Solar project description for Ingham County Medical Care Facility
Domestic hot water preheating is provided by a solar energy system utilizing 9425 square feet of liquid flat plate collectors. The collectors are double-glazed with tempered glass, have copper absorber plates and a non-selective black coating. A 50% propylene glycol/water solution protects the collectors from freezing down to -20/sup 0/F. A steam-fired heat exchanger and circulation pump with an emergency generator provide heat to protect the collectors below -20/sup 0/F. A 5000 gallon, currently uninsulated, steel storage tank, is located in the existing mechanical room. The preheated water in the tank is provided directly to a steam-fired hot water heater for use in the laundry facility. A heat exchanger provides preheated water to a steam-fired domestic hot water heater. A gas/oil fired boiler provides steam to the hot water heaters. (MHR)
- Research Organization:
- Mueller Associates, Inc., Baltimore, MD (USA); Ehrenkrantz Group, New York (USA); PRC Energy Analysis Co., McLean, VA (USA)
- DOE Contract Number:
- EX-76-C-01-2382; EG-77-C-01-2522
- OSTI ID:
- 5567918
- Report Number(s):
- SOLAR/2056-79/50
- Country of Publication:
- United States
- Language:
- English
Similar Records
Solar project description for Blakedale Professional Center, Greenwood, South Carolina
Solar project cost report for the Loudoun County Vocational-Technical Education Center, Leesburg, Virginia
Related Subjects
HOSPITALS
LAUNDRIES
SOLAR WATER HEATING
SOLAR WATER HEATERS
DESIGN
SPECIFICATIONS
ANTIFREEZE
GLYCOLS
HEAT EXCHANGERS
MEDICAL CENTERS
PUMPS
RETROFITTING
TANKS
ALCOHOLS
APPLIANCES
BUILDINGS
CONTAINERS
EQUIPMENT
GAS APPLIANCES
HEATERS
HEATING
HYDROXY COMPOUNDS
ORGANIC COMPOUNDS
SOLAR EQUIPMENT
SOLAR HEATING
WATER HEATERS
140907* - Solar Thermal Utilization- Water Heating