Evaluation test on a hospital refuse incinerator at Saint Agnes Medical Center, Fresno, California. Air pollution test report
An evaluation test program was conducted to evaluate the emissions from a hospital-refuse incinerator. The test was conducted as a part of the Air Resources Board's program to assess emissions from stationary sources. The incinerator was operated at an average burn rate of 780 pounds of hospital refuse per hour during the entire test period. Daily average oxygen and carbon dioxide concentrations ranged from 13.3% and 5.8%, respectively to 16.3% and 3.8%. The carbon monoxide concentrations were less than 50 parts per million by volume, (PPMV), during the entire test period. Analysis for selected trace metals was conducted and emission rates determined. Mass emission rates for chlorinated and aromatic compounds were determined. Sampling for PCDDs and PCDFs was conducted to assess if hospital incinerators had the potential to emit such compounds. Based on data obtained, mass emission rates were determined for the tetra-chlorinated through hepta-chlorinated homologues of the PCDDs and PCDFs. The dioxin emissions ranged from 4.3 nonograms per second (ng/sec) for tetrachloro dioxin (TCDD) to 270 (ng/sec) for the octachloro dioxin (OCDD). Furan emission rates ranged from 64.9 (ng/sec) for the tetrachloro furan to 319 (ng/sec) for the heptachloro furan. Polychlorinated biphenyls were not detected in the outlet gas stream samples.
- Research Organization:
- California State Air Resources Board, Sacramento (USA). Stationary Source Div.
- OSTI ID:
- 6283556
- Report Number(s):
- PB-87-204400/XAB; ARB/SS-87-01
- Country of Publication:
- United States
- Language:
- English
Similar Records
C15-C18 isomers synthesized from ( TC)-2,3,7,8-tetrachlorodibenzofuran via surface chlorination
Evaluation retest on a hospital-refuse incinerator at Sutter General Hospital, Sacramento, California
Related Subjects
AIR POLLUTION
MEASURING METHODS
HOSPITALS
INCINERATORS
ORGANIC COMPOUNDS
VOLATILE MATTER
COMBUSTION PRODUCTS
DIOXIN
EVALUATION
FURANS
BUILDINGS
HETEROCYCLIC COMPOUNDS
MATTER
MEDICAL ESTABLISHMENTS
ORGANIC OXYGEN COMPOUNDS
POLLUTION
500200* - Environment
Atmospheric- Chemicals Monitoring & Transport- (-1989)