Title: A method for encapsulating high voltage power transformers

Conference ·
OSTI ID:6176956

Voltage breakdowns become a major concern in reducing the size of high-voltage power converter transformers. Even the smallest of voids can provide a path for corona discharge which can cause a dielectric breakdown leading to a transformer failure. A method of encapsulating small high voltage transformers has been developed. The method virtually eliminates voids in the impregnation material, provides an exceptional dielectric between windings and provides a mechanically rugged package. The encapsulation material is a CTBN modified mica filled epoxy. The method requires heat/vacuum to impregnate the coil and heat/pressure to cure the encapsulant. The transformer package utilizes a Diallyl Phthalate (DAP) contact assembly in which a coated core/coil assembly is mounted and soldered. This assembly is then loaded into an RTV mold and the encapsulation process begins.

Research Organization:
Sandia National Labs., Albuquerque, NM (USA)
Sponsoring Organization:
DOE/DP
DOE Contract Number:
AC04-76DP00789
OSTI ID:
6176956
Report Number(s):
SAND-90-2435C; CONF-9103102-2; ON: DE91006644
Resource Relation:
Conference: 11. capacitor and resistor technology symposium (CARTS), Las Vegas, NV (USA), 4-7 Mar 1991