skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Behavior of zinc oxide surge arresters under pollution

Journal Article · · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA)
DOI:https://doi.org/10.1109/61.131128· OSTI ID:5867263
; ;  [1];  [2]
  1. Univ. of Stuttgart (DE)
  2. Technical Univ. of Wroclaw (PL)

This paper presents results of pollution tests with AC voltages which were carried out with a multi-unit zinc oxide arrester. The interaction between the polluted porcelain housing and the inner varistor column due to capacitive coupling has been found to be responsible for the temperature rise of varistor elements. The different voltage distribution between inside and outside of the arrester also causes a high radial electric field which can lead to internal discharges if the radial insulation system is not properly designed. These internal discharges may damage varistor elements which are not adequately coated and may cause a total destruction of the arrester.

OSTI ID:
5867263
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA), Vol. 6:2; ISSN 0885-8977
Country of Publication:
United States
Language:
English