Advanced wet-dry cooling tower concept cross-flow tests
The design, operation, instrumentation, and performance testing of a crossflow evaporative cooling tower are discussed, and computer predictions for performance are compared with test data. Experimental results for 14 runs agreed with heat and mass transfer coefficient calculations within 5% for 11 runs and within 8% for the remaining 3 runs. It was concluded that the computer model is valid for use in future design studies, that the wet-dry packing is effective in reducing cooling water consumption, and that the crossflow air-water arrangement shows much promise for future development. (LCL)
- Research Organization:
- Massachusetts Inst. of Technology (MIT), Cambridge, MA (United States)
- DOE Contract Number:
- EY-76-S-02-2500
- OSTI ID:
- 6771228
- Report Number(s):
- COO-2500-2(Vol.2); MIT-EL-77-002(Vol.2)
- Country of Publication:
- United States
- Language:
- English
Similar Records
Advanced wet--dry cooling tower concept performance prediction
Advanced dry cooling tower concept
Advanced dry cooling tower concept
Technical Report
·
Sat Jan 01 00:00:00 EST 1977
·
OSTI ID:6771228
+2 more
Advanced dry cooling tower concept
Technical Report
·
Tue Sep 30 00:00:00 EDT 1975
·
OSTI ID:6771228
+1 more
Advanced dry cooling tower concept
Technical Report
·
Tue Sep 30 00:00:00 EDT 1975
·
OSTI ID:6771228
+1 more