOL determined mercury speciation and removal at 10 bituminous coal-fired facilities; at four of these facilities, additional tests were performed on units without SCR, or with the existing SCR bypassed. This project final report summarizes the results and discusses the findings of the body of work as a whole. Eleven Topical Reports were issued (prior to this report) that describe in great detail the sampling results at each of the ten power plants individually. The results showed that the SCR-FGD combination removed a substantial fraction of mercury from flue gas. The coal-to-stack mercury removals ranged from 65% to 97% for the units with SCR and from 53% to 87% for the units without SCR. There was no indication that any type of FGD system was more effective at mercury removal than others. The coal-to-stack mercury removal and the removal in the wet scrubber were both negatively correlated with the elemental mercury content of the flue gas and positively correlated with the scrubber liquid chloride concentration. The coal chlorine content was not a statistically significant factor in either case. Mercury removal in the ESP was positively correlated with the fly ash carbon content and negatively correlated with the flue gas temperature. At most of the units, a substantial fraction (>35%) of the flue gas mercury was in the elemental form at the boiler economizer outlet. After passing through the SCR-air heater combination very little of the total mercury (<10%) remained in the elemental form in the flue gas; this was true for all SCR catalyst types and sources. Although chlorine has been suggested as a factor affecting the mercury speciation in flue gas, coal chlorine was not a statistically significant factor affecting mercury speciation at the economizer exit or at the air heater exit. The only statistically significant factors were the coal ash CaO content and the fly ash carbon content; the fraction of mercury in the elemental form at the economizer exit was positively correlated with both factors. In a direct comparison at four SCR-equipped units vs. similar units at the same sites without SCR (or with the SCR bypassed), the elemental mercury fractions (measured at the ESP outlet) were lower, and the coal-to-stack mercury removals were higher, when the SCR was present and operating. The average coal-to-stack mercury removal at the four units without an operating SCR was 72%, whereas the average removal at the same sites with operating SCRs was 88%. The unit mercury mass balance (a gauge of the overall quality of the tests) at all of the units ranged from 81% to 113%, which were within our QA/QC criterion of 80-120%.

J.A. Withum

2006-03-07T23:59:59.000Z

172

3.12 A WILDLAND FIRE DYNAMIC DATA-DRIVEN APPLICATION SYSTEM Janice L. Coen  

E-Print Network [OSTI]

University of Colorado at Denver and Health Sciences Center, Denver, CO 3 University of Kentucky, Lexington- range forecast of wildfire behavior using a coupled atmosphere-fire model injected with real disparate data sources. The DDDAS is built upon a previously existing coupled atmosphere-wildfire model

Douglas, Craig C.

173

Fire Protection  

Broader source: Directives, Delegations, and Requirements [Office of Management (MA)]

This Standard was developed to provide acceptable methods and approaches for meeting DOE fire protection program and design requirements and to address special or unique fire protection issues at DOE facilities that are not comprehensively or adequately addressed in national consensus standards or other design criteria.

2012-12-05T23:59:59.000Z

174

Direct thermal to electrical energy conversion using very low bandgap TPV cells in a gas-fired furnace system  

Science Journals Connector (OSTI)

Abstract In this paper, electricity generation using very low bandgap InGaAsSb thermophotovoltaic (TPV) cells whose bandgap is 0.53eV was investigated in a gas-fired furnace system where thermal radiation was emitted from a metal alloy emitter. The electric output of the InGaAsSb TPV cells was characterized under various operating conditions. The cell short circuit density was measured to be 3.01A/cm2 at an emitter temperature of 1197C. At this emitter temperature, an electric power density of 0.65W/cm2 was produced by the TPV cells. Experimental results show that direct thermal to electrical energy conversion was achieved in a gas-fired heating furnace system. Such a system could be employed to form a micro-combined heat and power (micro-CHP) process where exhaust heat is utilized for home heating needs. The TPV integrated energy system provides an effective means for primary energy savings.

K. Qiu; A.C.S. Hayden

2014-01-01T23:59:59.000Z

175

Conceptual design of a coal-fired MHD retrofit plant. Topical report, Seed Regeneration System Study 2  

SciTech Connect (OSTI)

Westinghouse Advanced Energy Systems (WAES), through Contract No. DE-AC22-87PC79668 funded by US DOE/PETC, is conducting a conceptual design study to evaluate a coal-fired magnetohydrodynamic (MHD) retrofit of a utility plant of sufficient size to demonstrate the technical and future economic viability of an MHD system operating within an electric utility environment. The objective of this topical report is to document continuing seed regeneration system application studies and the definition of will system integration requirements for the Scholz MHD retrofit plant design. MHD power plants require the addition of a seeding material in the form of potassium to enhance the ionization of the high temperature combustion gas in the MHD channel. This process has an added environmental advantage compared to other types of coal-fired power plants in that the potassium combines with the naturally occurring sulfur in the coal to form a potassium sulfate flyash (K{sub 2}SO{sub 4}) which can be removed from the process by appropriate particulate control equipment. Up to 100% of the Sulfur in the coal can be removed by this process thereby providing environmentally clean power plant operation that is better than required by present and anticipated future New Source Performance Standards (NSPS).

Not Available

1992-11-01T23:59:59.000Z

176

ENVIRONMENT, SAFETY & HEALTH DIVISION Chapter 12: Fire and Life Safety  

E-Print Network [OSTI]

ENVIRONMENT, SAFETY & HEALTH DIVISION Chapter 12: Fire and Life Safety Fire Protection Equipment The purpose of these requirements is to ensure the adequate provision and operability of fire protection Requirements Fire protection equipment includes Automatic fire suppression systems (such as sprinkler, clean

Wechsler, Risa H.

177

A coal-fired combustion system for industrial process heating applications. Quarterly technical progress report, April 1992--June 1992  

SciTech Connect (OSTI)

PETC has implemented a number of advanced combustion research projects that will lead to the establishment of a broad, commercially acceptable engineering data base for the advancement of coal as the fuel of choice for boilers, furnaces, and process heaters. Vortec Corporation`s Phase III development contract DE-AC22-91PC91161 for a ``Coal-Fired Combustion System for Industrial Process Heating Applications`` is project funded under the DOE/PETC advanced combustion program. This advanced combustion system research program is for the development of innovative coal-fired process heaters which can be used for high temperature melting, smelling and waste vitrification processes. The process heater concepts to be developed are based on advanced glass melting and ore smelting furnaces developed and patented by Vortec Corporation. The process heater systems to be developed have multiple use applications; however, the Phase III research effort is being focused on the development of a process heater system to be used for producing value added vitrified glass products from boiler/incinerator ashes and industrial wastes. The primary objective of the Phase III project is to develop and integrate all the system components, from fuel through total system controls, and then test the complete system in order to evaluate its potential marketability. During the current reporting period, approval of Vortec`s Environmental Assessment (EA) required under the National Environmental Policy Act (NEPA) was approved. The EA approval cycle took approximately 9 months. The preliminary test program which was being held in abeyance pending approval of the EA was initiated. Six preliminary test runs were successfully competed during the period. Engineering and design activities in support of the Phase III proof of concept are continuing, and modifications to the existing test system configuration to allow performance of the preliminary tests were completed.

Not Available

1992-09-03T23:59:59.000Z

178

Painterly fire  

Science Journals Connector (OSTI)

This sketch describes how to construct a painterly 'wall' of fire, one which exhibits realistic motion while managing to maintain an artistic look. Keywords: effects animation, natural phenomena, rendering

Saty Raghavachary; Fernando Benitez

2002-07-01T23:59:59.000Z

179

Fuel supply system and method for coal-fired prime mover  

DOE Patents [OSTI]

A coal-fired gas turbine engine is provided with an on-site coal preparation and engine feeding arrangement. With this arrangement, relatively large dry particles of coal from an on-site coal supply are micro-pulverized and the resulting dry, micron-sized, coal particulates are conveyed by steam or air into the combustion chamber of the engine. Thermal energy introduced into the coal particulates during the micro-pulverizing step is substantially recovered since the so-heated coal particulates are fed directly from the micro-pulverizer into the combustion chamber.

Smith, William C. (Morgantown, WV); Paulson, Leland E. (Morgantown, WV)

1995-01-01T23:59:59.000Z

180

Coal-fired power generation: Proven technologies and pollution control systems  

SciTech Connect (OSTI)

During the last two decades, significant advances have been made in the reduction of emissions from coal-fired power generating plants. New technologies include better understanding of the fundamentals of the formation and destruction of criteria pollutants in combustion processes (low nitrogen oxides burners) and improved methods for separating criteria pollutants from stack gases (FGD technology), as well as efficiency improvements in power plants (clean coal technologies). Future demand for more environmentally benign electric power, however, will lead to even more stringent controls of pollutants (sulphur dioxide and nitrogen oxides) and greenhouse gases such as carbon dioxide.

Balat, M. [University of Mah, Trabzon (Turkey)

2008-07-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


181

Fires - 1946  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Fires - 1946 Fires - 1946 Nature Bulletin No. 85 September 28, 1946 Forest Preserve District of Cook County Clayton F. Smith, President Roberts Mann, Superintendent of Conservation FIRES - 1946 It happens every fall. Thousands of acres of vacant land are being burned-off: some of them because of matches, cigarettes or pipe dottle carelessly tossed aside along the highways and along the trails; some of them set afire by thoughtless boys; most of them deliberately burned by people who believe they will improve the crop of grass next year. That is stupid. And if you start a fire which burns over another person's property you are liable to arrest and heavy penalty, under the Illinois law, unless you have given that person proper notice of your intention. Fires harm -- they never help. The tough seeds and roots of the worthless grasses and weeds survive a fire but the good nutritious grasses and most wildflowers are killed. Further, all the winter food and cover for birds and other wildlife are destroyed.

182

Engineering development of coal-fired high performance power systems, Phase II and Phase III. Quarter progress report, April 1, 1996--June 30, 1996  

SciTech Connect (OSTI)

Work is presented on the development of a coal-fired high performance power generation system by the year 2000. This report describes the design of the air heater, duct heater, system controls, slag viscosity, and design of a quench zone.

NONE

1996-11-01T23:59:59.000Z

183

A dual fired downdraft gasifier system to produce cleaner gas for power generation: Design, development and performance analysis  

Science Journals Connector (OSTI)

Abstract The existing biomass gasifier systems have several technical challenges, which need to be addressed. They are reduction of impurities in the gas, increasing the reliability of the system, easy in operation and maintenance. It is also essential to have a simple design of gasifier system for power generation, which can work even in remote locations. A dual fired downdraft gasifier system was designed to produce clean gas from biomass fuel, used for electricity generation. This system is proposed to overcome a number of technical challenges. The system is equipped with dry gas cleaning and indirect gas cooling equipment. The dry gas cleaning system completely eliminates wet scrubbers that require large quantities of water. It also helps to do away with the disposal issues with the polluted water. With the improved gasifier system, the tar level in the raw gas is less than 100mgNm?3.Cold gas efficiency has improved to 89% by complete gasification of biomass and recycling of waste heat into the reactor. Several parameters, which are considered in the design and development of the reactors, are presented in detail with their performance indicators.

P. Raman; N.K. Ram; Ruchi Gupta

2013-01-01T23:59:59.000Z

184

FIRE PROTECTION IMPAIRMENTS University Fire Marshal  

E-Print Network [OSTI]

FIRE PROTECTION IMPAIRMENTS University Fire Marshal Guidance Document Approved by: R. Flynn Last revised by: R. Flynn Revision date: 08/18/2012 Fire Protection Impairments Page 1 of 1 This document contains excerpts from the Fire Code of New York State that pertain to the impairment of a fire protection

Pawlowski, Wojtek

185

Wireless Short Range Communication Technologies for Home Automation.  

E-Print Network [OSTI]

?? A modern home contains varieties of electronic equipment and systems like: TV, Hi-fi equipment, central heating systems, fire alarm systems, security alarm systems, lighting (more)

Oyekunle, Abiola Taiwo

2008-01-01T23:59:59.000Z

186

Solar heating and domestic hot water system installed at Kansas City, Fire Station, Kansas City, Missouri. Final report  

SciTech Connect (OSTI)

This document is the final report of the solar energy heating and hot water system installed at the Kansas City Fire Station, Number 24, 2309 Hardesty Street, Kansas City, Missouri. The solar system was designed to provide 47 percent of the space heating, 8800 square feet area and 75 percent of the domestic hot water (DHW) load. The solar system consists of 2808 square feet of Solaron, model 2001, air, flat plate collector subsystem, a concrete box storage subsystem which contains 1428 cubic feet of 1/2 inch diameter pebbles weighing 71 1/2 tons, a DHW preheat tank, blowers, pumps, heat exchangers, air ducting, controls and associated plumbing. Two 120-gallon electric DHW heaters supply domestic hot water which is preheated by the solar system. Auxiliary space heating is provided by three electric heat pumps with electric resistance heaters and four 30-kilowatt electric unit heaters. There are six modes of system operation. This project is part of the Department of Energy PON-1 Solar Demonstration Program with DOE cost sharing $154,282 of the $174,372 solar system cost. The Final Design Review was held March 1977, the system became operational March 1979 and acceptance test was completed in September 1979.

None

1980-07-01T23:59:59.000Z

187

Fire protection program fiscal year 1997 site support program plan - Hanford fire department  

SciTech Connect (OSTI)

The mission of the Hanford Fires Department (HFD) is to support the safe and timely cleanup of the Hanford Site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating situations which could threaten the operations, employees, or interest of the US Department of Energy operated Hanford Site. this includes response to surrounding fire department districts under mutual aids agreements and contractual fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System) and various commercial entities operating on site. the fire department also provides site fire marshal overview authority, fire system testing, and maintenance, respiratory protection services, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention and education.

Good, D.E., Westinghouse Hanford

1996-07-01T23:59:59.000Z

188

Fire Protection Program fiscal year 1996, site support program plan Hanford Fire Department. Revision 2  

SciTech Connect (OSTI)

The mission of the Hanford Fire Department (HFD) is to support the safe and timely cleanup of the Hanford site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating emergency situations which could threaten the operations, employees, or interest of the US Department of Energy operated Hanford Site. This includes response to surrounding fire departments/districts under a mutual aid agreement and contractual fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System). The fire department also provides site fire marshal overview authority, fire system testing and maintenance, self-contained breathing apparatus maintenance, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention education. This report gives a program overview, technical program baselines, and cost and schedule baseline.

Good, D.E.

1995-09-01T23:59:59.000Z

189

Fire protection program fiscal year 1995 site support program plan, Hanford Fire Department  

SciTech Connect (OSTI)

The mission of the Hanford Fire Department (HFD) is to support the safe and timely cleanup of the Hanford site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating emergency situations which could threaten the operations, employees, or interest of the US Department of Energy operated Hanford Site. This includes response to surrounding fire departments/districts under a mutual aid agreement and contractual fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System). The fire department also provides site fire marshal overview authority, fire system testing and maintenance, self-contained breathing apparatus maintenance, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention education. This report describes the specific responsibilities and programs that the HFD must support and the estimated cost of this support for FY1995.

Good, D.E.

1994-09-01T23:59:59.000Z

190

DEVELOPMENT OF FINE PARTICULATE EMISSION FACTORS AND SPECIATION PROFILES FOR OIL AND GAS FIRED COMBUSTION SYSTEMS  

SciTech Connect (OSTI)

This report provides results from the second year of this three-year project to develop dilution measurement technology for characterizing PM2.5 (particles with aerodynamic diameter smaller than 2.5 micrometers) and precursor emissions from stationary combustion sources used in oil, gas and power generation operation. Detailed emission rate and chemical speciation tests results for a gas turbine, a process heater, and a commercial oil/gas fired boiler are presented. Tests were performed using a research dilution sampling apparatus and traditional EPA methods. A series of pilot tests were conducted to identify the constraints to reduce the size of current research dilution sampler for future stack emission tests. Based on the test results, a bench prototype compact dilution sampler developed and characterized in GE EER in August 2002.

Glenn England; Oliver Chang; Stephanie Wien

2002-02-14T23:59:59.000Z

191

Coal-fired high performance power generating system. Quarterly progress report, October 1, 1994--December 31, 1994  

SciTech Connect (OSTI)

This report covers work carried out under Task 3, Preliminary R and D, under contract DE-AC22-92PC91155, {open_quotes}Engineering Development of a Coal-Fired High Performance Power Generation System{close_quotes} between DOE Pittsburgh Energy Technology Center and United Technologies Research Center. The goals of the program are to develop a coal-fired high performance power generation system (HIPPS) by the year 2000 that is capable of (1) > 47% thermal efficiency; (2) NO{sub x}, SO{sub x} and particulates {<=}25% NSPS; (3) cost {>=}65% of heat input; (4) all solid wastes benign. In our design consideration, we have tried to render all waste streams benign and if possible convert them to a commercial product. It appears that vitrified slag has commercial values. If the flyash is reinjected through the furnace, along with the dry bottom ash, then the amount of the less valuable solid waste stream (ash) can be minimized. A limitation on this procedure arises if it results in the buildup of toxic metal concentrations in either the slag, the flyash or other APCD components. We have assembled analytical tools to describe the progress of specific toxic metals in our system. The outline of the analytical procedure is presented in the first section of this report. The strengths and corrosion resistance of five candidate refractories have been studied in this quarter. Some of the results are presented and compared for selected preparation conditions (mixing, drying time and drying temperatures). A 100 hour pilot-scale stagging combustor test of the prototype radiant panel is being planned. Several potential refractory brick materials are under review and five will be selected for the first 100 hour test. The design of the prototype panel is presented along with some of the test requirements.

NONE

1995-08-01T23:59:59.000Z

192

Fire Protection  

Broader source: Energy.gov (indexed) [DOE]

NOT MEASUREMENT NOT MEASUREMENT SENSITIVE DOE-STD-1066-2012 December 2012 _______________ Supersedes DOE-STD-1066-99 DOE STANDARD FIRE PROTECTION U.S. Department of Energy AREA FIRP Washington, DC 20585 DISTRIBUTION STATEMENT. Approved for public release; distribution is unlimited. This document is available on the Department of Energy Technical Standards Program Web page at http://www.hss.doe.gov/nuclearsafety/ns/techstds/ DOE-STD-1066-2012 FOREWORD This Department of Energy (DOE) Standard (STD) supersedes DOE-STD-1066-99 1 and is approved for use by DOE and its contractors. The following fire protection standard is canceled with the issuance of this Standard and appropriate technical content was incorporated into this Standard:  DOE-STD-1088-95, Fire Protection for Relocatable Structures

193

A PC-Based Information System for the Management and Modelling of Subsurface Coal Fires in Mining Areas (Coalman)  

Science Journals Connector (OSTI)

COALMAN is a coal-fire monitoring and management software, which was... http://www.itc.nl/ILWIS for the GIS and remote sensing functions. It comprises of... ...

Zoltn Vekerdy

2002-01-01T23:59:59.000Z

194

Emission reduction of NOx and CO by optimization of the automatic control system in a coal-fired stoker boiler  

SciTech Connect (OSTI)

To date research on NO, and CO emission reduction in stoker-fired boilers has been devoted to combustion modification to the overfire air, diverting air to a selected set of burners, using modified low-NOx, burners, using flue gas recirculation or flue gas treatment with specially controlled catalyst and additives. This study introduces a concept that focuses on the dynamics of the boiler and the automatic control system. The objective of this study was to reduce the NO and CO emissions by restructuring the automatic control system and then tuning the control system with parameters that have been optimized with emission reduction as the objective. Dynamic data were obtained from a step-input test of either the underfire air or the overfire air. These data were used to model the boiler with a transfer function describing the emissions. The analyzer dynamic response was included in the overall model. The control parameters were determined from this overall emissions transfer function by mathematical optimization. These control parameters constituted the initial values in the automatic control system used for the final tests in the boiler. Additional adjustments to reduce the emissions were carried out during boiler operation. A low controller gain and a fast reset time were found to be the most suitable setting for the control system. The NO emissions controlled by the overfire air and CO emissions controlled by the underfire air produced the best results.

Schnelle, K.B.; Laungphairojana, A.; Debelak, K.A. [Vanderbilt University, Nashville, TN (United States). Dept. of Chemical Engineering

2006-07-15T23:59:59.000Z

195

Fire Protection Account Request Form  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection System Account Request Form Fire Protection System Account Request Form To obtain a user id and password to access the Fire Protection system, please complete the form, save the file and email it to hssUserSupport@hq.doe.gov or print and fax it to 301-903-9823. We will provide a username and password to new account holders. Please allow several business days to process your account request. When your request is approved, you will be contacted with your

196

Enhancing Carbon Reactivity in Mercury Control in Lignite-Fired Systems  

SciTech Connect (OSTI)

This project was awarded through the U.S. Department of Energy (DOE) National Energy Technology Laboratory Program Solicitation DE-PS26-03NT41718-01. The Energy & Environmental Research Center (EERC) led a consortium-based effort to resolve mercury (Hg) control issues facing the lignite industry. The EERC team-the Electric Power Research Institute (EPRI); the URS Corporation; the Babcock & Wilcox Company; ADA-ES; Apogee; Basin Electric Power Cooperative; Otter Tail Power Company; Great River Energy; Texas Utilities; Montana-Dakota Utilities Co.; Minnkota Power Cooperative, Inc.; BNI Coal Ltd.; Dakota Westmoreland Corporation; the North American Coal Corporation; SaskPower; and the North Dakota Industrial Commission-demonstrated technologies that substantially enhanced the effectiveness of carbon sorbents to remove Hg from western fuel combustion gases and achieve a high level ({ge} 55% Hg removal) of cost-effective control. The results of this effort are applicable to virtually all utilities burning lignite and subbituminous coals in the United States and Canada. The enhancement processes were previously proven in pilot-scale and limited full-scale tests. Additional optimization testing continues on these enhancements. These four units included three lignite-fired units: Leland Olds Station Unit 1 (LOS1) and Stanton Station Unit 10 (SS10) near Stanton and Antelope Valley Station Unit 1 (AVS1) near Beulah and a subbituminous Powder River Basin (PRB)-fired unit: Stanton Station Unit 1 (SS1). This project was one of three conducted by the consortium under the DOE mercury program to systematically test Hg control technologies available for utilities burning lignite. The overall objective of the three projects was to field-test and verify options that may be applied cost-effectively by the lignite industry to reduce Hg emissions. The EERC, URS, and other team members tested sorbent injection technologies for plants equipped with electrostatic precipitators (ESPs) and spray dryer absorbers combined with fabric filters (SDAs-FFs). The work focused on technology commercialization by involving industry and emphasizing the communication of results to vendors and utilities throughout the project.

Chad Wocken; Michael Holmes; John Pavlish; Jeffrey Thompson; Katie Brandt; Brandon Pavlish; Dennis Laudal; Kevin Galbreath; Michelle Olderbak

2008-06-30T23:59:59.000Z

197

Applications of Living Fire PRA models to Fire Protection Significance Determination Process in Taiwan  

SciTech Connect (OSTI)

The living fire probabilistic risk assessment (PRA) models for all three operating nuclear power plants (NPPs) in Taiwan had been established in December 2000. In that study, a scenario-based PRA approach was adopted to systematically evaluate the fire and smoke hazards and associated risks. Using these fire PRA models developed, a risk-informed application project had also been completed in December 2002 for the evaluation of cable-tray fire-barrier wrapping exemption. This paper presents a new application of the fire PRA models to fire protection issues using the fire protection significance determination process (FP SDP). The fire protection issues studied may involve the selection of appropriate compensatory measures during the period when an automatic fire detection or suppression system in a safety-related fire zone becomes inoperable. The compensatory measure can either be a 24-hour fire watch or an hourly fire patrol. The living fire PRA models were used to estimate the increase in risk associated with the fire protection issue in terms of changes in core damage frequency (CDF) and large early release frequency (LERF). In compliance with SDP at-power and the acceptance guidelines specified in RG 1.174, the fire protection issues in question can be grouped into four categories; red, yellow, white and green, in accordance with the guidelines developed for FD SDP. A 24-hour fire watch is suggested only required for the yellow condition, while an hourly fire patrol may be adopted for the white condition. More limiting requirement is suggested for the red condition, but no special consideration is needed for the green condition. For the calculation of risk measures, risk impacts from any additional fire scenarios that may have been introduced, as well as more severe initiating events and fire damages that may accompany the fire protection issue should be considered carefully. Examples are presented in this paper to illustrate the evaluation process. (authors)

De-Cheng, Chen; Chung-Kung, Lo; Tsu-Jen, Lin; Ching-Hui, Wu [Institute of Nuclear Energy Research, P. O. Box 3-3, Lung-Tan, Tao-Yuan Taiwan (China); Lin, James C. [ABSG Consulting Inc., 300 Commerce Drive, Suite 200, Irvine, CA 92602 (United States)

2004-07-01T23:59:59.000Z

198

Evaluation of coverage of enriched UF{sub 6} cylinder storage lots by existing criticality accident alarms  

SciTech Connect (OSTI)

The Portsmouth Gaseous Diffusion Plant (PORTS) is leased from the US Department of Energy (DOE) by the United States Enrichment Corporation (USEC), a government corporation formed in 1993. PORTS is in transition from regulation by DOE to regulation by the Nuclear Regulatory Commission (NRC). One regulation is 10 CFR Part 76.89, which requires that criticality alarm systems be provided for the site. PORTS originally installed criticality accident alarm systems in all building for which nuclear criticality accidents were credible. Currently, however, alarm systems are not installed in the enriched uranium hexafluoride (UF{sub 6}) cylinder storage lots. This report analyzes and documents the extent to which enriched UF{sub 6} cylinder storage lots at PORTS are covered by criticality detectors and alarms currently installed in adjacent buildings. Monte Carlo calculations are performed on simplified models of the cylinder storage lots and adjacent buildings. The storage lots modelled are X-745B, X-745C, X745D, X-745E, and X-745F. The criticality detectors modelled are located in building X-343, the building X-344A/X-342A complex, and portions of building X-330. These criticality detectors are those located closest to the cylinder storage lots. Results of this analysis indicate that the existing criticality detectors currently installed at PORTS are largely ineffective in detecting neutron radiation from criticality accidents in most of the cylinder storage lots at PORTS, except sometimes along portions of their peripheries.

Lee, B.L. Jr.; Dobelbower, M.C.; Woollard, J.E.; Sutherland, P.J.; Tayloe, R.W. Jr.

1995-03-01T23:59:59.000Z

199

Institutional project summary University of Redlands direct fired gas absorption chiller system  

SciTech Connect (OSTI)

The University of Redlands, located in the California Inland Empire City of Redlands supplies six campus building with chilled and hot water for cooling and space heating from a centrally located Mechanical Center. The University was interested in lowering chilled water production costs and eliminating Ozone depleting chloroflourocarbon (CFC) refrigerants in addition to adding chiller capacity for future building to be added to the central plant piping {open_quotes}loop{close_quotes}. After initially providing a feasibility study of chiller addition alternatives and annual hourly load models, GRT & Associates, Inc. (GRT) provided design engineering for the installation of a 500 Ton direct gas fired absorption chiller addition to the University of Redland`s mechanical center. Based on the feasibility study and energy consumption tests done after the new absorption chiller was added, the university estimates annual energy cost saving versus the existing electric chiller is approximately $65,000 per year. Using actual construction costs, the simple before tax payback period for the project is six years.

Tanner, G.R.

1996-05-01T23:59:59.000Z

200

Rawls' Fairness, Income Distribution and Alarming Level of Gini Coefficient  

E-Print Network [OSTI]

The argument that the alarming level of Gini coefficient is 0.4 is very popular, especially in the media industry, all around the world for a long time. Although the 0.4 standard is widely accepted, the derivation of the value lacks rigid theoretical foundations. In fact, to the best of our knowledge, it is not based on any prevalent and convincing economic theories. In this paper, we incorporate Rawls' principle of fair equality of opportunity into Arrow-Debreu's framework of general equilibrium theory with heterogeneous agents, and derive the alarming level of Gini coefficient formally. Our theory reveals that the exponential distribution of income not only satisfies Pareto optimality, but also obeys social fairness in Rawls' sense. Therefore, we specify the maximal value of the Gini coefficient when income follows exponential distribution as a possible alarming level. Our computations show that the alarming level should be specified at least equal or larger than 0.5 rather than 0.4. We empirically investig...

Tao, Yong; Li, Changshuai

2014-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


201

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network [OSTI]

the Authoritarian Model: How Putin?s Crackdown Holds RussiaAuthoritarianism Under Putin, Demokratizatsiya: The Journal

Hart, Melanie M.

2010-01-01T23:59:59.000Z

202

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network [OSTI]

Wang?s factory was burning hazardous waste materials, China?waste materials, not the more stringent standards for factories burning (

Hart, Melanie M.

2010-01-01T23:59:59.000Z

203

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network [OSTI]

and standards for heavy metal pollution. The MEP passed aHandling of Heavy Metal Pollution on August 28, 2009.

Hart, Melanie M.

2010-01-01T23:59:59.000Z

204

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network [OSTI]

Hygiene] Law and cause food poisoning accidents or otherFood and Drug Administration (SFDA) traces the poisonouspoisonings were most likely a macro-level issue stemming from a wide variety of sources such as contaminated food,

Hart, Melanie M.

2010-01-01T23:59:59.000Z

205

China's post-reform policy implementation gaps and governmental vs. non-governmental fire alarm solutions  

E-Print Network [OSTI]

Ibid. Walker (2008). planned hydropower projects in Yunnanlands are expropriated for hydropower developments. In 2004to lose their lands for a hydropower project on the Nujiang

Hart, Melanie M.

2010-01-01T23:59:59.000Z

206

Trottier BuildingTrottier Building Fire SafetyFire Safety  

E-Print Network [OSTI]

building 1.1. Fire SafetyFire Safety 2.2. Fire Protection equipmentFire Protection equipment 3 OfficersFire Prevention Officers #12;Trottier BuildingTrottier Building Fire ProtectionFire Protection#12;Trottier BuildingTrottier Building Fire SafetyFire Safety in Trottier buildingin Trottier

Pientka, Brigitte

207

CONSTRUCTION ALERT Additional Notice to Ongoing Project  

E-Print Network [OSTI]

-541-510 CONTRACTOR: Circuit Builders Inc. SCOPE OF WORK: Testing of the new fire alarm system DURATION OF PROJECT Operations, Campus Security, and Fire Safety. SUBJECT: Bachman Hall Replace Fire Alarm System UHM 09

208

Thermodynamic analysis of a low-pressure economizer based waste heat recovery system for a coal-fired power plant  

Science Journals Connector (OSTI)

Abstract An LPE (low-pressure economizer) based waste heat recovery system for a CFPP (coal-fired power plant) is investigated thermodynamically. With the installation of LPE in the flue before the FGD (flue gas desulfurizer), the heat contained in the exhaust flue gas can be recovered effectively and the water consumption can be reduced in the FGD resulted from the temperature dropped flue gas. The impacts on the related apparatuses after installing LPE in a CFPP are analyzed and the internal relationships among correlated parameters are presented. The efficiencies of LPE installed in a CFPP evaluated by the first law, the second law and the thermal equilibrium efficiencies are also compared and analyzed. A detailed case study based on a 350MW CFPP unit is presented and the variations of the thermal performance after the installation of LPE are investigated. The results show that the second law and the thermal equilibrium efficiencies are increased which can be indicators to evaluate the performance of the LPE system while the first law efficiency is decreased after installing LPE. Results also show that the saving of SCE (standard coal equivalent) is 3.85g/(kWh) for this CFPP unit under full load after installing LPE.

Chaojun Wang; Boshu He; Linbo Yan; Xiaohui Pei; Shinan Chen

2014-01-01T23:59:59.000Z

209

Advanced Turbine Systems Program conceptual design and product development. Task 3.0, Selection of natural gas-fired Advanced Turbine System  

SciTech Connect (OSTI)

This report presents results of Task 3 of the Westinghouse ATS Phase II program. Objective of Task 3 was to analyze and evaluate different cycles for the natural gas-fired Advanced Turbine Systems in order to select one that would achieve all ATS program goals. About 50 cycles (5 main types) were evaluated on basis of plant efficiency, emissions, cost of electricity, reliability-availability-maintainability (RAM), and program schedule requirements. The advanced combined cycle was selected for the ATS plant; it will incorporate an advanced gas turbine engine as well as improvements in the bottoming cycle and generator. Cost and RAM analyses were carried out on 6 selected cycle configurations and compared to the baseline plant. Issues critical to the Advanced Combined Cycle are discussed; achievement of plant efficiency and cost of electricity goals will require higher firing temperatures and minimized cooling of hot end components, necessitating new aloys/materials/coatings. Studies will be required in combustion, aerodynamic design, cooling design, leakage control, etc.

NONE

1994-12-01T23:59:59.000Z

210

Annual Fire Safety Report  

E-Print Network [OSTI]

2010 Annual Fire Safety Report University of California, Irvine HIGHER EDUCATION OPPORTUNITY to the Fire Safety in Student Housing Buildings of current or perspective students and employees be reported publish an annual fire safety report, keep a fire log, and report fire statistics to the Secretary

Loudon, Catherine

211

Fire Safety January 2011  

E-Print Network [OSTI]

1 Fire Safety PROCEDURES January 2011 firesafety@uwo.ca Campus Phones ­ EMERGENCY ­ Dial 911 Fire Safety Service is the focal point for the coordinated administration of the University Fire Safety Prevention and Fire Safety to minimize the risk of injury or loss of life or property due to fire

Lennard, William N.

212

Tracking New Coal-Fired Power Plants  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

January 8, 2010 National Energy Technology Laboratory Office of Systems Analyses and Planning Erik Shuster 2 Tracking New Coal-Fired Power Plants This report is intended to...

213

Load Preheating Using Flue Gases from a Fuel-Fired Heating System  

Broader source: Energy.gov [DOE]

This tip sheet discusses how the thermal efficiency of a process heating system can be improved significantly by using heat contained in furnace flue gases to preheat the furnace load.

214

Eliminating air heater plugging and corrosion caused by SCR/SNCR systems for NOx control on coal-fired boilers  

SciTech Connect (OSTI)

In a typical coal-fired power plant the rotary regenerative air heater is responsible for 5-10% of the boiler's total efficiency. The three biggest threats to air heater performance deterioration are corrosion of the heat exchange surfaces, plugging, and air heater leakage through the seals. The article concentrates on the vastly increased level of corrosion and plugging issues associated with installing selective catalytic reduction (SCR) and selective non-catalytic reduction (SNCR) systems for controlling nitrogen oxide emissions. Some injected ammonia in the SCR process reacts with SO{sub 2} to form ammonium sulphate and bisulphate (ABS) which is deposited on the air heater element surfaces. This can be overcome by applying coatings, using corrosion-resistant steels, reconfiguring the air heaters to a two layer design, improving air heater blowers, improving technologies for removing ammonia 'slip' before it enters the air heater, and using new catalysts that reduce the oxidation of SO{sub 2} to SO{sub 3}. 4 figs.

Guffre, J. [Paragon Airheater Technologies (United States)

2007-10-15T23:59:59.000Z

215

Preventing Laboratory FiresPreventing Laboratory Fires AgendaAgenda  

E-Print Network [OSTI]

.contents. #12;Laboratory Fire CodeLaboratory Fire Code RegulationsRegulations #12;National Fire ProtectionNational Fire Protection Association (NFPA)Association (NFPA) NFPA 1NFPA 1 ­­ General Protection against FireGeneral Protection against Fire NFPA 10NFPA 10 ­­ Fire ExtinguishersFire Extinguishers NFPA 30NFPA 30 ­­ Flammable

Farritor, Shane

216

Oxy-fuel combustion systems for pollution free coal fired power generation  

SciTech Connect (OSTI)

Jupiter Oxygen's patented oxy-fuel combustion systems1 are capable of economically generating power from coal with ultra-low emissions and increased boiler efficiency. Jupiter's system uses pure oxygen as the combustion agent, excluding air and thus nitrogen, concentrating CO2 and pollutants for efficient capture with near zero NOx production, reducing exhaust mass flow, and increasing radiant heat transfer. Flue-gas recirculation rates can be varied to add flexibility to new boiler designs using this technology. Computer modeling and thermal analysis have identified important design considerations in retrofit applications.

Ochs, Thomas L.; Oryshchyn, Danylo B.; Gross, Dietrich (Jupiter Oxygen Corp.); Patrick, Brian (Jupiter Oxygen Corp.); Gross, Alex (Jupiter Oxygen Corp.); Dogan, Cindy; Summers, Cathy A.; Simmons, William (CoalTeck LLC); Schoenfeld, Mark (Jupiter Oxygen Corp.)

2004-01-01T23:59:59.000Z

217

Fire Safety Training: Fire Modeling- NUREG 1934  

Broader source: Energy.gov [DOE]

Presenter: Frederick W. Mowrer, Ph.D., P.E. Director Fire Protection Engineering Programs - Cal Poly SLO

218

Stone Fire  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Effect of Change in Cookstove Types on Visibility - Case Study of the Berkeley-Darfur Stove and Three- Stone Fire Extended Abstract #1 Yungang Wang, Ashok J. Gadgil, Thomas W. Kirchstetter Environmental Energy Technologies Division Indoor Environment Group Lawrence Berkeley National Laboratory Berkeley, CA September 2012 This publication was made possible by grant number 500-99-013 from the California Energy Commission (CEC). This work was also supported by the Assistant Secretary for Energy Efficiency and Renewable Energy, Building Technologies Program of the U.S. Department of Energy under contract DE- AC02- 05CH11231. LBNL-6291E LBNL-6291E Disclaimer This document was prepared as an account of work sponsored by the United States

219

FIRE PROTECTION ENGINEERING  

E-Print Network [OSTI]

FIRE PROTECTION ENGINEERING FPE College of Engineering California Polytechnic State University San problems and develop fire safety design solutions in a variety of professional settings. Fire Protection Engineering Science � Apply concepts associated with the thermal sciences, to the analysis of fire protection

Sze, Lawrence

220

FIRE PROTECTION ENGINEERING  

E-Print Network [OSTI]

FIRE PROTECTION ENGINEERING FPE College of Engineering California Polytechnic State University San and develop fire safety design solutions in a variety of professional settings. Fire Protection Engineering Science · Apply concepts associated with the thermal sciences, to the analysis of fire protection

Sze, Lawrence

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


221

The Importance of Technical Reachback in the Adjudication of Radiation Alarms  

SciTech Connect (OSTI)

The large-scale deployment of radiation sensors at borders, ports-of-entry and other locations carries two disparate priorities: the reliable detection and identification of threat materials and the rapid characterization of non-threat materials comprised of naturally occurring radioactive materials (NORM) and legitimate radioactive materials in streams of commerce. These priorities are partially achieved through the technologies contained in the detection systems and the procedures developed for their operation. However, questions and ambiguities will occur. Without established capabilities and procedures for the operators of these detector systems to 'reach back' to trained spectroscopists and appropriate subject matter experts, the system will likely experience an unacceptable number of response operations and delays resolving alarms. Technical reachback operations need to be able to address the priorities discussed above while causing minimal perturbations in the flow of legitimate streams of commerce. Yet when necessary, reachback needs to be able to rapidly mobilize the appropriate response assets.

Buckley, W M; Allen, R W

2009-03-18T23:59:59.000Z

222

DOE Standard: Fire protection design criteria  

SciTech Connect (OSTI)

The development of this Standard reflects the fact that national consensus standards and other design criteria do not comprehensively or, in some cases, adequately address fire protection issues at DOE facilities. This Standard provides supplemental fire protection guidance applicable to the design and construction of DOE facilities and site features (such as water distribution systems) that are also provided for fire protection. It is intended to be used in conjunction with the applicable building code, National Fire Protection Association (NFPA) Codes and Standards, and any other applicable DOE construction criteria. This Standard replaces certain mandatory fire protection requirements that were formerly in DOE 5480.7A, ``Fire Protection``, and DOE 6430.1A, ``General Design Criteria``. It also contains the fire protection guidelines from two (now canceled) draft standards: ``Glove Box Fire Protection`` and ``Filter Plenum Fire Protection``. (Note: This Standard does not supersede the requirements of DOE 5480.7A and DOE 6430.1A where these DOE Orders are currently applicable under existing contracts.) This Standard, along with the criteria delineated in Section 3, constitutes the basic criteria for satisfying DOE fire and life safety objectives for the design and construction or renovation of DOE facilities.

Not Available

1999-07-01T23:59:59.000Z

223

Boilers and Fired Systems  

SciTech Connect (OSTI)

This chapter examines how energy is consumed, how energy is wasted, and opportunities for reducing energy consumption and costs in the operation of boilers.

Parker, Steven A.; Scollon, R. B.

2009-07-14T23:59:59.000Z

224

Simulation study on lignite-fired power system integrated with flue gas drying and waste heat recovery Performances under variable power loads coupled with off-design parameters  

Science Journals Connector (OSTI)

Abstract Lignite is a kind of low rank coal with high moisture content and low net heating value, which is mainly used for electric power generation. However, the thermal efficiency of power plants firing lignite directly is very low. Pre-drying is a proactive option, dehydrating raw lignite to raise its heating value, to improve the power plant thermal efficiency. A pre-dried lignite-fired power system integrated with boiler flue gas drying and waste heat recovery was proposed in this paper. The plant thermal efficiency could be improved by 1.51% at benchmark condition due to pre-drying and waste heat recovery. The main system performances under variable power loads were simulated and analyzed. Simulation results show that the improvement of plant thermal efficiency reduced to 1.36% at 50% full load. Moreover, the influences of drying system off-design parameters were simulated coupled with power loads. The variation tendencies of main system parameters were obtained. The influence of pre-drying degree (including moisture content of pre-dried lignite and raw lignite) on the plant thermal efficiency diminishes gradually with the decreasing power load. The dryer thermal efficiency and dryer exhaust temperature are also main factors and the influences on system parameters have been quantitatively analyzed.

Xiaoqu Han; Ming Liu; Jinshi Wang; Junjie Yan; Jiping Liu; Feng Xiao

2014-01-01T23:59:59.000Z

225

E-Print Network 3.0 - alarm processing techniques Sample Search...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

TASA Summary: relationships of the alarms into account. 2.2. TASA methodology A KDD process, adapted from 11, consists of: 1... Interactive exploration of interesting...

226

Testing and Evaluation Protocol for Alarming Personal Radiation Detectors for Homeland Security  

E-Print Network [OSTI]

Testing and Evaluation Protocol for Alarming Personal Radiation Detectors for Homeland Security T................................................................................1 4. Test and evaluation steps .........................................................................................1 5. Recording test results

227

Quantifying the role of fire in the Earth system - Part 2: Impact on the net carbon balance of global terrestrial ecosystems for the 20th century  

SciTech Connect (OSTI)

Fire is the primary terrestrial ecosystem disturbance agent on a global scale. It affects carbon balance of global terrestrial ecosystems by emitting carbon to atmosphere directly and immediately from biomass burning (i.e., fire direct effect), and by changing net ecosystem productivity and land-use carbon loss in post-fire regions due to biomass burning and fire-induced vegetation mortality (i.e., fire indirect effect). Here, we provide the first quantitative assessment about the impact of fire on the net carbon balance of global terrestrial ecosystems for the 20th century, and investigate the roles of fire direct and indirect effects. This study is done by quantifying the difference between the 20th century fire-on and fire-off simulations with NCAR community land model CLM4.5 as the model platform. Results show that fire decreases net carbon gain of the global terrestrial ecosystems by 1.0 Pg C yr-1 average across the 20th century, as a results of fire direct effect (1.9 Pg C yr-1) partly offset by indirect effect (-0.9 Pg C yr-1). Fire generally decreases the average carbon gains of terrestrial ecosystems in post-fire regions, which are significant over tropical savannas and part of forests in North America and the east of Asia. The general decrease of carbon gains in post-fire regions is because fire direct and indirect effects have similar spatial patterns and the former (to decrease carbon gain) is generally stronger. Moreover, the effect of fire on net carbon balance significantly declines prior to ~1970 with trend of 8 Tg C yr-1 due to increasing fire indirect effect and increases afterward with trend of 18 Tg C yr-1 due to increasing fire direct effect.

Li, Fang; Bond-Lamberty, Benjamin; Levis, Samuel

2014-03-07T23:59:59.000Z

228

Development of a Low NOx Burner System for Coal Fired Power Plants Using Coal and Biomass Blends  

E-Print Network [OSTI]

.................................................................................... 36 Figure 19 Result of Combustion Performance Tests after Retrofits of Thermal Power Plant IN in Finland Consisting of Four 265 MW Pulverized Coal-Fired Boilers... on to include the International Energy Agency Bioenergy Task 32 group?s draft position paper that indicates cofiring represents among the lowest risk, least expensive, most efficient, and shortest term options for renewable-based electrical power generation...

Gomez, Patsky O.

2010-01-16T23:59:59.000Z

229

Fire Protection Program  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Program Program Fire Protection Overview The Department of Energy (DOE) Fire Protection Program is multi-faceted. It includes published fire safety directives (Orders, standards, and guidance documents), a range of oversight activities, an annual fire protection program summary, and a directory of fire safety professionals. DOE also sponsors fire safety conferences, various training initiatives, and a spectrum of technical assistance activities. This Home Page is intended to bring together in one location as much of the Program's resources as possible to facilitate greater understanding, communication, and efficiency of operations. Guidelines -- NFPA Codes and standards, CFRs, and DOE Directives (policy statements, Orders, Standards, and Guidance Documents)

230

Economic analysis of amine based carbon dioxide capture system with bi-pressure stripper in supercritical coal-fired power plant  

Science Journals Connector (OSTI)

Post-combustion CO2 capture and storage is among the most mature technologies to capture, compress, transport and store CO2 from flue gas in coal-fired power plant. This paper presents the simulation of monoethanolamine (MEA) based CO2 capture and compression process integrated within a 600MWe supercritical coal-fired power plant using chemical process simulators. Comparison between bi-pressure stripper and single-pressure stripper reveals that improved CO2 capture system with bi-pressure stripper minimizes energy penalty of CO2 capture and compression by up to 6.3% at full unit load. The study also explores optimization of some important process parameters affecting the performance of coal-fired power plant by taking into account both CO2 capture process and CO2 compression at full unit load. These parameters include operating stripper pressure, CO2 capture efficiency and steam extraction location. Results show that the optimal stripper pressure is within the range of 1.92.1bar and feasible CO2 capture efficiency is between 60% and 90%. Results also show that low-pressure steam extraction reduces energy penalty. Evaluation of improved CO2 capture system is also performed at part flue gas load ranging from 40% to 90%. The study reveals that operating at part flue gas load, as compared with full load, increases energy penalty of carbon capture. Not only energy penalty but also lean solution flow rate and plant efficiency are studied at different flue load levels in this paper. In addition, results show that bi-pressure stripper configuration is also effective in reducing energy penalty at part unit load.

Haiwen Liang; Zhigao Xu; Fengqi Si

2011-01-01T23:59:59.000Z

231

Project examples Install new HVAC, electrical, fire protection,  

E-Print Network [OSTI]

Project examples Install new HVAC, electrical, fire protection, and plumbing systems in Mechanical. · Totransformthisspaceandincreaseaccessibility, anelevatorisrequired.Currently,Blakelydoesnot haveone. Replace HVAC and electrical system

Blanchette, Robert A.

232

Stochastic Representation of Fire Behavior in a Wildland Fire Protection  

E-Print Network [OSTI]

Stochastic Representation of Fire Behavior in a Wildland Fire Protection Planning Model on wildland fire used by the California Department of Forestry and Fire Protection. Fire rate of spread (ROS. S IMULATIONMODELSOFINITIALATTACKonwildland fireare important tools for wildland fire protection planning, and several new models have been

Fried, Jeremy S.

233

Regulation study for the facility control system design at the Facility Operations Center at TA55  

SciTech Connect (OSTI)

NMT-8 is proposing to upgrade the existing Facility Control System (FCS) located within the Facility Operations Center (FOC) at the TA-55 Plutonium Processing and Handling Facility (PPHF). The FCS modifications will upgrade the existing electronics to provide better reliability of system functions. Changes include replacement of the FCS computers and field multiplex units which are used for transmitting systems data. Data collected at the FCS include temperature, pressure, contact closures, etc., and are used for monitoring and/or control of key systems at TA-55. Monitoring is provided for the electrical power system status, PF-4 HVAC air balance status (Static Differential pressure), HVAC fan system status, site chill water return temperature, fire system information, and radioactive constant air monitors alarm information, site compressed air pressure and other key systems used at TA-55. Control output signals are provided for PF-4 HVAC systems, and selected alarms for criticality, fire, loss of pressure in confinement systems. A detailed description of the FCS modifications is provided in Section 2.

NONE

1994-03-16T23:59:59.000Z

234

Repository Subsurface Preliminary Fire Hazard Analysis  

SciTech Connect (OSTI)

This fire hazard analysis identifies preliminary design and operations features, fire, and explosion hazards, and provides a reasonable basis to establish the design requirements of fire protection systems during development and emplacement phases of the subsurface repository. This document follows the Technical Work Plan (TWP) (CRWMS M&O 2001c) which was prepared in accordance with AP-2.21Q, ''Quality Determinations and Planning for Scientific, Engineering, and Regulatory Compliance Activities''; Attachment 4 of AP-ESH-008, ''Hazards Analysis System''; and AP-3.11Q, ''Technical Reports''. The objective of this report is to establish the requirements that provide for facility nuclear safety and a proper level of personnel safety and property protection from the effects of fire and the adverse effects of fire-extinguishing agents.

Richard C. Logan

2001-07-30T23:59:59.000Z

235

Fire Protection Related Sites  

Broader source: Energy.gov [DOE]

Fire Protection related sites for Department of Energy, Non-DOE Government and Non-Government information.

236

Modeling of integrated environmental control systems for coal-fired power plants. Technical progress report, [June 1, 1989--September 30, 1989  

SciTech Connect (OSTI)

The general goal of this research project is to enhance, and transfer to DOE, a new computer simulation model for analyzing the performance and cost of environmental control systems for coal-fired power plants. Systems utilizing pre-combustion, combustion, or post-combustion control methods, individually or in combination, may be considered. A unique capability of this model is the probabilistic representation of uncertainty in model input parameters. This stochastic simulation capability allows the performance and cost of environmental control systems to be quantified probabilistically, accounting for the interactions among all uncertain process and economic parameters. This method facilitates more rigorous comparisons between conventional and advanced clean coal technologies promising improved cost and/or effectiveness for SO{sub 2} and NO{sub x} removal. Detailed modeling of several pre-combustion and post-combustion processes of interest to DOE/PETC have been selected for analysis as part of this project.

Rubin, E.S.

1989-10-01T23:59:59.000Z

237

Review of the Headquarters Facilities Emergency Response Plans  

Energy Savers [EERE]

this review have comprehensive fire alarm systems that are automatically activated by heat, smoke, or fire suppression system activity or by manual pull stations. Manual pull...

238

System approach to reducing NO{sub x} emissions on a three cell high burner, heavy oil-fired boiler  

SciTech Connect (OSTI)

This paper documents the installation of plug-in low NO{sub x} burners on a utility boiler with cell burners. The original rapid mix burners and typical close burner centerline spacing produced a very hot furnace environment resulting in extremely high NO{sub x} emissions, in this case as high as 1.0 lbs/MMBtu. The unit was a {number_sign}6 oil-fired, 560 MW{sub e} supercritical pressure, three-cell burner boiler at Commonwealth Electric`s Canal Station, Unit {number_sign}1. This paper presents the results including emissions and boiler performance of the retrofit of DB Riley low NO{sub x} STS (Swirl Tertiary Stage) burners. Low NO{sub x} burners were used in conjunction with close-coupled overfire air using existing burner openings. The project reduced NO{sub x} emissions greater than 705 while firing {number_sign}6 oil, and this was accomplished with less than 10% flue gas recirculation.

Green, R.W.; Dorai, X.A. [DB Riley, Inc., Worcester, MA (United States); Hurley, B.A. [Commonwealth Electric Co., Wareham, MA (United States)

1996-11-01T23:59:59.000Z

239

242T FACP replacement  

SciTech Connect (OSTI)

This Acceptance Test Procedure (ATP) has been prepared to demonstrate that the Fire Protection system functions as required by project criteria. This ATP will test the Pyrotronic CP-400 fire alarm control panel (FACP), and interfaces with the radio fire alarm reporting box, alarm/supervisory initiating devices, and alarm indicating appliances. This document is to certify the installation and testing of the fire alarm control panel and all attached devices to insure the Hanford Fire Dept. receives the proper signals. This fire alarm control panel is located in Bldg. 242T in the 200 W Area of Hanford.

Ferry, M.F.

1994-11-17T23:59:59.000Z

240

2707SX FACP replacement  

SciTech Connect (OSTI)

This Acceptance Test Procedure (ATP) has been prepared to demonstrate that the Fire Protection system functions as required by project criteria. This ATP will test the Pyrotronic CP-400 fire alarm control panel (FACP), and interfaces with the radio fire alarm reporting box, alarm/supervisory initiating devices, and alarm indicating appliances. This document is to certify the installation of the fire alarm control panel and all attached devices to insure the Hanford Fire Dept. receives the proper signals. This particular fire alarm control panel services Bldg. 2707SX in the 200W Area of Hanford.

Ferry, M.F.

1994-11-17T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


241

ANNUAL FIRE SAFETY REPORT For Student Housing  

E-Print Network [OSTI]

and in the public areas of each of these 15 halls. The smoke detectors located in Estill Street Complex are battery, emergency lights and fire egress systems. Twenty Eight of the 50 apartments in the Ecovillage, designed

Baltisberger, Jay H.

242

Large-Scale Mercury Control Technology Testing for Lignite-Fired Utilities - Oxidation Systems for Wet FGD  

SciTech Connect (OSTI)

Mercury (Hg) control technologies were evaluated at Minnkota Power Cooperative's Milton R. Young (MRY) Station Unit 2, a 450-MW lignite-fired cyclone unit near Center, North Dakota, and TXU Energy's Monticello Steam Electric Station (MoSES) Unit 3, a 793-MW lignite--Powder River Basin (PRB) subbituminous coal-fired unit near Mt. Pleasant, Texas. A cold-side electrostatic precipitator (ESP) and wet flue gas desulfurization (FGD) scrubber are used at MRY and MoSES for controlling particulate and sulfur dioxide (SO{sub 2}) emissions, respectively. Several approaches for significantly and cost-effectively oxidizing elemental mercury (Hg{sup 0}) in lignite combustion flue gases, followed by capture in an ESP and/or FGD scrubber were evaluated. The project team involved in performing the technical aspects of the project included Babcock & Wilcox, the Energy & Environmental Research Center (EERC), the Electric Power Research Institute, and URS Corporation. Calcium bromide (CaBr{sub 2}), calcium chloride (CaCl{sub 2}), magnesium chloride (MgCl{sub 2}), and a proprietary sorbent enhancement additive (SEA), hereafter referred to as SEA2, were added to the lignite feeds to enhance Hg capture in the ESP and/or wet FGD. In addition, powdered activated carbon (PAC) was injected upstream of the ESP at MRY Unit 2. The work involved establishing Hg concentrations and removal rates across existing ESP and FGD units, determining costs associated with a given Hg removal efficiency, quantifying the balance-of-plant impacts of the control technologies, and facilitating technology commercialization. The primary project goal was to achieve ESP-FGD Hg removal efficiencies of {ge}55% at MRY and MoSES for about a month.

Steven A. Benson; Michael J. Holmes; Donald P. McCollor; Jill M. Mackenzie; Charlene R. Crocker; Lingbu Kong; Kevin C. Galbreath

2007-03-31T23:59:59.000Z

243

Conventional Facilities Chapter 8: Fire Protection 8-1 NSLS-II Preliminary Design Report  

E-Print Network [OSTI]

Conventional Facilities Chapter 8: Fire Protection 8-1 NSLS-II Preliminary Design Report 8 FIRE of New York State National Institute of Standards and Technology National Fire Protection Association, corresponding to the ring pentants. 8.2.2 Fire Protection System #12;8-2 Part 3: Conventional Facilities Scope

Ohta, Shigemi

244

Savannah River Site Waste Solidification Building Corrective Actions from the January 2013 Report on Construction Quality of Mechanical Systems Installation and Fire Protection Design, May 2013  

Broader source: Energy.gov (indexed) [DOE]

HIAR SRS-2013-5-07 HIAR SRS-2013-5-07 Site: Savannah River Site Subject: Office of Enforcement and Oversight's Office of Safety and Emergency Management Evaluations Activity Report for the Savannah River Site (SRS) Waste Solidification Building (WSB) Corrective Actions from the January 2013 Report on Construction Quality of Mechanical Systems Installation and Fire Protection Design Dates of Activity : 05/07/2013 - 05/09/2013 Report Preparer: Joseph Lenahan Activity Description/Purpose: 1. Review the corrective actions being implemented by the construction contractor to address Findings 1-4, 6, and 9 from a construction quality review performed by the Office of Health, Safety and Security (HSS) (Reference 1). 2. Meet with the SRS WSB project staff and Savannah River Nuclear Solutions (SRNS) engineers to discuss the

245

Savannah River Site Waste Solidification Building Corrective Actions from the January 2013 Report on Construction Quality of Mechanical Systems Installation and Fire Protection Design, May 2013  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

HIAR SRS-2013-5-07 HIAR SRS-2013-5-07 Site: Savannah River Site Subject: Office of Enforcement and Oversight's Office of Safety and Emergency Management Evaluations Activity Report for the Savannah River Site (SRS) Waste Solidification Building (WSB) Corrective Actions from the January 2013 Report on Construction Quality of Mechanical Systems Installation and Fire Protection Design Dates of Activity : 05/07/2013 - 05/09/2013 Report Preparer: Joseph Lenahan Activity Description/Purpose: 1. Review the corrective actions being implemented by the construction contractor to address Findings 1-4, 6, and 9 from a construction quality review performed by the Office of Health, Safety and Security (HSS) (Reference 1). 2. Meet with the SRS WSB project staff and Savannah River Nuclear Solutions (SRNS) engineers to discuss the

246

Wildland Fire Management Program  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Significant Wildland Fire Potential Outlook Significant Wildland Fire Potential Outlook Predictive Services National Interagency Fire Center Issued: June 1, 2013 Next Issuance: July 1, 2013 Outlook Period - June, July and August through September Executive Summary The June, July and August through September 2013 significant wildland fire potential forecasts included in this outlook represent the cumulative forecasts of the eleven Geographic Area Predictive Services Units and the National Predictive Services Unit. June - Significant fire potential will be above normal for much of the interior mountains and foothills of California, the Sacramento Valley, and adjacent lower foothills as well as the coastal areas. - Significant fire potential will increase to above normal in Arizona, western New Mexico, and far

247

NREL: Energy Analysis - Natural Gas-Fired Generation Results...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

assessments have shown wide-ranging results. To better understand the greenhouse gas (GHG) emissions from utility-scale, natural gas-fired electricity generation systems (based...

248

NREL: Energy Analysis - Coal-Fired Electricity Generation Results...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

assessments have shown wide-ranging results. To better understand the greenhouse gas (GHG) emissions from utility-scale, coal-fired electricity generation systems (based on...

249

E-Print Network 3.0 - alarming oxygen depletion Sample Search...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

protecting life on Earth (1). In 1985, scientists and the public became alarmed when Farman et al. (2... studies (5-8). These studies showed that ozone depletion has a large...

250

E-Print Network 3.0 - alarm border monitoring Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

deployed at U.S. ports of entry. Due... to the occurrence of nuisance alarms based on naturally occurring radioactive material and the low base rate of nu Source: Parasuraman, Raja...

251

Development of a coal-fired combustion system for industrial process heating applications. Phase 3 final report, November 1992--December 1994  

SciTech Connect (OSTI)

A three phase research and development program has resulted in the development and commercialization of a Cyclone Melting System (CMS{trademark}), capable of being fueled by pulverized coal, natural gas, and other solid, gaseous, or liquid fuels, for the vitrification of industrial wastes. The Phase 3 research effort focused on the development of a process heater system to be used for producing value added glass products from the vitrification of boiler/incinerator ashes and industrial wastes. The primary objective of the Phase 3 project was to develop and integrate all the system components, from fuel through total system controls, and then test the complete system in order to evaluate its potential for successful commercialization. The demonstration test consisted of one test run with a duration of 105 hours, approximately one-half (46 hours) performed with coal as the primary fuel source (70% to 100%), the other half with natural gas. Approximately 50 hours of melting operation were performed vitrifying approximately 50,000 lbs of coal-fired utility boiler flyash/dolomite mixture, producing a fully-reacted vitrified product.

NONE

1995-09-26T23:59:59.000Z

252

FIRE MANAGEMENT PLAN MONTAGUE PLAIN  

E-Print Network [OSTI]

FIRE MANAGEMENT PLAN FOR MONTAGUE PLAIN WILDLIFE MANAGEMENT AREA #12;Fire Management Plan for Montague Plain Wildlife Management Area prepared for Massachusetts Dept. of Fisheries, Wildlife. 2003. Fire Management Plan for Montague Plain Wildlife Management Area. Department of Natural Resources

Schweik, Charles M.

253

H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2013.doc Annual Fire Safety Report  

E-Print Network [OSTI]

and Fire Protection (Cal Fire) responds to the State Response Area of campus, including the outlyingH:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2013.doc Annual Fire Safety #12;H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2013.doc Fire and Life

Sze, Lawrence

254

H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2012.doc Annual Fire Safety Report  

E-Print Network [OSTI]

and Fire Protection (Cal Fire) responds to the State Response Area of campus, including the outlyingH:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2012.doc Annual Fire Safety #12;H:\\Transfer\\My Documents\\Cleary Fire Report\\Annual Fire Safety Report 2012.doc Fire and Life

Sze, Lawrence

255

Fire and Emergency Management Group SLAC-I-730-0A12A-001-R000  

E-Print Network [OSTI]

Fire and Emergency Management Group SLAC-I-730-0A12A-001-R000 Fire Protection System Impairment NFPA National Fire Protection Association SLAC Stanford Linear Accelerator Center SSO DOE Stanford Site000 iii #12;#12;1 Introduction This document describes the fire protection system impairment program

Wechsler, Risa H.

256

Interest of the Theory of Uncertain in the Dynamic LCA- Fire Methodology to Assess Fire Effects  

Science Journals Connector (OSTI)

Abstract Life Cycle Impact Assessment (LCIA) is the third phase of Life Cycle Assessment (LCA) described in ISO 14042. The purpose of LCIA is to assess a product system's life cycle inventory analysis (LCI) in order to better understand its environmental significance. However, LCIA typically excludes spatial, temporal, threshold and dose-response information, and combines emissions or activities over space and/or time. This may diminish the environmental relevance of the indicator result. The methodology, Dynamic LCA -Fire proposed in this paper to complete the International Standard ISO 14042 in the fire field, combines the LCA - Fire method with the Dispersion Numerical Model. It is based on the use of the plume model used to assess pollutant concentrations and thermal effects from fire accident scenarios. In this study, The Dynamic LCA - Fire methodology is applied to a case study for petroleum production process management.

Samia Chettouh; Rachida Hamzi; Fares Innal; Djamel Haddad

2014-01-01T23:59:59.000Z

257

Electrical Sitchgear Building No. 5010-ESF Fire Hazards Technical Report  

SciTech Connect (OSTI)

The purpose of this Fire Hazards Analysis Technical Report (hereinafter referred to as Technical Report) is to assess the risk from fire within individual fire areas to ascertain whether the U.S. Department of Energy (DOE) fire safety objectives are met. The objectives, identified in DOE Order 420.1, Change 2, Fire Safety, Section 4.2, establish requirements for a comprehensive fire and related hazards protection program for facilities sufficient to minimize the potential for: (1) The occurrence of a fire or related event; (2) A fire that causes an unacceptable on-site or off-site release of hazardous or radiological material that will threaten the health and safety of the employees, the public, and the environment; (3) Vital DOE programs suffering unacceptable interruptions as a result of fire and related hazards; (4) Property losses from a fire and related events exceeding defined limits established by DOE; and (5) Critical process controls and safety class systems being damaged as a result of a fire and related event.

N.M. Ruonavaara

2001-05-08T23:59:59.000Z

258

DynCorp Tricities Services, Inc. Hanford fire department FY 1998 annual work plan  

SciTech Connect (OSTI)

The mission of the Hanford Fire Department (HFD) is to support the safe and timely cleanup of the Hanford site by providing fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating emergency situations which could threaten the operations, employees, or interest of the U.S. Department of Energy operated Hanford site. This includes response to surrounding fire departments/districts under mutual aid and state mobilization agreements and fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System) and various commercial entities operating on site through Requests for Service from DOE-RL. This fire department also provides site fire marshal overview authority, fire system testing and maintenance, respiratory protection services, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention education. This plan provides a program overview, program baselines, and schedule baseline.

Good, D.E.

1997-08-19T23:59:59.000Z

259

FIELD TEST PROGRAM FOR LONG-TERM OPERATION OF A COHPAC SYSTEM FOR REMOVING MERCURY FROM COAL-FIRED FLUE GAS  

SciTech Connect (OSTI)

With the Nation's coal-burning utilities facing the possibility of tighter controls on mercury pollutants, the U.S. Department of Energy is funding projects that could offer power plant operators better ways to reduce these emissions at much lower costs. Sorbent injection technology represents one of the simplest and most mature approaches to controlling mercury emissions from coal-fired boilers. It involves injecting a solid material such as powdered activated carbon into the flue gas. The gas-phase mercury in the flue gas contacts the sorbent and attaches to its surface. The sorbent with the mercury attached is then collected by the existing particle control device along with the other solid material, primarily fly ash. During 2001, ADA Environmental Solutions (ADA-ES) conducted a full-scale demonstration of sorbent-based mercury control technology at the Alabama Power E.C. Gaston Station (Wilsonville, AL). This unit burns a low-sulfur bituminous coal and uses a hot-side electrostatic precipitator (ESP) in combination with a Compact Hybrid Particulate Collector (COHPAC{trademark}) baghouse to collect fly ash. The majority of the fly ash is collected in the ESP with the residual being collected in the COHPAC{trademark} baghouse. Activated carbon was injected between the ESP and COHPAC{trademark} units to collect the mercury. Short-term mercury removal levels in excess of 90% were achieved using the COHPAC{trademark} unit. The test also showed that activated carbon was effective in removing both forms of mercury--elemental and oxidized. However, a great deal of additional testing is required to further characterize the capabilities and limitations of this technology relative to use with baghouse systems such as COHPAC{trademark}. It is important to determine performance over an extended period of time to fully assess all operational parameters. The project described in this report focuses on fully demonstrating sorbent injection technology at a coal-fired power generating plant that is equipped with a COHPAC{trademark} system. The overall objective is to evaluate the long-term effects of sorbent injection on mercury capture and COHPAC{trademark} performance. The work is being done on one-half of the gas stream at Alabama Power Company's Plant Gaston Unit 3 (nominally 135 MW). Data from the testing will be used to determine: (1) If sorbent injection into a high air-to-cloth ratio baghouse is a viable, long-term approach for mercury control; and (2) Design criteria and costs for new baghouse/sorbent injection systems that will use a similar, polishing baghouse (TOXECON{trademark}) approach.

Jean Bustard; Charles Lindsey; Paul Brignac; Travis Starns; Sharon Sjostrom; Trent Taylor; Cindy Larson

2004-01-29T23:59:59.000Z

260

Field Test Program for Long-Term Operation of a COHPAC System for Removing Mercury from Coal-Fired Flue Gas  

SciTech Connect (OSTI)

With the Nation's coal-burning utilities facing the possibility of tighter controls on mercury pollutants, the U.S. Department of Energy is funding projects that could offer power plant operators better ways to reduce these emissions at much lower costs. Sorbent injection technology represents one of the simplest and most mature approaches to controlling mercury emissions from coal-fired boilers. It involves injecting a solid material such as powdered activated carbon into the flue gas. The gas-phase mercury in the flue gas contacts the sorbent and attaches to its surface. The sorbent with the mercury attached is then collected by the existing particle control device along with the other solid material, primarily fly ash. During 2001, ADA Environmental Solutions (ADA-ES) conducted a full-scale demonstration of sorbent-based mercury control technology at the Alabama Power E.C. Gaston Station (Wilsonville, Alabama). This unit burns a low-sulfur bituminous coal and uses a hot-side electrostatic precipitator (ESP) in combination with a Compact Hybrid Particulate Collector (COHPAC{reg_sign}) baghouse to collect fly ash. The majority of the fly ash is collected in the ESP with the residual being collected in the COHPAC{reg_sign} baghouse. Activated carbon was injected between the ESP and COHPAC{reg_sign} units to collect the mercury. Short-term mercury removal levels in excess of 90% were achieved using the COHPAC{reg_sign} unit. The test also showed that activated carbon was effective in removing both forms of mercury-elemental and oxidized. However, a great deal of additional testing is required to further characterize the capabilities and limitations of this technology relative to use with baghouse systems such as COHPAC{reg_sign}. It is important to determine performance over an extended period of time to fully assess all operational parameters. The project described in this report focuses on fully demonstrating sorbent injection technology at a coal-fired power generating plant that is equipped with a COHPAC{reg_sign} system. The overall objective is to evaluate the long-term effects of sorbent injection on mercury capture and COHPAC{reg_sign} performance. The work is being done on one-half of the gas stream at Alabama Power Company's Plant Gaston Unit 3 (nominally 135 MW). Data from the testing will be used to determine: (1) If sorbent injection into a high air-to-cloth ratio baghouse is a viable, long-term approach for mercury control; and (2) Design criteria and costs for new baghouse/sorbent injection systems that will use a similar, polishing baghouse (TOXECON{trademark}) approach.

Jean Bustard; Charles Lindsey; Paul Brignac; Travis Starns; Sharon Sjostrom; Trent Taylor; Cindy Larson

2004-06-04T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


261

Anticipation in the Rodent Head Direction System Can Be Explained by an Interaction of Head Movements and Vestibular Firing Properties  

E-Print Network [OSTI]

Anticipation in the Rodent Head Direction System Can Be Explained by an Interaction of Head Rossum MC. Anticipation in the rodent head direction system can be explained by an interaction of head, 2007; doi:10.1152/jn.00233.2007. The rodent head-direction (HD) system, which codes for the animal

van Rossum, Mark

262

Fire Protection Database | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection Database Fire Protection Database Fire Protection Database DOE O 231.1, Environment, Safety, And Health Reporting, requires the submission of an Annual Fire Protection Summary. The previous process used to collect the required data utilizes a Microsoft Access database that was downloaded, completed by the field and then sent to Headquarters for summation and analysis by engineers in Office of Sustainability Support. Data collection for the CY2013 Summary will begin Jan. 1, 2014, and a commitment has been made to the Defense Nuclear Facilities Safety Board to collect this information and make it available utilizing a standard systematic approach. This approach will be accomplished via a web based system which will allow reporting organizations to enter or edit information.

263

RPP Computer Automated Surveillance System (CASS) to Tank Monitor and Control System (TMACS) transfer project plan  

SciTech Connect (OSTI)

Management plan to ensure the orderly, systematic transfer of alarms from the retired Computer Automated Surveillance System (CASS) to the Tank Monitor and Control System (TMACS).

SHIPLER, C.E.

1999-07-13T23:59:59.000Z

264

Nuclear incident monitor criticality alarm instrument for the Savannah River Site: Technical manual  

SciTech Connect (OSTI)

The Savannah River Site is a Department of Energy facility. The facility stores, processes, and works with fissionable material at a number of locations. Technical standards and US Department of Energy orders, require these locations to be monitored by criticality alarm systems under certain circumstances. The Savannah River Site calls such instruments Nuclear Incident Monitors or NIMs. The Sole purpose of the Nuclear Incident Monitor is to provide an immediate evacuation signal in the case of an accidental criticality in order to minimize personnel exposure to radiation. The new unit is the third generation Nuclear Incident Monitor at the Savannah River Site. The second generation unit was developed in 1979. It was designed to eliminate vacuum-tube circuits, and was the first solid state NIM at SRS. The major design objectives of the second generation NIM were to improve reliability and reduce maintenance costs. Ten prototype units have been built and tested. This report describes the design of the new NIM and the testing that took place to verify its acceptability.

Jenkins, J.B.

1996-05-21T23:59:59.000Z

265

Cycling firing method for bypass operation of bridge converters  

SciTech Connect (OSTI)

The bridge converter comprises a number of switching elements and an electronic logic system which regulated the electric power levels by controlling the firing, i.e., the initiation of the conduction period of the switching elements. Cyclic firing of said elements allows the direct current to bypass the alternating current system with high power factor and negligible losses.

Zabar, Zivan (99-72 66th Rd., Apt. 9N, Forest Hills, NY 11375)

1982-01-01T23:59:59.000Z

266

Diagnosis of Systemic Inflammation Using Transendothelial Electrical Resistance and Low-Temperature Co-fired Ceramic Materials.  

E-Print Network [OSTI]

??Systemic inflammation involves a complex array of cytokines that can result in organ dysfunction. Mortality remains high despite the vast amount of research conducted to (more)

Mercke, William L

2013-01-01T23:59:59.000Z

267

The development of a high reliability auxiliary power system for a coal-fired cycling generating station  

SciTech Connect (OSTI)

An auxiliary system for a fossil generating station is evolved based on operating and reliability criteria including the capabilities of switchgear and standard auxiliary transformer impedances. These criteria are used to design a flexible and reliable auxiliary power system for a cyclic duty power generating station. The effect of mechanical equipment selection on the auxiliary power system design is discussed. An economic comparison of single voltage versus dual-voltage is made. A one-line diagram of the resulting proposed system is included.

Jackowski, M.; Bailey, M.

1983-06-01T23:59:59.000Z

268

Fire-resistant pits: Reducing the probability of accidental plutonium dispersal from fuel fires  

SciTech Connect (OSTI)

Reductions in risk of Pu dispersal from hydrocarbon fuel fires were estimated using pool and spill fire data. Improvements in FRP temperature capabilities, on a system-independent basis, lead to the following estimated reductions in risk, using three probabilistic temperature distributions normalized to a temperature capability of 640[degree]C (the melting point of plutonium): 1OOO[degree]C - factor of 3 to 5; 11OO[degree]C - factor of 10 to 13; and 1200[degree]C - factor of 120 to 300. The above values would, of course, vary for a different normalization temperature. These values were derived to be as system-independent as possible. Incorporation of fuel fire durations or of longer time-averaging (than the two minutes employed in this study) would tend to increase these FRP improvement factors. Incorporation of propellant fires, burning metal or of combined impact/fire accidents would tend to decrease them. Further studies of fuel fire durations, particularly of a fuel fire duration model, is recommended, as is an uncertainty analysis of the temperature distributions.

Stephens, D.R.

1992-03-01T23:59:59.000Z

269

Flooding and Fire Ants  

E-Print Network [OSTI]

Fire ants can be a serious problem during and after a flood. This publication explains how to protect yourself when you must return to flooded structures or deal with storm debris....

Nester, Paul

2008-08-05T23:59:59.000Z

270

Safety, Security & Fire Report  

E-Print Network [OSTI]

2013 Safety, Security & Fire Report Stanford University #12;Table of Contents Public Safety About the Stanford University Department of Public Safety Community Outreach & Education Programs Emergency Access Transportation Safety Bicycle Safety The Jeanne Clery and Higher Education Act Timely Warning

Straight, Aaron

271

Surface Fire Hazards Analysis Technical Report-Constructor Facilities  

SciTech Connect (OSTI)

The purpose of this Fire Hazards Analysis Technical Report (hereinafter referred to as Technical Report) is to assess the risk from fire within individual fire areas to ascertain whether the U.S. Department of Energy (DOE) fire safety objectives are met. The objectives identified in DOE Order 420.1, Change 2, Facility Safety, Section 4.2, establish requirements for a comprehensive fire and related hazards protection program for facilities sufficient to minimize the potential for: The occurrence of a fire or related event; A fire that causes an unacceptable on-site or off-site release of hazardous or radiological material that will threaten the health and safety of employees, the public, or the environment; Vital DOE programs suffering unacceptable interruptions as a result of fire and related hazards; Property losses from a fire and related events exceeding defined limits established by DOE; and Critical process controls and safety class systems being damaged as a result of a fire and related events.

R.E. Flye

2000-10-24T23:59:59.000Z

272

Engineering development of coal-fired high performance power systems, Phases 2 and 3. Quarterly progress report, October 1--December 31, 1996. Final report  

SciTech Connect (OSTI)

The goals of this program are to develop a coal-fired high performance power generation system (HIPPS) by the year 2000 that is capable of: {gt} 47% efficiency (HHV); NO{sub x}, SO{sub x}, and particulates {gt} 10% NSPS; coal providing {ge} 65% of heat input; all sold wastes benign; and cost of electricity 90% of present plant. Work reported herein is from Task 1.3 HIPPS Commercial Plant Design, Task 2,2 HITAF Air Heater, and Task 2.4 Duct Heater Design. The impact on cycle efficiency from the integration of various technology advances is presented. The criteria associated with a commercial HIPPS plant design as well as possible environmental control options are presented. The design of the HITAF air heaters, both radiative and convective, is the most critical task in the program. In this report, a summary of the effort associated with the radiative air heater designs that have been considered is provided. The primary testing of the air heater design will be carried out in the UND/EERC pilot-scale furnace; progress to date on the design and construction of the furnace is a major part of this report. The results of laboratory and bench scale activities associated with defining slag properties are presented. Correct material selection is critical for the success of the concept; the materials, both ceramic and metallic, being considered for radiant air heater are presented. The activities associated with the duct heater are also presented.

NONE

1996-12-31T23:59:59.000Z

273

Fire dynamics during the 20th century simulated by the Community Land Model  

E-Print Network [OSTI]

Fire is an integral Earth System process that interacts with climate in multiple ways. Here we assessed the parametrization of fires in the Community Land Model (CLM-CN) and improved the ability of the model to reproduce ...

Kloster, S.; Mahowald, N. M.; Randerson, J. T.; Thornton, P. E.; Hoffman, F. M.; Levis, Samuel; Lawrence, P. J.; Feddema, Johannes J.; Oleson, Keith W.; Lawrence, D. M.

2010-01-01T23:59:59.000Z

274

DOE/EA-1472: Finding of No Significant Impact for the Commercial Demonstration of the Low NOx Burner/Separated Over-Fire Air Integration System Emission Reduction Technology (03/11/03)  

Broader source: Energy.gov (indexed) [DOE]

IMPACT IMPACT COMMERCIAL DEMONSRATION OF THE LOW NOx BURNER/SEPARATED OVER- FIRE AIR (LNB/SOFA) INTEGRATON SYSTEM EMISSION REDUCTION TECHNOLOGY HOLCOMB STATION SUNFLOWER ELECTRIC POWER CORPORATION FINNEY COUNTY, KANSAS AGENCY: U.S. Department of Energy (DOE) ACTION: Finding of No Significant Impact (FONSI) SUMMARY: The DOE has prepared an Environmental Assessment (EA), to analyze the potential impacts of the commercial application of the Low-NOx Burner/Separated Over-Fire Air (LNB/SOFA) integration system to achieve nitrogen oxide (NOx) emissions reduction at Sunflower's Holcomb Unit No. 1 (Holcomb Station), located near Garden City, in Finney County, Kansas. The Holcomb Station would be modified in three distinct phases to demonstrate the synergistic effect of layering NO,

275

Hanford Site Fire June 2000 AM  

SciTech Connect (OSTI)

The Hanford Site Fire on the morning of June 29, 2000. Fire crews working to contain a fire on the Hanford Site in June 2000.

2000-06-29T23:59:59.000Z

276

Ignition and spread of electrical wire fires  

E-Print Network [OSTI]

Airplane fires; (b) Nuclear power plant fires; (c) Chemicalignition sources in nuclear power plants: statistical,number of fire cases in nuclear power plants (NPP) [2]. Most

Huang, Xinyan

2012-01-01T23:59:59.000Z

277

Fire hazards analysis for the uranium oxide (UO{sub 3}) facility  

SciTech Connect (OSTI)

The Fire Hazards Analysis (FHA) documents the deactivation end-point status of the UO{sub 3} complex fire hazards, fire protection and life safety systems. This FHA has been prepared for the Uranium Oxide Facility by Westinghouse Hanford Company in accordance with the criteria established in DOE 5480.7A, Fire Protection and RLID 5480.7, Fire Protection. The purpose of the Fire Hazards Analysis is to comprehensively and quantitatively assess the risk from a fire within individual fire areas in a Department of Energy facility so as to ascertain whether the objectives stated in DOE Order 5480.7, paragraph 4 are met. Particular attention has been paid to RLID 5480.7, Section 8.3, which specifies the criteria for deactivating fire protection in decommission and demolition facilities.

Wyatt, D.M.

1994-12-06T23:59:59.000Z

278

Forest Fire Modeling and Early Detection using Wireless Sensor Networks  

E-Print Network [OSTI]

cases fires are part of the forest ecosys- tem and they are important to the life cycle of indigenous. The analysis of the FWI System could be of interest in its own right to researchers working in the sensor Columbia, Canada. The fire was spread by the strong wind and within a few days it turned into a firestorm

Zhang, Richard "Hao"

279

False Alarms and Close Calls: A Conceptual Model of Warning Accuracy LINDSEY R. BARNES*  

E-Print Network [OSTI]

of the key metrics for verifying National Weather Service (NWS) weather warnings. The national FAR, Health, & Hazards Center, Colorado Springs, Colorado Submitted to Weather and Forecasting Forecasters. In addition, we argue that the metrics used to evaluate false alarms do not accurately represent the numbers

Schultz, David

280

IE 361 Module 14 Patterns on Control Charts and "Special Checks"/Extra Alarm Rules  

E-Print Network [OSTI]

3.4 of Statistical Quality Assurance Methods for Engineers Prof. Steve Vardeman and Prof. Max MorrisIE 361 Module 14 Patterns on Control Charts and "Special Checks"/Extra Alarm Rules Reading: Section equipment or a clear change in the quality of a raw material

Vardeman, Stephen B.

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


281

Fire Test of Profile Plank for Transformer Pit Fire Protection  

Science Journals Connector (OSTI)

In general it is recommended to fill a transformer pit with rock ballast to extinguish the fire if there is a leakage of burning transformer oil. There is a lack of ... design of solutions for fire extinguishment...

Johan Lindstrm; Michael Frsth

2014-05-01T23:59:59.000Z

282

An environment friendly and efficient lignite-fired power generation process based on a boiler with an open pulverizing system and the recovery of water from mill-exhaust  

Science Journals Connector (OSTI)

Abstract This paper advances a novel lignite-fired power generation process based on a OPSB (boiler with an open pulverizing system) and the recovery of water from mill-exhaust after the comprehensive analysis of the open pulverizing system used for high-moisture coals and heat/water recovery from boiler exhaust. Then, the thermal calculation method that applies to OPSB is presented based on heat and mass balance analyses of the boiler. Finally, an efficient unit applying the OPSB process is compared with a conventional 600MW lignite-fired power unit, and the performance of the efficient unit is calculated and discussed in detail. The results show that the efficient unit not only yields a notable increase in the boiler's (2.6%) and the power plant's (1.3%) thermal efficiency but also provides a remarkable advantage in water recovery due to the mass of water vapor concentrated in mill-exhaust. In the efficient unit, the volume fraction of water vapor in mill-exhaust reaches 34%, the water reclaimed from mill-exhaust is so much that a lignite-fired power plant with zero water consumption can be expected, while the pollutant emissions can be reduced in proportion to the increase in boiler thermal efficiency.

Youfu Ma; Yichao Yuan; Jing Jin; Hua Zhang; Xiaohong Hu; Dengyu Shi

2013-01-01T23:59:59.000Z

283

Emergency, Fire Information  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Emergency, Fire Information Emergency, Fire Information Emergency, Fire Information Protecting our people, emergency personnel, national security information, facilities, lands, and neighboring communities. Contact Communications Office (505) 667-7000 Email LANL Update (505) 667-6622 or (877) 723-4101 toll-free Emergency Public Information In the event of an emergency, Los Alamos National Laboratory will provide you with needed information here as it becomes available. The Los Alamos Site Office/Los Alamos National Laboratory Emergency Public Information Plan provides a framework for coordinated, accurate, and timely release of information to Laboratory employees, the news media, potentially affected members of the public, and other stakeholders. Want emergency news emailed to you? Subscribe here.

284

Gas reburning in tangentially-fired, wall-fired and cyclone-fired boilers  

SciTech Connect (OSTI)

Gas Reburning has been successfully demonstrated for over 4,428 hours on three coal fired utility boilers as of March 31, 1994. Typically, NO{sub x} reductions have been above 60% in long-term, load-following operation. The thermal performance of the boilers has been virtually unaffected by Gas Reburning. At Illinois Power`s Hennepin Station, Gas Reburning in a 71 MWe tangentially-fired boiler achieved an average NO{sub x} reduction of 67% from the original baseline NO{sub x} level of 0.75 lb NO{sub x}/10{sup 6} Btu over a one year period. The nominal natural gas input was 18% of total heat input. Even at 10% gas heat input, NO{sub x} reduction of 55% was achieved. At Public Service Company of Colorado`s Cherokee Station, a Gas Reburning-Low NO{sub x} Burner system on a 172 MWe wall-fired boiler has achieved overall NO{sub x} reductions of 60--73% in parametric and long-term testing, based on the original baseline NO{sub x} level of 0.73 lb/10{sup 6} Btu. NO{sub x} reduction is as high as 60--65% even at relatively low natural gas usage (5--10% of total heat input). The NO{sub x} reduction by Low NO{sub x} Burners alone is typically 30--40%. NO{sub x} reduction has been found to be insensitive to changes in recirculated flue gas (2--7% of total flue gas) injected with natural gas. At City Water, Light and Power Company`s Lakeside Station in Springfield, Illinois, Gas Reburning in a 33 MWe cyclone-fired boiler has achieved an average NO{sub x} reduction of 66% (range 52--77%) at gas heat inputs of 20--26% in long-term testing, based on a baseline NO{sub x} level of 1.0 lb/10{sup 6} Btu (430 mg/MJ). This paper presents a summary of the operating experience at each site and discusses the long term impacts of applying this technology to units with tangential, cyclone and wall-fired (with Low NO{sub x} Burner) configurations.

May, T.J. [Illinois Power Co., Decatur, IL (United States); Rindahl, E.G. [Public Service Co. of Colorado, Denver, CO (United States); Booker, T. [City Water Light and Power, Springfield, IL (United States)] [and others

1994-12-31T23:59:59.000Z

285

An assessment of fire vulnerability for aged electrical relays  

SciTech Connect (OSTI)

There has been some concern that, as nuclear power plants age, protective measures taken to control and minimize the impact of fire may become ineffective, or significantly less effective, and hence result in an increased fire risk. One objective of the Fire Vulnerability of Aged Electrical Components Program is to assess the effects of aging and service wear on the fire vulnerability of electrical equipment. An increased fire vulnerability of components may lead to an overall increase in fire risk to the plant. Because of their widespread use in various electrical safety systems, electromechanical relays were chosen to be the initial components for evaluation. This test program assessed the impact of operational and thermal aging on the vulnerability of these relays to fire-induced damage. Only thermal effects of a fire were examined in this test program. The impact of smoke, corrosive materials, or fire suppression effects on relay performance were not addressed in this test program. The purpose of this test program was to assess whether the fire vulnerability of electrical relays increased with aging. The sequence followed for the test program was to: identify specific relay types, develop three fire scenarios, artificially age several relays, test the unaged and aged relays in the fire exposure scenarios, and compare the results. The relays tested were Agastat GPI, General Electric (GE) HMA, HGA, and HFA. At least two relays of each type were artificially aged and at least two relays of each type were new. Relays were operationally aged by cycling the relay under rated load for 2,000 operations. These relays were then thermally aged for 60 days with their coil energized.

Vigil, R.A. [Sandia National Labs., Albuquerque, NM (United States)]|[Science and Engineering Associates, Inc., Albuquerque, NM (United States); Nowlen, S.P. [Sandia National Labs., Albuquerque, NM (United States)

1995-03-01T23:59:59.000Z

286

3D building reconstruction and thermal mapping in fire brigade operations  

Science Journals Connector (OSTI)

Fire fighting remains a dangerous profession despite many recent technological and organizational measures. Sensors and technical systems can augment the performance of fire fighters to increase safety and efficiency during operation. An important aspect ... Keywords: augmented reality, fire fighter safety, real-time dense reconstruction, thermal camera

Christian Schnauer; Emanuel Vonach; Georg Gerstweiler; Hannes Kaufmann

2013-03-01T23:59:59.000Z

287

Particle and Gas Emissions from a Simulated Coal-Burning Household Fire Pit  

Science Journals Connector (OSTI)

Particle and Gas Emissions from a Simulated Coal-Burning Household Fire Pit ... Chinese anthracite and bituminous coals produce different amounts of emissions when burned in a fire pit that simulates common rural household use of these fuels. ... Here we present emissions from burning 15 different fuels in a laboratory system designed to mimic the fire pits used in Xuan Wei County, China. ...

Linwei Tian; Donald Lucas; Susan L. Fischer; S. C. Lee; S. Katharine Hammond; Catherine P. Koshland

2008-02-21T23:59:59.000Z

288

DEVELOPMENT OF FINE PARTICULATE EMISSION FACTORS AND SPECIATION PROFILES FOR OIL AND GAS-FIRED COMBUSTION SYSTEMS  

SciTech Connect (OSTI)

In 1997, the United States Environmental Protection Agency (EPA) promulgated new National Ambient Air Quality Standards (NAAQS) for particulate matter, including for the first time particles with aerodynamic diameter smaller than 2.5 micrometers ({micro}m) referred to as PM2.5. PM2.5 in the atmosphere also contributes to reduced atmospheric visibility, which is the subject of existing rules for siting emission sources near Class 1 areas and new Regional Haze rules. There are few existing data regarding emissions and characteristics of fine aerosols from oil, gas and power generation industry combustion sources, and the information that is available is generally outdated and incomplete. Traditional stationary source air emission sampling methods tend to underestimate or overestimate the contribution of the source to ambient aerosols because they do not properly account for primary aerosol formation, which occurs after the gases leave the stack. Primary aerosol includes both filterable particles that are solid or liquid aerosols at stack temperature plus those that form as the stack gases cool through mixing and dilution processes in the plume downwind of the source. These deficiencies in the current methods can have significant impacts on regulatory decision-making. PM2.5 measurement issues were extensively reviewed by the American Petroleum Institute (API) (England et al., 1998), and it was concluded that dilution sampling techniques are more appropriate for obtaining a representative particulate matter sample from combustion systems for determining PM2.5 emission rate and chemical speciation. Dilution sampling is intended to collect aerosols including those that condense and/or react to form solid or liquid aerosols as the exhaust plume mixes and cools to near-ambient temperature immediately after the stack discharge. These techniques have been widely used in recent research studies. For example, Hildemann et al. (1994) and McDonald et al. (1998) used filtered ambient air to dilute the stack gas sample followed by 80-90 seconds residence time to allow aerosol formation and growth to stabilize prior to sample collection and analysis. More accurate and complete emissions data generated using the methods developed in this program will enable more accurate source-receptor and source apportionment analysis for PM2.5 National Ambient Air Quality Standards (NAAQS) implementation and streamline the environmental assessment of oil, gas and power production facilities. The overall goals of this program were to: (1) Develop improved dilution sampling technology and test methods for PM2.5 mass emissions and speciation measurements, and compare results obtained with dilution and traditional stationary source sampling methods. (2) Develop emission factors and speciation profiles for emissions of fine particulate matter, especially organic aerosols, for use in source-receptor and source apportionment analyses. (3) Identify and characterize PM2.5 precursor compound emissions that can be used in source-receptor and source apportionment analyses.

Glenn C. England

2004-10-20T23:59:59.000Z

289

Externally fired gas turbine technology: A review  

Science Journals Connector (OSTI)

Abstract Externally fired heat engines were used widely since helium the industrial revolution using dirty solid fuels for example coal, due to the lack of refined fuels. However, with the availability of clean fuels, external firing mode was abandoned, except for steam power plants. Lately, with the global trend moving towards green power production, the idea of the external fired system has captured the attention again especially externally fired gas turbine (EFGT) due to its wider range of power generation and the potential of using environment friendly renewable energy sources like biomass. In this paper, a wide range of thermal power sources utilizing EFGT such as concentrated solar power (CSP), fossil, nuclear and biomass fuels are reviewed. Gas turbine as the main component of EFGT is investigated from micro scale below 1MWe to the large scale central power generation. Moreover, the different high temperature heat exchanger (HTHE) materials and designs are reviewed. Finally, the methods of improving cycle efficiency such as the externally fired combined cycle (EFCC), humidified air turbine (HAT), EFGT with fuel cells and other cycles are reviewed thoroughly.

K.A. Al-attab; Z.A. Zainal

2015-01-01T23:59:59.000Z

290

E-Print Network 3.0 - accident experience alarm Sample Search...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

, accident investigation, indoor air quality, bloodborne pathogens, chemical safety, lockout-tagout, hot work... Campus Fires 11 12 Accident Reporting 14 Employee Accidents 15...

291

EHSO TRAINING CLASSES Fire Safety Program Training  

E-Print Network [OSTI]

EHSO TRAINING CLASSES Fire Safety Program Training 1. Fire Safety (60 minutes) Instruction includes an actual fire eperience. 2. Fire Extinguisher Training (30 minutes) A practical demonstration on actual burnable liquid fires. This practical extinguisher training is a critical portion of the fire

292

Fire-Immune Cable  

Science Journals Connector (OSTI)

... A FACTORY, opened by Lord Ridley on October 12, for making fire-resist ing cable called 'Pyrotenax', marks a new development which promises to be of far-reaching ... -plate elements, which are made of resistance wire embedded in the oxide. 'Pyrotenax' cable has a copper conductor, magnesia insulation, and copper sheath. The new technique enables ...

1937-11-20T23:59:59.000Z

293

System Design and the Safety Basis  

SciTech Connect (OSTI)

The objective of this paper is to present the Bechtel Jacobs Company, LLC (BJC) Lessons Learned for system design as it relates to safety basis documentation. BJC has had to reconcile incomplete or outdated system description information with current facility safety basis for a number of situations in recent months. This paper has relevance in multiple topical areas including documented safety analysis, decontamination & decommissioning (D&D), safety basis (SB) implementation, safety and design integration, potential inadequacy of the safety analysis (PISA), technical safety requirements (TSR), and unreviewed safety questions. BJC learned that nuclear safety compliance relies on adequate and well documented system design information. A number of PIS As and TSR violations occurred due to inadequate or erroneous system design information. As a corrective action, BJC assessed the occurrences caused by systems design-safety basis interface problems. Safety systems reviewed included the Molten Salt Reactor Experiment (MSRE) Fluorination System, K-1065 fire alarm system, and the K-25 Radiation Criticality Accident Alarm System. The conclusion was that an inadequate knowledge of system design could result in continuous non-compliance issues relating to nuclear safety. This was especially true with older facilities that lacked current as-built drawings coupled with the loss of 'historical knowledge' as personnel retired or moved on in their careers. Walkdown of systems and the updating of drawings are imperative for nuclear safety compliance. System design integration with safety basis has relevance in the Department of Energy (DOE) complex. This paper presents the BJC Lessons Learned in this area. It will be of benefit to DOE contractors that manage and operate an aging population of nuclear facilities.

Ellingson, Darrel

2008-05-06T23:59:59.000Z

294

RL-721 REV7 I. Project Title: NEPA REVIEW SCREENING FORM Document...  

Broader source: Energy.gov (indexed) [DOE]

alarm and surveillance systems, control systems to provide automatic shutdown, fire detection and protection systems, water consumption monitors and flow control...

295

Lessons Learned from Internal Fire PSAs on Candu Reactors and PWRs in Korea  

SciTech Connect (OSTI)

Internal fire risk has been one of the major concerns for nuclear power plants. To reduce the risk from internal fire, installing the suppression system, establishment of fire protection program, changing to qualified cables, and sealing the opening can be considered. The approaches to fire protection design are different for each plant design, and they are highly dependent on the plant type. The fire PSA revealed that the potential plant risk due to a fire event is highly dependent on the design. The approaches to fire protection design are different for each plant type, especially between Wolsong Unit 1 (Candu) and Korea Standard Nuclear Plants (KSNP). In this paper, plant design and fire PSA of Wolsong Unit 1 (Candu) were compared with those of the KSNP (PWR) to identify plant-specific and risk-significant items. (authors)

Kim, Sung-Hyun; Jeong, Beom-Hee; Kang, Sun-Koo [Integrated Safety Assessment Department Korea Power Engineering Co., 360-9, Mabuk-Ri, Kusung-Eup, Yongin-Shi, Kyunggi-Do, 449-713 (Korea, Republic of); Jeong, Young-Ki; Kim, Poong-Shick; Cho, Byung-Ok [Nuclear Safety and Technology Department, Korea Hydro and Nuclear Power Co., 167, Samseong-Dong, Gangnam-Gu, Seoul 135-791 (Korea, Republic of)

2004-07-01T23:59:59.000Z

296

Coal-fired diesel generator  

SciTech Connect (OSTI)

The objective of the proposed project is to test the technical, environmental, and economic viability of a coal-fired diesel generator for producing electric power in small power generating markets. Coal for the diesel generator would be provided from existing supplies transported for use in the University`s power plant. A cleanup system would be installed for limiting gaseous and particulate emissions. Electricity and steam produced by the diesel generator would be used to supply the needs of the University. The proposed diesel generator and supporting facilities would occupy approximately 2 acres of land adjacent to existing coal- and oil-fired power plant and research laboratory buildings at the University of Alaska, Fairbanks. The environmental analysis identified that the most notable changes to result from the proposed project would occur in the following areas: power plant configuration at the University of Alaska, Fairbanks; air emissions, water use and discharge, and the quantity of solid waste for disposal; noise levels at the power plant site; and transportation of coal to the power plant. No substantive adverse impacts or environmental concerns were identified in analyzing the effects of these changes.

NONE

1997-05-01T23:59:59.000Z

297

Technical aspects of the sigma factor alarm method in alpha CAMs  

SciTech Connect (OSTI)

Some test must be applied to the low-level count data from alpha continuous air monitors (CAMs) to determine if the count is statistically significant (i.e., different from background). The test should also automatically account for different levels of background (i.e., ambient radon progeny concentrations). The method should, in other words, be as sensitive as possible, automatically desensitize when required, but in such a manner as to not exceed a previously-chosen acceptable false-alarm rate.

Justus, Alan Lawrence [Los Alamos National Laboratory

2009-01-01T23:59:59.000Z

298

Cold Vacuum Drying (CVD) Facility Diesel Generator Fire Protection  

SciTech Connect (OSTI)

This Acceptance Test Procedure (ATP) has been prepared to demonstrate that the Fire Protection and Detection System installed by Project W-441 (Cold Vacuum Drying Facility and Diesel Generator Building) functions as required by project specifications.

SINGH, G.

2000-04-25T23:59:59.000Z

299

Micronized coal-fired retrofit system for SO{sub x} reduction Krakow clean fossil fuels and energy efficiency program. Final report  

SciTech Connect (OSTI)

This report describes results of a technical, financial and environmental assessment study for a project, which would have included a new TCS micronized coal-fired heating plant for the Produkcja I Hodowla Roslin Ogrodniczych (PHRO) Greenhouse Complex; Krzeszowice, Poland. Project site is about 20 miles west of Krakow, Poland. During the project study period, PHRO utilized 14 heavy oil-fired boilers to produce heat for its greenhouse facilities and also home heating to several adjacent apartment housing complexes. The boilers burn a high-sulfur content heavy crude oil, called mazute, The project study was conducted during a period extended from March 1996 through February 1997. For size orientation, the PHRO Greenhouse complex grows a variety of vegetables and flowers for the Southern Poland marketplace. The greenhouse area under glass is very large and equivalent to approximately 50 football fields, The new micronized coal fired boiler would have: (1) provided a significant portion of the heat for PHRO and a portion of the adjacent apartment housing complexes, (2) dramatically reduced sulfur dioxide air pollution emissions, while satisfying new Polish air regulations, and (3) provided attractive savings to PHRO, based on the quantity of displaced oil.

NONE

1997-04-01T23:59:59.000Z

300

Fire Protection Program: Summary  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Summary Summary Since May 1950, an Annual Fire Protection Program Summary has been submitted by DOE's fire protection community. Currently, this report is required by section 5a.(8) of DOE Order 231.1. "Environment, Safety and Health Reporting." In 1999, an automation initiative was undertaken to streamline data collection and provide a more through review of DOE Reporting Element activities. This action resulted in the delayed publications of the CY 1999 and 2000 reports until 2002. It is now possible however to view all Annual Summary Reporting Element responses since 1991 at the Site, Operations, Lead Program Secretarial Office and Headquarters levels. Additionally, a build-in reference to other DOE reporting activities (CAIRS and ORPS) is available that allows Reporting Elements and managers the opportunity to review all fire protection events along previously mentioned categories. Reports listed below were generated from this application. To obtain a copy of the Annual Summary Application please contact Jim Bisker in the Office of Nuclear and Facility Safety Policy (EH-53) at (301)903-6542 or Jim Bisker.

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


301

Computational Science Technical Note CSTN-163 Transients in a Forest-Fire Simulation Model with Varying Combustion  

E-Print Network [OSTI]

to the model system. KEY WORDS fire-model; simulation; dynamics; fire-break; transient; cy- cles. 10 Computational Science Technical Note CSTN-163 Transients in a Forest-Fire Simulation Model and the eect of a fractal watercourse introduced into the system is investigated. The presence of the water

Hawick, Ken

302

Application of a Heat Integrated Post-combustion CO2 Capture System with Hitachi Advanced Solvent into Existing Coal-Fired Power Plant Award Number: DE-FE0007395 DOE Project Manager: José D. Figueroa  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

a Heat Integrated Post- a Heat Integrated Post- combustion CO 2 Capture System with Hitachi Advanced Solvent into Existing Coal-Fired Power Plant University of Kentucky Research Foundation Partnered with U.S. Department of Energy NETL Louisville Gas & Electric and Kentucky Utilities Electric Power Research Institute (with WorleyParsons) Hitachi Power Systems America Smith Management Group July 9, 2013 Goals and Objectives * Objectives 1) To demonstrate a heat-integrated post-combustion CO 2 capture system with an advanced solvent; 2) To collect information/data on material corrosion and identify appropriate materials of construction for a 550 MWe commercial-scale carbon capture plant.  To gather data on solvent degradation kinetics, water management, system dynamic control as well as other information during the long-term

303

Abstract B31: Collaborative breast health education addressing an alarming public health concern in the District of Columbia  

Science Journals Connector (OSTI)

...meeting-abstract Behavioral and Social Science Poster Presentations - Proffered Abstracts...B31: Collaborative breast health education addressing an alarming public health...Early Awareness is a breast health education program of Howard University Cancer...

Kimberly Higginbotham; Deon Regis; Lucile Adams-Campbell; Carla WIlliams; Wayne Frederick; Karen Peterson; Jasmine Greenamyer; Erica Childs; and Carolyn Aldige

2008-11-01T23:59:59.000Z

304

Lab and field estimates of active time of chemical alarm cues of a cyprinid fish and an  

E-Print Network [OSTI]

Lab and field estimates of active time of chemical alarm cues of a cyprinid fish and an amphipod., 1999; Stankowich, 2008), seismic (Gregory et al., 1986) and vibratory mechanostimuli (Kirchner et al

Wisenden, Brian D.

305

Effect Of False Alarm Rate On Pilot Use And Trust Of Automation Under Conditions Of Simulated High Risk  

E-Print Network [OSTI]

An experimental study was conducted to investigate the relationships between automation false alarm rate, human trust in automation, and human use of automation, specifically under conditions of simulated high risk. The ...

Cafarelli, Deborah

2010-11-05T23:59:59.000Z

306

Report Wildland Fire Area Hazard  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Report Wildland Fire Area Hazard Report Wildland Fire Area Hazard Report Wildland Fire Area Hazard Report wildland fire area hazards or incidents that are non-life threatening only. Call 911 for all emergencies that require immediate assistance. How to report wildland fire hazard Use the following form to report any wildland fire area hazards or incidents that are non-life threatening only. Call 911 for all emergencies that require immediate assistance. Fill out this form as completely as possible so we can better assess the hazard. All submissions will be assessed as promptly as possible. For assistance with a non-emergency situation, contact the Operations Support Center at 667-6211. Name (optional): Hazard Type (check one): Wildlife Sighting (check box if animal poses serious threat) Trails (access/egress)

307

E-Print Network 3.0 - advanced coal fired Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

CHILE ESCUELA DE INGENIERIA Summary: of more advanced technologies on the future coalpetcoke-fired power plants, and the system's operation... were compared with more advanced...

308

E-Print Network 3.0 - advanced coal-fired gas Sample Search Results  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

CHLORINE LINK IN COMMERCIAL SCALE SYSTEM FLUE GASES? Summary: that Battelle measured dioxins in coal fired utility boiler stack emissions in the United States and by ETSU... in...

309

Dendrochronology-based fire history of mixed-conifer forests in the San Jacinto Mountains, California  

Science Journals Connector (OSTI)

The growing public awareness of the increasing number of large wildfires across forested landscapes, coupled with needs of resource base management has accelerated research into forest reference conditions and the historical role of fire in coniferous ecosystems. This work investigates historical fire regimes of mixed-conifer forests in the San Jacinto Mountains of southern California using fire-scar dendrochronology. As such this is the first reconstruction of fire history in the mixed-conifer forests of southern California using landscape-scale systematic-based fire-scar dendrochronology. The pre-historical fire size, seasonality, and frequency within these forests are reconstructed and demonstrated graphically, employing systematic sampling and Geographical Information System (GIS) reconstruction. A 250m grid system was overlaid upon a 270ha sample location, and fire-scar samples were collected from each of the grid intersection points. Fire-scar dendrochronology resulted in a 653 years long chronology, indicating a point mean fire return interval of 5.2 years, and an area wide grand mean fire interval of 32.2 years. The majority of fires occurred within latewood or at the ring boundary. Graphic modelling of fire events indicate three-quarters of all fires sampled were less than 6.25ha in size, but burned over 50% of the area sampled during the period; only a small portion of fires were larger than 18ha within the sample area. Use of systematic sampling is an important step in modeling long-term frequency and effects of fire on a landscape level, and is invaluable to the long-term management planning.

Richard G. Everett

2008-01-01T23:59:59.000Z

310

ANNUAL SECURITY FIRE SAFETY REPORT  

E-Print Network [OSTI]

ANNUAL SECURITY AND FIRE SAFETY REPORT OCTOBER 1, 2013 DARTMOUTH COLLEGE http................................................................................................................................................................... 7 ANNUAL SECURITY REPORT........................................................................................................................9 PREPARATION OF THE REPORT AND DISCLOSURE OF CRIME STATISTICS

311

Fire and Ice Issue 9  

E-Print Network [OSTI]

s FIRE AND ICE # 9 IB FIRE ICE #9 A Blake/Avon slash fanzine r Available from: Kathleen Resch POBox 1766 Temple City, CA 91780 Kathleener@aol.com FIRE AND ICE # 9copyright May, 2005 by Kathleen Resch for the contributors. No reprints... or reproduction without the written permission ofthe author/artist This is an amateur publication and is not p intended to infringe upon the rights ofany holders of"Blake's 7" copyrights. FIRE AND ICE 9 TABLE OF CONTENTS LEAVING ROOM 101 by Nova 2 TOO MANY...

Multiple Contributors

2005-01-01T23:59:59.000Z

312

Benchmark enclosure fire suppression experiments - phase 1 test report.  

SciTech Connect (OSTI)

A series of fire benchmark water suppression tests were performed that may provide guidance for dispersal systems for the protection of high value assets. The test results provide boundary and temporal data necessary for water spray suppression model development and validation. A review of fire suppression in presented for both gaseous suppression and water mist fire suppression. The experimental setup and procedure for gathering water suppression performance data are shown. Characteristics of the nozzles used in the testing are presented. Results of the experiments are discussed.

Figueroa, Victor G.; Nichols, Robert Thomas; Blanchat, Thomas K.

2007-06-01T23:59:59.000Z

313

EHS 5-6 September 2006 DEPARTMENT OF ENVIRONMENTAL HEALTH & SAFETY  

E-Print Network [OSTI]

Mechanical HVAC Test & Balance Electrical Gas Other Site accessibility Protection From Site Construction requesting Certificate Environmental Certificates Department of Environmental Protection Operations Alarm Certification Approved Fire Alarm Shop Drawings Sprinkler Certification Approved Sprinkler System

Sura, Philip

314

Fire tests to evaluate the potential fire threat and its effects on HEPA filter integrity in cell ventilation at the Oak Ridge National Laboratory, Building 7920  

SciTech Connect (OSTI)

As a result of a DOE (Tiger Team) Technical Safety Appraisal (November 1990) of the Radiochemical Engineering Development Center (REDC), ORNL Building 7920, a number of fire protection concerns were identified. The primary concern was the perceived loss of ventilation system containment due to the thermal destruction and/or breaching of the prefilters and/or high-efficiency particulate air filters (HEPA `s) and the resultant radioactive release to the external environment. The following report describes the results of an extensive fire test program performed by the Fire Research Discipline (FRD) of the Special Projects Division of Lawrence Livermore National Lab (LLNL) and funded by ORNL to address these concerns. Full scale mock-ups of a REDC hot cell tank pit, adjacent cubicle pit, and associated ventilation system were constructed at LLNL and 13 fire experiments were conducted to specifically answer the questions raised by the Tiger Team. Our primary test plan was to characterize the burning of a catastrophic solvent spill (kerosene) of 40 liters and its effect on the containment ventilation system prefilters and HEPA filters. In conjunction with ORNL and Lockwood Greene we developed a test matrix that assessed the fire performance of the prefilters and HEPA filters; evaluated the fire response of the fiber reinforced plastic (FRP) epoxy ventilation duct work; the response and effectiveness of the fire protection system, the effect of fire in a cubicle on the vessel off-gas (VOG) elbow, and other fire safety questions.

Hasegawa, H.K.; Staggs, K.J.; Doughty, S.M. [Oak Ridge National Lab., TN (United States)

1992-12-01T23:59:59.000Z

315

Fire Lane must Fire Lane must be kept clear  

E-Print Network [OSTI]

#12;#12; Fire Lane must Fire Lane must be kept clear at all timesa a es #12; Emergency Egress Keep Safety Data Sheets #12; Safety glasses Safety goggles Face shield #12; Eye protection Skin protection Spectators protection from the light energygy #12; Safety glasses are required when any machinery

Asaithambi, Asai

316

Fire Safety Committee Meeting Minutes- May 2014  

Broader source: Energy.gov [DOE]

DOE Fire Safety Committee Meeting Minutes, May, 2014 Topics included discussions on Fire modeling, revisions to DOE regulations and other important items relating to DOE and Fire Safety Community.

317

RFAR installation for Buildings 703, 712, 747, 748 and 1163  

SciTech Connect (OSTI)

This document is to certify the installation and testing of the Radio Fire Alarm Reporting box (RFAR). The Hanford Fire Dept. will be notified of troubles via RFAR. The document outlines prerequisites, necessary equipment, and the fire alarm system test to insure the system is operating correctly.

Ferry, M.

1995-12-31T23:59:59.000Z

318

MARGINAL VALUATION OF FIRE EFFECTS  

E-Print Network [OSTI]

in the planning unit's land, resource and fire management plans. These goals and objectives can assist you with identifying the resources that are important to protect or improve through fire management activities. As you and cultural attributes of the landscape that have value. Defining the resource considered for value change 2

319

WHC fire hazards analysis policy  

SciTech Connect (OSTI)

The purpose of this document is to establish the fire protection policy for Westinghouse Hanford Company (WHC) relative to US Department of Energy (DOE) directives for Fire Hazards Analyses (FHAs) and their relationship to facility Safety Analysis Reports (SARs) as promulgated by the DOE Richland Operations Office.

Evans, C.B.

1994-04-01T23:59:59.000Z

320

ANNUAL SECURITY & FIRE SAFETY REPORT  

E-Print Network [OSTI]

ANNUAL SECURITY & FIRE SAFETY REPORT 2014 A guide to policies, procedures, practices, and programs implemented to keep students, faculty, and staff safe and facilities secure. www.montana.edu/reports/security.pdf #12;Inside this Report 2014 Annual Security and Fire Safety Report for Reporting Year 2013

Maxwell, Bruce D.

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


321

BlueFire Ethanol | Department of Energy  

Office of Energy Efficiency and Renewable Energy (EERE) Indexed Site

BlueFire Ethanol BlueFire Ethanol Construct and operate a facility that converts green waste and lignocellulosic fractions diverted from landfills or Southern California Materials...

322

Fire hazards analysis of central waste complex  

SciTech Connect (OSTI)

This document analyzes the fire hazards associated with operational the Central Waste Complex. It provides the analysis and recommendations necessary to ensure compliance with applicable fire codes.

Irwin, R.M.

1996-05-30T23:59:59.000Z

323

New Buildings at the Fire Research Station  

Science Journals Connector (OSTI)

... THE new buildings of the Fire Research Station A of the Joint Fire Research Organization of the Department ... chemicals will be studied in the new chemical engineering laboratory.

D. I. LAWSON

1961-01-14T23:59:59.000Z

324

Proceedings of the ASME Heat Transfer Division. Volume 4: Natural convection within a horizontal circular cylinder heated from below and cooled from above; Numerical methods for coupled fluid-thermal-structural interaction; Thermal analysis in waste processing and disposal; Heat transfer in fire and combustion systems; HTD-Volume 335  

SciTech Connect (OSTI)

The first two sections as listed in the title contain 7 papers. The third section on thermal analysis contains 18 papers arranged into the following topical areas: Thermal treatment and municipal wastes; Thermal hydraulics in hazardous and nuclear waste processing and disposal; and Waste processing. Heat transfer in fire and combustion systems contains 17 papers arranged into the following topical sections: Soot/radiation; Combustion systems; Multiphase combustion; and Flames and fires. Most papers have been processed separately for inclusion on the data base.

Pepper, D.W. [ed.] [Univ. of Nevada, Las Vegas, NV (United States); Douglass, R.W. [ed.] [Idaho National Engineering Lab., Idaho Falls, ID (United States); Heinrich, J.C. [ed.] [Univ. of Arizona, Tucson, AZ (United States)] [and others

1996-12-31T23:59:59.000Z

325

fire & fuels management Spruce Beetle-Induced Changes to Engelmann  

E-Print Network [OSTI]

. Keywords: crown fire, bark beetles, heat of combustion, fire behavior, time to ignition E ngelmann spruce

326

FOA for the Demonstration of an Integrated Biorefinery System...  

Broader source: Energy.gov (indexed) [DOE]

Blue Fire Ethanol, Inc. FOA for the Demonstration of an Integrated Biorefinery System: Blue Fire Ethanol, Inc. FOA for the Demonstration of an Integrated Biorefinery System: Blue...

327

Remote keyless entry honking, convenience horn honking, and audible car alarms: redundancies and quieter options  

Science Journals Connector (OSTI)

Vehicle sound emissions car alarms and horn honking are the subject of many noise complaints. Auto manufacturers spent years engineering quieter vehicles and have created cars whose approach is so subtle that they pose a danger to blind pedestrians. But while engine noise has decreased and car alarms are less reactive horn honking that is linked with remote keyless entry (RKE) technology increasingly contributes to community noise. RKE horn noise has never been the subject of public health inquiry. In scientific literature discussion of road noise and health does not distinguish noise among separate sources and tends to measure aggregate ambient noise levels rather than impulsive noise. RKE horn noise violates state traffic laws and some local noise ordinances regarding horn use but there have been no legislative attempts to address the technology. This raises questions about whether political leaders and policy setters are not exposed to RKE noise or do not discern RKE sounds from traffic noise and are therefore unaware of it. Using available auto industry data and case studies this paper will introduce key facts about RKE horn use in the United States and Canada reviewing new technologies that render noisy counterparts still in use as redundant.

Jeanine Botta

2013-01-01T23:59:59.000Z

328

Remote keyless entry honking, convenience horn honking, and audible car alarms: Redundancies and quieter options  

Science Journals Connector (OSTI)

Vehicle sound emissions car alarms and horn honking are the subject of many noise complaints. Auto manufacturers spent years engineering quieter vehicles and have created cars whose approach is so subtle that they pose a danger to blind pedestrians. But while engine noise has decreased and car alarms are less reactive horn honking that is linked with remote keyless entry (RKE) technology increasingly contributes to community noise. RKE horn noise has never been the subject of public health inquiry. In scientific literature discussion of road noise and health does not distinguish noise among separate sources and tends to measure aggregate ambient noise levels rather than impulsive noise. RKE horn noise violates state traffic laws and some local noise ordinances regarding horn use but there have been no legislative attempts to address the technology. This raises questions about whether political leaders and policy setters are not exposed to RKE noise or do not discern RKE sounds from traffic noise and are therefore unaware of it. Using available auto industry data and case studies this paper will introduce key facts about RKE horn use in the United States and Canada reviewing new technologies that render noisy counterparts still in use as redundant.

2013-01-01T23:59:59.000Z

329

Wireless boundary monitor system and method  

DOE Patents [OSTI]

A wireless boundary monitor system used to monitor the integrity of a boundary surrounding an area uses at least two housings having at least one transmitting means for emitting ultrasonic pressure waves to a medium. Each of the housings has a plurality of receiving means for sensing the pressure waves in the medium. The transmitting means and the receiving means of each housing are aimable and communicably linked. At least one of the housings is equipped with a local alarm means for emitting a first alarm indication whereby, when the pressure waves propagating from a transmitting means to a receiving means are sufficiently blocked by an object a local alarm means or a remote alarm means or a combination thereof emit respective alarm indications. The system may be reset either manually or automatically. This wireless boundary monitor system has useful applications in both indoor and outdoor environments.

Haynes, Howard D. (Knoxville, TN); Ayers, Curtis W. (Kingston, TN)

1997-01-01T23:59:59.000Z

330

Overview of the ARM/FIRE Water Vapor Experiment (AFWEX)  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Overview of the ARM/FIRE Water Vapor Overview of the ARM/FIRE Water Vapor Experiment (AFWEX) D. C. Tobin, H. E. Revercomb, and D. D. Turner University of Wisconsin-Madison Madison, Wisconsin Introduction An overview of the ARM/FIRE Water Vapor Experiment (AFWEX) is given. This field experiment was conducted during November-December 2000 near the central ground-based Atmospheric Radiation Measurement (ARM) site in north central Oklahoma, and was sponsored jointly by the ARM, the National Aeronautics and Space Administration (NASA) First ISCCP Regional Experiment (FIRE), and the National Polar-orbiting Operational Environmental Satellite System (NPOESS) programs. Its primary goal was to collect accurate measurements of upper-level (~8 to 12 km) water vapor near the ground-based ARM site. These data are being used to determine the accuracy of measurements that are

331

Audit Report, "Fire Protection Deficiencies at Los Alamos National Laboratory"  

SciTech Connect (OSTI)

The Department of Energy's Los Alamos National Laboratory (Los Alamos) maintains some of the Nation's most important national security assets, including nuclear materials. Many of Los Alamos' facilities are located in close proximity to one another, are occupied by large numbers of contract and Federal employees, and support activities ranging from nuclear weapons design to science-related activities. Safeguarding against fires, regardless of origin, is essential to protecting employees, surrounding communities, and national security assets. On June 1, 2006, Los Alamos National Security, LLC (LANS), became the managing and operating contractor for Los Alamos, under contract with the Department's National Nuclear Security Administration (NNSA). In preparation for assuming its management responsibilities at Los Alamos, LANS conducted walk-downs of the Laboratory's facilities to identify pre-existing deficiencies that could give rise to liability, obligation, loss or damage. The walk-downs, which identified 812 pre-existing fire protection deficiencies, were conducted by subject matter professionals, including fire protection experts. While the Los Alamos Site Office has overall responsibility for the effectiveness of the fire protection program, LANS, as the Laboratory's operating contractor, has a major, day-to-day role in minimizing fire-related risks. The issue of fire protection at Los Alamos is more than theoretical. In May 2000, the 'Cerro Grande' fire burned about 43,000 acres, including 7,700 acres of Laboratory property. Due to the risk posed by fire to the Laboratory's facilities, workforce, and surrounding communities, we initiated this audit to determine whether pre-existing fire protection deficiencies had been addressed. Our review disclosed that LANS had not resolved many of the fire protection deficiencies that had been identified in early 2006: (1) Of the 296 pre-existing deficiencies we selected for audit, 174 (59 percent) had not been corrected; and, (2) A substantial portion of the uncorrected deficiencies, 86 (49 percent) were considered by the walk-down teams to be significant enough to warrant compensatory actions until the deficiency was corrected or was tracked to closure through implementation of corrective actions. Further, we found that 32 of the significant deficiencies had been closed by the previous Los Alamos contractor, prior to LANS assuming responsibility for operation of the Laboratory, even though the deficiencies had not been corrected. A fire protection expert provided technical support during the audit. As an example of uncorrected problems, LANS had not resolved, by performing periodic tests, a deficiency identified in 2006 regarding a kitchen hood fire suppression system in a facility located within the Los Alamos Neutron Science Center. Such systems are required to be tested twice a year by the National Fire Protection Association standard, a standard that had been adopted by Department of Energy under DOE Order 420.1B. Yet, in 2006, the LANS walk-down team recognized that this system had not been inspected since May 2004 and noted that deficient suppression systems could result in significantly high levels of property damage and loss. After we brought this issue to management's attention on February 6, 2009, LANS officials stated that the Laboratory would correct this deficiency. As with the problems involving the fire suppression system, we observed that LANS had not always corrected life safety deficiencies involving building exits at one of its primary facilities. This included providing a secondary emergency exit for a building with occupants on multiple floor levels. LANS had removed personnel from the third floor and improved the sprinkler system of the facility, but it had still not provided a secondary exit for personnel on the second floor by the time we completed our review. NNSA has since stated that this fire protection issue will be completely addressed by relocating personnel from the second floor. Perhaps most serious, our testing revealed that a number of deficien

None

2009-06-01T23:59:59.000Z

332

INEEL/EXT-99-00778  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

any warning alarm. * Neither OSHA regulations nor NFPA codes and standards required lockouttagout of the CO 2 fire suppression system for the maintenance work in progress at...

333

Fire and Ice Issue 7  

E-Print Network [OSTI]

       ' FIRE and ICE # 7 -p! jP) FIRE AND ICE VII Available from: Kathleen Resch PO Box 1766 Temple City, CA 91780 Kathleener@aol.com May 2002by Kathleen Reschfor the contributors. No reprints or reproduction without the written... permission of the author/artist. Thisis an amateur publication and is not in tended to infringe upon the rights ofTerryNation, BBC-TV or any others. i - J FIRE AND ICE VI Table of Contents HALF A LOAF by Linda Norman 1 GROUNDHOG LAY by Predatrlx 5 PLAYTIME...

Multiple Contributors

2002-01-01T23:59:59.000Z

334

Fire and Ice Issue 3  

E-Print Network [OSTI]

,fpl ^1 FIRE AND ICE Available from: Kathleen Resch PO Box 1766 Temple City,CA 91780 III May, 1995 by Kathleen Resch for the contributors. No reprints or reproduction without the written permission of the author/artist. This is an amateur... publication and is not intended to infringe upon the rightsof "Blake's 7" copyright holders.. FIRE AND ICE TABLE OF CONTENTS THE GIFT by Pat Terra 1 "innerspace" by Pat Terra 24 WILD, BEAUTIFUL AND DAMNED by Gemini 25 SET THE NIGHT ON FIRE by Riley Cannon 40...

Multiple Contributors

1995-01-01T23:59:59.000Z

335

History of Fire Events in the U.S. Commercial Nuclear Industry  

SciTech Connect (OSTI)

Over the past decade, interest in performance-based fire protection has increased within the nuclear industry. In support of this growing interest, in 1997 the Electric Power Research Institute (EPRI) developed a long-range plan to develop/improve data and tools needed to support Risk-Informed/Performance-Based fire protection. This plan calls for continued improvement in collection and use of information obtained from fire events at nuclear plants. The data collection process has the objectives of improving the insights gained from such data and reducing the uncertainty in fire risk and fire modeling methods in order to make them a more reliable basis for performance based fire protection programs. In keeping with these objectives, EPRI continues to collect, review and analyze fire events in support of the nuclear industry. EPRI collects these records in cooperation with the Nuclear Electric Insurance Limited (NEIL), by compiling public fire event reports and by direct solicitation of U.S. nuclear facilities. EPRI fire data collection project is based on the principle that the understanding of history is one of the cornerstones of improving fire protection technology and practice. Therefore, the goal has been to develop and maintain a comprehensive database of fire events with flexibility to support various aspects of fire protection engineering. With more than 1850 fire records over a period of three decades and 2400 reactor years, this is the most comprehensive database of nuclear power industry fire events in existence today. In general, the frequency of fires in the U.S. commercial nuclear industry remains constant. In few cases, e.g., transient fires and fires in BWR offgas/recombiner systems, where either increasing or decreasing trends are observed, these trends tend to slow after 1980. The key issues in improving quality of the data remain to be consistency of the recording and reporting of fire events and difficulties in collection of records. EPRI has made significant progress towards improving the quality of the fire events data through use of multiple collection methods as well as its review and verification. To date EPRI has used this data to develop a generic fire ignition frequency model for U.S. nuclear power industry (Ref. 1, 4 and 5) as well as to support other models in support of EPRI Fire Risk Methods such as a cable fire manual suppression model. EPRI will continue its effort to collect and analyze operating data to support risk informed/performance based fire safety engineering, including collection and analysis of impairment data for fire protection systems and features. This paper provides details on the collection and application of fire events to risk informed/performance based fire protection. The paper also provides valuable insights into improving both collection and use of fire events data. (authors)

Bijan Najafi; Joglar-Biloch, Francisco [Science Applications International Corporation, 10260 Campus Point Drive, San Diego, CA 92121 (United States); Kassawara, Robert P. [Electric Power Research Institute, Electric Power Research Institute, 3412. Hillview Avenue, Palo Alto, CA 94303 (United States); Khalil, Yehia [Dominion Nuclear Connecticut, Rope Ferry Road Waterford, CT 06385 (United States)

2002-07-01T23:59:59.000Z

336

Fire Behavior at the Landscape Scale  

E-Print Network [OSTI]

Fire Behavior at the Landscape Scale Scott Stephens, ESPMScott Stephens, ESPM DepartmentStrategies for Landscape Fuel TreatmentsLandscape Fuel Treatments Fire Containment · Fuelbreaks Fire Modification · Area (WUI) ·· Maintenance? Must maintain into futureMaintenance? Must maintain into future #12;Tyee Fire

Stephens, Scott L.

337

Wildland Fire Protection Program NEBRASKA FOREST SERVICE  

E-Print Network [OSTI]

Wildland Fire Protection Program NEBRASKA FOREST SERVICE HOW NEBRASKANS BENEFIT: · improved protection of life and property from wildland fires · improved firefighting capability in rural fire districts · increased firefighter knowledge of wildland fire suppression and prevention · reduced forest

Farritor, Shane

338

FIRE PREVENTION AND PROTECTION Table Of Contents  

E-Print Network [OSTI]

EM 385-1-1 XX Sep 13 i Section 9 FIRE PREVENTION AND PROTECTION Table Of Contents Section: Page 09 and Melting Kettles.............................9-25 09.F First response Fire Protection FIRE PREVENTION AND PROTECTION 09.A GENERAL 09.A.01 A fire prevention plan shall be written for all

US Army Corps of Engineers

339

Firing of pulverized solvent refined coal  

DOE Patents [OSTI]

An air-purged burner for the firing of pulverized solvent refined coal is constructed and operated such that the solvent refined coal can be fired without the coking thereof on the burner components. The air-purged burner is designed for the firing of pulverized solvent refined coal in a tangentially fired boiler.

Derbidge, T. Craig (Sunnyvale, CA); Mulholland, James A. (Chapel Hill, NC); Foster, Edward P. (Macungie, PA)

1986-01-01T23:59:59.000Z

340

No material is "fire proof;" however, proper use and assembly of fire-rated building materials  

E-Print Network [OSTI]

C has the least resistance. However, Class A materials generally need an underlayment of additional-Defensible Zones 6.303, Fire-Resistant Landscaping 6.304, Forest Home Fire Safety 6.305, FireWise Plant Materials 6General No material is "fire proof;" however, proper use and assembly of fire-rated building

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


341

fire Protection The Fire Protection Technology associate degree is awarded by UNL's College of  

E-Print Network [OSTI]

fire Protection DeGreeS offereD A.S. The Fire Protection Technology associate degree is awarded Protection courses are taught by UNL College of Engineering faculty, as well as fire service and industry fire protection specialists. These fire protection specialists teach students not only from textbooks

Farritor, Shane

342

Fire in a contaminated area  

SciTech Connect (OSTI)

This document supports the development and presentation of the following accident scenario in the TWRS Final Safety Analysis Report: Fire in Contaminated Area. The calculations needed to quantify the risk associated with this accident scenario are included within.

Ryan, G.W., Westinghouse Hanford

1996-08-02T23:59:59.000Z

343

New Canadian Fire Research Laboratory  

Science Journals Connector (OSTI)

... which follows the time - temperature curve designated in the current U.S. Standard (ASTM E119-57, Standard Methods of Fire Tests of Building Construction and Materials).

R. F. LEGGET

1959-03-07T23:59:59.000Z

344

Model Fire Protection Assessment Guide  

Broader source: Energy.gov [DOE]

This Assessment guide covers the implementation of the DOE's responsibility of assuring that DOE and the DOE Contractors have established Fire Protection Programs that are at the level required for the area being assessed.

345

Hanford fire department FY 99 annual work plan WBS 6.5.7  

SciTech Connect (OSTI)

The mission of the Hanford Fire Department (HFD) is to support the safe and timely cleanup of the Hanford site by providing a full range of services at the lowest possible cost to customers. These services include fire suppression, fire prevention, emergency rescue, emergency medical service, and hazardous materials response; and to be capable of dealing with and terminating emergency situations which could threaten the operations, employees, the general public, or interest of the U. S. Department of Energy operated Hanford Site. This includes response to surrounding fire departments/districts under mutual aid and state mobilization agreements and fire fighting, hazardous materials, and ambulance support to Washington Public Power Supply System (Supply System) and various commercial entities operating on site through Requests for Service from DOE-RL. The fire department also provides site fire marshal overview authority, fire system testing and maintenance, respiratory protection services, building tours and inspections, ignitable and reactive waste site inspections, prefire planning, and employee fire prevention education.

GOOD, D.E.

1999-02-24T23:59:59.000Z

346

Untrained Forward Observer (UFO) translator for call for fire .  

E-Print Network [OSTI]

??Many observers need indirect fire but are not proficient in Call for Fire, the procedure used to request indirect fire. To alleviate this, we propose (more)

King, Regan R.

2013-01-01T23:59:59.000Z

347

Prescriptive vs. performance based cook-off fire testing.  

SciTech Connect (OSTI)

In the fire safety community, the trend is toward implementing performance-based standards in place of existing prescriptive ones. Prescriptive standards can be difficult to adapt to changing design methods, materials, and application situations of systems that ultimately must perform well in unwanted fire situations. In general, this trend has produced positive results and is embraced by the fire protection community. The question arises as to whether this approach could be used to advantage in cook-off testing. Prescribed fuel fire cook-off tests have been instigated because of historical incidents that led to extensive damage to structures and loss of life. They are designed to evaluate the propensity for a violent response. The prescribed protocol has several advantages: it can be defined in terms of controllable parameters (wind speed, fuel type, pool size, etc.); and it may be conservative for a particular scenario. However, fires are inherently variable and prescribed tests are not necessarily representative of a particular accident scenario. Moreover, prescribed protocols are not necessarily adaptable and may not be conservative. We also consider performance-based testing. This requires more knowledge and thought regarding not only the fire environment, but the behavior of the munitions themselves. Sandia uses a performance based approach in assuring the safe behavior of systems of interest that contain energetic materials. Sandia also conducts prescriptive fire testing for the IAEA, NRC and the DOT. Here we comment on the strengths and weakness of both approaches and suggest a path forward should it be desirable to pursue a performance based cook-off standard.

Nakos, James Thomas; Tieszen, Sheldon Robert; Erikson, William Wilding; Gill, Walter; Blanchat, Thomas K.

2010-07-01T23:59:59.000Z

348

PROOF-OF-CONCEPT OF A DUAL-FIRED (SOLAR & NATURAL GAS) GENERATOR  

E-Print Network [OSTI]

PROOF-OF-CONCEPT OF A DUAL-FIRED (SOLAR & NATURAL GAS) GENERATOR FOR USE IN A SPACE-COOLING SYSTEM REPORT (FAR) PROOF-OF-CONCEPT OF A DUAL-FIRED (SOLAR & NATURAL GAS) GENERATOR FOR USE IN A SPACE COOLING Technologies · Environmentally-Preferred Advanced Generation · Energy-Related Environmental Research · Energy

349

A Wood-Fired Gas Turbine Plant  

E-Print Network [OSTI]

-fired turbine, it probably seems that a wood gasification system must be involved. This is a proven and accepted method of producing gas to drive this type of power unit, but the fuel produced is a dirty fuel containing large amounts of me' ~ "'1 re, tars..., and other undesirable impurities that make it unsuitable for use as a fuel until a rather expensive cleanup process and residual waste disposal can take place. However, Aerospace Research felt that there must be a way to improve on the wood gasification...

Powell, S. H.; Hamrick, J. T.

350

Fire safety of LPG in marine transportation. Final report  

SciTech Connect (OSTI)

This report contains an analytical examination of cargo spill and fire hazard potential associated with the marine handling of liquefied petroleum gas (LPG) as cargo. Principal emphasis was on cargo transfer operations for ships unloading at receiving terminals, and barges loading or unloading at a terminal. Major safety systems, including emergency shutdown systems, hazard detection systems, and fire extinguishment and control systems were included in the analysis. Spill probabilities were obtained from fault tree analyses utilizing composite LPG tank ship and barge designs. Failure rates for hardware in the analyses were generally taken from historical data on similar generic classes of hardware, there being very little historical data on the specific items involved. Potential consequences of cargo spills of various sizes are discussed and compared to actual LPG vapor cloud incidents. The usefulness of hazard mitigation systems (particularly dry chemical fire extinguishers and water spray systems) in controlling the hazards posed by LPG spills and spill fires is also discussed. The analysis estimates the probability of fatality for a terminal operator is about 10/sup -6/ to 10/sup -5/ per cargo transfer operation. The probability of fatality for the general public is substantially less.

Martinsen, W.E.; Johnson, D.W.; Welker, J.R.

1980-06-01T23:59:59.000Z

351

EXHAUST GAS BOILER FIRE PERVENTION  

E-Print Network [OSTI]

Today's demands for better overall usability of fuel oil in large two-stroke low speed marine diesel engines greatly influenced their development, and the purity of their exhaust gases. With this paper we would like to indicate on to factors which directly influence on soot forming, deposition and cause of occurance of fire in exhaust gas boiler (EGB). Due the fact that a fire in the EGB can result in complete destruction of the boiler, and a longer interruption of the vessel commercial operations, crew must be familiar with the main reasons of soot deposition on the boiler tubes and elements and origination of fire, and to have taken proper and timely protection measures 1.

Branko Lali? Dipl. Ing; Mr. Ivan Komar; Dipl. Ing

352

Initial Joint Review of Wildland Fire Safety at DOE Sites  

Broader source: Energy.gov (indexed) [DOE]

Wildland Fire" November 2000 2. U.S. Fish & Wildlife, "24 Command Fire, A National Level Review by the Interagency Fire Team," September 2000 INEEL Site (Tea Kettle Fire, etc.) In...

353

SOLVENT FIRE BY-PRODUCTS  

SciTech Connect (OSTI)

Southwest Research Institute (SwRI) conducted a burn test of the Caustic-Side Solvent Extraction (CSSX) solvent to determine the combustion products. The testing showed hydrogen fluoride gas is not a combustion product from a solvent fire when up to 70% of the solvent is consumed. The absence of HF in the combustion gases may reflect concentration of the modifier containing the fluoride groups in the unburned portion. SwRI reported results for other gases (CO, HCN, NOx, formaldehyde, and hydrocarbons). The results, with other supporting information, can be used for evaluating the consequences of a facility fire involving the CSSX solvent inventory.

Walker, D; Samuel Fink, S

2006-05-22T23:59:59.000Z

354

Fire suppression and detection equipment  

SciTech Connect (OSTI)

Inspection and testing guidelines go beyond the 'Code of Federal Regulation'. Title 30 of the US Code of Federal Regulations (30 CFR) contains requirements and references to national standards for inspection, testing and maintenance of fire suppression and detection equipment for mine operators. However, federal requirements have not kept pace with national standards and best practices. The article lists National Fire Protection (NFPA) standards that are referenced by the US Mine Safety and Health Administration (MSHA) in 30 CFR. It then discusses other NFPA Standards excluded from 30 CFR and explains the NFPA standard development process. 2 refs., 3 tabs., 5 photos.

E.E. Bates [HSB Professional Loss Control, Lexington, KY (United States)

2006-01-15T23:59:59.000Z

355

Fire and Ice Issue 6  

E-Print Network [OSTI]

9#HDIQNV3>IM ".: FIRE AND ICE VI Available from: Kathleen Resch PO Box 1766 Temple City, CA 91780 October, 2000 by Kathleen Resch for the contributors. No reprints or reproduction without the written permission of the author.../artist. This is an amateur publication and is not intended to infringe upon the rights ofTerry Nation, BBC-TV or any others. FIRE AND ICE VI 1 Table of Contents A DANGEROUS CONCEPT by Nova 1 A FRIEND IN NEED... by Julia Stamford 14 ...IS A FRIEND INDEED by Julia Stamford 19...

Multiple Contributors

2000-01-01T23:59:59.000Z

356

Fire and Ice Issue 2  

E-Print Network [OSTI]

. fipl cpn r FLASHPOINT A flame that can't be seen, cloaked in black and silver and disdain, born of anger and of love no longer dared. An ice-encrusted soul, dormant in the aftermath of accusations piled like snow against the heated passions of a man who...^ $$% i&l /P^ \\0 rffej FIRE AND ICE AVAILABLE FROM Kathleen Resch PO Box 1766 Temple City, CA 91780 FIRE AND ICE II TABLE OF CONTENTS COVER by Phoenix FRONTISPIECE by Gayle Feyrer "Flashpoint" by Rachel Duncan 1 PEDESTAL by Thomas 2 "A Damn Fine...

Multiple Contributors

1993-01-01T23:59:59.000Z

357

A residential micro tri-generation system based on a gas fired stirling engine CHP and thermo-chemical accumulator (TCA).  

E-Print Network [OSTI]

??Cooling production has application in a considerable number of fields in human life, such as: food processing, air-conditioning, pharmaceuticals, etc. The conventional refrigeration system driven (more)

Hasib`, Zannatul, M (Author)

2013-01-01T23:59:59.000Z

358

Fire Protection Engineering Qualification Standard Reference Guide  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection Fire Protection Engineering Qualification Standard Reference Guide SEPTEMBER 2009 This page is intentionally blank. Table of Contents i ACRONYMS ................................................................................................................................. ii PURPOSE.......................................................................................................................................1 SCOPE ............................................................................................................................................1 PREFACE.......................................................................................................................................1 TECHNICAL COMPETENCIES................................................................................................3

359

Fire performance of gable frame structures  

E-Print Network [OSTI]

Fire protection engineering and structural engineering are two relevant but separated fields of study. Many experiments conducted by fire protection engineers are under certain ideal boundary conditions, which may not be ...

Qian, Congyi

2013-01-01T23:59:59.000Z

360

Solid waste drum array fire performance  

SciTech Connect (OSTI)

Fire hazards associated with drum storage of radioactively contaminated waste are a major concern in DOE waste storage facilities. This report is the second of two reports on fire testing designed to provide data relative to the propagation of a fire among storage drum arrays. The first report covers testing of individual drums subjected to an initiating fire and the development of the analytical methodology to predict fire propagation among storage drum arrays. This report is the second report, which documents the results of drum array fire tests. The purpose of the array tests was to confirm the analytical methodology developed by Phase I fire testing. These tests provide conclusive evidence that fire will not propagate from drum to drum unless an continuous fuel source other than drum contents is provided.

Louie, R.L. [Westinghouse Hanford Co., Richland, WA (United States); Haecker, C.F. [Los Alamos Technical Associates, Inc., Kennewick, WA (United States); Beitel, J.J.; Gottuck, D.T.; Rhodes, B.T.; Bayier, C.L. [Hughes Associates, Inc., Baltimore, MD (United States)

1995-09-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


361

FireStream: Sensor Stream Processing for Monitoring Fire Spread Venkatesh Raghavan1  

E-Print Network [OSTI]

Institute, Worcester, MA 01609 2 Department of Fire Protection Engineering, Worcester Polytechnic Institute. In this demonstration, we present FireStream, a collabo- rative effort between Computer Science and Fire Protection experiments conducted at lab- oratories such as NIST/BFRL and the Department of Fire Protection Engineering

362

Wildland fire emissions, carbon, and climate: Wildland fire detection and burned area in the United States  

E-Print Network [OSTI]

Wildland fire emissions, carbon, and climate: Wildland fire detection and burned area in the United Wildland fires can be an important source of greenhouse gases as well as black carbon emissions that have of climate response to fire emissions compared to other emission sources of GHG, aerosols, and black carbon

363

Planning Rural Fire Protection for Texas.  

E-Print Network [OSTI]

IOC rA24S.7 73 ).1196 (Blank Pa.ge InOdgiuat Bulletinl ~ ; ''; . : .. . ~. " PLANNING RURAL FIRE PROTECTION FOR TEXAS JACK L. JONES, EXTENSION COMMUNITY DEVELOPMENT SPECIALIST TEXAS AGRICULTURAL EXTENSION SERVICE INTRODUCTION A home fire... is one of the most feared accidents a homeowner can? have, especially in rural areas where extended distances, inadequate water supplies or lack of any community fire fighting services limit fire fighting capability. Unless a rural resident makes prior...

Jones, Jack L.

1981-01-01T23:59:59.000Z

364

Development of custom fire behavior fuel models from FCCS fuelbeds for the Savannah River fuel assessment project.  

SciTech Connect (OSTI)

The purpose of this project is to create fire behavior fuel models that replicate the fire behavior characteristics (spread rate and fireline intensity) produced by 23 candidate FCCS fuelbeds developed for the Savannah River National Wildlife Refuge. These 23 fuelbeds were created by FERA staff in consultation with local fuel managers. The FCCS produces simulations of surface fire spread rate and flame length (and therefore fireline intensity) for each of these fuelbeds, but it does not produce maps of those fire behavior characteristics or simulate fire growththose tasks currently require the use of the FARSITE and/or FlamMap software systems. FARSITE and FlamMap do not directly use FCCS fuelbeds, but instead use standard or custom fire behavior fuel models to describe surface fuel characteristics for fire modeling. Therefore, replicating fire growth and fire behavior potential calculations using FCCS?simulated fire characteristics requires the development of custom fuel models that mimic, as closely as possible, the fire behavior characteristics produced by the FCCS for each fuelbed, over a range of fuel moisture and wind speeds.

Scott, Joe, H.

2009-07-23T23:59:59.000Z

365

Fire protection review, Westinghouse Idaho Nuclear Company, Idaho Falls, Idaho  

SciTech Connect (OSTI)

A fire protection survey was conducted for the Department of Energy at the Westinghouse Idaho Nuclear Company, INC., Idaho Falls, Idaho, on April 24--27, April 30--May 4, June 4--8, and June 11--15, 1990. The purpose of the survey was to review the facility's fire protection program and to make recommendations according to the following criteria established by the Department of Energy: (1) Recommendations which would be made as the result of an improved risk or Highly Protected Risk (HPR) fire inspection of an industrial insured facility. (2) Identification of areas which are presently not protected or are inadequately protected where provision of automatic protection would reduce a fire or explosion loss to less than $1 million. (3) Identification of areas where loss potentials exceed $50 million assuming a failure of automatic protection systems and subsequent reliance only on separation and fire walls. (4) Evaluation of adequacy of compliance with recommendations made in prior surveys. Findings and recommendations in this report reflect to some degree the relative importance of the operation and the time to restore it to useful condition in the event that a loss were to occur.

Dobson, P.H.

1990-10-01T23:59:59.000Z

366

Multi-Function Fuel-Fired Heat Pump  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Multi-Function Fuel-Fired Heat Pump Multi-Function Fuel-Fired Heat Pump CRADA Ed Vineyard Oak Ridge National Laboratory, Building Equipment Research vineyardea@ornl.gov, 865-576-0576 April 2, 2013 2 | Building Technologies Office eere.energy.gov Purpose & Objectives Problem Statement: 55% residential building energy use for space conditioning & water heating; highly efficient systems needed to facilitate DOE/BTO goal for 50% reduction in building energy use by 2030 Impact of Project: Cumulative energy savings potential of 0.25 Quads

367

Energy from waste via coal/waste co-firing  

SciTech Connect (OSTI)

The paper reviews the feasibility of waste-to-energy plants using the cocombustion of coal with refuse-derived fuels. The paper discusses the types of wastes available: municipal solid wastes, plastics, tires, biomass, and specialized industrial wastes, such as waste oils, post-consumer carpet, auto shredder residues, and petroleum coke. The five most common combustion systems used in co-firing are briefly described. They are the stoker boiler, suspension-fired boilers, cyclone furnaces, fluidized bed boilers, and cement kilns. The paper also discusses the economic incentives for generating electricity from waste.

Winslow, J.; Ekmann, J.; Smouse, S. [Dept. of Energy, Pittsburgh, PA (United States). Pittsburgh Energy Technology Center; Ramezan, M. [Burns and Roe Services Corp., Pittsburgh, PA (United States); Harding, S.

1996-12-31T23:59:59.000Z

368

CONSTITUTION AND BY-LAWS FIRE DEPARTMENT  

E-Print Network [OSTI]

of lives, and the protection of property endangered by fires and other disasters, and to promote the teaching and practice of fire prevention and protection. ARTICLE II Section 1. The OfficersSAMPLE CONSTITUTION AND BY-LAWS OF THE FIRE DEPARTMENT WHEREAS, Certain laws and regulations

369

Research Overview Department of Fire Protection Engineering  

E-Print Network [OSTI]

Research Overview Department of Fire Protection Engineering University of Maryland College Park, MD, detection M.J. Gollner wildfires, flammability, structures A.W. Marshall fire flows, combustion, suppression J.A. Milke structures, detection, egress S.I. Stoliarov pyrolysis, flammability, fire growth P

Shapiro, Benjamin

370

Cyber Friendly Fire: Research Challenges for Security Informatics  

SciTech Connect (OSTI)

This paper addresses cognitive implications and research needs surrounding the problem of cyber friendly fire (FF). We define cyber FF as intentional offensive or defensive cyber/electronic actions intended to protect cyber systems against enemy forces or to attack enemy cyber systems, which unintention-ally harms the mission effectiveness of friendly or neutral forces. Just as with combat friendly fire, maintaining situation awareness (SA) is paramount to avoiding cyber FF incidents. Cyber SA concerns knowledge of a systems topology (connectedness and relationships of the nodes in a system), and critical knowledge elements such as the characteristics and vulnerabilities of the components that comprise the system and its nodes, the nature of the activities or work performed, and the available defensive and offensive countermeasures that may be applied to thwart network attacks. Mitigation strategies to combat cyber FF including both training concepts and suggestions for decision aids and visualization approachesare discussed.

Greitzer, Frank L.; Carroll, Thomas E.; Roberts, Adam D.

2013-06-06T23:59:59.000Z

371

Fire-Induced Response in Foam Encapsulants  

SciTech Connect (OSTI)

The paper provides a concise overview of a coordinated experimental/theoretical/numerical program at Sandia National Laboratories to develop an experimentally validated model of fire-induced response of foam-filled engineered systems for nuclear and transportation safety applications. Integral experiments are performed to investigate the thermal response of polyurethane foam-filled systems exposed to fire-like heat fluxes. A suite of laboratory experiments is performed to characterize the decomposition chemistry of polyurethane. Mass loss and energy associated with foam decomposition and chemical structures of the virgin and decomposed foam are determined. Decomposition chemistry is modeled as the degradation of macromolecular structures by bond breaking followed by vaporization of small fragments of the macromolecule with high vapor pressures. The chemical decomposition model is validated against the laboratory data. Data from integral experiments is used to assess and validate a FEM foam thermal response model with the chemistry model developed from the decomposition experiments. Good agreement was achieved both in the progression of the decomposition front and the in-depth thermal response.

Borek, T.T.; Chu, T.Y.; Erickson, K.L.; Gill, W.; Hobbs, M.L.; Humphries, L.L.; Renlund, A.M.; Ulibarri, T.A.

1999-04-02T23:59:59.000Z

372

Low NOx firing technology of Mitsubishi Heavy Industries  

SciTech Connect (OSTI)

This paper presents super low NO{sub x} combustion technologies successfully developed by MHI (Mitsubishi Heavy Industries, Ltd.) and its use in practice. PM (Pollution Minimum) burners directly reduce NO{sub x} from the burners themselves and MACT (Mitsubishi Advanced Combustion Technology) system, an in-furnace NO{sub x} removal system, reduces NO{sub x} generated from the main burners within the boiler. These firing systems are applicable to coal, oil, gas and also to other exotic fuels like Orimulsion or CWM (Coal Water Mixture). MRS (Mitsubishi Rotary Separator) mills minimizes unburnt carbon with its reliable ultra-fine grinding of coal and hence contribute to low NO{sub x}. These technologies have been applied in various combinations to 227 boilers for both new installation and retrofit jobs. Large 1,000 MWe oil or gas fired boilers and 700 MWe coal fired boilers have been put into commercial use, and a 1,000 MWe coal fired boiler is under commissioning. The technologies have been applied to small sized boilers for industrial use as well. All the delivered systems have been working both domestic and overseas to the customers` satisfaction.

Kaneko, Shozo; Tokuda, Kimishiro; Sato, Susumu [Mitsubishi Heavy Industries, Yokohama (Japan)

1996-01-01T23:59:59.000Z

373

Interactive Simulation of Fire Zeki Melek John Keyser  

E-Print Network [OSTI]

and air inside each grid cell. The combustion process produces heat, and we model the resulting spread of temperature through the system. The heat distribution induces convection currents in the air, causing the flame to take the appropriate shape. By modeling heat distribution, we also simulate the spread of fire

Keyser, John

374

Gas-Fired Boilers and Furnaces | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Gas-Fired Boilers and Furnaces Gas-Fired Boilers and Furnaces Gas-Fired Boilers and Furnaces May 16, 2013 - 4:36pm Addthis A residential natural gas meter. A residential natural gas meter. What does this mean for me? Your gas boiler or furnace may be oversized, particularly if you've upgraded the energy efficiency of your home. Your gas boiler or furnace can be retrofitted to improve its energy efficiency. Gas boilers and furnaces can be fueled by either natural gas or propane with simple modifications accounting for the different characteristics of the fuels. Propane is usually more expensive as a fuel, but is available throughout the United States. Natural gas supplies depend on having a natural gas distribution system in your area, and areas at the end of the pipeline (such as the Northeast) tend to pay higher prices for natural gas.

375

Gas-Fired Boilers and Furnaces | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Gas-Fired Boilers and Furnaces Gas-Fired Boilers and Furnaces Gas-Fired Boilers and Furnaces May 16, 2013 - 4:36pm Addthis A residential natural gas meter. A residential natural gas meter. What does this mean for me? Your gas boiler or furnace may be oversized, particularly if you've upgraded the energy efficiency of your home. Your gas boiler or furnace can be retrofitted to improve its energy efficiency. Gas boilers and furnaces can be fueled by either natural gas or propane with simple modifications accounting for the different characteristics of the fuels. Propane is usually more expensive as a fuel, but is available throughout the United States. Natural gas supplies depend on having a natural gas distribution system in your area, and areas at the end of the pipeline (such as the Northeast) tend to pay higher prices for natural gas.

376

Avestar® - Syngas-Fired Combined Cycle Dynamic Simulator  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Syngas-Fired Combined Cycle Dynamic Simulator Syngas-Fired Combined Cycle Dynamic Simulator The AVESTAR® center offers courses using the Combined Cycle Simulator, focusing on the power generation process after gasification. This simulator is well-suited for concentrated training on operation and control of the gas and steam turbines; condensate, feed water, and circulating water systems; heat recovery steam generator; and selective catalytic reduction (SCR) unit. Combined cycle simulator startup operations include bringing up the gas turbine to rated speed on natural gas and then switching over to the firing of synthesis gas. Key capabilities of the Combined Cycle Simulator include: Combined Cycle Simulator Operator training station HMI display for overview of Gas Turbine - Train A Normal base load operation

377

Integration of a MEMS based safe arm and fire device  

Science Journals Connector (OSTI)

The paper describes a new architecture of a Safe Arm and Fire device (SAF) that could constitute a real breakthrough for safe miniature fuzing device. On the one hand, it takes all the functions embodied in a conventional mechanical arm and fire system and integrates them in a single 1cm3 package made of assembly of different parts. On the other hand, for the first time, it combines a mechanical arming unit with electrical safety functionalities on the same silicon initiator's chip. It respects the STANAG 4187 norm (1A/W during 5min of not fire) and requires only 635mW for ignition. The paper presents the design, fabrication and test of one miniature SAF device integrating a micropyrotechnical actuation.

Hlne Pezous; Carole Rossi; Marjorie Sanchez; Fabrice Mathieu; Xavier Dollat; Samuel Charlot; Ludovic Salvagnac; Vronique Condra

2010-01-01T23:59:59.000Z

378

Imperial College London FIRE SERVICES  

E-Print Network [OSTI]

to minimise the hazard the following precautions are recommended: Christmas tree lights, fibre optic trees hazards. Avoid leaving Christmas lights on unattended for long periods. Lighted candles are generally at Christmas During the lead up to Christmas the risk of fire can be increased with the introduction

379

HOURGLASS FIRE Pingree Park Vicinity  

E-Print Network [OSTI]

needles). Fuel moistures were extremely low throughout Colorado during spring/early summer of 1994 firefighters in a blowup near Glenwood Springs. Table 1 indicates dead fuel moistures in the Pingree Park). Spotting was occurring 1/2 mile in advance of the fire. By this time personnel/engines from Colorado State

380

Slurry fired heater cold-flow modelling  

SciTech Connect (OSTI)

This report summarizes the experimental and theoretical work leading to the scale-up of the SRC-I Demonstration Plant slurry fired heater. The scale-up involved a theoretical model using empirical relations in the derivation, and employed variables such as flow conditions, liquid viscosity, and slug frequency. Such variables have been shown to affect the heat transfer characteristics ofthe system. The model assumes that, if all other variables remain constant, the heat transfer coefficient can be scaled up proportional to D/sup -2/3/ (D = inside diameter of the fired heater tube). All flow conditions, liquid viscosities, and pipe inclinations relevant to the demonstration plant have indicated a slug flow regime in the slurry fired heater. The annular and stratified flow regimes should be avoided to minimize the potential for excessive pipe erosion and to decrease temperature gradients along the pipe cross section leading to coking and thermal stresses, respectively. Cold-flow studies in 3- and 6.75-in.-inside-diameter (ID) pipes were conducted to determine the effect of scale-up on flow regime, slug frequency, and slug dimensions. The developed model assumes that conduction heat transfer occurs through the liquid film surrounding the gas slug and laminar convective heat transfer to the liquid slug. A weighted average of these two heat transfer mechanisms gives a value for the average pipe heat transfer coefficient. The cold-flow work showed a decrease in the observed slug frequency between the 3- and 6.75-ID pipes. Data on the ratio of gas to liquid slug length in the 6.75-in. pipe are not yet complete, but are expected to yield generally lower values than those obtained in the 3-in. pipe; this will probably affect the scale-up to demonstration plant conditions. 5 references, 15 figures, 7 tables.

Moujaes, S.F.

1983-07-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


381

Evaluating fuel complexes for fire hazard mitigation planning in the southeastern United States.  

SciTech Connect (OSTI)

Fire hazard mitigation planning requires an accurate accounting of fuel complexes to predict potential fire behavior and effects of treatment alternatives. In the southeastern United States, rapid vegetation growth coupled with complex land use history and forest management options requires a dynamic approach to fuel characterization. In this study we assessed potential surface fire behavior with the Fuel Characteristic Classification System (FCCS), a tool which uses inventoried fuelbed inputs to predict fire behavior. Using inventory data from 629 plots established in the upper Atlantic Coastal Plain, South Carolina, we constructed FCCS fuelbeds representing median fuel characteristics by major forest type and age class. With a dry fuel moisture scenario and 6.4 km h{sub 1} midflame wind speed, the FCCS predicted moderate to high potential fire hazard for the majority of the fuelbeds under study. To explore fire hazard under potential future fuel conditions, we developed fuelbeds representing the range of quantitative inventorydata for fuelbed components that drive surface fire behavior algorithms and adjusted shrub species composition to represent 30% and 60% relative cover of highly flammable shrub species. Results indicate that the primary drivers of surface fire behavior vary by forest type, age and surface fire behavior rating. Litter tends to be a primary or secondary driver in most forest types. In comparison to other surface fire contributors, reducing shrub loading results in reduced flame lengths most consistently across forest types. FCCS fuelbeds and the results from this project can be used for fire hazard mitigation planning throughout the southern Atlantic Coastal Plain where similar forest types occur. The approach of building simulated fuelbeds across the range of available surface fuel data produces sets of incrementally different fuel characteristics that can be applied to any dynamic forest types in which surface fuel conditions change rapidly.

Andreu, Anne G.; Shea, Dan; Parresol, Bernard, R.; Ottmar, Roger, D.

2012-01-01T23:59:59.000Z

382

Tracking New Coal-Fired Power Plants  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

New Coal-Fired Power Plants New Coal-Fired Power Plants (data update 1/13/2012) January 13, 2012 National Energy Technology Laboratory Office of Strategic Energy Analysis & Planning Erik Shuster 2 Tracking New Coal-Fired Power Plants This report is intended to provide an overview of proposed new coal-fired power plants that are under development. This report may not represent all possible plants under consideration but is intended to illustrate the potential that exists for installation of new coal-fired power plants. Additional perspective has been added for non-coal-fired generation additions in the U.S. and coal-fired power plant activity in China. Experience has shown that public announcements of power plant developments do not provide an accurate representation of eventually

383

Pigments which reflect infrared radiation from fire  

DOE Patents [OSTI]

Conventional paints transmit or absorb most of the intense infrared (IR) radiation emitted by fire, causing them to contribute to the spread of fire. The present invention comprises a fire retardant paint additive that reflects the thermal IR radiation emitted by fire in the 1 to 20 micrometer (.mu.m) wavelength range. The important spectral ranges for fire control are typically about 1 to about 8 .mu.m or, for cool smoky fires, about 2 .mu.m to about 16 .mu.m. The improved inventive coatings reflect adverse electromagnetic energy and slow the spread of fire. Specific IR reflective pigments include titanium dioxide (rutile) and red iron oxide pigments with diameters of about 1 .mu.m to about 2 .mu.m and thin leafing aluminum flake pigments.

Berdahl, Paul H. (Oakland, CA)

1998-01-01T23:59:59.000Z

384

Pigments which reflect infrared radiation from fire  

DOE Patents [OSTI]

Conventional paints transmit or absorb most of the intense infrared (IR) radiation emitted by fire, causing them to contribute to the spread of fire. The present invention comprises a fire retardant paint additive that reflects the thermal IR radiation emitted by fire in the 1 to 20 micrometer ({micro}m) wavelength range. The important spectral ranges for fire control are typically about 1 to about 8 {micro}m or, for cool smoky fires, about 2 {micro}m to about 16 {micro}m. The improved inventive coatings reflect adverse electromagnetic energy and slow the spread of fire. Specific IR reflective pigments include titanium dioxide (rutile) and red iron oxide pigments with diameters of about 1 {micro}m to about 2 {micro}m and thin leafing aluminum flake pigments. 4 figs.

Berdahl, P.H.

1998-09-22T23:59:59.000Z

385

Error-eliminating rapid ultrasonic firing  

DOE Patents [OSTI]

A system for producing reliable navigation data for a mobile vehicle, such as a robot, combines multiple range samples to increase the confidence'' of the algorithm in the existence of an obstacle. At higher vehicle speed, it is crucial to sample each sensor quickly and repeatedly to gather multiple samples in time to avoid a collision. Erroneous data is rejected by delaying the issuance of an ultrasonic energy pulse by a predetermined wait-period, which may be different during alternate ultrasonic firing cycles. Consecutive readings are compared, and the corresponding data is rejected if the readings differ by more than a predetermined amount. The rejection rate for the data is monitored and the operating speed of the navigation system is reduced if the data rejection rate is increased. This is useful to distinguish and eliminate noise from the data which truly represents the existence of an article in the field of operation of the vehicle.

Borenstein, J.; Koren, Y.

1993-08-24T23:59:59.000Z

386

Error-eliminating rapid ultrasonic firing  

DOE Patents [OSTI]

A system for producing reliable navigation data for a mobile vehicle, such as a robot, combines multiple range samples to increase the "confidence" of the algorithm in the existence of an obstacle. At higher vehicle speed, it is crucial to sample each sensor quickly and repeatedly to gather multiple samples in time to avoid a collision. Erroneous data is rejected by delaying the issuance of an ultrasonic energy pulse by a predetermined wait-period, which may be different during alternate ultrasonic firing cycles. Consecutive readings are compared, and the corresponding data is rejected if the readings differ by more than a predetermined amount. The rejection rate for the data is monitored and the operating speed of the navigation system is reduced if the data rejection rate is increased. This is useful to distinguish and eliminate noise from the data which truly represents the existence of an article in the field of operation of the vehicle.

Borenstein, Johann (Ann Arbor, MI); Koren, Yoram (Ann Arbor, MI)

1993-08-24T23:59:59.000Z

387

Design and implementation of a dedicated prototype GIS for coal fire investigations in North China  

Science Journals Connector (OSTI)

This paper presents the design architecture and functioning of CoalMan, a tailor made Geographic Information System (GIS) for managing surface and underground fires in coal mining areas. CoalMan is specially designed for and installed in the Rujigou coal field in north-west China. It uses ILWIS as the supporting GIS package. It functions through its database and management tools, processing and analysis tools and featured display tools. The processing and analysis tools are uniquely designed to detect, map, and monitor coal mine fires in time. These tools also help to generate maps showing fire depth, fire risk and priority for fire fighting. The display tools help to generate cross-sectional views along any selected profile line in the study area. CoalMan has a bilingual interface and has a potential to be adapted to other coal mining areas facing similar problems.

Anupma Prakash; Zoltn Vekerdy

2004-01-01T23:59:59.000Z

388

Parallel Chip-Firing on the Complete Graph: Devil's Staircase and Poincare Rotation Number  

E-Print Network [OSTI]

We study how parallel chip-firing on the complete graph K_n changes behavior as we vary the total number of chips. Surprisingly, the activity of the system, defined as the average number of firings per time step, does not increase smoothly in the number of chips; instead it remains constant over long intervals, punctuated by sudden jumps. In the large n limit we find a "devil's staircase" dependence of activity on the number of chips. The proof proceeds by reducing the chip-firing dynamics to iteration of a self-map of the circle S^1, in such a way that the activity of the chip-firing state equals the Poincare rotation number of the circle map. The stairs of the devil's staircase correspond to periodic chip-firing states of small period.

Levine, Lionel

2008-01-01T23:59:59.000Z

389

Forecast of Advanced Technology Adoption for Coal Fired Power Generation Towards the Year of 2050  

Science Journals Connector (OSTI)

The considered systems of coal fired power generation are Supercritical Unit, Ultra Supercritical Unit, ... . In order to compare with the natural gas case, Natural Gas Combined Cycle (NGCC) is included. Evaluati...

Keiji Makino

2013-01-01T23:59:59.000Z

390

Fire hazard analysis for the fuel supply shutdown storage buildings  

SciTech Connect (OSTI)

The purpose of a fire hazards analysis (FHA) is to comprehensively assess the risk from fire and other perils within individual fire areas in a DOE facility in relation to proposed fire protection so as to ascertain whether the objectives of DOE 5480.7A, Fire Protection, are met. This Fire Hazards Analysis was prepared as required by HNF-PRO-350, Fire Hazards Analysis Requirements, (Reference 7) for a portion of the 300 Area N Reactor Fuel Fabrication and Storage Facility.

REMAIZE, J.A.

2000-09-27T23:59:59.000Z

391

Monitored Geologic Repository Operations Monitoring and Control System Description Document  

SciTech Connect (OSTI)

The Monitored Geologic Repository Operations Monitoring and Control System provides supervisory control, monitoring, and selected remote control of primary and secondary repository operations. Primary repository operations consist of both surface and subsurface activities relating to high-level waste receipt, preparation, and emplacement. Secondary repository operations consist of support operations for waste handling and treatment, utilities, subsurface construction, and other selected ancillary activities. Remote control of the subsurface emplacement operations, as well as, repository performance confirmation operations are the direct responsibility of the system. In addition, the system monitors parameters such as radiological data, air quality data, fire detection status, meteorological conditions, unauthorized access, and abnormal operating conditions, to ensure a safe workplace for personnel. Parameters are displayed in a real-time manner to human operators regarding surface and subsurface conditions. The system performs supervisory monitoring and control for both important to safety and non-safety systems. The system provides repository operational information, alarm capability, and human operator response messages during emergency response situations. The system also includes logic control to place equipment, systems, and utilities in a safe operational mode or complete shutdown during emergency response situations. The system initiates alarms and provides operational data to enable appropriate actions at the local level in support of emergency response, radiological protection response, evacuation, and underground rescue. The system provides data communications, data processing, managerial reports, data storage, and data analysis. This system's primary surface and subsurface operator consoles, for both supervisory and remote control activities, will be located in a Central Control Center (CCC) inside one of the surface facility buildings. The system consists of instrument and control equipment and components necessary to provide human operators with sufficient information to monitor and control the operation of the repository in an efficient and safe manner. The system consists of operator consoles and workstations, multiple video display terminals, communications and interfacing equipment, and instrument and control software with customized configuration to meet the needs of the Monitored Geologic Repository (MGR). Process and logic controllers and the associated input/output units of each system interfaced with this system will be configured into Remote Terminal Units (RTU) and located close to the systems to be monitored and controlled. The RTUs are configured to remain operational should communication with CCC operations be lost. The system provides closed circuit television to selectively view systems, operations, and equipment areas and to aid in the operation of mechanical systems. Control and monitoring of site utility systems will be located in the CCC. Site utilities include heating, ventilation, and air conditioning equipment; plant compressed air; plant water; firewater; electrical systems; and inert gases, such as nitrogen, if required. This system interfaces with surface and subsurface systems that either generate output data or require remote control input. The system interfaces with the Site Communications System for bulk storage of operational data, on-site and off-site communication, and a plant-wide public announcement system. The system interfaces with the Safeguards and Security System to provide operational status and emergency alarm indications. The system interfaces with the Site Operation System to provide site wide acquisition of data for analysis and reports, historical information for trends, utility information for plant operation, and to receive operating plans and procedures.

E.F. Loros

2000-06-29T23:59:59.000Z

392

THE HYPOTHETICAL EFFECTS ON VADOSE ZONE & GROUNDWATER CONTAMINATION BY FIRE SUPPRESSION OF HANFORD SITE BUILDINGS AWAITING DECOMMISSIONING  

SciTech Connect (OSTI)

Numerical modeling was used to assess the effects of nearby contamination of hypothetical fire-suppression activities. The modeling focused on the 333 Building as being representative of a ''worst case'' situation in deactivated buildings at the Hanford Nuclear Site in Washington State. For purposes of the analysis, the fire-suppression sprinkler systems of these buildings were assumed to have been deactivated, requiring that the hypothetical fires be extinguished using water supplied by nearby fire hydrants. The amount of water specified by Fire-Protection personnel as needed to extinguish a hypothetical fire was specified as 1,500 gpm for 2 hours, for a total of 180,000 gallons or about 681 m{sup 3}.

DAVIS, J.D.

2005-03-18T23:59:59.000Z

393

How to Choose and Use Fire Extinguishers  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

How to Choose and Use Fire Extinguishers How to Choose and Use Fire Extinguishers By: John Kelsey, This Old House magazine A fire extinguisher can be a lifesaver. Placed near an exit, in an easy-to-grab spot, it can put out a small fire before the firefighters arrive, or at least suppress the flames while you escape. All household extinguishers are classified A, B, or C (or a combination of these) on the label to indicate which types of fires - ordinary combustibles, flammable liquids, or electrical-you can use them on. Many of the ones sold at home stores are classified A:B:C and fight all three types of fires. The main distinction among home extinguishers is size. In most cases bigger is better, but sometimes the biggest extinguishers are too heavy to maneuver. (The weight on an extinguisher refers to

394

FAQS Job Task Analyses - Fire Protection Engineering  

Broader source: Energy.gov (indexed) [DOE]

Job Task Analysis and Competency Review Job Task Analysis and Competency Review for All Level Competencies Fire Protection Engineering FAQS Initially conducted (expert competencies): August 2010 Updated (includes ALL Competencies): April 2011 Updated (includes ALL Competencies): October 2012 STEP 1: Job Task Analysis for Tasks Task (and Number) Source Importance Frequency Serve as the subject matter expert in the area of fire protection, life safety, and fire department emergency related services. FAQS Duties and Responsibilities Paragraph A 5 4 Review fire hazard analyses, assessments, and other fire safety documentation for compliance with applicable requirements. FAQS Duties and Responsibilities Paragraph B 5 3 Evaluate the adequacy of site emergency services. This includes all facets of the fire

395

Stirling engines for gas fired micro-cogen and cooling  

SciTech Connect (OSTI)

This paper describes the design and performance of free-piston Stirling engine-alternators particularly suited for use as natural gas fired micro-cogen and cooling devices. Stirling based cogen systems offer significant potential advantages over internal combustion engines in efficiency, to maintain higher efficiencies at lower power levels than than combustion engines significantly expands the potential for micro-cogen. System cost reduction and electric prices higher than the U.S. national average will have a far greater effect on commercial success than any further increase in Stirling engine efficiency. There exist niche markets where Stirling engine efficiency. There exist niche markets where Stirling based cogen systems are competitive. Machines of this design are being considered for production in the near future as gas-fired units for combined heat and power in sufficiently large quantities to assure competitive prices for the final unit.

Lane, N.W.; Beale, W.T. [Sunpower, Inc., Athens, OH (United States)

1996-12-31T23:59:59.000Z

396

Subtask 3.12 - Oxygen-Fired CFBC  

SciTech Connect (OSTI)

Traditionally, air is used as the source of oxygen for firing a combustion system. A fully oxygen-fired circulating fluidized-bed combustion (CFBC) system would result in the production of a flue gas stream consisting of mostly carbon dioxide and water. The concentrated carbon dioxide stream would be available for sequestering or other purposes. Temperatures in an oxygen-blown CFBC system would be controlled by a combination of flue gas recycle, solids recirculation, and by appropriately sizing and locating the amount of heat-transfer surface required. Flue gas recycle provides the additional gas required for adequate fluidization and circulation of solids replacing the nitrogen that would be present in an air-blown system. The amount of flue gas recycle will determine how much of the remaining heat from the coal combustion will have to be removed. If the amount of flue gas recycle required by increasing solids recirculation and oxygen staging is limited, introducing the pure oxygen at multiple locations in the combustor to result in a more even temperature profile should result in a more compact system, thus reducing initial capital costs for construction. The overall efficiency of the process should be greater than that of an air-blown system since less fuel is required for the creation of the same amount of energy. The Energy & Environmental Research Center (EERC) is in a unique position to advance this technology. It has a world-class CFBC pilot plant, has experience with firing a wide range of fuels in our air-fired CFBC pilot plant, has prior experience with oxygen-firing a slagging furnace system in a pulverized coal-fired mode with a bituminous coal, and has all of the components required for oxygen-firing right next to the CFBC pilot plant already in place. An engineering study was performed to identify methods, an overall appropriate configuration, and an operating strategy for a fully oxygen-fired CFBC pilot plant by: (1) developing a plan to optimize the amount of flue gas recycle required to control bed temperature; (2) determining how to best utilize the heat-transfer surfaces in a CFBC pilot plant, such as increased external bed surface, to more beneficially use increased solids recycle; (3) identifying appropriate methods for staged addition of the oxygen/recycled flue gas streams to maintain a good temperature profile in the combustor; and (4) determining the level of effort required to convert the EERC CFBC pilot plant to one that is oxygen-blown. The EERC additionally used its experience to consider what would be required for firing a wide range of fuels from biomass to low-rank coals to high-rank coals and petroleum cokes. These proposed modifications will be performed based upon obtaining the required funding.

Douglas Hajicek; Mark Musich; Ann Henderson

2007-02-28T23:59:59.000Z

397

Fire Hazard Analysis for the Cold Vacuum Drying (CVD) Facility  

SciTech Connect (OSTI)

This Fire Hazard Analysis assesses the risk from fire within individual fire areas in the Cold Vacuum Drying Facility at the Hanford Site in relation to existing or proposed fire protection features to ascertain whether the objectives of DOE Order 5480.7A Fire Protection are met.

JOHNSON, B.H.

1999-08-19T23:59:59.000Z

398

TU Vienna Fire Protection Regulations 1 General provisions  

E-Print Network [OSTI]

TU Vienna Fire Protection Regulations § 1 General provisions § 2 Scope § 3 Responsibility for preventive fire protection § 7 Conduct in the event of fire § 8 Assembly point § 9 Measures following a fire § 1 General provisions (1) Purpose and relationship to other legal regulations a) The fire protection

Szmolyan, Peter

399

Interagency Panel: Agency Fire Management Chair: Philip N. Omi  

E-Print Network [OSTI]

of Forestry and Fire Protection: Fire Management Summary1 Wayne Mitchell2 Abstract The California Department of Forestry and Fire Protection (CDF) is a full service wildland, rural, and urban fire department. CDF acres. About 55 percent of CDF's $452 million annual budget is used for wildland fire protection

Standiford, Richard B.

400

Cryogenic slurry for extinguishing underground fires  

DOE Patents [OSTI]

A cryogenic slurry comprising a mixture of solid carbon dioxide particles suspended in liquid nitrogen is provided which is useful in extinguishing underground fires.

Chaiken, Robert F. (Pittsburgh, PA); Kim, Ann G. (Pittsburgh, PA); Kociban, Andrew M. (Wheeling, WV); Slivon, Jr., Joseph P. (Tarentum, PA)

1994-01-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


401

Sandia National Laboratories: National Fire Protection Association  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Fire Protection Association More California Gas Stations Can Provide Hydrogen than Previously Thought, Sandia Study Says On July 29, 2014, in Center for Infrastructure Research and...

402

Contained Firing Facility | National Nuclear Security Administration  

National Nuclear Security Administration (NNSA)

Contained Firing Facility | National Nuclear Security Administration Contained Firing Facility | National Nuclear Security Administration Our Mission Managing the Stockpile Preventing Proliferation Powering the Nuclear Navy Emergency Response Recapitalizing Our Infrastructure Continuing Management Reform Countering Nuclear Terrorism About Us Our Programs Our History Who We Are Our Leadership Our Locations Budget Our Operations Media Room Congressional Testimony Fact Sheets Newsletters Press Releases Speeches Events Social Media Video Gallery Photo Gallery NNSA Archive Federal Employment Apply for Our Jobs Our Jobs Working at NNSA Blog Contained Firing Facility Home > About Us > Our Programs > Defense Programs > Office of Research, Development, Test, and Evaluation > Office of Research and Development > Facilities > Contained Firing Facility

403

Summary of fire protection programs of the United States Department of Energy  

SciTech Connect (OSTI)

This edition of the Annual Summary of DOE Fire Protection Programs continues the series started in 1972. Since May 1950, an annual report has been required from each field organization. The content has varied through the years and most of the accident data reporting requirements have been superseded by the Computerized Accident/Incident Reporting System administered by EG G, Idaho. However, this report is the sole source of information relating to fire protection programs, and to the actions of the field offices and to headquarters that are of general fire protection interest.

Not Available

1991-10-01T23:59:59.000Z

404

(BSET) FIRE SAFETY ENGINEERING TECHNOLOGY CURRICULUM FOUR YEAR FIRE SAFETY CONCENTRATION CURRICULUM  

E-Print Network [OSTI]

. ETFS 4323 3 Intro to Performance-based Fire Safety8 ETFS 32338 3 Ethical Issues and Cultural Critique3(BSET) FIRE SAFETY ENGINEERING TECHNOLOGY CURRICULUM FOUR YEAR FIRE SAFETY CONCENTRATION CURRICULUM 3 Technical Drawing I ETGR 1103 2 Western Culture and Hist. Awareness LBST 2101 3 Total Hours 16

Raja, Anita

405

What is prescribed fire? Prescribed fire is the controlled application of  

E-Print Network [OSTI]

What is prescribed fire? Prescribed fire is the controlled application of fire to the land an uncontrolled wildfire occur. What is a burn prescription? A burn prescription helps ensure that the objectives species to naturally regenerate. (Lodgepole pine is one such example.) What about the smoke? Controlling

406

Housing & Residence Education Disclosure of Fire Safety Standards and Measures 1 Campus Fire Safety Right-to-Know  

E-Print Network [OSTI]

Housing & Residence Education Disclosure of Fire Safety Standards and Measures 1 Campus Fire Safety and death resulting from each fire. #12;Housing & Residence Education Disclosure of Fire Safety Standards) -- HVAC fan motor burned up -- Alpha Chi Omega -- 3/13/10 $1,500 (Greek) -- Futon mattress caught fire

Fang, Yuguang "Michael"

407

Housing & Residence Education Disclosure of Fire Safety Standards and Measures 1 Campus Fire Safety Right-to-Know  

E-Print Network [OSTI]

Housing & Residence Education Disclosure of Fire Safety Standards and Measures 1 Campus Fire Safety and death resulting from each fire. #12;Housing & Residence Education Disclosure of Fire Safety Standards) -- Grease Fire -- Beaty Towers -- 9/10/10 $100 (Greek) -- HVAC fan motor burned up -- Alpha Chi Omega -- 3

Slatton, Clint

408

Sample Lesson Plan Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection 1 Sample Lesson Plan  

E-Print Network [OSTI]

, Emergency Action Plans, Fire Prevention Plans, and Fire Protection Overview of the OSHA Standard Subpart E problems finding and using it. Subpart L, Fire Protection, contains requirements for fire brigades, and all installed to meet the fire protection requirements of 29 CFR Part 1910. Step 1: Planning the Lesson

Homes, Christopher C.

409

Mathematical Modeling and Experimental Study of Biomass Combustion in a Thermal 108 MW Grate-Fired Boiler  

E-Print Network [OSTI]

Mathematical Modeling and Experimental Study of Biomass Combustion in a Thermal 108 MW Grate, the noncontinuous biomass feeding and grate movement, the combustion instabilities inside the fuel bed used to fire biomass for heat and power production. However, grate-firing systems are often reported

Rosendahl, Lasse

410

Test Plan to Assess Fire Effects on the Function of an Engineered Surface Barrier  

SciTech Connect (OSTI)

Wildfire is a frequent perturbation in shrub steppe ecosystems, altering the flora, fauna, atmosphere, and soil of these systems. Research on the fire effects has focused mostly on natural ecosystems with essentially no attention on engineered systems like surface barriers. The scope of the project is to use a simulated wildfire to induce changes in an engineered surface barrier and document the effects on barrier performance. The main objective is to quantify the effects of burning and the resulting post-fire conditions on alterations in soil physical properties; hydrologic response, particularly the water balance; geochemical properties; and biological properties. A secondary objective is to use the lessons learned to maximize fire protection in the design of long-term monitoring systems based on electronic sensors. A simulated wildfire will be initiated, controlled and monitored at the 200-BP-1 barrier in collaboration with the Hanford Fire Department during the fall of 2008. The north half of the barrier will be divided into nine 12 x 12 m plots, each of which will be randomly assigned a fuel load of 2 kg m-2 or 4 kg m-2. Each plot will be ignited around the perimeter and flames allowed to carry to the centre. Any remaining unburned vegetation will be manually burned off using a drip torch. Progress of the fire and its effects will be monitored using point measurements of thermal, hydrologic, and biotic variables. Three measures of fire intensity will be used to characterize fire behavior: (1) flame height, (2) the maximum temperature at three vertical profile levels, and (3) total duration of elevated temperature at these levels. Pre-burn plant information, including species diversity, plant height, and canopy diameter will be measured on shrubs from the plots to be burned and from control plots at the McGee ranch. General assessments of shrub survival, recovery, and recruitment will be made after the fire. Near-surface soil samples will be collected pre- and post-burn to determine changes in the gravel content of the surface layer so as to quantify inflationary or deflationary responses to fire and to reveal the ability of the surface to resist post-fire erosive stresses. Measures of bulk density, water repellency, water retention, and hydraulic conductivity will be used to characterize changes in infiltration rates and water storage capacity following the fire. Samples will also be analyzed to quantify geochemical changes including changes in soil pH, cation exchange capacity, specific surface area, and the concentration of macro nutrients (e.g. N, P, K) and other elements such as Na, Mg, Ca, that are critical to the post-fire recovery revegetation. Soil CO2 emissions will be measured monthly for one year following the burn to document post-fire stimulation of carbon turnover and soil biogenic emissions. Surface and subsurface temperature measurements at and near monitoring installations will be used to document fire effects on electronic equipment. The results of this study will be used to bridge the gaps in knowledge on the effects of fire on engineered ecosystems (e.g. surface barriers), particularly the hydrologic and biotic characteristics that govern the water and energy balance. These results will also support the development of practical fire management techniques for barriers that are compatible with wildfire suppression strategies. Furthermore, lessons learned will be use to develop installation strategies needed to protect electronic monitoring equipment from the intense heat of fire and the potential damaging effects of smoke and fire extinguishing agents. Such information is needed to better understand long-term barrier performance under extreme conditions, especially if site maintenance and operational funding is lost for activities such as barrier revegetation.

Ward, Anderson L.; Berlin, Gregory T.; Cammann, Jerry W.; Leary, Kevin D.; Link, Steven O.

2008-09-29T23:59:59.000Z

411

Fire Ecology Special Issue Vol. 5, No. 1, 2009  

E-Print Network [OSTI]

-fire rainfall events. Soil losses in the high end of that range definitely exceed soil loss tolerances, humankind transformed fire into one of its oldest tools. Human and lightning ignited fires altered

412

Old Dominion University Annual Security and Fire Safety Report  

E-Print Network [OSTI]

Protection Features in Residence Halls____________________ 21 Residential Facilities Fire Safety AmenitiesOld Dominion University 2012 Annual Security and Fire Safety Report All statements and policies _________________________________________ 17 Fire Safety ______________________________________________________________ 19 Residence Halls

413

FSEP-Rev.02 Fire Safety Evacuation Plan  

E-Print Network [OSTI]

.......................................................................................... 1 3.2 Fire Protection Authority ............................................................................................... 2 3.5 Fire Protection EquipmentFSEP-Rev.02 Fire Safety Evacuation Plan Henrietta Harvey Building Prepared By: Graham Mowbray Date

Oyet, Alwell

414

Fire Protection Engineering Four Year Academic Plan Name:_______________________________________________ UID:___________________________  

E-Print Network [OSTI]

Fire Protection Engineering Four Year Academic Plan Name;FIRE PROTECTION ENGINEERING NAME: _____________________________________ Major Requirements Requirements Dev Seminar 1 ENFP 405 - Structural Fire Protection 3 Requirements Course Credits Grade ENFP 410

Shapiro, Benjamin

415

FSEP-Rev.02 Fire Safety Evacuation Plan  

E-Print Network [OSTI]

.......................................................................................... 4 3.2 Fire Protection Authority ............................................................................................... 5 3.5 Fire Protection EquipmentFSEP-Rev.02 Fire Safety Evacuation Plan Ocean Sciences Centre Prepared By: Connie Short Date: April

Oyet, Alwell

416

ANNUAL FIRE SAFETY REPORT 2011 Ithaca, NY Campus  

E-Print Network [OSTI]

Plan ____________________________________________________ 14 Cornell University Fire Safety Plan including programs in: Fire Protection, Emergency Services, Emergency Management o Fire Protection Services o Research and Laboratory Safety o Chemical Safety o Radiation Safety o Biological Safe

Chen, Tsuhan

417

Underground Salt Haul Truck Fire at the Waste Isolation Pilot...  

Office of Environmental Management (EM)

Underground Salt Haul Truck Fire at the Waste Isolation Pilot Plant February 5, 2014 March 2014 Salt Haul Truck Fire at the Waste Isolation Pilot Plant Salt Haul Truck Fire at the...

418

Fire Hazard Analysis for the Cold Vacuum Drying facility (CVD) Facility  

SciTech Connect (OSTI)

The CVDF is a nonreactor nuclear facility that will process the Spent Nuclear Fuels (SNF) presently stored in the 105-KE and 105-KW SNF storage basins. Multi-canister overpacks (MCOs) will be loaded (filled) with K Basin fuel transported to the CVDF. The MCOs will be processed at the CVDF to remove free water from the fuel cells (packages). Following processing at the CVDF, the MCOs will be transported to the CSB for interim storage until a long-term storage solution can be implemented. This operation is expected to start in November 2000. A Fire Hazard Analysis (FHA) is required for all new facilities and all nonreactor nuclear facilities, in accordance with U.S. Department of Energy (DOE) Order 5480.7A, Fire Protection. This FHA has been prepared in accordance with DOE 5480.7A and HNF-PRO-350, Fire Hazard Analysis Requirements. Additionally, requirements or criteria contained in DOE, Richland Operations Office (RL) RL Implementing Directive (RLID) 5480.7, Fire Protection, or other DOE documentation are cited, as applicable. This FHA comprehensively assesses the risk of fire at the CVDF to ascertain whether the specific objectives of DOE 5480.7A are met. These specific fire protection objectives are: (1) Minimize the potential for the occurrence of a fire. (2) Ensure that fire does not cause an onsite or offsite release of radiological and other hazardous material that will threaten the public health and safety or the environment. (3) Establish requirements that will provide an acceptable degree of life safety to DOE and contractor personnel and ensure that there are no undue hazards to the public from fire and its effects in DOE facilities. (4) Ensure that vital DOE programs will not suffer unacceptable delays as a result of fire and related perils. (5) Ensure that property damage from fire and related perils does not exceed an acceptable level. (6) Ensure that process control and safety systems are not damaged by fire or related perils. This FHA is based on the facility as constructed and with planned operation at the time of document preparation. Changes in facility planned and actual operation require that the identified fire risks associated with the CVDF be re-evaluated. Consequently, formal documentation and future revision of this FHA may be required.

SINGH, G.

2000-09-06T23:59:59.000Z

419

Scheduling screening inspections for replaceable and non-replaceable systems  

E-Print Network [OSTI]

This dissertation focuses on developing inspection schedules to detect non-self- announcing events which can only detected by inspections. Failures of protective sys- tems ,such as electronic equipments, alarms and stand-by systems, incipient...

Aral, Bahadir

2009-05-15T23:59:59.000Z

420

Bagasse-fired steam boiler station for Kenana Sugar in Sudan  

SciTech Connect (OSTI)

The equipment and operation of the bagasse fired steam boiler station of the Kenana Sugar factory in Sudan are described. The station consists of six bagasse-fired, steam boilers with individual capacities of 113 tonnes per hour which provide steam for a 40 MN power station. During the off-season it serves as a regional power station which also operates irrigation facilities to the cane fields. The bagasse handling and feeding system is also described.

Not Available

1981-02-01T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


421

Live Fire Range Environmental Assessment  

SciTech Connect (OSTI)

The Central Training Academy (CTA) is a DOE Headquarters Organization located in Albuquerque, New Mexico, with the mission to effectively and efficiently educate and train personnel involved in the protection of vital national security interests of DOE. The CTA Live Fire Range (LFR), where most of the firearms and tactical training occurs, is a complex separate from the main campus. The purpose of the proposed action is to expand the LFR to allow more options of implementing required training. The Department of Energy has prepared this Environmental Assessment (EA) for the proposed construction and operation of an expanded Live Fire Range Facility at the Central Training Academy in Albuquerque, New Mexico. Based on the analysis in the EA, DOE has determined that the proposed action is not a major Federal action significantly affecting the quality of the human environment, within the meaning of the National Environmental Policy Act (NEPA) of 1969. Therefore, the preparation of an environmental impact statement is not required and DOE is issuing this Finding of No Significant Impact (FONSI).

None

1993-08-01T23:59:59.000Z

422

Functions and Requirements and Specifications for Replacement of the Computer Automated Surveillance System (CASS)  

SciTech Connect (OSTI)

This functions, requirements and specifications document defines the baseline requirements and criteria for the design, purchase, fabrication, construction, installation, and operation of the system to replace the Computer Automated Surveillance System (CASS) alarm monitoring.

SCAIEF, C.C.

1999-12-16T23:59:59.000Z

423

O:\\AVP\\EHS\\EH&S #20-Contractors-MinorProjects.doc Page 1 of 3 Environmental Health & Safety  

E-Print Network [OSTI]

a fire hazard, put themselves or any occupant at risk, cause a false alarm or damage any fire protection response. The contractor shall provide fire watch if the fire protection system of an occupied building of minor projects in order to ensure the protection of persons, property and the environment. The prime

Fernandez, Eduardo

424

Fire and explosion hazards of oil shale  

SciTech Connect (OSTI)

The US Bureau of Mines publication presents the results of investigations into the fire and explosion hazards of oil shale rocks and dust. Three areas have been examined: the explosibility and ignitability of oil shale dust clouds, the fire hazards of oil shale dust layers on hot surfaces, and the ignitability and extinguishment of oil shale rubble piles. 10 refs., 54 figs., 29 tabs.

Not Available

1989-01-01T23:59:59.000Z

425

Managing Imported Fire Ants in Urban Areas  

E-Print Network [OSTI]

The imported fire ant is found in much of Texas and across the southeastern U.S. This publication describes options for managing the pest in specific locations such as home lawns, gardens and buildings. Other topics include fire ant treatment...

Drees, Bastiaan M.

2006-08-17T23:59:59.000Z

426

The Fire Walk Ceremony in Tahiti  

Science Journals Connector (OSTI)

... all essential particulars with those in the accounts already cited. According to these, a pit was dug in which large stones were heated red hot by a fire which had ... dug in which large stones were heated red hot by a fire which had been burning many hours. The upper stones were pushed away just before the ceremony, so as ...

S. P. LANGLEY

1901-08-22T23:59:59.000Z

427

Modeling long-term fire regimes of southern California shrublands1 (Suggested running head: "Modeling fire regimes with HFire")3  

E-Print Network [OSTI]

of three fire regime metrics (fire size24 distributions, fire return interval maps, cumulative total area pattern of ignitions, fuels, weather,38 and topography, and describes the size, spatial pattern

Carlson, Jean

428

Commercialization Development of Oxygen Fired CFB for Greenhouse Gas Control  

SciTech Connect (OSTI)

Given that fossil fuel fired power plants are among the largest and most concentrated producers of CO{sub 2} emissions, recovery and sequestration of CO{sub 2} from the flue gas of such plants has been identified as one of the primary means for reducing anthropogenic (i.e., man-made) CO{sub 2} emissions. In 2001, ALSTOM Power Inc. (ALSTOM) began a two-phase program to investigate the feasibility of various carbon capture technologies. This program was sponsored under a Cooperative Agreement from the US Department of Energy's National Energy Technology Laboratory (DOE). The first phase entailed a comprehensive study evaluating the technical feasibility and economics of alternate CO{sub 2} capture technologies applied to Greenfield US coal-fired electric generation power plants. Thirteen cases, representing various levels of technology development, were evaluated. Seven cases represented coal combustion in CFB type equipment. Four cases represented Integrated Gasification Combined Cycle (IGCC) systems. Two cases represented advanced Chemical Looping Combined Cycle systems. Marion, et al. reported the details of this work in 2003. One of the thirteen cases studied utilized an oxygen-fired circulating fluidized bed (CFB) boiler. In this concept, the fuel is fired with a mixture of oxygen and recirculated flue gas (mainly CO{sub 2}). This combustion process yields a flue gas containing over 80 percent (by volume) CO{sub 2}. This flue gas can be processed relatively easily to enrich the CO{sub 2} content to over 96 percent for use in enhanced oil or gas recovery (EOR or EGR) or simply dried for sequestration. The Phase I study identified the O{sub 2}-fired CFB as having a near term development potential, because it uses conventional commercial CFB technology and commercially available CO{sub 2} capture enabling technologies such as cryogenic air separation and simple rectification or distillation gas processing systems. In the long term, air separation technology advancements offer significant reductions in power requirements, which would improve plant efficiency and economics for the oxygen-fired technology. The second phase consisted of pilot-scale testing followed by a refined performance and economic evaluation of the O{sub 2} fired CFB concept. As a part of this workscope, ALSTOM modified its 3 MW{sub th} (9.9 MMBtu/hr) Multiuse Test Facility (MTF) pilot plant to operate with O{sub 2}/CO{sub 2} mixtures of up to 70 percent O{sub 2} by volume. Tests were conducted with coal and petroleum coke. The test objectives were to determine the impacts of oxygen firing on heat transfer, bed dynamics, potential agglomeration, and gaseous and particulate emissions. The test data results were used to refine the design, performance, costs, and economic models developed in Phase-I for the O{sub 2}-fired CFB with CO{sub 2} capture. Nsakala, Liljedahl, and Turek reported results from this study in 2004. ALSTOM identified several items needing further investigation in preparation for large scale demonstration of the oxygen-fired CFB concept, namely: (1) Operation and performance of the moving bed heat exchanger (MBHE) to avoid recarbonation and also for cost savings compared to the standard bubbling fluid bed heat exchanger (FBHE); (2) Performance of the back-end flash dryer absorber (FDA) for sulfur capture under high CO{sub 2}/high moisture flue gas environment using calcined limestone in the fly ash and using fresh commercial lime directly in the FDA; (3) Determination of the effect of recarbonation on fouling in the convective pass; (4) Assessment of the impact of oxygen firing on the mercury, other trace elements, and volatile organic compound (VOC) emissions; and (5) Develop a proposal-level oxygen-fired retrofit design for a relatively small existing CFB steam power plant in preparation for a large-scale demonstration of the O{sub 2} fired CFB concept. Hence, ALSTOM responded to a DOE Solicitation to address all these issues with further O{sub 2} fired MTF pilot testing and a subsequent retrofit design study of oxygen firing and CO{s

Nsakala ya Nsakala; Gregory N. Liljedahl; David G. Turek

2007-03-31T23:59:59.000Z

429

CRAD, Fire Protection - Oak Ridge National Laboratory High Flux...  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection - Oak Ridge National Laboratory High Flux Isotope Reactor CRAD, Fire Protection - Oak Ridge National Laboratory High Flux Isotope Reactor February 2006 A section of...

430

The Simulation Analysis of Fire Feature on Underground Substation  

Science Journals Connector (OSTI)

Underground transformer substations constructed with non-dwelling buildings have a ... out simulation analysis of fire feature on underground substation. The corresponding fire protection strategy is also...

Xin Han; Xie He; Beihua Cong

2012-01-01T23:59:59.000Z

431

Suspension-fired biomass boilers. Three case studies  

SciTech Connect (OSTI)

A discussion of the conversion of oil-or gas-fired boilers to fire pulverized bark and wood wastes in suspension.

Robinson, L.

1986-01-01T23:59:59.000Z

432

Sandia National Laboratories: Sandia Study Shows Large LNG Fires...  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

ClimateECInfrastructure SecurityAnalysisSandia Study Shows Large LNG Fires Hotter but Smaller Than Expected Sandia Study Shows Large LNG Fires Hotter but Smaller Than Expected...

433

An integrated approach to fire penetration seal program management  

SciTech Connect (OSTI)

This paper discusses the utilization of a P.C. based program to facilitate the management of Entergy Operations Arkansas Nuclear One (ANO) fire barrier penetration seal program. The computer program was developed as part of a streamlining process to consolidate all aspects of the ANO Penetration Seal Program under one system. The program tracks historical information related to each seal such as maintenance activities, design modifications and evaluations. The program is integrated with approved penetration seal design details which have been substantiated by full scale fire tests. This control feature is intended to prevent the inadvertent utilization of an unacceptable penetration detail in a field application which may exceed the parameters tested. The system is also capable of controlling the scope of the periodic surveillance of penetration seals by randomly selecting the inspection population and generating associated inspection forms. Inputs to the data base are required throughout the modification and maintenance process to ensure configuration control and maintain accurate data base information. These inputs are verified and procedurally controlled by Fire Protection Engineering (FPE) personnel. The implementation of this system has resulted in significant cost savings and has minimized the allocation of resources necessary to ensure long term program viability.

Rispoli, R.D. [Entergy Operations, Russellville, AR (United States)

1996-07-01T23:59:59.000Z

434

Version 2 Global Fire Emissions Database Available  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Global Fire Emissions Database Available Global Fire Emissions Database Available The ORNL DAAC announces the release of the data set "Global Fire Emissions Database, Version 2 (GFEDv2)." This data set, which supersedes and replaces the Global Fire Emissions Database, Version 1 (GFEDv1), consists of 1 degree x 1 degree gridded monthly burned area, fuel loads, combustion completeness, and fire emissions of carbon (C), carbon dioxide (CO2), carbon monoxide (CO), methane (CH4), non-methane hydrocarbons (NMHC), molecular hydrogen (H2), nitrogen oxides (NOx), nitrous oxide (N2O), particulate matter (PM2.5), total particulate matter (TPM), total carbon (TC), organic carbon (OC), and black carbon (BC) for the time period January 1997 - December 2004. For more information or to access this data set, please see the Vegetation

435

t_fired.p65  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

-MWE DEMONSTRATION OF ADVANCED -MWE DEMONSTRATION OF ADVANCED TANGENTIALLY FIRED COMBUSTION TECHNIQUES FOR THE REDUCTION OF NO X EMISSIONS SOUTHERN COMPANY SERVICES, INC. PROJECT PERFORMANCE SUMMARY CLEAN COAL TECHNOLOGY DEMONSTRATION PROGRAM JUNE 1999 DOE/FE-0397 Disclaimer This report was prepared using publically available information, including the Final Technical Report and other reports prepared pursuant to a cooperative agreement partially funded by the U.S. Department of Energy. Neither the United States Government nor any agency, employee, contractor, or representative thereof, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe upon privately

436

Coal-Fired Power Plants  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Impacts of TMDLs on Impacts of TMDLs on Coal-Fired Power Plants April 2010 DOE/NETL-2010/1408 Disclaimer This report was prepared as an account of work sponsored by an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference therein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof. The

437

Kuwaiti oil fires: Composition of source smoke  

SciTech Connect (OSTI)

While the Kuwaiti oil-fire smoke plumes manifested a pronounced impact on solar radiation in the Gulf region (visibility, surface temperatures, etc.), smoke plume concentrations of combustion-generated pollutants suggest that the overall chemical impact on the atmosphere of the smoke from these fires was probably much less than anticipated. Combustion in the Kuwaiti oil fires was surprisingly efficient, releasing on average more than 93% of the combusted hydrocarbon fuels as carbon dioxide (CO{sub 2}). Correspondingly, combustion-produced quantities of carbon monoxide (CO) and carbonaceous particles were low, each {approximately} 2% by weight. The fraction of methane (CH{sub 4}) produced by the fires was also relatively low ({approximately} 0.2%), but source emissions of nonmethane hydrocarbons were high ({approximately} 2%). Processes other than combustion (e.g., volatilization) probably contributed significantly to the measured in-plume hydrocarbon concentrations. Substantially, different elemental to organic carbon ratios were obtained for aerosol particles from several different types of fires/smokes. Sulfur emissions (particulate and gaseous) measured at the source fires were lower ({approximately} 0.5%) than predicted based on average sulfur contents in the crude. Sulfur dioxide measurements (SO{sub 2}) reported herein, however, were both limited in actual number and in the number of well fires sampled. Nitrous oxide (N{sub 2}O) emissions from the Kuwaiti oil fires were very low and often could not be distinguished from background concentrations. About 25-30% of the fires produced white smoke plumes that were found to be highly enriched in sodium and calcium chlorides. 18 refs., 1 fig., 4 tabs.

Cofer, W.R. III; Cahoon, D.R. [Langley Research Center, Hampton, VA (United States); Stevens, R.K.; Pinto, J.P. [Environmental Protection Agency, Research Triangle Park, NC (United States); Winstead, E.L.; Sebacher, D.I. [Hughes STX Corp., Hampton, VA (United States); Abdulraheem, M.Y. [Kuwait Environmental Protection Dept., Kuwait City (Kuwait); Al-Sahafi, M. [Ministry of Defense and Aviation, Eastern Province (Saudi Arabia); Mazurek, M.A. [Brookhaven National Lab., Upton, NY (United States); Rasmussen, R.A. [Oregon Graduate Institute of Science and Technology, Beaverton, OR (United States)] [and others

1992-09-20T23:59:59.000Z

438

Material Analysis for a Fire Assessment.  

SciTech Connect (OSTI)

This report consolidates technical information on several materials and material classes for a fire assessment. The materials include three polymeric materials, wood, and hydraulic oil. The polymers are polystyrene, polyurethane, and melamine- formaldehyde foams. Samples of two of the specific materials were tested for their behavior in a fire - like environment. Test data and the methods used to test the materials are presented. Much of the remaining data are taken from a literature survey. This report serves as a reference source of properties necessary to predict the behavior of these materials in a fire.

Brown, Alexander; Nemer, Martin

2014-08-01T23:59:59.000Z

439

The Research about Fire Prevention of Vehicle Refuelling Stations  

Science Journals Connector (OSTI)

Abstract Fuel oil and gas offered by vehicle refuelling stations have combustion and explosion characteristics, serious casualties and economic losses often caused by fire. The research about oil and gas fire risk, refuelling process and facilities, proposing appropriate fire prevention measures possess great significance for reducing refuelling stations fire losses, and ensuring the safety of the station and surrounding environment.

Hong-yu Zhang

2014-01-01T23:59:59.000Z

440

Fire Hazards Analysis for the Inactive Equipment Storage Sprung Structure  

SciTech Connect (OSTI)

The purpose of the analysis is to comprehensively assess the risk from fire within individual fire areas in relation to proposed fire protection so as to ascertain whether the fire protection objective of DOE Order 5480.1A are met. The order acknowledges a graded approach commensurate with the hazards involved.

MYOTT, C.F.

2000-02-03T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


441

Page 1 of 3 Policy: Fire Protection Equipment Policy  

E-Print Network [OSTI]

Page 1 of 3 Policy: Fire Protection Equipment Policy Responsible Party: Director, Safety and Risk The Office of Safety and Risk Management (SRM) has developed, and implemented the Fire Protection Equipment of Fire Protection Equipment throughout MSU to maintain its working order. Fire Protection Equipment

Dyer, Bill

442

(BSET) -FIRE SAFETY ENGINEERING TECHNOLOGY CURRICULUM Effective Fall 2003  

E-Print Network [OSTI]

Disasters State and Local Government Active Fire Protection Fire Safety Engr. Prob. Analysis Sem. & Year.Apps Intro to Fire Protection* (3hrs) Hydraulics and Water Distribution* (3hrs) FSET Specific Life Education* (3hrs) Building Construction* (3hrs) (not offered at UNCC) ETFS 1252 -Fire Protection Law (not

Raja, Anita

443

FAQS Qualification Card - Fire Protection | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Fire Protection Fire Protection FAQS Qualification Card - Fire Protection A key element for the Department's Technical Qualification Programs is a set of common Functional Area Qualification Standards (FAQS) and associated Job Task Analyses (JTA). These standards are developed for various functional areas of responsibility in the Department, including oversight of safety management programs identified as hazard controls in Documented Safety Analyses (DSA). For each functional area, the FAQS identify the minimum technical competencies and supporting knowledge and skills for a typical qualified individual working in the area. FAQC-FireProtection-2007.docx Description Fire Protection Qualification Card - 2007 FAQC-FireProtection-2000.docx Description Fire Protection Qualification Card - 2000

444

Modeling organic matter dynamics in conifer-broadleaf forests in different site types upon fires: A computational experiment  

Science Journals Connector (OSTI)

The effect of forest fires differing in intensity on organic matter dynamics in forest soils has been assessed in different types of forest sites using the EFIMOD system of models. Differences between the patt...

A. S. Komarov; T. S. Kubasova

2007-08-01T23:59:59.000Z

445

Analysis of RHIC beam dump pre-fires  

SciTech Connect (OSTI)

It has been speculated that the beam may cause instability of the RHIC Beam Abort Kickers. In this study, we explore the available data of past beam operations, the device history of key modulator components, and the radiation patterns to examine the correlations. The RHIC beam abort kicker system was designed and built in the 90's. Over last decade, we have made many improvements to bring the RHIC beam abort kicker system to a stable operational state. However, the challenge continues. We present the analysis of the pre-fire, an unrequested discharge of kicker, issues which relates to the RHIC machine safety and operational stability.

Zhang, W.; Ahrens, L.; Fischer, W.; Hahn, H.; Mi, J.; Sandberg, J.; Tan, Y.

2011-03-28T23:59:59.000Z

446

Fire victim helped by area programs  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Fire victim helped by area programs Fire victim helped by area programs Fire victim helped by local nonprofit organizations A perennial helper, didn't realize that she might someday need help herself. April 3, 2012 Beatrice Dubois is grateful for the help she received from Lab-supported Beatrice Dubois is grateful for the help she received from Lab-supported, local nonprofits during her time of need. Contact Kurt Steinhaus Community Programs Office (505) 665-7370 Email Beatrice Dubois, dedicated fundraiser, assisted after home fire Beatrice Dubois has always been a strong advocate for LANL employee giving programs. Every year, she organizes a bake sale in support of the annual employee giving campaign and musters support with her coworkers for the Lab's annual holiday drive. A perennial helper, she didn't realize

447

Forest fire near Los Alamos National Laboratory  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Forest fire near Los Alamos National Laboratory Forest fire near Los Alamos National Laboratory Forest fire near Los Alamos National Laboratory The Las Conchas fire burning in the Jemez Mountains approximately 12 miles southwest of the boundary of LANL has not entered Lab property at this time. June 26, 2011 Los Alamos National Laboratory sits on top of a once-remote mesa in northern New Mexico with the Jemez mountains as a backdrop to research and innovation covering multi-disciplines from bioscience, sustainable energy sources, to plasma physics and new materials. Los Alamos National Laboratory sits on top of a once-remote mesa in northern New Mexico with the Jemez mountains as a backdrop to research and innovation covering multi-disciplines from bioscience, sustainable energy sources, to plasma physics and new materials.

448

Fire Island Wind Project | Open Energy Information  

Open Energy Info (EERE)

Island Wind Project Island Wind Project Jump to: navigation, search Name Fire Island Wind Project Facility Fire Island Wind Project Sector Wind energy Facility Type Commercial Scale Wind Facility Status In Service Owner CIRI Developer Fire Island Wind LLC Energy Purchaser Chugach Location Fire Island AK Coordinates 61.144146°, -150.217652° Loading map... {"minzoom":false,"mappingservice":"googlemaps3","type":"ROADMAP","zoom":14,"types":["ROADMAP","SATELLITE","HYBRID","TERRAIN"],"geoservice":"google","maxzoom":false,"width":"600px","height":"350px","centre":false,"title":"","label":"","icon":"","visitedicon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"wmsoverlay":"","layers":[],"controls":["pan","zoom","type","scale","streetview"],"zoomstyle":"DEFAULT","typestyle":"DEFAULT","autoinfowindows":false,"kml":[],"gkml":[],"fusiontables":[],"resizable":false,"tilt":0,"kmlrezoom":false,"poi":true,"imageoverlays":[],"markercluster":false,"searchmarkers":"","locations":[{"text":"","title":"","link":null,"lat":61.144146,"lon":-150.217652,"alt":0,"address":"","icon":"","group":"","inlineLabel":"","visitedicon":""}]}

449

Fire Protection for Laboratories Using Chemicals  

Broader source: Energy.gov (indexed) [DOE]

Protection Engineer Fire Protection Engineering Pacific Northwest National Laboratory Phone 509-371-7902; Cell 509-308-7658 Fax 509-371-7890 andrew.minister@pnnl.gov Questions?...

450

Fire Protection Training | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

Project. The goal of this contract was to provide needed information and a method to train fire departments and other emergency responders who may be called upon to respond to...

451

Fire Protection Program Guidelines | Department of Energy  

Broader source: Energy.gov (indexed) [DOE]

14, 1995 Guidelines for Developing Medical Standards for Fire Fighters December 1994 Primer on Spontaneous Heating and Pyrophoricity (DOE-HDBK-1081-94) Oct 1994 Guidance for the...

452

Annual Fire Protection Summary Information Reporting Guide  

Broader source: Energy.gov [DOE]

The Department of Energy (DOE) Annual Fire Protection Program Summary continues the series started in 1972. The report annually summarizes monetary loss information sent to Headquarters by reporting elements.

453

Physically-based realistic fire rendering  

Science Journals Connector (OSTI)

Accurately rendering fires is a challenging problem due to the various subtle ways in which the electromagnetic waves interact with this complex participating medium. We present a new method for physically-based rendering of flames from detailed simulations ...

Vincent Pegoraro; Steven G. Parker

2006-09-01T23:59:59.000Z

454

POST-FIRE REVEGETATION AT HANFORD  

SciTech Connect (OSTI)

Range fires on the Hanford Site can have a long lasting effect on native plant communities. Wind erosion following removal of protective vegetation from fragile soils compound the damaging effect of fires. Dust storms caused by erosion create health and safety hazards to personnel, and damage facilities and equipment. The Integrated Biological Control Program (IBC) revegetates burned areas to control erosion and consequent dust. Use of native, perennial vegetation in revegetation moves the resulting plant community away from fire-prone annual weeds, and toward the native shrub-steppe that is much less likely to burn in the future. Over the past 10 years, IBC has revegetated major fire areas with good success. IBC staff is monitoring the success of these efforts, and using lessons learned to improve future efforts.

ROOS RC; JOHNSON AR; CAUDILL JG; RODRIGUEZ JM; WILDE JW

2010-01-05T23:59:59.000Z

455

Fire spread in concealed foamed plastic insulation  

Science Journals Connector (OSTI)

A test program, jointly sponsored by the Society of the Plastics Industry of Canada and the National Research Council, examined the contribution of plastic foams to fire spread in buildings. The conditions und...

Dr. W. Taylor

1983-08-01T23:59:59.000Z

456

California State Fire Marshal Information Bulletin  

Alternative Fuels and Advanced Vehicles Data Center [Office of Energy Efficiency and Renewable Energy (EERE)]

California State Fire Marshal California State Fire Marshal Information Bulletin April 27, 2009 INFORMATION REGARDING PLACEMENT OF E85 FUEL DISPENSING EQUIPMENT ON STATE OWNED OR STATE LEASED FACILITIES In an effort to assist interested parties with criteria addressing E85 dispensing equipment, the Office of the State Fire Marshal (OSFM) is providing this informational bulletin. E85 is the acronym for an alcohol-blended gasoline fuel that contains between 15 to 85 percent ethanol (alcohol). Presently, there are over 10,000 gas service stations in California selling petroleum fuels (gasoline and diesel); and the number of stations dispensing E85 fuel continues to increase. The California Fire Code (CFC) and Title 19 of the California Code of Regulations (CCR) require all fuel-dispensers to be listed and labeled by an approved testing

457

Final Manuscript submitted to the Fire Safety Journal Chen et. al., Fire detection using smoke and gas sensors  

E-Print Network [OSTI]

Santa Fe, NM 87505, USA 2 Department of Fire Protection Engineering University of Maryland, College Park Protection Engineering University of Maryland, College Park, MD 20742-3031, USA Abstract Fire detectionFinal Manuscript submitted to the Fire Safety Journal Chen et. al., Fire detection using smoke

458

Georgia Institute of Technology Fire Watch Procedures  

E-Print Network [OSTI]

-385-1000) Area II (404-385-2000) Area III (404-385-3000) Area IV (404-385-4000) Area V (404-385-5000) II. Fire Marshal 404-894-2990 2. Georgia Tech Police Department 404-894-2500 3. Facilities-Area 1 (404 the fire watch is in effect. 2. Patrol the entire area affected by the service outage every 30 minutes

459

Wild Fire Computer Model Helps Firefighters  

ScienceCinema (OSTI)

A high-tech computer model called HIGRAD/FIRETEC, the cornerstone of a collaborative effort between U.S. Forest Service Rocky Mountain Research Station and Los Alamos National Laboratory, provides insights that are essential for front-line fire fighters. The science team is looking into levels of bark beetle-induced conditions that lead to drastic changes in fire behavior and how variable or erratic the behavior is likely to be.

Canfield, Jesse

2014-06-02T23:59:59.000Z

460

Estimating Fire Risks at Industrial Nuclear Facilities  

SciTech Connect (OSTI)

The Savannah River Site (SRS) has a wide variety of nuclear production facilities that include chemical processing facilities, machine shops, production reactors, and laboratories. Current safety documentation must be maintained for the nuclear facilities at SRS. Fire Risk Analyses (FRAs) are used to support the safety documentation basis. These FRAs present the frequency that specified radiological and chemical consequences will be exceeded. The consequence values are based on mechanistic models assuming specific fire protection features fail to function as designed.

Coutts, D.A.

1999-07-12T23:59:59.000Z

Note: This page contains sample records for the topic "fire alarm system" from the National Library of EnergyBeta (NLEBeta).
While these samples are representative of the content of NLEBeta,
they are not comprehensive nor are they the most current set.
We encourage you to perform a real-time search of NLEBeta
to obtain the most current and comprehensive results.


461

Reducing NOx in Fired Heaters and Boilers  

E-Print Network [OSTI]

-6, 2000 Reducing NOx in Fired Heaters Air Pollution Control and Boilers Keeping the environment clean Presented by Ashutosh Garg Furnace Improvements Low cost solutions for fired heaters Trace compounds ? Nitric oxides ? Carbon monoxide ? Sulfur... it is essential to estimate accurately baseline NOx emissions. ? This will establish each units current compliance status. ? Emissions ? Current excess air level ? Carbon monoxide ? Combustibles ? NOx corrected to 3% 02 314 ESL-IE-00-04-46 Proceedings...

Garg, A.

462

if it is a gas leak, do not activate building alarms, use mobile phones, hand held radios, electronic equipment or light flammable material!  

E-Print Network [OSTI]

gas leak gas leak if it is a gas leak, do not activate building alarms, use mobile phones, hand held radios, electronic equipment or light flammable material! 1. If you discover a Gas Leak, shout and check that the nearest gas isolator switch is off. 4. Evacuate the building immediately, avoiding

Hickman, Mark

463

Aerosol nucleation in coal-fired power-plant plumes  

Science Journals Connector (OSTI)

New-particle nucleation within coal-fired power-plant plumes can have large effects on particle number concentrations particularly near source regions with implications for human health and climate. In order to resolve the formation and growth of particles in these plumes we have integrated TwO-Moment Aerosol Sectional (TOMAS) microphysics in the System for Atmospheric Modelling (SAM) a large-eddy simulation/cloud-resolving model (LES/CRM). We have evaluated this model against aircraft observations for three case studies and the model reproduces well the major features of each case. Using this model we have shown that meteorology and background aerosol concentrations can have strong effects on new-particle formation and growth in coal-fired power-plant plumes even if emissions are held constant. We subsequently used the model to evaluate the effects of SO 2 and NOx pollution controls on newparticle formation in coal-fired power-plant plumes. We found that strong reductions in NOx emissions without concurrent reductions in SO 2 emissions may increase new-particle formation due to increases in OH formation within the plume. We predicted the change in new-particle formation due to changes in emissions between 1997 and 2010 for 330 coal-fired power plants in the US and we found a median decrease of 19% in new-particle formation. However the magnitude and sign of the aerosol changes depend greatly on the relative reductions in NOx and SO 2 emissions in each plant. More extensive plume measurements for a range of emissions of SO 2 and NOx and in varying background aerosol conditions are needed however to better quantify these effects.

2013-01-01T23:59:59.000Z

464

FY 2013 EL Program Description EL Program: Fire Risk Reduction in Buildings  

E-Print Network [OSTI]

product. Structure fires and fire protection account for $170 B. To reduce the U.S. fire burden, the Fire of installed fire protection through performance-based design ($63 B) and a reduction in residential fire of structures and their contents by enabling innovative, cost-effective fire protection technologies by 2016

Bentz, Dale P.

465

EA-1472: Commercial Demonstration fo the Low Nox Burner/Separated Over-Fire  

Broader source: Energy.gov (indexed) [DOE]

472: Commercial Demonstration fo the Low Nox Burner/Separated 472: Commercial Demonstration fo the Low Nox Burner/Separated Over-Fire Air (LNB/SOFA) Integration System Emission Reduction Technology, Holcolm Station, Sunflower Electric Power Corporation Finnety County, Kansas EA-1472: Commercial Demonstration fo the Low Nox Burner/Separated Over-Fire Air (LNB/SOFA) Integration System Emission Reduction Technology, Holcolm Station, Sunflower Electric Power Corporation Finnety County, Kansas SUMMARY The DOE has prepared an Environmental Assessment (EA), to analyze the potential impacts of the commercial application of the Low-NOx Burner/Separated Over-Fire Air (LNB/SOFA) integration system to achieve nitrogen oxide (NOx) emissions reduction at Sunflower's Holcomb Unit No. 1 (Holcomb Station), located near Garden City, in Finney County, Kansas.

466

NIST Technical Note 1629 Fire Fighting Tactics Under Wind Driven Fire Conditions  

E-Print Network [OSTI]

(FEMA) Assistance to Firefighters Research and Development Grant Program and the United States Fire Administrator United States Fire Administration Glenn A. Gaines, Acting Assistant Administrator U.S. Department to differences in staffing, equipment, building stock, typical weather conditions, etc. There is uniformity

Bentz, Dale P.

467

Fuel Treatment, Prescribed Fire, and Fire Restoration: Are the Benefits Worth It?  

E-Print Network [OSTI]

Fuel Treatment, Prescribed Fire, and Fire Restoration: Are the Benefits Worth It? Chairs: Susan Husari and Melanie Miller #12;Applying Simulation and Optimization to Plan Fuel Treatments at Landscape Scales1 J. Greg Jones,2 Jimmie D. Chew,2 Hans R. Zuuring3 Abstract Fuel treatment activities are analyzed

Standiford, Richard B.

468

FIRE ECOLOGY Perhaps the image most often associated with wildland fire is  

E-Print Network [OSTI]

. While it is true that fire has a great potential for the destruction of homes, wildlife, and even human that influence intensity are available fuel, moisture and temperature, fuel composition, wind, and topography. Wind increases oxygen supply, convects heat and can produce "spot fires" from fragments that blow down-wind

Johnson, Matthew

469

Thanks to Our Neighbors in Fighting Fire on INL  

Broader source: All U.S. Department of Energy (DOE) Office Webpages (Extended Search)

Thanks to Our Neighbors in Fighting Fire on INL Thanks to Our Neighbors in Fighting Fire on INL Idaho Bureau of Homeland Security view of the Twin Buttes Wildland fire aftermath atop the East Twin Butte. As the Department of Energy's manager at the Idaho National Laboratory, I want to commend the outstanding efforts of More than 50 firefighters and equipment battled the fire that was contained at 9:10 p.m. Mountain Standard Time July 19, 2007 An aerial scan of the area indicated the fire burned more than 9,000 acres. INL employees, and firefighting and law enforcement staff from our regional neighbors for the outstanding team-work they exhibited in controlling the Twin Buttes Fire on the INL from July 18-20. The INL Firefighters and support workers joined together with the Blackfoot Fire Department, Idaho Falls Fire Department, Shelley Fire

470

Surveillance Guide - FPS 12.2 Fire Protection and Prevention  

Broader source: Energy.gov (indexed) [DOE]

FIRE PROTECTION AND PREVENTION FIRE PROTECTION AND PREVENTION 1.0 Objective The objective of this surveillance is to ensure that the contractor is implementing an effective program to minimize the potential for fires that could threaten the health and safety of the public or DOE's workers, or produce significant losses. In addition, the surveillance examines the effectiveness of steps taken to mitigate any fires that might occur. Finally, the surveillance provides an opportunity to evaluate compliance with requirements and standards for fire prevention and mitigation established by DOE. 2.0 References DOE 5480.7A, Fire Protection (or DOE O 420.1, Facility Safety) RLID 5480.7, Fire Protection (or RLID 420.1, Fire Protection) 29 CFR 1910 29 CFR 1926 DOE-HDBK-1062-96, "DOE Fire Protection Handbook (See this as well as other

471

Fire hazard analysis of the radioactive mixed waste trenchs  

SciTech Connect (OSTI)

This Fire Hazards Analysis (FHA) is intended to assess comprehensively the risk from fire associated with the disposal of low level radioactive mixed waste in trenches within the lined landfills, provided by Project W-025, designated Trench 31 and 34 of the Burial Ground 218-W-5. Elements within the FHA make recommendations for minimizing risk to workers, the public, and the environment from fire during the course of the operation`s activity. Transient flammables and combustibles present that support the operation`s activity are considered and included in the analysis. The graded FHA contains the following elements: description of construction, protection of essential safety class equipment, fire protection features, description of fire hazards, life safety considerations, critical process equipment, high value property, damage potential--maximum credible fire loss (MCFL) and maximum possible fire loss (MPFL), fire department/brigade response, recovery potential, potential for a toxic, biological and/or radiation incident due to a fire, emergency planning, security considerations related to fire protection, natural hazards (earthquake, flood, wind) impact on fire safety, and exposure fire potential, including the potential for fire spread between fire areas. Recommendations for limiting risk are made in the text of this report and printed in bold type. All recommendations are repeated in a list in Section 18.0.

McDonald, K.M. [Westinghouse Hanford Co., Richland, WA (United States)

1995-04-27T23:59:59.000Z

472

Figure 7.1. Control of an alarm system. Figure 7.2. A simple memory element.  

E-Print Network [OSTI]

-digit BCD counter. Enable Q0 Q1 Q2 D0 D1 D2 Load Clock 1 0 0 0 Clock Q30 D3 Enable Q0 Q1 Q2 D0 D1 D2 Load Clock 0 0 0 Q30 D3 BCD0 BCD1 Clear Figure 7.30. Johnson counter. D Q Q Clock D Q Q D Q Q Q0 Q1 Qn 1 by CAD tools. Data Clock Latch #12;Figure 7.34. Timing simulation of storage elements. Figure 7.35. Code

Kalla, Priyank

473

Mitsubishi FGD plants for lignite fired boilers  

SciTech Connect (OSTI)

In order to respond to the increasing electric energy demand for sustaining economic growth, construction of coal-fired thermal power plants worldwide is indispensable. As a countermeasure for environmental pollution which otherwise may reach a serious proportion from the operation of these plants, construction of flue gas desulfurization (FGD) plants is being promoted. Among these power stations where lignite fuel is burnt, the FGD plants concerned have to be designed to cope with high gas volume and SO{sub x} concentration as well as violent fluctuations in their values caused by such features of lignite as high sulfur content, low calorific volume, and unstable properties. Mitsubishi Heavy Industries (MHI) has received construction awards for a total of seven (7) FGD plants for lignite-fired boilers in succession starting from that for CEZ as, Czech Republic followed by those for EGAT, Thailand in 1993. All these plants are presently operating satisfactorily since successful completion of their performance tests in 1996. Further, a construction award of three (3) more FGD plants for lignite-fired boilers was received from ENDESA (Spain) in 1995 which are now being outfitted and scheduled to start commercial operation in 1998. In this paper, the authors discuss the outline design of FGD plants for lignite-fired boilers based on experience of FGD plants constructed since 1970 for heavy oil--as well as black coal-fired boilers, together with items confirmed from the operation and design guideline hereafter.

Kotake, Shinichiro; Okazoe, Kiyoshi; Iwashita, Koichiro; Yajima, Satoru

1998-07-01T23:59:59.000Z

474

The Advanced Candu reactor annunciation system - Compliance with IEC standard and US NRC guidelines  

SciTech Connect (OSTI)

Annunciation is a key plant information system that alerts Operations staff to important changes in plant processes and systems. Operational experience at nuclear stations worldwide has shown that many annunciation implementations do not provide the support needed by Operations staff in all plant situations. To address utility needs for annunciation improvement in Candu plants, AECL in partnership with Canadian Candu utilities, undertook an annunciation improvement program in the early nineties. The outcome of the research and engineering development program was the development and simulator validation of alarm processing, display, and information presentation techniques that provide practical and effective solutions to key operational deficiencies with earlier annunciation implementations. The improved annunciation capabilities consist of a series of detection, information processing and presentation functions called the Candu Annunciation Message List System (CAMLS). The CAMLS concepts embody alarm processing, presentation and interaction techniques, and strategies and methods for annunciation system configuration to ensure improved annunciation support for all plant situations, especially in upset situations where the alarm generation rate is high. The Advanced Candu Reactor (ACR) project will employ the CAMLS annunciation concepts as the basis for primary annunciation implementations. The primary annunciation systems will be implemented from CAMLS applications hosted on AECL Advanced Control Centre Information System (ACCIS) computing technology. The ACR project has also chosen to implement main control room annunciation aspects in conformance with the following international standard and regulatory review guide for control room annunciation practice: International Electrotechnical Commission (IEC) 62241 - Main Control Room, Alarm Function and Presentation (International standard) US NRC NUREG-0700 - Human-System Interface Design Review Guidelines, Section 4 - Alarm System (Regulatory review guide) In order for the ACR annunciation system to comply with IEC-62241 and NUREG-0700, the CAMLS concepts must satisfy their respective requirements and guidelines. This paper