The eddy-current technique for nondestructive evaluation of generator retaining rings: Feasibility study: Interim report
An evaluation of the feasibility of using eddy current nondestructive inspection techniques to detect intergranular stress corrosion in generator rotor retaining rings was conducted by the EPRI NDE Center. Experiments were conducted using a bend-bar containing representative stress corrosion damage, a calibration block containing electrical discharge machined (EDM) notches, and four retired retaining rings containing EDM notches and stress corrosion damage. An eddy current transducer transport was designed and fabricated to interface with an existing computer-controlled, two-axis positioner and digital eddy current data acquisition system. Test results of experiments performed with this equipment on the retaining ring test-bed provided experimental validation of the eddy current method's feasibility as a retaining ring inspection method. Details are given of the system and its performance under laboratory and simulated service-inspection conditions. 9 refs., 47 figs.
- Research Organization:
- Jones (J.A.) Applied Research Co., Charlotte, NC (USA)
- OSTI ID:
- 5162619
- Report Number(s):
- EPRI-EL-5814; ON: TI88010353
- Country of Publication:
- United States
- Language:
- English
Similar Records
Eddy-current nondestructive testing of turbine generators. Final report
A feature-based eddy-current imaging system for personal computers: Final report
Related Subjects
42 ENGINEERING
STEAM GENERATORS
INTERGRANULAR CORROSION
NONDESTRUCTIVE TESTING
COMPUTER GRAPHICS
CRACKING
DAMAGE
DATA ACQUISITION SYSTEMS
EDDY CURRENTS
FEASIBILITY STUDIES
PERFORMANCE
QUALITY ASSURANCE
RINGS
ROTORS
STRESS ANALYSIS
THREE-DIMENSIONAL CALCULATIONS
BOILERS
CHEMICAL REACTIONS
CORROSION
CURRENTS
DECOMPOSITION
ELECTRIC CURRENTS
MATERIALS TESTING
PYROLYSIS
TESTING
THERMOCHEMICAL PROCESSES
VAPOR GENERATORS
200104* - Fossil-Fueled Power Plants- Components
420200 - Engineering- Facilities
Equipment
& Techniques