skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: EMCS and time-series energy data analysis in a large government office building

Conference ·
OSTI ID:787118

Energy Management Control System (EMCS) data are an underutilized source of information on the performance of commercial buildings. Newer EMCS's have the ability and storage capacity to trend large amounts of data and perform preliminary analyses; however, these features often receive little or no use, as operators are generally not trained in data management, visualization, and analysis. Whole-building hourly electric-utility data are another readily available and underutilized source of information. This paper outlines the use of EMCS and utility data to evaluate the performance of the Ronald V. Dellums Federal Building in Oakland, California, a large office building operated by the Federal General Services Administration (GSA). The project began as an exploratory effort at Lawrence Berkeley National Laboratory (LBNL) to examine the procedures operators were using to obtain information and operate their buildings. Trending capabilities were available, but in limited use by the operators. LBNL worked with the building operators to use EMCS to trend one-minute data for over one-hundred points. Hourly electricity-use data were also used to understand usage patterns and peak demand. The paper describes LBNL's key findings in the following areas: Characterization of cooling plant operations; Characterization of economizer performance; Analysis of annual energy use and peak demand operations; Techniques, strengths, and shortcomings of EMCS data analysis; Future plans at the building for web-based remote monitoring and diagnostics. These findings have helped GSA develop strategies for peak demand reduction in this and other GSA buildings. Such activities are of great interest in California and elsewhere, where electricity reliability and demand are currently problematic. Overall, though the building's energy use is fairly low, significant energy savings are available by improving the existing EMCS control strategies.

Research Organization:
Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States)
Sponsoring Organization:
USDOE Assistant Secretary for Energy Efficiency and Renewable Energy. Office of Building Technology, State and Community Programs. Office of Building Research and Standards (US)
DOE Contract Number:
AC03-76SF00098
OSTI ID:
787118
Report Number(s):
LBNL-47699; CD-433; R&D Project: 43EH01; TRN: AH200134%%179
Resource Relation:
Conference: 9th National Conference on Building Commissioning, Cherry Hill, NJ (US), 05/09/2001--05/11/2001; Other Information: PBD: 1 Apr 2001
Country of Publication:
United States
Language:
English