Title: Desiccant Enhanced Evaporative Air Conditioning: Parametric Analysis and Design; Preprint

Conference ·
OSTI ID:1052892

This paper presents a parametric analysis using a numerical model of a new concept in desiccant and evaporative air conditioning. The concept consists of two stages: a liquid desiccant dehumidifier and a dew-point evaporative cooler. Each stage consists of stacked air channel pairs separated by a plastic sheet. In the first stage, a liquid desiccant film removes moisture from the process(supply-side) air through a membrane. An evaporatively-cooled exhaust airstream on the other side of the plastic sheet cools the desiccant. The second-stage indirect evaporative cooler sensibly cools the dried process air. We analyze the tradeoff between device size and energy efficiency. This tradeoff depends strongly on process air channel thicknesses, the ratio of first-stage to second-stagearea, and the second-stage exhaust air flow rate. A sensitivity analysis reiterates the importance of the process air boundary layers and suggests a need for increasing airside heat and mass transfer enhancements.

Research Organization:
National Renewable Energy Lab. (NREL), Golden, CO (United States)
Sponsoring Organization:
USDOE Office of Energy Efficiency and Renewable Energy (EERE), Energy Efficiency Office. Building Technologies Office
DOE Contract Number:
AC36-08GO28308
OSTI ID:
1052892
Report Number(s):
NREL/CP-5500-54087
Resource Relation:
Conference: Presented at the Second International Conference on Building Energy and Environment (COBEE2012), 1-4 August 2012, Boulder, Colorado
Country of Publication:
United States
Language:
English