skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Cooling tower waste reduction

Conference ·
OSTI ID:651792

At Lawrence Livermore National Laboratory (LLNL), the two main cooling tower systems (central and northwest) were upgraded during the summer of 1997 to reduce the generation of hazardous waste. In 1996, these two tower systems generated approximately 135,400 lbs (61,400 kg) of hazardous sludge, which is more than 90 percent of the hazardous waste for the site annually. At both, wet decks (cascade reservoirs) were covered to block sunlight. Covering the cascade reservoirs reduced the amount of chemical conditioners (e.g. algaecide and biocide), required and in turn the amount of waste generated was reduced. Additionally, at the northwest cooling tower system, a sand filtration system was installed to allow cyclical filtering and backflushing, and new pumps, piping, and spray nozzles were installed to increase agitation. the appurtenance upgrade increased the efficiency of the cooling towers. The sand filtration system at the northwest cooling tower system enables operators to continuously maintain the cooling tower water quality without taking the towers out of service. Operational costs (including waste handling and disposal) and maintenance activities are compared for the cooling towers before and after upgrades. Additionally, the effectiveness of the sand filter system in conjunction with the wet deck covers (northwest cooling tower system), versus the cascade reservoir covers alone (south cooling tower south) is discussed. the overall expected return on investment is calculated to be in excess of 250 percent. this upgrade has been incorporated into the 1998 DOE complex-wide water conservation project being led by Sandia National Laboratory/Albuquerque.

Research Organization:
Lawrence Livermore National Lab. (LLNL), Livermore, CA (United States)
Sponsoring Organization:
USDOE, Washington, DC (United States)
DOE Contract Number:
W-7405-ENG-48
OSTI ID:
651792
Report Number(s):
UCRL-JC-130889; CONF-980654-; ON: DE98057713; BR: YN0100000
Resource Relation:
Conference: 14. DOE pollution prevention conference, Seattle, WA (United States), 2-4 Jun 1998; Other Information: PBD: 1 May 1998
Country of Publication:
United States
Language:
English

Similar Records

Sand filter system keeps cooling water clean; eliminates tower downtime
Journal Article · Tue Jan 01 00:00:00 EST 1985 · Chem. Process. (Chicago); (United States) · OSTI ID:651792

Cooling water filter saves over $60,000/yr
Journal Article · Sun Aug 01 00:00:00 EDT 1982 · Chem. Process. (Chicago); (United States) · OSTI ID:651792

Continuous Monitoring and Partial Water Softening for Cooling Tower Water Treatment