Health-hazard evaluation report HETA 91-158-2161, Immaculate Heart of Mary Church, Cincinnati, Ohio
In response to a request from a representative of the Immaculate Heart of Mary Church (SIC-8661), an investigation was made of indoor air quality in the church office. Particular attention was directed toward laser printer and photocopier emissions. Employees had complained of headaches, dizziness, confusion, nausea, eye irritation, and dry nose and throat. Day shift employees performed general office duties, often using a photocopier and a laser printer. Real time ozone (10028156) concentrations ranged from below the limit of detection (LOD) to 0.05 parts per million (ppm) in the breathing zone, all below the NIOSH limit for short term exposure of 0.10ppm. Ozone concentrations as high as 0.56ppm were detected at the laser printer exhaust. Carbon-dioxide (124389) concentrations ranged from 400 to 850ppm. Respirable dust concentrations ranged from below the LOD to 90 micrograms per cubic meter. Carbon-monoxide (630080) levels were not above the LOD of 5ppm. No volatile organic carbons were detected. Temperature and relative humidity levels were within the guidelines. Some of the symptoms were consistent with ozone exposure. The author concludes that efforts should be made to reduce ozone exposures. The author recommends relocating the laser printer, providing additional outside air to the building, and checking for possible overloading or inefficiency in the ozone filter in the printer.
- Research Organization:
- National Inst. for Occupational Safety and Health, Cincinnati, OH (United States)
- OSTI ID:
- 5325545
- Report Number(s):
- PB-92-176858/XAB; HETA-91-158-2161
- Country of Publication:
- United States
- Language:
- English
Similar Records
Health-hazard evaluation report HETA 91-056-2129, Oakland County Department of Social Services, Pontiac, Michigan
Health hazard evaluation determination report No. MHETA-81-108-9006, Consolidation Coal Company, central machine shop 20, Cadiz, Ohio
Related Subjects
63 RADIATION, THERMAL, AND OTHER ENVIRON. POLLUTANT EFFECTS ON LIVING ORGS. AND BIOL. MAT.
CARBON DIOXIDE
TOXICITY
CARBON MONOXIDE
OHIO
PUBLIC BUILDINGS
OZONE
INDOOR AIR POLLUTION
AIR POLLUTION MONITORING
ECOLOGICAL CONCENTRATION
INDUSTRIAL MEDICINE
INHALATION
OCCUPATIONAL EXPOSURE
OFFICE BUILDINGS
PERSONNEL
RECOMMENDATIONS
RISK ASSESSMENT
AIR POLLUTION
BUILDINGS
CARBON COMPOUNDS
CARBON OXIDES
CHALCOGENIDES
DEVELOPED COUNTRIES
INTAKE
MEDICINE
MONITORING
NORTH AMERICA
OXIDES
OXYGEN COMPOUNDS
POLLUTION
USA
540120* - Environment
Atmospheric- Chemicals Monitoring & Transport- (1990-)