Title: Rupture of Model 48Y UF/sub 6/ cylinder and release of uranium hexafluoride, Sequoyah Fuels Facility, Gore, Oklahoma, January 4, 1986. Volume 1

Technical Report ·
OSTI ID:6129426

At 11:30 a.m. on January 4, 1986, a Model 48Y UF/sub 6/ cylinder filled with uranium hexafluoride (UF/sub 6/) ruptured while it was being heated in a steam chest at the Sequoyah Fuels Conversion Facility near Gore, Oklahoma. One worker died because he inhaled hydrogen fluoride fumes, a reaction product of UF/sub 6/ and airborne moisture. Several other workers were injured by the fumes, but none seriously. Much of the facility complex and some offsite areas to the south were contaminated with hydrogen fluoride and a second reaction product, uranyl fluoride. The interval of release was approximately 40 minutes. The cylinder, which had been overfilled, ruptured while it was being heated because of the expansion of UF/sub 6/ as it changed from the solid to the liquid phase. The maximum safe capacity for the cylinder is 27,560 pounds of product. Evidence indicates that it was filled with an amount exceeding this limit. 18 figs.

Research Organization:
Nuclear Regulatory Commission, Washington, DC (USA). Augmented Investigation Team
OSTI ID:
6129426
Report Number(s):
NUREG-1179-Vol.1; ON: TI86901089
Country of Publication:
United States
Language:
English