Title: Advanced wet-dry cooling tower concept cross-flow tests

Technical Report ·
DOI:https://doi.org/10.2172/6771228· OSTI ID:6771228

The design, operation, instrumentation, and performance testing of a crossflow evaporative cooling tower are discussed, and computer predictions for performance are compared with test data. Experimental results for 14 runs agreed with heat and mass transfer coefficient calculations within 5% for 11 runs and within 8% for the remaining 3 runs. It was concluded that the computer model is valid for use in future design studies, that the wet-dry packing is effective in reducing cooling water consumption, and that the crossflow air-water arrangement shows much promise for future development. (LCL)

Research Organization:
Massachusetts Inst. of Technology (MIT), Cambridge, MA (United States)
DOE Contract Number:
EY-76-S-02-2500
OSTI ID:
6771228
Report Number(s):
COO-2500-2(Vol.2); MIT-EL-77-002(Vol.2)
Country of Publication:
United States
Language:
English