skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Aging, condition monitoring, and loss-of-coolant accident (LOCA) tests of class 1E electrical cables

Technical Report ·
OSTI ID:7004842
 [1]
  1. Sandia National Labs., Albuquerque, NM (United States)

This report describes the results of aging, condition monitoring, and accident testing of ethylene propylene rubber (EPR) cables. Three sets of cables were aged for up to 9 months under simultaneous thermal ([approx equal]100[degrees]C) and radiation ([approx equal]0.10 kGy/hr) conditions. A sequential accident consisting of high dose rate irradiation ([approx equal]6 kGy/hr) and high temperature steam followed the aging. Also exposed to the accident conditions was a fourth set of cables, which were unaged. The test results indicate that most properly installed EPR cables should be able to survive an accident after 60 years for total aging doses of at least 150--200 kGy and for moderate ambient temperatures on the order of 45--55[degrees]C (potentially higher or lower, depending on material specific activation energies and total radiation doses). Mechanical measurements (primarily elongation, modulus, and density) were more effective than electrical measurements for monitoring age-related degradation.

Research Organization:
Nuclear Regulatory Commission, Washington, DC (United States). Div. of Engineering; Sandia National Labs., Albuquerque, NM (United States)
Sponsoring Organization:
USNRC; Nuclear Regulatory Commission, Washington, DC (United States)
DOE Contract Number:
AC04-76DP00789
OSTI ID:
7004842
Report Number(s):
NUREG/CR-5772-Vol.2; SAND-91-1766/2; ON: TI93004663
Country of Publication:
United States
Language:
English